    Siemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    3/36

    2

    1

    3

    4

    Siemens Vacuum

    Recloser 3ADMedium-Voltage EquipmentCatalog HG 11.42 2008

    Contents Page

    DescriptionGeneral

    Switch unit

    Controller, protection functions

    Ambient conditions, altitude correction factor

    and number of operating cycles

    Product range overview and scope of delivery

    56

    7

    9

    13

    14

    Product SelectionOrdering data and configuration example

    Selection of primary ratings

    Selection of controller

    Selection of additional equipment

    1516

    17

    20

    24

    Technical DataElectrical data, dimensions and weights:

    Voltage level 12 kV

    Voltage level 15.5 kV

    Voltage level 27 kV

    Voltage level 38 kV

    27

    28

    28

    29

    29

    AnnexInquiry form

    3334

    Siemens Vacuum Recloser 3AD Contents

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    4/36

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    5/36

    1

    DescriptionContents

    Vacuum recloser with cubicle and controller

    R-H

    G11-

    301.t

    if

    Contents Page

    Description

    General

    Switch unit:

    Recloser principle

    Design

    Pole assemblies

    Operating mechanism

    Magnetic actuator

    Mechanical lockout

    Recloser cycle

    Controller:

    User interface

    Protection functions

    CommunicationsProtocols

    Metering functions

    Data records

    Software

    Standards

    Ambient conditions

    Altitude correction factor

    Number of operating cycles

    5

    6

    7

    7

    7

    7

    7

    8

    8

    9

    10

    1111

    11

    11

    12

    12

    13

    13

    13

    Siemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    6/36

    1

    Siemens vacuum recloser 3AD

    The switch unit is the primary part of the recloser. It is

    located on top of the pole to switch the overhead line

    As the heart of the recloser, the controller is located in a

    cubicle at the bottom of the pole

    Switch unit Controller inside the cubicle

    R-H

    G11-

    302.t

    if

    R-

    HG11-

    303.t

    if

    DescriptionGeneral

    3AD vacuum reclosers are outdoor circuit-breakers

    designed for frequent opening and reclosing in case of

    temporary faults. They fulfill this task automatically by

    monitoring the line and operating autonomously.

    The recloser consists of two main components: The

    switch unit being the circuit-breaker and the controller as

    protection and control unit. It is housed inside the control

    cubicle.

    Siemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    7/36

    1

    Recloser principle

    Reclosers are used in distribution systems of power supply

    companies (utilities). Like circuit-breakers they are capable

    of switching normal and fault currents. They are equipped

    with sensors and a controller being the protection and

    control device. In case of a line fault, they can break and

    make several times, thus avoiding longer network interrup-tions due to temporary faults.

    As outdoor devices they are normally pole-mounted and

    exposed to environment and weather. A recloser consists of

    two components: The switch unit (circuit-breaker) and the

    controller (inside the control cubicle), both connected

    through a control cable.

    Design

    Switching operation

    The vacuum switching technology, proven and fully

    developed for more than 30 years, is the basis for the

    vacuum interrupters.

    Pole assemblies

    Each vacuum interrupter is embedded in an epoxy-resin pole

    made out of weather-proof cycloalyphatic resin. This enables

    a small design as well as resistance against environmental

    effects. The vacuum interrupter is vertically mounted inside

    the pole, providing a long service life. Each recloser is equip-

    ped with an integrated current transformer. For special pro-

    tection purposes, a resistive voltage sensor can also be

    incorporated in the pole. The accuracy achieved in this way

    is much higher than that of capacitive dividers.

    Operating mechanism

    The pole assemblies of the recloser are directly mounted on

    the operating mechanism housing. Besides the complete

    kinematics, it also accommodates the position indicator and

    a mechanical operations counter. The operating mechanism

    housing is made of mild steel with a special coating for out-

    door applications. Optionally, a stainless-steel housing is

    available.

    DescriptionSwitch unit

    Siemens Vacuum Recloser 3AD

    Switch unit front view

    Switch unit rear view

    R

    -HG11-3

    04.t

    if

    R-

    HG11-

    305.t

    if

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    8/36

    1

    Siemens Vacuum Recloser 3ADDescriptionSwitch unit

    Mechanical lockout

    A mechanical lockout enables tripping independently on the

    controller. If this handle is pulled, the recloser opens and is

    simultaneously locked out electrically and mechanically. The

    handle stays extended, thus indicating the interlocked state.

    To close the recloser again, the operating rod must first be

    pushed back to the operation position in order to release the

    lockout. Then the recloser can be closed electrically via the

    control.

    Recloser cycle

    In case of a network fault, the recloser opens and recloses

    several times. In case of temporary faults the automatic

    reclosing significantly reduces the loss of power supply.

    The recloser cycle is optimized accordingly:

    The first interruption of a fault is done quickly and

    instantaneously, so that even the fuses in the system do not

    operate. After approx. 300 ms (user settable), it recloses

    back on.

    The second and third interruption has a definite or inverse-

    time delay. Thus, downstream fuses in the network have the

    chance to operate and isolate the affected network section,

    restoring normal operation in the remaining network. The

    following dead time is usually 210 s (user settable).

    The fourth (optional up to the fifth) interruption is fast

    again and serves as a check. This for example utilizes the

    physical effect that, when the short-circuit occurs, the lines

    move due to the magnetic forces of the current, and foreign

    objects are shaken off.

    If the fault still exists, the recloser turns to the lockout and

    can only be closed from the operator panel or via SCADA.

    Lock-out handle pushed in

    (operational position)

    R-H

    G11-

    306.t

    if

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    9/36

    1

    The controller

    The Siemens Argus-M controller is based on the Argus-M

    directional overcurrent protection relay. These relays provide

    protection, control, monitoring, instrumentation and me-

    tering with integrated input and output logic, data logging

    & fault reports.

    Communication access to relay functionality is via a front

    USB port for local PC connection or a rear electrical RS485

    port for remote connection. Additional rear port options are

    available.

    The controller is mounted in the control cubicle. Along with

    the controller, this cubicle also contains the auxiliary power

    supply with batteries for uninterruptible power supply,

    electronic boards, fuses, and a general-purpose outlet to

    power a laptop.The controller contains a large number of protection

    functions (elements) which can be selected or deselected

    through the menu driven display. These elements can be

    customized to the utilities needs by parameters (settings) as

    described below.

    User interface

    20-character x 4-line backlit LCD

    Menu navigation keys

    3 fixed LEDs

    8 or 16 programmable tri-color LEDs are available

    eliminating the need for expensive panel-mounted pilot

    lights and associated wiring. Each LED is tri-colored (red,

    green, yellow) allowing for clear indication of the associated

    functions state.

    12 programmable function keys each with tri-color LED are

    available for implementing scheme control functionality.

    Each function key has an associated tri-color LED (red,

    green, yellow) allowing for clear indication of the associated

    functions state.

    DescriptionController

    Siemens Vacuum Recloser 3AD

    Argus-M controller

    Tri-color LEDs and pushbuttonsof the controller

    R-

    HG11-

    308.t

    if

    R-

    HG11-3

    09.t

    if

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    10/36

    1

    DescriptionController

    Siemens Vacuum Recloser 3AD

    Protection functions

    (in order of ANSI numbering)

    37 Undercurrent

    Each element has settings for pickup level and Definite Time

    Lag (DTL) delays. Operates if current falls below setting for

    duration of delay.

    46BC Broken conductor/phase unbalance

    Element has settings for pickup level and DTL delay. With the

    circuit-breaker closed, if one or two of the line currents fall

    below setting, this could be due to a broken conductor.

    46NPS Negative phase-sequence overcurrent

    Each element has user settings for pickup level and Inverse

    Definite Minimum Time Lag (IDMTL) or DTL delay. It operates

    if NPS current exceeds setting and delay. NPS current ele-ments can be used to detect unbalances on the system or

    remote earth faults when a delta-star transformer is in

    circuit.

    49 Thermal overload

    The thermal algorithm calculates the thermal states from the

    measured currents and can be applied to lines, cables and

    transformers. Outputs are available for thermal overload and

    thermal capacity.

    50/51 Phase fault

    50 INST (instantaneous)/DTL (Definite Time Lag) and

    51 IDMTL (Inverse Definite Minimum Time Lag)/DTL ele-

    ments provide overcurrent protection, each with indepen-

    dent settings for pickup current, time-multiplier (51) and

    time delays. The user can select IEC or ANSI time current

    characteristics. The IDMT stage has a user programmable

    reset characteristic, either DTL or shaped current/time resetcharacteristic to improve grading with electromechanical

    protection.

    50G/51G/50N/51N Earth fault/sensitive earth fault

    Earth-fault current is derived from the residual connection of

    the 3 integrated line CTs 50 INST/DTL and 51 IDMTL/DTL

    64H Restricted earth-fault scheme

    The measured earth-fault input may be used in a 64H high

    impedance restricted earth-fault scheme. Required external

    series stabilizing resistor and non-linear shunt resistor can be

    supplied.

    74TC Trip-circuit supervisionThe trip-circuit(s) can be monitored via binary inputs. Trip-

    circuit failure raises an HMI alarm and output(s).

    81HBL2 Inrush restrain/second harmonic block

    Where second harmonic current is detected (i.e. during

    transformer energization) user selectable elements can be

    blocked.

    Cold load pickup

    If a circuit-breaker is closed onto a cold load, i.e. one that

    has not been powered for a prolonged period, this can

    impose a higher than normal load-current demand on the

    system which could exceed normal settings. These

    conditions can exist for an extended period and must not be

    interpreted as a fault. To allow optimum setting levels to be

    applied for normal operation, the cold load pickup feature

    will apply alternative settings for a limited period. The fea-

    ture resets when either the circuit-breaker has been closedfor a settable period, or if the current has been reduced

    beneath a set level for a user set period.

    27/59 Under/overvoltage

    Each element has settings for pickup level, drop-off level and

    Definite Time Lag (DTL) delays. It operates if voltage exceeds

    setting for duration of delay. It can be applied in load shed-

    ding schemes.

    47 Negative phase-sequence overvoltage

    Each element has settings for pickup level and Definite Time

    Lag (DTL) delays. It operates if NPS voltage exceeds setting

    for duration of delay.

    59N Neutral overvoltage

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    11/36

    1

    DescriptionController

    Siemens Vacuum Recloser 3AD

    67/67N Directional control

    Phase-fault, earth-fault and sensitive earth-fault elements

    can be directionalized. Each element can be user set to

    forward, reverse, or non-directional. Directional phase-fault

    elements are polarized from quadrature voltage. Earth-fault

    elements can be user set to be polarized from residual

    voltage or negative phase-sequence voltage.

    81 Under/overfrequency

    Each element has settings for pickup level, drop-off level and

    Definite Time Lag (DTL) delays. It operates if frequency ex-

    ceeds setting for duration of delay. It is typically applied in

    load shedding schemes.

    79 Auto-reclose

    Each element provides independent phase-fault and earth-fault/sensitive earth-fault sequences of up to 5 trips, i.e.

    4 reclose attempts before lockout. Auto-reclose sequence

    can be user set to be initiated from internal protection

    operation or via binary input from an external protection.

    Each trip in the sequence can be user set to be either instan-

    taneous (fast) or delayed. The user can set each reclose

    (dead) time and the reclaim time.

    Battery and capacitor check (no number)Sag/swell detection

    Optional protection functionality

    Sync check

    Fault locator

    Loop automation

    Single-triple operation

    Communications Front USB port

    Rear RS485 port

    Optional functions

    Rear fiber optic ports

    Metering functions

    Primary current phases and earth

    Secondary current phases and earth

    Positive phase-sequence (PPS) current

    Negative phase-sequence (NPS) current

    Zero phase-sequence (ZPS) current

    Binary input/output status

    Trip circuit healthy/failure

    Time and date

    Starters

    Fault records

    Event records

    Frequency

    Waveform records

    Circuit-breaker trip counters

    It summation for contact wear

    Direction

    Primary line and phase voltages

    Secondary voltages

    Apparent power and power factor

    Real and reactive power

    W Hr forward and reverse

    VAr Hr forward and reverse

    Historical demand record

    Positive phase-sequence (PPS) voltage

    Negative phase-sequence (NPS) voltage

    Zero phase-sequence (ZPS) voltage

    Data records

    Sequence of event records

    Up to 5000 events can be stored.

    Fault records

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    12/36

    1

    DescriptionController, standards

    Siemens Vacuum Recloser 3AD

    Software

    Reydisp Evolution

    For communication with the relay via a PC (personal

    computer) a user-friendly software package, Reydisp

    Evolution, is available to allow transfer of relay settings,

    waveform records, event records, fault data records,

    instruments/meters and control functions. Reydisp Evolution

    is compatible with IEC 60870-5-103.

    Programmable logic

    The user can map binary inputs and protection operated

    outputs to function inhibits, logic inputs, LEDs and/or binary

    outputs. The user can also enter up to 16 equations defining

    scheme logic using standard functions e.g. timers and/or

    gates, inverters and counters. Each protection element

    output can be used for alarm & indication and/or tripping.

    Waveform records analysis

    See figure left

    Quick logic

    The Quick logic feature allows the user to input up to 16

    logic equations (E1 to E16) in text format. Equations can be

    entered using Reydisp or at the relay fascia.

    Each logic equation is built up from text representing control

    characters. Each can be up to 20 characters long.

    Standards

    The recloser conforms to the following standards

    ANSI C37.60 (2003)

    IEC 60255

    IEC 60694 (in future IEC 62271-1)

    Typical Reydisp Evolution screenshot

    R-

    HG11-3

    10.t

    if

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    13/36

    1

    Ambient conditions

    The recloser is designed for the normal operating conditions

    defined in ANSI C37.60. This comprises an ambient tempera-

    ture from 40 C to +55 C plus solar radiation.

    Altitude correction factor

    The dielectric strength of air insulation decreases withincreasing altitude due to low air density. The rated lightning

    impulse withstand voltage values specified in the chapter

    Technical Data apply to a site altitude of 1000 m above sea

    level. For an altitude above 1000 m, the insulation level

    must be corrected according to the opposite drawing.

    The characteristic shown applies to the rated short-duration

    power-frequency withstand voltage and the rated lightning

    impulse withstand voltage.

    To select the devices, the following applies:

    U W U0 x Ka

    U Ratedwithstand voltage understandardreference atmosphere

    U0 Rated withstand voltage requestedfor theplace of installation

    Ka Altitude correctionfactor according to the opposite diagram

    Example

    For a requested rated lightning impulse withstand voltage

    of 75 kV at an altitude of 2500 m, an insulation level of90 kV under standard reference atmosphere is required as

    a minimum:

    90 kVW 75 kV x 1.2

    Number of operating cycles

    The recloser is designed for 10,000 operating cycles at

    normal current.

    According to the standard IEEE C37.60, the recloser has been

    tested for 116 short-circuit breaking operations. The actual

    number of short-circuit breaking operations is higher than

    that, and can be even more than 200 depending on the pa-

    rameters of the short-circuit current (amplitude, DC compo-

    nent).

    DescriptionAmbient conditions, altitude correction factor and number of operating cycles

    Siemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    14/36

    1

    DescriptionProduct range overview and scope of delivery

    Siemens Vacuum Recloser 3AD

    Product range overview

    Rated voltage Ratedshort-circuit

    breaking current

    Ratedlightning impulsewithstand voltage

    Ratednormal current

    kV kA kV 400 A 630 A 800 A

    12 12.5 95

    15.5 12.5 110 16 110

    27 12.5 125

    12.5 150

    16 150

    38 12.5 170

    16 170

    Scope of delivery

    Standard equipment Optional available Remarks

    Switch unit

    Operatingmechanism Electrical operatingmechanism

    (magnetic actuator)Operating mechanismhousing

    Mildsteelwith outdoor protectioncoating IP 55 with liftingeyesand earthing connection

    Stainlesssteel

    Switching medium Vacuum interrupters

    Insulation Cycloaliphatic epoxy resin/air

    Power supply Auxiliary power input Auxiliary transformer for supplyfrom HV line

    Position indicator OPEN: greenCLOSED: red

    Customer-specificcoloror inscription

    Operations c ounter Mechanical in the s witch u nit;electronical in the controller

    Interlocking Electrical; mechanical lockoutConfiguration Pole mounting and 6m

    control cableOthercable lengths and/orsubstationframe

    Sensors Integrated current transformers Integrated voltage sensors

    Controller andcontrol cubicle

    Cubicle Mild steel with outdoor protectioncoating IP 65 with liftingeyes

    Stainlesssteel

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    15/36

    2

    Switch unit bottom view

    Contents Page

    Product Selection

    Ordering data and configuration example

    Selection of primary ratings:

    Voltage level 12 kV

    Voltage level 15.5 kV

    Voltage level 27 kV

    Voltage level 38 kV

    Selection of controller:

    Recloser configuration

    Current and voltage measuring

    Controller size

    Auxiliary voltage

    Control and sensor cables

    Communication protocols

    Communication interfaces

    Function packages

    Languages and power socket

    Selection of additional equipment

    Accessories and spare parts

    15

    16

    17

    17

    18

    19

    20

    20

    21

    21

    22

    22

    22

    23

    23

    24

    25

    Product SelectionContents

    R-

    HG11-3

    11.t

    if

    Siemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    16/36

    2

    Order number structure

    The vacuum reclosers consist of a primary part as well as of a

    controller or secondary part. The relevant data make up the

    16-digit order number. The primary part covers the main

    electrical data of the circuit-breaker poles. The controller and

    secondary part covers all auxiliary devices and the controller,

    which are necessary for operating and controlling therecloser.

    Order codes

    Individual equipment versions, marked with 9 orZ in the 8th

    to 16th position, are explained more in detail by a 3-digit

    order code. Several order codes can be added to the order

    number in succession and in any sequence.

    Mounting parts and special versions (

    )

    In case of special versions, - Z is added to the order number

    and a descriptive order code follows. If several special

    versions are required, the suffix -Z is only listed once.

    If a requested special version is not in the catalog and can

    therefore not be ordered via order code, it has to be

    identified withY 9 9 after consultation. The agreementhereto is made between your responsible sales partner and

    the order processing department in our Switchgear Factory

    in Berlin.

    a:alphabetical n:numerical

    Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes

    Order No.: 3 A D n n n n n a a n n n a a n

    Primary part

    1st position Superior groupSwitching devices

    2nd position Main groupCircuit-breaker

    3rd position SubgroupOutdoor vacuum recloser

    4th to 7th position Basic equipmentDesign and ratingsof thevacuum recloser

    Secondary part

    8th to16th position Controller, sensors, cables andother necessary data

    Ordercodes

    Group of3 afterthe Order No.Format: a n a

    Special versions ( )

    Initiated with -ZGroup of3 afterthe Order No.Format: a n n

    Product SelectionOrdering data and configuration example

    Siemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    17/36

    2

    Product SelectionSelection of primaryratings

    12 kV Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes50/60 Hz OrderNo.: 3 A D

    Type

    Ur Up Ud Isc Ir

    kV kV kV kA A

    12 75 42 12.5 630 3 A D 1 1 2 2

    3 A D 3 1 2 2

    3 A D 4 1 2 2

    3 A D 6 1 2 2

    800 3 A D 1 1 2 3 3 A D 3 1 2 3

    3 A D 4 1 2 3

    3 A D 6 1 2 3

    15.5 kV50/60 Hz

    Ur Up Ud Isc Ir

    kV kV kV kA A15.5 110 50 12.5 400 3 A D 1 2 2 1

    3 A D 3 2 2 1

    3 A D 4 2 2 1

    3 A D 6 2 2 1

    630 3 A D 1 2 2 2

    3 A D 3 2 2 2

    3 A D 4 2 2 2

    3 A D 6 2 2 2

    800 3 A D 1 2 2 3

    3 A D 3 2 2 3 3 A D 4 2 2 3

    3 A D 6 2 2 3

    16 630 3 A D 1 2 3 2

    3 A D 3 2 3 2

    3 A D 4 2 3 2

    3 A D 6 2 3 2

    Seepag

    e20

    Seepag

    e20

    Seepag

    e21

    Seepag

    e21

    Seepag

    e22

    Seepag

    e22

    Seepag

    e22

    Seepag

    e23

    Seepag

    e23

    Seepag

    e24

    Ratedvoltage

    Ratedlightningimpulse

    withstandvoltage

    Ratedshort-duration

    power-frequency

    withstandvoltage

    Ratedshort-circuit

    breakingcurrent

    Ratedn

    ormalcurrent

    Single-p

    hase

    Three-p

    hase

    3xsing

    le-phase/

    single-triple

    Three-p

    hasefor

    loopautomation

    Siemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    18/36

    2

    Product SelectionSelection of primary ratings

    Siemens Vacuum Recloser 3AD

    27 kV Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes50/60 Hz OrderNo.: 3 A D

    Type

    Ur Up Ud Isc Ir

    kV kV kV kA A

    27 125 60 12.5 400 3 A D 1 3 2 1

    3 A D 3 3 2 1

    3 A D 4 3 2 1

    3 A D 6 3 2 1

    630 3 A D 1 3 2 2 3 A D 3 3 2 2

    3 A D 4 3 2 2

    3 A D 6 3 2 2

    800 3 A D 1 3 2 3

    3 A D 3 3 2 3

    3 A D 4 3 2 3

    3 A D 6 3 2 3

    150 60 12.5 400 3 A D On request

    3 A D On request

    3 A D On request 3 A D On request

    630 3 A D On request

    3 A D On request

    3 A D On request

    3 A D On request

    800 3 A D On request

    3 A D On request

    3 A D On request

    3 A D On request

    16 630 3 A D On request 3 A D On request

    3 A D On request

    3 A D On request

    800 3 A D On request

    3 A D On request

    3 A D On request

    Seepag

    e20

    Seepag

    e20

    Seepag

    e21

    Seepag

    e21

    Seepag

    e22

    Seepag

    e22

    Seepag

    e22

    Seepag

    e23

    Seepag

    e23

    Seepag

    e24

    Ratedvoltage

    Ratedlightningimpulse

    withstandvoltage

    Ratedshort-duration

    power-frequency

    withstandvoltage

    Ratedshort-circuit

    breakin

    gcurrent

    Ratedn

    ormalcurrent

    Single-p

    hase

    Three-p

    hase

    3xsing

    le-phase/

    single-triple

    Three-p

    hasefor

    loopau

    tomation

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    19/36

    2

    Produt SelectionSelection of primaryratings

    Siemens Vacuum Recloser 3AD

    38 kV Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes50/60 Hz OrderNo.: 3 A D

    Type

    Ur Up Ud Isc Ir

    kV kV kV kA A

    38 170 70 12.5 630 3 A D On request

    3 A D On request

    3 A D On request

    3 A D On request

    800 3 A D On request 3 A D On request

    3 A D On request

    3 A D On request

    16 630 3 A D On request

    3 A D On request

    3 A D On request

    3 A D On request

    800 3 A D On request

    3 A D On request

    3 A D On request 3 A D On request

    Seepag

    e20

    Seepag

    e20

    Seepag

    e21

    Seepag

    e21

    Seepag

    e22

    Seepag

    e22

    Seepag

    e22

    Seepag

    e23

    Seepag

    e23

    Seepag

    e24

    Ratedvoltage

    Ratedlightningimpulse

    withsta

    ndvoltage

    Ratedshort-duration

    power-frequency

    withsta

    ndvoltage

    Ratedshort-circuit

    breakin

    gcurrent

    Ratedn

    ormalcurrent

    Single-p

    hase

    Three-p

    hase

    3xsing

    le-phase/

    single-triple

    Three-p

    hasefor

    loopau

    tomation

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    20/36

    2

    8th position Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes

    Recloser configuration Order No.: 3 A D

    Recloser for pole mounting1)

    incl.cubicle, controller and control cable 1Recloser for substationapplication incl.cubicle and controller 2

    Switchunit only (w/o cubicle, controller andcontrol cable) 2) 3 Y 0 0 0 Y Y

    1) Pole mountingaccording tolistof accessories

    2) Thisoption isonlypossible inthe stated order number

    9th

    positionCurrent and voltage measuring

    Current transformers Voltage sensors

    1 integrated CTperpole

    1 integratedsensorperpole

    (includingsensor cables)

    3 x external VTs(to bedefined as

    accessories)

    A

    B

    1)

    1)

    1) C

    1) Necessary forrecloser type: Three-phase forloop automation

    Options

    Seepage21

    Seepage21

    Seepage22

    Seepage22

    Seepage22

    Seepage23

    Seepage23

    Seepage24

    Product SelectionSelection of controller

    Siemens Vacuum Recloser 3AD

    d l iSi V R l 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    21/36

    2

    10th position Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes

    Controller size Order No.: 3 A D

    E10 E12 12 8 16 13 23 33 43 14 22 30

    For 3-phase and single-phase applications

    A

    B

    C

    D E

    For loop automation

    F

    Without controller (refers to switch unitonly) Y

    11th position

    Auxiliary voltage

    Without auxiliary voltage supply(need for switchunit only) 0

    48 V On request

    60 V On request

    110 V 3

    220 V 4

    110/120 V 5

    220/240 V 6

    With auxiliary transformerand rated voltage as below:

    Rated voltage 11 kV 9 With ordercode T 3 A

    Rated voltage 12 kV 9 With ordercode T 3 B

    Rated voltage 13.8 kV 9 With ordercode T 3 C

    Rated voltage 15 kV 9 With ordercode T 3 D

    Seepa

    ge22

    Seepa

    ge22

    Seepa

    ge22

    Seepa

    ge23

    Seepa

    ge23

    Seepa

    ge24

    Product SelectionSelection of controller

    Siemens Vacuum Recloser 3AD

    DC voltage AC voltage

    Controllersize

    Functionkeys

    Numberof

    tri-colorLEDs

    Numberof

    binaryinputs

    (partlyforcustomeruse)

    Numberof

    binaryoutputs

    (partlyforcustomeruse)

    P d t S l ti Si s V c R cl s 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    22/36

    2

    Product SelectionSelection of controller

    Siemens Vacuum Recloser 3AD

    12th position Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes

    Control and sensor cables Order No.: 3 A D

    Without (need forswitch unit only) 0

    Cable length6 m 1

    Cable with special length(to be specified in clear text) 9 M 1 Y

    13th position

    Communication protocols

    Without communication protocol (needfor switch unitonly) 0

    IEC 60870-5-103 and Modbus RTU 1

    DNP3.0 2

    14th positionCommunication interfaces

    A B

    C

    D

    E

    Without communication interface (needforswitch unitonly) Y

    Seepage23

    Seepage23

    Seepage24

    Options(also comprisessensor cablesfor external voltage sensors if selected)

    Options

    1xUSB(front)

    1xRS485(rear)

    2xRS485(rear)

    1xRS232(rear)

    1xIRIG-B

    2xoptical

    STplug(singlemode)

    STplug(multiplemode)

    Product SelectionSiemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    23/36

    2

    15th position Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes

    Function packages Order No.: 3 A D

    Standardprotection and monitoringfunctions A

    Standardprotection and monitoringfunctionsplussynchro-check and fault locator C

    Standardprotection and monitoringfunctionsfor loop automation D

    Standardprotection and monitoringfunctionsfor loop automationwith synchro-check and fault locator E

    Standardprotection and monitoringfunctionsforsingle-triple application F

    Standardprotection and monitoringfunctionsforsingle-triple application with synchro-check and fault locator G

    Without protection functions(need for switch unitonly) Y

    16th position

    Languages and power socket

    English UK 1

    American English USA 2

    Spanish Mexico 3

    Portuguese Brazil 4

    Other languages on request 9 R 1 Y

    S

    eepage24

    Language of operating Standard of power socketinstructions and nameplate

    Options

    Product SelectionSelection of controller

    Siemens Vacuum Recloser 3AD

    Product Selection Siemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    24/36

    2

    Selection of additional equipment Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes

    Order No.: 3 A D

    Ambient temperature down to 40C Z A 3 8

    Seaworthypacking inside Germany Z F 0 2

    Stainlesssteelfor tank,control cubicle Z T 0 1

    Radio modem power supply 12 V DC Z T 0 2

    Serial to Ethernet converter Z T 0 3

    Pole mounting frame with bracket forsurge arrester(source and load side) Z T 2 1

    Polemounting frame Siemensdesign(with bracket for surge arresters, source andload side) Z T 2 2

    Further non-listed special versions (onlyafterconsultation with

    yourresponsible salespartner). Information additionally in clear text Z Y 9 9

    Configuration example

    Siemens vacuum recloser 3AD 3 A D

    Ratedvoltage Ur =27kV

    Ratedlightning impulse withstand voltage Up = 125kV

    Options

    Product SelectionSelection of additional equipment

    Siemens Vacuum Recloser 3AD

    Product SelectionSiemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    25/36

    2

    Accessories and spare parts

    A wide range of spare parts and accessories is available.

    Please contact your responsible sales partner and the order

    processing department in our Switchgear Factory in Berlin.

    Product SelectionAccessories and spare parts

    Siemens Vacuum Recloser 3AD

    Note:

    For any request regarding spare parts,

    subsequent deliveries, etc. the followingdetails are necessary:

    Type designation

    SerialNo.

    Design code

    Year of manufacture

    Data on the nameplate

    Siemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    26/36

    Technical DataSiemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    27/36

    3

    Switch unit driver - discarge switch for the capacitor

    Contents Page

    Technical Data

    Electrical data, dimensions and weights:Voltage level 12 kV

    Voltage level 15.5 kV

    Voltage level 27 kV

    Voltage level 38 kV

    27

    28

    28

    29

    29

    Contents

    R-H

    G11-

    314.t

    if

    Technical Data Siemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    28/36

    3

    Electrical data, dimensions and weights

    12 kV50/60 Hz

    Ir tk Isc Ima Up Ud

    A s kA kA kV kV mV mm mm mm kg A A

    3AD 122 630 3 12.5 31.5 75 42 24 810 312 287 142 2 10

    3AD 123 800 3 12.5 31.5 75 42 24 810 312 287 142 2 10

    15.5 kV50/60 Hz Ir tk Isc Ima Up Ud

    A s kA kA kV kV mV mm mm mm kg A A

    3AD 221 400 3 12.5 31.5 110 50 24 810 312 287 142 2 10

    3AD 222 630 3 12.5 31.5 110 50 24 810 312 287 142 2 10

    3AD 223 800 3 12.5 31.5 110 50 24 810 312 287 142 2 10

    3AD 232 630 3 16 40 110 50 24 810 312 287 142 2 10

    3AD 233 800 3 16 40 110 50 24 810 312 287 142 2 10

    Ratednormalcurrent

    Ratedoperating

    sequence:O-0.2s-CO-

    2s-CO-2s-CO

    (-30s-CO)-Lock-out

    Rateddurationo

    fshort-circuit

    Ratedshort-circu

    itbreakingcurrent

    Ratedshort-circu

    itmakingcurrent

    Ratedlightningimpulsewithstandvoltage

    Ratedshort-dura

    tion

    power-frequencywithstandvoltage

    VoltagedropU

    betweenconnections

    Creepagedistance,phase-to-earth

    Clearance,

    phase-to-phase

    Minimum

    clearance,

    phase-to-earth

    Weight

    Linechargingcu

    rrent

    Cablechargingc

    urrent

    Order No.

    Technical DataSiemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    29/36

    3

    27 kV50/60 Hz

    Ir tk Isc Ima Up Ud

    A s kA kA kV kV mV mm mm mm kg A A

    3AD 321 400 3 12.5 31.5 125 60 24 810 312 287 142 5 25

    3AD 322 630 3 12.5 31.5 125 60 24 810 312 287 142 5 25

    3AD 323 800 3 12.5 31.5 125 60 24 810 312 287 142 5 25

    3AD ... 400 3 12.5 31.5 150 60 On request 5 25

    3AD 630 3 12.5 31.5 150 60 On request 5 25

    3AD 800 3 12.5 31.5 150 60 On request 5 25

    3AD 630 3 16 40 150 60 On request 5 25

    3AD 800 3 16 40 150 60 On request 5 25

    38 kV50/60 Hz Ir tk Isc Ima Up Ud

    A s kA kA kV kV mV mm mm mm kg A A

    3AD 630 3 12.5 31.5 170 70 On request 5 40

    3AD 800 3 12.5 31.5 170 70 On request 5 40

    3AD 630 3 16 40 170 70 On request 5 40

    3AD 800 3 16 40 170 70 On request 5 40

    Electrical data, dimensions and weights

    Ratednormalcurrent

    Ratedoperating

    sequence:O-0.2s-CO-

    2s-CO-2s-CO

    (-30s-CO)-Lock-out

    Rateddurationo

    fshort-circuit

    Ratedshort-circu

    itbreakingcurrent

    Ratedshort-circu

    itmakingcurrent

    Ratedlightningimpulsewithstandvoltage

    Ratedshort-dura

    tion

    power-frequencywithstandvoltage

    VoltagedropU

    betweenconnections

    Creepagedistance,phase-to-earth

    Clearance,

    phase-to-phase

    Minimum

    cleara

    nce,

    phase-to-earth

    Weight

    Linechargingcu

    rrent

    Cablechargingc

    urrent

    Order No.

    Technical DataDi i d i

    Siemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    30/36

    3

    Mabild 1

    Mabild 2

    Dimension drawings

    Dimensions of control cubicle

    Dimension drawings

    Dimensions of switch unit

    Technical DataDimension drawings

    Siemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    31/36

    3

    Dimension drawings

    Mabild 2

    Dimension drawings

    Siemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    32/36

    AnnexContents

    Siemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    33/36

    4

    Contents Page

    Annex

    Inquiry form

    Configuration instructions

    Configuration aid

    33

    34

    35

    Contents

    Foldout page

    Switchgear Factory in Berlin, Germany

    R-

    HG11-1

    80.e

    ps

    AnnexInquiry form

    Siemens Vacuum Recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    34/36

    4

    Inquiry form

    Inquiry concerning

    Siemens vacuum

    recloser 3AD

    Please

    Submit an offer Call us Visit us

    Your address

    Company

    Dept.

    Name

    Street

    Postal code/city

    Phone

    Fax

    E-mail

    Siemens AG

    Technical dataOthervalues

    Rated voltage 12kV

    27kV

    15.5 kV

    38kV _ _ _ kV

    Rated lightning impulse

    withstand voltage

    75kV

    150 kV

    110 kV

    170 kV

    125 kV

    _ _ _ kV

    Rated short-duration

    power-frequency

    withstand voltage

    42kV

    60kV

    50kV

    70kV _ _ _ kV

    Rated short-circuit

    breaking current

    12.5 kA 16kA _ _ _ kA

    Ratednormal current 400 A 630 A 800 A _ _ _ A

    Secondary equipment

    For possible combinations see pages 20 to 23

    Recloser configuration Recloser for

    pole mounting

    Without control

    cubicle

    Made of

    stainless steel

    Others

    Applicationin

    substation

    Current and voltage sensing Integrated current

    transformers

    Integrated voltage

    sensors

    External voltage

    transformers

    Controller equipment 4 binaryinputs

    34 binary inputs

    9 binaryoutputs

    _ _ _

    14 binary inputs

    17 binary outputs

    24 binaryinputs

    25 binaryoutputs

    Auxiliary voltage _ _ _ V DC _ _ _ V AC, _ _ _ Hz

    Control and sensorcable Without 6 m _ _ _ m

    Communication interfaces USB

    Optical

    RS485

    IRIG-B

    RS232

    Function packages additional

    to standard functions

    Synchronizing and

    synchro-check

    Loop automation

    Fault locating

    Single-triple

    Please copy, fill in and return to yourSiemens partner

    You prefer to configure your Siemens vacuum recloser 3AD on your own?Please follow the steps for configuration and enter the order number in the configuration aid.Alternatively you can also use your prompted online configurator under www.siemens.com/energy

    For configuration of yourSiemens vacuum recloser 3AD

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    35/36

    Instruction for configuration of the Siemens vacuum recloser 3AD

    1st step: Definition of the primary part (see pages 17 to 19)

    Please specify the following ratings: Possible options:

    Rated voltage (Ur) Ur: 12kVto38kV

    Rated lightningimpulsewithstand voltage(Up) Up: 75kVto170kV

    Rated short-duration power-frequency withstandvoltage(Ud) Ud: 42kVto70kV

    Rated short-circuit breakingcurrent(Isc) Isc: 12.5kAand16kA

    Rated normal current (Ir) Ir: 400Ato800A

    Theseratingsdefinethe positions4 to7 oftheordernumber.

    2nd step: Definition of the secondary equipment (see pages 20 to 23)

    Pleasespeci fythefollowingequipmentfeatures: Possibleoptions:

    Recloser configuration(position8)

    Recloserincl. controlcubicleand cables, recloser without controlcubicleandcables,recloserfor transformer substation, retrofitrecloser

    Sensors

    (position9)

    Integratedcurrenttransformers,integratedvoltagetransformers,

    external voltage transformersController(position10)

    Housingsize, numberof functionkeys andthree-color LEDs,number of available binary inputs andoutputs

    Auxiliary voltage(position11)

    Voltagesfrom48V DCto 240V AC

    Cable length ofcontroland sensor cable(position12)

    Standardlength6 m, special lengths possible

    Communicationprotocol(position13)

    IEC60870-5-103and Modbus RTU,DNP 3.0

    Communicationinterfaces(position14)

    USB,RS485,RS232,IRIG-B,optical, STplug

    Functionsof thecontroller(position15)

    Standardprotection and monitoringfunctions,synchronizingand synchro-check,fault location

    Languageof operatinginstructionsand nameplate(position16)

    English,AmericanEnglish,Spanish andPortuguese

    Theseequipment featuresdefine thepositions 8 to16 of theorder number.

    3rd step: Do you have any further requirements concerning the equipment? (Please refer to page 24)

    Should you still need more options than the possible special equipment like country-specific mains sockets,

    weather resistance down to 40 C, stainless-steel design, etc. please contact your responsible sales partner.

    1 2 3 4 5 6 7 8 9 10 11 12 1 3 14 15 16

    Z

    3 A D

    + + + +

    + + + +

    3 A D

    + + + +

    + + + +

    3 A D

    + + + +

    + + + +

    3 A D

    + + + +

    + + + +

    3 A D

    + + + +

    + + + +

    3 A D

    + + + +

    + + + +

    3 A D

    + + + +

    + + + +

    3 A D

    + + + +

    + + + +

    3 A D

    + + + +

    + + + +

    35SiemensHG 11.42 2008

    See

    page

    20

    See

    page

    20

    See

    page

    21

    See

    page

    21

    See

    page

    22

    See

    page

    22

    See

    page

    22

    See

    page

    23

    See

    page

    23

    See

    page

    24

    See

    page

    17

    to

    See

    page

    19

  • 8/10/2019 Catalogue Vacuum Recloser 3ad En

    36/36

    For questions concerning Power

    Transmission and Distribution:

    You can c ontact ou r Custom er Suppor t

    Center 24 hours a day, 365 days a year.

    Tel.: +49 180/524 70 00

    Fax: +49 180/524 24 71

    (Charges depending on provider)

    E-Mail: [email protected]

    www.siemens.com/energy-support

    Siemens AG

    Energy Sector

    Medium Voltage Division

    Nonnendammallee 104

    13623 Berlin

    Germany

    www.siemens.com/energy

    Subject to change without notice

    Order No.E50001-K1511-A421-A1-7600

    Printed in Germany

    Dispo 31601

    KG 03.08 1.0 36 En

    103063 6101/6519

    The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases.

    The required features should therefore be specified in each individual case at the time of closing the contract.

    R-

    HG11-

    182

    .tif

    If not stated otherwise on the individual pages of this catalog,

    we reserve the right to include modifications, especially regarding

    the stated values, dimensions and weights.

    Drawings are not binding. All product designations used are

    trademarks or product names of Siemens AG or other suppliers.

    If not stated otherwise, all dimensions in this catalog are given

    in mm.

    Responsible for

    Technical contents: General editin g:Siemens AG, Dept. PTD M C PPM Siemens AG, Dept. PTD CC MBerlin Erlangen