Manual
Central CO
CO Control Panel
Centrale CO
REF.
CCO122 / CCO222 / CCO322 / CCO422
CCO110 / CCO115
CCO122 / CCO222 / CCO322 / CCO422 CCO110 / CCO115
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS FIRE PROTECTION MANUFACTURER - FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 1 -
CONTENIDO / CONTENTS
CASTELLANO ......................................................................................... Pag. 2
CENTRALES CCO122, CCO222, CCO322 Y CCO422 ................................................................................ Pag. 2
CENTRALES CCO110 Y CCO115 ... ........................... Pag. 7
ENGLISH .................................................................................................... Pag. 10
CONTROL PANELS CCO122, CCO222, CCO322 & CCO422 ............................................................................... Pag. 10
CONTROL PANELS CCO110 & CCO115 .............................. Pag. 15
PORTUGUS... Pag. 18
CENTRALE CCO 122, CCO 222, CCO 322 & CCO442... Pag 18
CENTRALE CCO 122, CCO 222, CCO 322 & CCO442 Dupla ventilao e (OPCIONAL) baterias. Pag 22
CENTRALE CCO110 &CCO115........Pag 23
MAR11
CCO122 / CCO222 / CCO322 / CCO422 CASTELLANO
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 2 -
CENTRALES CCO122, CCO222, CCO322 Y CCO422
Indicadores luminosos
A Led verde: Indica que el sistema est operativo. B Led rojo: Indica la activacin del Rel de Alarma. C Led verde: Indica que se ha activado el Rel de Ventilacin. D Led mbar: Indica que se ha superado el Nivel de Ventilacin. E Led mbar: Indica una avera o una irregularidad en la lnea de deteccin.
Pulsadores de mando
1 y 2. : Permiten el desplazamiento vertical por las diferentes opciones y lneas del men. Tambin permite incrementar ( ) o decrementar ( ) los parmetros numricos.
3. ESC/MENU: Permite retroceder una pgina de pantalla. 4. ENTER: Permite avanzar hacia la siguiente pgina de pantalla o
confirmar una seleccin. Manejo de la central
En condiciones normales de operacin la central muestra la pantalla principal, visualizando la concentracin de CO en cada zona y el estado de la lnea de deteccin y los rels de ventilacin y alarma.
ZONA 1 AnuladaZONA 2 Sin SensoresZONA 3 AnuladaZONA 4 Anulada
Z1: 100 Vent. Man. HZ2: 250 Vent. Man. FZ3: 065 Niv. V. :050Z4: 300 Vent. Autom.
Nmero de zona
Concentracin de CO (ppm)
Estado de la zona
CCO122 / CCO222 / CCO322 / CCO422 CASTELLANO
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 3 -
Pulsando la tecla men se accede a las pantallas de men. Existen 5 pantallas de men a las que se puede acceder a travs de las teclas o :
Ventilacin (Activacin Manual/Modo Ventilacin, ver figura 1). Servicio (Zonas On/Off, ver figura 2). Programacin de Ventilacin (Nivel y Retardo, ver figura 3). Programacin de Retardo de Alarmas
(figura 4). Recuperar Datos de Origen (figura 5).
Los datos de origen son los siguientes:
Parmetro Valor Margen
Nivel de Ventilacin: 50 ppm Programable (20 150 ppm) Retardo Ventilacin: 4 min Programable (1 9 min) Retardo Postventilacin: 4 min Fijo Nivel de Alarma: 300 ppm Fijo Retardo Alarma: 15 min Programable (10 30 min)
Las flechas y que aparecen en algunas pantallas de men, indican la existencia de pantallas anteriores y posteriores, respectivamente, a la pantalla actual.
Instalacin
La figura muestra el esquema general de conexionado de los diferentes elementos con la central. Se pueden conectar un mximo de 22 detectores por zona. Se recomienda el uso de cable con una seccin mnima de 1.5 mm2 y la longitud mxima del mismo por zona no debe exceder los 400m, en una distribucin lineal de detectores.
Importante. Los detectores de Monxido de Carbono DCO tienen polaridad.
+-ZONAVENT.
+-ALAR.
+
-
+
-
+
-
+
-
+
-
+
-
Ventilacin
Alarma
Detectores CO (mx. 22)
Estructura por Zona
+-
Alarma Parada [CO]
Nivel de Ventilacin
Nivel de Alarma
Retardo Ventilacin
Ventilacin Activada
Ventilacin Activada
Retardo Postventilacin
Ventilacin Parada
Alarma Activada
Retardo Alarma
Tiempo
CCO122 / CCO222 / CCO322 / CCO422 CASTELLANO
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 4 -
M : A / VENTILACIONActivar Manual
A / VENT. zona 2zona 1
zona 3zona 4
MANUAL A / ZONA 1MODO VENT
fija1 hora
ENTER Seleccin de zona + ENTER
fija + ENTER
ENTER1 hora +
A / ZONA 1VENT. MAN. F
start stop
A / ZONA 1VENT. MAN. H
start stop
ZONA 1Conectada fija
Ventilacion
ZONA 1Manual Parada
Ventilacion
ZONA 1Conectada 1 hora
Ventilacion
ZONA 1Manual Parada
Ventilacion
start + ENTER
stop + ENTER
start + ENTER
stop + ENTER
Figura 1. Pantalla Ventilacin Manual.
M : B / SERVICIOOn / Off Zonas
B / SERV.zona 2zona 1
zona 3zona 4
ON_OFF
ENTER Seleccin de zona + ENTER
ZONA 1 QuedaAnulada
ZONA 1 Queda en Servicio
on + ENTER
ENTERoff +
B / ZONA 1SERVICIO
on off
Figura 2. Pantalla Servicio.
CCO122 / CCO222 / CCO322 / CCO422 CASTELLANO
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 5 -
M : C / PROGRAMACIONVENT: NIvel / Ret
C / PROG. zona 2zona 1
zona 3zona 4
NIVELRETARDO
C / PROG.Nivel: 050 ppm
ZONA 1 C / GRABAR NIVELNO: esc SI: enter
C / PROG. ZONA 1Retardo: 4 min
C / GRABAR RETARDONO: esc SI: enter
ENTER Seleccin de zona + ENTER
nivel + ENTER
ENTERretardo +
C / PROG.ZONA 1
nivel retardo
Seleccin de nivel + ENTER
Seleccin de retardo + ENTER
ENTER
ENTER
ESC
ESC
Zona 1 GrabandoseNivel de ventilacion ... OK
Zona 1 Grabandoseretardo de ventilacion ... OK
C / PROG.ZONA 1
nivel retardo
C / PROG.ZONA 1
nivel retardo
Figura 3. Pantalla Programacin de Ventilacin.
D / GRABA RETARDONO: esc SI: enter
M : D/ PROG. ALARMASRetardo: 10 min
Seleccin de retardo + ENTERENTER
ESC
Zona 1 RetardoAlarma grabandose ... OK
M : D/ PROG. ALARMASRetardo: 10 min
Figura 4. Pantalla Programacin Retardo de Alarmas.
M : E/ RECUPERARDATOS DE ORIGEN
< E / GRABAR DATOS ?NO: esc SI: enter
ENTER
ESC
Zona 1 Datos deorigen grabandose ... OK
M : E/ RECUPERARDATOS DE ORIGEN
Figura 5. Pantalla Recuperar Datos de Origen.
CCO122 / CCO222 / CCO322 / CCO422 CASTELLANO
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 6 -
Doble ventilacin y (OPCIONAL) bateras
Doble ventilacin:
En el caso de que la central disponga de doble ventilacin, el conexionado se debe realizar tal y como se muestra en la figura.
Los datos de origen son los siguientes:
Bateras:
Se deben conectar a la entrada del circuito situado en la parte derecha de la fuente de alimentacin, esta salida est identificada.
Conexin de las dos bateras de 12 V en serie:
Parmetro Valor Margen
Nivel de Ventilacin 1: 50 ppm Programable (20 150 ppm)
Retardo Ventilacin 1: 4 min Programable (1 9 min)
Retardo Postventilacin 1: 4 min Fijo Nivel de Ventilacin 2: 200 ppm Programable
(20 300 ppm) y Nivel ventilacin 1
Retardo Ventilacin 2: 10 min Programable (1 30 min) y Retardo ventilacin 1
Retardo Postventilacin: 4 min Fijo Nivel de Alarma: 300 ppm Fijo Retardo Alarma: 15 min Programable
(10 30 min)
12V12V
-
+
-
+-
Alar VentAlar Vent Zona2 Zona1
+ - + -+ +--Alar VentAlar Vent Zona2 Zona1
+ - + -+ +--
Vent1 Z1
Vent1 Z2
Vent1 Z3( *Z1)
Vent1 Z4( *Z2)
61
R2
K1
Q4
D2D1D3
R3
K2
Q3Q1
R1
K3
R5
K5
R4
1
U5
K4
J4
1
U1
Q5
U3
1
U4
1
U2
D4 D5
Q2
- +ALZ4Z3Z2Z1
Vent2Z4
- +
J1
GND CPU
Vent2 Z2
Vent2 Z3
Vent2 Z1
Vent2 Z4
En caso de que la central sea de 1 o 2 zonas seguir las indicaciones con *
Bateras
+-
BAT
Vent2Z2 Vent2Z3Vent2Z1
Alarma Z4(*Z2)
Alarma Z3(*Z1)
Alarma Z2
Alarma Z1
Alarma Parada [CO]
Nivel de Ventilacin 2
Retardo Ventilacin 1
Ventilacin 1
Ventilacin 1
Retardo Postventilacin 1
Ventilacin 1 Parada
Alarma Activada
Retardo Alarma
Tiempo
Nivel de Alarma
Retardo Ventilacin 2
Ventilacin 2
Ventilacin 2
Retardo Postventilacin
Ventilacin 2
Nivel de Ventilacin 1
CCO110 / CCO115
CASTELLANO
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 7 -
CENTRALES CCO110 Y CCO115
Indicadores luminosos
A Led verde: Indica que el sistema est operativo. B Led rojo: Indica la activacin del Rel de Alarma. C Led verde: Indica que se ha activado el Rel de Ventilacin. D Led mbar: Indica que se ha superado el Nivel de Ventilacin. E Led mbar: Indica una avera o una irregularidad en la lnea de deteccin. F Led verde: Indica que el display muestra concentracin de CO (ppm). G Led verde: Indica que el display muestra el Nivel de Ventilacin. H Led verde: Indica que el display muestra el Retardo de Ventilacin
Pulsadores de mando
1. Seleccin Display: Permite seleccionar el dato mostrado por el display: Concentracin de CO, Nivel de Ventilacin o Retardo de Ventilacin.
2 y 3. : Permiten incrementar ( ) o decrementar ( ) los parmetros numricos
4. ON/OFF Ventilacin Permite activar o desactivar manualmente la ventilacin en cualquier momento
CCO110 / CCO115
CASTELLANO
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 8 -
+-ZONA VENT.
+-ALAR.
+
-
+
-
+
-
+
-
+
-
+
-
Ventilacin
Alarma
Estructura por Zona
+
(max. 15 en CCO115)
Detectores CO
Manejo de la central
La central permite la programacin del Nivel de Ventilacin y del Retardo de Ventilacin mediante las teclas y SELECCION DISPLAY. La tecla ON/OFF VENTILACION MANUAL permite activar/desactivar manualmente la ventilacin en cualquier momento.
Los datos de origen son los siguientes:
Parmetro Valor Margen
Nivel de Ventilacin: 50 ppm Programable (20 150 ppm, en incrementos de 10 ppm)
Retardo Ventilacin: 4 min Programable (1 9 min, en incrementos de 1 min)
Retardo Postventilacin: 4 min Fijo Nivel de Alarma: 300 ppm Fijo Retardo Alarma: 0 min Fijo
Instalacin
La figura muestra el esquema general de conexionado de los diferentes elementos con la central. Se pueden conectar un mximo de 10 detectores por zona en la central CCO110 y 15 en la central CCO115. Se recomienda el uso de cable con una seccin mnima de 1,5mm2 y la longitud mxima del mismo por zona no debe exceder los 400m, en una distribucin lineal de detectores.
Importante. Los detectores de Monxido de Carbono DCO tienen polaridad
Alarma Parada [CO]
Nivel de Ventilacin
Nivel de Alarma
Retardo Ventilacin
Ventilacin Activada
Ventilacin Activada
Retardo Postventilacin
Ventilacin Parada
Alarma Activada
Retardo Alarma
Tiempo
CCO110 / CCO115
CASTELLANO
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 9 -
Doble ventilacin y (OPCIONAL) bateras
Doble ventilacin:
En el caso de que la central disponga de doble ventilacin, dispondremos de dos salidas de ventilacin.
La primera salida de ventilacin est identificada como VENT1, y la segunda ventilacin como VENT2.
El nivel de alarma tambin queda modificado en estas centrales a 200 ppm.
Los datos de origen son los siguientes:
Parmetro Valor Margen
Nivel de Ventilacin 1: 50 ppm Fijo Retardo Ventilacin 1: 1 min Programable
(1 9 min) Retardo Postventilacin 1: 4 min Fijo Nivel de Ventilacin 2: 100 ppm Fijo Retardo Ventilacin 2: 0 min Fijo Retardo Postventilacin: 0 min Fijo Nivel de Alarma: 200 ppm Fijo Retardo Alarma: 0 min Fijo
Bateras:
Las bateras se deben conectar a la entrada de bateras del circuito situada en la parte derecha del circuito fuente de alimentacin, esta salida est identificada.
Conexin de las dos bateras de 12 V en serie:
12V12V
-
+
-
+-
Alarma Parada [CO]
Nivel de Ventilacin 2
Retardo Ventilacin 1
Ventilacin 1
Ventilacin 1
Retardo Postventilacin 1
Ventilacin 1 Parada
Alarma Activada
Retardo Alarma
Tiempo
Nivel de Alarma
Retardo Ventilacin 2
Ventilacin 2
Ventilacin 2
Retardo Postventilacin
Ventilacin 2
Nivel de Ventilacin 1
Alarm OFF
CCO122 / CCO222 / CCO322 / CCO422 ENGLISH
FIRE PROTECTION MANUFACTURER Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 10 -
CCO122, CCO222, CCO322 & CCO422 CONTROL PANELS
Light Indicators
A Green LED: system operating normal. B Red LED: Indicates activation of Alarm Relay. C Green LED: Indicates activation of Ventilation Relay. D Amber LED: Indicates Ventilation Level has been exceed. E Amber LED: Indicates Fault or trouble on detection zone.
External Controls
1 & 2. : To move up and down trough different options and lines of menu. Also, allows to increase ( ) or decrease ( ) numerical parameters.
3. ESC/MENU: To go back a display. 4. ENTER: To move forward next display or confirm a selection
Operation of Control Panel
Under normal condition, display of control panel shows main screen, visualizing CO concentration on each zone, situation of detection zone, and situation of ventilation and alarm relays.
CO Concentration (ppm)
ZONE 1 Disabled
ZONE 3 DisabledZONE 4 Disabled
ZONE 2 No Sensors
Zone information
Z1: 100 Man.Vent.HZ2: 250 Man.Vent.FZ3: 065 V.Lev.:050Z4: 300 Autom.Vent.
N of zone
CCO122 / CCO222 / CCO322 / CCO422 ENGLISH
FIRE PROTECTION MANUFACTURER Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 11 -
To accede into menu displays, press MENU pushbutton. There are 5 different menu displays.
Using cursors or to move forward different menus:
Ventilation (Activate Manual/Ventilation Mode, see picture 1).
Operation (Zones On/Off, see picture 2).
Programming of Ventilation (Level and Delay, see picture 3).
Programming of Alarm delays (see picture 4).
Restore Factory Settings (see picture 5).
Factory settings are as follows:
Parameter Value Margins
Ventilation Levels: 50 ppm Programmable (20 150
ppm, on a 10 ppm increase rate)
Ventilation Delay: 4 min Programmable (1 9 min)
Post-ventilation delay: 4 min Fixed Alarm Level: 300 ppm Fixed
Alarm Delay: 15 min Programmable (10 30 min)
Cursors and which appears in some displays of menu, indicates that there are previous and next displays, respectively, than the current one.
Installation
Below picture shows the general connection outline of different components. It is possible to connect up to 22 sensors per zone. Wiring: it is recommended to use cable with 1.5 mm2 of minimum section. Maximum length of cable per zone must not exceed 400m, in a lineal distribution of sensors.
Note. Attention to polarity requirements of CO sensors.
[CO]
Ventilation level
Alarm level
Ventilation Delay
Ventilation ON
Ventilation ON
Post-ventilation Delay
Postventilacin Ventilation OFF
Alarm ON
Alarm Delay
Time
CCO122 / CCO222 / CCO322 / CCO422 ENGLISH
FIRE PROTECTION MANUFACTURER Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 12 -
ENTERstart stop
start + ENTER
stop + ENTER
start + ENTER
stop + ENTER
1 hour + A / ZONE 1 MAN.VENT
A / VENT. MANUAL
ENTER ENTER
ENTER start stop
fixed + A / ZONE 1 MAN.VENT
M: A / VENTILATIONActivate Manual
zone 1zone 2zone 3zone 4
A / ZONE 1 fixedVENT. MODE 1 hour
Zone selection +
ZONE 1 VentilationConnected fixed
ZONE 1 VentilationManual Stopped
ZONE 1
ZONE 1
Manual Stopped
Ventilation
Ventilation
Connected 1 hour
Picture 1. Manual Ventilation display.
ON_OFF
ENTER ENTER
on + ENTER
ENTERoff +
on
offOn / Off Zones
B / OPER. zone 1zone 2zone 3zone 4
B / ZONE 1OPERATION
zone selection +
ZONE 1 isoperating
ZONE 1 isdisabled
M : B / OPERATION
Picture 2. Operation display.
CCO122 / CCO222 / CCO322 / CCO422 ENGLISH
FIRE PROTECTION MANUFACTURER Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 13 -
ENTERretardo +
C / PROG.
ENTER
ENTER
ESC
C / PROG.
leveldelay
leveldelay
C / PROG. ZONE 1Delay: 4 min
C / PROG.
C / PROG.
ENTER ENTER
ENTER
Seleccin de nivel + ENTERENTER
ESC
C / PROG.M : C / PROGRAMMINGVENT: Level / Del
LEVELDELAY
zone 1zone 2zone 3zone 4
zone selection +
ZONE 1
level + ZONE 1Level: 050 ppmC / SAVE LEVEL
NO: esc YES: enter
NO: esc YES: enterC / SAVE DELAY
leveldelayZONE 1
ZONE 1
Zone 1 SavingVentilation level ..... OK
Zone 1 Savingventilation delay ..... OKDelay selection +
Picture 3. Programming of ventilation display.
ENTERENTER
ESC
Delay selection +
M : D/ PROG. ALARMSDelay: 10 min
D / SAVE DELAYNO: esc YES: enter
M : D/ PROG. ALARMSDelay: 10 min
Zone 1 savingAlarm delay ..... OK
Picture 4. Programming of Alarms delays display.
M : E/ RESTOREFACTORY SETTINGS
ENTER
ESC
M : E/ RESTOREFACTORY SETTINGS
< E/ SAVE SETTINGS?NO: esc YES: enter
Zone 1 savingfactory settings ..... OK
Picture 5. Restore Factory settings screen.
CCO122 / CCO222 / CCO322 / CCO422 ENGLISH
FIRE PROTECTION MANUFACTURER Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 14 -
12V12V
-
+
-
+-
Double ventilation and (OPTIONAL) batteries
Double ventilation:
If the control panel has double ventilation, then it should be connected according to the following schematic.
Factory settings are as follows:
Parameter Value Margins
Ventilation 1 Level: 50 ppm Programmable
(20 150 ppm)
Ventilation 1 Delay: 4 min Programmable
(1 9 min)
Post-ventilation 1 delay: 4 min Fixed Ventilation 2 Level: 200 ppm Programable
(20 300 ppm) and Ventilation 1 level
Ventilation 2 Delay: 10 min Programable (1 30 min) and Ventilation 1 delay
Post-ventilation 2 delay: 4 min Fixed Alarm Level: 300 ppm Fixed
Alarm Delay: 15 min Programmable
(10 30 min)
Batteries:
Batteries must be wired to the to the battery output on the board on the right side of the panel, this output is labelled.
Two 12V-batteries series-connected:
Alarm OFF [CO]
Ventilation 2 level
Ventilation 1 Delay
Ventilation 1 ON
Ventilation 1 ON
Post-ventilation 1 Delay
Ventilation 1 OFF
Alarm ON
Alarm Delay
Tiempo
Alarm level
Ventilation 2 Delay
Ventilation 2 ON
Ventilation 2 ON
Post-ventilation 2 Delay
Ventilation 2 OFF
Ventilation 1 level
Alar VentAlar Vent Zona2 Zona1
+ - + -+ +--Alar VentAlar Vent Zona2 Zona1
+ - + -+ +--
Vent1 Z1
Vent1 Z2
Vent1 Z3( *Z1)
Vent1 Z4( *Z2)
61
R2
K1
Q4
D2D1D3
R3
K2
Q3Q1
R1
K3
R5
K5
R4
1
U5
K4
J4
1
U1
Q5
U3
1
U4
1
U2
D4 D5
Q2
- +ALZ4Z3Z2Z1
Vent2Z4
- +
J1
GND CPU
Vent2 Z2
Vent2 Z3
Vent2 Z1
Vent2 Z4
Bateras
+-
BAT
Vent2Z2 Vent2Z3Vent2Z1
Alarma Z4(*Z2)
Alarma Z3(*Z1)
Alarma Z2
Alarma Z1
In case of 1 or 2 zones Control Panel, you have to follow indications with *
CCO110 / CCO115 ENGLISH
FIRE PROTECTION MANUFACTURER Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 15 -
CCO110 & CCO115 CONTROL PANELS
Light Indicators
A Green LED: System operating normal. B Red LED: Indicates Alarm Relay activation. C Green LED: Indicates Ventilation Relay activated. D Amber LED: Indicates that Ventilation Level has been exceed. E Amber LED: Indicates fault or trouble on detection zone. F Green LED: Indicates that display is showing a CO concentration (ppm). G Green LED: Indicates that display is showing the Ventilation Level. H Green LED: Indicates that display is showing the Ventilation Delay (temporization).
External Controls
1. Seleccin Display: To select the information shown in the display: CO Concentration, Ventilation Level or Ventilation Delay.
2 & 3. : To increase ( ) or decrease ( ) the numerical parameters. 4. ON/OFF Ventilation To activate/deactivate on manual mode the ventilation at any
moment.
CCO110 / CCO115 ENGLISH
FIRE PROTECTION MANUFACTURER Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 16 -
+-ZONE VENT.
+-ALAR.
+
-
+
-
+
-
+
-
+
-
+
-
Ventilation
Alarm
Estructure per Zone
+
(CCO115 up to 15)
CO Detectors
Operation of control panel
The control panel allows to program the Ventilation Level and the Ventilation Delay using cursors , and DISPLAY SELECTION. The MANUAL VENTILATION ON/OFF pushbutton allows to activate/deactivate on manual mode the ventilation at any moment. The factory settings are as follows:
Installation
Below picture shows the general connection outline of different components. It is possible to connect up to 10 sensors per zone in CCO110 panel and up to 15 sensors in CCO115 panel. Wiring: it is recommended to use cable with 1.5 mm2 of minimum section. Maximum length of cable per zone must not exceed 400m, in a lineal distribution of sensors.
NOTE: Attention to polarity requirements of CO sensors.
Parameter Value Margin Ventilation Level: 50 ppm Programmable (20 150 ppm,
on a 10 ppm increase rate) Ventilation Delay: 4 min Programmable (1 9 min, on a
1 min increase) Post-ventilation Delay: 4 min Fixed Alarm Level: 300 ppm Fixed Alarm Delay: 0 min Fixed
Alarm OFF [CO]
Ventilation level
Alarm level
Ventilation Delay
Ventilation ON
Ventilation ON
Post-ventilation Delay
Postventilacin Ventilation OFF
Alarm ON
Alarm Delay
Time
CCO110 / CCO115 ENGLISH
FIRE PROTECTION MANUFACTURER Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 17 -
Double ventilation and (OPTIONAL) batteries
Double ventilation:
If the control panel has double ventilation, we have two ventilation outputs.
The first ventilation output is VENT1 labeled, and second ventilation level is VENT2 labeled.
The alarm level in this control panels is 200 ppm.
Factory settings are as follows:
Parameter Value Margins
Ventilation 1 Level: 50 ppm Fixed
Ventilation 1 Delay: 1 min Programmable
(1 9 min)
Post-ventilation 1 delay: 4 min Fixed Ventilation 2 Level: 100 ppm Fixed Ventilation 2 Delay: 0 min Fixed Post-ventilation 2 delay: 0 min Fixed Alarm Level: 200 ppm Fixed
Alarm Delay: 0 min Fixed
Batteries:
Batteries must be wired to the to the battery output on the board on the right side of the panel, this output is labelled.
Two 12V-batteries series-connected
12V12V
-
+
-
+-
Alarm OFF [CO]
Ventilation 2 level
Ventilation 1 Delay
Ventilation 1 ON
Ventilation 1 ON
Post-ventilation 1 Delay
Ventilation 1 OFF
Alarm ON
Alarm Delay
Tiempo
Alarm level
Ventilation 2 Delay
Ventilation 2 ON
Ventilation 2 ON
Post-ventilation 2 Delay
Ventilation 2 OFF
Ventilation 1 level
CCO122 / CCO222 / CCO322 / CCO422 PORTUGUS
FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 18 -
CENTRALE CCO122, CCO222, CCO322 Y CCO422
Indicadores luminosos
A Led verde: Indica que o sistema est operativo. B Led vermelho: Indica a activao do Rel de Alarme. C Led verde: Indica que se activou o Rel de Ventilao. D Led mbar: Indica que se superou o Nvel de Ventilao. E Led mbar: Indica uma avaria ou uma irregularidade na linha de deteco.
Botes de comando
1 e 2. : Permitem o deslocamento vertical pelas diferentes opes e linhas do menu. Tambm permite aumentar ( ) ou diminuir ( ) os parmetros
numricos.
3. ESC/MENU: Permite retroceder uma pgina de ecr. 4. ENTER: Permite avanar para a pgina seguinte de ecr ou confirmar uma
seleco.
Manuseio da central
Em condies normais de funcionamento a central mostra o ecr principal, visualizando a concentrao
de CO em cada zona e o estado da linha de deteco e os rels de ventilao e alarme.
CCO122 / CCO222 / CCO322 / CCO422 PORTUGUS
FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 19 -
+-ZONAVENT.
+-ALAR.
+
-
+
-
+
-
+
-
+
-
+
-
Ventilacin
Alarma
Detectores CO (mx. 22)
Estructura por Zona
+-Ventilao
Alarme
Estructura por zona
Premindo a tecla menu acede-se aos ecrs de menu. Existem 5 ecrs de menu aos quais se pode aceder atravs das teclas ou :
* Ventilao (Activao Manual/Modo Ventilao, ver figura 1). * Servio (Zonas On/Off, ver figura 2). * Programao de Ventilao (Nvel e Atraso, ver figura 3). * Programao de Atraso de Alarmes (figura 4). * Recuperar Dados de Origem (figura 5).
Os dados de origem so os seguintes:
Parmetro Valor Margem
Nvel de Ventilao: 50 ppm Programvel (20 150 ppm) Atraso Ventilao: 4 min Programvel (1 9 min) Atraso Ps-ventilao: 4 min Fixo Nivel de Alarme: 300 ppm Fixo Atraso Alarme: 15 min Programvel (10 30 min)
As flechas e que aparecem em alguns ecrs de menu, indicam a existncia de ecrs anteriores e posteriores, respectivamente, ao ecr actual.
Instalao
A figura mostra o esquema geral de ligao dos diferentes elementos com a central.
Pode ligar-se um mximo de 22 detectores por zona. Recomenda-se o uso de cabo com uma seco mnima de 1.5 mm
2 e a longitude mxima do mesmo por
zona no deve exceder os 400m, numa distribuio linear de detectores.
Importante. Os detectores de Monxido de Carbono DCO tm polaridade.
Alarme OFF [CO]
Nivel Ventilaco
Nivel Alarme
Atraso Ventilaco
Ventilaco ON
Ventilaco ON
Atraso Ps-ventilaco
Ventilaco OFF
Alarme ON
Atraso Alarme
Tempo
CCO122 / CCO222 / CCO322 / CCO422 PORTUGUS
FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 20 -
Figura 1. Ecr Ventilao Manual.
Figura 2. Ecr Servio.
CCO122 / CCO222 / CCO322 / CCO422 PORTUGUS
FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 21 -
Figura 3. Ecr Programao de Ventilao.
Figura 4. Ecr Programao Atraso de Alarmes.
Figura 5. Ecr Recuperar Dados de Origem.
CCO122 / CCO222 / CCO322 / CCO422 PORTUGUS
FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 22 -
12V12V
-
+
-
+-
Dupla ventilao e (OPCIONAL) baterias
Dupla ventilao:
No caso em que a central tm dupla ventilao a ligao deve ser feita como mostrado na figura.
Os dados de origem so os seguintes:
Parmetro Valor Margem
Nvel de Ventilao 1: 50 ppm Programvel (20 150 ppm)
Atraso Ventilao 1: 4 min Programvel (0 9 min)
Atraso Ps-ventilao 1: 4 min Fixo Nvel de Ventilao 2: 120 ppm Programvel
(20 200 ppm) e
Nivel ventilaco 1 Atraso Ventilao 2: 10 min Programvel
(0 30 min) e
Atraso ventilaco 1 Atraso Ps-ventilao 2: 4 min Fixo Nivel de Alarme: 200 ppm Fixo Atraso Alarme: 0 min Programvel
(0 30 min)
Baterias: As baterias devem ligar-se entrada de
baterias do circuito situado na parte direita do cofre, esta sada est identificada
Ligao das duas baterias de 12 V em srie:
Alar VentAlar Vent Zona2 Zona1
+ - + -+ +--Alar VentAlar Vent Zona2 Zona1
+ - + -+ +--
Vent1 Z1
Vent1 Z2
Vent1 Z3( *Z1)
Vent1 Z4( *Z2)
61
R2
K1
Q4
D2D1D3
R3
K2
Q3Q1
R1
K3
R5
K5
R4
1
U5
K4
J4
1
U1
Q5
U3
1
U4
1
U2
D4 D5
Q2
- +ALZ4Z3Z2Z1
Vent2Z4
- +
J1
GND CPU
Vent2 Z2
Vent2 Z3
Vent2 Z1
Vent2 Z4
Bateras
+-
BAT
Vent2Z2 Vent2Z3Vent2Z1
Alarma Z4(*Z2)
Alarma Z3(*Z1)
Alarma Z2
Alarma Z1
No caso em que a central de 1 ou 2 zonas, siga com *
Alarme OFF [CO]
Nivel Ventilaco 2
Atraso Ventilaco 1
Ventilaco 1 ON
Ventilaco1 ON
Atraso Post-ventilaco 1
Ventilaco1 OFF
Alarme ON
Atraso Alarme
Tempo
Nivel Alarme
Atraso Ventilaco 2
Ventilaco 2 ON
Ventilaco 2 ON
Atraso Post-ventilaco 2
Ventilaco 2 OFF
Nivel Ventilaco 1
CCO110 / CCO115 PORTUGUS
FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 23 -
CENTRALE CCO110 Y CCO115
A Led verde: Indica que o sistema est operativo. B Led vermelho: Indica a activao do Rel de Alarme. C Led verde: Indica que se activou o Rel de Ventilao. D Led mbar: Indica que se superou o Nvel de Ventilao. E Led mbar: Indica uma avaria ou uma irregularidade na linha de deteco. F Led verde: Indica que o display mostra concentrao de CO (ppm). G Led verde: Indica que o display mostra o Nvel de Ventilao. H Led verde: Indica que o display mostra o Atraso de Ventilao.
Botes de comando
1. Seleco Display: Permite seleccionar o dado mostrado pelo diplay: Concentrao de Co, Nvel de Ventilao ou Atraso de Ventilao.
2 e 3. Permitem aumentar ( ) ou diminuir ( ) os parmetros numricos. 4. ON/OFF Ventilao: Permite activar ou desactivar manualmente a ventilao a qualquer
momento.
CCO110 / CCO115 PORTUGUS
FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 24 -
+-ZONA VENT.
+-ALAR.
+
-
+
-
+
-
+
-
+
-
+
-
ventilao
Alarme
Estructura por Zona
+
(CCO115 max 15)
Detectores CO
Manobra da central
A central permite a programao do Nvel de Ventilao e do Atraso de Ventilao a travs das teclas
, e SELECO DISPLAY.
A tecla ON/OFF VENTILAO MANUAL permite activar/desactivar manualmente a ventilao a
qualquer momento.
Os dados de origen so os seguintes:
Parmetro Valor Margem
Nvel de Ventilao: 50 ppm Programvel (20 150 ppm) Atraso Ventilao: 4 min Programvel (1 9 min) Atraso Ps-ventilao: 4 min Fixo Nivel de Alarme: 300 ppm Fixo Atraso Alarme: 0 min Fixo
Instalao
A figura mostra o esquema geral de ligao dos diferentes elementos com a central.
Pode ligar-se um mximo de 10 detectores por zona.
Recomenda-se o uso de cabo com uma seco mnima de 1.5 mm2 e a longitude mxima do mesmo por
zona no debe exceder os 400m, numa distribuio linear de detectores.
Importante. Os detectores de Monxido de Carbono DCO tm polaridade.
Alarme OFF [CO]
Nivel Ventilaco
Nivel Alarme
Atraso Ventilaco
Ventilaco ON
Ventilaco ON
Atraso Ps-ventilaco
Ventilaco OFF
Alarme ON
Atraso Alarme
Tempo
CCO110 / CCO115 PORTUGUS
FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 25 -
Dupla ventilao e baterias
Dupla ventilao:
No caso da central dispor de dupla ventilao, disporemos de duas sadas de ventilao.
A primeira sada de ventilao est identificada como VENT1. A segunda ventilao est identificada como VENT2.
O nvel de alarme tambm fica modificado nestas centrais a 200 ppm.
Os dados de origen so os seguintes:
Parmetro Valor Margem
Nvel de Ventilao 1: 50 ppm Fixo Atraso Ventilao 1: 1 min Programvel
(1 9 min)
Atraso Ps-ventilao 1: 4 min Fixo Nvel de Ventilao 2: 100 ppm Fixo Atraso Ventilao 2: 0 min Fixo Atraso Ps-ventilao 2: 0 min Fixo Nivel de Alarme: 200 ppm Fixo Atraso Alarme: 0 min Fixo
Baterias:
As baterias devem ligar-se entrada de baterias do circuito situada na parte direita do circuito fonte de alimentao, esta sada est identificada.
Ligao das duas baterias de 12 V em srie:
12V12V
-
+
-
+-
Alarme OFF [CO]
Nivel Ventilaco 2
Atraso Ventilaco 1
Ventilaco 1 ON
Ventilaco1 ON
Atraso Post-ventilaco 1
Ventilaco1 OFF
Alarme ON
Atraso Alarme
Tempo
Nivel Alarme
Atraso Ventilaco 2
Ventilaco 2 ON
Ventilaco 2 ON
Atraso Post-ventilaco 2
Ventilaco 2 OFF
Nivel Ventilaco 1
CCO122 / CCO222 / CCO322 / CCO422 CCO110 / CCO115
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS FIRE PROTECTION MANUFACTURER - FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 26 -
NOTAS/NOTES/NOTAS
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
18
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS - FIRE PROTECTION MANUFACTURE FABRICANTS DE PRODUITS CONTRE INCENDIES
Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) SPAIN.
Atencin Tcnico Comercial +34 902 448 811 [email protected] Technical & Commercial Service Ventas +34 935 862 690 [email protected] Sales Marketing +34 935 862 690 [email protected] Marketing S.A.T. +34 935 862 692 [email protected] T.A.S. Compras +34 935 862 693 [email protected] Purchase Export +34 935 862 694 [email protected] Export Fax pedidos +34 902 338 811 Orders Fax Fax general +34 936 999 261 Fax