CCC-G2-18 IBC: 202 Proponent: Michael O'Brian, Chair, representing FCAC ([email protected]); Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected]) 2018 International Building Code Delete without substitution: [BG] CABLE-REST RAINED, AIR-SUPPORT ED ST RUCT URE. A structure in which the uplift is resisted by cables or webbings which are anchored to either foundations or dead men. Reinforcing cable or webbing is attached by various methods to the membrane or is an integral part of the membrane. This is not a cable-supported structure. Reason: The words CABLE-REST RAINED, AIR-SUPPORT ED ST RUCT URE are not used anywhere in IBC or IFC, except in the definition. The term “air-supported” is defined separately, the term “cable-restrained” is intuitive. The last sentence of the definition is present to make a clear distinction between “cable-restrained”, and “cable-supported”, yet the term “cable-supported” is also neither defined nor used. Cost Impact The code change proposal will not increase or decrease the cost of construction . This proposal simply deletes an obsolete definition. Internal ID: 345

CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

CCC-G2-18IBC: 202Proponent: Michael O'Brian, Chair, representing FCAC ([email protected]); Ed Kullik, Chair, representing ICC BuildingCode Action Committee ([email protected])

2018 International Building Code

Delete without substitution:

[BG ] CABLE-RESTRAINED, AIR-SUPPORTED STRUCTURE. A structure in which the uplift is resisted by cables orwebbings which are anchored to either foundations or dead men. Reinforcing cable or webbing is attached by variousmethods to the membrane or is an integral part of the membrane. This is not a cable-supported structure.

Reason:The words CABLE-RESTRAINED, AIR-SUPPORTED STRUCTURE are not used anywhere in IBC or IFC, except in thedefinition. The term “air-supported” is defined separately, the term “cable-restrained” is intuitive. The last sentence ofthe definition is present to make a clear distinction between “cable-restrained”, and “cable-supported”, yet the term“cable-supported” is also neither defined nor used. Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This proposal simply deletes an obsolete definition.Internal ID: 345

Page 2: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E13-18IBC: 1006.2.2, (IFC[BE] 1006.2.2)Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Revise as follows:

1006.2.2 Egress based on use. The numbers, types and locations of exits or access to exits shall be provided in theuses described in Sections 1006.2.2.1 through 1006.2.2.6.

Reason:The subsections of 1006.2.2 includes not only the number of exits and exit access doorways, but also requirementsregarding the exit and exit access doors, types of exit access, and their locations. This provides clarity in the scopingof this section.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This proposal is a clarification reminder of the scope of requirements included in the identified sections.Internal ID: 447

Page 3: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E17-18IBC: 1006.2.2.4 (New), (IFC[BE] 1006.2.2.4 (New))Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Add new text as follows:

1006.2.2.4 Electrical rooms. The location and number of exit or exit access doorways shall be provided forelectrical rooms in accordance with Section 110.26 of NFPA 70 for electrical equipment rated 1000V or less, andSection 110.33 of NFPA 70 for electrical equipment rated over 1000V. Panic hardware shall be provided where requiredin accordance with Section 1010.1.10.1.

Reason:Section 1006.2.2 provides the specific requirements for the numbers, types, and locations of exits or access to exitsfor specific uses. Requirements are already provided in Section 1006.2.2.1 for boiler, incinerator and furnace rooms,which is based on the ASME Boiler and Pressure Vessel Code, and Section 1006.2.2.2 for refrigeration machinery rooms,which is based on ASHRAE 15. The requirements for egress for electrical rooms are not currently addressed in this code, except for where panic orfire exit hardware is used in Section 1010.1.10, which does not provide direction on how many or where the exits or exitaccess doorways are to be located.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .Chapter 27 of the IBC already requires electrical installations to comply with the provisions of NFPA 70. This proposalspecifically directs the code user to the applicable requirements for electrical rooms in NFPA 70.Internal ID: 448

Page 4: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E19-18IBC: 404.9.3, 1006.3.1, 1017.3,1023.2, (IFC[BE] 1006.3.1, 1017.3, 1023.2))Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

404.9 Exit access travel distance. Exit access travel distance for areas open to an atrium shall comply with therequirements of this section.

404.9.1 Egress not through the atrium. Where required access to the exits is not through the atrium, exit accesstravel distance shall comply with Section 1017.

404.9.2 Exit access travel distance at the level of exit discharge. Where the path of egress travel is throughan atrium space, exit access travel distance at the level of exit discharge shall be determined in accordance withSection 1017.

Revise as follows:

404.9.3 Exit access travel distance at other than the level of exit discharge. Where the path of egresstravel is not at the level of exit discharge from the atrium, that portion of the total permitted exit access travel distancethat occurs within the atrium shall be not greater than 200 feet (60 960 mm). Exit access travel distance shall bemeasured in accordance with Sections 1006.3.1 and 1017.3.

404.10 Interior exit stairways. Not greater than 50 percent of interior exit stairways are permitted to egressthrough an atrium on the level of exit discharge in accordance with Section 1028.

CHAPTER 10 MEANS OF EGRESS

1006.3 Egress f rom stories or occupied roofs. The means of egress system serving any story or occupied roofshall be provided with the number of separate and distinct exits or access to exits based on the aggregate occupantload served in accordance with this section. Where stairways serve more than one story, only the occupant load of eachstory considered individually shall be used in calculating the required number of exits or access to exits serving thatstory.

1006.3.1 Adjacent story. The path of egress travel to an exit shall not pass through more than one adjacent story.Exception: The path of egress travel to an exit shall be permitted to pass through more than one adjacent story inany of the following:

1. In Group R-1, R-2 or R-3 occupancies, exit access stairways and ramps connecting four stories orless serving and contained within an individual dwelling unit, sleeping unit or live/work unit.

2. Exit access stairways serving and contained within a Group R-3 congregate residence or aGroup R-4 facility.

3. Exit access stairways and ramps within an atrium complying with the provisions of Section 404.4. Exit access stairways and ramps in open parking garages that serve only the parking garage.5.4 Exit access stairways and ramps serving open-air assembly seating complying with the exit

access travel distance requirements of Section 1029.7.6.5 Exit access stairways and ramps between the balcony, gallery or press box and the main

assembly floor in occupancies such as theaters, places of religious worship, auditoriums andsports facilities.

1017.3 Measurement. Exit access travel distance shall be measured from the most remote point of each room, areaor space along the natural and unobstructed path of horizontal and vertical egress travel to the entrance to an exit.

Exceptions:

1. Within atriums, exit access travel distance is permitted to be measured to the closest riser of anexit access stairway or the closest slope of an exit access ramp.

2. In open parking garages, exit access travel distance is permitted to be measured to the closestriser of an exit access stairway or the closest slope of an exit access ramp.

Page 5: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

1017.3.1 Exit access stairways and ramps. Travel distance on exit access stairways or ramps shall be included inthe exit access travel distance measurement. The measurement along stairways shall be made on a plane parallel andtangent to the stair tread nosings in the center of the stair and landings. The measurement along ramps shall be madeon the walking surface in the center of the ramp and landings.

1023.2 Construction. Enclosures for interior exit stairways and ramps shall be constructed as fire barriers inaccordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. Interior exitstairway and ramp enclosures shall have a fire-resistance rating of not less than 2 hours where connecting four storiesor more and not less than 1 hour where connecting less than four stories. The number of stories connected by theinterior exit stairways or ramps shall include any basements, but not any mezzanines. Interior exit stairways and rampsshall have a fire-resistance rating not less than the floor assembly penetrated, but need not exceed 2 hours.

Exceptions:

1. Interior exit stairways and ramps in Group I-3 occupancies in accordance with the provisions ofSection 408.3.8.

2. Interior exit stairways within an atrium enclosed in accordance with Section 404.6.

Reason:The membership approved E139-12 (AS) which added the allowance for a stairway within an atrium to be considered anexit stairway into Section 1023.2. There is confusion where an atrium is called an exit stairway – how to measure traveldistance, what could be in the atrium, if you could travel through an atrium to get to an exit stairway. Section 1019.3states that open stairways in atriums is an ‘exit access stairway’, so the same stairway is currently called twodifferent things in the code. The intent of this proposal is to call the open stairway in the atrium an exit access stairway to be consistent with theterminology in Section 1019.3, Item 3.The revision to Section 404.8.3 is a pointer for where exit access travel distance within an atrium includes travel downan exit access stairway. The revision to Sections 1006.3.1 and 1017.3 are to measure exit access travel distance in amanner that would be consistent with the using the open stairway as a required means of egress off a story consistentwith if this stairway was an exit off the floor. The smoke protection provisions for atrium in Section 404 would have tobe in place to be able to use this allowance as a required means of egress.The BCAC also has a proposal to reformat the atrium requirements. If both changes pass, there will be no conflicts. The references to the location of requirements can be correlated.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This proposal is effectively codifying the intent to allow the use of open stairways within an atrium “as if” they are in anexit enclosure due to the enhanced safety that exists within an atrium that complies with all the requirements of IBCSection 404, without applying all the other limitations that exist for an exit enclosure elsewhere in the code.Internal ID: 452

Page 6: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E20-18IBC: 1006.3.1, (IFC[BE] 1006.3.1)Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

1006.3 Egress f rom stories or occupied roofs. The means of egress system serving any story or occupied roofshall be provided with the number of separate and distinct exits or access to exits based on the aggregate occupantload served in accordance with this section. Where stairways serve more than one story, only the occupant load of eachstory considered individually shall be used in calculating the required number of exits or access to exits serving thatstory.

Delete without substitution:

1006.3.1 Adjacent story. The path of egress travel to an exit shall not pass through more than one adjacent story.Exception: The path of egress travel to an exit shall be permitted to pass through more than one adjacent story inany of the following:

1. In Group R-1, R-2 or R-3 occupancies, exit access stairways and ramps connecting four stories orless serving and contained within an individual dwelling unit, sleeping unit or live/work unit.

2. Exit access stairways serving and contained within a Group R-3 congregate residence or aGroup R-4 facility.

3. Exit access stairways and ramps in open parking garages that serve only the parking garage.4. Exit access stairways and ramps serving open-air assembly seating complying with the exit

access travel distance requirements of Section 1029.7.5. Exit access stairways and ramps between the balcony, gallery or press box and the main

assembly floor in occupancies such as theaters, places of religious worship, auditoriums andsports facilities.

Reason:The current list of exceptions allows for exit access stairways within 5 of the 8 options to use travel distance without astory limitation (individual dwelling units(#2), Group R-3 and R-4 congregate residences(#3), open parkinggarages(#6), open air seating(#7) and balconies(#8)). The 3 options currently limited to one story are the 2 storyconfiguration (#1), water curtains around stairways opening (#4) and atriums (#5). These exceptions were added tothe code by E27-15.Travel distance, rather than stories should be the controlling factor. There would be no impact on two storyconfigurations. Deletion of the requirement would allow for exit access travel distance to be measured down the openexit access stairway, regardless of the number of stories. This would now include open exit access stairways that usewater curtains around stairways opening (#4) and atriums with smoke protection (#5). With the removal of thelimitation for one story, none of the exceptions are needed.This would be consistent with the BCAC proposal to revise measurement for travel distance along open exit accessstairways in atriums.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will decrease the cost of construction .This will reduce the cost in those situations where an enclosure would have been required for the stairway in buildingswith more than two stories.Internal ID: 526

Page 7: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E22-18IBC: SECTION TABLE 1006.3.2, TABLE 1006.3.3(1), TABLE 1006.3.3(2), (IFC[BE] TABLE 1006.3.2, TABLE1006.3.3(1), TABLE 1006.3.3(2))Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Revise as follows:

SECTION 1006 NUMBER OF EXITS AND EXIT ACCESS DOORWAYS

1006.3 Egress f rom stories or occupied roofs. The means of egress system serving any story or occupied roofshall be provided with the number of separate and distinct exits or access to exits based on the aggregate occupantload served in accordance with this section. Where stairways serve more than one story, only the occupant load of eachstory considered individually shall be used in calculating the required number of exits or access to exits serving thatstory.

1006.3.2 Egress based on occupant load. Each story and occupied roof shall have the minimum number ofseparate and distinct exits, or access to exits, as specified in Table 1006.3.2. A single exit or access to a single exitshall be permitted in accordance with Section 1006.3.3. The required number of exits, or exit access stairways or rampsproviding access to exits, from any story or occupied roof shall be maintained until arrival at the exit discharge or apublic way.

Page 8: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

TABLE 1006.3.2MINIMUM NUMBER OF EXITS OR ACCESS TO EXITS PER STORY OR OCCUPIED ROOF

Page 9: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

1006.3.3 Single exits. A single exit or access to a single exit shall be permitted from any story or occupied roofwhere one of the following conditions exists:

1. The occupant load, number of dwelling units and common path of egress travel distance do notexceed the values in Table 1006.3.3(1) or 1006.3.3(2).

2. Rooms, areas and spaces complying with Section 1006.2.1 with exits that discharge directly to theexterior at the level of exit discharge, are permitted to have one exit or access to a single exit.

3. Parking garages where vehicles are mechanically parked shall be permitted to have one exit oraccess to a single exit.

4. Group R-3 and R-4 occupancies shall be permitted to have one exit or access to a single exit.5. Individual single-story or multistory dwelling units shall be permitted to have a single exit or access

to a single exit from the dwelling unit provided that both of the following criteria are met:5.1. The dwelling unit complies with Section 1006.2.1 as a space with one means of egress.5.2. Either the exit from the dwelling unit discharges directly to the exterior at the level of exit

discharge, or the exit access outside the dwelling unit's entrance door provides access tonot less than two approved independent exits.

Page 10: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

TABLE 1006.3.3(1)STORIES AND OCCUPIED ROOFS WITH ONE EXIT OR ACCESS TO ONE EXIT FOR R-2 OCCUPANCIES

For SI: 1 foot = 3048 mm.NP = Not Permitted.NA = Not Applicable.

a. Buildings classified as Group R-2 equipped throughout with an automatic sprinkler system inaccordance with Section 903.3.1.1 or 903.3.1.2 and provided with emergency escape and rescueopenings in accordance with Section 1030.

b. This table is used for R-2 occupancies consisting of dwelling units. For R-2 occupancies consistingof sleeping units, use Table 1006.3.3(2).

Page 11: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

TABLE 1006.3.3(2)STORIES AND OCCUPIED ROOFS WITH ONE EXIT OR ACCESS TO ONE EXIT FOR OTHER OCCUPANCIES

For SI: 1 foot = 304.8 mm.NP = Not Permitted.NA = Not Applicable.

a. Buildings classified as Group R-2 equipped throughout with an automatic sprinkler system inaccordance with Section 903.3.1.1 or 903.3.1.2 and provided with emergency escape and rescueopenings in accordance with Section 1030.

b. Group B, F and S occupancies in buildings equipped throughout with an automatic sprinkler system inaccordance with Section 903.3.1.1 or on the roof of such buildings shall have a maximum exit accesstravel distance of 100 feet.

c. This table is used for R-2 occupancies consisting of sleeping units. For R-2 occupancies consistingof dwelling units, use Table 1006.3.3(1).

d. The length of exit access travel distance in a Group S-2 open parking garage shall be not more than100 feet.

Reason:This is part of a series of 3 proposals dealing with occupied roofs. See BCAC proposals to the definition of penthouseand Section 1009.The change to the title and heading in Table 1006.3.2 is for consistency with the text. The proposed modifications to Section 1006 includes adding ‘occupied roofs’ to Table 1006.3.3(1) to clarify theconditions in which one exit or access to one exit is allowed for Group R-2 occupancies. The tables are modified toclarify that the occupied roofs are allowed ‘over the allowable stories.’Similarly this proposal adds ‘occupied roofs’ to Table 1006.3.3(2) to clarify the conditions in which one exit or access toone exit is allowed for the other occupancies. The table was also modified to clarify that the occupied roofs areallowed ‘over the allowable stories.’ A proposed modification to footnote b or the table clarifies that the allowableincrease in exit access travel distance from 75 feet to 100 feet for properly sprinklered Group B, F and S occupanciesalso includes the roof area for these uses.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portions

Page 12: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

thereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This proposal provides clarification to a subject that was not previously addressed. The changes to the singleoccupant tables could allow for one exit stairway from an occupied roof instead of two.Internal ID: 520

Page 13: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E24-18IBC: 1006.3.3, TABLE 1006.3.3(1), TABLE 1006.3.3(2), (IFC[BE] 1006.3.3, TABLE 1006.3.3(1), TABLE1006.3.3(2))Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Revise as follows:

1006.3.3 Single exits. A single exit or access to a single exit shall be permitted from any story or occupied roofwhere one of the following conditions exists:

1. The occupant load, number of dwelling units and common path of egress exit access travel distancedo not exceed the values in Table 1006.3.3(1) or 1006.3.3(2).

2. Rooms, areas and spaces complying with Section 1006.2.1 with exits that discharge directly to theexterior at the level of exit discharge, are permitted to have one exit or access to a single exit.

3. Parking garages where vehicles are mechanically parked shall be permitted to have one exit oraccess to a single exit.

4. Group R-3 and R-4 occupancies shall be permitted to have one exit or access to a single exit.5. Individual single-story or multistory dwelling units shall be permitted to have a single exit or access

to a single exit from the dwelling unit provided that both of the following criteria are met:5.1. The dwelling unit complies with Section 1006.2.1 as a space with one means of egress.5.2. Either the exit from the dwelling unit discharges directly to the exterior at the level of exit

discharge, or the exit access outside the dwelling unit's entrance door provides access tonot less than two approved independent exits.

Page 14: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

TABLE 1006.3.3(1)STORIES WITH ONE EXIT OR ACCESS TO ONE EXIT FOR R-2 OCCUPANCIES

For SI: 1 foot = 3048 mm.NP = Not Permitted.NA = Not Applicable.

a. Buildings classified as Group R-2 equipped throughout with an automatic sprinkler system inaccordance with Section 903.3.1.1 or 903.3.1.2 and provided with emergency escape and rescueopenings in accordance with Section 1030.

b. This table is used for R-2 occupancies consisting of dwelling units. For R-2 occupancies consistingof sleeping units, use Table 1006.3.3(2).

Page 15: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

TABLE 1006.3.3(2)STORIES WITH ONE EXIT OR ACCESS TO ONE EXIT FOR OTHER OCCUPANCIES

For SI: 1 foot = 304.8 mm.NP = Not Permitted.NA = Not Applicable.

a. Buildings classified as Group R-2 equipped throughout with an automatic sprinkler system inaccordance with Section 903.3.1.1 or 903.3.1.2 and provided with emergency escape and rescueopenings in accordance with Section 1030.

b. Group B, F and S occupancies in buildings equipped throughout with an automatic sprinkler system inaccordance with Section 903.3.1.1 shall have a maximum exit access travel distance of 100 feet.

c. This table is used for R-2 occupancies consisting of sleeping units. For R-2 occupancies consistingof dwelling units, use Table 1006.3.3(1).

d. The length of exit access travel distance in a Group S-2 open parking garage shall be not more than100 feet.

Reason:There is a conflict in terminology used for single exit criteria for stories/buildings in the IBC Section/Tables 1006.3.3 andIEBC Section/Tables 805.3.1.1. The intent of this proposal is a clarification, without technical revisions.Below is the definition for common path of egress travel and exit access and a graphic from the IBC commentaryillustrating the terms. Single exit stories/buildings cannot have a common path of egress travel since two exits are notrequired. The correct term is “exit access travel distance”. This would match the terminology in the column headingsfor single exit tables with the footnotes for the single exit tables in the IBC and the table heading and footnotes in theIEBC.If you look at the history for the single exit tables, until the reorganization that combined single exit spaces andstories, the term used was ‘exit access travel distance.’With the text incorrectly used in IBC Section 1006.3.3, it could be interpreted that the travel distance has to be to aplace where there are two exits – which is on the ground floor - regardless if the stairway is an exit access or exitstairway. Exit access travel distance should stop at the door to the exit stairway. COMMON PATH OF EGRESS TRAVEL. That portion of the exit access travel distance measured from the mostremote point within a story to that point where the occupants have separate access to two exits o r exit accessdoorways.EXIT ACCESS. That portion of a means of egress system that leads from any occupied portion of a building orstructure to an exit.

Page 16: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.

Figure 1006.2.1 from IBC CommentaryCost ImpactThe code change proposal will not increase or decrease the cost of construction .As the proposal essentially provides clarification to a subject that has created confusion.Internal ID: 453

Page 17: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E29-18IBC: 1009.2.1, (IFC[BE] 1009.2.1)Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Revise as follows:

1009.2.1 Elevators required. In buildings where a required accessible floor is four or more stories above or below alevel of exit discharge, not less than one required accessible means of egress shall be an elevator complying with Section1009.4. For purposes of determining where an elevator is required for accessible means of egress, in buildingsequipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, anoccupied roof shall not be considered a story.

Exceptions:

1. In buildings equipped throughout with an automatic sprinkler system installed in accordance withSection 903.3.1.1 or 903.3.1.2, the elevator shall not be required on floors provided with ahorizontal exit and located at or above the levels of exit discharge.

2. In buildings equipped throughout with an automatic sprinkler system installed in accordance withSection 903.3.1.1 or 903.3.1.2, the elevator shall not be required on floors provided with a rampconforming to the provisions of Section 1012.

Reason:This is part of a series of 3 proposals dealing with occupied roofs. See BCAC proposals to the definition of penthouseand Section 1006.This is NOT for when an accessible route is required to an occupied roof. That is already addressed in Section 1104.4. This is ONLY for when an elevator would be required to serve as part of an accessible means of egress, and thus add arequirement for standby power. This allowance would only be applicable where there was an occupied roof on a 4story building. If there is an occupied roof on any taller buildings, unless those buildings meet one of the otherexceptions for ramps or horizontal exits, standby power would be required to all floors, including the occupied roof. The roof is required to be open to the outside, so there is not the accumulation for smoke that would be found on atypical interior floor – so that offers extra passive protection of occupants on the roof. Therefore, there did not seemto be any justification to require standby power for this limited situation. The stairways would still be required tocomply with Section 1009 for accessible means of egress from the roof.This proposal reinforces the concept that an occupied roof is not a story for the purpose of determining that anelevator is required as an accessible means of egress in properly sprinklered buildings.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This clarifies that standby power is not required for an elevator serving an occupied roof on a 4 story building. Withoutthis clarification, if standby power was required, that would be a significant cost increase.Internal ID: 522

Page 18: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E37-18IBC: SECTION 1010, (IFC[BE] 1010)Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Revise as follows:

SECTION 1010 DOORS, GATES AND TURNSTILES

1010.1 Doors. Means Doors in the means of egress shall comply with the requirements of Sections 1010.1.1 through1010.1.3.4. Exterior exit doors shall meet also comply with the requirements of this section. Doors serving a Section1022.2. Gates in the means of egress shall comply with the requirements of Section 1010.4 through 1010.4.1. Turnstilesin the means of egress system shall meet comply with the requirements of this section and Section 1022.2. DoorsSection 1010.5 through 1010.5.4.Doors, gates and turnstiles provided for egress purposes in numbers greater than required by this code shall meetcomply with the requirements of this section.Doors in the Means means of egress doors shall be readily distinguishable from the adjacent construction and finishessuch that the doors are easily recognizable as doors. Mirrors or similar reflecting materials shall not be used on meansof egress doors. Means of egress doors shall not be concealed by curtains, drapes, decorations or similar materials.

1010.1.1 Size of doors. (No change to text)

1010.1.1.1 Projections into clear width. (No change to text)

1010.1.2 Door swing. (No change to text)

1010.1.2.1 Direction of swing. (No change to text)

1010.1.3 Door opening force. (No change to text)

1010.1.3.1 Location of applied forces. (No change to text)

1010.1.51010.1.4 Floor elevation. (No change to text)

1010.1.61010.1.5 Landings at doors. (No change to text)

1010.1.71010.1.6 Thresholds. (No change to text)

1010.1.81010.1.7 Door arrangement. (No change to text)

1010.1.91010.2 Door operations. (No change to text)

1010.1.9.61010.2.1 Unlatching. (No change to text)

1010.1.9.11010.2.2 Hardware. (No change to text)

1010.1.9.21010.2.3 Hardware height. (No change to text)

1010.1.9.41010.2.4 Locks and latches. (No change to text)

1010.1.9.51010.2.5 Bolt locks. (No change to text)

1010.1.9.6.11010.2.6 Closet doors. (No change to text)

1010.1.9.121010.2.7 Stairway doors. (No change to text)

1010.1.4.4 1010.2.8 Locking arrangements in educational occupancies. In Group E and Group B educationaloccupancies, egress doors from classrooms, offices and other occupied rooms shall be permitted to be provided withlocking arrangements designed to keep intruders from entering the room where all of the following conditions are met:

Page 19: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

1. The door shall be capable of being unlocked from outside the room with a key or other approvedmeans.

2. The door shall be openable from within the room in accordance with Section 1010.1.9.3.Modifications shall not be made to listed panic hardware, fire door hardware or door closers.

1010.1.4.4.11010.2.8.1 Remote operation of locks. (No change to text)

1010.1.101010.2.9 Panic and f ire exit hardware. (No change to text)

1010.1.10.11010.2.9.1 Installation. (No change to text)

1010.1.10.21010.2.9.2 Balanced doors. (No change to text)

1010.1.9.31010.2.10 Monitored or recorded egress. (No change to text)

1010.1.9.101010.2.11 Door hardware release of electrically locked egress doors. (No change to text)

1010.1.9.91010.2.12 Sensor release of electrically locked egress doors. (No change to text)

1010.1.9.81010.2.13 Delayed egress. (No change to text)

1010.1.9.8.11010.2.13.1 Delayed egress locking system. (No change to text)

1010.1.9.71010.2.14 Controlled egress doors in Groups I-1 and I-2. (No change to text)

1010.1.9.111010.2.15 Locking arrangements in buildings within correctional facilities. (No change to text)

1010.1.41010.3 Special doors. (No change to text)

1010.1.4.11010.3.1 Revolving doors. (No change to text)

Page 20: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

TABLE 1010.1.4.11010.3.1(1)MAXIMUM DOOR SPEED MANUAL REVOLVING DOORS

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

REVOLVING DOOR MAXIMUM NOMINAL DIAMETER (FT-IN) MAXIMUM ALLOWABLE REVOLVING DOOR SPEED (RPM)6-0 127-0 118-0 109-0 910-0 8

Page 21: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

TABLE 1010.1.4.11010.3.1(2)MAXIMUM DOOR SPEED AUTOMATIC OR POWER-OPERATED REVOLVING DOORS

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

REVOLVING DOOR MAXIMUM NOMINAL DIAMETER (FT-IN)

MAXIMUM ALLOWABLE REVOLVING DOOR SPEED (RPM)

8-0 7.29-0 6.410-0 5.711-0 5.212-0 4.812-6 4.614-0 4.116-0 3.617-0 3.418-0 3.220-0 2.924-0 2.4

Page 22: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

1010.1.4.1.11010.3.1.1 Egress component. (No change to text)

1010.1.4.1.21010.3.1.2 Other than egress component. (No change to text)

1010.1.4.21010.3.2 Power-operated doors. (No change to text)

1010.1.4.31010.3.3 Special purpose horizontal sliding, accordion or folding doors. (No change to text)

1010.1.4.51010.3.4 Security grilles. (No change to text)

1010.21010.4 Gates. (No change to text)

1010.2.11010.4.1 Stadiums. (No change to text)

1010.31010.5 Turnstiles and similar devices. (No change to text)

1010.3.11010.5.1 Capacity. (No change to text)

1010.3.1.11010.5.1.1 Clear width. (No change to text)

1010.3.21010.5.2 Security access turnstiles. (No change to text)

1010.3.31010.5.3 High turnstile. (No change to text)

1010.3.41010.5.4 Additional door. (No change to text)

Reason:This is a reorganization of the door section to group like items together. There is not intended to be any technicalchanges.Start in 1010.1 by recognizing that this section covers doors, gates and turnstiles. Clean up the reference to Section1022.2 to be more specific.List all door requirements – 1010.1.1 through 1010.1.7Separate out door hardware requirements from the doors themselves – new section 1010.2Relocate unlatching as generic requirement to beginning of hardware section – relocate to 1010.2.1Group hardware requirements – height, monitoring, locks, bolt locks, sensor release, door hardware releaseGroup requirements for special safety concerns – closets, stairways, locking in schools, panic hardware. (The schoolcriteria is currently under specials doors – this is definitely a locking criteria. With the new location, Item 2 is notneeded).Moved all the electrical locking arrangements (other than I-3 correctional facilities) to be next to each other, andordered from most common to least common. Put the monitored or recorded egress section prior to these 4 electricallocking sections because monitored or recorded egress would almost exclusively be used with one of the electricallocking arrangements. Group Special doors: revolving, power operated, horizontal sliding security grills – new section 1010.3Renumber gates and turnstiles.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This proposal reorganizes Section 1010 to provide clarity for the code user for the requirements for doors and door

Page 23: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

hardware. There are no technical changes to Section 1010.Internal ID: 451

Page 24: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E45-18IBC: 1010.1.3.2 (New), (IFC[BE] 1010.1.3.2 (New))Proponent: John Williams, Chair, representing Healthcare Committee ([email protected]); Ed Kullik, Chair, representingICC Building Code Action Committee ([email protected])

2018 International Building Code

Add new text as follows:

1010.1.3.2 Manual horizontal sliding doors. Where a manual horizontal sliding door is required to latch, the latchor other mechanism shall prevent the door from rebounding into a partially open position when the door is closed.

Reason:In the event that horizontal doors are installed under these conditions the proposed language clarifies performancewhen a door is forcefully closed.For Group I-2 and ambulatory care facilities this clarification of language is required in order to conform to FederalStandards and Centers for Medicaid and Medicare Services enforcement rules (K224). This proposal is submitted by the ICC Committee on Healthcare (CHC) and the ICC Building Code Action Committee(BCAC). The CHC was established by the ICC Board to evaluate and assess contemporary code issues relating tohealthcare facilities. This is a joint effort between ICC and the American Society for Healthcare Engineering (ASHE), asubsidiary of the American Hospital Association, to eliminate duplication and conflicts in healthcare regulation. In 2017the CHC held 2 open meetings and numerous conference calls, which included members of the committees as well asany interested parties, to discuss and debate the proposed changes. Information on the CHC, including: meetingagendas; minutes; reports; resource documents; presentations; and all other materials developed in conjunction withthe CHC effort can be downloaded from the CHC website at: https://www.iccsafe.org/codes-tech-support/cs/icc-committee-on-healthcare/.BCAC was established by the ICC Board of Directors in July 2011 to pursue opportunities to improve and enhanceassigned International Codes or portions thereof. In 2017 the BCAC has held 3 open meetings. In addition, there werenumerous Working Group meetings and conference calls for the current code development cycle, which includedmembers of the committee as w ell as any interested party to discuss and debate the proposed changes. Relateddocumentation and reports are posted on the BCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will increase the cost of construction .If a horizontal sliding door is chosen where a door is required to latch, this requirement would add some performancerequirements to stop the door from rebounding.Internal ID: 594

Page 25: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E48-18IBC: 1010.1.4.4, 1010.1.4.4.1, (IFC[BE] 1010.1.4.4, 1010.1.4.4.1); IFC: 1031.2.2Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected]); Michael O'Brian,Chair, representing FCAC ([email protected])

2018 International Building Code

Revise as follows:

1010.1.4.4 Locking arrangements in educational occupancies. In Group E and occupancies, Group Beducational occupancies and Group I-4 occupancies, egress doors from classrooms, offices and other occupied roomsshall be permitted to be provided with locking arrangements designed to keep intruders from entering the room whereshall comply with all of the following conditions are met:

1. The door shall be capable of being unlocked from outside the room with a key or other approvedmeans.

2. The door shall be openable from within the room in accordance with Section 1010.1.9.3. Modifications shall not be made to listed panic hardware, fire door hardware or door closers.4. Modifications to fire door assemblies shall be in accordance with NFPA 80.

Remote locking or unlocking of doors from an approved location shall be permitted in addition to the unlockingoperation in Item 1.

Delete without substitution:

1010.1.4.4.1 Remote operation of locks. Remote operation of locks complying with Section 1010.1.4.4 shall bepermitted.

2018 International Fire Code

Revise as follows:

[BE] 1031.2.2 Locking arrangements in educational occupancies. In Group E occupancies, Group Beducational occupancies and Group I-4 occupancies, egress doors from classrooms, offices and other occupied roomsshall be permitted to be provided with locking arrangements designed to keep intruders from entering the room shallcomply with Section 1010.1.4.4. where all of the following conditions are met:

1. The door shall be capable of being unlocked from outside the room with a key or other approvedmeans.

2. The door shall be openable from within the room in accordance with Section 1010.1.9.3. Modifications shall not be made to existing listed panic hardware, fire door hardware or door

closers.4. Modifications to fire door assemblies shall be in accordance with NFPA 80.

Reason:During the last code development cycle several proposals were accepted to address various locking arrangementsbeing proposed for educational occupancies. During the Group A and Group B cycles, there were additions made tothe various proposals, which results in current code language that is not entirely correlated. This proposal attempts tocorrelate the codes so requirements are consistent throughout. IFC includes allowances for Group I-4, which are not listed in the IBC. Lock-down plans for day care facilities are asimportant as for schools. The further language for Group I-4 “child day care” is not needed to describe the occupancy.The reason statement for the public comment said that the committee did not want to make these locks mandatory,but by using “shall be permitted”, lock-down systems could be provided that did not comply with these requirements. With the proposed language, a school could choose to add locks to keep out intruders, but those locks would have tocomply with these important safety features.Subsection 1010.1.4.4.1 is confusing. The allowance for remote unlocking from the outside could easily be included inSection 1010.1.4.4. This was not included in IFC.

Page 26: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

There will be a correlative change submitted to IEBC as part of Group B proposals since this is an importantmodification being done by schools across the country.This proposal is submitted by the ICC Building Code Action Committee (BCAC) and Fire Code Action Committee (FCAC).BCAC was established by the ICC Board of Directors in July 2011 to pursue opportunities to improve and enhanceassigned International Codes or portions thereof. In 2017 the BCAC has held 3 open meetings. In addition, there werenumerous Working Group meetings and conference calls for the current code development cycle, which includedmembers of the committee as w ell as any interested party to discuss and debate the proposed changes. Relateddocumentation and reports are posted on the BCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.The FCAC was established by the ICC Board of Directors to pursue opportunities to improve and enhance assignedInternational Codes with regard to fire safety and hazardous materials in new and existing buildings and facilities andthe protection of life and property in wildland urban interface areas. In 2017 the Fire-CAC has held 3 open meetings. Inaddition, there were numerous conference calls, Regional Work Group and Task Group meetings for the current codedevelopment cycle, which included members of the committees as well as any interested parties, to discuss anddebate the proposed changes. Related documentation and reports are posted on the FCAC website at:https://www.iccsafe.org/codes-tech-support/cs/fire-code-action-committee-fcac/Cost ImpactThe code change proposal will not increase or decrease the cost of construction .. This is a correlation between the IFC and IBC with no technical change.Internal ID: 515

Page 27: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E51-18IBC: 1010.1.9 (New), (IFC[BE] 1010.1.9 (New))Proponent: Ed Kullik, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Add new text as follows:

1010.1.9 Vestibules. Where required by a compliance path of the International Energy Conservation Code, buildingentrances shall be provided with vestibules.

Reason:The IECC requires vestibules to be provided at building entrances in all climate zones other than 1 and 2. In the designof buildings this can be a significant feature of entrances. The requirement can be overlooked by designers if theyfocus on the IBC during initial design and then are perhaps surprised by the requirement when adding the IECC to theirconstruction documents. This proposal provides a direct reference to the compliance paths in the IECC for vestibules. The proposal puts the reference for vestibules in Chapter 10 after the section for door arrangements (Section1010.1.8). Since Section 1010.1.8 addresses doors in a series, this is the most logical place for designers tounderstand that a vestibule may be required by the IECC.The BCAC developed this proposal with the SEHPCAC. This proposal is submitted by the ICC Building Code ActionCommittee (BCAC). BCAC was established by the ICC Board of Directors in July 2011 to pursue opportunities to improveand enhance assigned International Codes or portions thereof. In 2017 the BCAC has held 3 open meetings. In addition,there were numerous Working Group meetings and conference calls for the current code development cycle, whichincluded members of the committee as w ell as any interested party to discuss and debate the proposed changes.Related documentation and reports are posted on the BCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This requirement already exists in the IECC. Inclusions in the IBC doesn’t result in any construction not alreadyanticipated.Internal ID: 527

Page 28: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E58-18IBC: 1010.1.9.8, 1010.1.10, (IFC[BE] 1010.1.9.8, 1010.1.10)Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Revise as follows:

1010.1.9.8 Delayed egress. Delayed egress locking systems shall be permitted to be installed on doors serving thefollowing occupancies in buildings that are equipped throughout with an automatic sprinkler system in accordance withSection 903.3.1.1 or an approved automatic smoke or heat detection system installed in accordance with Section 907.

1. Group B, F, I, M, R, S and U occupancies.2. Group E classrooms with an occupant load of less than 50.

Exception: Delayed3. In a courthouse, delayed egress locking systems shall be permitted to be installed on exit or exit

access doors, other than the main exit or exit access door, serving a Group A-3 courtroom inbuildings equipped throughout with an automatic sprinkler system in accordance with Section903.3.1.1.

1010.1.10 Panic and f ire exit hardware. Swinging doors serving a Group H occupancy and swinging doors servingrooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch orlock other than panic hardware or fire exit hardware.

Exceptions:

1. A main exit of a Group A occupancy shall be permitted to have locking devices in accordancewith Section 1010.1.9.4, Item 2.

2. Doors provided with panic hardware or fire exit hardware and serving a Group A or E occupancyshall be permitted to be electrically locked in accordance with Section 1010.1.9.9 or 1010.1.9.10.

3. Courtrooms shall be permitted to be locked in accordance with Section 1010.1.9.8, Item 3.Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet (1829 mm) wide, and that containovercurrent devices, switching devices or control devices with exit or exit access doors, shall be equipped with panichardware or fire exit hardware. The doors shall swing in the direction of egress travel.

Reason:This is only a format issue resulting from the multiple changes last cycle to the delayed egress locks - E66-15 AMPC1,E68-15 AM/AMPC1, E69-15 AS. The allowance for courtrooms, while logical, is out of place as an exception to Items 1and 2 in Section 1010.1.9.8. Correlation with Section 1010.1.9.8 in Section 1010.1.10 is needed because this is Group A where panic hardware isotherwise required.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This is a format revision with no change to technical criteria.Internal ID: 514

Page 29: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E61-18IBC: 1010.1.9.9, (IFC[BE] 1010.1.9.9)Proponent: John Williams, Chair, representing Healthcare Committee ([email protected]); Ed Kullik, representing ICCBuilding Code Action Committee ([email protected])

2018 International Building Code

Revise as follows:

1010.1.9.9 Sensor release of electrically locked egress doors. Sensor release of electric locking systemsshall be permitted on doors located in the means of egress in any occupancy except Group H where installed andoperated in accordance with all of the following criteria:

1. The sensor shall be installed on the egress side, arranged to detect an occupant approaching thedoors, and shall cause the electric locking system to unlock.

2. The electric locks shall be arranged to unlock by a signal from or loss of power to the sensor.3. Loss of power to the lock or locking system shall automatically unlock the electric locks.4. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48

inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secureddoors. Ready access shall be provided to the manual unlocking device and the device shall beclearly identified by a sign that reads "PUSH TO EXIT.” When operated, the manual unlocking deviceshall result in direct interruption of power to the electric lock-independent of other electronics andthe electric lock shall remain unlocked for not less than 30 seconds.

5. Activation of the building fire alarm system, where provided, shall automatically unlock the electriclock, and the electric lock shall remain unlocked until the fire alarm system has been reset.

6. Activation of the building automatic sprinkler system or fire detection system, where provided, shallautomatically unlock the electric lock. The electric lock shall remain unlocked until thefire alarmsystem has been reset.

7. Emergency lighting shall be provided on the egress side of the door.8. The door locking system units shall be listed in accordance with UL 294.

Reason:The requirement for egress side emergency lighting provides all occupants with minimum egress illumination levels atthe door for operation and to read the sign. This proposed requirement is aligned with current delayed egress andcontrolled egress locking conditions.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .If the locking system is installed, added cost may be incurred where emergency lighting is not currently in place.Internal ID: 588

Page 30: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E64-18IBC: 1010.1.10, 1010.1.10.1 (New), (IFC[BE] 1010.1.10, 1010.1.10.1 (New))Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Revise as follows:

1010.1.10 Panic and f ire exit hardware. Swinging doors serving a Group H occupancy and swinging doors servingrooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch orlock other than panic hardware or fire exit hardware.

Exceptions:

1. A main exit of a Group A occupancy shall be permitted to have locking devices in accordancewith Section 1010.1.9.4, Item 2.

2. Doors provided with panic hardware or fire exit hardware and serving a Group A or E occupancyshall be permitted to be electrically locked in accordance with Section 1010.1.9.9 or 1010.1.9.10.

Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet (1829 mm) wide, and that containovercurrent devices, switching devices or control devices with exit or exit access doors, shall be equipped with panichardware or fire exit hardware. The doors shall swing in the direction of egress travel.

Add new text as follows:

1010.1.10.1 Rooms with electrical equipment. Exit or exit access doors serving transformer vaults, roomsdesignated for batteries or energy storage systems, or modular data centers shall be equipped with panic hardwareor fire exit hardware. Where rooms contain electrical rooms with equipment rated 800 amperes or more that containovercurrent devices, switching devices or control devices and where the exit or exit access door is less than 25 feetfrom the equipment working space, shall be equipped with panic hardware or fire exit hardware. The doors shall swingin the direction of egress travel.

Reason:The current requirements in the International Building Code are not in alignment with the requirements in NFPA 70, theNational Electrical Code. Section 110.26(C)(3) requires where there are exit or exit access doors serving a room withelectrical equipment rated 800 amperes or more those doors shall be equipped with listed panic hardware. Equipmentrated 1200 amperes or more is used to determine the number and locations of exits or exit access doorways, which isaddressed in Section 1006.2.2. Also, NFPA 70 for transformer vaults (in SectionsThis proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .Chapter 27 of the IBC already requires electrical installations to comply with the provisions of NFPA 70. This proposalaligns the requirements in the IBC with NFPA 70.Internal ID: 449

Page 31: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E106-18IBC: 1029.16, 1029.16.1, (IFC[BE] 1029.16. 1029.16.1)Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Revise as follows:

1029.16 Handrails. Ramped aisles having a slope exceeding one unit vertical in 15 units horizontal (6.7-percentslope) and stepped aisles shall be provided with handrails in compliance with Section 1014 located either at one orboth sides of the aisle or within the aisle width. Where the stepped aisle have seating on one side and the aisle width is74 inches (1880 mm) or greater, two handrails are required. Where two handrails are required, one of the handrailsshall be within 30 inches horizontally of the end of the aisle accessways.

Exceptions:

1. Handrails are not required for ramped aisles with seating on both sides.2. Handrails are not required where, at the side of the aisle, there is a guard with a top surface

that complies with the graspability requirements of handrails in accordance with Section 1014.3.3. Handrail extensions are not required at the top and bottom of stepped aisles and ramped aisles

to permit crossovers within the aisles.

1029.16.1 Discontinuous handrails. Where there is seating on both sides of the aisle, the mid-aisle handrails shallbe discontinuous with discontinuous. Where the stepped aisle is required to have two handrails, handrails not locatedon a guard or wall shall be discontinuous. The gaps or breaks at intervals shall not exceeding exceed five rows tofacilitate access to seating and to permit crossing from one side of the aisle to the other. These gaps or breaks shallhave a clear width of not less than 22 inches (559 mm) and not greater than 36 inches (914 mm), measuredhorizontally, and the mid-aisle handrail shall have rounded terminations or bends.

1029.16.2 Handrail termination. Handrails located on the side of stepped aisles shall return to a wall, guard or thewalking surface or shall be continuous to the handrail of an adjacent stepped aisle flight.

1029.16.3 Mid-aisle termination. Mid-aisle handrails shall not extend beyond the lowest riser and shall terminatewithin 18 inches (381 mm), measured horizontally, from the lowest riser. Handrail extensions are not required.

Exception: Mid-aisle handrails shall be permitted to extend beyond the lowest riser where the handrail extensionsdo not obstruct the width of the cross aisle.

Reason:The social stairway is a new style being used in common areas of schools and multi-assembly buildings. It appears tofall somewhere between stairways and assembly seating. If this is considered a stairway next to platforms, thegeneral requirement for handrails on both sides of the stairway prevents access to the platforms (Example 4). Considering this configuration as assembly seating would require one handrail with current text. This proposal considers this arrangement as a type of assembly seating. The width would have to be determinedusing both the general circulation number from the upper/lower floor and the seating in accordance with Section1029.6.1, which requires extra width if a handrail is not with 30”. By considering this assembly seating, accessiblewheelchairs spaces would already be addressed. Drop offs along the top would have to meet guard provisions.To address occupant safety, this proposal will require a mid-aisle handrail on wide stepped aisles in addition to thehandrail on the wall. The reasoning for 74” was that we did not want either side of the handrails to create a width thatwas not readily useable (30” + 44” = 74”). The second handrail being within 30” of the edge of the platform allowsflexibility in handrail placement, but still keeps the handrail within reach of persons moving off the platforms. Wherethere is not a cross aisle, the handrail would still have to have handrail extensions at the top and bottom, as well asmeet all the other handrail provisions in Section 1014 and 1029.6. This 2 handrails would typically not show up instadium seating where aisles are typically less wide than specified here.As you can see in the examples provided: Example 1 has two handrails, but with one on the far side of the platform. Example 4 a 2 handrail blocks access to the platforms, so people either climb up the platforms, or go under thehandrail. In example 2 and 3 a handrail is only provided on one side of the stairway, regardless of width. None ofthese configuration would address stairway safety and access to the platforms. Example 3 has an example handraildrawn in red of what these requirements would add.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Board

nd

nd

Page 32: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

of Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.

Figure 1

Figure 2

Figure 3

Page 33: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

Figure 4Cost ImpactThe code change proposal will increase the cost of construction .In some situations, this could require a 2 handrail for occupant safe egress on the stairways.Internal ID: 479

nd

Page 34: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E107-18IBC: SECTION 1030.1, (IFC[BE] 1030.1)Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

SECTION 1030 EMERGENCY ESCAPE AND RESCUE

Revise as follows:

1030.1 General.Where required. In addition to the means of egress required by this chapter, emergency escapeand rescue openings shall be provided in the following occupancies:

1. Group R-2 occupancies located in stories with only one exit or access to only one exit as permittedby Tables 1006.3.3(1) and 1006.3.3(2).

2. Group R-3 and R-4 occupancies.Basements and sleeping rooms below the fourth story above grade plane shall have not fewer than one exterioremergency escape and rescue opening in accordance with this section. Where basements contain one or more sleepingrooms, an emergency escape and rescue openingsopening shall be required in each sleeping room, but shall not berequired in adjoining areas of the basement. Such openings shall open directly into a public way or to a yard or courtthat opens to a public way.

Exceptions:

1. Basements with a ceiling height of less than 80 inches (2032 mm) shall not be required to haveemergency escape and rescue openings.

2. Emergency escape and rescue openings are not required from basements or sleeping rooms thathave an exit door or exit access door that opens directly into a public way or to a yard, court orexterior exit egress balcony that opens to a public way.

3. Basements without habitable spacesused only to house mechanical equipment and having notmore than 200 square feet (18.6 m ) in floor area shall not be required to have emergencyescape and rescue openings.4. Storm shelters are not required to comply with this section where the shelter is constructed inaccordance with ICC 500.

45. Within individual dwelling and sleeping units in Groups R-2 and R-3, where the building isequipped throughout with an automatic sprinkler system installed in accordance with Section903.3.1.1, 903.3.1.2 or 903.3.1.3, sleeping rooms in basements shall not be required to haveemergency escape and rescue openings provided that the basement has one of the following:4.15.1. One means of egress and one emergency escape and rescue opening.4.25.2. Two means of egress.

Reason:This is one of a series of 11 proposals to coordinate the Emergency Escape and Rescue Openings (EERO) technicalcriteria in the IBC and IRC. Please see the proposal for the definition of Emergency Escape and Rescue Openings foradditional information. Due to the code development schedule the proposals for IBC will be proposed in Group A andthe proposals for IRC will be proposed in Group B.IBC

The definition includes ‘exterior’, so it does not need to be repeated in the text. It was decided not to add the IRC defined ‘habitable attic’. If added to the IBC, would the IBC also have

to pick up the definition and the number of stories below the habitable attic space? (the IRC definition saysthis is not a story).

IBC Exception 2 – change to correct term for ‘exterior egress balcony’IBC Exception 3 – coordination with IRC, limit is just size without additional criteria for habitable. Add storm shelter exception to IBC. Reference ICC 500 so that the escape openings provided are what

is specified for storm shelters.There will be a similar proposal for the IRC in Group B.

2

Page 35: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This is a coordination item for exceptions for EEROs already permitted between the codes.Internal ID: 458

Page 36: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E108-18IBC: 1030.1.1, (IFC[BE] 1030.1.1)Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Revise as follows:

1030.1.1 Operational constraints and opening control devices. Emergency escape and rescue openings shallbe operational from inside the room without the use of keys or tools. Window-opening control devices complying withASTM F2090 shall be permitted for use on windows serving as a required emergency escape and rescue opening shallcomply with ASTM F2090.

Reason:This is one of a series of 11 proposals to coordinate the Emergency Escape and Rescue Openings (EERO) technicalcriteria in the IBC and IRC. Please see the proposal for the definition of Emergency Escape and Rescue Openings foradditional information. Due to the code development schedule the proposals for IBC will be proposed in Group A andthe proposals for IRC will be proposed in Group B.IBC - Last sentence reworded as a requirement to be consistent with IRCThis proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This is a coordination item for requirements for EEROs already permitted between the codes.Internal ID: 459

Page 37: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E109-18IBC: 1030.2, 1030.2.1, 1030.3, (IFC[BE] 1030.2, 1030.2.1, 1030.3)Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Add new text as follows:

1030.2 Emergency escape and rescue openings. . Emergency escape and rescue openings shall have minimumdimensions in accordance with Section 1030.2.1 through 1030.2.3.

Revise as follows:

1030.21030.2.1 Minimum size. Emergency escape and rescue openings shall have a minimum net clear opening of5.7 square feet (0.53 m2).

Exception: The minimum net clear opening for grade-floor emergency escape and rescue openings shall be 5 squarefeet (0.46 m2).

1030.2.11030.2.2 Minimum dimensions. The minimum net clear opening height dimension shall be 24 inches (610mm). The minimum net clear opening width dimension shall be 20 inches (508 mm). The net clear opening dimensionsshall be the result of normal operation of the opening.

1030.31030.2.3 Maximum height f rom f loor. Emergency Where a window is provided as the emergency escapeand rescue openings, such window shall have the bottom of the clear opening not greater than 44 inches (1118 mm)measured from the floor.

Reason:This is one of a series of 11 proposals to coordinate the Emergency Escape and Rescue Openings (EERO) technicalcriteria in the IBC and IRC. Please see the proposal for the definition of Emergency Escape and Rescue Openings foradditional information. Due to the code development schedule the proposals for IBC will be proposed in Group A andthe proposals for IRC will be proposed in Group B.This proposal deals with Minimum size, dimensions and height.IBC 310.3 – revise to coordinate language and organization with the IRC.There will be a similar proposal to Group B for IRC:This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This is a coordination item for requirements for EEROs already permitted between the codes.Internal ID: 460

Page 38: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E110-18IBC: 1030.3 (New), (IFC[BE] 1030.3 (New))Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Add new text as follows:

1030.3 Emergency escape and rescue doors. Where a door is provided as the required emergency escape andrescue opening, it shall be a swinging door or a sliding door.

Reason:This is one of a series of 11 proposals to coordinate the Emergency Escape and Rescue Openings (EERO) technicalcriteria in the IBC and IRC. Please see the proposal for the definition of Emergency Escape and Rescue Openings foradditional information. Due to the code development schedule the proposals for IBC will be proposed in Group A andthe proposals for IRC will be proposed in Group B.This proposal deals with doors used as emergency escape and rescue openings. IBC and IRC have different phrasesfor types of doors. Rather than totally separate requirements for doors and windows, the intent of this proposal is touse the same criteria as much as possible. That is literally what the current IRC text does, but with a lot of duplication. There will be a coordination change for IRC as part of Group B.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This is a coordination item for requirements for EEROs already permitted between the codes.Internal ID: 461

Page 39: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E111-18IBC: 1030.4, 1030.4.1, 1030.4.2, 1030.4.2.1 (New), 1030.4.3 (New), 1030.5, (IFC[BE] 1030.4, 1030.4.1,1030.4.2, 1030.4.2.1 (New), 1030.4.3 (New), 1030.5)Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Revise as follows:

1030.4 Window Area wells. An emergency escape and rescue opening with a finished sill height the bottom of theclear opening below the adjacent ground level grade shall be provided with a window an area well in accordance withSections 1030.4.1 and 1030.4.2 through 1030.4.4.

1030.4.1 Minimum size. The minimum horizontal area of the window area well shall be 9 square feet (0.84 m2), witha minimum dimension of horizontal projection and width of not less than 36 inches (914 mm). The area of the windowwell shall allow the emergency escape and rescue opening to be fully opened.

Exception: The ladder or steps required by Section 1030.4.2.1 shall be permitted to encroach not more than 6inches (152 mm) into the required dimensions of the area well.

1030.4.2 Ladders or steps. Window Area wells with a vertical depth of more than 44 inches (1118 mm) shall beequipped with an approved permanently affixed ladder or steps. Ladders or rungs shall have an inside width of not lessthan 12 inches (305 mm), shall project not less than 3 inches (76 mm) from the wall and shall be spaced not more than18 inches (457 mm) on center (o.c.) vertically for the full height of the window well. The ladder or steps shall notencroach into the required dimensions of the window well by more than 6 inches (152 mm). The ladder or steps shallnot be obstructed by the emergency escape and rescue opening . when the window or door is in the open position.Ladders or steps required by this section are exempt from the stairway requirements of shall not be required tocomply with Section 1011.

Add new text as follows:

1030.4.2.1 Ladders. Ladders or rungs shall have an inside width of at least 12 inches (305 mm), shall project at least3 inches (76 mm) from the wall and shall be spaced not more than 18 inches (457 mm) on center (o.c.) vertically for thefull height of the area well.

1030.4.3 Drainage. Area wells shall be designed for proper drainage by connecting to the building's foundationdrainage system required by Section 1805.

Exception: A drainage system for area wells is not required where the foundation is on well-drained soil or sand-gravel mixture soils in accordance with the United Soil Classification System, Group I Soils, in accordance withSection 1803.5.1.

Revise as follows:

1030.51030.4.4 Bars, grilles, covers and screens. BarsWhere bars, grilles, covers, screens or similar devicesare permitted to be placed over emergency escape and rescue openings, bulkhead enclosures or window area wellsthat serve such openings, provided that the minimum net clear opening size complies shall comply with Sections1030.1.1 through 1030.4.2 1030.2.2 and such 1030.4. Such devices shall be releasable or removable from the insidewithout the use of a key, tool or force greater than that which is required for normal operation of the emergencyescape and rescue opening. Where such bars, grilles, covers, screens or similar devices are installed in existingbuildings, they shall not reduce the net clear opening of the emergency escape and rescue opening and smoke alarmsshall be installed in accordance with Section 907.2.10 regardless of the valuation of the alteration.

Reason:This is one of a series of 11 proposals to coordinate the Emergency Escape and Rescue Openings (EERO) technicalcriteria in the IBC and IRC. Please see the proposal for the definition of Emergency Escape and Rescue Openings foradditional information. Due to the code development schedule the proposals for IBC will be proposed in Group A andthe proposals for IRC will be proposed in Group B.This proposal deals with area wells. There will be a coordinated change for IRC in Group B.

IBC 1030.4 - The same point of measurement should be used for both the maximum height above floor

Page 40: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

(section above) and the window well. Should not mix ‘grade’ and ‘ground level’.IBC 1030.4.1 - “horizontal projection and width” is more specific. IBC exception for ladder encroachment

moved up from 1030.4.2.IBC 1030.4.2 - IBC encroachment of ladder into well moved up to 1030.4.1. IRC. The sentence about the

window not obstructing the ladder has been clarified. Added ‘doors’. Requirements for ladders moved intoseparate section.

IBC 1030.4.3 - No change to requirements. Just pulled out to separate section.IBC 1030.4.4 - Revisions for coordination. Reference to emergency and escape opening size and

minimum window well size. IBC existing building sentence should be in IEBC. “Special knowledge is revisedto be consistent with IBC – the term allows for too broad of an interpretation.

There will be a coordination change for IRC as part of Group B.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This is a coordination item for requirements for EEROs already permitted between the codes.Internal ID: 462

Page 41: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E112-18IBC: 1030.4.2.2 (New), (IFC[BE] 1030.4.2.2(New))Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Add new text as follows:

1030.4.2.2 Steps. Steps shall have an inside width of not less than 12 inches (305 mm), shall have treads greaterthan 5 inches (127 mm) in depth and a riser height not greater than 18 inches (457 mm) for the full height of the areawell.

Reason:This is one of a series of 11 proposals to coordinate the Emergency Escape and Rescue Openings (EERO) technicalcriteria in the IBC and IRC. Please see the proposal for the definition of Emergency Escape and Rescue Openings foradditional information. Due to the code development schedule the proposals for IBC will be proposed in Group A andthe proposals for IRC will be proposed in Group B.The current provisions says ladders and steps don’t have to comply with the standard stairway provisions, however,while specific provisions are provided for ladders, no limits are provided for steps. The option here it the same widthand distance between steps are permitted for ladders. The tread depth is the minimum width from alternating treaddevices and ships ladders.Following are examples of stepped configurations that are used today. The proposed language would allow for theuse of Figures 1 and 3, but not 2 and 4.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.

Figure 1

Figure 2

Page 42: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

Figure 3

Figure 4Cost ImpactThe code change proposal will increase the cost of construction .There would be an increase for costs at EEROs where a home owner wanted to have the option of a stepped areawell. This could possibly add extra steps, but there is not an increase in size requirements.Internal ID: 463

Page 43: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

E114-18IBC: 1104.4Proponent: Ed Kullik, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Revise as follows:

1104.4 Multistory buildings and facilities. At least one accessible route shall connect each accessible story,mezzanineand occupied roofs in multilevel buildings and facilities.

Exceptions:

1. An accessible route is not required to stories, of not more than 3,000 square feet (278.7 m ) andare located above and below accessible levels. This exception shall not apply to:1.1. Multiple tenant facilities of Group M occupancies containing five or more tenant spaces

used for the sales or rental of goods and where at least one such tenant space islocated on a floor level above or below the accessible levels.

1.2. Stories or mezzanines containing offices of health care providers (Group B or I).1.3. Passenger transportation facilities and airports (Group A-3 or B).1.4. Government buildings.1.5. Structures with 4 or more dwelling units.

2. Storiesmezzanines contain accessible elements or other spaces as determined by Section 1107or 1108 are not required to be served by an accessible route from an accessible level.

3. In air traffic control towers, an accessible route is not required to serve the cab and the floorimmediately below the cab.

4. Where a two-story building or facility has one story or mezzanine with an occupant load of five orfewer persons that does not contain public use space, that story or mezzanine shall not berequired to be connected by an accessible route to the story above or below.

Reason:The intent of this proposal is a correlation items so that the efficiency units do not conflict with the Type Brequirements in the codes. The best way to explain the need for this is to use the example of a two story building with apartments over anotheruse, such as parking or mercantile. Section 1107.7.1.1 would require Type B units on that 2 floor. With typicalapartments, it would be very unlikely for 4 apartments and the corridor to have an area of less than 3,000 sq. ft. Therefore, they would not be able to use Section 1104.4 Exception 1 – which is correlated with Fair Housingrequirements. However, with efficiency units (IBC Section 1207.4 and IPC Section 404.6) , there could be 4 or moreefficiency units with a total area of less than 3,000 sq.ft. The addition of Item 1.5 would clarify that Section 1104.4Exception 1 should not be used for dwelling units. Other apartment building arrangements would continue to useSection 1104.4 Exception 2.This is important because the market is trending toward smaller living areas in multi-family R-2 structures particularly inurban areas. US Census statistics show that in 2000, app. 46,000 rental units built were less than 1,000 sq.ft. In 2015,114,000 units and in 2016, 99,000 units were less than 1,000 sq.ft. The Urban Land Institute reported in 2013 that majorMunicipalities including New York City, San Francisco, Boston, Dallas and Philadelphia are allowing smaller apartmentswith Seattle and Portland (OR) having no minimum sizes.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. Cost ImpactThe code change proposal will increase the cost of construction .This provision would require a elevator in buildings with four or more efficiency units on the 2nd floor over otheroccupancies where the 2nd floor area was less than 3,000 sq.ft. However, this is already a requirement under the Fair

2

nd

Page 44: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

Housing Accessibility Guidelines, so you are helping developers/architects/municipalities reduce the chance of beingsited and retrofitting to add an elevator at a later date. This would not have any effect on larger buildings or buildingswith apartments on the 1st floor. Internal ID: 3400

Page 45: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

F181-18IFC: 1031.7; IPMC: [F]702.4Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected]); Michael O'Brian,Chair, representing FCAC ([email protected])

2018 International Fire Code

Revise as follows:

1031.7 Emergency escape and rescue openings. Required emergency escape and rescue openings shall bemaintained in accordance with the that was code in effect at the time of construction, and both of the following:

1. Required emergency escape and rescue openings shall be operational from the inside of the roomwithout the use of keys or tools.

2. Bars, grilles, grates or similar devices are allowed permitted to be placed over emergency escapeand rescue openings provided that the minimum net clear opening size complies with the code thatwas in effect at the time of construction and such the unit is equipped with smoke alarms installedin accordance with Section 907.2.10 of the International Building Code. Such devices shall bereleasable or removable from the inside without the use of a key, tool or force greater than thatwhich is required for normal operation of the emergency escape and rescue opening.

2018 International Property Maintenance Code

Revise as follows:

[F] 702.4 Emergency escape openings.and rescue openings.. Required emergency escape and rescueopenings shall be maintained in accordance with the code in effect at the time of construction, and the following. bothof the following:

1. Required emergency escape and rescue openings shall be operational from the inside of the roomwithout the use of keys or tools.

2. Bars, grilles, grates or similar devices are permitted to be placed over emergency escape andrescue openings provided that the minimum net clear opening size complies with the code that wasin effect at the time of construction and such the unit is equipped with smoke alarms installed inaccordance with Section 907.2.10 of the International Building Code. Such devices shall bereleasable or removable from the inside without the use of a key, tool or force greater than thatwhich is required for normal operation of the escape and rescue opening.

Reason:This is one of a series of 11 proposals to coordinate the Emergency Escape and Rescue Openings (EERO) technicalcriteria in the I-codes. Please see the proposal for the definition of Emergency Escape and Rescue Openings foradditional information. Due to the code development schedule the proposals for IFC and IPMC will be proposed inGroup A and the proposals for IEC will be proposed in Group B.The IPMC should be revised to follow the format in the IFC, with a slight editorial change in language. To addresssituations where someone added these grills without a permit and for consistency with IEBC, add a requirement forsmoke detectors.There will be a coordinating proposal to the IEBC Section 505.4 and 701.4 as part of Group B.This proposal is submitted by the ICC Fire Code Action Committee (FCAC). The FCAC w as established by the ICC Boardof Directors to pursue opportunities to improve and enhance assigned International Codes with regard to fire safetyand hazardous materials in new and existing buildings and facilities and the protection of life and property in wildlandurban interface areas. In 2017 the Fire-CAC has held 3 open meetings. In addition, there were proposed changes.Related documentation and reports are posted on the FCAC website at: FCAC.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This is an existing requirement in the IEBC. To add this to IFC and IPMC is just reminding someone what therequirements are, so there is no change to requirements where someone wants to add grills.Internal ID: 465

Page 46: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

F276-18IBC: 307.1.1, 311.2, 311.3;IFC: 903.2.4.2 (New) (IBC:[F]903.2.4.2), 903.2.9.3 (New) (IBC:[F]903.2.9.3), Chapter 40 (New), 5001.1, 5701.2IMC: [F] 502.9.5Proponent: Michael O'Brian, Chair, representing FCAC ([email protected]); Ed Kullik, Chair, representing ICC BuildingCode Action Committee ([email protected])

2018 International Building Code

Revise as follows:

[F] 307.1.1 Uses other than Group H. An occupancy that stores, uses or handles hazardous materials asdescribed in one or more of the following items shall not be classified as Group H, but shall be classified as theoccupancy that it most nearly resembles.

1. Buildings and structures occupied for the application of flammable finishes, provided that suchbuildings or areas conform to the requirements of Section 416 and the International Fire Code.

2. Wholesale and retail sales and storage of flammable and combustible liquids in mercantileoccupancies conforming to the International Fire Code.

3. Closed piping system containing flammable or combustible liquids or gases utilized for theoperation of machinery or equipment.

4. Cleaning establishments that utilize combustible liquid solvents having a flash point of 140°F (60°C)or higher in closed systems employing equipment listed by an approved testing agency, providedthat this occupancy is separated from all other areas of the building by 1-hour fire barriersconstructed in accordance with Section 707 or 1-hour horizontal assemblies constructed inaccordance with Section 711, or both.

5. Cleaning establishments that utilize a liquid solvent having a flash point at or above 200°F (93°C).6. Liquor stores and distributors without bulk storage.7. Refrigeration systems.8. The storage or utilization of materials for agricultural purposes on the premises.9. Stationary storage battery systems installed in accordance with the International Fire Code.10. Corrosive personal or household products in their original packaging used in retail display.11. Commonly used corrosive building materials.12. Buildings and structures occupied for aerosol product storage shall be classified as Group S-1,

provided that such buildings conform to the requirements of the International Fire Code.13. Display and storage of nonflammable solid and nonflammable or noncombustible liquid hazardous

materials in quantities not exceeding the maximum allowable quantity per control area in Group M orS occupancies complying with Section 414.2.5.

14. The storage of black powder, smokeless propellant and small arms primers in Groups M and R-3and special industrial explosive devices in Groups B, F, M and S, provided such storage conforms tothe quantity limits and requirements prescribed in the International Fire Code.

15. Stationary fuel cell power systems installed in accordance with the International Fire Code.16. Capacitor energy storage systems in accordance with the International Fire Code.17. Group B higher education laboratory occupancies complying with Section 428 and Chapter 38 of the

International Fire Code18. Distilling or brewing of beverages conforming to the requirements of the International Fire Code.19. The storage of beer, distilled spirits and wines in barrels and casks conforming to the requirements

of the International Fire Code.

311.2 Moderate-hazard storage, Group S-1. Storage Group S-1 occupancies are buildings occupied for storageuses that are not classified as Group S-2, including, but not limited to, storage of the following:

Aerosol products, Levels 2 and 3

Page 47: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

Aircraft hangar (storage and repair)Bags: cloth, burlap and paperBamboos and rattanBasketsBelting: canvas and leatherBeverages: over 16-percent alcohol contentBooks and paper in rolls or packsBoots and shoesButtons, including cloth covered, pearl or boneCardboard and cardboard boxesClothing, woolen wearing apparelCordageDry boat storage (indoor)FurnitureFursGlues, mucilage, pastes and sizeGrainsHorns and combs, other than celluloidLeatherLinoleumLumberMotor vehicle repair garages complying with the maximum allowable quantities of hazardous materials

listed in Table 307.1(1) (see Section 406.8)Photo engravingsResilient flooringSelf-service storage facility (mini-storage)SilksSoapsSugarTires, bulk storage ofTobacco, cigars, cigarettes and snuffUpholstery and mattressesWax candles

311.3 Low-hazard storage, Group S-2. Storage Group S-2 occupancies include, among others, buildings used forthe storage of noncombustible materials such as products on wood pallets or in paper cartons with or without singlethickness divisions; or in paper wrappings. Such products are permitted to have a negligible amount of plastic trim,such as knobs, handles or film wrapping. Group S-2 storage uses shall include, but not be limited to, storage of thefollowing:

AsbestosBeverages up to and including 16-percent alcohol in metal, glass or ceramic containersCement in bagsChalk and crayonsDairy products in nonwaxed coated paper containersDry cell batteriesElectrical coils

Page 48: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

Electrical motorsEmpty cansFood productsFoods in noncombustible containersFresh fruits and vegetables in nonplastic trays or containersFrozen foodsGlassGlass bottles, empty or filled with noncombustible liquidsGypsum boardInert pigmentsIvoryMeatsMetal cabinetsMetal desks with plastic tops and trimMetal partsMetalsMirrorsOil-filled and other types of distribution transformersParking garages, open or enclosedPorcelain and potteryStovesTalc and soapstonesWashers and dryers

2018 International Fire Code

Add new text as follows:

903.2.4.2 Group F-1 Distilled Spirits. An automatic sprinkler system shall be provided throughout a Group F-1 firearea used for the manufacture of distilled spirits.

903.2.9.3 Group S-1 Distilled spirits or wine. An automatic sprinkler system shall be provided throughout a GroupS-1 fire area used for the bulk storage of distilled spirits or wine.

CHAPTER 40 STORAGE OF DISTILLED SPIRITS AND WINES

SECTION 4001 GENERAL

4001.1 General. The storage of distilled spirits and wines in barrels and casks shall comply with this chapter inaddition to other applicable requirements of this code.

4001.1.1 Nonapplicability. Chapter 50 and Chapter 57 of this code are not applicable to the storage of distilledspirits and wines in barrels and casks as identified in Section 5001.1, Exception 10, and Section 5701.2, Item 10.

SECTION 4002 DEFINIT IONS

4002.1 Terms def ined in Chapter 2. Words and terms used in this chapter and defined in Chapter 2 shall have themeanings ascribed to them as defined therein.

4003 PRECAUTIONS AGAINST FIRE

4003.1 Spill Control. Drainage or containment systems shall be provided by means of curbs, scuppers, specialdrains, or other suitable means to prevent the flow of spills throughout the building.

Page 49: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

4003.2 Ventilation. Ventilation shall be provided for rooms and spaces where distilled spirits and wines in barrelsand casks are stored in accordance with the International Mechanical Code and one of the following:

1. The rooms and spaces shall be ventilated at a rate sufficient to maintain the concentration ofvapors within the area at or below 25% of the LFL . This shall be confirmed by sampling of the actualvapor concentration under normal operating conditions. The sampling shall be conductedthroughout the enclosed storage area extending to or toward the bottom and the top of theenclosed storage area. The vapor concentration used to determine the required ventilation rateshall be the highest measured concentration during the sampling procedure. The sampling shall beconducted manually or by installation of a continuously monitoring flammable vapor detectionsystem.

2. The rooms and spaces shall be provided exhaust ventilation at a rate of not less than 1 cfm/ft2 (0.3m3/min) of solid floor area. The exhaust ventilation shall be accomplished by natural or mechanicalmeans, with discharge of the exhaust to a safe location outside the building.

4003.3 Sources of ignition.. Sources of ignition shall be controlled in accordance with Sections 4003.3.1 through4003.4.

4003.3.1 Smoking. Smoking shall be prohibited and "No Smoking" signs provided as follows:

1. In rooms or areas where hazardous materials are stored or dispensed or used in open systems inamounts requiring a permit in accordance with Section 105.6 and 105.7

2. Within 25 feet (7620mm) of outdoor storage, dispensing or open use areas.3. Facility or areas within facilities that have been designated as totally "no smoking" shall have "No

Smoking" signs placed at all entrances to the facility or area. Designated areas within such facilitieswhere smoking is permitted either permanently or temporarily shall be identified with signsdesignating that smoking is permitted in these areas only.

4. In rooms or areas where flammable or combustible hazardous materials are stored, dispensed orused.

Signs required by this section shall be in English as a primary language or in symbols allowed by this code and shallcomply with Section 310.

4003.3.2 Open Flame. Open flames and high-temperature devices shall not be used in a manner that creates ahazardous condition and shall be listed for use with the hazardous materials stored or used.

4003.3.3 Industrial trucks. Powered industrial trucks used in areas designated as hazardous (classified)locationsin accordance with NFPA 70 shall be listed and labeled for use in the environment intended in accordance with NFPA505.

4003.3.4 Electrical. Electrical wiring and equipment shall be installed and maintained in accordance with Section 605and NFPA 70.

4003.4 Lightning. Structures containing barrel storage should be protected from lightning. The lightning protectionequipment shall be installed in accordance with NFPA 780 and NFPA 70.

SECTION 4004 STORAGE

4004.1 Storage. Storage shall be in accordance with this section and Section 315.

4004.2 Empty containers. The storage of empty containers previously used for the storage of flammable orcombustible liquids, unless free from explosive vapors, shall be stored as required for filled containers.

4004.3 Basement storage. Class I liquids shall be allowed to be stored in basements in amounts not exceeding themaximum allowable quantity over control area for use-open systems in Table 5003.1.1(1), provided that automaticsuppression and other fire protection are provided in accordance with Chapter 9. Class II and IIIA liquids shall also beallowed to be stored in basements, provided that automatic suppression and other fire protection are provided inaccordance with Chapter 9.

4004.4 Bulk beverage storage areas. There shall be no storage of combustible materials in the bulk beveragestorage areas not related to the beverage storage activities.

Page 50: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

SECTION 4005 FIRE PROTECTION

4005.1 Automatic sprinkler system. The storage of distilled spirits and wines shall be protected by an approvedautomatic sprinkler system as required by Chapter 9.

4005.2 Portable Fire Extinguishers. Approved portable fire extinguishers shall be provided in accordance withSection 906.

SECTION 4006 SIGNAGE

4006.1 Hazard identif ication signs. Unless otherwise exempted by the fire code official, visible hazardidentification signs as specified in NFPA 704 for the specific material contained shall be placed on stationarycontainers and above ground tanks and at entrances to locations where hazardous materials are stored, dispensed,used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire codeofficial.

4006.1.1 Maintenance and style. Signs and markings required by Section 4006.1 shall not be obscured orremoved, shall be in English as a primary language or in symbols allowed by this code, shall be durable, and the size,color, and lettering shall be approved.

Revise as follows:

5001.1 Scope. Prevention, control and mitigation of dangerous conditions related to storage, dispensing, use andhandling of hazardous materials shall be in accordance with this chapter.This chapter shall apply to all hazardous materials, including those materials regulated elsewhere in this code, exceptthat where specific requirements are provided in other chapters, those specific requirements shall apply in accordancewith the applicable chapter. Where a material has multiple hazards, all hazards shall be addressed.

Exceptions:

1. In retail or wholesale sales occupancies, the quantities of medicines, foodstuff or consumerproducts and cosmetics containing not more than 50 percent by volume of water-miscible liquidsand with the remainder of the solutions not being flammable shall not be limited, provided thatsuch materials are packaged in individual containers not exceeding 1.3 gallons (5 L).

2. Quantities of alcoholic beverages in retail or wholesale sales occupancies shall not be limitedproviding the liquids are packaged in individual containers not exceeding 1.3 gallons (5 L).

3. Application and release of pesticide and agricultural products and materials intended for use inweed abatement, erosion control, soil amendment or similar applications where applied inaccordance with the manufacturers' instructions and label directions.

4. The off-site transportation of hazardous materials where in accordance with Department ofTransportation (DOTn) regulations.

5. Building materials not otherwise regulated by this code.6. Refrigeration systems (see Section 605).7. Stationary storage battery systems regulated by Section 1206.2.8. The display, storage, sale or use of fireworks and explosives in accordance with Chapter 56.9. Corrosives utilized in personal and household products in the manufacturers' original consumer

packaging in Group M occupancies.10. The storage of beer, distilled spirits and wines in wooden barrels and casks.11. The use of wall-mounted dispensers containing alcohol-based hand rubs classified as Class I or II

liquids where in accordance with Section 5705.5.

5701.2 Nonapplicability. This chapter shall not apply to liquids as otherwise provided in other laws or regulations orchapters of this code, including:

1. Specific provisions for flammable liquids in motor fuel-dispensing facilities, repair garages, airportsand marinas in Chapter 23.

2. Medicines, foodstuffs, cosmetics and commercial or institutional products containing not more than50 percent by volume of water-miscible liquids and with the remainder of the solution not being

Page 51: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

NFPA National Fire Protection Association1 Batterymarch Park

Quincy MA 02169-7471

flammable, provided that such materials are packaged in individual containers not exceeding 1.3gallons (5 L).

3. Quantities of alcoholic beverages in retail or wholesale sales or storage occupancies, providiedthat the liquids are packaged in individual containers not exceeding 1.3 gallons (5 L).

4. Storage and use of fuel oil in tanks and containers connected to oil-burning equipment. Suchstorage and use shall be in accordance with Section 603. For abandonment of fuel oil tanks, thischapter applies.

5. Refrigerant liquids and oils in refrigeration systems (see Section 605).6. Storage and display of aerosol products complying with Chapter 51.7. Storage and use of liquids that do not have a fire point when tested in accordance with ASTM D92.8. Liquids with a flash point greater than 95°F (35°C) in a water-miscible solution or dispersion with a

water and inert (noncombustible) solids content of more than 80 percent by weight, which do notsustain combustion.

9. Liquids without flash points that can be flammable under some conditions, such as certainhalogenated hydrocarbons and mixtures containing halogenated hydrocarbons.

10. The storage of beer, distilled spirits and wines in wooden barrels and casks.11. Commercial cooking oil storage tank systems located within a building and designed and installed

in accordance with Section 608 and NFPA 30.

Add new standard(s) follows:

780-17:Standard f or the Installation of Lightning Protection Systems

2018 International Mechanical Code

Revise as follows:

[F] 502.9.5 Flammable and combustible liquids. Exhaust ventilation systems shall be provided as required bySections 502.9.5.1 through 502.9.5.5 for the storage, use, dispensing, mixing and handling of flammable and combustibleliquids. Unless otherwise specified, this section shall apply to any quantity of flammable and combustible liquids.

Exception Exceptions:

1. This section shall not apply to flammable and combustible liquids that are exempt from theInternational Fire Code.

2. The storage of beer, distilled spirits and wines in barrels and casks conforming to therequirements of the International Fire Code.

.

Reason:Currently, due to changes over several code change cycles, there is confusion on how to treat distilled spirits andwines as a Group in the International Building Code and for applicable safety requirements of the International FireCode. Coordination between the codes on this subject is important because distilled spirits still have the properties offlammable liquids and proper safeguards must be provided for the occupancies housing such activities. [F] COMBUSTIBLE LIQUID. A liquid having a closed cup flash point at or above 100°F (38°C). Combustible liquids shallbe subdivided as follows:Class II. Liquids having a closed cup flash point at or above 100°F (38°C) and below 140°F (60°C).Class IIIA. Liquids having a closed cup flash point at or above 140°F (60°C) and below 200°F (93°C).Class IIIB. Liquids having a closed cup flash point at or above 200°F (93°C).The category of combustible liquids does not include compressed gases or cryogenic fluids.

Page 52: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

[F] FLAMMABLE LIQUID. A liquid having a closed cup flash point below 100°F (38°C). Flammable liquids are furthercategorized into a group known as Class I liquids. The Class I category is subdivided as follows:Class IA. Liquids having a flash point below 73°F (23°C) and a boiling point below 100°F (38°C).Class IB. Liquids having a flash point below 73°F (23°C) and a boiling point at or above 100°F (38°C).Class IC. Liquids having a flash point at or above 73°F (23°C) and below 100°F (38°C). The category of flammableliquids does not include compressed gases or cryogenic fluids.

Page 53: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

The International Building Code classifies the various activities into Groups. The manufacturing of beverages with over16 percent alcohol is classified as an F-1 and the manufacturing of beverages 16 percent alcohol or less is classifiedas an F-2:306.2 Moderate-hazard factory industrial, Group F-1. Factory industrial uses that are not classified as FactoryIndustrial F-2 Low Hazard shall be classified as F-1 Moderate Hazard and shall include, but not be limited to, thefollowing:Beverages: over 16-percent alcohol content306.3 Low-hazard factory industrial, Group F-2. Factory industrial uses that involve the fabrication ormanufacturing of noncombustible materials that during finishing, packing or processing do not involve a significant firehazard shall be classified as F-2 occupancies and shall include, but not be limited to, the following:Beverages: up to and including 16-percent alcohol contentThe storage of beverages with up to and including 16-percent alcohol in metal, glass or ceramic containers is classifiedas an S-2:311.3 Low -hazard storage, Group S-2. Storage Group S-2 occupancies include, among others, buildings used for

Page 54: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

the storage of noncombustible materials such as products on wood pallets or in paper cartons with or without singlethickness divisions; or in paper wrappings. Such products are permitted to have a negligible amount of plastic trim,such as knobs, handles or film w rapping. Group S-2 storage uses shall include, but not be limited to, storage of thefollowing:Beverages up to and including 16-percent alcohol in metal, glass or ceramic containersHowever, there is no Group S classification listed for storage of beverages with over 16 percent alcohol and there areno listed “Uses other than Group H” for distilling activities or bulk storage of distilled spirits in Section 307 High HazardGroup H.311.2 Moderate-hazard storage, Group S-1. Storage Group S-1 occupancies are buildings occupied for storageuses that are not classified as Group S-2, including, but not limited to, storage of the following:???[F] 307.1.1 Uses other than Group H. An occupancy that stores, uses or handles hazardous materials asdescribed in one or more of the following items shall not be classified as Group H, but shall be classified as theoccupancy that it most nearly resembles.2. Wholesale and retail sales and storage of flammable and combustible liquids in mercantile occupancies conformingto the International Fire Code.6. Liquor stores and distributors without bulk storage.The lack of a S-1 Group designation for storage activities for beverages over 16-percent alcohol or any bulk storagerecognition and the lack of recognition under “Uses other than Group H” causes disputes between code officials as toapplication of a Group H to storage of the finished product after it leaves the Factory group process.In the International Fire Code there is confusion about the applicability of Chapter 50 Hazardous Materials-GeneralProvisions and Chapter 57 Flammable and Combustible Liquids provisions to distilled spirits because of the exceptionfor distilled spirits and wines stored in wooden barrels and casks in IFC Chapters 50 and 57. The issue is arisingbecause of the growing popularity of "boutique" or "craft" distillers.A review of the International Fire Code Commentary concerning the distilled spirits in wooden barrels exception findsthe following statement which highlights the conflict between the codes:5001.1 Scope.Prevention, control and mitigation of dangerous conditions related to storage, dispensing, use and handling ofhazardous materials shall be in accordance with this chapter.This chapter shall apply to all hazardous materials, including those materials regulated elsewhere in this code, exceptthat w here specific requirements are provided in other chapters, those specific requirements shall apply inaccordance with the applicable chapter. Where a material has multiple hazards, all hazards shall be addressed.Exceptions:10. The storage of distilled spirits and wines in wooden barrels and casks.IFC Commentary:"Exception 10 covers the storage of distilled spirits and wines in wooden barrels and casks. This statement mayappear to exempt all requirements for these products from being a Group H occupancy. However, the IBC will stillclassify the storage area as a Group H occupancy if the amounts exceed the maximum allow able quantities (MAQs)per control area listed in Table 307.1(1) of that code for flammable or combustible liquids. All requirements for a GroupH occupancy in the IBC are still applicable; however, any requirements from the code (fire code) are not."5701.1 Scope and application. Prevention, control and mitigation of dangerous conditions related to storage, use,dispensing, mixing and handling of flammable and combustible liquids shall be in accordance with Chapter 50 and thischapter.5701.2 Nonapplicability. This chapter shall not apply to liquids as otherwise provided in other laws or regulations orchapters of this code, including:10. The storage of distilled spirits and wines in wooden barrels and casks.IFC Commentary:“Item 10 makes the storage of distilled spirits and wines in wooden barrels and casks exempt from this chapter.Although their contents are classified as flammable liquids, the containers do not pose the rupture hazard that othercontainers do. Barrels and casks will leak their contents and contribute to the fire as the metal bands that secure thestaves expand and loosen. Even this hazard feature is generally mitigated by the operation of automatic sprinklersthat prevent the fire from progressing to the point where the metal bands get hot enough to expand. A similarexception also appears in Section 5001.1.”

Page 55: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

In summary, when you manufacture distilled spirits you are an F-1 occupancy. When you manufacture wine or beer youare an F-2 occupancy. When you store wine and beer you are an S-2 occupancy. When you store distilled spirits inretail packaging you are not an H occupancy but there is no clarifying entry under S-1. If you store any beverage withover 16% alcohol in bulk, (includes some wines), you have an H occupancy. As far as risk goes, manufacturing has ahigher risk than storage for an event, yet manufacturing of distilled spirits is an F-1 regardless of amount but an H ifstored in bulk. This makes no sense. To top it off, when you go to the IFC, if you store your distilled spirits in bulk inwooden barrels Chapter 50 and 57 do not apply so there are no code requirements.This proposal attempts to address this confusion recognizing the main safety issues are the need for automatic firesuppression, the need for mechanical ventilation and need for containment of spills. In 2005 the Distilled Spirits Councilof The United States (DISCUS) released recommended guidelines for these facilities which addressed fire protection,ventilation and secondary containment requirements. Those guidelines were consulted in drafting the new chapterproposed for the International Fire Code.It is proposed to make the following Group designation changes to the International Building Code:Add a classification under S-1 for storage of beverages over 16% alcohol whether in bulk or retail packaging.Modify the classification under S-2 to apply to all beverages up to and including 16-percent alcohol regardless ofcontainer type.Modify Section [F] 307.1.1 “Uses other than Group H” to add classifications for distilling, brewing or storage of thesematerials.In the International Fire Code, it is proposed to strike the word “wooden” and addition of the "word beer" in theexceptions in Chapters 50 and 57:10. The storage of beer, distilled spirits and wines in wooden barrels and casks.In the International Mechanical Code it is proposed to strike the word “wooden” from Section [F] 502.9.5 “Flammableand combustible liquids”.In conjunction with the Group classification cleanup and striking the word wooden in both the IFC and IMC, protectionfeatures will be addressed by establishing new sprinkler thresholds for the manufacture of distilled spirits or bulkstorage of distilled spirits regardless of square footage along with the creation of a new chapter in the InternationalFire Code for the Storage of Distilled Spirits and Wines.This proposal is submitted by the ICC Fire Code Action Committee (FCAC) and the ICC Building Code Action Committee(BCAC). The FCAC was established by the ICC Board of Directors to pursue opportunities to improve and enhanceassigned International Codes with regard to fire safety and hazardous materials in new and existing buildings andfacilities and the protection of life and property in wildland urban interface areas. In 2017 the Fire-CAC has held 3 openmeetings. In addition, there were numerous conference calls, Regional Work Group and Task Group meetings for thecurrent code development cycle, which included members of the committees as well as any interested parties, todiscuss and debate the proposed changes. Related documentation and reports are posted on the FCAC website at:https://www.iccsafe.org/codes-tech-support/cs/fire-code-action-committee-fcac/. BCAC was established by the ICCBoard of Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes orportions thereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Groupmeetings and conference calls for the current code development cycle, which included members of the committee as well as any interested party to discuss and debate the proposed changes. Related documentation and reports areposted on the BCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. Bibliography:Recommended Fire Protection Practices for Distilled Spirits Beverage Facilities, Third EditionPrepared Under the Auspices of The Distilled Spirits Council of the United States, Inc.http://www.discus.org/policy/fireprotection/Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This proposal will likely break even on the cost of construction by clarifying what the appropriate Group designation is,elimination of the unnecessary H classifications, and clarifying what protection levels are necessary.Internal ID: 182

Page 56: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G4-18IBC: 202Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

THIS CODE CHANGE WILL BE HEARD BY THE MEANS OF EGRESS COMMITTEE. SEE THE TENTATIVE HEARING ORDER FORTHIS COMMITTEE.

2018 International Building Code

SECTION 202 DEFINIT IONS

Revise as follows:

[BE] GRADE FLOOR EMERGENCY ESCAPE AND RESCUE OPENING. A window or other An emergency escape and rescueopening located such that the sill height bottom of the clear opening is not more than 44 inches (1118 mm) above orbelow the finished ground level adjacent to the opening.

Reason:This is one of a series of 11 proposals to coordinate the Emergency Escape and Rescue Openings (EERO) technicalcriteria in the IBC and IRC. Please see the proposal for the definition of Emergency Escape and Rescue Openings foradditional information. Due to the code development schedule the proposals for IBC will be proposed in Group A andthe proposals for IRC will be proposed in Group B.The phrase “grade floor emergency escape and rescue opening” is used in IBC 1030.2 and IRC R310.2.1. The definitionshould be for the phrase as utilized in the text. The definition for EEROs includes “windows, doors or other similardevices.” Using the defined term EERO instead of “windows and other openings” encompasses all options.What is a ‘sill’ is not clear – the change to “bottom of the clear opening” will set a specific height for consistency withtechnical criteria.There will be a Group B proposal for the IRC.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This coordination of an existing definition with no technical changes to the text.Internal ID: 455

Page 57: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G5-18 Part IPART 1:IBC: 202; IFC: 202; PART 2: IPMC: 202 (New)Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

THIS IS A TWO PART CODE CHANGE. PART 1 WILL BE HEARD BY THE MEANS OF EGRESS COMMITTEE. PART 2 WILL BEHEARD BY THE PROPERTY MAINTENANCE COMMITTEE. SEE THE TENTATIVE HEARING ORDER FOR THESE COMMITTEE.

2018 International Building Code

SECTION 202 DEFINIT IONS

Revise as follows:

[BE] EMERGENCY ESCAPE AND RESCUE OPENING. An operable exterior window, door or other similar device thatprovides for a means of escape and access for rescue in the event of an emergency.

2018 International Fire Code

SECTION 202 GENERAL DEFINIT IONS

Revise as follows:

[BE] EMERGENCY ESCAPE AND RESCUE OPENING. An operable exterior window, door or other similar device thatprovides for a means of escape and access for rescue in the event of an emergency.

Internal ID: 454

Page 58: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G5-18 Part IIIPMC: SECTION 202, 202 (New)Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Property Maintenance Code

SECTION 202 GENERAL DEFINIT IONS

Add new def inition as follows:

EMERGENCY ESCAPE AND RESCUE OPENING. An operable window, door or other similar device that provides for ameans of escape and access for rescue in the event of an emergency.

Reason:The intent of this proposal is the coordinate the definitions for emergency escape and rescue openings (EERO)between IBC, IRC, IEBC, IPMC, IFC. The EERO is always an exterior opening, and this descriptor is in the definition inIRC. The definition should appear in all codes where there are criteria for EEROs, so the definition should be added toIPMC and IEBC.There will be a code proposal in Group B to coordinate IRC and IEBC.This is the start of a series of 11 proposals to coordinate the requirements for Emergency Escape and Rescue Opening(EERO) requirements, primarily in the IBC and IRC, but also in the IEBC, IPMC and IFC. Due to the code developmentschedule the proposals for IBC, IPMC and IFC will be proposed in Group A and the proposals for IRC and IEBC will beproposed in Group B.So that it is clear what the result of these overall proposals will be, the following is a clean version of what the text forEERO would be if all proposals are approved. The one section in the IRC that the BCAC is not proposing to duplicate inthe IBC is the allowance for a EERO to be located below a deck.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.This is what the EERO requirements would look like if all of the proposals are approved.IBCEMERGENCY ESCAPE AND RESCUE OPENING. An operable exterior window, door or other similar device thatprovides for a means of escape and access for rescue in the event of an emergency.GRADE FLOOR EMERGENCY ESCAPE AND RESCUE OPENING. An emergency escape and rescue opening locatedsuch that the bottom of the clear opening is not more than 44 inches (1118 mm) above or below the finished groundlevel adjacent to the opening.SECTION 1030EMERGENCY ESCAPE AND RESCUE1030.1 Where required. In addition to the means of egress required by this chapter emergency escape and rescueopenings shall be provided in the following occupancies:1. Group R-2 occupancies located in stories with only one exit or access to only one exit as permitted by Tables1006.3.3(1) and 1006.3.3(2)2. Group R-3 and R-4 occupancies.Basements and sleeping rooms below the fourth story above grade plane shall have no fewer than one emergencyescape and rescue opening in accordance with this section. Where basements contain one or more sleeping rooms, anemergency escape and rescue openings shall be required in each sleeping room, but shall not be required in adjoiningareas of the basement. Such openings shall open directly into a public way or to a yard or court that opens to a publicway.Exceptions:

Page 59: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

1. Basements with a ceiling height of less than 80 inches (2032 mm) shall not be required to have emergency escapeand rescue openings.2. Emergency escape and rescue openings are not required from basements or sleeping rooms that have an exit dooror exit access door that opens directly into a public way or to a yard, court or exterior egress balcony that opens to apublic way.3. Basements used only to house mechanical equipment and having not more than 200 square feet (18.6 m2) in floorarea shall not be required to have emergency escape and rescue openings.4. Storm shelters are not required to comply with this section where the shelter is constructed in accordance with ICC500.5. Within individual dwelling and sleeping units in Groups R-2 and R-3, where the building is equipped throughout with anautomatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3, sleeping rooms inbasements shall not be required to have emergency escape and rescue openings provided that the basement has oneof the following:5.1. One means of egress and one emergency escape and rescue opening 5.2. Two means of egress.1030.1.1 Operational constraints and opening control devices. Emergency escape and rescue openings shallbe operational from inside the room without the use of keys or tools. Window opening control devices on windowsserving as a required emergency escape and rescue opening shall comply with ASTM F2090.1030.2 Emergency escape and rescue openings. Emergency escape and rescue opening shall have minimumdimensions in accordance with Section 1030.2.1 through 1030.2.3.1030.2.1 Minimum size. Emergency escape and rescue openings shall have a minimum net clear opening of 5.7square feet (0.53 m ).Exception: The minimum net clear opening for grade-floor emergency escape and rescue openings shall be 5 squarefeet (0.46 m ).1030.2.2 Minimum dimensions. The minimum net clear opening height dimension shall be 24 inches (610 mm). Theminimum net clear opening width dimension shall be 20 inches (508 mm). The net clear opening dimensions shall be theresult of normal operation of the opening.1030.2.3 Maximum height f rom floor. Where a window is provided as the Emergency escape and rescueopenings, such window shall have the bottom of the clear opening not greater than 44 inches (1118 mm) measuredfrom the floor.1030.3 Emergency escape and rescue doors. Where a door is provided as the required emergency escape andrescue opening, it shall be a swinging door or a sliding door.1030.4 Area wells. An emergency escape and rescue opening with the bottom of the clear opening below theadjacent grade shall be provided with an area well in accordance with Sections 1030.4.1 through 1030.4.4.1030.4.1 Minimum size. The minimum horizontal area of the area well shall be 9 square feet (0.84 m ), with ahorizontal projection and width of not less than 36 inches (914 mm). The area well shall allow the emergency escapeand rescue opening to be fully opened.Exception: The ladder or steps required by Section 1030.4.2.1 shall be permitted to encroach not more than 6 inches(152 mm) into the required dimensions of the area well.1030.4.2 Ladders or steps. Area wells with a vertical depth of more than 44 inches (1118 mm) shall be equippedwith an approved permanently affixed ladder or steps. The ladder or steps shall not be obstructed by the emergencyescape and rescue opening when the window or door is in the open position. Ladders or steps required by this sectionshall not be required to comply with Section 1011.1030.4.2.1 Ladders. Ladders or rungs shall have an inside width of at least 12 inches (305 mm), shall project at least3 inches (76 mm) from the wall and shall be spaced not more than 18 inches (457 mm) on center (o.c.) vertically for thefull height of the area well.1030.4.2.2 Steps. Steps shall have an inside width of at least 12 inches (305 mm), shall have minimum treads depthof 5 inches (127 mm) and a maximum riser height of 18 inches (457 mm) for the full height of the area well.1030.4.3 Drainage. Area wells shall be designed for proper drainage by connecting to the building’s foundationdrainage system required by Section 1805.Exception: A drainage system for area wells is not required where the foundation is on well-drained soil or sand-gravel mixture soils in accordance with the United Soil Classification System, Group I Soils, in accordance with Section1803.5.1.

2

2

2

Page 60: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

1030.4.4 Bars, grilles, covers and screens. Where Bars, grilles, covers, screens or similar devices are placedover emergency escape and rescue openings, bulkhead enclosures, or area wells that serve such openings theminimum net clear opening size shall comply with Section 1030.1.1 through 1030.2.2 and 1030.4. Such devices shall bereleasable or removable from the inside without the use of a key, tool or force greater than that which is required fornormal operation of the emergency escape and rescue opening.IRC[RB] EMERGENCY ESCAPE AND RESCUE OPENING. An operable exterior window, door or similar device that providesfor a means of escape and access for rescue in the event of an emergency.GRADE FLOOR EMERGENCY ESCAPE AND RESCUE OPENING. An emergency escape and rescue opening locatedsuch that the bottom of the clear opening is not more than 44 inches (1118 mm) above or below the finished groundlevel adjacent to the opening.SECTION R310EMERGENCY ESCAPE AND RESCUE OPENINGSR310.1 Where required. Basements, habitable attics and every sleeping room shall have no fewer than oneemergency escape and rescue opening in accordance with this section. Where basements contain one or moresleeping rooms, an emergency escape and rescue opening shall be required in each sleeping room, but shall not berequired in adjoining areas of the basement. Such openings shall open directly into a public way, or to a yard or courtthat opens to a public way.Exceptions:1. Basements with a ceiling height of less than 80 inches (2032 mm) shall not be required to have emergency escapeand rescue openings.2. Emergency escape and rescue openings are not required from basements or sleeping rooms that have an exit dooror exit access door that opens directly into a public way or to a yard, or that opens to a public way.3. Basements used only to house mechanical equipment not exceeding a total floor area of 200 square feet (18.58 m )shall not be required to have emergency escape and rescue openings.4. Storm shelters are not required to comply with this section where the shelter is constructed in accordance with ICC500.5. Where the dwelling or townhouse is equipped with an automatic sprinkler system installed in accordancewith Section P2904, sleeping rooms in basements shall not be required to have emergency escape and rescueopenings provided that the basement has one of the following:5.1. One means of egress complying with Section R311 and one emergency escape and rescue opening.5.2. Two means of egress complying with Section R311.R310.1.1 Operational constraints and opening control devices. Emergency escape and rescue openings shallbe operational from the inside of the room without the use of keys, or tools. Window opening control devices onwindows serving as a required emergency escape and rescue opening shall comply with ASTM F2090.R310.2 Emergency escape and rescue openings. Emergency escape and rescue openings shall have minimumdimensions in accordance with Section R310.2.1 through R310.2.3.R310.2.1 Minimum size. Emergency and escape rescue openings shall have a net clear opening of not less than 5.7square feet (0.530 m ).Exception: The minimum net clear opening for grade-floor emergency escape and rescue openings shall be 5 squarefeet (0.465 m ).R310.2.2 Minimum dimensions. The minimum net clear opening height dimension shall be 24 inches (610 mm). Theminimum net clear opening width dimension shall be 20 inches (508 mm). The net clear opening dimensions shall be theresult of normal operation of the opening.R310.2.3 Maximum height f rom f loor. Where a window is provided as the emergency escape and rescue openingssuch window shall have the bottom of the clear opening not greater than 44 inches (1118 mm) above the floor.R310.3 Emergency escape and rescue doors. Where a door is provided as the required emergency escape andrescue opening, it shall be a swinging door or a sliding door.R310.4 Area wells. An emergency escape and rescue opening with the bottom of the clear opening below theadjacent grade shall be provided with an area well in accordance with Sections R310.4.1 through R310.4.4.R310.4.1 Minimum size. The horizontal area of the area well shall be not less than 9 square feet (0.9 m ), with ahorizontal projection and width of not less than 36 inches (914 mm). The area well shall allow the emergency escape

2

2

2

2

Page 61: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

and rescue opening to be fully opened.Exception: The ladder or steps required by Section R310.4.2.1 shall be permitted to encroach not more than 6 inches(152 mm) into the required dimensions of the area well.R310.4.2 Ladder and steps. Area wells with a vertical depth greater than 44 inches (1118 mm) shall be equippedwith a an approved permanently affixed ladder or steps. The ladder or steps shall not be obstructed by the emergencyescape and rescue opening when the window or door is in the open position. Ladders or steps required by this sectionshall not be required to comply with Section R311.7.R310.4.2.1 Ladders. Ladders or rungs shall have an inside width of at least 12 inches (305 mm), shall project at least3 inches (76 mm) from the wall and shall be spaced not more than 18 inches (457 mm) on center (o.c.) vertically for thefull height of the area well.R310.4.2.2 Steps. Steps shall have an inside width of at least 12 inches (305 mm), shall have minimum treads depthof 5 inches (127 mm) and a maximum riser height of 18 inches (457 mm) for the full height of the area well.R310.4.3 Drainage. Area wells shall be designed for proper drainage by connecting to the building’s foundationdrainage system required by Section R405.1.Exception: A drainage system for area wells is not required where the foundation is on well-drained soil or sand-gravel mixture soils in accordance with the United Soil Classification System, Group I Soils, as detailed in Table R405.1.R310.4.4 Bars, grilles, covers and screens. Where bars, grilles, covers, screens or similar devices are placedover emergency escape and rescue openings, bulkhead enclosures, or area wells that serve such openings, theminimum net clear opening size shall comply with Sections R310.2 through R310.2.2 and R310.4.1. Such devices shall bereleasable or removable from the inside without the use of a key or tool or force greater than that required for thenormal operation of the escape and rescue opening.R310.5 Emergency escape and rescue openings under decks and porches. Emergency escape and rescueopenings installed under decks and porches shall be fully operable and provide a path not less than 36 inches (914mm) in height to a yard or court. IFC[BE] EMERGENCY ESCAPE AND RESCUE OPENING. An operable exterior window, door or other similar device thatprovides for a means of escape and access for rescue in the event of an emergency.403.10.3.6 Resident participation in drills. Emergency evacuation drills shall involve the actual evacuation ofresidents to a selected assembly point and shall provide residents with experience in exiting through all required exits.All required exits shall be used during emergency evacuation drills.Exception: Actual exiting from emergency escape and rescue openings shall not be required. Opening the emergencyescape and rescue openings and signaling for help shall be an acceptable alternative.1031.7 Emergency escape and rescue openings. Required emergency escape and rescue openings shall bemaintained in accordance with the code in effect at the time of construction, and both of the following:1. Required emergency escape and rescue openings shall be operational from the inside of the room without the use ofkeys or tools.2. Bars, grilles, grates or similar devices are allowed to be placed over emergency escape and rescue openingsprovided the minimum net clear opening size complies with the code that was in effect at the time of construction andthe unit is equipped with smoke alarms installed in accordance with Section 907.2.11 of the International Building Code.Such devices shall be releasable or removable from the inside without the use of a key, tool or force greater than thatwhich is required for normal operation of the emergency escape and rescue opening.IEBC[BE] EMERGENCY ESCAPE AND RESCUE OPENING. An operable exterior window, door or other similar device thatprovides for a means of escape and access for rescue in the event of an emergency.IEBC (prescriptive method)505.4 Emergency escape and rescue openings. Emergency escape and rescue openings shall be operationalfrom the inside of the room without the use of keys or tools.Bars, grilles, grates or similar devices are allowed to be placed over emergency escape and rescue openings providedthe minimum net clear opening size complies with the code that was in effect at the time of construction and the unit isequipped with smoke alarms installed in accordance with Section 907.2.11 of the International Building Code. Suchdevices shall be releasable or removable from the inside without the use of a key, tool or force greater than that whichis required for normal operation of the emergency escape and rescue opening.IEBC (Alterations Level 1)

Page 62: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

701.4 Emergency escape and rescue openings. Emergency escape and rescue openings shall be operationalfrom the inside of the room without the use of keys or tools.Bars, grilles, grates or similar devices are allowed to be placed over emergency escape and rescue openings providedthe minimum net clear opening size complies with the code that was in effect at the time of construction and the unit isequipped with smoke alarms installed in accordance with Section 907.2.11 of the International Building Code. Suchdevices shall be releasable or removable from the inside without the use of a key, tool or force greater than that whichis required for normal operation of the emergency escape and rescue opening.IPMC[BE] EMERGENCY ESCAPE AND RESCUE OPENING. An operable exterior window, door or other similar device thatprovides for a means of escape and access for rescue in the event of an emergency.[F] 702.4 Emergency escape and rescue openings. Required emergency escape and rescue openings shall bemaintained in accordance with the code in effect at the time of construction, and both of the following:1. Required emergency escape and rescue openings shall be operational from the inside of the room without the use ofkeys or tools. 2. Bars, grilles, grates or similar devices are permitted to be placed over emergency escape and rescue openingsprovided the minimum net clear opening size complies with the code that was in effect at the time of construction andthe unit is equipped with smoke alarms installed in accordance with Section 907.2.11 of the International Building Code.Such devices shall be releasable or removable from the inside without the use of a key, tool or force greater than thatwhich is required for normal operation of the escape and rescue opening.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This coordination of an existing definition with no technical changes to the text.Internal ID: 3406

Page 63: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G13-18IBC: SECTION 303.1.5 (New), 304.2 (New), 304.3 (New), 304.4 (New), 305.3 (New), 306.2.1 (New), 308.2,308.3.1, 308.4, 309.3 (New), 310.1, 311.1.2 (New), 311.2.1 (New), 311.2.2 (New), 311.3, 311.3.1 (New), 312.2(New), 312.3 (New)Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

SECTION 303 ASSEMBLY GROUP A

303.1 Assembly Group A. Assembly Group A occupancy includes, among others, the use of a building or structure, ora portion thereof, for the gathering of persons for purposes such as civic, social or religious functions; recreation, foodor drink consumption or awaiting transportation.

Add new text as follows:

303.1.5 Special amusement buildings. Special amusement buildings shall comply with Section 411.

SECTION 304 BUSINESS GROUP B

Revise as follows:

304.1 Business Group B. Business Group B occupancy includes, among others, the use of a building or structure, ora portion thereof, for office, professional or service-type transactions, including storage of records and accounts.Business occupancies shall include, but not be limited to, the following:

Airport traffic control towersAmbulatory care facilities

Animal hospitals, kennels and poundsBanksBarber and beauty shopsCar washCivic administrationClinic, outpatient

Dry cleaning and laundries: pick-up and delivery stations and self-serviceEducational occupancies for students above the 12th grade, including higher education laboratries.Electronic data processingFood processing establishments and commercial kitchens not associated with restaurants, cafeterias

and similar dining facilities not more than 2,500 square feet (232 m ) in area.Laboratories: testing and researchMotor vehicle showroomsPost officesPrint shopsProfessional services (architects, attorneys, dentists, physicians, engineers, etc.)Radio and television stationsTelephone exchangesTraining and skill development not in a school or academic program (this shall include, but not be limited

to, tutoring centers, martial arts studios, gymnastics and similar uses regardless of the ages served, andwhere not classified as a Group A occupancy).

Add new text as follows:

304.2 Airport traf f ic control towers. Airport traffic control towers shall comply with Section 412.2.

2

Page 64: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

304.3 Ambulatory care facilities. Ambulatory care facilities shall comply with Section 422.

304.4 Higher education laboratries. Higher education laboratories shall comply with Section 428.

SECTION 305 EDUCATIONAL GROUP E

305.3 Storm shelters in Group E occupancies. Storm shelters shall be provided for Group E occupancies whererequired by Section 423.4.

SECTION 306 FACTORY GROUP F

Revise as follows:

306.2 Moderate-hazard factory industrial, Group F-1. Factory industrial uses that are not classified as FactoryIndustrial F-2 Low Hazard shall be classified as F-1 Moderate Hazard and shall include, but not be limited to, thefollowing:

Aircraft (manufacturing, not to include repair)AppliancesAthletic equipmentAutomobiles and other motor vehiclesBakeriesBeverages: over 16-percent alcohol contentBicyclesBoatsBrooms or brushesBusiness machinesCameras and photo equipmentCanvas or similar fabricCarpets and rugs (includes cleaning)ClothingConstruction and agricultural machineryDisinfectantsDry cleaning and dyeingElectric generation plantsElectronicsEngines (including rebuilding)Food processing establishments and commercial kitchens not associated with restaurants, cafeterias

and similar dining facilities more than 2,500 square feet (232 m ) in area.FurnitureHemp productsJute productsLaundriesLeather productsMachineryMetalsMillwork (sash and door)Motion pictures and television filming (without spectators)Musical instrumentsOptical goods

2

Page 65: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

Paper mills or productsPhotographic filmPlastic productsPrinting or publishingRecreational vehiclesRefuse incinerationShoesSoaps and detergentsTextilesTobaccoTrailersUpholsteringWood; distillationWoodworking (cabinet)

Add new text as follows:

306.2.1 Aircraf t manufacturing facilities. Aicraft manufacturing facilities shall comply with Section 412.6.

SECTION 308 INSTITUTIONAL GROUP I

Revise as follows:

308.2 Institutional Group I-1. Institutional Group I-1 occupancy shall include buildings, structures or portions thereoffor more than 16 persons, excluding staff, who reside on a 24-hour basis in a supervised environment and receivecustodial care. Buildings of Group I-1 shall be classified as one of the occupancy conditions specified in Section 308.2.1or 308.2.2 . and shall comply with Section 420. This group shall include, but not be limited to, the following:

Alcohol and drug centersAssisted living facilitiesCongregate care facilitiesGroup homes

Halfway housesResidential board and care facilitiesSocial rehabilitation facilities

308.3 Institutional Group I-2. Institutional Group I-2 occupancy shall include buildings and structures used formedical care on a 24-hour basis for more than five persons who are incapable of self-preservation. This group shallinclude, but not be limited to, the following:

Foster care facilities

Detoxification facilities

Hospitals

Nursing homes

Psychiatric hospitals

308.3.1 Occupancy conditions. Buildings of Group I-2 shall be classified as one of the occupancy conditionsspecified in Section 308.3.1.1 or 308.3.1.2 .and shall comply with Section 407.

308.4 Institutional Group I-3. Institutional Group I-3 occupancy shall include buildings and structures that areinhabited by more than five persons who are under restraint or security. A Group I-3 facility is occupied by persons whoare generally incapable of self-preservation due to security measures not under the occupants' control. This group shallinclude, but not be limited to, the following:

Page 66: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

Correctional centersDetention centersJailsPrerelease centersPrisonsReformatories

Buildings of Group I-3 shall be classified as one of the occupancy conditions specified in Sections 308.4.1 through308.4.5 (see Section 408.1).and shall comply with Section 408.

SECTION 309 MERCANTILE GROUP M

Add new text as follows:

309.1 Mercantile Group M. Mercantile Group M occupancy includes, among others, the use of a building or structureor a portion thereof for the display and sale of merchandise, and involves stocks of goods, wares or merchandiseincidental to such purposes and accessible to the public. Mercantile occupancies shall include, but not be limited to, thefollowing:

Department storesDrug storesMarketsGreenhouses for display and sale of plants that provide public access.Motor fuel-dispensing facilitiesRetail or wholesale storesSales rooms

309.3 Motor fuel-dispensing facilities. Motor fuel-dispensing facilities shall comply with Section 406.7.

SECTION 310 RESIDENTIAL GROUP R

Revise as follows:

310.1 Residential Group R. Residential Group R includes, among others, the use of a building or structure, or aportion thereof, for sleeping purposes when not classified as an Institutional Group I or when not regulated by theInternational Residential Code. Group R occupancies not constructed in accordance with the International ResidentialCode as permited by Sections 301.4.1 and 301.4.2 shall comply with Section 420.

SECTION 311 STORAGE GROUP S

Add new text as follows:

311.1.2 Combustible storage. High-piled stock or rack storage, or attic, under-floor and concealed spaces used forstorage of combustible materials, shall be in accordance with Section 413.

311.2 Moderate-hazard storage, Group S-1. Storage Group S-1 occupancies are buildings occupied for storageuses that are not classified as Group S-2, including, but not limited to, storage of the following:

Aerosol products, Levels 2 and 3Aircraft hangar (storage and repair)Bags: cloth, burlap and paperBamboos and rattanBasketsBelting: canvas and leatherBooks and paper in rolls or packsBoots and shoes

Page 67: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

Buttons, including cloth covered, pearl or boneCardboard and cardboard boxesClothing, woolen wearing apparelCordageDry boat storage (indoor)FurnitureFursGlues, mucilage, pastes and sizeGrainsHorns and combs, other than celluloidLeatherLinoleumLumberMotor vehicle repair garages complying with the maximum allowable quantities of hazardous materials

listed in Table 307.1(1) (see Section 406.8)Photo engravingsResilient flooringSelf-service storage facility (mini-storage)SilksSoapsSugarTires, bulk storage ofTobacco, cigars, cigarettes and snuffUpholstery and mattressesWax candles

311.2.1 Aircraf t hangars. Aircraft hangars used for storage or repair shall comply with Section 412.3.

311.2.2 Motor vehicle repair garages. Motor vehicle repair garages shall comply with Section 406.8.

311.3 Low-hazard storage, Group S-2. Storage Group S-2 occupancies include, among others, buildings used forthe storage of noncombustible materials such as products on wood pallets or in paper cartons with or without singlethickness divisions; or in paper wrappings. Such products are permitted to have a negligible amount of plastic trim,such as knobs, handles or film wrapping. Group S-2 storage uses shall include, but not be limited to, storage of thefollowing:

AsbestosBeverages up to and including 16-percent alcohol in metal, glass or ceramic containersCement in bagsChalk and crayonsDairy products in nonwaxed coated paper containersDry cell batteriesElectrical coilsElectrical motorsEmpty cansFood productsFoods in noncombustible containersFresh fruits and vegetables in nonplastic trays or containers

Page 68: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

Frozen foodsGlassGlass bottles, empty or filled with noncombustible liquidsGypsum boardInert pigmentsIvoryMeatsMetal cabinetsMetal desks with plastic tops and trimMetal partsMetalsMirrorsOil-filled and other types of distribution transformersParking Public parking garages, open or enclosedPorcelain and potteryStovesTalc and soapstonesWashers and dryers

311.3.1 Public parking garages. Public parking garages shall comply with Section 406.4 and the additinalrequirements of Section 406.5 for open parking garages or Section 406.6 for enclosed parking garages.

SECTION 312 UT ILITY AND MISCELLANEOUS GROUP U

312.2 Private garages and carports. Private garages and carports shall comply with Section 406.3.

312.3 Residential aircraf t hangars. Aircraft hangars accessory to a one- or two-family residence shall complywith Section 412.4.

Reason:During the 2015-2015 code development cycle, a series of proposals were submitted to relocate the bulk of thedetailed use and occupancy requirements in Chapter 4 to other sections of the code, primarily Chapter 3. The primaryjustification was concern that some code users may overlook key Chapter 4 criteria that apply to their buildings. Theproposals were all defeated, most of them overwhelmingly.The concern still remains, especially as Chapter 4 remains a dumping ground for use- or occupancy-related provisionsthat don’t have a clear home elsewhere in the code. The BCAC elected to revisit the issue, but rather than taking achainsaw to the provisions and clearing out huge clumps opted for a more surgical approach. Primarily, the BCACproposes to add a series of pointers from the appropriate occupancy groups in Chapter 3 to the relevant provisions inChapter 4. Pointers to uses in Chapter 4 which can occur in a variety of different occupancy groups are added inSection 302. These changes will highlight for architects, engineers and building officials when detailed provisions inChapter 4 apply to a building, or portion thereof, which they are designing or reviewing.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. Cost ImpactThe code change proposal will not increase or decrease the cost of construction .The code change proposal will not increase or decrease the cost of construction. This is an editorial reorganization toplace requirements in a more appropriate location.

Page 69: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

Internal ID: 180

Page 70: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G14-18IBC: 303.1, 303.1.3Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

SECTION 303 ASSEMBLY GROUP A

Revise as follows:

303.1 Assembly Group A. Assembly Group A occupancy includes, among others, the use of a building or structure, ora portion thereof, for the gathering of persons for purposes such as civic, social or religious functions; recreation, foodor drink consumption or awaiting transportation.

303.1.3 Associated with Group E occupancies. A room or space used for assembly purposes that is associatedwith a Group E occupancy, with an occupant load of 300 or less, is not considered a separate occupancy.

Reason:To be consistent, the exceptions for assembly spaces in Section 303.1.1 through 303.1.4 (below) seem to indicate thatthe exceptions are intended for small spaces. However, the language in 303.1.3 has been widely interpreted. Somepeople feel this should be limited to spaces just typically open to students - such as libraries, music rooms, bandrooms, and cafeterias. Others have interpreted this to include large gymnasiums and auditoriums with significantseating. While a school basketball game may be a school function, there would be students from another school, aswell as significant number of the public, including a high percentage of families. The same concern for large number ofthe public also hold true in an auditorium.303.1.1 Small buildings and tenant spaces. A building or tenant space used for assembly purposes with anoccupantload of less than 50 persons shall be classified as a Group B occupancy.303.1.2 Small assembly spaces. The following rooms and spaces shall not be classified as Assembly occupancies:1. A room or space used for assembly purposes with an occupant load of less than 50 persons and accessory toanother occupancy shall be classified as a Group B occupancy or as part of that occupancy.2. A room or space used for assembly purposes that is less than 750 square feet (70 m2) in area and accessory toanother occupancy shall be classified as a Group B occupancy or as part of that occupancy.303.1.3 Associated with Group E occupancies. A room or space used for assembly purposes that is associated with aGroup E occupancy is not considered a separate occupancy.303.1.4 Accessory to places of religious worship.Accessory religious educational rooms and religious auditoriums withoccupant loads of less than 100 per room orspace are not considered separate occupancies.This also may be considered a conflict with Section 302.1 which states “A room or space that is intended to beoccupied at different times for different purposes shall comply with all of the requirements that are applicable to eachof the purposes for which the room or space will be occupied.”This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. Cost ImpactThe code change proposal will increase the cost of construction .This code change proposal will increase the cost of construction. Sprinkler system installation in new construction for aGroup A can vary from $1.00 to $3.00 per square foot. This proposal will require larger gymnasiums and auditoriumsassociated with a Group E occupancy to be protected with a fire suppression system in areas where the previousinterpretation was to allow these larger spaces to be considered part of the Group E occupancy.Internal ID: 183

Page 71: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G17-18IBC: 306.2Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected]); Robert Davidson,Davidson Code Concepts, LLC, representing Tesla, USA ([email protected])

2018 International Building Code

Revise as follows:

306.2 Moderate-hazard factory industrial, Group F-1. Factory industrial uses that are not classified as FactoryIndustrial F-2 Low Hazard shall be classified as F-1 Moderate Hazard and shall include, but not be limited to, thefollowing:

Aircraft (manufacturing, not to include repair)AppliancesAthletic equipmentAutomobiles and other motor vehiclesBakeriesBeverages: over 16-percent alcohol contentBicyclesBoatsBrooms or brushesBusiness machinesCameras and photo equipmentCanvas or similar fabricCarpets and rugs (includes cleaning)ClothingConstruction and agricultural machineryDisinfectantsDry cleaning and dyeingElectric generation plantsElectronicsEnergy storage systems (ESS) in dedicated use buildingsEngines (including rebuilding)Food processing establishments and commercial kitchens not associated with restaurants, cafeterias

and similar dining facilities more than 2,500 square feet (232 m ) in area.FurnitureHemp productsJute productsLaundriesLeather productsMachineryMetalsMillwork (sash and door)Motion pictures and television filming (without spectators)Musical instrumentsOptical goods

2

Page 72: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

Paper mills or productsPhotographic filmPlastic productsPrinting or publishingRecreational vehiclesRefuse incinerationShoesSoaps and detergentsTextilesTobaccoTrailersUpholsteringWood; distillationWoodworking (cabinet)

Reason:This proposal is a correlation issue with the FCAC IFC Section 1206 ESS rewrite. The FCAC looked at the hazardsassociated with dedicated use utility type ESS installations covered under the following section and decided thatGroup F-1 was an appropriate classification. For the most part they will serve the grid scale areas of ESS deploymentand large facilities.(IFC) 1206.7.2 Dedicated use buildings. For the purpose of Table 1206.7 dedicated use ESS buildings shall beclassified as Group F-1 occupancies and comply with all the following.The building shall only be used for ESS, electrical energy generation, and other electrical grid related operations.Occupants in the rooms and areas containing ESS are limited to personnel that operate, maintain, service, test andrepair the ESS and other energy systems.No other occupancy types shall be permitted in the building.Administrative and support personnel shall be permitted in areas within the buildings that do not contain ESS, provided:The areas do not occupy more than 10 percent of the building area of the story in which they are located.A means of egress is provided from the incidental use areas to the public way that does not require occupants totraverse through areas containing ESS or other energy system equipment.(Also the administrative support areas are separated from the ESS by a 2 hour fire separation.)When looking at the group classifications and expected fuel loads the F-1 fits the ESS Dedicated Use Building from thatstandpoint, especially since Electric Generation Plants are already an F-1 Group. ESS are part of the overall electricgeneration and storage. If ESS is installed in a building occupied by another group it will remain that Group and berequired to have the increased fire protection features for the space the ESS occupies. That does not change from howthe current code addresses ESS.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. Cost ImpactThe code change proposal will decrease the cost of construction .This proposal provides correlation with an IFC proposal. The IFC proposal will actually decrease the cost ofconstruction because it will allow larger ESS installations in dedicated use indoor locations to be in Group F-1occupancies, rather than in H-2 occupancies. Internal ID: 250

Page 73: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G26-18IBC: [F] 402.7.2Proponent: Ed Kullik, representing ICC Building Code Action Committee ([email protected])

THIS CODE CHANGE WILL BE HEARD BY THE FIRE CODE COMMITTEE. SEE THE TENTATIVE HEARING ORDER FOR THISCOMMITTEE

2018 International Building Code

SECTION 402 COVERED MALL AND OPEN MALL BUILDINGS

Revise as follows:

[F] 402.7 Emergency systems. Covered and open mall buildings, anchor buildings and associated parking garagesshall be provided with emergency systems complying with Sections 402.7.1 through 402.7.5.

[F] 402.7.2 Smoke control. Where a covered mall building contains an atrium, Atriums connecting three or morestories in covered mall buildings shall be provided with a smoke control system shall be provided in accordance withSection 909.404.5

Exception: A smoke control system is not required in covered mall buildings where an atrium connects only twostories.

Reason:This proposal simply makes a more direct reference to the need for a smoke control system instead of sending thereader to Section 404.5 and through the exception. The technical requirements do not change. Smoke control is onlyrequired where an atrium connects 3 or more stories whether associated with a covered mall or other type of building.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This proposal simply makes the provisions more direct as to when smoke control would be required in a covered mallbuilding. Internal ID: 185

Page 74: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G27-18Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Delete without substitution:

403.2.2 Seismic considerations. For seismic considerations, see Chapter 16.

Reason:This proposal deletes the existing pointer to Chapter 16 for seismic considerations .The existing pointer was usefulwhen Chapter 16 substantially copied seismic design requirements from ASCE 7, including direction on which seismicdesign methods were applicable to high-rise buildings and limitations on lateral force-resisting systems for buildings ofcertain heights in certain seismic design categories. All of that information with the exception of the basic informationneeded for a building official to verify the seismic ground motions and seismic design category has been removed fromChapter 16 and replaced with references to ASCE 7. Thus, the pointer is no longer needed. This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This is an editorial clarification and will therefore not increase or decrease the cost of construction.Internal ID: 171

Page 75: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G29-18IBC: 403.5.6Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

THIS CODE CHANGE WILL BE HEARD BY THE MEANS OF EGRESS COMMITTEE. SEE THE TENTATIVE HEARING ORDER FORTHIS COMMITTEE.

2018 International Building Code

Delete without substitution:

403.5.6 Emergency escape and rescue. Emergency escape and rescue openings specified in Section 1030 arenot required.

Reason:EERO not required for high-rises in Section 1030.1, so the exception not needed in the high-rise provisions in Section403.This is one of a series of 11 proposals to coordinate the Emergency Escape and Rescue Openings (EERO) technicalcriteria in the I-codes. Please see the proposal for the definition of Emergency Escape and Rescue Openings foradditional information.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .There is no requirement or change in technical criteria for construction.Internal ID: 457

Page 76: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G31-18IBC: 404.1, 404.9, 404.9.1, 404.9.2, 404.9.3, 404.10, 712.1.7, TABLE 1017.2, 1017.3.2 (New), 1017.3.2.1(New), 1017.3.2.2 (New), 1017.3.2.3 (New), 1028.1, (IFC[BE] TABLE 1017.2, 1017.3.2 (New), 1017.3.2.1 (New),1017.3.2.2 (New), 1017.3.2.3 (New), 1028.1)Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

THIS CODE CHANGE WILL BE HEARD BY THE MEANS OF EGRESS COMMITTEE. SEE THE TENTATIVE HEARING ORDER FORTHIS COMMITTEE.

2018 International Building Code

Revise as follows:

404.1 General. In other than Group H occupancies, and where permitted by Section 712.1.7, the The provisions ofSections 404.1 through 404.10 shall apply to buildings containing atriums. Atriums are not permitted in buildings orstructures containing vertical openings defined as “Atriums.”classified as Group H.

404.9 Exit access travel distance. Exit access travel distance for areas open to an atrium shall comply with therequirements of this section.Section 1017.

Delete without substitution:

404.9.1 Egress not through the atrium. Where required access to the exits is not through the atrium, exit accesstravel distance shall comply with Section 1017.

404.9.2 Exit access travel distance at the level of exit discharge. Where the path of egress travel is throughan atrium space, exit access travel distance at the level of exit discharge shall be determined in accordance withSection 1017.

404.9.3 Exit access travel distance at other than the level of exit discharge. Where the path of egresstravel is not at the level of exit discharge from the atrium, that portion of the total permitted exit access travel distancethat occurs within the atrium shall be not greater than 200 feet (60 960 mm).

Revise as follows:

404.10 Interior exit stairways. Not greater than 50 percent Discharge of interior exit stairways are permitted toegress through an atrium on the level of exit discharge shall be in accordance with Section 1028.

712.1.7 Atriums. In other than Group H occupancies, atriums complying with Section 404 shall be permitted.Atriums inbuildings shall comply with Section 404.

Page 77: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

TABLE 1017.2EXIT ACCESS TRAVEL DISTANCE

For SI: 1 foot = 304.8 mm.a. See the following sections for modifications to exit access travel distance requirements:

Section 402.8: For the distance limitation in malls.Section 404.9:For the distance limitation through an atrium space.Section 407.4: For the distance limitation in Group I-2.Sections 408.6.1 and 408.8.1: For the distance limitations in Group I-3.Section 411.3: For the distance limitation in special amusement buildings.Section 412.6: For the distance limitations in aircraft manufacturing facilities.Section 1006.2.2.2: For the distance limitation in refrigeration machinery rooms.Section 1006.2.2.3: For the distance limitation in refrigerated rooms and spaces.Section 1006.3.3: For buildings with one exit.Section 1017.2.2: For increased distance limitation in Groups F-1 and S-1.Section 1029.7: For increased limitation in assembly seating.Section 3103.4: For temporary structures.Section 3104.9: For pedestrian walkways.

b. Buildings equipped throughout with an automatic sprinkler system in accordance with Section903.3.1.1 or 903.3.1.2. See Section 903 for occupancies where automatic sprinkler systems arepermitted in accordance with Section 903.3.1.2.

c. Buildings equipped throughout with an automatic sprinkler system in accordance with Section903.3.1.1.

d. Group H occupancies equipped throughout with an automatic sprinkler system in accordance withSection 903.2.5.1.

e. Group R-3 and R-4 buildings equipped throughout with an automatic sprinkler system in accordancewith Section 903.3.1.3. See Section 903.2.8 for occupancies where automatic sprinkler systems arepermitted in accordance with Section 903.3.1.3.

a

OCCUPANCY WITHOUT SPRINKLERSYSTEM (f eet ) WITH SPRINKLER SYSTEM(f eet )

A, E, F-1, M, R, S-1 200e 250b

I-1 Not Permitted 250b

B 200 300c

F-2, S-2, U 300 400c

H-1 Not Permitted 75d

H-2 Not Permitted 100d

H-3 Not Permitted 150d

H-4 Not Permitted 175d

H-5 Not Permitted 200c

I-2, I-3 Not Permitted 200c

I-4 150 200c

Page 78: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

1017.3 Measurement. Exit access travel distance shall be measured from the most remote point of each room, areaor space along the natural and unobstructed path of horizontal and vertical egress travel to the entrance to an exit.

Exception: In open parking garages, exit access travel distance is permitted to be measured to the closest riser ofan exit access stairway or the closest slope of an exit access ramp.

1017.3.1 Exit access stairways and ramps. Travel distance on exit access stairways or ramps shall be included inthe exit access travel distance measurement. The measurement along stairways shall be made on a plane parallel andtangent to the stair tread nosings in the center of the stair and landings. The measurement along ramps shall be madeon the walking surface in the center of the ramp and landings.

Add new text as follows:

1017.3.2 Atriums. Exit acess travel distance for areas open to an atrium shall comply with the requirements of thissection.

1017.3.2.1 Egress not through the atrium. Where required access to the exits is not through the atrium, exitaccess travel distance shall comply with Section 1017.2.

1017.3.2.2 Exit access travel distance at the level of exit discharge. Where the path of egress travel isthrough an atrium space, exit access travel distance at the level of exit discharge shall be determined in accordancewith Section 1017.2.

1017.3.2.3 Exit access travel distance at other than the level exit discharge. Where the path of egresstravel is not at the level of exit discharge from the atrium, that portion of the total permitted exit access traveldistance that occurs within the atrium shall be not greater than 200 feet (60 960 mm).

Revise as follows:

1028.1 General. Exits shall discharge directly to the exterior of the building. The exit discharge shall be at grade orshall provide a direct path of egress travel to grade. The exit discharge shall not reenter a building. The combined useof Exceptions 1 and 2 shall not exceed 50 percent of the number and minimum width or required capacity of therequired exits.

Exceptions:

1. Not more than 50 percent of the number and minimum width or required capacity of interior exitstairways and ramps is permitted to egress through areas, including atriums, on the level ofdischarge provided that all of the following conditions are met:1.1. Discharge of interior exit stairways and ramps shall be provided with a free and

unobstructed path of travel to an exterior exit door and such exit is readily visible andidentifiable from the point of termination of the enclosure.

1.2. The entire area of the level of exit discharge is separated from areas below byconstruction conforming to the fire-resistance rating for the enclosure.

1.3. The egress path from the interior exit stairway and ramp on the level of exit discharge isprotected throughout by an approved automatic sprinkler system. Portions of the level ofexit discharge with access to the egress path shall be either equipped throughout withan automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2,or separated from the egress path in accordance with the requirements for theenclosure of interior exit stairways or ramps.

1.4. Where a required interior exit stairway or ramp and an exit access stairway or ramp servethe same floor level and terminate at the same level of exit discharge, the termination ofthe exit access stairway or ramp and the exit discharge door of the interior exit stairway orramp shall be separated by a distance of not less than 30 feet (9144 mm) or not lessthan one-fourth the length of the maximum overall diagonal dimension of the building,whichever is less. The distance shall be measured in a straight line between the exitdischarge door from the interior exit stairway or ramp and the last tread of the exit accessstairway or termination of slope of the exit access ramp.

2. Not more than 50 percent of the number and minimum width or required capacity of the interiorexit stairways and ramps is permitted to egress through a vestibule provided that all of thefollowing conditions are met:

Page 79: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

2.1. The entire area of the vestibule is separated from areas below by constructionconforming to the fire-resistance rating of the interior exit stairway or ramp enclosure.

2.2. The depth from the exterior of the building is not greater than 10 feet (3048 mm) and thelength is not greater than 30 feet (9144 mm).

2.3. The area is separated from the remainder of the level of exit discharge by a fire partitionconstructed in accordance with Section 708.

Exception: The maximum transmitted temperature rise is not required.2.4. The area is used only for means of egress and exits directly to the outside.

3. Horizontal exits complying with Section 1026 shall not be required to discharge directly to theexterior of the building.

Reason:The purpose of this proposal is to relocate portions of the Section 404 atrium requirements to other appropriateportions of the IBC. As defined in Chapter 2, an atrium is a particular type of a vertical opening in a building or structure,but not the only method permitted by Chapter 7 for dealing with a vertical opening.A proposal last cycle (G51-15)attempted to relocate the entire Section 404 provisions into Section 712. While the proposal was disapproved by avote of 8-6, there was support expressed for considering a relocation of these provisions if clarifications to theexisting text were provided and at least a minimum set of provisions be retained in Chapter 4 as a starting point foraddressing requirements specific to certain building features. This proposal retains Section 404 but makes sometargeted relocations. In all cases, pointers are left in Section 404 so the link is not totally lost and code users still haveSection 404 as a guide to all of the considerations for atriums.Requirements relative to exit access travel distance andinterior exit stair discharge are also moved to Section 1017 and Section 1028 respectively. While these provisionsperhaps appear specific to atriums, they are not entirely self-contained and clearly need to be evaluated as part ofthe general travel distance and exit discharge requirements for the building. For exit access travel distance, theatrium-specific provisions are added under the exiting Section 1017.3 on measurement of exit access travel distance.For exit discharge, a reference to atriums is added under Exception #1 of Section 1028.1. Finally, the charging languageis clarified. A circular reference between Section 404 and Section 712.1 is removed. The existing language, especially inSection 404, also makes it vague as to whether an atrium is allowed in a Group H building or structure, versus anothermethod of treating a vertical opening. The implication (especially in Section 712.1) is that such an atrium is notpermitted. The charging language in both sections is revised accordingly. In addition, an exception is added permittinga vertical opening meeting the definition of an atrium to be constructed in accordance with any of the other methodsfor treating a vertical opening (e.g. a shaft enclosure per Section 712.1.1 or a generic two-story opening per Section712.1.9).This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. Cost ImpactThe code change proposal will not increase or decrease the cost of construction .The code change proposal will not increase or decrease the cost of construction. This is an editorial reorganization toplace requirements in a more appropriate location.Internal ID: 174

Page 80: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G59-18IBC: 423.1, 423.2, 423.3 (New), 423.3.1 (New), 423.3.2 (New)Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

SECTION 423 STORM SHELTERS

Revise as follows:

423.1 General. This section applies to the construction of storm shelters constructed as separate detached buildingsor constructed as rooms or spaces within buildings for the purpose of providing protection from storms that producehigh winds, such as tornadoes and hurricanes during the storm. Such structures shall be designated to be hurricaneshelters, tornado shelters, or combined hurricane and tornado This section specifies where storm shelters are requiredand provides requirements for the design and construction of storm shelters. Design of facilities for use as emergencyshelters after the storm are outside the scope of ICC 500 and shall comply with Table 1604.5 as a Risk Category IVStructure.

423.2 Construction. In addition to other applicable requirements in this code, storm Storm shelters shall beconstructed in accordance with ICC 500. this code and ICC 500, and shall be designated as hurricane shelters, tornadoshelters, or combined hurricane and tornado shelters. Buildings or structures that are also designated as emergencyshelters shall also comply with Table 1604.5 as Risk Category IV structures.Any storm shelter not required by this section shall be permitted to be constructed provided such structures meet therequirements of this code and ICC 500.

Add new text as follows:

423.3 Occupancy classif ication. The occupancy classification for a storm shelter shall be determined inaccordance with this section.

423.3.1 Dedicated storm shelters. A facility designed to be occupied solely as a storm shelter shall be classifiedas Group A-3 for the determination of requirements other than those covered in ICC 500.

Exceptions:

1. The occupancy category for dedicated storm shelters with an occupant load of less than 50persons as determined in accordance with ICC 500 shall be in accordance with Section 303.

2. The occupancy category for a dedicated residential storm shelter shall be the Group Roccupancy served.

423.3.2 Storm shelters within host buildings. Where designated storm shelters are constructed as a room orspace within a host building which will normally be occupied for other purposes, the requirements of this code for theoccupancy of the building, or the individual rooms or spaces thereof, shall apply unless otherwise required by ICC 500.

Reason:ICC 500 contains specific requirements for determining the occupancy classification of storm shelters, whetherconstructed as a standalone building or as a room or space inside a host building which will normally be occupied forother purposes (e.g. a multi-purpose room in a Group E school or a conference room in a Group B office building). Thiscode change adapts the occupancy language from ICC 500 and adds it to Section 423 where it will be directlyaccessible to all code users.Occupancy classifications for storm shelters are broken down into four categories:1. Dedicated storm shelters: Large community storm shelters may house hundreds of occupants. Thus, the ICC 500committee deemed it appropriate to classify these shelters as Assembly Group A-3.2. Small dedicated storm shelters: Some community shelters may only serve a small number of occupants. The ICC 500committee deemed it appropriate to permit these smaller shelters to be classified as Group B as allowed by IBCSection 303.1.13. Shelters in a host building: Storm shelters constructed within a larger building as a room or space which will be usedfor other purposes under normal conditions (e.g. a multi-purpose room in a Group E school or a conference room in aGroup B office building) are permitted to be classified using the occupancy category applicable to the space as it is

Page 81: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

normally used.4. Residential storm shelters. Currently under ICC 500 these would be classified as Group B since they are limited to amaximum of 16 occupants, thus could use the Section 303.1.1 allowance. It is more appropriate that they be classifiedas Group R since that is the occupancy to which they are an accessory structure.In addition, Sections 423.1 (General) and 423.2 (Construction) are revised to provide better scoping and charginglanguage for storm shelters. The General paragraph is amended to highlight that Section 423 contains languagerequiring the installation of storm shelters in critical facilities such as fire stations, ambulance stations, and emergencyoperations centers (existing Section 423.3) and in Group E occupancies (existing Section 423.4). The requirement toclassify storm shelters as hurricane, tornado, or both is relocated to the Construction provision, and a new paragraphis added to clarify that a storm shelter may be constructed in, or accessory to, any other buildings or structuresgoverned by the IBC, where they would not otherwise be required, as long as the shelter complies with the appropriaterequirements of the IBC and ICC 500. This is similar to language that exists in Section 901.2 for fire protection systems.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This proposal clarifies the occupancy classifications of storm shelters by adding the requirements from ICC 500 toSection 423. Internal ID: 2261

Page 82: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G66-18IBC: 402.6.3, 424.1, 424.2, 424.3, 424.4, 424.5, 424.5.1 (New), [F] TABLE 903.2.11.6 IFC TABLE 903.2.11.6Proponent: Ed Kullik, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Revise as follows:

402.6.3 Children's play Play structures. Children's play Play structures located within the mall of a covered mallbuilding or within the perimeter line of an open mall building shall comply with Section 424. The horizontal separationbetween children's play structures, kiosks and similar structures within the mall shall be not less than 20 feet (6096mm).

SECTION 424 CHILDREN'S PLAY STRUCTURES

424.1 General. Children's play Play structures installed inside all occupancies covered by this code that exceed 10feet (3048 mm) in height or 150 square feet (14 m ) in area shall comply with Sections 424.2 through 424.5.

424.2 Materials. Children's play Play structures shall be constructed of noncombustible materials or of combustiblematerials that comply with the following:

1. Fire-retardant-treated wood complying with Section 2303.2.2. Light-transmitting plastics complying with Section 2606.3. Foam plastics (including the pipe foam used in soft-contained play equipment structures) having a

maximum heat-release rate not greater than 100 kilowatts when tested in accordance with UL 1975or when tested in accordance with NFPA 289, using the 20 kW ignition source.

4. Aluminum composite material (ACM) meeting the requirements of Class A interior finish inaccordance with Chapter 8 when tested as an assembly in the maximum thickness intended for use.

5. Textiles and films complying with the fire propagation performance criteria contained in TestMethod 1 or Test Method 2, as appropriate, of NFPA 701.

6. Plastic materials used to construct rigid components of soft-contained play equipment structures(such as tubes, windows, panels, junction boxes, pipes, slides and decks) exhibiting a peak rate ofheat release not exceeding 400 kW/ m when tested in accordance with ASTM E1354 at an incidentheat flux of 50 kW/m in the horizontal orientation at a thickness of 6 mm.

7. Ball pool balls, used in soft-contained play equipment structures, having a maximum heat-releaserate not greater than 100 kilowatts when tested in accordance with UL 1975 or when tested inaccordance with NFPA 289, using the 20 kW ignition source. The minimum specimen test size shallbe 36 inches by 36 inches (914 mm by 914 mm) by an average of 21 inches (533 mm) deep, and theballs shall be held in a box constructed of galvanized steel poultry netting wire mesh.

8. Foam plastics shall be covered by a fabric, coating or film meeting the fire propagationperformance criteria contained in Test Method 1 or Test Method 2, as appropriate, of NFPA 701.

9. The floor covering placed under the children's play structure shall exhibit a Class I interior floorfinish classification, as described in Section 804, when tested in accordance with ASTM E648 orNFPA 253.

10. Interior finishes for structures exceeding 300 square feet (28 m ) in area or 10 feet (3048 mm) inheight shall have a flame spread index not greater than that specified in Table 803.13 for theoccupancy group and location designated. Interior wall and ceiling finish materials tested inaccordance with NFPA 286 and meeting the acceptance criteria of Section 803.1.1.1, shall bepermitted to be used where a Class A classification in accordance with ASTM E84 or UL 723 isrequired.

[F] 424.3 Fire protection. Children's play Play structures shall be provided with the same level of approved firesuppression and detection devices required for other structures in the same occupancy.

424.4 Separation. Children's play Play structures shall have a horizontal separation from building walls, partitionsand from elements of the means of egress of not less than 5 feet (1524 mm). Children's Playground structures shall havea horizontal separation from other children's play structures of not less than 20 feet (6090 mm).

2

22

2

2

Page 83: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

424.5 Area limits. Children's play Play structures shall be not greater than 300 square feet (28 m ) in area, unless aspecial investigation, acceptable to the building official, has demonstrated adequate fire safety.

Add new text as follows:

424.5.1 Design. Play structures exceeding 300 square feet (28 m ) in area or 10 feet (3048 mm) in height shall bedesigned in accordance with Section 1601.1.

2

2

Page 84: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

Revise as follows:

[F] TABLE 903.2.11.6ADDIT IONAL REQUIRED SUPPRESSION SYSTEMS

Reason:Indoor play structures can cover a wide range of activities and are not limited to children’s play structures. Someexamples of these are; indoor skydiving, permanent haunted houses, very large and tall rock climbing walls ingymnasiums of schools and universities, laser tag facilities with elevated and large structures having massiveconcealed spaces, Indoor archery ranges with foam 3d targets and any number of other indoor activities withrecreational structures located within a building. A growing number of “I” Occupancy structures are now adding adultplaygrounds. A climbing or skydiving facility may be well over 1000 sf in area/footprint and I have recently reviewedone over 42’ in height. The structure in many cases needs to be designed per IBC Chapter 16 and ASCE 7, in a seismiczone it may be considered a “nonbuilding structure or attachment” with special design considerations needed. Thereare often unique structural stability and anchorage requirements, plus many potential fire safety issues dealing withconcealed spaces and flame spread requirements. I think this change will not clutter the section nor create confusionas 424.1 already calls out “Children’s Play Structures installed inside all occupancies. I have not altered the term“Children’s” in section 424.4 as I believe that is a very unique requirement applicable to children’s playgroundequipment and would not apply to other larger play structures where they meet the design and FLS requirements forfinishes and fire protection by submitting a special Investigation to the building Official as noted in section 424.5.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. Cost ImpactThe code change proposal will increase the cost of construction .This proposal is primarily a revision that clarifies that play structures are not necessarily just used by children. Therequirements apply regardless of this designation. I one were to interpret the code as meaning that this is anexpansion of requirements, then this could be taken to be that the cost of construction is increased. Since therequirements for larger play structures is expanded somewhat, the cost of construction may increase.

SECTION SUBJECT402.5, 402.6.2 Covered and open mall buildings403.3 High-rise buildings404.3 Atriums405.3 Underground structures407.6 Group I-2410.7 Stages411.4 Special amusement buildings412.3.6 Airport traffic control towers412.4.6, 412.4.6.1, 412.6.5 Aircraft hangars415.11.11 Group H-5 HPM exhaust ducts416.5 Flammable finishes417.4 Drying rooms419.5 Live/work units

424.3 Children’s Play structures427 Buildings containing laboratory suites507 Unlimited area buildings509.4 Incidental uses1029.6.2.3 Smoke-protected assembly seatingIFC Sprinkler system requirements as set forth in Section 903.2.11.6 of

the International Fire Code

Page 85: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

Internal ID: 1457

Page 86: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G81-18IBC: TABLE 504.4, TABLE 506.2Proponent: Ed Kullik, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Revise as follows:

TABLE 504.4ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANEaPLANEa, b

Page 87: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

UL = Unlimited; NP = Not Permitted; NS = Buildings not equipped throughout with an automatic sprinkler system; S =Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R= Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2;S13D = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section903.3.1.3.

a. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter.b. See Section 903.2 for the minimum thresholds for protection by an automatic sprinkler system for

specific occupancies.c. New Group H occupancies are required to be protected by an automatic sprinkler system in

accordance with Section 903.2.5.d. The NS value is only for use in evaluation of existing building height in accordance with the

International Existing Building Code.e. New Group I-1 and I-3 occupancies are required to be protected by an automatic sprinkler system

in accordance with Section 903.2.6. For new Group I-1 occupancies, Condition 1, see Exception 1 ofSection 903.2.6.

f. New and existing Group I-2 occupancies are required to be protected by an automatic sprinklersystem in accordance with Section 903.2.6 and 1103.5 of the International Fire Code.

g. For new Group I-4 occupancies, see Exceptions 2 and 3 of Section 903.2.6.h. New Group R occupancies are required to be protected by an automatic sprinkler system in

accordance with Section 903.2.8.

Page 88: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

TABLE 506.2ALLOWABLE AREA FACTOR (At = NS, S1, S13R, S13D or SM, as applicable) IN SQUARE FEETaFEET a, b

Page 89: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

For SI: 1 square foot = 0.0929 m .UL = Unlimited; NP = Not Permitted; NS = Buildings not equipped throughout with an automatic sprinkler system; S1 =Buildings a maximum of one story above grade plane equipped throughout with an automatic sprinkler system installedin accordance with Section 903.3.1.1; SM = Buildings two or more stories above grade plane equipped sprinkler systeminstalled in accordance with Section 903.3.1.2; S13D = Buildings equipped throughout with an automatic sprinklersystem installed in accordance with Section 903.3.1.3.

a. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter.b. See Section 903.2 for the minimum thresholds for protection by an automatic sprinkler system for

specific occupancies.c. New Group H occupancies are required to be protected by an automatic sprinkler system in

accordance with Section 903.2.5.d. The NS value is only for use in evaluation of existing building area in accordance with the

International Existing Building Code.e. New Group I-1 and I-3 occupancies are required to be protected by an automatic sprinkler system

in accordance with Section 903.2.6. For new Group I-1 occupancies, Condition 1, see Exception 1 ofSection 903.2.6.

f. New and existing Group I-2 occupancies are required to be protected by an automatic sprinklersystem in accordance with Section 903.2.6 and Section 1103.5 of the International Fire Code.

g. New Group I-4 occupancies see Exceptions 2 and 3 of Section 903.2.6.h. New Group R occupancies are required to be protected by an automatic sprinkler system in

accordance with Section 903.2.8.i. The maximum allowable area for a single-story nonsprinklered Group U greenhouse is permitted to

be 9,000 square feet, or the allowable area shall be permitted to comply with Table C102.1 ofAppendix C.

2

Page 90: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

Reason:Tables 504.4 and 506.2 were introduced into the code by code change G101-12, submitted by the ICC Building CodeAction Committee (BCAC), as part of a substantial overhaul of the height and area provisions. The new tables replacedTable 503. It was not the intent of G101-12 to make any changes to allowable building height or area rendered bythese provisions, compared to what was previously allowed. This proposed change corrects two tabular value errorsthat went undetected in the original code change until after the completion of the 2012 cycle: the tabular story heightnumbers for Type IV Group S-2, and the allowable area factor for Type II-A Group I-3. The following is taken from the2012 edition of the IBC which shows the height and areas for S-2 and I-3 as shown in Table 503, from which Tables 504.4and 506.2 were derived.TABLE 503ALLOWABLE BUILDING HEIGHTS AND AREAS Building height limitations shown in feet abovegrade plane. Story limitations shown as stories above grade plane.Building area limitations shown insquare feet, as determined by the def inition of “Area, building,” per stor

(Only portions of table are shown)This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. Cost ImpactThe code change proposal will decrease the cost of construction .This is a correction to the height and area tables based upon an error in previous code change submittals. Theproposal will restore these values to the correct values. Will actually decrease the cost of construction compared tothe current code because more lenient limitations are imposed.Internal ID: 1548

a, b

Page 91: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G88-18IBC: TABLE 508.4Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Revise as follows:

TABLE 508.4REQUIRED SEPARATION OF OCCUPANCIES (HOURS)

S = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1.NS = Buildings not equipped throughout with an automatic sprinkler system installed in accordance with Section903.3.1.1.N = No separation requirement.NP = Not Permitted.

a See Section 420.b. The required separation from areas used only for private or pleasure vehicles shall be reduced by 1

hour but not to less than 1 hour.c. See Section 406.3.2.d. Separation is not required between occupancies of the same classification.e. See Section 422.2 for ambulatory care facilities.f. Occupancy separations that serve to define fire area limits established in Chapter 9 for requiring

fire protection systems shall also comply with Section 707.3.10 and Table 707.3.10 in accordancewith Section 901.7.

Reason:Filling in the balance of Table 508.4 will avoid confusion and make the table more clear and functional.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This proposal is an editorial change and adds no new requirements to the code.Internal ID: 3018

f

OCCUPANCY A, E I-1 , I-3,I-4

a I-2 Ra F-2, S-2 ,U

b B , F-1,M,S-1

e H-1 H-2 H-3, H-4 H-5

S NS S NS S NS S NS S NS S NS S NS S NS S NS S NSA, E N N 1 2 2 NP 1 2 N 1 1 2 NP NP 3 4 2 3 2 NPI-1 , I-3, I-4a 1 2 N N 2 NP 1 NP 1 2 1 2 NP NP 3 NP 2 NP 2 NPI-2 2 NP 2 NP N N 2 NP 2 NP 2 NP NP NP 3 NP 2 NP 2 NPRa 1 2 N N 2 NP N N 1c 2c 1 2 NP NP 3 NP 2 NP 2 NPF-2, S-2 , Ub N 1 1 2 N N 1c 2c N N 1 2 NP NP 3 4 2 3 2 NPB , F-1, M, S-1e 1 2 1 2 2 NP N N 1 2 N N NP NP 2 3 1 2 1 NPH-1 NP NP NP NP NP NP NP NP NP NP NP NP N NP NP NP NP NP NP NPH-2 3 4 3 NP 3 NP 3 NP 3 4 2 3 NP NP N NP 1 NP 1 NPH-3, H-4 2 3 2 NP 2 NP 2 NP 2 3 1 2 NP NP 1 NP 1d NP 1 NPH-5 2 NP 2 NP 2 NP 2 NP 2 NP 1 NP NP NP 1 NP 1 NP N NP

Page 92: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G90-18IBC: 508.1, 508.5, 508.5.1, 508.5.2, 508.5.3, 508.5.4, 508.5.5, 508.5.6, 508.5.7, 508.5.8, 508.5.9, 508.5.10,508.5.11Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Delete without substitution:

SECTION 419 LIVE/WORK UNITS

Revise as follows:

508.1 General. Each portion of a building shall be individually classified in accordance with Section 302.1. Where abuilding contains more than one occupancy group, the building or portion thereof shall comply with the applicableprovisions of Section 508.2, 508.3 or , 508.4, 508.5, or a combination of these sections.

Exceptions:

1. Occupancies separated in accordance with Section 510.2. Where required by Table 415.6.2, areas of Group H-1, H-2 and H-3 occupancies shall be located

in a detached building or structure.3. Uses within live/work units, complying with Section 419, are not considered separate

occupancies.

419.1508.5 General.Live/Work Units. A live/work unit shall comply with Sections 419.1 508.5 through 419.9.508.5.11.Exception: Dwelling or sleeping units that include an office that is less than 10 percent of the area of the dwellingunit are permitted to be classified as dwelling units with accessory occupancies in accordance with Section 508.2.

419.1.1508.5.1 Limitations. All of the following shall apply to live/work areas:

1. The live/work unit is permitted to be not greater than 3,000 square feet (279 m ) in area.2. The nonresidential area is permitted to be not more than 50 percent of the area of each live/work

unit.3. The nonresidential area function shall be limited to the first or main floor only of the live/work unit.4. Not more than five nonresidential workers or employees are allowed to occupy the nonresidential

area at any one time.

419.2508.5.2 Occupancies. Live/work units shall be classified as a Group R-2 occupancy. Separation requirementsfound in Sections 420 and 508 shall not apply within the live/work unit where the live/work unit is in compliance withSection 419. 508.5. Nonresidential uses that would otherwise be classified as either a Group H or S occupancy shall notbe permitted in a live/work unit.

Exception: Storage shall be permitted in the live/work unit provided that the aggregate area of storage in thenonresidential portion of the live/work unit shall be limited to 10 percent of the space dedicated to nonresidentialactivities.

419.3508.5.3 Means of egress. Except as modified by this section, the means of egress components for a live/workunit shall be designed in accordance with Chapter 10 for the function served.

419.3.1508.5.4 Egress capacity. The egress capacity for each element of the live/work unit shall be based on theoccupant load for the function served in accordance with Table 1004.5.

419.3.2508.5.5 Spiral stairways. Spiral stairways that conform to the requirements of Section 1011.10 shall bepermitted.

419.4508.5.6 Vertical openings. Floor openings between floor levels of a live/work unit are permitted withoutenclosure.

2

Page 93: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

[F] 419.5508.5.7 Fire protection. The live/work unit shall be provided with a monitored fire alarm system whererequired by Section 907.2.9 and an automatic sprinkler system in accordance with Section 903.2.8.

419.6508.5.8 Structural. Floors within a live/work unit shall be designed for the live loads in Table 1607.1, based onthe function within the space.

419.7508.5.9 Accessibility. Accessibility shall be designed in accordance with Chapter 11 for the function served.

419.8508.5.10 Ventilation. The applicable ventilation requirements of the International Mechanical Code shall applyto each area within the live/work unit for the function within that space.

419.9508.5.11 Plumbing facilities. The nonresidential area of the live/work unit shall be provided with minimumplumbing facilities as specified by Chapter 29, based on the function of the nonresidential area. Where thenonresidential area of the live/work unit is required to be accessible by Section 1107.6.2.1, the plumbing fixturesspecified by Chapter 29 shall be accessible.

Reason:Relocating Section 419 on Live/Work Units to Section 508 Mixed Occupancies provides a clearer description underMixed Use Occupancies since the unit is not only residential nor business use. An example is a doctor’s officeoccupying part of a detached dwelling, or townhouses with an office, store or restaurant on the first floor and aresidence occupying parts or all of upper floors.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This is an editorial relocation of existing requirements.Internal ID: 2257

Page 94: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G91-18IBC: [F] TABLE 509Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

THIS CODE CHANGE WILL BE HEARD BY THE FIRE CODE COMMITTEE. SEE THE TENTATIVE HEARING ORDER FOR THISCOMMITTEE

2018 International Building Code

Revise as follows:

[F] TABLE 509INCIDENTAL USES

For SI: 1 square foot = 0.0929 m , 1 pound per square inch (psi) = 6.9 kPa, 1 British thermal unit (Btu) per hour = 0.293watts, 1 horsepower = 746 watts, 1 gallon = 3.785 L, 1 cubic foot = 0.0283 m .a. See Chapter 6 of the International Fire Code for additional construction related requirements

Reason:This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Board

ROOM OR AREA SEPARATION AND/OR PROTECTIONFurnace room where any piece of equipment is over 400,000Btu per hour input a

1 hour or provide automatic sprinkler system

Rooms with boilers where the largest piece of equipment is over15 psi and 10 horsepower a

1 hour or provide automatic sprinkler system

Refrigerant machinery room a 1 hour or provide automatic sprinkler systemHydrogen fuel gas rooms, not class ified as Group H 1 hour in Group B, F, M, S and U occupancies; 2 hours in

Group A, E,I and R occupancies.Incinerator rooms a 2 hours and provide automatic sprinkler systemPaint shops, not class ified as Group H, located in occupanciesotherthan Group F

2 hours; or 1 hour and provide automatic sprinkler system

In Group E occupancies, laboratories and vocational shopsnotclass ified as Group H

1 hour or provide automatic sprinkler system

In Group I-2 occupancies, laboratories not class ified as Group H 1 hour and provide automatic sprinkler systemIn ambulatory care facilities, laboratories not class ified as GroupH

1 hour or provide automatic sprinkler system

Laundry rooms over 100 square feet 1 hour or provide automatic sprinkler systemIn Group I-2, laundry rooms over 100 square feet 1 hourGroup I-3 cells and Group I-2 patient rooms equipped withpaddedsurfaces

1 hour

In Group I-2, physical plant maintenance shops 1 hourIn ambulatory care facilities or Group I-2 occupancies, wasteandlinen collection rooms with containers that have an aggregatevolume of 10 cubic feet or greater

1 hour

In other than ambulatory care facilities and Group I-2occupancies, waste and linen collection rooms over 100 squarefeet

1 hour or provide automatic sprinkler system

In ambulatory care facilities or Group I-2 occupancies, storagerooms greater than 100 square feet

1 hour

Stationary storage battery systems having an energy capacitygreater than the threshold quantity specified in Table 1206.2 ofthe International Fire Code

1 hour in Group B, F, M, S and U occupancies; 2 hours inGroup A, E, I and R occupancies.

Electrical installations and transformers a See Sections 110.26 through 110.34 and Sections 450.8through 450.48 of NFPA 70 for protection and separationrequirements.

23

Page 95: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

of Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. This is a simple footnote pointer so designers are aware of additional construction and/or installation requirements forthese incidental use building systems that are located in Chapter 6 of the International Fire Code.This proposal is part of a comprehensive update to IFC Chapter 6 by the F-CAC. F-CAC fully supports this proposal. Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This proposal adds a pointer to existing requirements in the IFC. No new or additional construction requirements arebeing introduced into the IBC.Internal ID: 347

Page 96: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G92-18IBC: [F] TABLE 509Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected]); Robert Davidson,Davidson Code Concepts, LLC, representing Tesla, USA ([email protected])

THIS CODE CHANGE WILL BE HEARD BY THE FIRE CODE COMMITTEE. SEE THE TENTATIVE HEARING ORDER FOR THISCOMMITTEE

2018 International Building Code

Revise as follows:

[F] TABLE 509INCIDENTAL USES

For SI: 1 square foot = 0.0929 m , 1 pound per square inch (psi) = 6.9 kPa, 1 British thermal unit (Btu) per hour = 0.293watts, 1 horsepower = 746 watts, 1 gallon = 3.785 L, 1 cubic foot = 0.0283 m .

Reason:This proposal eliminates stationary storage battery systems as incidental use from Table 509. A rewrite of the IFC

ROOM OR AREA SEPARATION AND/OR PROTECTIONFurnace room where any piece of equipment is over 400,000Btu perhour input

1 hour or provide automatic sprinkler system

Rooms with boilers where the largest piece of equipment is over15psi and 10 horsepower

1 hour or provide automatic sprinkler system

Refrigerant machinery room 1 hour or provide automatic sprinkler systemHydrogen fuel gas rooms, not class ified as Group H 1 hour in Group B, F, M, S and U occupancies; 2 hours in

Group A, E,I and R occupancies.Incinerator rooms 2 hours and provide automatic sprinkler systemPaint shops, not class ified as Group H, located in occupanciesotherthan Group F

2 hours; or 1 hour and provide automatic sprinkler system

In Group E occupancies, laboratories and vocational shopsnotclass ified as Group H

1 hour or provide automatic sprinkler system

In Group I-2 occupancies, laboratories not class ified as Group H 1 hour and provide automatic sprinkler systemIn ambulatory care facilities, laboratories not class ified as GroupH

1 hour or provide automatic sprinkler system

Laundry rooms over 100 square feet 1 hour or provide automatic sprinkler systemIn Group I-2, laundry rooms over 100 square feet 1 hourGroup I-3 cells and Group I-2 patient rooms equipped withpaddedsurfaces

1 hour

In Group I-2, physical plant maintenance shops 1 hourIn ambulatory care facilities or Group I-2 occupancies, wasteandlinen collection rooms with containers that have an aggregatevolume of 10 cubic feet or greater

1 hour

In other than ambulatory care facilities and Group I-2occupancies, waste and linen collection rooms over 100 squarefeet

1 hour or provide automatic sprinkler system

In ambulatory care facilities or Group I-2 occupancies, storagerooms greater than 100 square feet

1 hour

Stationary storage battery systems having an energy capacitygreater than the threshold quantity specified in Table 1206.2 ofthe International Fire Code

1 hour in Group B, F, M, S and U occupancies; 2 hours inGroup A, E, I and R occupancies.

Electrical installations and transformers See Sections 110.26 through 110.34 and Sections 450.8through 450.48 of NFPA 70 for protection and separationrequirements.

23

Page 97: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

Section 1206 has added extensive protection features to such installations including detection, suppression, fireseparation, and explosion control, along with large scale testing to document the effectiveness of chosen protectionlevels. With the increased level of protection mandated by the IFC, there is no longer a need to limit such uses to 10%of a floor area as an incidental use.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. Cost ImpactThe code change proposal will decrease the cost of construction .Eliminating the incidental use 10% floor area restriction can reduce the cost of providing energy storage systems inmixed use buildings. Internal ID: 251

Page 98: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G103-18IBC: 202, TABLE 601, 704.4Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected]); Michael O'Brian,Chair, representing FCAC ([email protected])

2018 International Building Code

Revise as follows:

[BG] PRIMARY STRUCTURAL FRAME. The primary structural frame shall include all of the following structural members:1. The columns.2. Structural members having direct connections to the columns, including girders, beams, trusses and

spandrels.3. Members of the floor construction and roof construction having direct connections to the columns.4. Bracing members Members that are essential to the vertical stability of the primary structural

frame under gravity loading shall be considered part of the primary structural frame whether or notthe bracing member carries gravity loads.loading.

[BG] SECONDARY STRUCTURAL MEMBERS. The following structural members shall be considered secondary membersand not part of the primary structural frame:

1. Structural members not having direct connections to the columns.2. Members of the floor construction and roof construction not having direct connections to the

columns.3. Bracing members other than those that are not designated as part of the a primary structural

frame of bearing wall.

Page 99: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

TABLE 601FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (HOURS)

For SI: 1 foot = 304.8 mm.a. Roof supports: Fire-resistance ratings of primary structural frame and bearing walls are permitted

to be reduced by 1 hour where supporting a roof only.b. Except in Group F-1, H, M and S-1 occupancies, fire protection of structural members in roof

construction shall not be required, including protection of primary structural frame members, roofframing and decking where every part of the roof construction is 20 feet or more above any floorimmediately below. Fire-retardant-treated wood members shall be allowed to be used for suchunprotected members.

c. In all occupancies, heavy timber complying with Section 2304.11 shall be allowed where a 1-hour orless fire-resistance rating is required.

d. Not less than the fire-resistance rating required by other sections of this code.e. Not less than the fire-resistance rating based on fire separation distance (see Table 602).f. Not less than the fire-resistance rating as referenced in Section 704.10.

Page 100: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

704.4 Protection of secondary structural members. Secondary structural members that are required to haveprotection to achieve a fire-resistance rating shall be protected by individual encasement protection.

Reason:The definitions for the terms “primary structural frame” and “secondary members” are proposed to be modified so asto:• update the terms to adequately address new technologies, • to remove parts of the definition which could beconsidered archaic, and to remove what was viewed as redundant language. The new technologies being addressed is mass timber (e.g. glu-laminated, structural composite, cross laminated). Theproposed cleanup of this language will allow designers and code officials to better identify the structuralcharacteristics, such as when an entire building is constructed of mass timber panels (e.g. no columns). This will alsobenefit the same parties when other new materials technologies enter the market.The proposal focuses on modifying the “bracing members” subcategories where over time with modifications thecurrent language has become difficult to distinguish between the two. One example being when a lateral supportmember does not act as an element that part of the vertical stability of the structure, what is it? When reviewedmultiple responses were received suggesting the language in the definitions needed greater clarity.The proposal also have removed language from “Primary Structural Frame” that was felt to be redundant (e.g. theterm “bracing”)These terms are used in Chapter 6 “Types of Construction,” Chapter 7 “Smoke and Fire Protection Features,” andAppendix L “Requirements for Fire Fighting Air Replenishing Systems,” and focus on the fire resistance characteristicsof those structural elements. These terms are not used in Chapter 16 “Structural” nor the materials chapters of theIBC.Adding the word “structural” to the term "Secondary structural member" clarifies the intent and link to the definition for“primary structural members”. The word "structural" is also added to the applicable portions of Table 601.This proposal is submitted by the ICC Building Code Action Committee (BCAC) and the ICC Fire Code Action Committee(FCAC). The BCAC was established by the ICC Board of Directors in July 2011 to pursue opportunities to improve andenhance assigned International Codes or portions thereof. In 2017 the BCAC has held 3 open meetings. In addition,there were numerous Working Group meetings and conference calls for the current code development cycle, whichincluded members of the committee as w ell as any interested party to discuss and debate the proposed changes.Related documentation and reports are posted on the BCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. The FCAC was established by theICC Board of Directors to pursue opportunities to improve and enhance assigned International Codes with regard tofire safety and hazardous materials in new and existing buildings and facilities and the protection of life and property inwildland urban interface areas. In 2017 the Fire-CAC has held 3 open meetings. In addition, there were numerousconference calls, Regional Work Group and Task Group meetings for the current code development cycle, whichincluded members of the committees as well as any interested parties, to discuss and debate the proposed changes.Related documentation and reports are posted on the FCAC website at: https://www.iccsafe.org/codes-tech-support/cs/fire-code-action-committee-fcac/.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This proposal represents a clarification of the definitions to more clearly align with the original intent of the terms.Internal ID: 1149

Page 101: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G130-18 Part IIBC: 1207.4Proponent: Ed Kullik, representing ICC Building Code Action Committee ([email protected])

THIS IS A 2 PART CODE CHANGE PROPOSAL. PART I WILL BE HEARD BY THE GENERAL CODE DEVELOPMENT COMMITTEE. PART II WILL BE HEARD BY THE PROPERTY MAINTENANCE CODE COMMITTEE. SEE THE TENTATIVE HEARING ORDERS FORTHESE COMMITTEES.

2018 International Building Code

Revise as follows:

1207.4 Ef f iciency dwelling units. An efficiency living dwelling unit shall conform to the requirements of the codeexcept as modified herein:

1. The unit shall have a living room of not less than 220 190 square feet (20.4 17.6 m ) of floor area. Anadditional 100 70 square feet (9.3 6.5 m ) of floor area shall be provided for each occupant of suchunit in excess of two.

2. The unit shall be provided with a separate closet.3. The For other than Accessible, Type A and Type B dwelling units, the unit shall be provided with a

kitchen sink, cooking appliance and refrigeration facilitiesrefrigerator, each having a clear workingspace of not less than 30 inches (762 mm) in front. Light and ventilation conforming to this codeshall be provided.

4. The unit shall be provided with a separate bathroom containing a water closet, lavatory andbathtub or shower.

Internal ID: 1579

22

Page 102: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G130-18 Part IIIPMC: 404.6Proponent: Ed Kullik, representing ICC Building Code Action Committee ([email protected])

2018 International Property Maintenance Code

Revise as follows:

404.6 Ef f iciency unit. Nothing in this section shall prohibit an efficiency living dwelling unit from meeting the followingrequirements:

1. A unit occupied by not more than one occupant shall have a minimum clear floor area of 120 squarefeet (11.2 m ). A unit occupied by not more than two occupants shall have a minimum clear floorarea of 220 19 0 square feet (20.4 17.6 m ). A unit occupied by three occupants shall have aminimum clear floor area of 320 260 square feet (29.7 24.1 m ). These required areas shall beexclusive of the areas required by Items 2 and 3.

2. The unit shall be provided with a kitchen sink, cooking appliance and refrigeration facilities, eachhaving a minimum clear working space of 30 40 inches (762 990 mm) in front. Light and ventilationconforming to this code shall be provided.

Exception:Dwelling units not required to be Accessible units, Type A units and Type B units shallhave a clear working space of not less than 30 inches (762 mm) in front of the kitchen sink,cooking appliacne and refrigerator.

3. The unit shall be provided with a separate bathroom containing a water closet, lavatory andbathtub or shower.

4. The maximum number of occupants shall be three.

Reason:The market is trending toward smaller living areas in multi-family R-2 structures particularly in urban areas. US Censusstatistics show that in 2000, app. 46,000 rental units built were less than 1,000 sq.ft. In 2015, 114,000 units and in 2016,99,000 units were less than 1,000 sq.ft. The Urban Land Institute reported in 2013 that major Municipalities includingNew York City, San Francisco, Boston, Dallas and Philadelphia are allowing smaller apartments with Seattle andPortland (OR) having no minimum sizes. The proposed reduction allows for a modest decrease (13.6%) in the requiredliving room area and (30%) in the floor area for each occupant of such unit in excess of two. Code Professionals arereceiving proposals for dwelling units in R2 structures that are nonconforming with the minimum standards in the IBC.The Room Area standard for dwelling units in BOCA and SBBC as well as the 2000 edition of IBC required that one roommust have a minimum floor area of 150 sq.ft. This was reduced to 120 sq.ft in the 2003 IBC and remains today. Theminimum living room area for efficiency units in the 2000 IBC is the same as the 2018 IBC. No reduction has beenproposed even though the overall dwelling unit room area standard has been reduced. The proposal complies with thecurrent language in IBC Section 1207.3. which requires that habitable rooms be at least 120 sq.ft. IBC 1207.4: The change from "living unit" to "dwelling unit" is to use a defined term to describe these efficiencyapartments. The change in Item 3 corrects potential existing conflicts with Chapter 10 of ICC A117.1. which requiring aclear working space of 40 inches in front of the kitchen sink, cooking appliance and refrigerator for Accessible, Type Aor B units. The change from "refrigeration facilities" to "refrigerator" is to use a more clearly understood term, andeliminate someone believing that another type of fixture, such as a beer cooler, would be sufficient.IPC 404.6: The changes to the IPC are for coordination with the revisions to the IBC for efficiency apartments.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. Cost ImpactThe code change proposal will decrease the cost of construction .

22

2

Page 103: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

This proposal could decrease the cost of construction where efficiency apartments are built to the lower minimumsizes required by the text that is proposed.Internal ID: 3398

Page 104: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G136-18IBC: 202, 503.1.4, 1510.2.2Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

SECTION 202 DEFINIT IONS

Revise as follows:

[BG] PENTHOUSE. An enclosed, unoccupied rooftop structure used for sheltering mechanical and electrical equipment,tanks, elevators and related machinery, stairways and vertical shaft openings.

503.1.4 Occupied roofs. A roof level or portion thereof shall be permitted to be used as an occupied roof providedthe occupancy of the roof is an occupancy that is permitted by Table 504.4 for the story immediately below the roof.The area of the occupied roofs shall not be included in the building area as regulated by Section 506. An occupied roofshall not be included in the building height or number of stories as regulated by Section 504 provided the penthousesand other enclosed roof structures comply with Section 1510.

Exceptions:

1. The occupancy located on an occupied roof shall not be limited to the occupancies allowed ont he story immediately below the roof where the building is equipped throughout with anautomatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 and occupantnotification in accordance with Section 907.5 is provided in the area of the occupied roof.

2. Assembly occupancies shall be permitted on roofs of open parking spaces of Type I or Type IIconstruction, in accordance with the exception to Section 903.2.1.6.

SECTION 1510 ROOFTOP STRUCTURES

[BG] 1510.1 General. The provisions of this section shall govern the construction of rooftop structures.

1510.1.1 Area limitation. The aggregate area of penthouses and other enclosed rooftop structures shall not exceedone-third the area of the supporting roof deck. Such penthouses and other enclosed rooftop structures shall not berequired to be included in determining the building area or number of stories as regulated by Section 503.1. The area ofsuch penthouses shall not be included in determining the fire area specified in Section 901.7.

[BG] 1510.2 Penthouses. Penthouses in compliance with Sections 1510.2.1 through 1510.2.5 shall be considered as aportion of the story directly below the roof deck on which such penthouses are located. Other penthouses shall beconsidered as an additional story of the building.

[BG] 1510.2.1 Height above roof deck. Penthouses constructed on buildings of other than Type I construction shallnot exceed 18 feet (5486 mm) in height above the roof deck as measured to the average height of the roof of thepenthouse. Penthouses located on the roof of buildings of Type I construction shall not be limited in height.

Exception: Where used to enclose tanks or elevators that travel to the roof level, penthouses shall be permittedto have a maximum height of 28 feet (8534 mm) above the roof deck.

[BG] 1510.2.2 Use limitations. Penthouses shall not be used for purposes other than the shelter of mechanical orelectrical equipment, tanks, elevators and related machinery, stairways or vertical shaft openings in the roofassembly.assembly, including ancillary spaces used to access elevators and stairways.

Reason:This is part of a series of 3 proposals dealing with occupied roofs. See BCAC proposals to Section 1006 and 1009.Although it was felt the original intent of the egress associated with occupied roofs was clear, we felt there were a fewremaining provisions that left doubt as to what was intended. It had been reported that some code officials hadinterpreted the existing code provision to treat an unoccupied roof as an additional story so as to decrease the actualallowable stories in Chapter 5. To clarify that occupied roofs are not considered stories and are permitted to be usedprovide that egress is provided in accordance with all applicable sections of the IBC and IFC purposes in a manner “asif they were a story” without applying other “story” requirements like those associated with height and area limitationsin Chapter 5 or fire area provisions of Chapter 9, we propose the above modifications as summarized below:

Page 105: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

In Section 202, the definition of “PENTHOUSE” is proposed to be modified by adding the word “stairway”. Thisreinforces the existing and proposed language in Section 1510 that excludes certain allowable rooftop structures frombeing considered additional stories. The definition was not modified to include vestibule type areas as this isaddressed in the proposed change to Section 1510.2.2.The proposal in Section 503.1.4 Occupied roofs, adds a clarifying statement to support the concept that occupied roofsand other enclosed structures in Section 1510 are not an additional story.Proposed modifications to Section 1510 Rooftop Structures include the additions of the word “Stairways” and the term,including ancillary spaces used to access elevators and stairways.” to Section 1510.2.2. Use Limitations.As flat/ low-slope rooftops are increasingly, and intentionally, being designed and utilized for occupancies similar tothose on occupied floor levels below, modifications to the current code are necessary to define rooftop structures thatare occupied and ancillary to approved occupied roof uses and to clarify that these structures must comply withmeans of egress requirements, but are not a story for height and area limitations. In addition, the proposedmodifications described above align the limitations for Occupied roof ancillary structures with those for penthouses asa reasonable approach based upon the shared characteristics of the two structure types.This proposal is submitted by the ICC Building Code Action Committee (BCAC). BCAC was established by the ICC Boardof Directors in July 2011 to pursue opportunities to improve and enhance assigned International Codes or portionsthereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerous Working Group meetings andconference calls for the current code development cycle, which included members of the committee as w ell as anyinterested party to discuss and debate the proposed changes. Related documentation and reports are posted on theBCAC website at: https://www.iccsafe.org/codes-tech-support/codes/codedevelopment-process/building-code-action-committee-bcac.Cost ImpactThe code change proposal will not increase or decrease the cost of construction .This proposal is a clarification reminder of the scope of requirements included in the identified sections.Internal ID: 516

Page 106: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G140-18IBC: 3002.3, 3002.3.1 (New)Proponent: Ed Kullik, Chair, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Revise as follows:

3002.3 Emergency signs for other than occupant evacuation elevators... Where other than occupantevacuation elevators are provided, an approved pictorial sign of a standardized design shall be posted adjacent toeach elevator call station on all floors instructing occupants to use the exit stairways exits and not to use theelevators in case of fire. The sign shall read: IN CASE OF FIRE, ELEVATORS ARE OUT OF SERVICE. USE EXIT STAIRS.

Exceptions Exception:

1. The emergency sign shall not be required for elevators that are part of an accessible means ofegress complying with Section 1009.4.

2. The emergency sign shall not be required for elevators that are used for occupant self-evacuation in accordance with Section 3008.

Add new text as follows:

3002.3.1 Emergency signs for occupant evacuation elevators. Where occupant evacuation elevators areprovided, an approved pictorial sign of a standardized design shall be posted adjacent to each elevator call station onall floors instructing occupants to use occupant evacuation elevators in the event of fire. The sign shall read: IN CASEOF FIRE, THIS OCCUPANT EVACUATION ELEVATOR IS AVAILABLE FOR EXITING THE BUILDING.

Analysis: Duplicated text in the International Fire Code not shown for brevity.

Reason:This is one of 17 proposals being submitted as a package relating to technical and organizational changes proposedfor Chapter 6 of the Fire Code. While the Code Committees will consider each proposal independently, the intent is forapproval of all proposals in this package which have been submitted as a correlated set of companion code changeproposals.This proposal correlates with the series of proposals to the IFC Chapter 6 submitted by the F-CAC for correlation ofElevator requirements and specification of required signage for all elevators.This proposal addresses the emergency signage for the elevators in the IBC and the IFC. The changes are reflected inthe IBC as these are the parent sections for these requirements. If approved this language will be duplicated inChapter 6 of the IFC. This also correlates with the signage requirements in ASME A17.1. Exit stairways were changed to"exits" because there could be ramps instead of stairways.Two distinct sections are established between occupant evacuation elevators and other than those elevators. This proposal also adds standardized language to both the IBC and te IFC for occupant evacuation elevator signage toensure consistency between codes and to provide clear and concise building occupant instruction for their use.This proposal is submitted by the ICC Building Code Action Committee (BCAC) in support of the FCAC's efforts. BCACwas established by the ICC Board of Directors in July 2011 to pursue opportunities to improve and enhance assignedInternational Codes or portions thereof. In 2017 the BCAC has held 3 open meetings. In addition, there were numerousWorking Group meetings and conference calls for the current code development cycle, which included members of thecommittee as w ell as any interested party to discuss and debate the proposed changes. Related documentation andreports are posted on the BCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. Cost ImpactThe code change proposal will decrease the cost of construction .By providing standardized language for the emergency signs for occupant evacuation elevators, and correlating forconsistency the standardized language for other elevators.Internal ID: 407

Page 107: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G151-18IBC: (New), 3101.1, 3114 (New), 3114.1 (New), 3114.2 (New), 3114.3 (New), 3114.4 (New), 3114.5 (New),3114.6 (New), 3114.7 (New), 3114.8 (New), 3114.8.1 (New), 3114.8.1.1 (New), 3114.8.2 (New), 3114.8.3(New), 3114.8.4 (New), 3114.8.4.1 (New), 3114.8.4.2 (New), 3114.8.4.3 (New), 3114.8.5 (New), 3114.8.5.1(New), 3114.8.5.2 (New), 3114.8.5.3 (New), 3114.8.5.3(1) (New), 3114.8.5.3(2) (New), 3114.8.5.3(4) (New),3114.8.5.3(3) (New), 3114.8.5.3 (New), Chapter 35Proponent: Ed Kullik, representing ICC Building Code Action Committee ([email protected])

2018 International Building Code

Add new def inition as follows:

INTERMODAL SHIPPING CONTAINER. A six-sided steel unit originally constructed as a general cargo container used forthe transport of goods and materials.

Revise as follows:

3101.1 Scope. The provisions of this chapter shall govern special building construction including membrane structures,temporary structures, pedestrian walkways and tunnels, automatic vehicular gates, awnings and canopies, marquees,signs, towers, antennas, relocatable buildings, swimming pool enclosures and safety devices, and solar energysystems.systems and intermodal shipping containers.

Add new text as follows:

SECTION 3114 INTERMODAL SHIPPING CONTAINERS

3114.1 General. The provisions of Section 3114 and other applicable sections of this code, shall apply to intermodalshipping containers that are repurposed for use as buildings or structures or as a part of buildings or structures.

Exceptions:

1. Intermodal shipping containers previously approved as existing relocatable buildings complyingwith Chapter 14 of the International Existing Building Code.

2. Stationary storage battery arrays located in intermodal shipping containers complying withChapter 12 of the International Fire Code.

3. Intermodal shipping containers that are listed as equipment complying with the standard forequipment, such as air chillers, engine generators, modular data centers, and other similarequipment.

3114.2 Construction Documents. The construction documents shall contain information to verify the dimensionsand establish the physical properties of the steel components, and wood floor components, of the intermodal shippingcontainer in addition to the information required by Sections 107 and 1603.

3114.3 Intermodal shipping container information. Intermodal shipping containers shall bear an existing dataplate containing the following information as required by ISO 6346 and verified by an approved agency. A report of theverification process and findings shall be provided to the building owner.

1. Manufacturer's name or identification number2. Date manufactured.3. Safety approval number.4. Identification number.5. Maximum operating gross mass (kg) (Lbs)6. Allowable stacking load for 1.8G (kg) (lbs)7. Transverse racking test force (Newtons)8. Valid maintenance examination date

Where approved by the building official, the markings and existing data plate are permitted to be removed from theintermodal shipping containers before they are repurposed for use as buildings or structures or as a part of buildings

Page 108: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

or structures.

3114.4 Protection against decay and termites. Wood structural floors of intermodal shipping containers shall beprotected from decay and termites in accordance with the applicable provisions of Section 2304.12.1.1.

3114.5 Under-f loor ventilation. The space between the bottom of the floor joists and the earth under anyintermodal shipping container, except spaces occupied by basements and cellars, shall be provided with ventilation inaccordance with Section 1202.4.

3114.6 Roof assemblies. Intermodal shipping container roof assemblies shall comply with the applicablerequirements of Chapter 15.

Exception: Single-unit stand-alone intermodal shipping containers not attached to, or stacked vertically over,other intermodal shipping containers, buildings or structures.

3114.7 Joints and voids. Joints and voids that create concealed spaces between intermodal shipping containers,that are connected or stacked, at fire-resistance-rated walls, floor or floor/ceiling assemblies and roofs or roof/ceilingassemblies shall be protected by an approved fire-resistant joint system in accordance with Section 715.

3114.8 Structural. . Intermodal shipping containers which conform to ISO 1496-1 that are repurposed for use asbuildings or structures, or as a part of buildings or structures, shall be designed in accordance with Chapter 16 and thissection.

3114.8.1 Foundations. Intermodal shipping containers repurposed for use as a permanent building or structure shallbe supported on foundations or other supporting structures designed and constructed in accordance with Chapters 16through 23 of this code.

3114.8.1.1 Anchorage. Intermodal shipping containers shall be anchored to foundations or other supportingstructures as necessary to provide a continuous load path for all applicable design and environmental loads inaccordance with Chapter 16.

3114.8.2 Welds. All new welds and connections shall be equal to or greater than the original connections.

3114.8.3 Structural design. The structural design for the intermodal shipping containers repurposed for use as abuilding or structure, or as part of a building or structure, shall comply with Section 3114.8.4 or 3114.8.5.

3114.8.4 Detailed design procedure. A structural analysis meeting the requirements of this section shall beprovided to the building official to demonstrate the structural adequacy of the intermodal shipping containers.

Exception: Intermodal shipping containers designed in accordance with Section 3114.8.5.

3114.8.4.1 Material properties. Structural material properties for existing intermodal shipping container steelcomponents shall be established by material testing where the steel grade and composition cannot be identified bythe manufacturer's designation as to manufacture and mill test.

3114.8.4.2 Seismic design parameters. The appropriate detailing requirements of ASCE 7; response modificationcoefficient, R; overstrength factor, ⦠; deflection amplification factor, C ; and limits on structural height, h , for thecorrugated shear wall is permitted to be developed in accordance with generally accepted procedures whereapproved by the building official in accordance with Section 104.11. The seismic force-resisting system shall bedesigned and detailed in accordance with one of the following:

1. Where all or portions of the corrugated steel container sides are considered to be the seismicforce-resisting system, design and detailing shall be in accordance with the ASCE 7 Table 12.2-1requirements for light-frame bearing-wall systems with shear panels of all othermaterials,occupancies with an occupant load of 50 or less.

2. Where portions of the corrugated steel container sides are retained, but are not considered to bethe seismic force-resisting system, an independent seismic force-resisting system shall beselected, designed and detailed in accordance with ASCE 7 Table 12.2-1, or

3. Where portions of the corrugated steel container sides are retained and integrated into a seismicforce-resisting system other than as permitted by Sectuion 3114.4.2 Item 1, seismic designparameters shall be developed from testing and analysis in accordance with Section 104.11 andASCE 7 Section 12.2.1.1 or 12.2.1.2.

0 d n

Page 109: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

3114.8.4.3 Allowable shear value. The allowable shear values for the intermodal shipping container corrugatedsteel sheet panel side walls and end walls shall be demonstrated by testing and analysis accordance with Section104.11. Where penetrations are made in the side walls or end walls designated as part of the lateral force-resistingsystem, the penetrations shall be substantiated by rational analysis.

3114.8.5 Simplif ied structural design of single-unit containers. Single-unit intermodal shipping containersconforming to the limitations of Section 3114.8.5.1 shall be permitted to be designed in accordance with the simplifiedstructural design provisions of Section 3114.8.5.

3114.8.5.1 Limitations. Use of Section 3114.8.5 is subject to all the following limitations:

1. The intermodal shipping container shall be a single-unit, stand-alone unit supported on a foundationand shall not be in contact with or supporting any other shipping container or other structure.

2. The intermodal shipping container top and bottom rails, corner castings, and columns or anyportion thereof shall not be notched, cut, or removed in any manner.

3. The intermodal shipping container shall be erected in a level and horizontal position with the floorlocated at the bottom.

4. The intermodal shipping container shall be located in Seismic Design Category A, B, C or D.

3114.8.5.2 Simplif ied structural design. Where permitted by Section 3114.8.5.1, single-unit, stand-aloneintermodal shipping containers shall be designed using the following assumptions for the corrugated steel shear walls:

1. The appropriate detailing requirements contained in Chapters 16 through 23.2. Response modification coefficient, R=2,3. Overstrength factor, Ω =2.5,4. Deflection amplification factor, C = 2, and5. Limits on structural height, h = 9.5 feet (2,900 mm).

3114.8.5.3 Allowable shear. The allowable shear for the corrugated steel side walls (longitudinal) and end walls(transverse) for wind design and for seismic design using the coefficients of Section 3114.8.5.2 shall be permitted tohave the allowable shear values set forth in Table 3114.8.5.3 provided that all of the following conditions are met:

1. The total linear length of all openings in any individual side walls or end walls shall be limited to notmore than 50% of the length of that side walls or end walls, as shown in Figure 3114.8.5.3(1).

2. Any full height wall length, or portion thereof, less than 4 feet (305 mm) long shall not be consideredas a portion of the lateral force-resisting system, as shown in Figure 3114.8.5.3(2).

3. All side walls or end walls used as part of the lateral force-resisting system shall have an existingor new boundary element on all sides to form a continuous load path, or paths, with adequatestrength and stiffness to transfer all forces from the point of application to the final point ofresistance, as shown in Figure 3114.8.5.3(3).

4. Where openings are made in container walls, floors, or roofs for doors, windows and otheropenings:4.1 The openings shall be framed with steel elements that are designed in accordance with Chapter16 and Chapter 22.4.2. The cross section and material grade of any new steel element shall be equal to or greater

than the steel element removed. 5. A maximum of one penetration not greater than a 6-inch (152 mm) diameter hole for conduits,

pipes, tubes or vents, or not greater than 16 square inches (10,322 sq mm) for electrical boxes, ispermitted for each individual 8 foot length (2,438 mm) lateral force resisting wall. Penetrationslocated in walls that are not part of the wall lateral force resisting system shall not be limited insize or quantity. Existing intermodal shipping container vents shall not be considered a penetration,as shown in Figure 3114.8.5.3(4).

6. End wall door or doors designated as part of the lateral force-resisting system shall be weldedclosed.

.

0

d

n

Page 110: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

3114.8.5.3(1)Bracing Unit Distribution--Maximum Linear Length

Page 111: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

3114.8.5.3(2)Bracing Unit Distribution -- Minimum Linear Length

Page 112: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

3114.8.5.3(4)Bracing Unit Distribution -- Penetration Limitations

Page 113: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

3114.8.5.3(3)Bracing Unit Distribution -- Boundary Elements

Page 114: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

TABLE 3114.8.5.3Allowable Strength Values for Intermodal Shipping Container Corrugated Steel Siding Shear Walls for

Wind or Seismic Loading

1. The allowable strength shear for the side walls and end walls of the intermodal shipping containersare derived from ISO 1496-1 and reduced by a factor of safety of 5.

2. Container designation type is derived from ISO 668.3. Limitations of Sections 3114.8.5.1 shall apply

Page 115: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

ISO International Organization forStandardization

Chemin de Blandonnet 8 CP 4011214 Vernier

Geneva Switzerland

Add new standard(s) follows:

ISO 668: 2013:Series 1 Freight Containers - Classif ications, dimensions and ratings

ISO 1496-1: 2013:Series 1 Freight Containers - Specification and Testing - Part 1: General Cargo Containers forGeneral Purposes

ISO 6346: 1995, with Amendment 3: 2012:Freight Containers - Coding, Identif ication and marking

Reason:This code change purpose is to introduce intermodal shipping containers into the International Building Code based onrequests by code officials in the U.S. Prior to this proposal, several jurisdictions had created their own individualregulations or ordinances, or had administered additional requirements beyond the code (e.g. Section 104.11“Alternative materials, design and methods of construction and equipment ”) so as to be comfortable to ensure a safestructure. This code change proposal is in response to those requests to develop a set of consistent code provisionswhich cover the minimum safety requirements, but which do not duplicate existing code provisions.This proposal covers:

Creation of a new definition in order to separate the container from other I-code sections which refer to,but intentionally do not define, shipping containers,

Creating exceptions so to differentiate the intermodal shipping container from other code sections whichcould be interpreted as applying to intermodal shipping containers under other applications (e.g. temporarystorage, relocatable buildings, energy storage facilities, and listed equipment),

Verification of containers construction, condition, and structural integrity to assist the structural engineerin the evaluation for building construction,

References to other sections concerning foundations, decay and termite control, crawlspace ventilation,roof assemblies, interior finishes, and joints/intersections.

Introduction of structural provisions unique to intermodal shipping containers and which do not duplicatethe existing structural requirements, and

Addition of three ISO standards for reference.Chapter 2 - New definition - A new definition has been created in order that these provisions can be adequatelyenforced and not confused the other multiple varieties of definitions of containers currently in the market.Section 3114.1 – This represents the charging statement that outlines the requirements for containers, and list theappropriate exceptions with the I-codes in order to coordinate with other provisions that may appear similar in natureand where intermodal shipping containers could possibly be used in those other applications.Section 3114.2 – Construction documents – These provision emphasize the material requirements as specified in thissection.Section 3114.3 – Verification - These provisions focus on the characteristics of the intermodal shipping container priorto it being repurposed. In this case the provisions require a straight forward inspection by an approved agency, andverification of the data plate which is normally found on intermodal shipping containers. There was an intent not tospecify who the approved agency would be for two reasons; 1) so as to allow the code official or state law(s) tohandle this aspect recognizing that in each jurisdiction their requirements may be different, and 2) to avoid dictating aninternational agreement onto jurisdictions that are currently employed by the shipping and container manufacturersworldwide today. In this case, the standards are regulated by the International Convention of Safe Containers (CSC)that have policies and procedures for inspecting containers worldwide. These procedures include policies for ApprovedContinuous Examination Program (ACEP) at the time the container is used in production, and policies for third partyinspection agencies. The list shown in this section is a extract from the ISO standard and serves as a reference ofitems to be verified in order to validate the type of container.3114.4 through 3114.6 – While we have strived to focus on only those provisions that recognize the unique aspects ofintermodal shipping containers, we felt that some direction references were appropriate. In this case specific pointers

Page 116: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

are provided to foundations, decay and termite control, crawlspace ventilation, and roof requirements addressingdrainage and weather protection.3114.7 – Joints and voids – This provision is provided to address the interstitial spaces that may be created whenmultiple intermodal shipping containers are connected or stacked, whereby that concealed space between thecontainers is protected to prevent fire and hot gasses from passing between containers. Section 3114.8 – Structural - The structural provisions are divided into multiple categories, as follows: 1) the generalcharacteristics for all containers; 2) engineered structural design; and 3) simplified method for single-unit stand-alonecontainer.3114.8.1 – Foundations or supports – Provisions have been included to outline the two options for securing thecontainer; a foundation or the connection to another structure. This provision makes it clear that the load pathanchorage is required for all containers and to ensure the designed performance provided by the remainder of thestructural provisions.3114.8.2 – Welds – An additional provision has been added to require that any new welds be designed and installedwith welds of greater structural capabilities.Section 3114.8.4 – Detailed structural analysis - The detailed analysis engineering approach represents the generalengineering practice allowed for all other types of building constructions. For this section the engineer of record isallowed to practice as they normally would for any other building type. As may be noted much of this section requiressubmission through the alternative means and methods provisions in order to obtain a permit as information aboutintermodal shipping containers is not readily listed in the IBC provisions or referenced standards.Section 3114.8.5 – Simplified analysis - The concept for the single container approach is to make the design andconstruction process simpler. The provisions include a strict listing of limitations for use of these provisions. Theproposal also provides structural design information, and pre-established shear wall information that is contained inthe ISO 1496-1 standard, which is used to design and construct intermodal shipping containers. The shear wall valueswere obtained from the ISO 1496-1 standard through engineering analysis using a factor of safety of 5. In addition, aprovision was installed to limit the number and size of openings and service holes within the container, as well as toprevent building owners or designers from embellishing the size to something most engineers would define as anopening. This method is intended to address the simple structure approach and provide available information for useby the structural engineer to supplement their work.Chapter 35 – Referenced Standards – Included with this proposal are three ISO standards which are relevant to theintermodal shipping container’s construction. These standards are part of the industry standards regulated by theInternational Convention of Safe Containers (CSC) that have policies and procedures for inspecting containersworldwide.BCAC - The International Code Council’s Building Code Action Committee (BCAC) was established by the ICC Board ofDirectors to pursue opportunities to improve and enhance an assigned International Code or portion thereof. Thisincludes both the technical aspects of the codes as well as the code content in terms of scope and application ofreferenced standards. Since its inception in July, 2011, the BCAC has held open meetings and numerous workgroup callswhich included members of the BCAC as well as any interested party to discuss and debate the proposed changes andthe public comments. Related documentation and reports are posted on the BCAC website at:http://www.iccsafe.org/cs/BCAC/Pages/default.aspx.The ICC Building Code Action Committee created a task group to facilitate the development of this proposal. Membersof the assigned task group included representatives from: City of Long Beach, CA; County of Mecklenburg, NC; ModularBuilding Institute; American Iron and Steel Institute; Underwriters Laboratories; and the Portland Cement Association.Additional contacts included the State of California (Division of State Architect, Housing and Community Development),City of San Diego; City of Los Angeles, CA; City of Seattle; Clark County, NV; Falcon Structures, RADCO a TwiningCompany, SEABOX Company, FEMA ATC Seismic Code Support Committee, and other guests who provided theirindividual expertise.Cost ImpactThe code change proposal will decrease the cost of construction .The code change proposal will decrease the cost of construction. This new code section will provide clarity on how toconsistently design with, permit, and field inspect shipping containers that are repurposed for building construction.Current use of repurposed intermodal shipping containers requires the building owner or designee to submit throughthe alternative means and methods administrative provisions.

Analysis: A review of the standards proposed for inclusion in the code, ISO 668, ISO 1496-1 and ISO 6346, with regardto the ICC criteria for referenced standards (Section 3.6 of CP#28) will be posted on the ICC website on or before April2, 2018.

Page 117: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

Internal ID: 1586

Page 118: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

G154-18IBC: APPENDIX P (New), SECTION P101 (New), P101.1 (New), SECTION P102 (New), P102.1 (New), SECTIONP103 (New), P103.1 (New), TABLE P103.1(1) (New), TABLE P103.1(2) (New), SECTION P104 (New), P104.1(New), TABLE P104.1(1) (New), SECTION P105 (New), P105.1 (New), P105.1.1 (New), SECTION P106 (New),P106.1 (New), P106.1.1 (New), SECTION P107 (New), P107.1 (New), SECTION P108 (New), P108.1 (New), UL(New), CDPH (New)Proponent: Ed Kullik ([email protected])

2018 International Building Code

Add new text as follows:

APPENDIX P MATERIAL EMISSIONS

SECTION P101 GENERAL

P101.1 Scope. Site applied or installed adhesives and sealants, architectural coatings, floor, ceiling and wallassemblies and systems and insulation that are located on the interior side of the building envelope shall comply withSections P102 thorugh P107. Emission testing shall be performed by an ISO/IEC 17025 accredited laboratory that hasthe CDPH/EHLB/Standard Method v1.2, USEPA Method TO-17 and ASTM STandard Method D5197 within the scope of itsaccreditation. Approved agencies that are deeming products compliant with the product emission requirements shallbe accredited to ISO/IEC 17065 and have the relevant certification program in the scope of their accreditation.

SECTION P102 DEFINIT IONS

P102.1 General. The following words and terms shall, for the purposes of this appendix, have the following meaningsshown herein.VOLATILE ORGANIC COMPOUND (VOC). A chemical compound based on carbon chains or rings that typically containhydrogen and sometimes contain oxygen, nitrogen and other elements, and that has a boiling point in the range from(50 C to 100 C) to (240 C to 260 C).

SECTION P103 ADHESIVES AND SEALANTS

P103.1 General. Not less than 85 percent by weight or volume, of site-applied adhesives and sealants shall complywith the VOC content limits specified in Table P103.1(1) or the VOC emissions limits specified in Table P103.1(2). TheVOC content adhesives, sealants and sealant primers shall be determined and limited in accordance with SCAQMDRule 1168. HVAC duct sealants shall be classified as "Other" category within the SCAQMD Rule 1168 sealants table.The provisions of this section shall not apply to adhesives and sealants subject to state or federal consumer productVOC regulations. HVAC duct sealants shall be classified as "Other" category within the SCQQMD Rule 1168 sealantstable.Compliance with Table P103.1(2) shall be determined utilizing test methodology incorporated by reference in theCDPH/EHLB/Standard Method v1.2 and shall comply with the limit requirements for either office or classroom spaces,regardless of the space type.

Exceptions: The following solvent welding and sealant products are not required to comply with the emissions orthe VOC content requirements of this section

1. Cleaners, solvent cements and primers used with plastic piping and conduit in plumbing, firesuppression and electrical systems.

2. HVAC air duct sealants where the air temperature of teh space in which they are applied is lessthan 40 F (4.5 C).

o o o o

o o

Page 119: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

TABLE P103.1(1)SITE APPLIED ADHESIVE AND SEALANT VOC LIMITS a, b

Page 120: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

a. VOC limit less water and less exempt compounds in grams/liter (g/l)b. For low-solid adhesives and selants, the VOC limit is expressed in grams/liter of material as specified in SCAQMDRule 1168. For all other adhesives and sealants, the VOC limits are expressed as grams of VOC per liter of adhesive orsealant less water and less exempt compounds as specified in Rule 1168.

Page 121: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

TABLE P103.1(2)VOC EMISSION LIMITS

a. CDPH/EHLB/Standard Method v1.2 Chronic Reference Exposure Level (CREL).

Page 122: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

SECTION P104 ARCHITECTURAL COATINGS

P104.1 General. Not less than 85 percent of the weight or volume of site-applied architectural coatings specified inthis section shall comply with either VOC content limits established in Table P104.1(1) or the VOC emissions limits inTable P103.1(2)

1. Anticorrosive coatings.2. Basement specialty coatings.3. Concrete/masonry sealers.4. Concrete curing compounds.5. Dry fog coatings.6. Faux finish coatings.7. Fire-resistive coatings.8. Flat and non-flat topcoats.9. Floor coatings.10. Graphic arts (sign) coatings.11. High-temperature coatings.12. Industrial maintenance coatings.13. Low solids coatings14. Mastic texture coatings15. Metallic pigmented coatings.16. Multicolor coatings.17. Pretreatment wash primers.18. Primers19. Reactive penetrating sealers.20. Recyled coatings.21. Shellacs, clear and opaque.22. Specialty primers.23. Stains24. Stone consolidants.25. Swimming pool coatings.26. Tub- and tile-refining coatings.27. Under coaters.28. Waterproofing membranes.29. Wood coatings including clear wood finishes.30. Wood preservatives.31. Zinc primers.

Compliance with Table P103.1(2) shall be determined utilizing test methodology incorporated by reference in theCDPH/EHLB/Standard Method v1.2 and shall comply with the limit requirements for either office or classroom spaces ofthe space type.

Page 123: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

TABLE P104.1(1)VOC CONTENT LIMITS FOR ARCHITECTURAL COATINGS

a. The specified limits remain in effect unless revised limits are provided in subsequent columns of the table.b. Table P104.1(1) architectural coating regulatory category and VOC content compliance determination shall conformto the California Air Resources Board Suggested Control Measure for Architectural Coatings.c. Limits are expressed as VOC Regulatory (except as noted) thinned to the manufacturer's maximum thinningrecommendation, excluding any colorant added to tint bases.d. Limit is expressed as VOC actual.

a,b

Page 124: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

SECTION P105 FLOORING

P105.1 General. A minimum of 85 percent of the total area of flooring installed within the interior of the building shallcomply with the VOC limits in Table P103.1(2). Where flooring with more than one distinct product layer is installed, theemissions from each layer shall comply with these requirements. Compliance with Table P103.1(2). shall be determinedutilizing test methodology incorporated by reference in the CDPH/EHLB/Standard Method v1.2 and shall comply with thelimit requirements for either office or classroom spaces regardless of the space type.

P105.1.1 Deemed to comply. Floor covering materials that are composed of the following materials shall bedeemed to comply with the VOC emission limits in Table P103.1(2). Where these products include integral organic-based surface coatings, binders or sealants or are installed using adhesives, sealants, paints or coatings, thoseproducts shall be subject to other requirements of this appendix.

1. Ceramic and concrete tile.2. Natural stone.3. Gypsum plaster.4. Concrete masonry.5. Clay masonry.6. Metal.

SECTION P106 CEILING AND WALL ASSEMBLIES AND SYSTEMS

P106.1 General. A minimum of 85 percent of the total area of ceiling and wall assemblies and systems installed shallcomply with VOC limits in Table P103.1(2). Where assemblies and systems have more than one distinct product layerare installed, the emissions from each layer shall comply with these requirements. Compliance with Table P103.1(2)shall be determined utilizing test methodology incorporated by reference in the CDPH/EHLB/Standard Method v1.2 andshall comply with the limit requirements for either office or classroom spaces regardless of the space type.

P106.1.1 Deemed to comply. Ceiling and wall assembly and system materials that are composed of the followingmaterials shall be deemed to comply with the VOC limits in Table P103.1(2). Where these products include integralorganic-based surface coatings, binders or sealants or are installed using adhesives, sealants, paints or coatings,those products shall be subject to other requirements of this appendix.

1. Ceramic and concrete tile.2. Natural stone.3. Gypsum plaster.4. Concrete masonry.5. Clay masonry.6. Metal.

SECTION P107 INSULATION

P107.1 General. Not less than 85 percent of insulation, by square feet, installed shall comply with the VOC limits inTable P103.1(2). Compliance with Table P103.1(2) shall be determined utilizing test methodology incorporated byreference in the CDPH/EHLB/Standard Method v1.2 and shall comply with the limit requirements for either office orclassroom spaces regardless of the space type.

Add new standard(s) follows:

SECTION P108 REFERENCED STANDARDS CDPHCalifornia Department of Public Health, 850 Marina Bay Parkway, Richmond, CA 94804CDPH/EHLB/Standard Method v1.2' Standard Method for the Testing and Evaluation of Volatile Organic ChemicalEmissions from Indoor Sources Using Environmental Chambers Version 1.2"; January 2017, California Department ofPublic Health.ISOInternational Organization for Standardization, Chemin de Blandonnet 8, CP401, 1214 Vernier, Geneva, SwitzerlandISO/IEC 17025-05 General Requirements for the Competence of Testing and Calibration Laboratories.

Page 125: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

ISO/IEC 17065-12 Requirements for bodies certifying products, processes and services.EPAU.S. Environmental Protection Agency, Stationary Source Compliance Divisions, Washington D.C.US EPA Method TO-17 (issued 1/1999) Determination of Volatile Organic Compounds in Ambieent Air Using ActiveSampling on to Sorbent Tubes.ASTMASTM D5197-16 Standard Method for Determination of Formaldehyde and Other Carbonyl Compounds in Air (ActiveSampler Methodology)SCAQMDSouth Coast Air Quality Management District, 21865 Copley Drr. Diamond Bar, CA 91765Rule 1168-1989 Adhesive and Sealant Applications, with amendments through January 7, 2005.CEPACalifornia Environmental Protection Agency, Air Resources Board, 1001 I Street, Sacramento, CA 95814Suggested Control Measures for Architectural Coatings, February 1, 2008.

P108.1 General.

UL Underwriters Laboratories 36y8082130231- the standard title

CDPH California Department of Public Health, 850 Marina Bay Parkway, Richmond, CA 94804CDPHCaliforniaDepartment of Public Health, 850 Marina Bay Parkway, Richmond, CA 94804

CDPH/EHLB/Standard Method v1.2' Standard Method for the Testing and Evaluation of Volatile Organic ChemicalEmissions from Indoor Sources Using Environmental Chambers Version 1.2"; January 2017, California Department ofPublic Health.

Reason:In the last couple of decades our building codes have pushed for tighter building envelopes, more efficient andmechanical ventilation, with the goal of conserving energy and preserving water tightness. But this changes the indoorenvironment to a potentially adverse environment for occupants. Good indoor air quality (IAQ) is predicated on threefactors, correct ventilation, correct filtration, and source control. As our codes have evolved we’ve done well to focuson the first two (correct ventilation and filtration), but have not sufficiently addressed source control. Various materialswe regularly use in the construction and fit out of our buildings have emissions of volatile organic compounds (VOC).Limiting the emissions to an acceptable level has been established as the method for source control. The material emission requirements detailed in this proposal are based on commonly found VOC in our indoorenvironment that can come off of products. The California Office of Environmental Health Hazard Assessment (CAOEHHA) and California Department of Public Health (CDPH) developed the list of 35 individual VOC that are in eachrequirement. Numerous studies from around the globe show that exposure to high levels of some of the commonlyfound VOC detailed in these requirements can cause not only severe discomfort, but headaches, nose bleeds,increased asthma attacks, the onset of asthma, and potential long-term health effects. Some of these studies evenshow that continued exposure to some of these VOC can lead to an increase in C-reactive protein levels in humansubjects, which is the body’s response to inflammation.Section 101.3 of the IBC, states, “The purpose of this code is to establish the minimum requirements to provide areasonable level of safety, public health and general welfare…”. With the potential issues indoor occupants can receivedue to poor indoor air quality, the intent of the IBC implores us to put source control in to protect public health andgeneral welfare. Chapter 12 of the IBC governs the Interior Environment and has provisions for ventilation andsurrounding materials associated with the interior spaces of buildings.Many different stakeholder groups, including but not limited to, researchers, health officials, manufacturers,laboratories, and governmental representatives, have been involved in the development of the referenced testmethods, many of the studies, and in the codification of these requirements previously. North American and manyglobal manufacturers have embraced the lowering of emissions in the name of source control and there are thousandsof product that have proven to satisfy the proposed criteria in this section, at competitive prices, which ensures thereis enough supply to satisfy the demand. With these thousands of products available the cost of development andpurchase has steadily come down to levels that are on par with other products. Code officials, designers, installers,and building owners have many free resources to find compliant products and manufacturers even have ways to prove

Page 126: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

compliance to these requirements on their own.Builders will be able to show compliance in much the same way as they show compliance to many other fire, electrical,and other safety requirements in the codes. As with those other requirements, there are numerous laboratories aroundthe globe that meet the qualifications to perform the tests required in this proposal. Numerous ISO 17065 accreditedthird-parties around the globe also supply certifications that prove compliance to these requirements as well, so codeofficials have approved agencies that they already use and trust to help them prove compliance to these parameters. These requirements have been in the International Green Construction Code (IgCC) and ASHRAE 189.1 since theirinceptions and hundreds of authorities having jurisdictions already have these requirements in place, from large citiessuch as Washington DC, Dallas, TX, or Baltimore, MD to smaller jurisdictions such as Merced, CA, Scottsdale, AZ,Carbondale, CO, North Bend, WA, and Boynton Beach, FL. Products are available throughout the nation and builders areaware of how to find these products and show compliance to these requirements. As these types of requirements havebeen in green building codes and ratings systems for over a decade most North American manufacturers have many ifnot all of their products compliant with the requirements detailed above.The 85% level detailed in the requirements was originally put in to the other code documents in recognition of thenature of construction. Some of the products in the requirements are products that are common from project to projectand sometimes construction teams will utilize a little of the left over product from previous projects to complete a newproject. While this is not ideal for the potential emissions emitted into the indoor environment, the overall impact ofhaving to rip out all of the potentially impacted products for the small potential amount of emissions from the up to15% of non-compliance products.Some of the products detailed below are deemed not to need permits in the IBC and therefore may not be seen by thecode official, but IBC 105.2 states, “Exemptions from permit requirements of this code shall not be deemed to grantauthorization for any work to be done in any manner in violation of the provisions of this code or any other laws orordinances of this jurisdiction.” If there is a potential issue for indoor occupants the code should still cover it even if anAHJ decides that it doesn’t want to require documentation to detail compliance as the Intent detailed in Section 101.3of the IBC brings us back to ensure health and general welfare. Including these minimum material emission restrictionsin the IBC will ensure that all building occupants, not just those fortunate enough to be in a ‘sustainable’ building will beprotected from harmful chemicals and pollutants.The proposal adds new reference standard to Chapter 35 which have been previously referenced in the InternationalGreen Construction Code and they have been proven to be appropriate and acceptable for making the evaluations ofVOC content and emissions that are detailed in the proposal.In closing, the reasons for these requirements are:

As our building and energy codes require tighter and tighter buildings with less and less air changes, weneed to ensure that all three pillars of good indoor air quality are addressed in codes.

Almost all North American manufacturers have products that already show compliance to theserequirements, but some of our most recent issues have come with some products brought in fromoverseas.

Providing a reasonable level of safety, public health and general welfare is the stated purpose of thiscode. With the availability of products, ease of compliance review, and potential improvements in theindoor environment, these requirements fit the purpose of the IBC without extraordinary burden to any ofthe levels of building.

This proposal is submitted by the ICC Building Code Action Committee (BCAC). The proposal was brought to theBCAC by the ICC Sustainability, Energy, High Performance Code Action Committee (SEHPCAC). Both CACs wereestablished by the ICC Board of Directors in July 2011 to pursue opportunities to improve and enhance assignedInternational Codes or portions thereof. In 2017 the BCAC and SEHPCAC have each held 3 open meetings. In addition,there were numerous Working Group meetings and conference calls for the current code development cycle, whichincluded members of the committee as w ell as any interested party to discuss and debate the proposed changes.Related documentation and reports are posted on the BCAC website at: https://www.iccsafe.org/codes-tech-support/codes/code-development-process/building-code-action-committee-bcac. Bibliography:Studies or Statements:http://oem.bmj.com/content/52/6/388.abstract?ijkey=a259a5df5523262ebc77dbf9c265a51aa6d71686&keytype2=tf_ipsecshahttp://erj.ersjournals.com/content/20/2/403.abstract?ijkey=0fa737bd14c56216d6cda0c24409c8f3b4686dc7&keytype2=tf_ipsecshahttp://www.bioportfolio.com/resources/pmarticle/76147/Volatile-Organic-Compounds-Exposure-And-Cardiovascular-Effects-In-Hair-Salons.html

Page 127: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

http://onlinelibrary.wiley.com/doi/10.1111/j.1600-0668.2010.00673.x/abstracthttps://www.epa.gov/indoor-air-quality-iaq/volatile-organic-compounds-impact-indoor-air-qualityhttp://www.health.state.mn.us/divs/eh/indoorair/voc/https://www.healthlinkbc.ca/healthlinkbc-files/air-quality-VOCshttps://www.cdph.ca.gov/Programs/CCDPHP/DEODC/OHB/WRAPP/CDPH%20Document%20Library/full-disclosure-required-a-strategy-to-prevent-asthma-through-building-product-selection.pdf#search=%E2%80%9CStandard%20Method%20for%20the%20Testing%20and%20Evaluation%20of%20Volatile%20Organic%20Chemical%20Emissions%20from%20Indoor%20Sources%20Using%20Environmental%20Chambers%20Version%201%2E1%E2%80%9DStandardsCalifornia Department of Public Health850 Marina Bay ParkwayRichmond, CA 94804CDPH/EHLB/Standard Method V1.2 “Standard Method for the Testing and Evaluation of Volatile Organic ChemicalEmissions from Indoor Sources Using Environmental Chambers Version 1.2” dated January 2017, California Departmentof Public Health(http://berkeleyanalytical.com/sites/default/files/CDPH-IAQ_StandardMethod_V1_2_2017.pdf)ISOISO/IEC 17025-2005 General Requirements for the Competence of Testing and CalibrationLaboratories…(https://www.iso.org/standard/39883.html)ISO/IEC 17065:2012 Requirements for bodies certifying products, processes and services(https://www.iso.org/standard/46568.html)U. S. Environmental Protection AgencyStationary Source Compliance DivisionWashington, D.C.US EPA Method TO-17 (issued 1/1999) Determination of Volatile Organic Compounds in Ambient Air UsingActive Sampling Onto Sorbent Tubes (https://www3.epa.gov/ttnamti1/files/ambient/airtox/to-17r.pdf)ASTMASTM D5197-16 – Standard Method for Determination of Formaldehyde and Other Carbonyl Compounds in Air (ActiveSampler Methodology) (https://www.astm.org/Standards/D5197.htm)South Coast Air Quality Management District21865 Copley DrDiamond Bar, CA 91765Rule 1168-1989 Adhesive and Sealant Applications, with amendments through January 7, 2005………(http://www.aqmd.gov/docs/default-source/rule-book/reg-xi/rule-1168.pdf)California Environmental Protection AgencyAir Resources Board1001 I StreetSacramento, CA 95814California Air Resources Board Suggested Control Measure for Architectural Coatings, February 1, 2008(https://www.arb.ca.gov/coatings/arch/Approved_2007_SCM.pdf)Cost ImpactThe code change proposal will not increase or decrease the cost of construction .No impact should happen as these requirements have been in building codes and rating systems for over a decade.Due to this most manufacturers have products that meet these requirements already. In fact numerous manufacturersdon’t make a product that doesn’t meet these requirements.

Analysis: A review of the new standards proposed for inclusion in the code, ISO/IEC 17065-12 and USEPA Method TO-17, with regard to the ICC criteria for referenced standards (Section 3.6 of CP#28) will be posted on the ICC websiteon or before April 2. 2018.

Page 128: CCC-G2-18 · 4. Exit access stairways and ramps in open parking garages that serve only the parking garage. 5.4 Exit access stairways and ramps serving open-air assembly seating complying

The other standards referenced in the changes by this proposal, ISO/IEC 17025, CDPH/EHLB Standard Method v1.2,ASTM D5197, SCAQMD Rule 1168 and CEPA Suggested Control Measures for Architectural Coatings, are currentlyreferenced in other I-Codes.Internal ID: 1062