48
Chapter 9

Chapter 9. Please read chapter 9. Please review, know and understand the terms related to fire protection page 284. Know the Classifications of

Embed Size (px)

Citation preview

Chapter 9

Please read chapter 9Please review know and understand the terms related to fire protection page 284Know the Classifications of Fires 911Know Classification of Hazards 912Know the Use or Occupancy 914Void sections 977 through 979Study the remainder of the chapter See additional reading CSI specifications Article - The Evolution of Modern Automatic Fire Sprinklers

Commercial BuildingsCSI Division

Includes Electrical Piping Equipment Controls

Detection of fire and smoke Suppression

CSI Division Numbers Division 21 Fire Suppression (new)

21 10 00 Water ndash Based Fire- Suppression Systems

21 13 00 Fire-Suppression Sprinkler Systems21 13 13 Wet-Pipe Sprinkler Systems21 13 16 Dry-Pipe Sprinkler Systems21 13 19 Preaction Sprinkler Systems21 13 23 Combined Dry-Pipe and Preaction

Sprinkler Systems21 13 26 Deluge Fire-Suppression Sprinkler

Systems21 13 29 Water Spray Fixed Systems

21 13 36 Antifreeze Sprinkler Systems21 13 39 Foam-Water Systems

Old CSI Fire Protection System (See separate readings ndash Web Site)

Division 10520 Fire Extinguishers amp Cabinets

Old CSI Fire Protection System (See separate required readings ndash Web Site)

Division 15000 Mechanical General ProvisionsDivision 15300 Fire ProtectionDivision 16722 Fire Alarm System

Making sure the various Contract Documents coincide Shop Drawing Specifications Review Coordination

Section 15000 - MECHANICAL GENERAL PROVISIONS

Each specification section within their respective Division shall be coordinated with all other sections in that division for related work

The project documents contemplate the complete installation of the systems described herein or shown on the drawings so that at the conclusion of the construction the systems will be turned over to the Owner complete and ready for safe efficient operation

The Contractor shall be obliged to furnish and install all such items normally included on systems of this type which while not mentioned directly herein are obviously essential to the installationand operation of the systems and which are normally furnished on installations of this type

General Refer to the Division 1 sections for general coordination requirements applicable to the entire work The Contractor shall recognize that the Contract Documents are diagrammatic in showing certain physical relationships that must be established within the mechanical and electrical work and in its interface with other work including utilities and that such establishment is the exclusive responsibility of the Contractor This Contractor shall be responsible for work fitting in place without conflict with other trades where proper planning could avoid interference This Contractor shall examine the locations and verify all measurements distances elevations and existing conditions before starting work Because the drawings are diagrammatic and on a small scale all rises drops offsets etc have not been shown The Contractor shall agree to provide and install the necessary piping fittings valves duets duct fittings and offsets and other specialties to suit such conditions without additional cost to the Owner Mechanical drawings shall not be used for general construction dimensions or for type of material used for general construction For exact building layout dimensions and building materials used Contractor shall refer to Architectural Drawings

False Ceilings Tight spaces

High Rise Buildings Determined by length of fire ladder Around 75 feet Buildings constructed as high rise 50 to over

100 floors and there designs are coordinated by the local fire departments and fire marshals

Consideration for interior materials is paramount

Codes and structural components need to meet National Fire Codes

Types of Sprinkler Systems1048708Wet Sprinkler System1048708Dry Sprinkler System1048708Deluge Sprinkler System1048708Pre-Action Sprinkler System

Wet pipe systems Wet pipe sprinkler systems

Most installed Most reliable Simple Only operating components being the

automatic sprinklers An automatic water supply provides water

under pressure to the system piping

Wet Systems1048708Water is in branch lines and at the

sprinkler heads at all times1048708Wet Systems cannot be in areas that

may freeze1048708Water pressure must be maintained at

all times1048708Water Pumps are put in place to keep

water pressure at a certain PSI1048708There is no delay in time that water is

put on the fire1048708Require the least amount of

maintenance

Dry pipe systemsDry pipe systems installed where temperature will freeze water in a wet pipe system Dry pipe systems are most often used in unheated buildings in parking garages in outside canopies attached to heated buildings

Dry Sprinkler System1048708Require Air Pressure instead of water in the

Branch Lines1048708The Air Pressure holds down a Clapper

Valve so that water can not be introduced into the system unless the air pressure is lost

1048708Used in areas that may freeze1048708An air compressor keeps a constant

pressure in the system1048708When a Fire releases a sprinkler head the

air is released from the piping and stops holding down the valve that was holding the water back and water is released

Dry Sprinkler Systems1048708Standpipes are used in stairwells to

have a water way established for hand lines

1048708These systems have a high maintenance cost due to corrosion in the pipe with only air and a little bit of water

1048708Might take up to 60 seconds to get water on the fire depending on how big the system is

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Please read chapter 9Please review know and understand the terms related to fire protection page 284Know the Classifications of Fires 911Know Classification of Hazards 912Know the Use or Occupancy 914Void sections 977 through 979Study the remainder of the chapter See additional reading CSI specifications Article - The Evolution of Modern Automatic Fire Sprinklers

Commercial BuildingsCSI Division

Includes Electrical Piping Equipment Controls

Detection of fire and smoke Suppression

CSI Division Numbers Division 21 Fire Suppression (new)

21 10 00 Water ndash Based Fire- Suppression Systems

21 13 00 Fire-Suppression Sprinkler Systems21 13 13 Wet-Pipe Sprinkler Systems21 13 16 Dry-Pipe Sprinkler Systems21 13 19 Preaction Sprinkler Systems21 13 23 Combined Dry-Pipe and Preaction

Sprinkler Systems21 13 26 Deluge Fire-Suppression Sprinkler

Systems21 13 29 Water Spray Fixed Systems

21 13 36 Antifreeze Sprinkler Systems21 13 39 Foam-Water Systems

Old CSI Fire Protection System (See separate readings ndash Web Site)

Division 10520 Fire Extinguishers amp Cabinets

Old CSI Fire Protection System (See separate required readings ndash Web Site)

Division 15000 Mechanical General ProvisionsDivision 15300 Fire ProtectionDivision 16722 Fire Alarm System

Making sure the various Contract Documents coincide Shop Drawing Specifications Review Coordination

Section 15000 - MECHANICAL GENERAL PROVISIONS

Each specification section within their respective Division shall be coordinated with all other sections in that division for related work

The project documents contemplate the complete installation of the systems described herein or shown on the drawings so that at the conclusion of the construction the systems will be turned over to the Owner complete and ready for safe efficient operation

The Contractor shall be obliged to furnish and install all such items normally included on systems of this type which while not mentioned directly herein are obviously essential to the installationand operation of the systems and which are normally furnished on installations of this type

General Refer to the Division 1 sections for general coordination requirements applicable to the entire work The Contractor shall recognize that the Contract Documents are diagrammatic in showing certain physical relationships that must be established within the mechanical and electrical work and in its interface with other work including utilities and that such establishment is the exclusive responsibility of the Contractor This Contractor shall be responsible for work fitting in place without conflict with other trades where proper planning could avoid interference This Contractor shall examine the locations and verify all measurements distances elevations and existing conditions before starting work Because the drawings are diagrammatic and on a small scale all rises drops offsets etc have not been shown The Contractor shall agree to provide and install the necessary piping fittings valves duets duct fittings and offsets and other specialties to suit such conditions without additional cost to the Owner Mechanical drawings shall not be used for general construction dimensions or for type of material used for general construction For exact building layout dimensions and building materials used Contractor shall refer to Architectural Drawings

False Ceilings Tight spaces

High Rise Buildings Determined by length of fire ladder Around 75 feet Buildings constructed as high rise 50 to over

100 floors and there designs are coordinated by the local fire departments and fire marshals

Consideration for interior materials is paramount

Codes and structural components need to meet National Fire Codes

Types of Sprinkler Systems1048708Wet Sprinkler System1048708Dry Sprinkler System1048708Deluge Sprinkler System1048708Pre-Action Sprinkler System

Wet pipe systems Wet pipe sprinkler systems

Most installed Most reliable Simple Only operating components being the

automatic sprinklers An automatic water supply provides water

under pressure to the system piping

Wet Systems1048708Water is in branch lines and at the

sprinkler heads at all times1048708Wet Systems cannot be in areas that

may freeze1048708Water pressure must be maintained at

all times1048708Water Pumps are put in place to keep

water pressure at a certain PSI1048708There is no delay in time that water is

put on the fire1048708Require the least amount of

maintenance

Dry pipe systemsDry pipe systems installed where temperature will freeze water in a wet pipe system Dry pipe systems are most often used in unheated buildings in parking garages in outside canopies attached to heated buildings

Dry Sprinkler System1048708Require Air Pressure instead of water in the

Branch Lines1048708The Air Pressure holds down a Clapper

Valve so that water can not be introduced into the system unless the air pressure is lost

1048708Used in areas that may freeze1048708An air compressor keeps a constant

pressure in the system1048708When a Fire releases a sprinkler head the

air is released from the piping and stops holding down the valve that was holding the water back and water is released

Dry Sprinkler Systems1048708Standpipes are used in stairwells to

have a water way established for hand lines

1048708These systems have a high maintenance cost due to corrosion in the pipe with only air and a little bit of water

1048708Might take up to 60 seconds to get water on the fire depending on how big the system is

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Commercial BuildingsCSI Division

Includes Electrical Piping Equipment Controls

Detection of fire and smoke Suppression

CSI Division Numbers Division 21 Fire Suppression (new)

21 10 00 Water ndash Based Fire- Suppression Systems

21 13 00 Fire-Suppression Sprinkler Systems21 13 13 Wet-Pipe Sprinkler Systems21 13 16 Dry-Pipe Sprinkler Systems21 13 19 Preaction Sprinkler Systems21 13 23 Combined Dry-Pipe and Preaction

Sprinkler Systems21 13 26 Deluge Fire-Suppression Sprinkler

Systems21 13 29 Water Spray Fixed Systems

21 13 36 Antifreeze Sprinkler Systems21 13 39 Foam-Water Systems

Old CSI Fire Protection System (See separate readings ndash Web Site)

Division 10520 Fire Extinguishers amp Cabinets

Old CSI Fire Protection System (See separate required readings ndash Web Site)

Division 15000 Mechanical General ProvisionsDivision 15300 Fire ProtectionDivision 16722 Fire Alarm System

Making sure the various Contract Documents coincide Shop Drawing Specifications Review Coordination

Section 15000 - MECHANICAL GENERAL PROVISIONS

Each specification section within their respective Division shall be coordinated with all other sections in that division for related work

The project documents contemplate the complete installation of the systems described herein or shown on the drawings so that at the conclusion of the construction the systems will be turned over to the Owner complete and ready for safe efficient operation

The Contractor shall be obliged to furnish and install all such items normally included on systems of this type which while not mentioned directly herein are obviously essential to the installationand operation of the systems and which are normally furnished on installations of this type

General Refer to the Division 1 sections for general coordination requirements applicable to the entire work The Contractor shall recognize that the Contract Documents are diagrammatic in showing certain physical relationships that must be established within the mechanical and electrical work and in its interface with other work including utilities and that such establishment is the exclusive responsibility of the Contractor This Contractor shall be responsible for work fitting in place without conflict with other trades where proper planning could avoid interference This Contractor shall examine the locations and verify all measurements distances elevations and existing conditions before starting work Because the drawings are diagrammatic and on a small scale all rises drops offsets etc have not been shown The Contractor shall agree to provide and install the necessary piping fittings valves duets duct fittings and offsets and other specialties to suit such conditions without additional cost to the Owner Mechanical drawings shall not be used for general construction dimensions or for type of material used for general construction For exact building layout dimensions and building materials used Contractor shall refer to Architectural Drawings

False Ceilings Tight spaces

High Rise Buildings Determined by length of fire ladder Around 75 feet Buildings constructed as high rise 50 to over

100 floors and there designs are coordinated by the local fire departments and fire marshals

Consideration for interior materials is paramount

Codes and structural components need to meet National Fire Codes

Types of Sprinkler Systems1048708Wet Sprinkler System1048708Dry Sprinkler System1048708Deluge Sprinkler System1048708Pre-Action Sprinkler System

Wet pipe systems Wet pipe sprinkler systems

Most installed Most reliable Simple Only operating components being the

automatic sprinklers An automatic water supply provides water

under pressure to the system piping

Wet Systems1048708Water is in branch lines and at the

sprinkler heads at all times1048708Wet Systems cannot be in areas that

may freeze1048708Water pressure must be maintained at

all times1048708Water Pumps are put in place to keep

water pressure at a certain PSI1048708There is no delay in time that water is

put on the fire1048708Require the least amount of

maintenance

Dry pipe systemsDry pipe systems installed where temperature will freeze water in a wet pipe system Dry pipe systems are most often used in unheated buildings in parking garages in outside canopies attached to heated buildings

Dry Sprinkler System1048708Require Air Pressure instead of water in the

Branch Lines1048708The Air Pressure holds down a Clapper

Valve so that water can not be introduced into the system unless the air pressure is lost

1048708Used in areas that may freeze1048708An air compressor keeps a constant

pressure in the system1048708When a Fire releases a sprinkler head the

air is released from the piping and stops holding down the valve that was holding the water back and water is released

Dry Sprinkler Systems1048708Standpipes are used in stairwells to

have a water way established for hand lines

1048708These systems have a high maintenance cost due to corrosion in the pipe with only air and a little bit of water

1048708Might take up to 60 seconds to get water on the fire depending on how big the system is

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

CSI Division Numbers Division 21 Fire Suppression (new)

21 10 00 Water ndash Based Fire- Suppression Systems

21 13 00 Fire-Suppression Sprinkler Systems21 13 13 Wet-Pipe Sprinkler Systems21 13 16 Dry-Pipe Sprinkler Systems21 13 19 Preaction Sprinkler Systems21 13 23 Combined Dry-Pipe and Preaction

Sprinkler Systems21 13 26 Deluge Fire-Suppression Sprinkler

Systems21 13 29 Water Spray Fixed Systems

21 13 36 Antifreeze Sprinkler Systems21 13 39 Foam-Water Systems

Old CSI Fire Protection System (See separate readings ndash Web Site)

Division 10520 Fire Extinguishers amp Cabinets

Old CSI Fire Protection System (See separate required readings ndash Web Site)

Division 15000 Mechanical General ProvisionsDivision 15300 Fire ProtectionDivision 16722 Fire Alarm System

Making sure the various Contract Documents coincide Shop Drawing Specifications Review Coordination

Section 15000 - MECHANICAL GENERAL PROVISIONS

Each specification section within their respective Division shall be coordinated with all other sections in that division for related work

The project documents contemplate the complete installation of the systems described herein or shown on the drawings so that at the conclusion of the construction the systems will be turned over to the Owner complete and ready for safe efficient operation

The Contractor shall be obliged to furnish and install all such items normally included on systems of this type which while not mentioned directly herein are obviously essential to the installationand operation of the systems and which are normally furnished on installations of this type

General Refer to the Division 1 sections for general coordination requirements applicable to the entire work The Contractor shall recognize that the Contract Documents are diagrammatic in showing certain physical relationships that must be established within the mechanical and electrical work and in its interface with other work including utilities and that such establishment is the exclusive responsibility of the Contractor This Contractor shall be responsible for work fitting in place without conflict with other trades where proper planning could avoid interference This Contractor shall examine the locations and verify all measurements distances elevations and existing conditions before starting work Because the drawings are diagrammatic and on a small scale all rises drops offsets etc have not been shown The Contractor shall agree to provide and install the necessary piping fittings valves duets duct fittings and offsets and other specialties to suit such conditions without additional cost to the Owner Mechanical drawings shall not be used for general construction dimensions or for type of material used for general construction For exact building layout dimensions and building materials used Contractor shall refer to Architectural Drawings

False Ceilings Tight spaces

High Rise Buildings Determined by length of fire ladder Around 75 feet Buildings constructed as high rise 50 to over

100 floors and there designs are coordinated by the local fire departments and fire marshals

Consideration for interior materials is paramount

Codes and structural components need to meet National Fire Codes

Types of Sprinkler Systems1048708Wet Sprinkler System1048708Dry Sprinkler System1048708Deluge Sprinkler System1048708Pre-Action Sprinkler System

Wet pipe systems Wet pipe sprinkler systems

Most installed Most reliable Simple Only operating components being the

automatic sprinklers An automatic water supply provides water

under pressure to the system piping

Wet Systems1048708Water is in branch lines and at the

sprinkler heads at all times1048708Wet Systems cannot be in areas that

may freeze1048708Water pressure must be maintained at

all times1048708Water Pumps are put in place to keep

water pressure at a certain PSI1048708There is no delay in time that water is

put on the fire1048708Require the least amount of

maintenance

Dry pipe systemsDry pipe systems installed where temperature will freeze water in a wet pipe system Dry pipe systems are most often used in unheated buildings in parking garages in outside canopies attached to heated buildings

Dry Sprinkler System1048708Require Air Pressure instead of water in the

Branch Lines1048708The Air Pressure holds down a Clapper

Valve so that water can not be introduced into the system unless the air pressure is lost

1048708Used in areas that may freeze1048708An air compressor keeps a constant

pressure in the system1048708When a Fire releases a sprinkler head the

air is released from the piping and stops holding down the valve that was holding the water back and water is released

Dry Sprinkler Systems1048708Standpipes are used in stairwells to

have a water way established for hand lines

1048708These systems have a high maintenance cost due to corrosion in the pipe with only air and a little bit of water

1048708Might take up to 60 seconds to get water on the fire depending on how big the system is

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Old CSI Fire Protection System (See separate readings ndash Web Site)

Division 10520 Fire Extinguishers amp Cabinets

Old CSI Fire Protection System (See separate required readings ndash Web Site)

Division 15000 Mechanical General ProvisionsDivision 15300 Fire ProtectionDivision 16722 Fire Alarm System

Making sure the various Contract Documents coincide Shop Drawing Specifications Review Coordination

Section 15000 - MECHANICAL GENERAL PROVISIONS

Each specification section within their respective Division shall be coordinated with all other sections in that division for related work

The project documents contemplate the complete installation of the systems described herein or shown on the drawings so that at the conclusion of the construction the systems will be turned over to the Owner complete and ready for safe efficient operation

The Contractor shall be obliged to furnish and install all such items normally included on systems of this type which while not mentioned directly herein are obviously essential to the installationand operation of the systems and which are normally furnished on installations of this type

General Refer to the Division 1 sections for general coordination requirements applicable to the entire work The Contractor shall recognize that the Contract Documents are diagrammatic in showing certain physical relationships that must be established within the mechanical and electrical work and in its interface with other work including utilities and that such establishment is the exclusive responsibility of the Contractor This Contractor shall be responsible for work fitting in place without conflict with other trades where proper planning could avoid interference This Contractor shall examine the locations and verify all measurements distances elevations and existing conditions before starting work Because the drawings are diagrammatic and on a small scale all rises drops offsets etc have not been shown The Contractor shall agree to provide and install the necessary piping fittings valves duets duct fittings and offsets and other specialties to suit such conditions without additional cost to the Owner Mechanical drawings shall not be used for general construction dimensions or for type of material used for general construction For exact building layout dimensions and building materials used Contractor shall refer to Architectural Drawings

False Ceilings Tight spaces

High Rise Buildings Determined by length of fire ladder Around 75 feet Buildings constructed as high rise 50 to over

100 floors and there designs are coordinated by the local fire departments and fire marshals

Consideration for interior materials is paramount

Codes and structural components need to meet National Fire Codes

Types of Sprinkler Systems1048708Wet Sprinkler System1048708Dry Sprinkler System1048708Deluge Sprinkler System1048708Pre-Action Sprinkler System

Wet pipe systems Wet pipe sprinkler systems

Most installed Most reliable Simple Only operating components being the

automatic sprinklers An automatic water supply provides water

under pressure to the system piping

Wet Systems1048708Water is in branch lines and at the

sprinkler heads at all times1048708Wet Systems cannot be in areas that

may freeze1048708Water pressure must be maintained at

all times1048708Water Pumps are put in place to keep

water pressure at a certain PSI1048708There is no delay in time that water is

put on the fire1048708Require the least amount of

maintenance

Dry pipe systemsDry pipe systems installed where temperature will freeze water in a wet pipe system Dry pipe systems are most often used in unheated buildings in parking garages in outside canopies attached to heated buildings

Dry Sprinkler System1048708Require Air Pressure instead of water in the

Branch Lines1048708The Air Pressure holds down a Clapper

Valve so that water can not be introduced into the system unless the air pressure is lost

1048708Used in areas that may freeze1048708An air compressor keeps a constant

pressure in the system1048708When a Fire releases a sprinkler head the

air is released from the piping and stops holding down the valve that was holding the water back and water is released

Dry Sprinkler Systems1048708Standpipes are used in stairwells to

have a water way established for hand lines

1048708These systems have a high maintenance cost due to corrosion in the pipe with only air and a little bit of water

1048708Might take up to 60 seconds to get water on the fire depending on how big the system is

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Old CSI Fire Protection System (See separate required readings ndash Web Site)

Division 15000 Mechanical General ProvisionsDivision 15300 Fire ProtectionDivision 16722 Fire Alarm System

Making sure the various Contract Documents coincide Shop Drawing Specifications Review Coordination

Section 15000 - MECHANICAL GENERAL PROVISIONS

Each specification section within their respective Division shall be coordinated with all other sections in that division for related work

The project documents contemplate the complete installation of the systems described herein or shown on the drawings so that at the conclusion of the construction the systems will be turned over to the Owner complete and ready for safe efficient operation

The Contractor shall be obliged to furnish and install all such items normally included on systems of this type which while not mentioned directly herein are obviously essential to the installationand operation of the systems and which are normally furnished on installations of this type

General Refer to the Division 1 sections for general coordination requirements applicable to the entire work The Contractor shall recognize that the Contract Documents are diagrammatic in showing certain physical relationships that must be established within the mechanical and electrical work and in its interface with other work including utilities and that such establishment is the exclusive responsibility of the Contractor This Contractor shall be responsible for work fitting in place without conflict with other trades where proper planning could avoid interference This Contractor shall examine the locations and verify all measurements distances elevations and existing conditions before starting work Because the drawings are diagrammatic and on a small scale all rises drops offsets etc have not been shown The Contractor shall agree to provide and install the necessary piping fittings valves duets duct fittings and offsets and other specialties to suit such conditions without additional cost to the Owner Mechanical drawings shall not be used for general construction dimensions or for type of material used for general construction For exact building layout dimensions and building materials used Contractor shall refer to Architectural Drawings

False Ceilings Tight spaces

High Rise Buildings Determined by length of fire ladder Around 75 feet Buildings constructed as high rise 50 to over

100 floors and there designs are coordinated by the local fire departments and fire marshals

Consideration for interior materials is paramount

Codes and structural components need to meet National Fire Codes

Types of Sprinkler Systems1048708Wet Sprinkler System1048708Dry Sprinkler System1048708Deluge Sprinkler System1048708Pre-Action Sprinkler System

Wet pipe systems Wet pipe sprinkler systems

Most installed Most reliable Simple Only operating components being the

automatic sprinklers An automatic water supply provides water

under pressure to the system piping

Wet Systems1048708Water is in branch lines and at the

sprinkler heads at all times1048708Wet Systems cannot be in areas that

may freeze1048708Water pressure must be maintained at

all times1048708Water Pumps are put in place to keep

water pressure at a certain PSI1048708There is no delay in time that water is

put on the fire1048708Require the least amount of

maintenance

Dry pipe systemsDry pipe systems installed where temperature will freeze water in a wet pipe system Dry pipe systems are most often used in unheated buildings in parking garages in outside canopies attached to heated buildings

Dry Sprinkler System1048708Require Air Pressure instead of water in the

Branch Lines1048708The Air Pressure holds down a Clapper

Valve so that water can not be introduced into the system unless the air pressure is lost

1048708Used in areas that may freeze1048708An air compressor keeps a constant

pressure in the system1048708When a Fire releases a sprinkler head the

air is released from the piping and stops holding down the valve that was holding the water back and water is released

Dry Sprinkler Systems1048708Standpipes are used in stairwells to

have a water way established for hand lines

1048708These systems have a high maintenance cost due to corrosion in the pipe with only air and a little bit of water

1048708Might take up to 60 seconds to get water on the fire depending on how big the system is

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Making sure the various Contract Documents coincide Shop Drawing Specifications Review Coordination

Section 15000 - MECHANICAL GENERAL PROVISIONS

Each specification section within their respective Division shall be coordinated with all other sections in that division for related work

The project documents contemplate the complete installation of the systems described herein or shown on the drawings so that at the conclusion of the construction the systems will be turned over to the Owner complete and ready for safe efficient operation

The Contractor shall be obliged to furnish and install all such items normally included on systems of this type which while not mentioned directly herein are obviously essential to the installationand operation of the systems and which are normally furnished on installations of this type

General Refer to the Division 1 sections for general coordination requirements applicable to the entire work The Contractor shall recognize that the Contract Documents are diagrammatic in showing certain physical relationships that must be established within the mechanical and electrical work and in its interface with other work including utilities and that such establishment is the exclusive responsibility of the Contractor This Contractor shall be responsible for work fitting in place without conflict with other trades where proper planning could avoid interference This Contractor shall examine the locations and verify all measurements distances elevations and existing conditions before starting work Because the drawings are diagrammatic and on a small scale all rises drops offsets etc have not been shown The Contractor shall agree to provide and install the necessary piping fittings valves duets duct fittings and offsets and other specialties to suit such conditions without additional cost to the Owner Mechanical drawings shall not be used for general construction dimensions or for type of material used for general construction For exact building layout dimensions and building materials used Contractor shall refer to Architectural Drawings

False Ceilings Tight spaces

High Rise Buildings Determined by length of fire ladder Around 75 feet Buildings constructed as high rise 50 to over

100 floors and there designs are coordinated by the local fire departments and fire marshals

Consideration for interior materials is paramount

Codes and structural components need to meet National Fire Codes

Types of Sprinkler Systems1048708Wet Sprinkler System1048708Dry Sprinkler System1048708Deluge Sprinkler System1048708Pre-Action Sprinkler System

Wet pipe systems Wet pipe sprinkler systems

Most installed Most reliable Simple Only operating components being the

automatic sprinklers An automatic water supply provides water

under pressure to the system piping

Wet Systems1048708Water is in branch lines and at the

sprinkler heads at all times1048708Wet Systems cannot be in areas that

may freeze1048708Water pressure must be maintained at

all times1048708Water Pumps are put in place to keep

water pressure at a certain PSI1048708There is no delay in time that water is

put on the fire1048708Require the least amount of

maintenance

Dry pipe systemsDry pipe systems installed where temperature will freeze water in a wet pipe system Dry pipe systems are most often used in unheated buildings in parking garages in outside canopies attached to heated buildings

Dry Sprinkler System1048708Require Air Pressure instead of water in the

Branch Lines1048708The Air Pressure holds down a Clapper

Valve so that water can not be introduced into the system unless the air pressure is lost

1048708Used in areas that may freeze1048708An air compressor keeps a constant

pressure in the system1048708When a Fire releases a sprinkler head the

air is released from the piping and stops holding down the valve that was holding the water back and water is released

Dry Sprinkler Systems1048708Standpipes are used in stairwells to

have a water way established for hand lines

1048708These systems have a high maintenance cost due to corrosion in the pipe with only air and a little bit of water

1048708Might take up to 60 seconds to get water on the fire depending on how big the system is

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Section 15000 - MECHANICAL GENERAL PROVISIONS

Each specification section within their respective Division shall be coordinated with all other sections in that division for related work

The project documents contemplate the complete installation of the systems described herein or shown on the drawings so that at the conclusion of the construction the systems will be turned over to the Owner complete and ready for safe efficient operation

The Contractor shall be obliged to furnish and install all such items normally included on systems of this type which while not mentioned directly herein are obviously essential to the installationand operation of the systems and which are normally furnished on installations of this type

General Refer to the Division 1 sections for general coordination requirements applicable to the entire work The Contractor shall recognize that the Contract Documents are diagrammatic in showing certain physical relationships that must be established within the mechanical and electrical work and in its interface with other work including utilities and that such establishment is the exclusive responsibility of the Contractor This Contractor shall be responsible for work fitting in place without conflict with other trades where proper planning could avoid interference This Contractor shall examine the locations and verify all measurements distances elevations and existing conditions before starting work Because the drawings are diagrammatic and on a small scale all rises drops offsets etc have not been shown The Contractor shall agree to provide and install the necessary piping fittings valves duets duct fittings and offsets and other specialties to suit such conditions without additional cost to the Owner Mechanical drawings shall not be used for general construction dimensions or for type of material used for general construction For exact building layout dimensions and building materials used Contractor shall refer to Architectural Drawings

False Ceilings Tight spaces

High Rise Buildings Determined by length of fire ladder Around 75 feet Buildings constructed as high rise 50 to over

100 floors and there designs are coordinated by the local fire departments and fire marshals

Consideration for interior materials is paramount

Codes and structural components need to meet National Fire Codes

Types of Sprinkler Systems1048708Wet Sprinkler System1048708Dry Sprinkler System1048708Deluge Sprinkler System1048708Pre-Action Sprinkler System

Wet pipe systems Wet pipe sprinkler systems

Most installed Most reliable Simple Only operating components being the

automatic sprinklers An automatic water supply provides water

under pressure to the system piping

Wet Systems1048708Water is in branch lines and at the

sprinkler heads at all times1048708Wet Systems cannot be in areas that

may freeze1048708Water pressure must be maintained at

all times1048708Water Pumps are put in place to keep

water pressure at a certain PSI1048708There is no delay in time that water is

put on the fire1048708Require the least amount of

maintenance

Dry pipe systemsDry pipe systems installed where temperature will freeze water in a wet pipe system Dry pipe systems are most often used in unheated buildings in parking garages in outside canopies attached to heated buildings

Dry Sprinkler System1048708Require Air Pressure instead of water in the

Branch Lines1048708The Air Pressure holds down a Clapper

Valve so that water can not be introduced into the system unless the air pressure is lost

1048708Used in areas that may freeze1048708An air compressor keeps a constant

pressure in the system1048708When a Fire releases a sprinkler head the

air is released from the piping and stops holding down the valve that was holding the water back and water is released

Dry Sprinkler Systems1048708Standpipes are used in stairwells to

have a water way established for hand lines

1048708These systems have a high maintenance cost due to corrosion in the pipe with only air and a little bit of water

1048708Might take up to 60 seconds to get water on the fire depending on how big the system is

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

General Refer to the Division 1 sections for general coordination requirements applicable to the entire work The Contractor shall recognize that the Contract Documents are diagrammatic in showing certain physical relationships that must be established within the mechanical and electrical work and in its interface with other work including utilities and that such establishment is the exclusive responsibility of the Contractor This Contractor shall be responsible for work fitting in place without conflict with other trades where proper planning could avoid interference This Contractor shall examine the locations and verify all measurements distances elevations and existing conditions before starting work Because the drawings are diagrammatic and on a small scale all rises drops offsets etc have not been shown The Contractor shall agree to provide and install the necessary piping fittings valves duets duct fittings and offsets and other specialties to suit such conditions without additional cost to the Owner Mechanical drawings shall not be used for general construction dimensions or for type of material used for general construction For exact building layout dimensions and building materials used Contractor shall refer to Architectural Drawings

False Ceilings Tight spaces

High Rise Buildings Determined by length of fire ladder Around 75 feet Buildings constructed as high rise 50 to over

100 floors and there designs are coordinated by the local fire departments and fire marshals

Consideration for interior materials is paramount

Codes and structural components need to meet National Fire Codes

Types of Sprinkler Systems1048708Wet Sprinkler System1048708Dry Sprinkler System1048708Deluge Sprinkler System1048708Pre-Action Sprinkler System

Wet pipe systems Wet pipe sprinkler systems

Most installed Most reliable Simple Only operating components being the

automatic sprinklers An automatic water supply provides water

under pressure to the system piping

Wet Systems1048708Water is in branch lines and at the

sprinkler heads at all times1048708Wet Systems cannot be in areas that

may freeze1048708Water pressure must be maintained at

all times1048708Water Pumps are put in place to keep

water pressure at a certain PSI1048708There is no delay in time that water is

put on the fire1048708Require the least amount of

maintenance

Dry pipe systemsDry pipe systems installed where temperature will freeze water in a wet pipe system Dry pipe systems are most often used in unheated buildings in parking garages in outside canopies attached to heated buildings

Dry Sprinkler System1048708Require Air Pressure instead of water in the

Branch Lines1048708The Air Pressure holds down a Clapper

Valve so that water can not be introduced into the system unless the air pressure is lost

1048708Used in areas that may freeze1048708An air compressor keeps a constant

pressure in the system1048708When a Fire releases a sprinkler head the

air is released from the piping and stops holding down the valve that was holding the water back and water is released

Dry Sprinkler Systems1048708Standpipes are used in stairwells to

have a water way established for hand lines

1048708These systems have a high maintenance cost due to corrosion in the pipe with only air and a little bit of water

1048708Might take up to 60 seconds to get water on the fire depending on how big the system is

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

False Ceilings Tight spaces

High Rise Buildings Determined by length of fire ladder Around 75 feet Buildings constructed as high rise 50 to over

100 floors and there designs are coordinated by the local fire departments and fire marshals

Consideration for interior materials is paramount

Codes and structural components need to meet National Fire Codes

Types of Sprinkler Systems1048708Wet Sprinkler System1048708Dry Sprinkler System1048708Deluge Sprinkler System1048708Pre-Action Sprinkler System

Wet pipe systems Wet pipe sprinkler systems

Most installed Most reliable Simple Only operating components being the

automatic sprinklers An automatic water supply provides water

under pressure to the system piping

Wet Systems1048708Water is in branch lines and at the

sprinkler heads at all times1048708Wet Systems cannot be in areas that

may freeze1048708Water pressure must be maintained at

all times1048708Water Pumps are put in place to keep

water pressure at a certain PSI1048708There is no delay in time that water is

put on the fire1048708Require the least amount of

maintenance

Dry pipe systemsDry pipe systems installed where temperature will freeze water in a wet pipe system Dry pipe systems are most often used in unheated buildings in parking garages in outside canopies attached to heated buildings

Dry Sprinkler System1048708Require Air Pressure instead of water in the

Branch Lines1048708The Air Pressure holds down a Clapper

Valve so that water can not be introduced into the system unless the air pressure is lost

1048708Used in areas that may freeze1048708An air compressor keeps a constant

pressure in the system1048708When a Fire releases a sprinkler head the

air is released from the piping and stops holding down the valve that was holding the water back and water is released

Dry Sprinkler Systems1048708Standpipes are used in stairwells to

have a water way established for hand lines

1048708These systems have a high maintenance cost due to corrosion in the pipe with only air and a little bit of water

1048708Might take up to 60 seconds to get water on the fire depending on how big the system is

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

High Rise Buildings Determined by length of fire ladder Around 75 feet Buildings constructed as high rise 50 to over

100 floors and there designs are coordinated by the local fire departments and fire marshals

Consideration for interior materials is paramount

Codes and structural components need to meet National Fire Codes

Types of Sprinkler Systems1048708Wet Sprinkler System1048708Dry Sprinkler System1048708Deluge Sprinkler System1048708Pre-Action Sprinkler System

Wet pipe systems Wet pipe sprinkler systems

Most installed Most reliable Simple Only operating components being the

automatic sprinklers An automatic water supply provides water

under pressure to the system piping

Wet Systems1048708Water is in branch lines and at the

sprinkler heads at all times1048708Wet Systems cannot be in areas that

may freeze1048708Water pressure must be maintained at

all times1048708Water Pumps are put in place to keep

water pressure at a certain PSI1048708There is no delay in time that water is

put on the fire1048708Require the least amount of

maintenance

Dry pipe systemsDry pipe systems installed where temperature will freeze water in a wet pipe system Dry pipe systems are most often used in unheated buildings in parking garages in outside canopies attached to heated buildings

Dry Sprinkler System1048708Require Air Pressure instead of water in the

Branch Lines1048708The Air Pressure holds down a Clapper

Valve so that water can not be introduced into the system unless the air pressure is lost

1048708Used in areas that may freeze1048708An air compressor keeps a constant

pressure in the system1048708When a Fire releases a sprinkler head the

air is released from the piping and stops holding down the valve that was holding the water back and water is released

Dry Sprinkler Systems1048708Standpipes are used in stairwells to

have a water way established for hand lines

1048708These systems have a high maintenance cost due to corrosion in the pipe with only air and a little bit of water

1048708Might take up to 60 seconds to get water on the fire depending on how big the system is

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Types of Sprinkler Systems1048708Wet Sprinkler System1048708Dry Sprinkler System1048708Deluge Sprinkler System1048708Pre-Action Sprinkler System

Wet pipe systems Wet pipe sprinkler systems

Most installed Most reliable Simple Only operating components being the

automatic sprinklers An automatic water supply provides water

under pressure to the system piping

Wet Systems1048708Water is in branch lines and at the

sprinkler heads at all times1048708Wet Systems cannot be in areas that

may freeze1048708Water pressure must be maintained at

all times1048708Water Pumps are put in place to keep

water pressure at a certain PSI1048708There is no delay in time that water is

put on the fire1048708Require the least amount of

maintenance

Dry pipe systemsDry pipe systems installed where temperature will freeze water in a wet pipe system Dry pipe systems are most often used in unheated buildings in parking garages in outside canopies attached to heated buildings

Dry Sprinkler System1048708Require Air Pressure instead of water in the

Branch Lines1048708The Air Pressure holds down a Clapper

Valve so that water can not be introduced into the system unless the air pressure is lost

1048708Used in areas that may freeze1048708An air compressor keeps a constant

pressure in the system1048708When a Fire releases a sprinkler head the

air is released from the piping and stops holding down the valve that was holding the water back and water is released

Dry Sprinkler Systems1048708Standpipes are used in stairwells to

have a water way established for hand lines

1048708These systems have a high maintenance cost due to corrosion in the pipe with only air and a little bit of water

1048708Might take up to 60 seconds to get water on the fire depending on how big the system is

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Wet pipe systems Wet pipe sprinkler systems

Most installed Most reliable Simple Only operating components being the

automatic sprinklers An automatic water supply provides water

under pressure to the system piping

Wet Systems1048708Water is in branch lines and at the

sprinkler heads at all times1048708Wet Systems cannot be in areas that

may freeze1048708Water pressure must be maintained at

all times1048708Water Pumps are put in place to keep

water pressure at a certain PSI1048708There is no delay in time that water is

put on the fire1048708Require the least amount of

maintenance

Dry pipe systemsDry pipe systems installed where temperature will freeze water in a wet pipe system Dry pipe systems are most often used in unheated buildings in parking garages in outside canopies attached to heated buildings

Dry Sprinkler System1048708Require Air Pressure instead of water in the

Branch Lines1048708The Air Pressure holds down a Clapper

Valve so that water can not be introduced into the system unless the air pressure is lost

1048708Used in areas that may freeze1048708An air compressor keeps a constant

pressure in the system1048708When a Fire releases a sprinkler head the

air is released from the piping and stops holding down the valve that was holding the water back and water is released

Dry Sprinkler Systems1048708Standpipes are used in stairwells to

have a water way established for hand lines

1048708These systems have a high maintenance cost due to corrosion in the pipe with only air and a little bit of water

1048708Might take up to 60 seconds to get water on the fire depending on how big the system is

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Wet Systems1048708Water is in branch lines and at the

sprinkler heads at all times1048708Wet Systems cannot be in areas that

may freeze1048708Water pressure must be maintained at

all times1048708Water Pumps are put in place to keep

water pressure at a certain PSI1048708There is no delay in time that water is

put on the fire1048708Require the least amount of

maintenance

Dry pipe systemsDry pipe systems installed where temperature will freeze water in a wet pipe system Dry pipe systems are most often used in unheated buildings in parking garages in outside canopies attached to heated buildings

Dry Sprinkler System1048708Require Air Pressure instead of water in the

Branch Lines1048708The Air Pressure holds down a Clapper

Valve so that water can not be introduced into the system unless the air pressure is lost

1048708Used in areas that may freeze1048708An air compressor keeps a constant

pressure in the system1048708When a Fire releases a sprinkler head the

air is released from the piping and stops holding down the valve that was holding the water back and water is released

Dry Sprinkler Systems1048708Standpipes are used in stairwells to

have a water way established for hand lines

1048708These systems have a high maintenance cost due to corrosion in the pipe with only air and a little bit of water

1048708Might take up to 60 seconds to get water on the fire depending on how big the system is

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Dry pipe systemsDry pipe systems installed where temperature will freeze water in a wet pipe system Dry pipe systems are most often used in unheated buildings in parking garages in outside canopies attached to heated buildings

Dry Sprinkler System1048708Require Air Pressure instead of water in the

Branch Lines1048708The Air Pressure holds down a Clapper

Valve so that water can not be introduced into the system unless the air pressure is lost

1048708Used in areas that may freeze1048708An air compressor keeps a constant

pressure in the system1048708When a Fire releases a sprinkler head the

air is released from the piping and stops holding down the valve that was holding the water back and water is released

Dry Sprinkler Systems1048708Standpipes are used in stairwells to

have a water way established for hand lines

1048708These systems have a high maintenance cost due to corrosion in the pipe with only air and a little bit of water

1048708Might take up to 60 seconds to get water on the fire depending on how big the system is

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Dry Sprinkler System1048708Require Air Pressure instead of water in the

Branch Lines1048708The Air Pressure holds down a Clapper

Valve so that water can not be introduced into the system unless the air pressure is lost

1048708Used in areas that may freeze1048708An air compressor keeps a constant

pressure in the system1048708When a Fire releases a sprinkler head the

air is released from the piping and stops holding down the valve that was holding the water back and water is released

Dry Sprinkler Systems1048708Standpipes are used in stairwells to

have a water way established for hand lines

1048708These systems have a high maintenance cost due to corrosion in the pipe with only air and a little bit of water

1048708Might take up to 60 seconds to get water on the fire depending on how big the system is

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Dry Sprinkler Systems1048708Standpipes are used in stairwells to

have a water way established for hand lines

1048708These systems have a high maintenance cost due to corrosion in the pipe with only air and a little bit of water

1048708Might take up to 60 seconds to get water on the fire depending on how big the system is

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Dry Sprinkler Systems

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Fusible Link Sprinklers vs Glass Bulb Sprinklers All wet-pipe sprinklers are held closed by either a fusible link or a glass bulb that contains a heat-sensitive liquidA fusible link sprinkler head has a two-part metal element that is fused by a heat-sensitive alloy Water is only released by sprinkler heads where the ambient temperature reaches a specified level

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Glass bulb sprinkler heads have a small glass reservoir that holds a heat-sensitive liquid

This glass bulb holds the pip cap in place When the ambient temperature of the

liquid reaches a certain level the liquid expands causing the glass bulb to break which allows the pip cap to fall away releasing water

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Deluge1048708Deluge Valves are used in special

areas1048708Sprinkler heads are open at all times1048708Used in High Hazard areas1048708Deluge Valve opens during a smoke

or heat detection1048708Deluge systems are needed where

high velocity suppression is necessary

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Designer type of sprinkler heads

Painting

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Over 50000 types of sprinkler heads available for designers Based On System Type Activation Temperature Orifice Size Thread Size Coverage Finish Fusible Type

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Types of Sprinkler Heads Pendants Uprights Sidewalls Concealed Special Coverage

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Pendants

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Uprights

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Sidewalls

Sidewalls

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Concealed

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Special Coverage

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

Foam Water Fire Sprinkler System Special application system Discharging a mixture of water and low expansion foam concentrateUsed with special hazards occupancies

associated with high challenge fires flammable liquids airport hangars

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing

PBDErsquos

Furniture Clothing Electronics

  • Fire Protection Equipment amp Systems
  • Fire Protection
  • Slide 3
  • Slide 4
  • Slide 5
  • Fire Protection
  • Slide 7
  • Specification
  • Slide 9
  • Slide 10
  • Slide 11
  • Slide 12
  • Slide 13
  • Slide 14
  • Slide 15
  • Slide 16
  • Slide 17
  • Slide 18
  • Slide 19
  • Slide 20
  • Slide 21
  • Slide 22
  • Slide 23
  • Slide 24
  • Slide 25
  • Slide 26
  • Slide 27
  • Slide 28
  • Slide 29
  • Slide 30
  • Slide 31
  • Slide 32
  • Slide 33
  • Slide 34
  • Slide 35
  • Slide 36
  • Slide 37
  • Slide 38
  • Slide 39
  • Slide 40
  • Slide 41
  • Slide 42
  • Slide 43
  • Slide 44
  • Slide 45
  • Slide 46
  • Slide 47
  • Fire Proofing