1 Cathodic Protection for AST’s Presented by: James T. Lary Corrpro Companies, inc. 1055 West Smith Road Medina, Ohio 44256 [email protected] 330-241-6615 Preserve Assets Avoid Disruption of Service Enhance Safety Prevent Leaks Governmental Regulations Reduce Maintenance Costs Why is Cathodic Protection Important?

Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

1

Cathodic Protection for AST’s

Presented by:

James T. Lary

Corrpro Companies, inc.

1055 West Smith Road

Medina, Ohio 44256

[email protected]

330-241-6615

• Preserve Assets

• Avoid Disruption of Service

• Enhance Safety

• Prevent Leaks

• Governmental Regulations

• Reduce Maintenance

Costs

Why is Cathodic Protection Important?

Page 2: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

2

Terminal Tankage

Main Line

M

Valve

OPS

Inspection

Meter M

No OPS

Inspection

OPS Inspection Stops

(Enforcement Policy)

Loading

Terminal Product

Tank

(Terminal)

Product

Tank

(Terminal)

Breakout Tank

M

Main Line

Valve

OPS

Inspection

Meter M

Product

Tank

(Breakout)

M

Page 3: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

3

Charleston, WV Spill

The investigation found that two small

holes ranging in size from about 0.4-inch

to 0.75-inch in the bottom of the 48,000-

gallon tank 396 were caused by corrosion,

likely resulting from water leaking through

holes in the roof and settling on the tank

floor. Furthermore, the CSB inspection

found a similar hole penetrating the

bottom of nearby tank 397, containing the

same chemical at the facility, located in

Charleston. Other tanks also showed

multiple signs of pitting and metallurgical

damage, investigators said. The growing

corrosion in these tanks went unnoticed

until the bottom of 396 was breached and

up to an estimated 10,000 gallons of

product made their way through the

underlying mixture of soil and gravel

under the facility and into the Elk River on

January 9, 2014.

- Causes of Corrosion

- Cathodic Protection Applications

- Installation & Maintenance

- Rectifier Monitoring

What we will cover….

Page 4: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

4

Early Oil Tanks & Piping

did not Employ CP

IRON OXIDE REFINING MILLING

STEEL CORROSION IRON OXIDE

THE PROBLEM…..

Page 5: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

5

Anodic Area

-600mV Cathodic Area

-550mV

SAND

CURRENT FLOW

External Corrosion of

Tank Bottom

MFL Floor

Inspection

Page 6: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

6

SAND CURRENT FLOW

Corrosion Cell Caused

by Foreign Material in

Sand Cushion

CLAY

Steel Tank Floor

Page 7: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

7

DRY

SAND

MOIST SAND

WATER

Corrosion Caused by

Poor Water Drainage

New Bottom (Anode)

CURRENT FLOW

SAND

SAND

New Steel Coupled to Old Steel

Old Bottom (Cathode)

Page 8: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

8

Leak detection grove

under under bottom

Tank bottom required

30% floor

replacement

after 5 years in

service

Concrete Slab

Types of Cathodic Protection

Galvanic: Current obtained from a metal

with a higher energy level.

Impressed Current: Requires external

power source (transformer

rectifier).

Page 9: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

9

System Characteristics

Galvanic Impressed

No external power External power required

Fixed driving voltage Voltage can be varied

Limited current Current can be varied

Small current requirements High current requirements

Used in lower resistivity Used in almost any

environment resistivity environment

Usually negligible Must consider interference

interference with other structures

Above Ground Storage Tank With Galvanic Anodes

Anodes

Tank

Anodes

Page 10: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

10

Above Ground Storage Tank With Galvanic Anodes

Is Protection Being Achieved?

Anode

Tank

Uncoated Tank Bottom

Tank Grounded to Other

Structures

Test

Box

Anode

Cells

Tank

Galvanic Anodes

Page 11: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

11

• With the advent of secondary containment

liners for AST’s, some oil companies initially

installed galvanic (zinc or magnesium) anode

cathodic protection systems. Many of these

same companies have now abandoned this

approach due to the inability to obtain effective

levels of cathodic protection or limited system

design life.

• The industry preference for cathodic protection

for large AST’s is now impressed current.

Galvanic Anode Installation on AST. Note that anode life and current output are dependent upon sand / backfill conditions. Reference cells were rarely installed to monitor performance.

Galvanic

Anode

(Many galvanic systems installed by tank contractor)

Page 12: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

12

Recommended Practices

API-651 - Cathodic Protection of Aboveground Petroleum

Storage Tanks:

“Galvanic anodes method is not practical for

protection of large bare structures.”

NACE RP0193-2001 - External Cathodic Protection of On-

Grade Carbon Steel Storage Tank Bottoms:

“Galvanic protection systems can be applied to tank

bottoms where the metallic surface area exposed to

the electrolyte can be minimized through the

application of a dielectric coating or the area is small

due to the tank size or configuration.”

(+) (-)

Return

Rectifier

Anode

CURRENT FLOW

Impressed Current Cathodic Protection

Page 13: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

13

Impressed Current

Cathodic Protection System

Anodes

Rectifier

Wiring

Tanks & Piping

Page 14: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

14

Above Ground Storage Tank Vertical Impressed

Current Anodes - Existing Tanks

Sand

Anodes

Rectifier

Negative

Connection

+

-

Concrete

Ringwall

Tank

Anodes Rectifier

-

+

Negative

Connection

Tank

Page 15: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

15

Anodes

Junction

Box

Rectifier

- +

Deep Anode

Tank

(+)

(-)

Rectifier Tank

Tank Tank

Page 16: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

16

Computer Guided Horizontally

Bored Anode System

Tank

Rectifier

(+)

(-)

Anode

Splice Box

Anode

Pipe

Monitoring

Pipe

Anode Pipe

Page 17: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

17

ABOVEGROUND STORAGE TANK

CATHODIC PROTECTION

3” PVC 20%

Exposure

Anode Material

Anode Tube

10’

Typical

Test/Access

Station

Grade

Aboveground

Storage Tank

Page 18: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

18

Rectifier Units

Explosion or Non Explosion Proof ?

AC Input ?

AC Availability ?

CP Applications for Re-bottomed or

New Tanks

Page 19: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

19

CP Installation on Rebottomed Tank

Above Ground

Storage Tank Bottoms

with Secondary Containment

Page 20: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

20

Liner

Floor

Anode Conduit

CP Installation on Double Bottom Tank

New Tank Construction with Liner

Page 21: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

21

Anode

Reference

Cells

Tank

Impressed Current

Junction

Box

(-)

(+)

Rectifier

Anode & Reference Cell Placement

in High Resistance Sand

Page 22: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

22

Installation of CP System on

Lifted AST

Installation of CP System on

Lifted AST

Page 23: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

23

Cathodic Protection Survey (When Tank is Full)

Tank

Rim Potential Measurements

Portable Reference Cell

Soil

(+)

? ?

-850mV

Page 24: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

24

Soil Access Station (Thru Liner or Asphalt)

Reference Cell Placement Under Tank Bottom

(Note obtain and store native readings)

Page 25: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

25

Reference Cell Monitoring Conduit

Tank

Monitoring

Conduit

Cathodic Protection Monitoring

• Read rectifiers every

30 days.

• Conduct annual

inspection (obtain

potentials) by NACE

certified individuals.

Page 26: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

26

Hot Asphalt Tank Bottoms

Stray Current ?

Page 27: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

27

Pipeline Integrity Inspections

Qualifications

of the corrosion engineer

• Certified by N.A.C.E.

(National Association of Corrosion Engineers)

• Experienced in Cathodic Protection

• Experienced in Cathodic Protection of Fuel

Storage Systems

Page 28: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

28

Internal Corrosion

Anode Cathode

Water / Sediment

Fuel Product

Internal Corrosion

Page 29: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

29

Coating Anode

Bolt

Tank Bottom

Page 30: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

30

Recommended Practices

API-651 - Cathodic Protection of Aboveground Petroleum

Storage Tanks:

NACE RP0193-2001 - External Cathodic Protection of On-

Grade Carbon Steel Tank Bottoms:

Iron Water Fire Water

Piping

Pitting (concentrated)

corrosion attack on ductile iron

pipe.

Page 31: Cathodic Protection for AST’s Protection...gallon tank 396 were caused by corrosion, likely resulting from water leaking through holes in the roof and settling on the tank floor

31

Questions?