NSW GOVERNMENT Health Certificate of Accreditation Sewage Management Facility Septic Tanks & Collection Wells This Certificate of Accreditation is issued by the Secretary of the NSW Ministry of Health pursuant to Clause 41(1) of the Local Government (General) Regulation 2005. Manufacturer: Central Coast Septics Pty Ltd Of: 5 Marklea Close, Tuggerah, NSW, 2259 The Septic Tanks, Collection Wells and Pump Well as described in the following Schedule have been accredited as sewage management facilities for use in single domestic premises in NSW. LLA Director, Environmental Health for Secretary (delegation PH335) Issued: 8 January 2019 Certificate No: STCW015 Expires: 31 December 2022

Certificate of Accreditation - Ministry of Health

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Certificate of Accreditation - Ministry of Health

NSW GOVERNMENT Health

Certificate of Accreditation Sewage Management Facility

Septic Tanks & Collection Wells

This Certificate of Accreditation is issued by the Secretary of the NSW Ministry of Health pursuant to Clause 41(1) of the Local Government (General) Regulation 2005.

Manufacturer: Central Coast Septics Pty Ltd

Of: 5 Marklea Close, Tuggerah, NSW, 2259

The Septic Tanks, Collection Wells and Pump Well as described in the following Schedule have been accredited as sewage management facilities for use in single domestic premises in NSW.

LLA

Director, Environmental Health for Secretary (delegation PH335)

Issued: 8 January 2019 Certificate No: STCW015 Expires: 31 December 2022

Page 2: Certificate of Accreditation - Ministry of Health

oto. Ana* NSW Health GOVERNMENT

Accreditation Schedule The Certificate of Accreditation applies to the following

Septic Tanks and Collection Wells

Model Description Size

Septic Tank Vertical axis type precast concrete with 2300 L steel reinforcing mesh with lid, partition, 2800 L

access cover, inlet and outlet fittings. Burial 4000 L

depth of the tank lid is restricted to 0 mm 7100 L

Collection Well Vertical axis type precast concrete 2050 L with steel reinforcing mesh with 2300 L

lid, access cover and inlet fitting 2800 L

Burial depth of the tank lid is restricted to 4000 L

0 mm 5200L

7100 L

8500 L

10,000 L

Combined Septic Vertical axis type precast concrete 2300L/4600L

Tank/ with steel reinforcing mesh 3050L/4050L

Collection Well Certification applies only to the

construction of the tank, it does not include

the lid and any internal fittingssuch as partitions

Pump well Vertical axis type precast concrete 900 L

with steel reinforcing mesh, with lid, access 2000 L

cover and inlet fitting

Page 3: Certificate of Accreditation - Ministry of Health

GLDBAL CEPTIf ./.1101. LID Registered Office; 5 Marklea Close Tuggerah NSW 2259 PO Box 245 Wyong NSW 2259 Ph; (02) 4352 2154

Central Coast Septics Pty. Ltd.

Certified Product AS/NZS 1546.1:2008

Registration Number. 464

ABN 63 000 605 069

MANUFACTURES OF SEPTIC TANKS AND COLLECTION WELLS emai;[email protected]

A SECTION A-A

INSTALLATIONz

NOTE THAT THE TANK IS TO BE FOUNDED ON A BED OF UNIFORMLY COMPACTED

AND LEVELLED SAND AT LEAST 100MM THICK.

SPECIFICATIONS;

BASE; 80mm thick reinforced with one layer of SL72 reinforcement complying AS/NZS 4671

LID; 80mm thick reinforced with SL72 bottom plus N12 trimmer bars sitting on top of SL72. This lid has not been designed to carry fill or other surcharge loading apart from pedestrain traffic.

CONCRETE COVER; As per AS/NZS 1546-1;2008 minimum concrete cover is to be 20mm.

CAPACITY; Single Tank - Septic APPROVED Combined Collection Well Capacity 7100 litres - 8 JAN 2019

Access Holes (600mm) NSW MINISTRY OF HEALTH

Inlet 100mm PVC

Inlet Partitions located accordingly 100mm Outlet

100mm

(A) mm

(B) mm

(C) mm

(D) mm

CAPACITY Litres

2400 1650 50 80 710

INLET

(B)

1650

Page 4: Certificate of Accreditation - Ministry of Health

Central Coast Septics Pty. Ltd.

Registered Office; 5 Marklea Close Tuggerah NSW 2259 PO Box 245 Wyong NSW 2259 Ph; (02) 4352 2154

Certified Product AS/NZS 1546 12068

Registration Number.

464

ABN 63 000 605 069

MANUFACTURES OF SEPTIC TANKS AND COLLECTION WELLS emai;[email protected]

SPECIFICATIONS;

BASE; 80mm thick reinforced with one layer of SL72 reinforcement complying AS/NZS 4671

LID; 80mm thick reinforced with SL72 bottom plus N12 trimmer bars sitting on top of SL72. This lid has not been designed to carry fill or other surcharge loading apart from pedestrain traffic.

CONCRETE

COVER; As per AS/NZS 1546-1;2008 minimum concrete cover is to be 20mm.

Combined Collection Well Capacity 7100 litres

APPROVED

- 8 JAN 2019

NSW MINISTRY OF HEALTH

Inlet 100mm PVC

Inlet 100m

COLLECTION WELL

(A) mm

(B) n-m

(C) mm

(D) mm

CAPACITY Litres

2400 1650 50 80 7100

(-3 o INLET

(B) 1650

D A

SECTION A-A

INSTALLATION; NOTE THAT THE TANK IS TO BE

FOUNDED ON A BED OF UNIFORMLY COMPACTED AND LEVELLED SAND AT LEAST 100MM THICK.

Inspection Covers

Page 5: Certificate of Accreditation - Ministry of Health

Certified Product AS/NZS 1546.172008

Registration Number:

464

emai;info©centralcoastseptics.com.au

ABN 63 000 605 069

MANUFACTURES OF SEPTIC TANKS AND COLLECTION WELLS

A SECTION A-A

Central Coast (NV Septics Pty. Ltd.

Registered Office; 5 Marklea Close Tuggerah NSW 2259 PO Box 245 Wyong NSW 2259 Ph; (02) 4352 2154

SPECIFICATIONS;

BASE; 80mm thick reinforced with one layer of SL72 reinforcement complying AS/NZS 4671

LID; 80mm thick reinforced with SL72 bottom plus N12 trimmer bars sitting on top of SL72. This lid has not been designed to carry fill or other surcharge loading apart from pedestrain traffic.

CONCRETE

COVER; As per AS/NZS 1546-1;2008 minimum concrete cover is to be 20mm.

Combined Collection 7100 litres 8500 litres

Inspection Covers

Inlet 100mm PVC

COLLECTION WELL

(A) (B) (C) (D) CAPACITY mm mm mm mm Litres

2400 2000 50 80 8500

2400 1650 50 80 7100

INSTALLATION;

NOTE THAT THE TANK IS TO BE FOUNDED ON A BED OF UNIFORMLY COMPACTED

AND LEVELLED SAND AT LEAST 100MM THICK.

(N/

Inlet 100m

INLET (B)

2000 or

1650

Page 6: Certificate of Accreditation - Ministry of Health

Central Coast Septics Pty. Ltd.

Registered Office; 5 Marklea Close Tuggerah NSW 2259 PO Box 245 Wyong NSW 2259 Ph; (02) 4352 2154

Certified Product AS/NZS 1546 12008

Registration Number.

464

ABN 63 000 605 069

MANUFACTURES OF SEPTIC TANKS AND COLLECTION WELLS emai;[email protected]

SPECIFICATIONS;

BASE; 80mm thick reinforced with one layer of SL72 reinforcement complying AS/NZS 4671

LID; 80mm thick reinforced with SL72 bottom plus N12 trimmer bars sitting on top of SL72. This lid has not been designed to carry fill or other surcharge loading apart from pedestrain traffic.

CONCRETE

COVER; As per AS/NZS 1546-1;2008 minimum concrete cover is to be 20mm.

CAPACITY; Single Tank Septic/Collection 1-5 person capacity;- SEPTIC (2300)- COLLECTION WELL (4600 litres) 6-10 person capacity;- SEPTIC (3050)- COLLECTION WELL (4050 litres)

APPROVED

- 8 JAN 2019

MINISTRY C

Access Holes (600mm)

ZC7D Inspectio overs

eter)

Inlet 100mm PVC

Inlet 100 mm PVC

J_

Alk Inlet 100mn-L

f

cz) 0

i

INLET

1650

7-

-4 ___...... . .

Partitions located accordingly

(A) mm

(B) mm

(C) mm

(D) mm

CAPACITY Litres

2400 1650 50 80 7100

INSTALLATION;

NOTE THAT THE TANK IS TO BE FOUNDED ON A BED OF UNIFORMLY COMPACTED

AND LEVELLED SAND AT LEAST 100MM THICK.

Page 7: Certificate of Accreditation - Ministry of Health

SPECIFICATIONS;

BASE; 80mm thick reinforced with one layer of SL72 reinforcement complying AS/NZS 4671

LID; 120mm thick reinforced with SL72 bottom plus N12 trimmer bars sitting on top of SL72. This lid has not been designed to carry fill or other surcharge loading apart from pedestrain traffic.

CONCRETE COVER; As per AS/NZS 1546-1;2008 minimum concrete cover is to be 20mm.

Combined Collection Well Capacity 10,000 litres

2120

A SECTION A-A

COLLECTION WELL

(A) (B) (C) (D) CAPACITY min 111111 MITI 11111111 Litres

2450 2320 50 80 10,000

INSTALLATION;

NOTE THAT THE TANK IS TO BE FOUNDED ON A BED OF UNIFORMLY COMPACTED

AND LEVELLED SAND AT LEAST 100MM THICK.

1

Inlet r 100mm

CD 1---in (.1

INLET c) (B) Q (NI 2320 CN

Central Coast Septics Pty. Ltd.

ABN 63 000 605 069

MANUFACTURES OF SEPTIC TANKS AND COLLECTION WELLS

Registered Office; 5 Marklea Close Tuggerah NSW 2259 PO Box 245 Wyong NSW 2259 Ph; (02) 4352 2154

Certified Product AS/NZS 1546 1:2008 Registration Number

464

emai;info@centralc,oastseptics.com.au

Page 8: Certificate of Accreditation - Ministry of Health

Registered Office; 5 Marklea Close Tuggerah NSW 2259 PO Box 245 Wyong NSW 2259 Ph; (02) 4352 2154

Central Coast Septics Pty. Ltd.

Certified Product AS/NZS 1546.1:2008

Registration Number:

464

ABN 63 000 605 069

MANUFACTURES OF SEPTIC TANKS AND COLLECTION WELLS emai;[email protected]

A SECTION A-A

1420

SPECIFICATION%

BASE; 80mm thick reinforced with one layer of SL72 reinforcement complying AS/NZS 4671

LID; 120mm thick reinforced with SL72 bottom plus N12 trimmer bars sitting on top of SL72. This lid has not been designed to carry fill or other surcharge loading apart from pedestrain traffic.

CONCRETE

COVER; As per AS/NZS 1546-1;2008 minimum concrete cover is to be 20mm.

Combined Collection Well Capacity 5,200 litres

APPROVED

- 8 JAN 2019

(A) mm

(B) mm

(C) ITIM

(D) MM

CAPACITY Litres

2150 1650 50 80 5,200

INSTALLATION: NOTE THAT THE TANK IS TO BE

FOUNDED ON A BED OF UNIFORMLY COMPACTED AND LEVELLED SAND AT LEAST 100MM THICK.

Inlet 100mm •

-----„, NSW MINISTRY OF HEA

COLLECTION WELL

cy)

INLET o (B) -01650

Page 9: Certificate of Accreditation - Ministry of Health

Coddled Product AS/NZS 1546 1:2008 Registration Number:

464

Registered Office; 5 Marklea Close Tuggerah NSW 2259 PO Box 245 Wyong NSW 2259 Ph; (02) 4352 2154

e mai; [email protected]

Central Coast Septics Pty. Ltd.

ABN 63 000 605 069

MANUFACTURES OF SEPTIC TANKS AND COLLECTION WELLS

Inlet I DOmm

PVC Outset morn

PVC

150m INSPECTION COVERS

65

APPROVED

- 8 JAN 2019

W MINISTRY OF HEA

A

1650

SEPTIC

1115 BCD

50

TANK

65

LITRES

2050 1650 1200 50 65 2300 1830 1220 50 65 2800 1970 1440 50 65 4000

Capacity table in millimetres

A 1650

COLLECTION

1065 BCD

50

WELL

65

LITRES

2050 1650 1150 50 65 2300 1830 1170 50 65 2800 1970 1390 50 65 4000

Capacity table in millimetres

SPECIFICATIONS: *Reinforcement comp y with AS/NZS 4671

*Partition wall only in sep ic tanks over 2050 litres. *Concrete mimimum compressive strengtth 32 MPA -- 28 days reinforced with

steel mesh for base, walls and lids_ *The lid has not been designed to carry fill or any other surcharge loading

apart from pedestrian. *Tanks comply with AS/NZS 1546-1:2008

OVERALL

MI= 1605 '1750 '1605 1605

'1750 '1935

1818 2070

Page 10: Certificate of Accreditation - Ministry of Health

GLOBAL CERT., /CATON PrI, LTD

Certified Product AS/NZS 1546.1:2008 Registration Number:

464

Registered Office; 5 Marklea Close Tuggerah NSW 2259 PO Box 245 Wyong NSW 2259 Ph; (02) 4352 2154

ema i; [email protected]

Central Coast Septics Pty. Ltd.

ABN 63 000 605 069

MANUFACTURES OF SEPTIC TANKS AND COLLECTION WELLS

Tank Manufacture; Central Coast Septics P/L Single Tank Collection Well / Lid AS/NZS 1546.1

SPECIFICATIONS

BASE. 65mm thick reinforced with steel fibre as per AS/NZ 1546,1:2008

LID. 120mm thick reinforced with steel fibre as per AS/NZ 1546.1:2008 This lid has been designed to carry fill or pedestrian traffic.

CONCRETE COVER; As per AS/NZS 1546.1 minimum

concrete cover is to be 20mm

Cl INSTALLATION

NOTE that the tank is to be found on a bed of uniformly compacted and levelled sand at least 100mm thick

APPROVED

- 8 JAN 2019

NSW MINISTRY OF HEALTH

C2

CAPACITY A B Cl C2 D E F

E s900 935mm 2065mm 575 995 120 65 60

A