This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE OF APPROVAL No CF 5243
This is to certify that, in accordance with
TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of
JOTUN A/S
P.O. Box 2021, N-3202 Sandefjord, Norway Tel : + 47 33 45 7000 Fax: + 47 33 45 7242
Have been assessed against the requirements of the Technical Schedule(s)
denoted below and are approved for use subject to the conditions appended hereto:
______________________________________________________________________________
CERTIFIED PRODUCT TECHNICAL SCHEDULE
Steelmaster 1200WF TS 15 INTUMESCENT COATINGS FOR STEELWORK
Signed and sealed for and on behalf of CERTIFIRE
Sir Ken Knight Issued: 13th May 2014
Chairman - Management Council Revised: 25th July 2014
Page 1 of 31 Valid to: 12th May 2019
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 2 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF 1. This approval relates to the use of Steelmaster 1200WF for the fire protection of
I-shaped and hollow steel sections. The precise scope is given in Tables 1 to 20 which show the total dry film thickness of Steelmaster 1200WF (excluding primer and topcoat) required to provide fire resistance periods in accordance with BS476: Part 21: 1987 of 30 minutes up to 180 minutes for differing sections and section factors.
2. This certification is designed to demonstrate compliance of the product or system
specifically with Approved Document B (England and Wales), Section 2 of the Technical Standards (Scotland), Technical Booklet E (N. Ireland). If compliance is required to other regulatory or guidance documents there may be additional considerations or conflict to be taken into account.’
3. The products are approved on the basis of:
i) Initial type testing. ii) A design appraisal against TS15. iii) Certification of quality management system to ISO 9001: 2008.
iv) Inspection and surveillance of factory production control v) Audit testing
4. The data referring to three-sided fire exposure of beams relate to beams supporting
concrete floor slabs. Separate consideration is required where this is not the case. 5. The data shown is applicable to steel sections blast cleaned to Swedish Standard SA2.5
or equivalent and primed with a suitable and compatible primer. Specifications of surface preparations, primers and topcoats is available from Jotun Paints whose responsibility is to ensure that Steelmaster 1200WF is compatible for use in respect of both ambient and fire conditions. The total dry film thickness of primer and topcoat should not exceed that tested.
6. The data shown is applicable to Steelmaster 1200WF applied by spray to horizontal,
vertical, flexural and compression members supporting loads up to the maximum design loads specified in BS449: Part 2.
7. The approval relates to ongoing production. Product and/or its immediate packaging is
identified with the manufacturers’ name, the product name or number, the CERTIFIRE name or name and mark, together with the CERTIFIRE certificate number and application where appropriate.
8. The data shown in the tables is based on assessments which comply with the criteria for
acceptability now incorporated within the CERTIFIRE scheme.
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 3 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results also apply to I section beams with 4 sides fire exposure subject to a maximum DFT of 4.455mm.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
30 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
35 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
40 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
45 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
50 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
55 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
60 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
65 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
70 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
75 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
80 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
85 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
90 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
95 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
100 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
105 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
110 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
115 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
120 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
125 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
130 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
135 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
140 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
145 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
150 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
155 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
160 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
165 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
170 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
175 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
180 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
185 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
190 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
195 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
200 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
Table 1: I-Section Columns 30 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 4 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results also apply to I section beams with 4 sides fire exposure subject to a maximum DFT of 4.455mm.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
205 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
210 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
215 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
220 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
225 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
230 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
235 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
240 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
245 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
250 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
255 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
260 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
265 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
270 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
275 0.926 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
280 0.951 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
285 0.976 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
290 1.001 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
295 1.026 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
300 1.051 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
305 1.076 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
310 1.101 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
315 1.126 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
320 1.151 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
325 1.176 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
330 1.201 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
335 1.226 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
340 1.251 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
345 1.277 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
350 1.302 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
355 1.327 0.917 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
360 1.352 0.941 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
365 1.377 0.964 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
370 1.402 0.987 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
375 1.427 1.010 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
380 1.452 1.033 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
385 1.477 1.057 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
390 1.502 1.080 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
Thickness (mm) Required for a Design Temperature of
Table 1(Continued): I-Section Columns 30 Minutes
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 5 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results also apply to I section beams with 4 sides fire exposure subject to a maximum DFT of 4.455mm.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
30 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
35 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
40 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
45 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
50 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
55 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
60 0.927 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
65 0.970 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
70 1.013 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
75 1.056 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
80 1.099 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
85 1.142 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
90 1.185 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
95 1.228 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
100 1.271 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
105 1.314 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
110 1.357 0.912 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
115 1.400 0.949 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
120 1.443 0.986 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
125 1.486 1.023 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
130 1.529 1.060 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
135 1.571 1.097 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
140 1.614 1.134 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
145 1.657 1.171 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
150 1.700 1.208 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
155 1.743 1.245 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
160 1.786 1.282 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
165 1.829 1.319 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
170 1.872 1.356 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
175 1.915 1.393 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
180 1.958 1.430 0.939 0.911 0.911 0.911 0.911 0.911 0.911 0.911
185 2.001 1.467 0.977 0.911 0.911 0.911 0.911 0.911 0.911 0.911
190 2.044 1.504 1.016 0.911 0.911 0.911 0.911 0.911 0.911 0.911
195 2.087 1.541 1.054 0.911 0.911 0.911 0.911 0.911 0.911 0.911
200 2.130 1.578 1.092 0.911 0.911 0.911 0.911 0.911 0.911 0.911
Table 2: I-Section Columns 60 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 6 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results also apply to I section beams with 4 sides fire exposure subject to a maximum DFT of 4.455mm.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
205 2.173 1.615 1.130 0.911 0.911 0.911 0.911 0.911 0.911 0.911
210 2.216 1.652 1.169 0.911 0.911 0.911 0.911 0.911 0.911 0.911
215 2.259 1.689 1.207 0.936 0.911 0.911 0.911 0.911 0.911 0.911
220 2.301 1.727 1.245 0.972 0.911 0.911 0.911 0.911 0.911 0.911
225 2.344 1.764 1.283 1.008 0.911 0.911 0.911 0.911 0.911 0.911
230 2.387 1.801 1.322 1.045 0.911 0.911 0.911 0.911 0.911 0.911
235 2.430 1.838 1.360 1.081 0.911 0.911 0.911 0.911 0.911 0.911
240 2.473 1.875 1.398 1.117 0.911 0.911 0.911 0.911 0.911 0.911
245 2.516 1.912 1.436 1.153 0.911 0.911 0.911 0.911 0.911 0.911
250 2.551 1.949 1.475 1.190 0.911 0.911 0.911 0.911 0.911 0.911
255 2.587 1.986 1.513 1.226 0.945 0.911 0.911 0.911 0.911 0.911
260 2.623 2.023 1.551 1.262 0.980 0.911 0.911 0.911 0.911 0.911
265 2.659 2.060 1.589 1.298 1.014 0.911 0.911 0.911 0.911 0.911
270 2.694 2.097 1.628 1.335 1.048 0.911 0.911 0.911 0.911 0.911
275 2.730 2.134 1.666 1.371 1.083 0.911 0.911 0.911 0.911 0.911
280 2.766 2.171 1.704 1.407 1.117 0.911 0.911 0.911 0.911 0.911
285 2.801 2.208 1.742 1.444 1.151 0.911 0.911 0.911 0.911 0.911
290 2.837 2.245 1.781 1.480 1.186 0.911 0.911 0.911 0.911 0.911
295 2.873 2.282 1.819 1.516 1.220 0.911 0.911 0.911 0.911 0.911
300 2.909 2.319 1.857 1.552 1.254 0.933 0.911 0.911 0.911 0.911
305 2.944 2.356 1.895 1.589 1.289 0.966 0.911 0.911 0.911 0.911
310 2.980 2.393 1.934 1.625 1.323 0.999 0.911 0.911 0.911 0.911
315 3.016 2.430 1.972 1.661 1.357 1.032 0.912 0.911 0.911 0.911
320 3.052 2.467 2.010 1.697 1.392 1.065 0.944 0.911 0.911 0.911
325 3.087 2.505 2.048 1.734 1.426 1.097 0.976 0.911 0.911 0.911
330 3.123 2.543 2.087 1.770 1.460 1.130 1.008 0.911 0.911 0.911
335 3.159 2.582 2.125 1.806 1.495 1.163 1.040 0.911 0.911 0.911
340 3.194 2.621 2.163 1.842 1.529 1.196 1.072 0.911 0.911 0.911
345 3.230 2.660 2.201 1.879 1.563 1.229 1.104 0.911 0.911 0.911
350 3.266 2.699 2.240 1.915 1.598 1.261 1.136 0.911 0.911 0.911
355 3.302 2.738 2.278 1.951 1.632 1.294 1.168 0.935 0.911 0.911
360 3.337 2.776 2.316 1.987 1.666 1.327 1.200 0.967 0.911 0.911
365 3.373 2.815 2.354 2.024 1.701 1.360 1.232 0.998 0.911 0.911
370 3.409 2.854 2.393 2.060 1.735 1.393 1.264 1.030 0.911 0.911
375 3.445 2.893 2.431 2.096 1.769 1.425 1.296 1.061 0.911 0.911
380 3.480 2.932 2.469 2.132 1.803 1.458 1.328 1.093 0.911 0.911
385 3.516 2.971 2.507 2.169 1.838 1.491 1.360 1.125 0.911 0.911
390 3.552 3.010 2.548 2.205 1.872 1.524 1.392 1.156 0.911 0.911
Thickness (mm) Required for a Design Temperature of
Table 2(Continued): I-Section Columns 60 Minutes
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 7 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results also apply to I section beams with 4 sides fire exposure subject to a maximum DFT of 4.455mm.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
30 1.109 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
35 1.297 0.927 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
40 1.485 1.006 0.911 0.911 0.911 0.911 0.911 0.911 0.911 0.911
45 1.673 1.084 0.918 0.911 0.911 0.911 0.911 0.911 0.911 0.911
50 1.861 1.163 0.969 0.911 0.911 0.911 0.911 0.911 0.911 0.911
55 2.049 1.241 1.020 0.911 0.911 0.911 0.911 0.911 0.911 0.911
60 2.237 1.320 1.072 0.911 0.911 0.911 0.911 0.911 0.911 0.911
65 2.426 1.398 1.123 0.911 0.911 0.911 0.911 0.911 0.911 0.911
70 2.540 1.477 1.174 0.946 0.911 0.911 0.911 0.911 0.911 0.911
75 2.589 1.555 1.226 0.992 0.911 0.911 0.911 0.911 0.911 0.911
80 2.639 1.634 1.277 1.038 0.911 0.911 0.911 0.911 0.911 0.911
85 2.688 1.712 1.329 1.085 0.911 0.911 0.911 0.911 0.911 0.911
90 2.738 1.791 1.380 1.131 0.911 0.911 0.911 0.911 0.911 0.911
95 2.788 1.869 1.431 1.177 0.911 0.911 0.911 0.911 0.911 0.911
100 2.837 1.948 1.483 1.223 0.911 0.911 0.911 0.911 0.911 0.911
105 2.887 2.026 1.534 1.270 0.911 0.911 0.911 0.911 0.911 0.911
110 2.936 2.105 1.585 1.316 0.932 0.911 0.911 0.911 0.911 0.911
115 2.986 2.183 1.637 1.362 0.978 0.911 0.911 0.911 0.911 0.911
120 3.036 2.262 1.688 1.408 1.023 0.911 0.911 0.911 0.911 0.911
125 3.085 2.340 1.739 1.455 1.068 0.911 0.911 0.911 0.911 0.911
130 3.135 2.419 1.791 1.501 1.113 0.911 0.911 0.911 0.911 0.911
135 3.184 2.497 1.842 1.547 1.159 0.911 0.911 0.911 0.911 0.911
140 3.234 2.547 1.893 1.593 1.204 0.911 0.911 0.911 0.911 0.911
145 3.284 2.590 1.945 1.640 1.249 0.911 0.911 0.911 0.911 0.911
150 3.333 2.633 1.996 1.686 1.295 0.911 0.911 0.911 0.911 0.911
155 3.383 2.676 2.047 1.732 1.340 0.911 0.911 0.911 0.911 0.911
160 3.432 2.719 2.099 1.779 1.385 0.911 0.911 0.911 0.911 0.911
165 3.482 2.762 2.150 1.825 1.431 0.911 0.911 0.911 0.911 0.911
170 3.532 2.805 2.202 1.871 1.476 0.927 0.911 0.911 0.911 0.911
175 3.581 2.848 2.253 1.917 1.521 0.974 0.911 0.911 0.911 0.911
180 3.631 2.891 2.304 1.964 1.567 1.021 0.946 0.911 0.911 0.911
185 3.680 2.933 2.356 2.010 1.612 1.067 0.989 0.911 0.911 0.911
190 3.730 2.976 2.407 2.056 1.657 1.114 1.032 0.911 0.911 0.911
195 3.780 3.019 2.458 2.102 1.702 1.160 1.075 0.918 0.911 0.911
200 3.829 3.062 2.510 2.149 1.748 1.207 1.118 0.960 0.911 0.911
Table 3: I-Section Columns 90 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 8 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results also apply to I section beams with 4 sides fire exposure subject to a maximum DFT of 4.455mm.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
205 3.879 3.105 2.554 2.195 1.793 1.254 1.161 1.002 0.911 0.911
210 3.928 3.148 2.597 2.241 1.838 1.300 1.204 1.045 0.911 0.911
215 3.978 3.191 2.641 2.287 1.884 1.347 1.248 1.087 0.911 0.911
220 4.028 3.234 2.684 2.334 1.929 1.393 1.291 1.130 0.911 0.911
225 4.071 3.277 2.727 2.380 1.974 1.440 1.334 1.172 0.911 0.911
230 4.113 3.320 2.771 2.426 2.020 1.486 1.377 1.215 0.946 0.911
235 4.155 3.362 2.814 2.472 2.065 1.533 1.420 1.257 0.986 0.911
240 4.198 3.405 2.858 2.519 2.110 1.580 1.463 1.300 1.027 0.911
245 4.240 3.448 2.901 2.564 2.156 1.626 1.506 1.342 1.067 0.911
250 4.282 3.491 2.945 2.609 2.201 1.673 1.549 1.385 1.108 0.911
255 4.324 3.534 2.988 2.655 2.246 1.719 1.593 1.427 1.148 0.911
260 4.367 3.577 3.032 2.700 2.292 1.766 1.636 1.470 1.189 0.911
265 4.409 3.620 3.075 2.745 2.337 1.813 1.679 1.512 1.229 0.948
270 4.451 3.663 3.118 2.791 2.382 1.859 1.722 1.555 1.270 0.986
275 4.494 3.706 3.162 2.836 2.427 1.906 1.765 1.597 1.310 1.024
280 4.536 3.748 3.205 2.881 2.473 1.952 1.808 1.640 1.351 1.062
285 4.578 3.791 3.249 2.927 2.518 1.999 1.851 1.682 1.391 1.099
290 4.620 3.834 3.292 2.972 2.567 2.046 1.895 1.725 1.432 1.137
295 4.663 3.877 3.336 3.017 2.615 2.092 1.938 1.767 1.472 1.175
300 4.705 3.920 3.379 3.062 2.663 2.139 1.981 1.810 1.513 1.213
305 4.747 3.963 3.422 3.108 2.712 2.185 2.024 1.852 1.553 1.251
310 4.790 4.006 3.466 3.153 2.760 2.232 2.067 1.895 1.594 1.288
315 4.832 4.055 3.509 3.198 2.808 2.279 2.110 1.937 1.634 1.326
320 4.874 4.115 3.553 3.244 2.856 2.325 2.153 1.980 1.675 1.364
325 4.916 4.176 3.596 3.289 2.905 2.372 2.196 2.022 1.715 1.402
330 4.959 4.236 3.640 3.334 2.953 2.418 2.240 2.065 1.756 1.440
335 5.001 4.296 3.683 3.380 3.001 2.465 2.283 2.107 1.796 1.477
340 5.043 4.356 3.727 3.425 3.049 2.511 2.326 2.150 1.837 1.515
345 5.086 4.416 3.770 3.470 3.098 2.565 2.369 2.192 1.878 1.553
350 5.128 4.477 3.813 3.516 3.146 2.619 2.412 2.235 1.918 1.591
355 5.170 4.537 3.857 3.561 3.194 2.672 2.455 2.277 1.959 1.629
360 5.213 4.597 3.900 3.606 3.243 2.726 2.498 2.320 1.999 1.666
365 5.255 4.657 3.944 3.652 3.291 2.780 2.549 2.362 2.040 1.704
370 5.297 4.717 3.987 3.697 3.339 2.833 2.604 2.405 2.080 1.742
375 5.339 4.778 4.031 3.742 3.387 2.887 2.659 2.447 2.121 1.780
380 5.382 4.838 4.104 3.788 3.436 2.941 2.714 2.490 2.161 1.817
385 5.424 4.898 4.180 3.833 3.484 2.994 2.769 2.537 2.202 1.855
390 5.466 4.958 4.255 3.878 3.532 3.048 2.824 2.589 2.242 1.893
Thickness (mm) Required for a Design Temperature of
Table 3(Continued): I-Section Columns 90 Minutes
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 9 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results also apply to I section beams with 4 sides fire exposure subject to a maximum DFT of 4.455mm.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
30 2.457 1.622 1.107 0.911 0.911 0.911 0.911 0.911 0.911 0.911
35 2.660 1.919 1.305 0.946 0.911 0.911 0.911 0.911 0.911 0.911
40 2.863 2.216 1.502 1.062 0.917 0.911 0.911 0.911 0.911 0.911
45 3.066 2.513 1.699 1.178 0.975 0.911 0.911 0.911 0.911 0.911
50 3.269 2.638 1.897 1.293 1.032 0.911 0.911 0.911 0.911 0.911
55 3.472 2.762 2.094 1.409 1.090 0.938 0.911 0.911 0.911 0.911
60 3.675 2.887 2.291 1.524 1.148 0.991 0.911 0.911 0.911 0.911
65 3.878 3.011 2.489 1.640 1.205 1.043 0.942 0.911 0.911 0.911
70 4.058 3.136 2.580 1.755 1.263 1.096 0.994 0.911 0.911 0.911
75 4.163 3.261 2.656 1.871 1.321 1.148 1.045 0.925 0.911 0.911
80 4.269 3.385 2.732 1.986 1.378 1.200 1.097 0.974 0.911 0.911
85 4.374 3.510 2.808 2.102 1.436 1.253 1.148 1.024 0.911 0.911
90 4.480 3.634 2.884 2.218 1.494 1.305 1.200 1.073 0.911 0.911
95 4.586 3.759 2.960 2.333 1.551 1.358 1.251 1.122 0.911 0.911
100 4.691 3.883 3.036 2.449 1.609 1.410 1.303 1.172 0.911 0.911
105 4.797 4.008 3.111 2.545 1.667 1.463 1.354 1.221 0.911 0.911
110 4.902 4.083 3.187 2.617 1.724 1.515 1.406 1.271 0.911 0.911
115 5.008 4.144 3.263 2.689 1.782 1.567 1.457 1.320 0.911 0.911
120 5.114 4.206 3.339 2.761 1.840 1.620 1.509 1.370 0.947 0.911
125 5.219 4.268 3.415 2.833 1.897 1.672 1.560 1.419 0.998 0.911
130 5.325 4.330 3.491 2.905 1.955 1.725 1.612 1.468 1.049 0.911
135 5.430 4.392 3.567 2.977 2.013 1.777 1.664 1.518 1.100 0.911
140 5.536 4.454 3.643 3.049 2.070 1.829 1.715 1.567 1.151 0.911
145 5.641 4.516 3.719 3.121 2.128 1.882 1.767 1.617 1.201 0.911
150 5.747 4.578 3.795 3.193 2.186 1.934 1.818 1.666 1.252 0.911
155 5.853 4.640 3.871 3.265 2.243 1.987 1.870 1.715 1.303 0.911
160 5.958 4.702 3.947 3.337 2.301 2.039 1.921 1.765 1.354 0.911
165 - 4.764 4.023 3.409 2.359 2.092 1.973 1.814 1.405 0.911
170 - 4.826 4.072 3.481 2.416 2.144 2.024 1.864 1.455 0.911
175 - 4.888 4.117 3.553 2.474 2.196 2.076 1.913 1.506 0.962
180 - 4.950 4.162 3.625 2.542 2.249 2.127 1.963 1.557 1.015
185 - 5.012 4.207 3.697 2.633 2.301 2.179 2.012 1.608 1.068
190 - 5.073 4.251 3.769 2.724 2.354 2.230 2.061 1.659 1.121
195 - 5.135 4.296 3.841 2.815 2.406 2.282 2.111 1.709 1.174
200 - 5.197 4.341 3.913 2.906 2.458 2.333 2.160 1.760 1.227
Table 4: I-Section Columns 120 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 10 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results also apply to I section beams with 4 sides fire exposure subject to a maximum DFT of 4.455mm.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
205 - 5.259 4.386 3.985 2.997 2.511 2.385 2.210 1.811 1.280
210 - 5.321 4.431 4.047 3.088 2.564 2.437 2.259 1.862 1.333
215 - 5.383 4.476 4.090 3.179 2.617 2.488 2.308 1.913 1.386
220 - 5.445 4.520 4.133 3.269 2.670 2.539 2.358 1.964 1.439
225 - 5.507 4.565 4.176 3.360 2.723 2.590 2.407 2.014 1.492
230 - 5.569 4.610 4.219 3.451 2.776 2.640 2.457 2.065 1.545
235 - 5.631 4.655 4.261 3.542 2.829 2.691 2.506 2.116 1.598
240 - 5.693 4.700 4.304 3.633 2.882 2.742 2.556 2.167 1.650
245 - 5.755 4.744 4.347 3.724 2.935 2.792 2.607 2.218 1.703
250 - 5.817 4.789 4.390 3.815 2.988 2.843 2.657 2.268 1.756
255 - 5.879 4.834 4.433 3.906 3.041 2.894 2.708 2.319 1.809
260 - 5.941 4.879 4.476 3.997 3.094 2.944 2.758 2.370 1.862
265 - 6.003 4.924 4.518 4.063 3.147 2.995 2.808 2.421 1.915
270 - - 4.969 4.561 4.112 3.199 3.046 2.859 2.472 1.968
275 - - 5.013 4.604 4.162 3.252 3.096 2.909 2.522 2.021
280 - - 5.058 4.647 4.212 3.305 3.147 2.960 2.573 2.074
285 - - 5.103 4.690 4.262 3.358 3.197 3.010 2.624 2.127
290 - - 5.148 4.732 4.311 3.411 3.248 3.060 2.675 2.180
295 - - 5.193 4.775 4.361 3.464 3.299 3.111 2.725 2.233
300 - - 5.238 4.818 4.411 3.517 3.349 3.161 2.776 2.286
305 - - 5.282 4.861 4.461 3.570 3.400 3.212 2.827 2.339
310 - - 5.327 4.904 4.510 3.623 3.451 3.262 2.877 2.392
315 - - 5.372 4.947 4.560 3.676 3.501 3.312 2.928 2.445
320 - - 5.417 4.989 4.610 3.729 3.552 3.363 2.979 2.498
325 - - 5.462 5.032 4.659 3.782 3.603 3.413 3.029 2.550
330 - - 5.507 5.075 4.709 3.835 3.653 3.464 3.080 2.602
335 - - 5.551 5.118 4.759 3.888 3.704 3.514 3.131 2.654
340 - - 5.596 5.161 4.809 3.941 3.755 3.564 3.182 2.706
345 - - 5.641 5.203 4.858 3.994 3.805 3.615 3.232 2.757
350 - - 5.686 5.246 4.908 4.054 3.856 3.665 3.283 2.809
355 - - 5.731 5.289 4.958 4.132 3.906 3.716 3.334 2.861
360 - - 5.775 5.332 5.008 4.210 3.957 3.766 3.384 2.913
365 - - 5.820 5.375 5.057 4.289 4.008 3.816 3.435 2.965
370 - - 5.865 5.417 5.107 4.367 4.074 3.867 3.486 3.017
375 - - 5.910 5.460 5.157 4.445 4.157 3.917 3.537 3.069
380 - - 5.955 5.503 5.206 4.524 4.240 3.968 3.587 3.121
385 - - 6.000 5.546 5.256 4.602 4.322 4.018 3.638 3.173
390 - - 6.044 5.589 5.306 4.680 4.405 4.089 3.689 3.225
Thickness (mm) Required for a Design Temperature of
Table 4(Continued): I-Section Columns 120 Minutes
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 11 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results also apply to I section beams with 4 sides fire exposure subject to a maximum DFT of 4.455mm.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
30 4.743 3.861 2.368 2.578 1.489 1.354 1.051 0.918 0.911 0.911
35 4.743 4.301 3.212 2.971 2.126 1.986 1.813 1.721 0.911 0.911
40 - 4.741 4.056 3.364 2.763 2.618 2.575 2.524 1.033 1.028
45 - 5.182 4.395 3.758 3.087 2.823 2.749 2.657 2.523 1.323
50 - 5.622 4.734 4.112 3.410 3.028 2.923 2.791 2.606 1.617
55 - - 5.073 4.377 3.734 3.233 3.098 2.924 2.689 1.912
60 - - 5.412 4.642 4.048 3.439 3.272 3.057 2.772 2.207
65 - - 5.751 4.907 4.251 3.644 3.446 3.191 2.855 2.502
70 - - - 5.172 4.454 3.849 3.620 3.324 2.938 2.570
75 - - - 5.437 4.657 4.049 3.794 3.458 3.021 2.628
80 - - - 5.702 4.859 4.201 3.968 3.591 3.104 2.687
85 - - - 5.966 5.062 4.352 4.116 3.724 3.187 2.746
90 - - - - 5.265 4.504 4.247 3.858 3.270 2.805
95 - - - - 5.468 4.656 4.379 3.991 3.353 2.864
100 - - - - 5.670 4.808 4.511 4.104 3.436 2.923
105 - - - - 5.873 4.960 4.642 4.206 3.519 2.981
110 - - - - - 5.111 4.774 4.309 3.602 3.040
115 - - - - - 5.263 4.906 4.412 3.685 3.099
120 - - - - - 5.415 5.037 4.515 3.768 3.158
125 - - - - - 5.567 5.169 4.618 3.850 3.217
130 - - - - - 5.719 5.301 4.721 3.933 3.276
135 - - - - - 5.870 5.432 4.824 4.016 3.335
140 - - - - - 6.022 5.564 4.927 4.096 3.393
145 - - - - - - 5.696 5.030 4.176 3.452
150 - - - - - - 5.827 5.132 4.255 3.511
155 - - - - - - 5.959 5.235 4.335 3.570
160 - - - - - - - 5.338 4.414 3.629
165 - - - - - - - 5.441 4.493 3.688
170 - - - - - - - 5.544 4.573 3.746
175 - - - - - - - 5.647 4.652 3.805
180 - - - - - - - 5.750 4.732 3.864
185 - - - - - - - 5.853 4.811 3.923
190 - - - - - - - 5.956 4.890 3.982
195 - - - - - - - 6.058 4.970 4.039
200 - - - - - - - - 5.049 4.084
Table 5: I-Section Columns 180 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 12 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results also apply to I section beams with 4 sides fire exposure subject to a maximum DFT of 4.455mm.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
205 - - - - - - - - 5.128 4.129
210 - - - - - - - - 5.208 4.174
215 - - - - - - - - 5.287 4.219
220 - - - - - - - - 5.367 4.264
225 - - - - - - - - 5.446 4.309
230 - - - - - - - - 5.525 4.354
235 - - - - - - - - 5.605 4.399
240 - - - - - - - - 5.684 4.443
245 - - - - - - - - 5.763 4.488
250 - - - - - - - - 5.843 4.533
255 - - - - - - - - 5.922 4.578
260 - - - - - - - - 6.002 4.623
265 - - - - - - - - - 4.668
270 - - - - - - - - - 4.713
275 - - - - - - - - - 4.758
280 - - - - - - - - - 4.803
285 - - - - - - - - - 4.848
290 - - - - - - - - - 4.893
295 - - - - - - - - - 4.938
300 - - - - - - - - - 4.983
305 - - - - - - - - - 5.028
310 - - - - - - - - - 5.073
315 - - - - - - - - - 5.118
320 - - - - - - - - - 5.163
325 - - - - - - - - - 5.208
330 - - - - - - - - - 5.253
335 - - - - - - - - - 5.298
340 - - - - - - - - - 5.343
345 - - - - - - - - - 5.388
350 - - - - - - - - - 5.433
355 - - - - - - - - - 5.477
360 - - - - - - - - - 5.522
365 - - - - - - - - - 5.567
370 - - - - - - - - - 5.612
375 - - - - - - - - - 5.657
380 - - - - - - - - - 5.702
385 - - - - - - - - - 5.747
390 - - - - - - - - - 5.792
Thickness (mm) Required for a Design Temperature of
Table 5(Continued): I-Section Columns 180 Minutes
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 13 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results apply to I section beams with 3 sides fire exposure.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
30 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
35 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
40 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
45 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
50 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
55 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
60 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
65 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
70 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
75 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
80 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
85 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
90 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
95 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
100 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
105 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
110 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
115 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
120 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
125 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
130 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
135 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
140 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
145 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
150 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
155 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
160 1.033 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
165 1.049 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
170 1.065 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
175 1.081 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
180 1.098 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
185 1.114 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
190 1.130 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
195 1.146 1.022 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
200 1.162 1.036 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
Table 6: I-Section Beams 30 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 14 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results apply to I section beams with 3 sides fire exposure.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
205 1.178 1.050 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
210 1.194 1.064 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
215 1.210 1.078 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
220 1.226 1.091 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
225 1.242 1.105 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
230 1.258 1.119 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
235 1.274 1.133 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
240 1.290 1.147 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
245 1.306 1.161 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
250 1.322 1.175 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
255 1.338 1.189 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
260 1.354 1.203 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
265 1.370 1.217 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
270 1.386 1.230 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
275 1.402 1.244 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
280 1.418 1.258 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
285 1.434 1.272 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
290 1.450 1.286 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
295 1.466 1.300 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
300 1.482 1.314 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
305 1.498 1.328 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
310 1.514 1.342 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
315 1.530 1.356 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
320 1.546 1.369 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
325 1.562 1.383 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
330 1.578 1.397 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
Thickness (mm) Required for a Design Temperature of
Table 6(Continued): I-Section Beams 30 Minutes
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 15 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results apply to I section beams with 3 sides fire exposure.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
30 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
35 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
40 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
45 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
50 1.045 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
55 1.073 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
60 1.102 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
65 1.131 1.041 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
70 1.160 1.067 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
75 1.188 1.092 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
80 1.217 1.117 1.018 1.017 1.017 1.017 1.017 1.017 1.017 1.017
85 1.246 1.142 1.041 1.017 1.017 1.017 1.017 1.017 1.017 1.017
90 1.275 1.167 1.064 1.017 1.017 1.017 1.017 1.017 1.017 1.017
95 1.303 1.193 1.087 1.017 1.017 1.017 1.017 1.017 1.017 1.017
100 1.332 1.218 1.110 1.017 1.017 1.017 1.017 1.017 1.017 1.017
105 1.361 1.243 1.133 1.017 1.017 1.017 1.017 1.017 1.017 1.017
110 1.390 1.268 1.156 1.017 1.017 1.017 1.017 1.017 1.017 1.017
115 1.418 1.293 1.179 1.017 1.017 1.017 1.017 1.017 1.017 1.017
120 1.447 1.319 1.202 1.017 1.017 1.017 1.017 1.017 1.017 1.017
125 1.476 1.344 1.225 1.017 1.017 1.017 1.017 1.017 1.017 1.017
130 1.505 1.369 1.248 1.017 1.017 1.017 1.017 1.017 1.017 1.017
135 1.533 1.394 1.271 1.017 1.017 1.017 1.017 1.017 1.017 1.017
140 1.562 1.420 1.294 1.017 1.017 1.017 1.017 1.017 1.017 1.017
145 1.591 1.445 1.317 1.017 1.017 1.017 1.017 1.017 1.017 1.017
150 1.620 1.470 1.340 1.017 1.017 1.017 1.017 1.017 1.017 1.017
155 1.648 1.495 1.362 1.017 1.017 1.017 1.017 1.017 1.017 1.017
160 1.677 1.520 1.385 1.037 1.017 1.017 1.017 1.017 1.017 1.017
165 1.706 1.546 1.408 1.062 1.017 1.017 1.017 1.017 1.017 1.017
170 1.735 1.571 1.431 1.086 1.017 1.017 1.017 1.017 1.017 1.017
175 1.763 1.596 1.454 1.111 1.017 1.017 1.017 1.017 1.017 1.017
180 1.792 1.621 1.477 1.136 1.017 1.017 1.017 1.017 1.017 1.017
185 1.821 1.646 1.500 1.161 1.017 1.017 1.017 1.017 1.017 1.017
190 1.850 1.672 1.523 1.186 1.017 1.017 1.017 1.017 1.017 1.017
195 1.878 1.697 1.546 1.211 1.017 1.017 1.017 1.017 1.017 1.017
200 1.907 1.722 1.569 1.236 1.017 1.017 1.017 1.017 1.017 1.017
Table 7: I-Section Beams 60 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 16 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results apply to I section beams with 3 sides fire exposure.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
205 1.936 1.747 1.592 1.261 1.017 1.017 1.017 1.017 1.017 1.017
210 1.965 1.772 1.615 1.286 1.017 1.017 1.017 1.017 1.017 1.017
215 1.993 1.798 1.638 1.311 1.017 1.017 1.017 1.017 1.017 1.017
220 2.022 1.823 1.661 1.336 1.017 1.017 1.017 1.017 1.017 1.017
225 2.051 1.848 1.684 1.361 1.017 1.017 1.017 1.017 1.017 1.017
230 2.080 1.873 1.707 1.386 1.017 1.017 1.017 1.017 1.017 1.017
235 2.108 1.899 1.730 1.410 1.017 1.017 1.017 1.017 1.017 1.017
240 2.137 1.924 1.752 1.435 1.017 1.017 1.017 1.017 1.017 1.017
245 2.517 1.949 1.775 1.460 1.017 1.017 1.017 1.017 1.017 1.017
250 2.194 1.974 1.798 1.485 1.017 1.017 1.017 1.017 1.017 1.017
255 2.223 1.999 1.821 1.510 1.043 1.017 1.017 1.017 1.017 1.017
260 2.252 2.025 1.844 1.535 1.072 1.017 1.017 1.017 1.017 1.017
265 2.281 2.050 1.867 1.560 1.101 1.017 1.017 1.017 1.017 1.017
270 2.309 2.075 1.890 1.585 1.130 1.017 1.017 1.017 1.017 1.017
275 2.338 2.100 1.913 1.610 1.160 1.017 1.017 1.017 1.017 1.017
280 2.367 2.517 1.936 1.635 1.189 1.017 1.017 1.017 1.017 1.017
285 2.396 2.151 1.959 1.660 1.218 1.017 1.017 1.017 1.017 1.017
290 2.424 2.176 1.982 1.685 1.247 1.017 1.017 1.017 1.017 1.017
295 2.453 2.201 2.005 1.710 1.277 1.017 1.017 1.017 1.017 1.017
300 2.482 2.226 2.028 1.735 1.306 1.017 1.017 1.017 1.017 1.017
305 2.511 2.251 2.051 1.759 1.335 1.017 1.017 1.017 1.017 1.017
310 2.539 2.277 2.074 1.784 1.364 1.017 1.017 1.017 1.017 1.017
315 2.568 2.302 2.517 1.809 1.393 1.017 1.017 1.017 1.017 1.017
320 2.597 2.327 2.119 1.834 1.423 1.017 1.017 1.017 1.017 1.017
325 2.626 2.352 2.142 1.859 1.452 1.017 1.017 1.017 1.017 1.017
330 2.654 2.378 2.165 1.884 1.481 1.017 1.017 1.017 1.017 1.017
Thickness (mm) Required for a Design Temperature of
Table 7(Continued): I-Section Beams 60 Minutes
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 17 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results apply to I section beams with 3 sides fire exposure.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
30 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
35 1.149 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
40 1.352 1.059 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
45 1.554 1.131 1.042 1.017 1.017 1.017 1.017 1.017 1.017 1.017
50 1.756 1.204 1.085 1.017 1.017 1.017 1.017 1.017 1.017 1.017
55 1.959 1.276 1.127 1.023 1.017 1.017 1.017 1.017 1.017 1.017
60 2.161 1.349 1.170 1.054 1.017 1.017 1.017 1.017 1.017 1.017
65 2.363 1.421 1.213 1.085 1.017 1.017 1.017 1.017 1.017 1.017
70 2.536 1.494 1.256 1.116 1.017 1.017 1.017 1.017 1.017 1.017
75 2.617 1.566 1.298 1.147 1.037 1.017 1.017 1.017 1.017 1.017
80 2.697 1.639 1.341 1.178 1.066 1.017 1.017 1.017 1.017 1.017
85 2.778 1.711 1.384 1.210 1.095 1.017 1.017 1.017 1.017 1.017
90 2.858 1.784 1.427 1.241 1.124 1.017 1.017 1.017 1.017 1.017
95 2.939 1.856 1.469 1.272 1.153 1.018 1.017 1.017 1.017 1.017
100 3.019 1.929 1.512 1.303 1.182 1.046 1.017 1.017 1.017 1.017
105 3.099 2.001 1.555 1.334 1.211 1.074 1.017 1.017 1.017 1.017
110 3.180 2.074 1.598 1.365 1.240 1.102 1.032 1.017 1.017 1.017
115 3.260 2.146 1.640 1.396 1.269 1.130 1.060 1.017 1.017 1.017
120 3.341 2.219 1.683 1.428 1.298 1.157 1.088 1.017 1.017 1.017
125 3.421 2.291 1.726 1.459 1.327 1.185 1.115 1.017 1.017 1.017
130 3.502 2.364 1.768 1.490 1.356 1.213 1.143 1.017 1.017 1.017
135 3.582 2.436 1.811 1.521 1.385 1.241 1.171 1.025 1.017 1.017
140 3.663 2.509 1.854 1.552 1.414 1.269 1.199 1.053 1.017 1.017
145 3.743 2.660 1.897 1.583 1.443 1.297 1.226 1.082 1.017 1.017
150 3.824 2.820 1.939 1.614 1.472 1.325 1.254 1.110 1.017 1.017
155 3.904 2.980 1.982 1.645 1.501 1.353 1.282 1.138 1.017 1.017
160 3.984 3.140 2.025 1.677 1.530 1.381 1.309 1.166 1.017 1.017
165 4.065 3.301 2.068 1.708 1.559 1.409 1.337 1.195 1.017 1.017
170 4.145 3.461 2.110 1.739 1.588 1.436 1.365 1.223 1.017 1.017
175 4.226 3.621 2.153 1.770 1.617 1.464 1.393 1.251 1.017 1.017
180 4.306 3.782 2.196 1.801 1.646 1.492 1.420 1.279 1.017 1.017
185 4.387 3.942 2.239 1.832 1.675 1.520 1.448 1.308 1.017 1.017
190 - 4.102 2.281 1.863 1.704 1.548 1.476 1.336 1.031 1.017
195 - 4.263 2.324 1.895 1.733 1.576 1.504 1.364 1.060 1.017
200 - 4.423 2.367 1.926 1.762 1.604 1.531 1.392 1.090 1.017
Table 8: I-Section Beams 90 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 18 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results apply to I section beams with 3 sides fire exposure.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
205 - - 2.517 1.957 1.791 1.632 1.559 1.421 1.120 1.017
210 - - 2.452 1.988 1.820 1.660 1.587 1.449 1.150 1.017
215 - - 2.495 2.019 1.849 1.687 1.614 1.477 1.179 1.017
220 - - 2.538 2.050 1.878 1.715 1.642 1.505 1.209 1.017
225 - - 2.581 2.081 1.907 1.743 1.670 1.533 1.239 1.017
230 - - 2.623 2.112 1.936 1.771 1.698 1.562 1.268 1.017
235 - - 2.666 2.144 1.965 1.799 1.725 1.590 1.298 1.017
240 - - 2.709 2.175 1.994 1.827 1.753 1.618 1.328 1.017
245 - - 2.752 2.206 2.023 1.855 1.781 1.646 1.358 1.017
250 - - 2.794 2.237 2.052 1.883 1.808 1.675 1.387 1.017
255 - - 2.837 2.268 2.081 1.911 1.836 1.703 1.417 1.017
260 - - 2.880 2.299 2.110 1.939 1.864 1.731 1.447 1.017
265 - - 2.923 2.330 2.139 1.966 1.892 1.759 1.476 1.017
270 - - 2.965 2.361 2.168 1.994 1.919 1.788 1.506 1.017
275 - - 3.008 2.393 2.197 2.022 1.947 1.816 1.536 1.017
280 - - 3.051 2.424 2.226 2.050 1.975 1.844 1.566 1.018
285 - - 3.093 2.455 2.255 2.078 2.003 1.872 1.595 1.053
290 - - 3.136 2.486 2.284 2.106 2.030 1.901 1.625 1.089
295 - - 3.179 2.517 2.313 2.134 2.058 1.929 1.655 1.124
300 - - 3.222 2.582 2.342 2.162 2.086 1.957 1.684 1.160
305 - - 3.264 2.646 2.371 2.190 2.113 1.985 1.714 1.195
310 - - 3.307 2.711 2.400 2.217 2.141 2.014 1.744 1.231
315 - - 3.350 2.775 2.429 2.245 2.169 2.042 1.774 1.267
320 - - 3.393 2.840 2.458 2.273 2.197 2.070 1.803 1.302
325 - - 3.435 2.904 2.487 2.301 2.224 2.098 1.833 1.338
330 - - 3.478 2.969 2.516 2.329 2.252 2.127 1.863 1.373
Thickness (mm) Required for a Design Temperature of
Table 8(Continued): I-Section Beams 90 Minutes
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 19 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results apply to I section beams with 3 sides fire exposure.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
30 2.449 1.500 1.017 1.017 1.017 1.017 1.017 1.017 1.017 1.017
35 2.678 1.832 1.140 1.017 1.017 1.017 1.017 1.017 1.017 1.017
40 2.907 2.164 1.355 1.070 1.017 1.017 1.017 1.017 1.017 1.017
45 3.136 2.496 1.569 1.175 1.043 1.017 1.017 1.017 1.017 1.017
50 3.366 2.634 1.783 1.280 1.097 1.017 1.017 1.017 1.017 1.017
55 3.595 2.760 1.998 1.385 1.150 1.059 1.029 1.017 1.017 1.017
60 3.824 2.885 2.212 1.490 1.204 1.102 1.068 1.020 1.017 1.017
65 4.053 3.010 2.427 1.595 1.257 1.145 1.108 1.054 1.017 1.017
70 4.282 3.135 2.568 1.699 1.311 1.188 1.147 1.089 1.017 1.017
75 - 3.261 2.656 1.804 1.364 1.231 1.186 1.123 1.036 1.017
80 - 3.386 2.744 1.909 1.418 1.274 1.225 1.158 1.067 1.017
85 - 3.511 2.832 2.014 1.471 1.316 1.265 1.192 1.097 1.017
90 - 3.636 2.920 2.119 1.525 1.359 1.304 1.227 1.127 1.041
95 - 3.761 3.008 2.224 1.578 1.402 1.343 1.261 1.158 1.070
100 - 3.887 3.095 2.329 1.632 1.445 1.382 1.296 1.188 1.098
105 - 4.012 3.183 2.434 1.686 1.488 1.422 1.330 1.219 1.127
110 - 4.137 3.271 2.525 1.739 1.531 1.461 1.365 1.249 1.155
115 - 4.262 3.359 2.562 1.793 1.574 1.500 1.399 1.280 1.184
120 - 4.388 3.447 2.600 1.846 1.617 1.539 1.434 1.310 1.212
125 - - 3.535 2.637 1.900 1.660 1.579 1.468 1.340 1.241
130 - - 3.623 2.675 1.953 1.703 1.618 1.503 1.371 1.269
135 - - 3.711 2.712 2.007 1.746 1.657 1.537 1.401 1.298
140 - - 3.799 2.750 2.060 1.789 1.696 1.572 1.432 1.326
145 - - 3.887 2.787 2.114 1.832 1.736 1.606 1.462 1.355
150 - - 3.975 2.825 2.167 1.875 1.775 1.641 1.492 1.383
155 - - 4.063 2.863 2.221 1.917 1.814 1.675 1.523 1.412
160 - - 4.151 2.900 2.275 1.960 1.853 1.710 1.553 1.440
165 - - 4.239 2.938 2.328 2.003 1.893 1.744 1.584 1.468
170 - - 4.327 2.975 2.382 2.046 1.932 1.779 1.614 1.497
175 - - 4.415 3.013 2.435 2.089 1.971 1.813 1.645 1.525
180 - - - 3.050 2.489 2.132 2.010 1.848 1.675 1.554
185 - - - 3.088 2.541 2.175 2.050 1.882 1.705 1.582
190 - - - 3.125 2.591 2.218 2.089 1.917 1.736 1.611
195 - - - 3.163 2.642 2.261 2.128 1.951 1.766 1.639
200 - - - 3.200 2.692 2.304 2.167 1.986 1.797 1.668
Table 9: I-Section Beams 120 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 20 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results apply to I section beams with 3 sides fire exposure.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
205 - - - 3.238 2.743 2.347 2.207 2.020 1.827 1.696
210 - - - 3.275 2.793 2.390 2.246 2.055 1.857 1.725
215 - - - 3.313 2.844 2.433 2.285 2.089 1.888 1.753
220 - - - 3.351 2.894 2.476 2.324 2.124 1.918 1.782
225 - - - 3.388 2.945 2.519 2.364 2.158 1.949 1.810
230 - - - 3.426 2.995 2.576 2.403 2.193 1.979 1.839
235 - - - 3.463 3.046 2.633 2.442 2.227 2.010 1.867
240 - - - 3.501 3.096 2.690 2.481 2.262 2.040 1.896
245 - - - 3.538 3.147 2.747 2.523 2.296 2.070 1.924
250 - - - 3.576 3.197 2.804 2.584 2.331 2.101 1.953
255 - - - 3.613 3.248 2.861 2.645 2.365 2.131 1.981
260 - - - 3.651 3.298 2.918 2.707 2.400 2.162 2.010
265 - - - 3.688 3.349 2.975 2.768 2.434 2.192 2.038
270 - - - 3.726 3.399 3.032 2.829 2.469 2.222 2.067
275 - - - 3.763 3.450 3.088 2.891 2.503 2.253 2.095
280 - - - 3.801 3.500 3.145 2.952 2.559 2.283 2.123
285 - - - 3.839 3.551 3.202 3.013 2.629 2.314 2.152
290 - - - 3.876 3.601 3.259 3.075 2.699 2.344 2.180
295 - - - 3.914 3.652 3.316 3.136 2.770 2.375 2.209
300 - - - 3.951 3.702 3.373 3.197 2.840 2.405 2.237
305 - - - 3.989 3.753 3.430 3.259 2.910 2.435 2.266
310 - - - 4.026 3.803 3.487 3.320 2.981 2.466 2.294
315 - - - 4.064 3.854 3.544 3.381 3.051 2.496 2.323
320 - - - 4.101 3.904 3.601 3.443 3.121 2.541 2.351
325 - - - 4.139 3.954 3.658 3.504 3.191 2.619 2.380
330 - - - 4.176 4.005 3.715 3.565 3.262 2.697 2.408
Thickness (mm) Required for a Design Temperature of
Table 9(Continued): I-Section Beams 120 Minutes
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 21 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only. Results apply to I section beams with 3 sides fire exposure.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
30 - - 3.230 2.581 1.424 1.110 1.017 1.017 1.017 1.017
35 - - 3.230 2.945 2.068 1.846 1.696 1.368 1.017 1.017
40 - - - 3.310 2.712 2.582 2.547 2.395 1.308 1.017
45 - - - 3.675 2.986 2.743 2.679 2.599 2.190 1.249
50 - - - 4.040 3.260 2.904 2.812 2.692 2.560 1.550
55 - - - 4.404 3.535 3.065 2.944 2.785 2.629 1.851
60 - - - - 3.809 3.226 3.076 2.878 2.697 2.152
65 - - - - 4.083 3.387 3.208 2.971 2.766 2.453
70 - - - - 4.357 3.548 3.340 3.064 2.834 2.563
75 - - - - - 3.709 3.472 3.157 2.903 2.621
80 - - - - - 3.870 3.604 3.251 2.972 2.679
85 - - - - - 4.030 3.736 3.344 3.040 2.737
90 - - - - - 4.191 3.868 3.437 3.109 2.795
95 - - - - - 4.352 4.000 3.530 3.177 2.853
100 - - - - - - 4.132 3.623 3.246 2.911
105 - - - - - - 4.265 3.716 3.314 2.969
110 - - - - - - 4.397 3.809 3.383 3.027
115 - - - - - - - 3.902 3.452 3.085
120 - - - - - - - 3.995 3.520 3.143
125 - - - - - - - 4.088 3.589 3.201
130 - - - - - - - 4.181 3.657 3.259
135 - - - - - - - 4.274 3.726 3.317
140 - - - - - - - 4.367 3.794 3.375
145 - - - - - - - - 3.863 3.433
150 - - - - - - - - 3.931 3.491
155 - - - - - - - - 4.000 3.549
160 - - - - - - - - 4.069 3.607
165 - - - - - - - - 4.137 3.665
170 - - - - - - - - 4.206 3.723
175 - - - - - - - - 4.274 3.781
180 - - - - - - - - 4.343 3.839
185 - - - - - - - - 4.411 3.897
190 - - - - - - - - - 3.955
195 - - - - - - - - - 4.013
200 - - - - - - - - - 4.071
Table 10: I-Section Beams 180 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 22 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 550°C 600°C 620°C 650°C 700°C 750°C
205 - - - - - - - - - 4.129
210 - - - - - - - - - 4.187
215 - - - - - - - - - 4.245
220 - - - - - - - - - 4.303
225 - - - - - - - - - 4.361
230 - - - - - - - - - 4.419
235 - - - - - - - - - -
240 - - - - - - - - - -
245 - - - - - - - - - -
250 - - - - - - - - - -
255 - - - - - - - - - -
260 - - - - - - - - - -
265 - - - - - - - - - -
270 - - - - - - - - - -
275 - - - - - - - - - -
280 - - - - - - - - - -
285 - - - - - - - - - -
290 - - - - - - - - - -
295 - - - - - - - - - -
300 - - - - - - - - - -
305 - - - - - - - - - -
310 - - - - - - - - - -
315 - - - - - - - - - -
320 - - - - - - - - - -
325 - - - - - - - - - -
330 - - - - - - - - - -
Table 10(Continued): I-Section Beams 180 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 23 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 520°C 550°C 600°C 620°C 650°C 700°C 750°C
50 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
55 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
60 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
65 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
70 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
75 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
80 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
85 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
90 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
95 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
100 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
105 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
110 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
115 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
120 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
125 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
130 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
135 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
140 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
145 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
150 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
155 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
160 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
165 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
170 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
175 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
180 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
185 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
190 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
195 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
200 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
205 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
210 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
215 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
220 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
225 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
230 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
235 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
240 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
245 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
Table 11: Rectangular Hollow Columns 30 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 24 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 520°C 550°C 600°C 620°C 650°C 700°C 750°C
50 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
55 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
60 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
65 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
70 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
75 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
80 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
85 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
90 1.812 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
95 1.860 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
100 1.908 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
105 1.956 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
110 2.004 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
115 2.052 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
120 2.100 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
125 2.148 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
130 2.196 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
135 2.244 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
140 2.292 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
145 2.340 1.845 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
150 2.388 1.899 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
155 2.436 1.952 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
160 2.484 2.005 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
165 2.532 2.059 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
170 2.580 2.112 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
175 2.628 2.166 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
180 2.676 2.219 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
185 2.724 2.272 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
190 2.772 2.326 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
195 2.820 2.379 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
200 2.868 2.432 1.830 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
205 2.916 2.486 1.892 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
210 2.964 2.539 1.953 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
215 3.012 2.592 2.015 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
220 3.060 2.646 2.077 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
225 3.108 2.699 2.139 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
230 3.156 2.752 2.200 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
235 3.204 2.806 2.262 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
240 3.298 2.859 2.324 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
245 3.447 2.912 2.386 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
Table 12: Rectangular Hollow Columns 60 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 25 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 520°C 550°C 600°C 620°C 650°C 700°C 750°C
50 2.443 1.934 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
55 2.576 2.014 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
60 2.708 2.093 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
65 2.841 2.173 1.864 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
70 2.974 2.253 1.926 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
75 3.106 2.333 1.987 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
80 3.238 2.412 2.049 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
85 3.367 2.492 2.110 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
90 3.495 2.572 2.172 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
95 3.623 2.652 2.233 1.809 1.809 1.809 1.809 1.809 1.809 1.809 1.809
100 3.751 2.731 2.295 1.861 1.809 1.809 1.809 1.809 1.809 1.809 1.809
105 3.879 2.811 2.357 1.913 1.809 1.809 1.809 1.809 1.809 1.809 1.809
110 4.007 2.891 2.418 1.964 1.809 1.809 1.809 1.809 1.809 1.809 1.809
115 4.136 2.971 2.480 2.016 1.822 1.809 1.809 1.809 1.809 1.809 1.809
120 4.264 3.050 2.541 2.068 1.877 1.809 1.809 1.809 1.809 1.809 1.809
125 4.392 3.130 2.603 2.120 1.932 1.809 1.809 1.809 1.809 1.809 1.809
130 4.520 3.210 2.664 2.171 1.987 1.809 1.809 1.809 1.809 1.809 1.809
135 4.624 3.331 2.726 2.223 2.042 1.857 1.809 1.809 1.809 1.809 1.809
140 4.728 3.465 2.787 2.275 2.096 1.912 1.809 1.809 1.809 1.809 1.809
145 4.832 3.600 2.849 2.327 2.151 1.967 1.809 1.809 1.809 1.809 1.809
150 4.937 3.735 2.911 2.379 2.206 2.022 1.809 1.809 1.809 1.809 1.809
155 5.041 3.870 2.972 2.430 2.261 2.078 1.809 1.809 1.809 1.809 1.809
160 5.145 4.004 3.034 2.482 2.316 2.133 1.809 1.809 1.809 1.809 1.809
165 5.249 4.139 3.095 2.534 2.370 2.188 1.809 1.809 1.809 1.809 1.809
170 5.353 4.274 3.157 2.586 2.425 2.243 1.809 1.809 1.809 1.809 1.809
175 5.457 4.408 3.218 2.637 2.480 2.298 1.906 1.809 1.809 1.809 1.809
180 5.561 4.542 3.321 2.689 2.535 2.354 1.965 1.809 1.809 1.809 1.809
185 5.666 4.671 3.434 2.741 2.590 2.409 2.024 1.821 1.809 1.809 1.809
190 5.773 4.800 3.547 2.793 2.644 2.464 2.083 1.882 1.809 1.809 1.809
195 5.884 4.928 3.659 2.844 2.699 2.519 2.142 1.944 1.809 1.809 1.809
200 5.994 5.057 3.772 2.896 2.754 2.574 2.201 2.005 1.809 1.809 1.809
205 6.105 5.186 3.885 2.948 2.809 2.630 2.260 2.067 1.809 1.809 1.809
210 6.216 5.314 3.997 3.000 2.863 2.685 2.319 2.129 1.809 1.809 1.809
215 6.326 5.443 4.110 3.052 2.918 2.740 2.378 2.190 1.841 1.809 1.809
220 6.437 5.572 4.223 3.103 2.973 2.795 2.436 2.252 1.908 1.809 1.809
225 6.548 5.701 4.335 3.155 3.028 2.851 2.495 2.313 1.975 1.809 1.809
230 6.658 5.839 4.448 3.207 3.083 2.906 2.554 2.375 2.042 1.809 1.809
235 6.769 5.979 4.659 3.371 3.137 2.961 2.613 2.437 2.109 1.809 1.809
240 6.880 6.118 5.043 3.625 3.192 3.016 2.672 2.498 2.176 1.809 1.809
245 6.991 6.258 5.427 3.879 3.311 3.071 2.731 2.560 2.243 1.809 1.809
Table 13: Rectangular Hollow Columns 90 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 26 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 520°C 550°C 600°C 620°C 650°C 700°C 750°C
50 3.634 3.126 2.559 2.064 1.928 1.809 1.809 1.809 1.809 1.809 1.809
55 3.851 3.305 2.716 2.178 2.023 1.882 1.809 1.809 1.809 1.809 1.809
60 4.069 3.484 2.872 2.292 2.119 1.959 1.809 1.809 1.809 1.809 1.809
65 4.286 3.662 3.028 2.405 2.214 2.037 1.809 1.809 1.809 1.809 1.809
70 4.504 3.841 3.184 2.519 2.309 2.115 1.852 1.809 1.809 1.809 1.809
75 4.658 4.019 3.341 2.633 2.405 2.193 1.913 1.819 1.809 1.809 1.809
80 4.806 4.198 3.497 2.747 2.500 2.271 1.973 1.873 1.809 1.809 1.809
85 4.955 4.376 3.653 2.860 2.596 2.349 2.034 1.926 1.809 1.809 1.809
90 5.104 4.543 3.809 2.974 2.691 2.427 2.094 1.979 1.809 1.809 1.809
95 5.253 4.658 3.965 3.088 2.786 2.504 2.155 2.033 1.834 1.809 1.809
100 5.401 4.774 4.122 3.202 2.882 2.582 2.216 2.086 1.884 1.809 1.809
105 5.550 4.889 4.278 3.347 2.977 2.660 2.276 2.139 1.935 1.809 1.809
110 5.699 5.005 4.434 3.502 3.072 2.738 2.337 2.193 1.985 1.809 1.809
115 5.850 5.121 4.574 3.658 3.168 2.816 2.397 2.246 2.036 1.809 1.809
120 6.001 5.236 4.693 3.813 3.288 2.894 2.458 2.299 2.087 1.809 1.809
125 6.152 5.352 4.812 3.969 3.453 2.972 2.518 2.352 2.137 1.820 1.809
130 6.303 5.467 4.931 4.124 3.619 3.049 2.579 2.406 2.188 1.872 1.809
135 6.454 5.583 5.051 4.279 3.784 3.127 2.640 2.459 2.238 1.923 1.809
140 6.606 5.699 5.170 4.435 3.950 3.205 2.700 2.512 2.289 1.975 1.809
145 6.757 5.846 5.289 4.578 4.116 3.336 2.761 2.566 2.339 2.027 1.809
150 6.908 6.001 5.408 4.708 4.281 3.493 2.821 2.619 2.390 2.079 1.809
155 7.059 6.156 5.528 4.837 4.447 3.649 2.882 2.672 2.440 2.131 1.809
160 7.210 6.311 5.647 4.966 4.597 3.806 2.942 2.726 2.491 2.183 1.809
165 7.362 6.466 5.767 5.096 4.735 3.962 3.003 2.779 2.541 2.235 1.809
170 7.513 6.621 5.890 5.225 4.874 4.119 3.064 2.832 2.592 2.287 1.835
175 7.664 6.776 6.012 5.354 5.012 4.275 3.124 2.886 2.642 2.339 1.892
180 - 6.931 6.135 5.483 5.150 4.432 3.185 2.939 2.693 2.391 1.950
185 - 7.085 6.257 5.613 5.288 4.589 3.264 2.992 2.743 2.443 2.007
190 - 7.240 6.379 5.742 5.427 4.748 3.399 3.045 2.794 2.495 2.065
195 - 7.395 6.502 5.871 5.565 4.907 3.533 3.099 2.844 2.546 2.122
200 - 7.550 6.624 6.000 5.703 5.066 3.668 3.152 2.895 2.598 2.180
205 - 7.705 6.747 6.129 5.842 5.225 3.803 3.205 2.945 2.650 2.237
210 - - 6.869 6.258 5.980 5.384 3.938 3.335 2.996 2.702 2.294
215 - - 6.992 6.387 6.119 5.543 4.072 3.530 3.046 2.754 2.352
220 - - 7.114 6.516 6.257 5.702 4.207 3.724 3.097 2.806 2.409
225 - - 7.236 6.645 6.395 5.866 4.342 3.919 3.148 2.858 2.467
230 - - 7.359 6.774 6.534 6.032 4.476 4.114 3.198 2.910 2.524
235 - - 7.481 6.903 6.672 6.198 4.880 4.309 3.340 2.962 2.581
240 - - 7.604 7.031 6.811 6.363 5.413 4.503 3.639 3.014 2.639
245 - - 7.726 7.160 6.949 6.529 5.791 5.021 3.937 3.066 2.696
Table 14: Rectangular Hollow Columns 120 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 27 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 520°C 550°C 600°C 620°C 650°C 700°C 750°C
50 6.480 4.936 4.405 3.945 3.772 3.535 3.162 2.790 2.651 2.088 1.814
55 6.480 5.470 4.759 4.212 4.027 3.768 3.365 3.090 2.856 2.264 1.922
60 - 6.004 5.113 4.480 4.282 4.001 3.569 3.390 3.060 2.439 2.030
65 - 6.340 5.466 4.751 4.536 4.234 3.773 3.586 3.262 2.615 2.138
70 - 6.677 5.802 5.022 4.776 4.467 3.976 3.781 3.451 2.790 2.246
75 - 7.014 6.093 5.293 5.016 4.673 4.180 3.977 3.640 2.966 2.354
80 - 7.350 6.383 5.565 5.255 4.872 4.383 4.172 3.829 3.141 2.462
85 - 7.687 6.674 5.824 5.495 5.070 4.567 4.368 4.018 3.320 2.569
90 - - 6.964 6.068 5.734 5.268 4.712 4.550 4.207 3.503 2.677
95 - - 7.255 6.312 5.965 5.466 4.856 4.685 4.396 3.686 2.785
100 - - 7.545 6.556 6.196 5.664 5.000 4.820 4.566 3.868 2.893
105 - - - 6.800 6.427 5.880 5.144 4.955 4.700 4.051 3.001
110 - - - 7.044 6.658 6.103 5.289 5.091 4.834 4.234 3.109
115 - - - 7.287 6.889 6.326 5.433 5.226 4.968 4.416 3.217
120 - - - 7.531 7.119 6.549 5.577 5.361 5.102 4.578 3.373
125 - - - - 7.350 6.772 5.723 5.496 5.235 4.712 3.535
130 - - - - 7.581 6.995 6.001 5.631 5.369 4.846 3.698
135 - - - - - 7.218 6.279 5.815 5.503 4.980 3.860
140 - - - - - 7.441 6.557 6.090 5.637 5.114 4.023
145 - - - - - 7.665 6.835 6.366 5.807 5.248 4.185
150 - - - - - - 7.113 6.642 6.037 5.382 4.348
155 - - - - - - 7.390 6.917 6.268 5.516 4.510
160 - - - - - - 7.668 7.193 6.498 5.649 4.662
165 - - - - - - - 7.469 6.728 5.798 4.813
170 - - - - - - - - 6.958 5.961 4.965
175 - - - - - - - - 7.188 6.125 5.116
180 - - - - - - - - 7.418 6.289 5.267
185 - - - - - - - - 7.649 6.453 5.418
190 - - - - - - - - - 6.617 5.569
195 - - - - - - - - - 6.780 5.720
200 - - - - - - - - - 6.944 5.867
205 - - - - - - - - - 7.108 6.013
210 - - - - - - - - - 7.272 6.160
215 - - - - - - - - - 7.435 6.307
220 - - - - - - - - - 7.599 6.453
225 - - - - - - - - - - 6.600
230 - - - - - - - - - - 6.746
235 - - - - - - - - - - 6.893
240 - - - - - - - - - - 7.040
245 - - - - - - - - - - 7.186
Table 15: Rectangular Hollow Columns 180 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 28 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 520°C 550°C 600°C 650°C 700°C 750°C
50 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
55 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
60 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
65 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
70 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
75 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
80 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
85 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
90 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
95 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
100 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
105 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
110 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
115 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
120 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
125 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
130 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
135 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
140 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
145 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
150 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
155 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
160 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
165 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
170 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
175 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
180 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
185 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
190 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
195 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
200 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
205 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
210 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
215 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
220 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
225 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
Table 16: Circular Hollow Columns 30 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 29 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 520°C 550°C 600°C 650°C 700°C 750°C
50 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
55 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
60 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
65 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
70 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
75 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
80 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
85 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
90 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
95 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
100 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
105 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
110 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
115 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
120 1.857 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
125 1.933 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
130 2.010 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
135 2.087 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
140 2.164 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
145 2.240 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
150 2.317 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
155 2.394 1.854 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
160 2.471 1.935 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
165 2.547 2.016 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
170 2.624 2.097 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
175 2.701 2.178 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
180 2.778 2.260 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
185 2.854 2.341 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
190 2.931 2.422 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
195 3.008 2.503 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
200 3.085 2.584 1.861 1.796 1.796 1.796 1.796 1.796 1.796 1.796
205 3.161 2.665 1.954 1.796 1.796 1.796 1.796 1.796 1.796 1.796
210 3.238 2.747 2.048 1.796 1.796 1.796 1.796 1.796 1.796 1.796
215 3.360 2.828 2.141 1.796 1.796 1.796 1.796 1.796 1.796 1.796
220 3.483 2.909 2.234 1.796 1.796 1.796 1.796 1.796 1.796 1.796
225 3.606 2.990 2.328 1.796 1.796 1.796 1.796 1.796 1.796 1.796
Table 17: Circular Hollow Columns 60 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 30 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 520°C 550°C 600°C 650°C 700°C 750°C
50 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
55 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
60 1.900 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
65 2.197 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
70 2.494 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
75 2.791 1.880 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
80 3.088 2.029 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
85 3.351 2.179 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
90 3.577 2.329 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
95 3.804 2.479 1.872 1.796 1.796 1.796 1.796 1.796 1.796 1.796
100 4.030 2.628 1.983 1.796 1.796 1.796 1.796 1.796 1.796 1.796
105 4.257 2.778 2.095 1.796 1.796 1.796 1.796 1.796 1.796 1.796
110 4.484 2.928 2.207 1.796 1.796 1.796 1.796 1.796 1.796 1.796
115 4.646 3.078 2.319 1.796 1.796 1.796 1.796 1.796 1.796 1.796
120 4.797 3.227 2.430 1.796 1.796 1.796 1.796 1.796 1.796 1.796
125 4.948 3.406 2.542 1.796 1.796 1.796 1.796 1.796 1.796 1.796
130 5.098 3.587 2.654 1.871 1.860 1.796 1.796 1.796 1.796 1.796
135 5.249 3.769 2.765 1.954 1.943 1.796 1.796 1.796 1.796 1.796
140 5.400 3.950 2.877 2.036 2.027 1.796 1.796 1.796 1.796 1.796
145 5.550 4.132 2.989 2.119 2.110 1.858 1.796 1.796 1.796 1.796
150 5.701 4.313 3.100 2.202 2.193 1.942 1.796 1.796 1.796 1.796
155 5.802 4.494 3.212 2.284 2.277 2.027 1.796 1.796 1.796 1.796
160 5.886 4.607 3.317 2.367 2.360 2.112 1.796 1.796 1.796 1.796
165 5.969 4.709 3.421 2.450 2.443 2.196 1.796 1.796 1.796 1.796
170 6.053 4.810 3.524 2.532 2.527 2.281 1.796 1.796 1.796 1.796
175 6.137 4.912 3.627 2.615 2.610 2.365 1.842 1.796 1.796 1.796
180 6.220 5.013 3.731 2.698 2.693 2.450 1.933 1.796 1.796 1.796
185 6.304 5.115 3.834 2.780 2.777 2.535 2.024 1.796 1.796 1.796
190 6.388 5.217 3.937 2.863 2.860 2.619 2.115 1.796 1.796 1.796
195 6.471 5.318 4.041 2.946 2.943 2.704 2.206 1.796 1.796 1.796
200 6.555 5.420 4.144 3.028 3.027 2.789 2.297 1.796 1.796 1.796
205 6.639 5.521 4.247 3.111 3.110 2.873 2.388 1.832 1.796 1.796
210 6.722 5.623 4.351 3.194 3.193 2.958 2.479 1.926 1.796 1.796
215 6.806 5.724 4.454 3.311 3.311 3.042 2.570 2.019 1.796 1.796
220 6.889 5.902 4.626 3.472 3.472 3.127 2.661 2.112 1.796 1.796
225 6.973 6.094 4.918 3.633 3.633 3.212 2.752 2.206 1.796 1.796
Table 18: Circular Hollow Columns 90 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 31 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 520°C 550°C 600°C 650°C 700°C 750°C
50 2.318 2.130 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
55 3.094 2.664 1.796 1.796 1.796 1.796 1.796 1.796 1.796 1.796
60 3.870 3.198 1.946 1.796 1.796 1.796 1.796 1.796 1.796 1.796
65 4.646 3.548 2.291 1.796 1.796 1.796 1.796 1.796 1.796 1.796
70 5.268 3.883 2.635 1.866 1.796 1.796 1.796 1.796 1.796 1.796
75 5.791 4.217 2.980 2.073 1.871 1.796 1.796 1.796 1.796 1.796
80 6.004 4.559 3.321 2.281 2.041 1.796 1.796 1.796 1.796 1.796
85 6.218 4.972 3.654 2.488 2.210 1.913 1.796 1.796 1.796 1.796
90 6.431 5.386 3.986 2.696 2.379 2.045 1.796 1.796 1.796 1.796
95 6.644 5.759 4.319 2.904 2.548 2.177 1.796 1.796 1.796 1.796
100 6.857 5.890 4.624 3.111 2.717 2.308 1.840 1.796 1.796 1.796
105 7.070 6.021 4.888 3.374 2.887 2.440 1.952 1.796 1.796 1.796
110 7.283 6.151 5.151 3.728 3.056 2.572 2.064 1.796 1.796 1.796
115 7.496 6.282 5.415 4.082 3.225 2.703 2.176 1.796 1.796 1.796
120 7.709 6.413 5.678 4.436 3.582 2.835 2.288 1.815 1.796 1.796
125 - 6.544 5.814 4.629 3.956 2.967 2.399 1.903 1.796 1.796
130 - 6.675 5.911 4.772 4.331 3.098 2.511 1.991 1.796 1.796
135 - 6.806 6.008 4.914 4.573 3.230 2.623 2.080 1.796 1.796
140 - 6.937 6.105 5.057 4.681 3.432 2.735 2.168 1.802 1.796
145 - 7.068 6.202 5.200 4.788 3.640 2.846 2.257 1.883 1.796
150 - 7.199 6.300 5.342 4.896 3.848 2.958 2.345 1.963 1.796
155 - 7.329 6.397 5.485 5.004 4.056 3.070 2.433 2.043 1.796
160 - 7.460 6.494 5.627 5.111 4.264 3.182 2.522 2.124 1.796
165 - 7.591 6.591 5.764 5.219 4.472 3.294 2.610 2.204 1.808
170 - 7.722 6.688 5.880 5.326 4.615 3.407 2.698 2.284 1.885
175 - - 6.785 5.996 5.434 4.739 3.520 2.787 2.365 1.962
180 - - 6.882 6.111 5.541 4.862 3.633 2.875 2.445 2.038
185 - - 6.979 6.227 5.649 4.986 3.746 2.963 2.525 2.115
190 - - 7.076 6.342 5.766 5.109 3.859 3.052 2.606 2.192
195 - - 7.173 6.458 5.937 5.233 3.971 3.140 2.686 2.268
200 - - 7.270 6.573 6.108 5.356 4.084 3.229 2.766 2.345
205 - - 7.367 6.689 6.279 5.480 4.197 3.376 2.847 2.422
210 - - 7.464 6.805 6.450 5.603 4.310 3.531 2.927 2.499
215 - - 7.561 6.920 6.621 5.727 4.423 3.687 3.007 2.575
220 - - 7.658 7.036 6.793 5.998 4.571 3.843 3.088 2.652
225 - - - 7.151 6.964 6.286 4.934 3.999 3.168 2.729
Table 19: Circular Hollow Columns 120 Minutes
Thickness (mm) Required for a Design Temperature of
This certificate is the property of Warrington Certification Limited, part of Exova (UK) Ltd. Registered office: Lochend Industrial Estate, Newbridge, Midlothian, EH28 8PL, UK. Registered in Scotland, No. SC 70429
CERTIFICATE No CF 5243 JOTUN A/S
Page 32 of 32 Signed
Issued: 13th
May 2014 Revised: 25
th July 2014
Valid to: 12th
May 2019
Steelmaster 1200WF
Thickness is intumescent only.
Section
Factor up
to m -1
350°C 400°C 450°C 500°C 520°C 550°C 600°C 650°C 700°C 750°C
50 6.620 1.796 3.193 1.958 1.796 1.796 1.796 1.796 1.796 1.796
55 6.620 3.081 3.630 2.518 2.015 1.796 1.796 1.796 1.796 1.796
60 - 4.620 4.067 3.078 2.528 1.951 1.796 1.796 1.796 1.796
65 - 6.159 4.503 3.524 3.041 2.352 1.796 1.796 1.796 1.796
70 - 6.604 4.520 3.923 3.485 2.753 1.896 1.796 1.796 1.796
75 - 7.049 5.860 4.322 3.884 3.154 2.165 1.796 1.796 1.796
80 - 7.494 6.151 4.800 4.284 3.553 2.434 1.796 1.796 1.796
85 - - 6.443 5.356 4.722 3.951 2.703 1.894 1.796 1.796
90 - - 6.735 5.801 5.216 4.350 2.972 2.079 1.796 1.796
95 - - 7.026 5.997 5.710 4.750 3.242 2.263 1.796 1.796
100 - - 7.318 6.193 5.899 5.152 3.672 2.448 1.913 1.796
105 - - 7.610 6.389 6.068 5.553 4.103 2.632 2.046 1.796
110 - - - 6.585 6.237 5.818 4.528 2.817 2.179 1.796
115 - - - 6.781 6.406 5.965 4.793 3.001 2.312 1.796
120 - - - 6.977 6.575 6.111 5.058 3.186 2.445 1.796
125 - - - 7.173 6.744 6.257 5.322 3.682 2.579 2.116
130 - - - 7.369 6.913 6.404 5.587 4.308 2.712 2.204
135 - - - 7.565 7.082 6.550 5.786 4.594 2.845 2.292
140 - - - - 7.251 6.696 5.895 4.707 2.978 2.380
145 - - - - 7.420 6.842 6.004 4.819 3.112 2.468
150 - - - - 7.590 6.989 6.113 4.931 3.244 2.555
155 - - - - - 7.135 6.222 5.044 3.350 2.643
160 - - - - - 7.281 6.331 5.156 3.457 2.731
165 - - - - - 7.428 6.440 5.269 3.563 2.819
170 - - - - - 7.574 6.549 5.381 3.670 2.907
175 - - - - - 7.720 6.658 5.493 3.776 2.995
180 - - - - - - 6.767 5.606 3.883 3.083
185 - - - - - - 6.875 5.718 3.989 3.171
190 - - - - - - 6.984 5.893 4.096 3.271
195 - - - - - - 7.093 6.082 4.202 3.412
200 - - - - - - 7.202 6.271 4.309 3.552
205 - - - - - - 7.311 6.461 4.415 3.693
210 - - - - - - 7.420 6.650 4.529 3.833
215 - - - - - - 7.529 6.839 4.994 3.974
220 - - - - - - 7.638 7.029 5.459 4.115
225 - - - - - - - 7.218 5.907 4.255
Table 20: Circular Hollow Columns 150 Minutes
Thickness (mm) Required for a Design Temperature of