Upload
satya-sagar
View
244
Download
0
Embed Size (px)
DESCRIPTION
CONTROL SYSTEM IMPLIMENTATION
Citation preview
Control System Instrumentation
Standard Instrument Signals
• Pneumatic (air pressure): 3 – 15 psig
• Electrical: 4 – 20 mA
• I/P or E/P transducer
• Figure 9.3 illustrates the general configuration of a measurement transducer; it typically consists of a sensing element combined with a driving element (transmitter).
• Since about 1960, electronic instrumentation has come into widespread use.
Ch
apte
r 9
Transducers and Transmitters
Sensors
The book briefly discusses commonly used sensors for the most important process variables. (See text.)
Transmitters
• A transmitter usually converts the sensor output to a signal level appropriate for input to a controller, such as 4 to 20 mA.
• Transmitters are generally designed to be direct acting.
• In addition, most commercial transmitters have an adjustable input range (or span).
• For example, a temperature transmitter might be adjusted so that the input range of a platinum resistance element (the sensor) is 50 to 150 °C.
Ch
apte
r 9
Ch
apte
r 9
Ch
apte
r 9
Range and Scale Factor
range 50 to 150
20 4scale factor 0.16 mA /
150 500.16m
C
C
G s
Transfer Function – Nonlinear Case
nominal
mm m
dTG s K
dT
Ch
apte
r 9
Measurement / Transmission Lags
• Temperature sensor
make as small as possible (location, materials for thermowell)
• Pneumatic transmission lines
usually pure time delay, measure experimentally (no time delays for electronic lines); less common today compared to electronic transmissions.
( ) 1
( ) 1m s s
mm s s
T s m C
T s s U A
Ch
apte
r 9
m
Transmitter/Controller
Ch
apte
r 9
May need additional transducers for Gm if its output is in mA or psi. In the above case, Gc is dimensionless (volts/volts).
Measurement Errors
• Systematic errors– Drift: slowly changing instrument output when
input is constant.– Nonlinearity– Hysteresis or backlash– Dead band– Dynamic error
• Random errors
Figure 9.15 Nonideal instrument behavior: (a) hysteresis, (b) dead band.
Ch
apte
r 9
Ch
apte
r 9
Ch
apte
r 9
Precision, Resolution, Accuracy and Repeatability
• Precision can be interpreted as the number of significant digits in measurement, but more accurately it refers to the least significant digit which contains valid information, e.g., 0.01 in the present case. Therefore, 0.33 is more precise than 0.3.
• Resolution is defined as the smallest change in the input that will result in a significant change in the transducer output.
• Repeatability is +/- 0.02 in the present case.• Accuracy is 0.39-0.25=0.14, i.e., maximum error.
Final Control Elements
• The most-common manipulated variables to be adjusted are: (1) energy flow rates, and (2) material flow rates.
• Type (1): transducer + heating element
• Type (2): transducer + control valve (pump drive, screw conveyer, blower, etc.)
Ch
apte
r 9
Control Valve Characteristics (Inherent)
Design equation for liquids
: flow rate, gpm
: valve coefficient, valve size
: valve lift, 0 1 (fraction open of the valve)
: pressure drop across valve
: specific gravity
vv
s
v v
v
s
Pq C f
g
q
C C
P
g
Ch
apte
r 9
Ch
apte
r 9
1
(1) Quick Opening (square root trim)
(2) Linear Trim
(3) Equal Percentage
20-50
/Note that ln
f
f
f R
R
df dff R
d
1
ln constant
Note also that 0 0.05 inaccurate!
fR
d
f R
Pressure Drop Across Control Valve Installed On-Line
In practical applications, one must take other flow obstructions into account for actual valve performance.
Design Guideline
Since and
for ease of control high
for low cost low
1 1 to at design flow rate
3 4
s v
v
v
vd
P P P
P
P
Pq
P
Ch
apte
r 9
Design Calculation for a Linear Valve
pick 0.5
200127
0.5 10
select 4-in valve according to catalog
dv
v
s
qC
P
g
Rangeability (Turn-Down Ratio)
maximum controllable flow level flow at 95% lift
minimum controllable flow level flow at 5% lift
rangeability=19 for linear valves
rangeability=34 for equal-percentage valves (R=50)
rangeability=3 for q
uick-opening valves
Example
2
If the flow rate is reduced to 25% of the design level,
5030 1.9 (psi)
200
40 1.9 38.1 (psi)
500.06 (almost closed)
127 38.1
he
v
v
s
P
P
qf
PC
g
Installed Valve Characteristics
• Desired behavior: the flow rate is a linear function of valve lift.
• Let us assume that the control valve has linear trim and it is necessary to increase the flow rate. If p through exchanger did not change, then valve would behave linearly (true for low flow rates), since it takes most of p . For higher flow rates, p through exchanger will be important, changing effective valve characteristics (valve must open more than expected nonlinear behavior).
Linear Valve Behavior
2
2
0.52
0.52
0.5 200 gpm 127
30200
40 30200
127 40 30200
127
(calculated previously)
40 30200
d v
he
v
vv
s
q C
qP
qP
P qq C
g
q
q
Equal-Percentage Valve Characteristics
1
max
1 1 2
0.521
0.52
50 50
=1 1.1 1.1 200 220
220115
/ 50 40 30 1.1
115 50 40 30200
11 ln
ln 50 115 40 30 /
Assume
As
200
sume d
v
v s
R f
q q
qC
f P g
q
q
Ch
apte
r 9
Ch
apte
r 9
Control Valve Transfer Function
gpm gpmor
p
1
where
si %C
O
vv
v
v
t
KG s
s
qK
p
q
p