Cazul 6

Cazul 6 Generatoarele alimentate de pe bara 1, consumatorii alimentati de pe bara 2, cupla transversala stanga inchisa, cupla transversala dreapta deschisa, cupla longitudinala inchisa

Paladin DesignBase Power System Reliability Evaluation Program V5.40.00

=======================================================================

Project No. : Date & Time : 11/12/14 04:48:09 PM

Project Name: Title :

Drawing No. : Company :

Revision No.: Engineer :

Jobfile Name: Proiect Check by :

Scenario : Date :

System Information

==================

Base Power = 100000.00 (kVA)

Frequency = 50 (Hz)

MaxIterations = 1000

Error Tolerance = 10.000 (kVA), 0.0100 (%)

# of Active Buses = 23

# of Swing Buses = 0

# of Generators = 2

# of Lines/Breakers = 16

# of Transformers = 2

# of Loads = 2

# of Shunts = 0

Generator outages considered = upto 1

Branch outages considered = upto 1

Combine generator & branch outages = No

Abbreviations

=============

2-W xfmr = 2-winding transformer FeederM = Feeder in Magnetic Conduit

3-W xfmr = 3-winding transformer occ/yr = Occurrences per year

Autoxfmr = Autotransformer IEAR = Interrupted Energy Assessment Rate

curt = Curtailment or curtailed PhS xfmr = Phase-Shift Transformer

f./y = Failures per year SeriesC = Series Capacitor

Generator Reliability Input Information

=======================================

Generator Name Pmax Qmax Qmin Failure Repair Priority Consider

(MW) (MVAR) (MVAR) Rate Time 1 to 99 Reliability

(f./y) (hours) (Yes/No)

------------------------ -------- -------- -------- --------- ------- -------- --------

Generatorul 1 200.000 0.500 -0.500 0.001050 952.0 1 Yes

Generatorul 2 200.000 0.500 -0.500 0.001050 952.0 1 Yes

Branch Reliability Input Information

====================================

Branch Name Type Carrying Failure Repair Consider

Capacity Rate Time Reliability

(MVA) (f./y) (hours) (Yes/No)

------------------------ -------- -------- --------- ------- --------

Intrerupator 5 Breaker 15.588 0.010700 93.6 Yes

Intrerupator 6 Breaker 15.588 0.010700 93.6 Yes

Intrerupator cupla Breaker 15.588 0.010700 93.6 Yes

Intrerupatorul 1 Breaker 15.588 0.010700 93.6 Yes

Intrerupatorul 2 Breaker 15.588 0.010700 93.6 Yes

Intrerupatorul 4 Breaker 15.588 0.010700 93.6 Yes

Separatorul 1 Switch 25.981 0.000000 0.0 No

Separatorul 10 Switch 25.981 0.000000 0.0 No

Separatorul 11 Switch 25.981 0.000000 0.0 No

Separatorul 13 Switch 25.981 0.000000 0.0 No

Separatorul 14 Switch 25.981 0.000000 0.0 No

Separatorul 3 Switch 25.981 0.000000 0.0 No

Separatorul 5 Switch 25.981 0.000000 0.0 No

Separatorul 6 Switch 25.981 0.000000 0.0 No

Separatorul 7 Switch 25.981 0.000000 0.0 No

Separatorul 9 Switch 25.981 0.000000 0.0 No

Trafo 1 2-W xfmr 1.050 0.001620 616.0 Yes

Trafo 2 2-W xfmr 1.050 0.001620 616.0 Yes

Bus Availability Checking

=========================

Bus Name Type Required Calculated Pass/Fail

Availability (%) Availability (%)

------------------------ ------ ---------------- ---------------- ---------

Consumatorul 1 P_Load 100.00000 99.96592 Fail

Consumatorul 2 P_Load 100.00000 99.95450 Fail

System Summary - Expected Indices

=================================

------------------------------------------------------------------------------

Power supply disturbances

--------------------------------------------------------

All Causes Load Voltage Voltage

&Problems Interruption violations Violations

Load Level Events No Mvar With Mvar

------------ ------------ ------------ ------------

Probability 0.000682 0.000682 0.000000 0.000000

Frequency (occ/yr) 0.045990 0.045990 0.000000 0.000000

Duration (hrs/yr) 5.971329 5.971329 0.000000 0.000000

------------------------------------------------------------------------------

Power system interruption index = 0.027273 (MW/MW-yr)

Power system average MW interruption index = 0.296508 (MW/curt.)

Power system energy interruption index = 3.385902 (MWh/MW-yr)

Modified power system energy interruption index = 0.000387

Severity index = 203.154129 (Sys-Min)

System availability = 99.961349 (%)

Expected loss of load probability = 0.000682

Expected power not supplied = 0.000193 (MW/occ)

Expected energy not supplied = 0.047274 (MWh/occ)

Expected reactive power injection = 0.00 (Mvar/yr)

Average reactive power injection = 0.00 (Mvar/viol)

Expected outage cost = 0.00 (k$/yr)

Average outage cost = 0.00 (k$/curt.)

Bus Summary - Expected Indices

==============================

------------------------------------------------------------------------------------------

Bus Prob Freq Load curt Energy curt Duration Availability

(occ/yr) (MW/yr) (MWh/yr) (hrs/yr) (%)

------------------- ------- ----------- ---------- ----------- -------- ------------

Consumatorul 2 .000455 0.033689 0.0067 0.797 3.986 99.954498

Consumatorul 1 .000341 0.022995 0.0069 0.896 2.986 99.965919