Upload
ahmed-magdy
View
222
Download
0
Embed Size (px)
Citation preview
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 1/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation
Chapter 11
Power cables
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 2/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 2
11.1 Introduction
11.1.1 General Layout of the System
The conductor system by means of which electric power is conveyedfrom a generating station to the consumer’s premises may, in general,
be divided into two distinct parts i.etransmission system and distribution
system. Each part can again be sub-divided into two — primary
transmission and secondary transmission and similarly, primary
distribution and secondary distribution and then finally the system of
supply to individual consumers. Atypical layout of a generating,
transmission and distribution network of a large system would be made
up of elements as shown by a single-line diagram of Fig. 11.1 although
it has to be realized that one or more of these elements may be missing
in any particular system. For example, in a certain system, there maybe no secondary transmission and in another case, when the
generating station is nearby, there may be no transmission and thedistribution system proper may begin at the generator bus-bars.
Now-a-days, generation and transmission is
almost exclusively three-phase. The
secondary trans-mission is also 3-phase
whereas the distribution to the ultimate
customer may be 3-phase or single-phase
depending upon the requirements of thecustomers.
In Fig. 11.1 C.S. represents the central
station where power is generated by 3-
phase alternators at 6.6 or 11 or 13.2 or
even 32 kV. The voltage is then stepped up
by suitable 3-phase transformers for
transmission purposes. Taking the
generated voltage as 11 kV, the 3-phasetransformers step it up to 132kV as shown.
Primary or high-voltage transmission is
carried out at 132 kV
The 3-phase, 3-wire overhead high-voltage transmission line next
terminates in step-down trans-formers in a sub-station known as
Receiving Station R.Swhich usually lies at the outskirts of a citybecause
it is not safe to bring high-voltage overhead transmission lines intothickly-populated areas.
Figure11.1
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 3/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 3
Here, the voltage is stepped down to 33 kV. It may be noted here that
for ensuring continuity ofservicetransmission is always by duplicate
linesFrom the Receiving Station, power is next transmitted at 33 kV by
underground cables (andoccasionally by overhead lines) to varioussub-stations (SS) located at various strategic points in thecity. This is
known as secondary or low-voltage transmission. From now onwards
starts the primary and secondary distribution.
At the sub-station (SS) voltage is reduced from 33kV to 3.3kV 3-wire for
primary distribution.Consumers whose demands exceeds 50 kVA are
usually supplied fromSSby special 3.3 kV feeders.The secondary
distribution is done at 400/230 V for which purpose voltage is reduced
from3.3kV to 400 V at the distribution sub-stations.
Feeders radiating from distribution sub-stationsupply power to
distribution networks in their respective areas. If the distribution network
happens tobe at a great distance from sub-station, then they are
supplied from the secondaries of distributiontransformers which are
either pole-mounted or else housed in kiosks at suitable points of the
distribu-tion networks. The most common system for secondary
distribution is 400/230-V, 3-phase 4-wiresystem. The single-phase
residential lighting load is connected between any one line and the
neutral.
Note: Voltage levels are defined internationally, as follows:
Low voltage: up to 1000 V
Medium voltage: above 1000 V up to 36 kV
High voltage: above 36 kV
Supply standards variation between continents by two general
standards have emergedas the dominant ones:
In Europe
IEC governs supply standards
The frequency is 50 Hz and LV voltage is 230/400 V
In North America
IEEE/ANSI governs supply standards
The frequency is 60 Hz and the LV voltage is 110/190 V.
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 4/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 4
12.1.2 Difference between over head lines and under ground
systems
Overhead lines are far cheaper than underground cables for long
distances, mainly due
to the fact that air is used as the insulation medium between phase
conductors. The
support masts of overhead lines are quite a significant portion of the
costs, that is the
reason why aluminum lines are often used instead of copper, as
aluminum lines weight
less than copper, and are less expensive.
However,copper has a higher current conducting capacity than
aluminum per square mm, so once again the most economical line
design will depend on many factors.
Overhead lines are by nature prone to lightning strikes, causing a
temporary surge on
the line, usually causing flashover between phases or phase to ground.
This is of shortduration, and as soon as it is cleared, normal operation may be
resumed. Auto-reclosers
are employed on an increasing number of overhead lines.
And this table show the main advantages and disadvantages for both
systems as shown in ( table 1)
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 5/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 5
Over head lines Under ground systems
Advantages
Less expensive for longerdistances.
Easy to locate fault.
Advantages
Less expensive for shorterdistances
Not susceptible to lightning
Environment-friendly
Not maintenance intensive
Disadvantages
More expensive for shorter
distances
Susceptible to lightning
Not environment-friendly
Maintenance intensive High level of expertise and
specialized equipment needed for
installation.
Underground (buried) cable
installations are mostly used for
power distribution in industrial
applications.
Disadvantages
Expensive for long distances
Can be difficult to locate
fault.
Table 1
Overhead distribution or transmission becomes difficult in populatedarea like cities
and towns. in such areas necessary to use cable laid below the ground
surface . these
are known as underground cables.
All cables are fundamentally similar in that they contain conductors for
carrying current
, insulation for surrounding the conductors , and some form of covering
to provide
mechanical and possible corrosion protection to ensure that theinsulator may continue
to operate is satisfactorily through the life of the cable once the cable
has been installed.
The primary function of the cable is to carry energy reliably between
source and utilization. In carrying this energy ,there are heat losses
generated in the cable that must
be dissipated. The ability to dissipate these losses depends on how the
cable are
insulated ,and this affects their ratings.
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 6/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 6
The selections of conductor size requires consideration of the load
current to be carried
and the load cycle ,emergency overloading requirements and
duration ,fault clearing
time and interrupting capacity of the cable over current protection orsource capacity,
voltage drop ,d ambient temperatures for particular installation
conditions.
Cable may be installed in cable trays , underground in duct or direct
buried , in cable
bus ,or open runs of the cable.
12.2 cable construction
A typical cable is comprised of
conductors shielded by varioustypes of
material(see Figure 11.2).
Cables may have single core ,two
cores ,three cores
ormore.Cable core is a conductor
surrounded by insulating material which
isolates it from other
cable cores . Single – core cables are
preferred when more flexibility and
installation simplicity are required .
on other hand ,three-core cables are more economical and acquire
better electrical performance in three-phase transmission and
distribution.
11.2.1 Cable conductors:The core conductor is the current carrying conducting material of the
underground
power cable. The two conductor materials in common use are copper
and aluminum.
Copper has historically been used for conductors of insulated cables
primarily for its desirable electrical and mechanical properties. The use
of aluminum is based mainly on its favorable conductivity-to-weight
ratio, its ready availability, and the stable low cost of the primary metal.
Fig 11.2 cable construction
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 7/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 7
11.2.1.1 Comparison Between Copper and Aluminum.
Aluminum requires largerconductor sizes to carry the same current as
copper. The equivalent aluminum cable, whencompared to copper in
terms of ampacity, will be lighter in weight and larger in diameter . To decrease cross-sectional area of extra high voltage cable,
hard drawn copper core
conductors are used (Aluminum conductivity = 60% Copper
conductivity).
The hard drawn copper conductors are preferred in low-voltage
networks, as copper
material can withstand thermal stress during overloading operations
compared with
aluminum conductors.
The hard drawn aluminum conductors are commonly used inmedium-voltage and
high-voltage distribution networks to decrease costs where the three-
phase load
balancing and hence overloading problem is minimized.
12.2.1.2 Classes of Conductors
Conductors are classified as solid or stranded. A solidconductor is a
single conductor of solid circular section. A stranded conductor is
composed of a group of small conductors in common contact.
A stranded conductor is used where the solid conductor is too large
and not flexible enough to be handled readily. Large solid conductors
are also easily damaged by bending. The need for mechanical
flexibility usually determines whether a solid or astranded conductor is
used, and the degree of flexibility is a function of the totalnumber of
strands.
Fig11.3 Coparison between copper and
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 8/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 8
The strands in the stranded conductor are usually arranged in
concentric layers about a central core. The smallest number of wires in
a stranded conductor is three. The next number of strands are 7, 19, 37,
61, 91, 127, etc. Both copper and aluminum conductors may be
stranded as shown in figure 12.3
11.2.2 Cable Insulators:
There are many insulations (or dielectric materials) used in producing
the various
cables to deliver electric power. Cable insulation materials include oil
impregnatedpaper,
rubber , and extruded (or polymeric) insulations.
11.2.2.1 Insulating material should achieve the followingrequirement:
Long life
High dielectric strength
High resistance to corona and ionization
Resistance to high temperatures
Mechanical flexibility
Resistance to humidity
Low insulation losses
It is classified into three main categories:
Natural type :Such as Fabrics – Rubber – Wood – Papers.
Synthetic materials : Such asPolymeric Materials for Insulation
Polymeric insulations (known also as Extruded insulations) are long
chainhydrocarbon thermoplastic materials which are produced by the
polymerization
of petrochemical products like ethylene gas under high pressure
andtemperature. Extruded insulations used for wire and cable are
classified into twomain types:
Figure11.3 Stranded wires core conductors
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 9/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 9
11.2.2.2 Thermoplastic materials
that tend to lose their form upon subsequent heating. Polyethylene (PE)
and Polyvinyl chloride (PVC) are the most common thermoplastic type
extruded insulations.
For the power cable polyvinylchloride (pvc)is the most widely used
thermoplastic
insulation. Polyethylene being used in frequently and then only for high
voltages.
PVC insulating compounds have excellent electrical properties suited
to power cables
used up to including 3.3Kv ,but at higher voltages the material is not
suitable, mainly
because it has a relatively high dielectric constant and dielectric losses
become high.
One electrical characteristics of a PVC which is often not appreciated
in the fact that its
insulation resistance varies quite considerably with temperature .At 70
℃a PVC-insulated cable has an insulation resistance some 700 to1000
times less than the value at20℃.
Being thermoplastic material ,PVC is harder at lower temperatures and
becomes
progressively softer with increasing temperature .The grades of PVC
used for mains cables are designed for conductor continuous
operating temperatures of 70 ℃ and under short-circuit conditions the
conductor temperature should never exceed 1600C ,otherwise the
core insulation would flow and the cable would become permanentlydamaged.
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 10/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 1
11.2.2.3 Thermosetting materials
That tend to maintain their form upon subsequent heating. These
extruded insulations range from Cross linked Polyethylene (XLPE) and
Ethylene-Propylene Rubber (EPR) to the most recent advances in Tree-retardant Cross linked Polyethylene (TR-XLPE).
Almost all XLBE is made from high density polyethylene (HDPE). XLBEcontains
crosslinkedbonds in the polymer structure , changing the thermoplastic
to a thermoset.
Cross-linking is accomplished during or after the extrusion of the tubing.
The required
degree of cross-linking, according to ASTM (American Society for
Testing andMaterials) Standard F 876-93, is between 65 and 89%. A
higher degree of cross-linkingcould result in brittleness and stress
cracking of the material.
The high-temperature properties of the polymer are improved.
Adequate strength to
120-150°C is maintained by reducing the tendency to flow. Chemical
resistance is
enhanced by resisting dissolution. Low temperature properties are
improved. Impact
and tensile strength, scratch resistance, and resistance to brittle
fracture are enhanced.
XLPE-insulated cables have a rated maximum conductor temperature
of 90°C and an
emergency rating up to 140°C, depending on the standard used. They
have a conductor
short-circuit rating of 250°C. XLPE has excellent dielectric properties,
making it useful
for medium voltage - 10 to 50 kV AC - and high voltage cables - up to
380 kV AC voltage,and several hundred kV DC.
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 11/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation
12.2.2.4 comparison the different characteristics of
PVC, XLPE, and EPR
type extruded insulation power cables:
characteristics PVC XLBE
Chemical Structure Thermoplastic Polar Themoset, pure
Hydrocarbon.
Polymer Structure Amorphous Partial Crystalline
Recommended
continuous
working temperature
at
conductor surface in
°c
70 90
Intermittent
temperature
rating during
overloading
in°c
120 130
Maximum
temperature
during short-circuit °c
160 250
Current Carrying
Capacity
___________ 30% Higher than PVC
Dielectric Strength
(KV/mm)
350 550
Low Temperature
Brittleness
Deg. C
-15 -90
Mechanical and
electricalproperties at high
temperature during
overloading and long
shortcircuitperiods
Degraded muchwhen heating over
105 °c
Change slightly as
temperature increasesand does not melt at 105°c
Flexibility Flexible Hard to bend
Application Wiring installation
inside building
Primary feeder in MV
and in HV &EHV
systems
Acid Resistance Fair Excellent
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 12/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 2
In this project
PVC cables is used for low voltage application.
XLPE cables is used for High voltage application.
11.2.3 Shielding of Higher Voltage Cable
For operating voltages below 2 kV, nonshielded constructions are
normally used.
Insulation shielding is required for all nonmetallic, sheathed,single-
conductor cables operating above 2 kV and all metallic sheathed
cables and multiconductor cables
above 5 kV.
11.2.3.1 Procedure
Shielding is the practice of confining the electric field of the cable to
the insulation surrounding the conductor by means of conducting or
semiconducting layers,
closely fitting or bonded to the inner and outer surfaces of the
insulation. In other words, theouter shield confines the electric field to
the space between conductor and shield. The inner or strand stress
relief layer is at or near the conductor potential. The outer or insulationshield is designed to carry the charging currents and in many cases
fault currents.
11.2.3.2 Purpose
Insulation shields have several purposes:
Confine the electric field within the cable.
Equalize voltage stress within the insulation, minimizing surface
discharges.
Protect cable from induced potentials.
Limit electromagnetic or electrostatic interference (radio, TV,etc.).
Reduce shock hazard (when properly grounded).
11.2.4 Metallic Sheaths:
Materials used for cable sheathing are lead layer, aluminum layer or
copper wire.
The main function of it is to provide:
Good method of cable earthing.
Good path to the fault current.
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 13/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 3
12.2.4.1 Lead Sheathing:
Lead is one of the oldest sheathing materials used on power cables,
dating back to the
early 1900s. Use of lead sheaths has proven to be a very effective
moisture barriercontributing to long-term reliability of cable systems.
Disadvantage of lead sheaths is that:
They add a great deal of weight to the cable.
Lead sheaths are prone to deformation under continuous load
conditions due to the
creep characteristics of the material.
Also, lead sheaths are susceptible to failure due to metal fatigue
caused by
mechanical vibration or thermal cycling.
11.2.4.2 Aluminum Sheathing
Aluminum sheathing began to appear in the late 1940s. Aluminum is
attractive because
it is much lighter than lead and has good mechanical properties.
However, extra sheath
losses caused by eddy currents can be generated because Aluminummetal has higher
conductivity compared with lead sheath type.
11.2.5 Armoring:
Armoring is primarily used to protect the cable mechanically and add
strength to the
cable A flat galvanized steel metal tape is helically wrapped around
the cable core. The
tape is typically protected by an outer covering. Applications include
commercial or
industrial installations in conduit, ducts, troughs, and raceways.
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 14/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 4
11.2.5.1 Steel -tape armoring.
the steel tape is provided over the bending and they aren't very
flexible , and their use is limited where the bending of the cables can
not be avoided .
Figure 1
11.2.5.2 wire armoring
It has been found that asingle layer of wire armoring provides abettermechanical protection as against two layer of steel tape
Figure 2
11.2.6 Nonmetallic jackets:
Jackets, also called sheaths, are external covering layers that can
serve several purposes:
They provide mechanical, thermal, chemical and environmental
protection to the
insulated conductors they enclose.
They may act as electrical insulation when used over shields or
armor.
They ease installation and routing concerns by enclosing multipleinsulated
conductors.
They may also protect the characteristics of the underlying
insulation, for example,
a thin nylon jacket over PVC enhances the abrasion and fluid
resistance of a 600v
cable.
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 15/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 5
11.2.7 Bedding
It is an inner sheath of bituminous paper over the lead metal sheath to
provide: Round cross-section-area of cables to take largest volume in
least space area.
Separate the metallic sheath from the armored layer to prevent
galvanic
corrosion.
12.3 Cable selection
When selecting a cable for your specific application, a number ofvariables
require attention. These are:
Application (voltage rating)
Size and type of load to be supplied.
Emergency overload criteria.
Permissible voltage drop.
Prospective fault current.
Circuit protection.
Installation conditions.
11.3.1 Application
The selection of the cable insulation (voltage) rating is based on: the
phase-to-phase voltage of the system in which the cable is to be
applied, the general system category (depending on whether the
system is grounded or ungrounded), and the time in which a ground
fault on the system is cleared by protective equipment.
11.3.1.1 Low-voltage distribution
For LV distribution purposes, the choice is basically between XLPE and
PVC-
insulatedcables. The XLPE cables have higher current ratings than PVC
cables
for the sameconductor size, Normally XLPE cables tend to be slightly
moreexpensive than PVC cables.
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 16/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 6
The choice between these two types for LV applications will normally
be
determined by economic considerations (the relative prices at that
stage)andavailability. Bear in mind that a slightly smaller XLPE cable can be
chosen
for the same current requirement, which have other spin-offs, for
example
space-saving on cable racks or in trenches, slightly reduced labor costs
for installation, etc.
12.3.1.2 Medium-voltage distribution
For MV applications, the choice is more involved. First of all, the choice
lies between
overhead lines and underground cables. Nowadays, the tendency is to
move toward
underground cables for distribution purposes, which stated in the
previous.
where they are very economic compared to underground
cables.overhead lines are
mainlyconsidered for applications over relatively large distances,
where they are very economic compared to underground cables.
The next choice is then between aluminum or copper conductors.
Aluminum
conductors are larger than copper conductors for the same current-
carrying capacity,
which may add to installation costs. The choice will mainly be aneconomic one,
influenced by availability and the relative prices of the two metals at
that stage.
Aluminum conductors may be considered in high corrosive areas.
The third choice is the question of cable insulation type. For normal
distribution
purposes, the choice lies between PVC- or XLPE-insulated cables.
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 17/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 7
11.3.2 Load to be supplied
In order to select the appropriate cable, it is necessary to know the
voltage and the loadcurrent, as the first step in the selection process. The following formulae
apply:
,in case of knowing voltage, and power factor
, in case of knowing the kVA rating and voltage
Use this value of current to determine the cable size by reference to
the relevant
manufacturer’s tables for copper or aluminum conductors.
A slightly larger conductor size may be chosen for safety aspects, and
to provide for the
higher than usual current, which may be according to derating factors
in normal cases.
the starting current of electrical motor should be taken in our
calculation of the cable.
The deratinf factors can be obtained from the tables like in the project
from (ELSEWEDY
Power Cables Catalogue)
Then the manufacturer's ampacity recommendations should be
usedas load current criteria.
Ampacity tables indicate the minimum size conductor required,
however, conservative
engineering practice, future load growth considerations, voltage drop,
and short circuit
considerations may require the use of larger conductors.
IfL = KW× 1000√ 3 × × cos ∅
IfL = KVA× 1000√ 3 ×
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 18/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 8
11.3.3 Standard Cable Installation Conditions
Standard installation conditions for cables that are installed in free air
includes:
Ambient air temperature is 25 ℃ for transmission and distribution
cables, 30 ℃
forindoor wiring and 35 ℃ for wiring installations in ships.
Minimum distance between cable and wall is 20 mm.
Minimum distance between the cable and neighboring one is
150 cm.
Cable is isolated from direct sun rays.
While the standard installation conditions for cables that are directly
buried in ground
includes:
Soil temperature is 15℃
Thermal resistivity of soil is 1.2 ℃m/W.
Minimum distance between the cable and neighboring one is
1.8 m.
Buried depth is 0.5 m for 1-kV cables and 0.8 m for cables higher
than 1kV.
12.3.4 Emergency overload criteria
Normal loading limits of insulated wire and cable are determined
based on many years of practical experience. These limits account for
a rate of insulation deterioration that results in the most economical
and useful life of such cable systems.
The anticipated rate of deterioration equates to a useful life of
approximately 20 to 30 years. The life of cable insulation may be
halved, and the average thermal failure rate almost doubled for each
5 to 15 ℃increase in normal daily load temperature.
The normal daily load temperature is the average conductor
temperature over a typical 24 hour period. It reflects both the change
in ambient temperature and the change in conductor temperature
due to daily load fluctuations.
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 19/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 9
Additionally, sustained operation over and above maximum rated
operating temperatures or ampacities is not an effective or
economical practice, because the temperature rise is directly
proportional to the conductor loss, which increases as the square of
the current. The intensified voltage drop may also increase the risks toequipment and service continuity.
Maximumemergency overload temperatures for various types of
insulation have been established and are available as a practical
guide. Operation at these emergency overload temperatures should
not exceed 100 hours per year, and such 100 hour overload periods
should not exceed five during the life of the cable.
11.3.5 Permissible voltage drop:
The supply conductor, if not of sufficient size, will cause excessive
voltage drop in the circuit, and the drop will be in direct proportion to
the circuit length. Proper starting and running of motors, lighting
equipment, and other loads having heavy inrush currents must be
considered. It is recommended that the steady state voltage drop in
distribution feeders be no more than Five percent (5%)
And it will be stated in this chapter in details.
11.3.6 Cable Short Circuit Capacity :
The wiring design and installation of cable circuits requires an
adequate selection of the
nominal cross-sectional area based on:
Continuous current loading under practical installation
conditions of cable circuits.
Cable short-circuit capacity at duration starts from short-circuit
instant untilcomplete interruption by automatic circuit-breakers.
Under short-circuit conditions the temperature of the conductor rises
rapidly then, due to the thermal characteristics of the insulation,
sheath, and surrounding materials, it cools off slowly after the short-
circuit condition is cleared.
A transient temperature limit for each type of insulation for short-circuit
durations not in excess of 10 seconds has been established, and many
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 20/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 21
times this criterion is used to determine minimum conductor size.
Insulated Power Cable Engineers Association (IPCEA) standards define
the maximum conductor temperature limits allowable under worst-
case fault conditions.
Cable insulations among other cable layers that are affected much
with heat dissipationduring short-circuit, where the maximum
recommended temperature
θmax not toexceed 160 ℃ for PVC-insulation and 2500C for XLPE-
insulation
The maximum short-circuit current period (T) in seconds changes in an
inverse
relationship to the cable r.m.s short circuit capacity (Isc) in amperes as
shown in the
following formula:
S: is the normal cross-section area of core conductor in
mm
θ: is the recommended cable temperature for continuous operation
(70℃ for
PVC insulation, and 90℃ for XLPE-insulation
α, β:are constants depending upon materials of core conductor and
metallic sheath layer
(as indicated in the next )
T:Clearing time in (sec) It is recommended to select an adequate
nominal cross-sectionalarea of core conductor to carry short-circuit current less than short-
circuit current
capacity during 1 or 3 seconds standard interrupting duration
Material
Copper 256 234.5
Aluminum 148 228
Isc = αsT × l n (θmax+β
θo + β )
Diffirent values of ,
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 21/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 2
11.4 Classification of cables according to voltage
Cables are usually classified according to their operating voltage as
follows:
Low voltage cables (up to 1kv).
Figure 3
Medium voltage cables (3KV to 30KV)
Figure 4
High voltage cables(30KV to 500KV)
Figure 5
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 22/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 22
12.4.1 Low Voltage CablesThe following tables is up to(0.6/1KV)
300/500 V & 450/750 V
Figure 5
300/500 V & 450/750 V
Figure 6
300/500 V
Figure 7
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 23/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 23
0.6/1 (1.2) kV
Figure 8
0.6/1 (1.2) kV
Figure 9
0.6/1 (1.2) kV
Figure 10
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 24/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 24
0.6/1 (1.2) kV
Figure 11
0.6/1 (1.2) kV
Figure 12
0.6/1 (1.2) kV
Figure 13
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 25/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 25
0.6/1 (1.2) kV
Figure 14
0.6/1 (1.2) kV
Figure 15
0.6/1 (1.2) kV
Figure 16
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 26/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 26
0.6/1 (1.2) kV
Figure 17
0.6/1 (1.2) kV
Figure 18
0.6/1 (1.2) kV
Figure 19
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 27/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 27
11.4.2 Medium Voltage Cablesoperating voltage from 6/10 kV up to 18/30 Kv
6/10 (12) kV
Figure 20
6/10 (12) kV
Figure 21
6/10 (12) kV
Figure 22
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 28/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 28
6/10 (12) kV
Figure 23
8.5/15 (17.5) kV
Figure 24
8.5/15 (17.5) kV
Figure 25
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 29/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 29
38/66 (72.5) kV
Figure62
38/66 (72.5) kV
Figure 27
11.5 Determination of cable faults:
11.5.1 Reasons of cable faults :
mechanical factors.
Electrochemical factors.
bad industry.
bad burial, elongation and tide.
bad welding.
bad loading.
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 30/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 31
11.5.2 Types of faults:
single line to ground fault.
Double line to ground fault.
Three phase to ground fault.
Phase to phase fault.
Three phase fault.
11.5.3 Method of fault determination:
1) High voltage test (high voltage with small current).
2) Burning of fault location on the cable (high current with low
voltage).
3) Determine of fault location.
11.5.3.1the high voltage test:
First the faulted cable should be disconnected from starting
terminal and from endingterminal.
this cable is tested to determine the quality of insulation.
Rules of this test:
a)
inject each phase with voltage equal to three times the
operating voltage of the
cable (this voltage around 35KV for the new 11KV cable and 33KV for
the old 11KV
cable)
b) the second test in case of old cables it will be two times the
operating voltage
(25Kv for 11Kv cable).
c) each phase tested for 15 minutes.
d)
if the cable is good ,it will withstand the tested voltage.
e) it is not allowable to leak more than 150 micro ampere foe each
1 K.M from the
length of the cable .if the leakage current more than 150 micro
ampere ,that’s a
good indication that there is a fault.the values of leakage currents in
each phase
should be close to each other.
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 31/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 3
11.5.3.2 burning the fault location:
Inject the cable with high current and low voltage to burn the fault
location.
11.5.3.3 determination of the fault location:
The distance= speed(V)×time (t)
Distance of fault=×
11.6 Precautions burial of the cable:
it must be the shortest path and has low curvature.
Far from the paths of modern tree planting paths.
Far from the paths of public services.
Far from the ground which has high level from salts and acids, if it
is important
to follow through them. it should be put on special pipes against them.
Far from the paths of electrical trains and if it is important, it
should be made
earthed for the cable with the earthed bars.
Far from the paths of trains to avoid shakings and if it is important,
the cable should
be put in pipe makes from galvanized steel or from PVC .
11.6.1 Cable trenches:
There are different methods for laying depended on cable type, cable
importance & soil
surrounding cable. Such as:
Cables laid in ducts: this method for vital cable and for crossing
ways. Man holes aremade to maintain & repair the cable easily when a fault occurs.
Metallic shield: it
used when the cable is near to railways or duct of pipe lines to prevent
galvanic
corrosion.
Conduits (pipes) which used for buildings (walls & ceilings).
The cables laid in bitumen compound. This method is used where
the soil is
chemically corrosive to the cable.
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 32/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 32
11.6.2 Rules for burring of cable trenches:
The burial depth not less than 70Cm.
A layer of sands should be put with 10cm then put the cable on it
directly. Again put a layer of sand on the cable until reaches to 20cm
from burial depth.
Put bricks along the path of the cable as guidelines.
Put the original soil which is extracted during the process of burial
until reaches to
20cm from the edge of the hole and put warning strip at this deep then
make the
process of asphalt for the street.
Important note:
In the project, the cables not direct buried into soil but the cable are
put in the ducts.
Figure 28
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 33/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 33
12.7 cable selection for the project
The Diversty factor of different places in the village used to determining
the rating current is placed in the following table
1-Transformer 1 region cable selection:
Place
Lighting sockets
mosque 1 0.3
Food court 1 1
Hotel 0.5 0.6
Mall 0.7 0.3
administration building 0.7 0.5
chalet 0.5 0.8
cinema 0.2 0.3
Diversty factor
Location Ratedcurrent(A)
Cablecurrent(A)
Cable Type No ofcables
Corresponding
CSA( mm)
Bus way to GRD
Floor panel board
35.89 44.86 Multicore cables,stranded Copper
Conductors PVC Insulated PVC
sheathed laid in duct
1 (3× 1 0 +10)+10
Bus way to Floor 1
panel board
10.44 13.05 Multicore cables,stranded Copper
Conductors PVC Insulated PVC
sheathed laid in duct
1 (3× 1.5 + 1.5)
+1.5
Bus way to Floor 2
panel board
10.44 13.05 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1.5 + 1.5)
+1.5
Bus way to Floor 3
panel board
10.44 13.05 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1.5 + 1.5)
+1.5
Bus way to Floor 4
panel board
10.44 13.05 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1.5 + 1.5)
+1.5
Bus way to Floor 5
panel board
10.44 13.05 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1.5 + 1.5)
+1.5
Bus way to Floor 6
panel board
10.44 13.05 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1.5 + 1.5)
+1.5
Bus way to Floor 7panel board
10.44 13.05 Multicore cables,stranded CopperConductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1.5 + 1.5)+1.5
Bus way to Floor 8
panel board
10.44 13.05 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1.5 + 1.5)
+1.5
Bus way to Floor 9
panel board
10.44 13.05 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1.5 + 1.5)
+1.5
Bus way to Floor
10 panel board
10.44 13.05 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1.5 + 1.5)
+1.5
Bus way to Floor
11 panel board
10.44 13.05 Multicore cables,stranded Copper
Conductors PVC InsulatedPVCsheathed laid in duct
1 (3× 1.5 + 1.5)
+1.5
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 34/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 34
Bus way to Floor
12 panel board
30.77 38.46 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1 0 +10)+10
Bus way to Floor
13 panel board
78.8 98.5 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 5 0 +25)+25
Bus way to Floor14 panel board
35.78 44.73 Multicore cables,stranded CopperConductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1 0 +10)+10
Bus way to Floor
15 panel board
35.78 44.73 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1 0 +10)+10
Bus way to Floor
16 panel board
45 56.25 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1 0 +10)+10
Bus way to Floor
17 panel board
34.44 43.05 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1 6 +16)+10
Bus way to Floor
18 panel board
39.76 49.7 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1 6 +16)+10
Bus way to Chiller
1
337 421.25 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
2 (3× 1 5 0 + 7 0)
+70
Bus way to Chiller
2
337 421.25 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
2 (3× 1 5 0 + 7 0)
+70
Bus way to Chiller
3
337 421.25 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
2 (3× 1 5 0 + 7 0)
+70
Bus way to Chiller
4
337 421.25 Multicore cables,stranded Copper
Conductors PVC InsulatedPVCsheathed laid in duct
2 (3× 1 5 0 + 7 0)
+70
SDB to Elevator
odd doors
21.25 26.56 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 4 + 4)+4
SDB to Elevator
even doors
21.25 26.56 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 4 + 4)+4
SDB to Service
lighting
40 50 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1 6 +10)+10
SDB to Water
Pump
25.5 31.87 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1 0 +10)+10
SDB to Elevator
goods
46 57.5 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1 6 +16)+10
MDB to Bus way 1763.28 2204 Multicore cables,stranded CopperConductors PVC Insulated
PVCsheathed laid in duct
4 (3× 1 × 240
+120) +120
MDB to SDB 154 192.5 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 9 5 +50)+50
Transformer1 to
MDB
1917.28 2396.6 singlecorecables,stranded Copper
Conductors XLPE InsulatedPVCsheathed laid in duct
4 (3× 1 × 300
+150)+150
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 35/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 35
2-Transformer 2 region cable selection:
Location Rated
current(A)
Cable
current(A)
Cable Type No of
cables
Corres
ponding CSA
( mm)
Bus way to Floor 19
panel board
16.18 20.23 Multicore cables,stranded Copper
Conductors PVC Insulated PVC
sheathed laid in duct
1 (3× 2.5 + 2.5)
+2.5
Bus way to Floor 20panel board
37.9 47.38 Multicore cables,stranded CopperConductors PVC Insulated PVC
sheathed laid in duct
1 (3× 16 + 16)+10
Bus way to Floor 21
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 22
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 23
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 24
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 25
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 26
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 27
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 36/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 36
Bus way to Floor 28
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 29
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 30
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 31
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 32
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC InsulatedPVCsheathed laid in duct
1 (3
× 16 + 16)
+10
Bus way to Floor 33
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 34
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 35
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 36
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 37
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 38
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 39
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 37/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 37
Bus way to Floor 40
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 41
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 42
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 43
panel board
37.9 47.38 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)
+10
Bus way to Floor 44panel board
37.9 47.38 Multicore cables,stranded CopperConductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)+10
Bus way to Chiller 1 337 421.25 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
2 (3× 150 +70)
+70
Bus way to Chiller 2 337 421.25 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
2 (3× 150 +70)
+70
Bus way to Chiller 3 337 421.25 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
2 (3× 150 +70)
+70
Bus way to Chiller 4 337 421.25 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
2 (3× 150 +70)
+70
Water Pump 25.5 31.87 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 10 +10)+10
Service lighting 40 50 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 +10)+10
MDB to Bus way 2273.78 2842.23 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
5 (3× 1 +300)
+300
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 38/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 38
3-Transformer 3 region cable selection:
MDB to SDB 65.5 81.87 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 50 + 25)
+25
Transformer 2 to
MDB
2339.28 2924 singlecorecables,stranded Copper
Conductors XLPE Insulated
PVCsheathed laid in duct
5 (3× 1 × 300 +
150)+150
Location Rated
current(A)
Cable
current(A)
Cable Type No of
cables
Corres ponding
CSA ( mm)
MDB to Mosque
panel board
60.93 76.16 Multicore cables,stranded Copper
Conductors PVC Insulated PVC
sheathed laid in duct
1 (3× 25 + 25)+10
SDB 3 to GND floor
right panel board
151.24 189.05 Multicore cables,stranded Copper
Conductors PVC Insulated PVC
sheathed laid in duct
1 (3× 35 + 16)+16
SDB 3 to First floor
right panel board
32.1 40.13 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 2.5 +2.5)
+2.5
SDB4 to Chiller 1
Mall
354 442.5 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
2 (3× 1 8 5 + 9 5)
+95
SDB 4 to Chiller 2
Mall
354 442.5 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
2 (3× 1 8 5 + 9 5)
+95
SDB 2 to Cinema
chiller
101 126.25 Multicore cables,stranded Copper
Conductors PVC InsulatedPVCsheathed laid in duct
1 (3
× 50 + 25)
+25
SDB2 to Cinema
panel board
40.76 50.95 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 6 + 6)+6
SDB4 to Elevator
1
21.25 26.56 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 4 + 4)+4
SDB4 to Elevator
2
21.25 26.56 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 4 + 4)+4
SDB4 to Elevator
goods
46 57.5 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 16 + 16)+10
SDB4 to Water
pump
25.5 31.875 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 10 + 10)+10
MDB to SDB1 114 142.5 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3×150+150)
+70
MDB to SDB2 141.76 177.2 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1 2 0 + 7 0)
+70
MDB to SDB3 183.34 229.18 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 70 + 35)
+35
MDB to SDB4 354 442.5 Multicore cables,stranded CopperConductors PVC Insulated
PVCsheathed laid in duct
3 (3×300+150)+150
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 39/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 39
4-Transformer 4 region cable selection:
Transformer 3 to
MDB
854.03 1067.53 singlecorecables,stranded Copper
Conductors XLPE Insulated
PVCsheathed laid in duct
3 (3× 1 × 300 +150)+150
Location Rated
current(A)
Cable
current(A)
Cable Type No of
cables
Corres
ponding CSA
( mm)
Sub1 to Chalets 1:4
panel board
112.84 141.05 Multicore cables,stranded Copper
Conductors PVC Insulated PVC
sheathed laid in duct
1 (3× 5 0 +25)+25
Sub1 to Chalets 5:8
panel board
112.84 141.05 Multicore cables,stranded Copper
Conductors PVC Insulated PVC
sheathed laid in duct
1 (3× 5 0 +25)+25
Sub2 to Chalets
9:13 panel board
141.05 176.31 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3×120+70)
+70
Sub2 to Chalets
14:18 panel board
141.05 176.31 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3
×120+70)
+70
Sub3 to Chalets
19:23 panel board
141.05 176.31 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3×120+70)
+70
Sub3 to Chalets
24:28 panel board
141.05 176.31 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3×120+70)
+70
Sub4 to Chalets
29:33 panel board
141.05 176.31 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3×120+70)
+70
Sub4 to Chalets
34:38 panel board
141.05 176.31 Multicore cables,stranded Copper
Conductors PVC InsulatedPVCsheathed laid in duct
1 (3×120+70)
+70
GF2 Mall Panel
board to GF 2.1
panel board
34.5 43.13 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 10 + 10)
+10
GF2 Mall Panel
board to GF 2.2
panel board
32.6 40.75 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 10 + 10)
+10
GF2 Mall Panel
board to GF 2.3
panel board
33.4 41.75 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 10 + 10)
+10
Chillers to Chiller 1 294 367.5 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
2 (3×120+70)
+70
Chillers to Chiller 2 294 367.5 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
2 (3×120+70)
+70
Service panel to
Water Pump
22.6 28.25 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 4 + 4)+4
Elevator 1,2 Panel
board to Elevator 1
21.2 26.5 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 4 + 4)+4
Elevator 1,2 Panel
board to Elevator 2
21.2 26.5 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 4 + 4)+4
Service Panel toElevator 1,2 Panel
board
42.4 53 Multicore cables,stranded CopperConductors PVC Insulated
PVCsheathed laid in duct
1 (3× 1 0 +10)+10
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 40/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 41
5-Transformer 5 region cable selection:
Location Rated
current(A)
Cable
current(A)
Cable Type No of
cables
Corres ponding
CSA ( mm)
SDB1 to Foad court
panel board
55 68.75 Multicore cables,stranded Copper
Conductors PVC Insulated PVC
sheathed laid in duct
1 (3× 25 + 25)+10
sevice panel to Foad
court elevator
21.19 26.49 Multicore cables,stranded Copper
Conductors PVC Insulated PVC
sheathed laid in duct
1 (3× 4 + 4)+4
sevice panel to Foad
court water Pumps
16.95 21.19 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
1 (3× 4 + 4)+4
Escalator 1,2 Panel
board to Elevator 1
14.2 17.75 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 2.5 + 2.5)
+2.5
Escalator 1,2 Panel
board to Elevator 1
14.2 17.75 Multicore cables,stranded Copper
Conductors PVC InsulatedPVCsheathed laid in duct
1 (3× 2.5 + 2.5)
+2.5
Service Panel to
Escalator 1,2 Panel
board
28.4 35.5 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 6 + 6)+6
SDB1 to SUB1 225.68 282.1 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
2 (3× 70 + 35)
+35
SDB1 to SUB2 282.1 352.63 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
2 (3×120+70)
+70
SDB1 to SUB3 282.1 352.63 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
2 (3×120+70)
+70
SDB1to SUB4 282.1 352.63 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
2 (3×120+70)
+70
SDB2 to GF2 Mall
Panel board
100.5 125.63 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 70 + 35)
+35
SDB2 to chiller 1,2
panel board
588 735 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
4 (3×120+70)
+70
SDB2 to Service
Service board
93.4 116.75 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
1 (3× 3 5 +16)+16
SDB2 to Mall
second floor 3panel board
60.39 75.49 Multicore cables,stranded Copper
Conductors PVC InsulatedPVCsheathed laid in duct
1 (3
× 2 5 +25)+10
MDB to SDB1 842.29 1052.86 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
6 (3×185+95)
+95
MDB to SDB2 1071.98 1340 Multicore cables,stranded Copper
Conductors PVC Insulated
PVCsheathed laid in duct
4 (3×240+120)
+120
Transformer 4 to
MDB
2143.96 2679.95 singlecorecables,stranded Copper
Conductors XLPE Insulated
PVCsheathed laid in duct
6 (3× 1 × 240 +1×240
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 41/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 4
laid in duct
SDB1 to Foad court
chiller 1
101 126.25 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 70 + 35)
+35
GF 4 Mall Panel
board to GF4.1 Panel
board
39.5 49.38 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 10 + 10)+10
GF 4 Mall Panel
board to GF4.2 Panel
board
31 38.75 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 10 + 10)+10
GF 4 Mall Panel
board to GF4.3 Panel
board
24.8 31 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 6 + 6)+6
SDB2 to Mall GF4
water Pumps
22.6 28.25 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 4 + 4)+4
SDB2 to Chiller 2 294 367.5 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
2 (3×120+70)
+70
SDB3 to Mall GF5Panel board 22.6 28.25 Multicore cables,stranded CopperConductors PVC Insulated PVCsheathed
laid in duct
1 (3× 4 + 4)+4
SDB3 to Chiller 3 294 367.5 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
2 (3×120+70)
+70
Mall GF5 Escalator
1,2 board to
Escalator 1
14.13 17.66 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 5 0 +2.5)+2.5
Mall GF5 Escalator
1,2 board to Mall
GF5 Escalator 2
14.13 17.66 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 5 0 +2.5)+2.5
Mall GF5 Escalator
1,2 board
28.26 35.33 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 6 + 6)+6
GF5 Mallsevicepanel board
to water Pumps
16.95 21.19 Multicore cables,stranded CopperConductors PVC Insulated PVCsheathed
laid in duct
1 (3× 4 + 4)+4
SDB1 to Food
coartsevice panel
board
38.85 48.56 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 16 + 16)+16
SDB2 to GF4 Mall
panel board
95.3 119.13 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 70 + 35)
+35
SDB3 to GF5 Mall
sevicepanel board
45.2 56.5 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 16 + 16)+16
MDB to SDB1 194.85 243.56 Multicore cables,stranded CopperConductors PVC Insulated PVCsheathed
laid in duct
2 (3× 70 + 35)+35
MDB to SDB2 411.9 514.87 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
3 (3×120+70)
+70
MDB to SDB3 361.8 452.25 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
3 (3× 70 + 35)
+35
Transformer 5 to MDB 968.55 1210.69 singlecorecables,stranded Copper
Conductors XLPE Insulated PVCsheathed
laid in duct
1 (3× 1 × 240 +1 × 2 4 0)+ 1 ×240
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 42/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 42
6-Transformer 6 region cable selection:
Location Ratedcurrent(A)
Cablecurrent(A)
Cable Type No ofcables
Corres pondingCSA ( mm)
Mall GF1 , Floor 2 to
GF1.1 Panel board
34.5 43.125 Multicore cables,stranded Copper
Conductors PVC Insulated PVC sheathed
laid in duct
1 (3× 10 + 10)+10
Mall GF1 , Floor 2 to
GF1.2 Panel board
32.6 40.75 Multicore cables,stranded Copper
Conductors PVC Insulated PVC sheathed
laid in duct
1 (3× 10 + 10)+10
Mall GF1 , Floor 2 to
GF1.3 Panel board
33.4 41.75 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 10 + 10)+10
Mall GF1 , Floor 2 to
Floor 2 Panel board
30.3 37.87 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 10 + 10)+10
chillers 1 to Chiller 1 194 242.5 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 1 8 5 + 9 5)
+95
chillers 1 to Chiller 2 194 242.5 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 1 8 5 + 9 5)
+95
Water Pump mall to
Water Pumps
45.2 56.5 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 16 + 16)+10
Escalator1,Escalator2
to Panel board
Escalator1
14.2 17.75 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 1.5 + 1.5)
+1.5
Escalator1,Escalator2
to Panel Escalator2
14.2 17.75 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 1.5 + 1.5)
+1.5
Elevator1, Elevator2 to
Panel board Elevator
1
21.2 26.5 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 4 + 4)+4
Elevator1, Elevator2 to
Panel board Elevator
2
21.2 26.5 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 4 + 4)+4
Admin1,Admin2
Panel boards to
Admin 1 building
Panel board
33.7 42.13 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 10 + 10)+10
Admin1,Admin2Panel boards to
Admin 2 building
Panel board
26.2 32.75 Multicore cables,stranded CopperConductors PVC Insulated PVCsheathed
laid in duct
1 (3× 6 + 6)+6
Chillers 2 to Admin
Chiller 1
115 143.75 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 70 + 35)
+35
Chillers 2 to Admin
Chiller 2
115 143.75 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 70 + 35)
+35
water pump admin
to Water pumps
22.6 28.25 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 4 + 4)+4
SDB1 to Mall GF1,Floor 2
130.8 163.5 Multicore cables,stranded CopperConductors PVC Insulated PVCsheathed
laid in duct
1 (3× 95 + 50)+50
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 43/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 43
12.8 Voltage drop:
Voltage drop is a term used to describe any reduction in the supplyvoltage in a complete electrical circuit. The term may be used to
describe a voltage loss across aspecific component in the circuit, the
voltage loss measured across the entire circuit, or as
a broad description of the phenomenon of voltage loss in a circuit in
general.
All electrical circuits, no matter how simple, present a certain amount
of resistance to the
flow of electrical current through them. This resistance effectivelymakes the electrical
SDB1 to chillers 1 338 422.2 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
2 (3× 1 8 5 + 9 5)
+95
SDB1 to Water Pump
mall
45.2 56.5 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathedlaid in duct
1 (3× 16 + 16)+10
SDB1 to
Escalator1,Escalator2
Panel board
28.4 35.5 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 6 + 6)+6
SDB1 to Elevator1,
Elevator2
Panel board
42.4 53 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 16 + 16)+10
SDB2 to
Admin1,Admin2
Panel boards
59.9 74.87 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 25 + 25)+25
SDB2 to Chillers 2 230 287.5 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3×240+120)
+120
SDB2 to water pump
admin
22.6 28.25 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
1 (3× 6 + 6)+6
MDB to SDB1 634.8 793.5 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
3 (3×240+120)
+120
MDB to SDB2 312.5 390.63 Multicore cables,stranded Copper
Conductors PVC Insulated PVCsheathed
laid in duct
2 (3× 1 2 0 + 7 0)
+70
Transformer 6 to MDB 947.3 1184.13 singlecorecables,stranded Copper
Conductors XLPE Insulated PVCsheathed
laid in duct
1 (3× 1 × 1000+1 × 5 0 0)+ 1 ×500
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 44/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 44
current work harder, and thus absorbs energy. This expenditure of
energy is what causes
the reduction in voltage described by the term voltage drop.
For example, a simple circuit can be made up of a 9-volt battery
attached to a simple
flash light bulb with a small switch. If one were to measure the voltage
across the
batteries terminals with the switch open, the multimeter reading would
be
approximately 9 volts. If one were to close the switch and illuminate the
bulb, that
reading would drop by approximately 1.5 volts. That reduction in
voltage is what is
known as a voltage drop, and it comes about as the result of the work
the battery has to
do to illuminate the bulb. Each and every component in a circuit,
including the wiring,
offers a certain amount of resistance to the flow of electrical current
and will cause an
associated voltage drop.
In applications that are extremely supply voltage sensitive, such as
electronic devices,
these voltage losses have to be carefully calculated and the supply
voltage adjusted to
make provision for them. A 12 volt direct current (DC) power supply, for
instance, will
typically produce an output of 13.8 volts to accommodate.
this voltage drop phenomenon. In applications that require very long
cable runs, it is
common practice to uses fairly heavy cables that present less
resistance to the flow of
electric current in an attempt to minimize the effects of voltage losses.
The total
potential loss of voltage in any circuit thus needs to be carefully
calculated during the
design and specification phase of a project to ensure that the finalresult meets all
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 45/46
Chapter 11 Power Cables
Touristic Village with Renewable Energy Generation 45
requirements.
11.8.1 Permissible voltage drop
Calculate the volt drop that will be experienced at the load terminals.
The maximumvolt drop allowed by the Australian Standard for Electrical Installations
(Standard AS
3000; known as the SAA Wiring Rules) is 5%.
11.8.2 The volt drop may be calculated in two different ways:
Multiplying the current by the impedance of the length of cable.
Calculate the
percentage volt drop by reference to the phase-to-earth voltage.
Multiply the current by the length of cable, and then multiply the
result by the volt
drop per amp per meter
12.8.3 Checking for volt drop:
From the previous law as the current increase the impedance increase
and the voltage drop
increase.
11.8.4 In case of low voltage:
The current will be high because the voltage is low compared with high
voltage ,forsame power so the voltage drop will be high . If the voltage drop
exceeded certain limit
(5%) according to IEC standard ,the cable size should be increased to
decrease the overall
resistance hence decrease the voltage drop .which mean you pay
more money.
11.8.5 In case of high voltage:
Vdrop =√ ×Z ××dite
7/23/2019 Chapter 11 Power Cables
http://slidepdf.com/reader/full/chapter-11-power-cables 46/46
Chapter 11 Power Cables
The current will be smaller than it in case of low voltage for the same
power transmitted
,so the voltage drop will be small ,so we volt drop seldom be a problem
a higher voltage
11.8.6 Voltage drop calculation calculated in the project
From TO Rated Current(A) Length mv/Amp/meter Voltage Drop (VD) VD %
Transformer 3 Mosque 61.2 40 1.28 3.13344 0.824589
Transformer 5 Food Court 55 85 1.28 5.984 1.574737
Transformer 6 Adminstration building 26 40 5.199 5.40696 1.422884
Transformer 3 Cinema 28 40 5.199 5.82288 1.532337
Transformer 1 Ground of hotel 36 40 3.101 4.46544 1.175116
Transformer 2 Level 19 of hotel 17.5 19 7.741 2.5738825 0.677338
SDB 1(chalets 1:8) 225.68 40 0.244 2.2026368 0.57964
SDB 2(chalets 9:18) 282.1 80 0.18 4.06224 1.06901SDB 3(chalets 19:28) 282.1 120 0.18 6.09336 1.60352SDB 4(chalets 29:38 ) 282.1 160 0.18 8.12448 2.13802
chalets 1:4 28.21 10 5.199 1.4666379 0.38596chalets 5:8 28.21 40 5.199 5.8665516 1.54383
chalets 9:13 28.21 10 5.199 1.4666379 0.38596chalets 14:18 28.21 40 5.199 5.8665516 1.54383chalets 19:23 28.21 10 5.199 1.4666379 0.38596
chalets 24:28 28.21 40 5.199 5.8665516 1.54383chalets 29:33 28.21 10 5.199 1.4666379 0.38596
chalets 34:38 28.21 40 5.199 5.8665516 1.54383
Trans 4(MDB 1)
SDB 1
SDB 2
SDB 3
SDB 4