Power Transmission and Distribution Medium-Voltage Switchgear Catalog HA 35.41 · 2007

CATALOGO NX PLUS C.pdf

Embed Size (px)

Citation preview

  • Power Transmission and Distribution

    ! "#$#%Medium-Voltage Switchgear

    Catalog HA 35.41 2007

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 20072

    R-HA

    35-1

    05a

    eps

    #Types

    Siemens AG 2007

    Page

    Fixed-mounted circuit-breaker switchgearNXPLUS C is a factory-assembled, type-tested,metal-enclosed, metal-clad,SF6-insulated switchgearfor single-busbar anddouble-busbar applicationsfor indoor installation.

    Circuit-breaker panel (example)

    &%

    The products and systems described in this catalogare manufactured and sold according to a certifiedquality and environmental management system(acc. to ISO 9001 and ISO 14001).(DQS Certificate Reg. No. DQS 003473 QM UM).The certificate is accepted in all IQNet countries.

    Application

    Types, typical uses,ratings 2 to 4

    Requirements

    Features, safety, technology 4 and 5

    Technical Data

    Electrical data 6 and 7Room planning 8Shipping data, classification 9

    Dimensions

    Front views, sections,floor openings, fixing points 10 to 17

    Product Range

    Single-busbar panels 18 to 20Double-busbar panels 21

    Design

    Basic panel design 22

    Components

    Vacuum circuit-breaker 23 and 24Three-position switch 25 and 26HV HRC fuse assembly 27 and 28Vacuum contactor, motor protection 29Busbars 30Current and voltage transformers 31 to 33Panel connection 34 to 39Indicating and measuring equipment 40 to 43

    Standards

    Standards, specifications, guidelines 44 and 45

    Notes

    46

    Invalid: Catalog HA 35.41 2005

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 3

    R-HA

    35-1

    07.e

    ps

    R-HA

    35-1

    06.e

    ps

    R-HA35-109.eps

    R-HA

    35-1

    23.e

    ps

    Application:Public power supply system

    NXPLUS C switchgear20 kV (example)

    Application:Industry

    Application:Industry and offshore

    R-HA

    35-1

    22.ti

    fTypical uses

    &%

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 20074

    Environmental independence

    Hermetically tight, weldedswitchgear vessels made ofstainless steel make NXPLUS Cswitchgear

    Insensitive to aggressiveambient conditions, such as

    Salt water Air humidity Dust Temperature

    Tight to ingress of foreignbodies, such as

    Dust Pollution Small animals

    Independent of site altitude

    Compact design

    Thanks to the SF6 insulation,compact dimensions arepossible

    Thus,

    Existing switchgear roomscan be used effectively

    New constructions cost little

    Costly city-area space is saved

    Maintenance-free design

    Switchgear vessels designedas sealed pressure systems,maintenance-free switchingdevices and enclosed cableplugs ensure

    Maximized power supplyreliability

    Personnel safety

    Sealed-for-life design accord-ing to IEC 62 271-200 (sealedpressure system)

    Installation, operation, exten-sion and replacement with-out SF6 gas work

    Reduced operating costs

    Cost-efficient investment

    No maintenance cycles

    Innovations

    The use of digital second-ary systems and com-bined protection andcontrol devices ensures

    Clear integration in proc-ess control systems

    Flexible and highly sim-plified adaptation to newsystem conditions andthus to cost-efficientoperation

    Fixed-mounted circuit-breaker switchgearNXPLUS C is used in transformerand switching substations, e.g., in:

    Power supply companies Power stations Cement industry Automobile industry Iron and steel works Rolling mills Mining industry Textile, paper and food industries Chemical industry Petroleum industry Pipeline installations Offshore installations Electrochemical plants Petrochemical plants Shipbuilding industry Diesel power plants Emergency power supply installations Lignite open-cast mines Traction power supply systems

    1) 42 kV/75 kV according to somenational requirements

    2) 1200 mm for rated normalfeeder currents of 2000 A,2300 A and 2500 A

    Electrical data (maximum values) and dimensions

    Rated voltage kV 7.2 12 15 17.5 24

    Rated frequency Hz 50/60 50/60 50/60 50/60 50/60

    Rated short-duration power-frequency withstand voltage

    kV 20 28 1) 36 38 50

    Rated lightning impulsewithstand voltage

    kV 60 75 1) 95 95 125

    Rated peak withstand current kA 80 80 80 63 63

    Rated short-circuit makingcurrent

    kA 80 80 80 63 63

    Rated short-timewithstand current 3 s

    kA 31.5 31.5 31.5 25 25

    Rated short-circuit breakingcurrent

    kA 31.5 31.5 31.5 25 25

    Rated normal current of busbar A 2500 2500 2500 2500 2500

    Rated normal current offeeders

    A 2500 2500 2500 2000 2000

    Width mm 600 2) 600 2) 600 2) 600 2) 600 2)

    Depth without pressurerelief duct at the rear

    with pressurerelief duct at the rear

    mm

    mm

    1100

    1225

    1100

    1225

    1100

    1225

    1100

    1225

    1100

    1225

    Height mm 2250 2250 2250 2250 2250

    Typical uses, ratings Features

    &% '()#

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 5

    Personal safety

    Safe-to-touch and hermetical-ly sealed primary enclosure

    Cable terminations, busbarsand voltage transformers aresurrounded by earthed layers

    All high-voltage parts includ-ing the cable terminations,busbars and voltage trans-formers are metal enclosed

    Capacitive voltage detectingsystem to verify safe isolationfrom supply

    Operating mechanisms andauxiliary switches safely ac-cessible outside the primaryenclosure (switchgear vessel)

    Due to the system design,operation is only possiblewith closed switchgear enclo-sure

    Standard degree of protec-tion IP 65 for all high-voltageparts of the primary circuit,IP 3XD for the switchgearenclosure according toIEC 60 529 and VDE 0470-1

    High resistance to internalarcs by logical mechanicalinterlocks and testedswitchgear enclosure

    Panels tested for resistance tointernal faults up to 31.5 kA

    Logical mechanical interlocksprevent maloperation

    Make-proof earthing bymeans of the vacuum circuit-breaker

    Security of operation

    Hermetically sealed primaryenclosure independent ofenvironmental effects (pollu-tion, humidity and smallanimals)

    Maintenance-free inan indoor environment(IEC 62 271-1 andVDE 0671-1)

    Operating mechanisms ofswitching devices accessibleoutside the primary enclo-sure (switchgear vessel)

    Metal-coated, plug-in induc-tive voltage transformersmounted outside the SF6switchgear vessel

    Current transformers asring-core current transfor-mers mounted outside theSF6 switchgear vessel

    Complete logical mechanicalinterlocking system

    Welded switchgear vessels,sealed for life

    Minimum fire load

    Type and routine-tested

    Standardized, NC productionprocesses

    Quality assurance in accord-ance with DIN EN ISO 9001

    More than 500,000switchgear panels of Siemensin operation worldwide formany years

    Option: Aseismic design

    Reliability

    Type and routine-tested

    Standardized, NC productionprocesses

    Quality assurance in accord-ance with DIN EN ISO 9001

    More than 500,000switchgear panels of Siemensin operation worldwide formany years

    General

    Three-pole enclosure of theprimary part consisting of aswitchgear vessel made ofstainless steel

    Insulating gas SF6 Three-position switch as

    busbar disconnector andfeeder earthing switch

    Make-proof earthing bymeans of the vacuum circuit-breaker

    Compact dimensions due toSF6 insulation

    Hermetically tight, weldedswitchgear vessel made ofstainless steel

    Single-pole, solid-insulated,screened busbars, plug-intype

    Cable connection with out-side-cone plug-in system, orfor connection of solid-insu-lated bars

    Wall-standing or free-stand-ing arrangement

    Cable connection access fromfront

    Option: Cable connectionaccess from rear (only circuit-breaker panel 1250 A)

    Installation and extension ofexisting switchgear on bothsides without gas work andwithout modification of exist-ing panels

    Interlocks

    According to IEC 62 271-200and VDE 0671-200

    Logical mechanical interlocksprevent maloperation

    Three-position disconnectorcan only be operated with cir-cuit-breaker in OPEN position

    Circuit-breaker or contactorcan only be operated withthree-position switch in endposition and operating leverremoved

    Switch-disconnector, contac-tor, ring-main and meteringpanels are not interlockeddue to their own switchingcapacity

    Three-position disconnectorinterlocked against the cir-cuit-breaker in circuit-breakerpanels and in bus sectionali-zers with one panel width

    Locking device for feeder

    Locking device for three-position switch

    Cable compartment cover(access to HV HRC fuses)always interlocked againstthe three-position switch-disconnector in panels withHV HRC fuses (switch-discon-nector panel, metering paneland contactor panel withfuses)

    Option: Cable compartmentcover interlocked against thethree-position switch (circuit-breaker panel, disconnectorpanel, contactor panel with-out fuses, ring-main panel)

    Option: Electromagneticinterlocks

    Option: Actuating openingscan be locked with padlocks

    Option: Locking device forfeeder earthed

    Modular design

    Panel replacement possiblewithout SF6 gas work

    Low-voltage compartmentcan be removed, plug-in buswires

    Transformers

    Current transformers notsubjected to dielectric stress

    Easy replacement of ring-corecurrent transformers

    Metal-coated, plug-in anddisconnectable voltage trans-formers

    Vacuum circuit-breaker

    Maintenance-free undernormal ambient conditionsaccording to IEC 62 271-1and VDE 0671-1

    No relubrication or readjust-ment

    Up to 10,000 operatingcycles

    Vacuum-tight for life

    Secondary systems

    Numerical protection,measuring and controlequipment

    Option: Customary multi-function protection relay withintegrated protection, con-trol, communication, operat-ing and monitoring functions

    Can be integrated in processcontrol systems

    Safety Technology

    '()#

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 20076

    Commonelectrical data,filling pressureandtemperature

    Rated insulation level Rated voltage Ur kV 7.2 12 15 17.5 24Rated short-duration power-freq. withstand voltage Ud: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV

    2023

    28 1)32 1)

    3639

    3845

    5060

    Rated lightning impulse withstand voltage Up: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV

    6070

    75 1)85 1)

    95110

    95110

    125145

    Rated frequency fr 50/60 HzRated normal current Ir 2) for the busbar up to A 2500 2500 2500 2500 2500Rated filling level pre 3) 150 kPa (absolute) at 20 CMinimum functional level pme 3) 130 kPa (absolute) at 20 CAmbient air temperature 5 C to +55 C

    Panel dataCircuit-breakerpanel630 A

    Rated normal current Ir 2) A 630 630 630 630 630Rated short-timewithstand current Ik

    for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20 25for switchgear with tk = 3 s up to kA 20 20 20 20 20

    Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50 63Rated short-circuit making current Ima up to kA 50 63 50 63 50 63 50 63 50 63Rated short-circuit breaking current Isc up to kA 20 25 20 25 20 25 20 25 20 25

    Electrical endurance ofvacuum circuit-breakers

    at rated normal current 10,000 operating cyclesat rated short-circuit breaking current 50 breaking operations

    Circuit-breakerpanel and bussectionalizer1000 A 4)1250 A 5)2000 A2300 A2500 A

    Rated normal current Ir 2) AAAAA

    10001250200023002500

    10001250200023002500

    10001250200023002500

    100012502000

    100012502000

    Rated short-timewithstand current Ik

    for switchgear with tk = 1 s up to kA 31.5 31.5 31.5 25 25for switchgear with tk = 3 s up to kA 31.5 31.5 31.5 25 25

    Rated peak withstand current Ip up to kA 80 80 80 63 63Rated short-circuit making current Ima up to kA 80 80 80 63 63Rated short-circuit breaking current Isc up to kA 31.5 31.5 31.5 25 25

    Electrical endurance ofvacuum circuit-breakers

    at rated normal current 10,000 operating cyclesat rated short-circuit breaking current 50 breaking operations

    Switch-disconnectorpanel(with HV HRCfuses)

    Rated normal current Ir 2) for feeder 6) A 200 200 200 200 200Rated short-timewithstand current Ik

    for switchgear with tk = 1 s up to kA 31.5 31.5 31.5 25 25for switchgear with tk = 3 s up to kA 31.5 31.5 31.5 25 25

    Rated peak withstand current Ip 6) up to kA 80 80 80 63 63Rated short-circuit making current Ima 6) up to kA 80 80 80 63 63Dimension e of HV HRC fuse links mm 292 7) 292 7) 442 442 442

    Ring-mainpanel(switch-disconnectorpanel withoutHV HRC fuses)

    Rated normal current Ir 2) for feeder A 630 630 630 630 630Rated short-timewithstand current Ik

    for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20for switchgear with tk = 3 s up to kA 20 20 20 20 20

    Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50Rated short-circuit making current Ima up to kA 50 63 50 63 50 63 50 63 50

    Disconnectorpanel1000 A 4)1250 A2000 A2300 A2500 A

    Rated normal current Ir 2) AAAAA

    10001250200023002500

    10001250200023002500

    10001250200023002500

    100012502000

    100012502000

    Rated short-timewithstand current Ik

    for switchgear with tk = 1 s up to kA 31.5 31.5 31.5 25 25for switchgear with tk = 3 s up to kA 31.5 31.5 31.5 25 25

    Rated peak withstand current Ip up to kA 80 80 80 63 63

    Contactorpanel(with HV HRCfuses)

    Rated normal current Ir 2) for feeder 6) A 450 450 450 450 450Rated short-timewithstand current Ik

    for switchgear with tk = 1 s up to kA 31.5 8) 31.5 8) 31.5 8) 25 8) 25 8)

    for switchgear with tk = 3 s up to kA 31.5 8) 31.5 8) 31.5 8) 25 8) 25 8)

    Rated peak withstand current Ip 6) up to kA 80 80 80 63 63Rated short-circuit making current Ima 6) up to kA 80 80 80 63 63Electrical endurance at rated normal current 100,000 or 500,000 operating cyclesDimension e of HV HRC fuse links mm 292 7) 292 7) 442 442 442

    Metering panel(with HV HRCfuses)

    Rated short-timewithstand current Ik

    for switchgear with tk = 1 s up to kA 31.5 31.5 31.5 25 25for switchgear with tk = 3 s up to kA 31.5 31.5 31.5 25 25

    Rated peak withstand current Ip 6) up to kA 80 80 80 63 63Dimension e of HV HRC fuse links mm 292 7) 292 7) 442 442 442

    Electrical data, filling pressure, temperature for single-busbar switchgear

    % *

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 7

    Footnotes for pages 6 and 7

    1) Higher values of the rated short-duration power-frequencywithstand voltage available with: 42 kV for phase-to-phase,

    phase-to-earth, open contactgap as well as

    48 kV across the isolatingdistance

    Higher values of the rated lightningimpulse withstand voltage: 95 kV for phase-to-phase, phase-to-

    earth, open contact gap as well as 110 kV across the isolating distance

    2) The rated normal currents applyto ambient air temperatures ofmax. 40 C. The 24-hour meanvalue is max. 35 C(acc. to IEC 62 271-1/ VDE 0671-1)2300 A with natural ventilation2500 A with forced ventilation

    3) Pressure values for SF6 insulatedswitchgear vessels

    4) Bus sectionalizer panel 1000 A anddisconnector panel 1000 A only possiblewith rated short-time withstand current Ik25 kA, 1 s and 3 s, rated peak with-stand current Ip 63 kA and rated short-circuit breaking current ISC 25 kA

    5) Bus sectionalizer panel 1250 A in2 panel widths only possible with ratedshort-time withstand current Ik 25 kA,1 s and 3 s, rated peak withstand current Ip63 kA and rated short-circuit breakingcurrent ISC 25 kA

    6) Depending on the HV HRC fuselink, observe max. permissible let-throughcurrent ID of HV HRC fuse links

    7) Extension tube (150 mm long)required additionally

    8) Applies to combination of vacuumcontactor with HV HRC fuses:Vacuum contactor without HV HRC fusereaches rated short-time withstandcurrent Ik 8 kA, 1 s, and rated peakwithstand current Ip 20 kA (applies tothe complete switchgear)

    9) Bus coupler 1250 A on request

    Commonelectrical data,filling pressureandtemperature

    Rated insulation level Rated voltage Ur kV 7.2 12 15 17.5 24Rated short-duration power-freq. withstand voltage Ud: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV

    2023

    28 1)32 1)

    3639

    3845

    5060

    Rated lightning impulse withstand voltage Up: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV

    6070

    75 1)85 1)

    95110

    95110

    125145

    Rated frequency fr 50/60 HzRated normal current Ir 2) for the busbar up to A 2500 2500 2500 2500 2500Rated filling level pre 3) 150 kPa (absolute) at 20 CMinimum functional level pme 3) 130 kPa (absolute) at 20 CAmbient air temperature 5 C to +55 C

    Panel dataCircuit-breakerpanel, buscoupler 9)1000 A

    Rated normal current Ir 2) A 1000 1000 1000 1000 1000Rated short-timewithstand current Ik

    for switchgear with tk = 1 s up to kA 25 25 25 25 25for switchgear with tk = 3 s up to kA 25 25 25 25 25

    Rated peak withstand current Ip up to kA 63 63 63 63 63Rated short-circuit making current Ima up to kA 63 63 63 63 63Rated short-circuit breaking current Isc up to kA 25 25 25 25 25

    Electrical endurance ofvacuum circuit-breakers

    at rated normal current 10,000 operating cyclesat rated short-circuit breaking current 50 breaking operations

    Incomingsectionalizer1250 A

    Rated normal current Ir 2) A 1250 1250 1250 1250 1250Rated short-timewithstand current Ik

    for switchgear with tk = 1 s up to kA 25 25 25 25 25for switchgear with tk = 3 s up to kA 25 25 25 25 25

    Rated peak withstand current Ip up to kA 63 63 63 63 63Rated short-circuit making current Ima up to kA 63 63 63 63 63Rated short-circuit breaking current Isc up to kA 25 25 25 25 25

    Electrical endurance ofvacuum circuit-breakers

    at rated normal current 10,000 operating cyclesat rated short-circuit breaking current 50 breaking operations

    Furtherpanel types

    The above-mentioned panel types can on request be combinedwith panel types of the single-busbar range.

    Electrical data, filling pressure, temperature for double-busbar switchgear

    % *

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 20078

    ** For panel replacement:

    Control aisle W 1400 mmnecessary

    *** Lateral wall distanceW 50 mm optionallypossible on the left or right

    Room planning for double-busbar switchgear Free-standing arrangement (top view)

    * 125-mm-deep pressure reliefduct at the rear

    ** Depending on national require-ments; for extension/panelreplacement:Control aisle 1400 mmrecommended

    *** Lateral wall distances:On the left or right W 500 mmrecommended

    **** For panel width, see dimensionson pages 10 to 17

    Room height 2800 mm

    Switchgear arrangement

    For single-busbar applica-tions:

    Wall-standing arrangementor

    Free-standing arrangement Face-to-face arrangement

    accordingly

    For double-busbar applica-tions:

    Back-to-back arrangement(free-standing arrangement)

    Room dimensions

    See opposite dimensiondrawings

    Door dimensions

    The door dimensions dependon the dimensions of theindividual panels (see pages10 to 17)

    Switchgear fastening

    For floor openings and fixingpoints of the switchgear,see pages 10 to 17

    Foundations: Steel structure Steel-reinforced concrete

    with foundation rails,welded or bolted on

    Panel dimensions

    See pages 10 to 17

    Weights

    Single-busbar panels

    Panels for 1250 A:Approx. 800 kg

    Panels for > 1250 A:Approx. 1400 kg

    Double-busbar panels

    Panels for 1250 A:Approx. 1600 kg

    Wall-standing arrangement (top view)Panels without pressure relief duct

    Room planning for single-busbar switchgear

    Wall-standing arrangement(same as left side), but panelswith pressure relief duct

    Free-standing arrangement (top view)Panels with pressure relief duct

    Room height 2800 mm

    Room height 2800 mm

    Room planning

    % *

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 9

    Transport

    NXPLUS C switchgear is deliver-ed in form of individual panels.

    The following must be noted:

    Transport facilities on site

    Transport dimensions andweights

    Size of door openings inbuilding

    In case of double-busbar panelsthe A and B sides are suppliedseparately.

    Packing

    Place of destination insideGermany or other Europeancountries

    Means of transport:Rail and truck

    Type of packing: Panels on open pallets Open packing with PE

    protective foil

    Place of destination overseas

    Means of transport:Ship

    Type of packing: Panels on open pallets In closed crates with sealed

    upper and lower PEprotective foil

    With desiccant bags With sealed wooden base Max. storage time: 6 months

    1) Average values depending onthe degree to which panels areequipped

    2) The loss of service continuity cate-gory is referred to the completeswitchgear, i.e. the panel with thelowest category determines theloss of service continuity categoryof the complete switchgear.

    Transport dimensions, transport weights 1)

    Panel width

    mm

    Transport dimensionsWidth x Height x Depth

    mm x mm x mm

    Transport weightwith packing without packing

    approx. kg approx. kg

    Single-busbar switchgearTransport inside Germany or to other European countries

    1 x 600 1100 x 2470 x 1450 900 800

    1 x 1200 1450 x 2470 x 1450 1500 1400

    1 x 600 (cable connection top rear) 1100 x 2470 x 2100 900 800

    Transport overseas

    1 x 600 1130 x 2650 x 1450 900 800

    1 x 1200 1480 x 2650 x 1450 1500 1400

    1 x 600 (cable connection top rear) 1130 x 2650 x 2100 900 800

    Double-busbar switchgearTransport inside Germany or to other European countries

    1 x 600 1100 x 2470 x 1450 900 800

    Transport overseas

    1 x 600 1130 x 2650 x 1450 900 800

    Classification of the NXPLUS C switchgear according to IEC 62 271-200

    Design and construction

    Partition class PM (metallic partition)

    Loss of service continuity category 2)

    Panels with HV HRC fuses without HV HRC fuses

    LSC 2ALSC 2B

    Accessibility to compartments (enclosure) Busbar compartment Switching-device compartment Low-voltage compartment Cable compartment

    without HV HRC fuses with HV HRC fuses

    Tool-basedNon-accessibleTool-based

    Tool-basedInterlock-controlled and tool-based

    Internal arc classification

    Designation of internal arc classification IACIAC for

    Wall-standing arrangement Free-standing arrangement

    7.2 kV, 12 kV, 15 kVIAC A FL 31.5 kA, 1 sIAC A FLR 31.5 kA, 1 s

    17.5 kV, 24 kVIAC A FL 25 kA, 1 sIAC A FLR 25 kA, 1 s

    Type of accessibility A

    F L R

    Switchgear in closed electrical service location,access for authorized personnel only (according to IEC 62 271-200)FrontLateralRear (for free-standing arrangement)

    Arc test current 25 kA, 31.5 kA

    Test duration 1 s

    Shipping data, classification

    % *

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 200710

    Front views, sections, floor openings, fixing points for single-busbar switchgear

    *)##

    Circuit-breaker panels

    630 A 1000 A 1250 A

    2000 A, 2300 Aand 2500 A

    Legend and footnotes forpages 10 and 11

    1 Floor opening forcontrol cables

    2 Option: Pressurerelief duct

    3 Mounting holefor M8 / M10

    4 Mounting holefor M8 / M10 (foraseismic version only)

    5 Floor opening forhigh-voltage cables

    6 Cable compartment /pressure relief duct

    1) 2650 mm for higherlow-voltage compartment

    2) 752 mm for deepercable compartment cover

    3) 45 mm for deepercable compartment cover

    4) 1120 mm for deepercable compartment cover

    5) When only one cable isconnected, the dimensionis reduced by 275 mm

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 11

    Front views, sections, floor openings, fixing points for single-busbar switchgear

    *)##

    Circuit-breaker panels (for top-rear cable connection)

    For legend and foot-notes, see page 10

    1250 A

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 200712

    Front views, sections, floor openings, fixing points for single-busbar switchgear

    *)##

    Disconnector panels

    1000 A 1250 A

    2000 A, 2300 Aand 2500 A

    Legend and footnotes forpages 12 and 13

    1 Floor opening forcontrol cables

    2 Option: Pressurerelief duct

    3 Mounting holefor M8 / M10

    4 Mounting holefor M8 / M10(for aseismic version only)

    5 Floor opening forhigh-voltage cables

    1) 2650 mm for higherlow-voltage compartment

    2) 752 mm for deepercable compartment cover

    3) 45 mm for deepercable compartment cover

    4) 1120 mm for deepercable compartment cover

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 13

    ( p )

    Front views, sections, floor openings, fixing points for single-busbar switchgear

    *)##

    Bus sectionalizers with disconnector

    on the left on the left and on the rightof the circuit-breaker

    1000 A 1250 A

    1 panel width 1 panel width

    1250 A

    2 panel widths

    2000 A, 2300 Aand 2500 A

    1 panel width

    For legend and foot-notes, see page 12

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 200714

    Front views, sections, floor openings, fixing points for single-busbar switchgear

    *)##

    Switch-disconnector panel with HV HRC fuses

    Ring-main panel(switch-disconnector panel without HV HRC fuses)

    Vacuum contactor panel with HV HRC fuses Metering panel

    For legend and foot-notes, see page 15

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 15

    Front views, sections, floor openings, fixing points for double-busbar switchgear

    *)##

    Circuit-breaker panels

    Legend and footnotesfor pages 14 and 15

    1 Floor opening forcontrol cables

    2 Option: Pressurerelief duct

    3 Mounting holefor M8 / M10

    4 Mounting holefor M8 / M10(for aseismic version only)

    5 Floor opening forhigh-voltage cables

    7 Option:HV HRC fuses

    1) 2650 mm for higherlow-voltage compartment

    2) 752 mm for deepercable compartment cover

    3) 45 mm for deepercable compartment cover

    4) 1120 mm for deepercable compartment cover

    6) 2390 mm for deepercable compartment cover

    1000 A

    Side A Side B Side B Side A

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 200716

    Incoming sectionalizer

    Side A Side B

    1250 A

    *)##Front views, sections, floor openings, fixing points for double-busbar switchgear

    Legend and footnotesfor pages 16 and 17

    1 Floor opening forcontrol cables

    2 Pressure relief duct

    3 Mounting holefor M8 / M10

    4 Mounting holefor M8 / M10(for aseismic version only)

    5 Floor opening forhigh-voltage cables

    1) 2650 mm for higherlow-voltage compartment

    2) 752 mm for deepercable compartment cover

    3) 45 mm for deepercable compartment cover

    4) 1120 mm for deepercable compartment cover

    6) 2390 mm for deepercable compartment cover

    Side B Side A

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 17

    Bus coupler

    1000 A

    Side A Side B

    *)##Front views, sections, floor openings, fixing points for double-busbar switchgear

    For legend and foot-notes, see page 16

    Side B Side A

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 200718

    Vacuumcircuit-breaker

    Three-positiondisconnector

    Capacitive voltagedetecting system

    Disconnectable andplug-in voltage trans-former

    Forced ventilationat 2500 A

    Busbar earthingswitch

    Plug-in voltagetransformer

    Current transformer

    Surge arresteror limiter

    Cable connection withoutside-cone plugs(not included in thescope of supply)

    Cable connection withoutside-cone plugs(not included in thescope of supply)

    HA35

    -254

    1bep

    s

    Single-busbar panels

    '

    Circuit-breaker panels

    1) Only for 1250 A

    2000 A, 2300 A and 2500 A630 A

    1250 A, top-rear cable connection1000 A and 1250 A

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 19

    Three-positiondisconnector

    Capacitive voltagedetecting system

    Disconnectable andplug-in voltage trans-former

    Forced ventilationat 2500 A

    Plug-in voltagetransformer

    Vacuumcircuit-breaker

    Current transformer

    Surge arresteror limiter

    Cable connection withoutside-cone plugs(not included in thescope of supply)

    Cable connection withoutside-cone plugs(not included in thescope of supply)

    HA35

    -254

    1bep

    s

    Single-busbar panels

    '

    Disconnector panels

    1000 A and 1250 A

    Bus sectionalizers

    1250 A, 2 panel widths

    1250 A, 1 panel width

    2000 A, 2300 A and 2500 A

    1) Only for 1250 A

    2000 A, 2300 A and 2500 A, 1 panel width

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 200720

    Plug-in voltagetransformer

    Vacuum contactor

    HV HRC fuses

    Three-positionswitch-disconnector

    Cable connection withoutside-cone plugs(not included in thescope of supply)

    Surge arresteror limiter

    Capacitive voltagedetecting system

    Disconnectable andplug-in voltage trans-former

    Current transformer

    2nd earthingswitch for fuses

    HA35

    -254

    1bep

    s

    Single-busbar panels

    '

    Switch-disconnector panel

    1) Only possible when vacuum contactor panelis designed without fuse

    Ring-main panel

    Vacuum contactor panel Metering panel

    2)

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 21

    Three-positiondisconnector

    Capacitive voltagedetecting system

    Disconnectable andplug-in voltage trans-former

    Plug-in voltagetransformer,mounted separately

    Current transformer

    Surge arresteror limiter

    Vacuumcircuit-breaker

    Cable connection withoutside-cone plugs(not included in thescope of supply)

    Panel bars

    Plug-in voltagetransformer

    HA35

    -254

    1bep

    s

    Double-busbar panels

    '

    Circuit-breaker panels Incoming sectionalizer

    Bus coupler

    1250 A

    1000 A

    1000 A

    Abbreviations

    SS1 = Busbar 1SS2 = Busbar 2

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 200722

    Insulating system

    Switchgear vessel filled with SF6 gas

    Features of SF6 gas: Non-toxic Odourless and colourless Non-inflammable Inert Heavier than air Electronegative (high-quality

    insulator)

    Pressure of SF6 gas in theswitchgear vessel (absolute values):

    Rated filling level: 150 kPa Design pressure: 180 kPa Design temperature

    of SF6-gas: 80 C Operating pressure of bursting

    disk: 300 kPa Bursting pressure: 550 kPa Gas leakage rate: < 0.1 % per year

    Panel design

    Factory-assembled, type-tested

    Metal-enclosed, metal-clad

    Hermetically tight, weldedswitchgear vessel made ofstainless steel

    Single-pole, solid-insulated,screened busbars, plug-in type

    Maintenance-free

    Degree of protection IP 65 for all high-voltage parts

    of the primary circuit IP 3XD for the switchgear enclosure

    Vacuum circuit-breaker orvacuum contactor

    Three-position disconnector fordisconnecting and earthing bymeans of the circuit-breaker

    Make-proof earthing by meansof the vacuum circuit-breaker

    Three-position switch-disconnector

    Cable connection withoutside-cone plug-in systemaccording to DIN EN 50 181

    Wall-standing or free-standingarrangement

    Installation and possible later exten-sion of existing panels without gaswork

    Replacement of switchgear vesselwithout gas work

    Replacement of instrument trans-formers without gas work, as theyare located outside the gascompartments

    Enclosure made of galvanized sheet-steel, front cover, rear cover and endwalls painted in colour light basic(SN 700)

    Low-voltage compartment remov-able, plug-in bus wires

    Circuit-breaker panel (example)

    Front view

    Detail Z:

    Sectional view (cable connection from the front)

    1 Low-voltagecompartment

    2 Multifunction protectionrelay SIPROTEC 4 (example)

    3 Position indicatorfor circuit-breaker

    4 Actuating opening forcharging the circuit-breaker springs

    5 ON pushbutton forcircuit-breaker

    6 Spring chargedindicator

    7 Operations counterfor circuit-breaker

    8 Position indicatorfor disconnectingfunction of three-positionswitch

    9 Ready-for-serviceindicator

    10 Position indicatorfor ready-to-earthfunction of three-position switch

    11 Control gate andlocking device fordisconnecting/earthingfunctions of three-position switch

    12 Interrogation lever

    13 Actuating openingfor disconnectingfunction of three-positionswitch

    14 Actuating openingfor ready-to-earthfunction of three-positionswitch

    15 Option: Busbar voltagetransformer, plug-in type

    16 Busbars, single-pole,fully-insulated, plug-intype, earthed on theoutside

    17 Option: Busbar currenttransformer

    18 Switchgear vessel,hermetically welded,filled with SF6 gas

    19 Three-positiondisconnector

    20 OFF pushbutton forcircuit-breaker

    21 Vacuum interrupter ofcircuit-breaker

    22 Pressure relief(bursting disk)

    23 Capacitive voltagedetecting system

    24 Locking device for feeder(suitable for padlocking)

    25 Disconnecting facility forfeeder voltage transformer

    26 Bushing for feeder voltagetransformer

    27 Option: Feeder voltagetransformer

    28 Option: Pressure relief duct

    29 Cable compartment

    30 Operating mechanism forthree-position switch

    31 Operating mechanism forcircuit-breaker

    32 Feeder current transformer

    33 Cable connection withoutside-cone T-plug

    34 Operation of disconnectingfacility of the feeder voltagetransformer

    35 Earthing busbar withearthing connection

    36 Air guides for cableconnection

    Basic panel design

    *#

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 23

    R-HA

    35-0

    50ep

    s

    7

    8

    9

    10

    11

    6

    5

    4

    3

    2

    1

    Vacuum circuit-breaker

    Features

    According to IEC 62 271-100and VDE 0671-100 (forstandards refer to page 44)

    Application in hermeticallywelded switchgear vesselin conformity with the sys-tem

    Climate-independentvacuum interrupter polesin the SF6-filled switch-gear vessel

    Maintenance-free forindoor installation accord-ing to IEC 62 271-1 andVDE 0671-1

    Individual secondary equip-ment

    A metal bellows is used forgasketless separation ofthe SF6 insulation and theoperating mechanism asalready used with successfor over 1 million vacuuminterrupters

    Trip-freemechanism

    The vacuum circuit-breakeris fitted with a trip-freemechanism according toIEC 62 271 and VDE 0671.

    Switching duties andoperatingmechanisms

    The switching duties of thevacuum circuit-breaker are

    dependent, among otherfactors, on its type ofoperating mechanism.

    Motor operatingmechanism

    Motor operating stored-energy mechanism

    For auto-reclosing (K) For synchronization and

    rapid load transfer (U)

    Further operatingmechanism features

    Located outside the switch-gear vessel in the operatingmechanism box and be-hind the control board

    Stored-energy springmechanism for 10,000operating cycles

    Operatingmechanismfunctions

    Motor operatingmechanism 1) (M1 *)

    In the case of motor opera-ting mechanism, the closingspring is charged by meansof a motor and latchedin the charged position(spring charged indicationis visible). Closing is effectedeither by means of an ONpushbutton or a closing so-lenoid. The closing spring isrecharged automatically (forauto-reclosing).

    Abbreviations for switching dutiesand applications:

    U = Synchronization andrapid load transfer(make time 90 ms)

    K = Auto-reclosing

    1) Motor rating at24 V to 220 V DC: 350 W110 V and 220 V AC: 400 VA

    * Item designation

    For further technical data and description of typical applications,please refer also to Catalog HG 11.05 3AH5 Vacuum Circuit-Breakers

    12 Fixed terminal

    13 Pole support

    14 Vacuum interrupter

    15 Moving terminal

    16 Metal bellows

    17 Switchgear vessel,SF6-insulated, with vacuuminterrupter

    18 Operating mechanism box(see figure above)

    19 Operating kinematics

    Section through the vacuum circuit-breaker

    Vacuum circuit-breaker(operating mechanism open)

    1 Gear with motor (M1 *)2 Position switch (S4 *)3 Closing spring

    4 Closing spring chargedindicator

    5 Closing solenoid (Y9 *)6 Operations counter

    7 Auxiliary switch 6NO+6NC (S1 *),option: 12NO+12NC

    8 Position indicatorCLOSED/OPEN for circuit-breaker

    9 Option: 2nd release (Y2 *)10 1st release (Y1 *)11 Locking device for feeder

    Endurance class of circuit-breaker

    Function Class Standard Propery of NXPLUS C

    BREAKING M2 IEC 62 271-100 10,000 times mechanicallywithout maintenance

    E2 IEC 62 271-100 10,000 times rated normalcurrent without maintenance50 times rated short-circuitbreaking current without main-tenance

    C2 IEC 62 271-100 Very low probability of restrikes

    Operating times

    Closing time Closing solenoid < 75 ms

    Opening time 1st release2nd release

    < 65 ms< 50 ms

    Arcing time at 50 Hz < 15 ms

    Break time 1st release2nd release

    < 80 ms< 65 ms

    Dead time 300 ms

    Total charging time < 15 s

    Vacuum circuit-breaker

    )#

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 200724

    Perm

    issi

    ble

    oper

    atin

    gcy

    cles

    Rated operating sequences

    Rapid load transfer (U): O-t-CO-t'-CO (t, t' 3 min)Auto-reclosing (K): O-t-CO-t'-CO (t 0.3 s, t' 3 min)Multiple-shot reclosing: O-t-CO-t'-CO-t'-CO-t'-CO (t 0.3 s, t' 15 s)

    5 combination possibilities of the releases

    Release Release combination

    1 2 3 4 5

    1st shunt release type 3AY15 10

    2nd shunt release type 3AX11 01

    Current-transformer operated release type3AX11 02, 0.5 A or type 3AX11 04, 0.1 Ws

    Undervoltage release type 3AX11 03

    1 unit of each release; max. 2 releases can be combined

    and OPEN commands arepresent at the vacuum circuit-breaker, the vacuum circuit-breaker will return to theOPEN position after closing.It remains in this position untila new CLOSE command isgiven. In this manner continu-ous closing and opening(= pumping) is avoided.

    Circuit-breaker tripping signal

    For electrical signalling(as pulse > 10 ms), e.g. to re-mote control systems, in thecase of automatic tripping(e.g. protection)

    Via limit switch (S6 *) andcut-out switch (S7 *)

    Varistor module

    To limit overvoltages toapprox. 500 V for protectiondevices (when inductivedevices are mounted in thevacuum circuit-breaker)

    For auxiliary voltagesW 60 V DC

    Auxiliary switch

    Type 3SV9 (S1 *)

    Standard: 6NO+6NC, of which3NO+4NC contacts are free 1)

    Option: 12NO+12NC, of which9NO+6NC contacts are free 1)

    Position switch

    Type 3SE4 (S4 *)

    For signalling closing springcharged

    Mechanical interlocking

    Mechanical interlockingto the three-positiondisconnector

    During operation of thethree-position switch, thevacuum circuit-breakercannot be operated

    Secondary equipment

    The scope of the secondaryequipment of the vacuumcircuit-breaker depends on thetype of application and offers awide range of variations, thusallowing even the highestrequirements to be satisfied:

    Closing solenoid

    Type 3AY15 10 (Y9 *)

    For electrical closing

    Shunt releases

    Types: Standard: 3AY15 10 (Y1 *) Option: 3AX11 01 (Y2 *),

    with energy store

    Tripping by protection deviceor electrical actuation

    Current-transformer operatedrelease

    Type 3AX11 02 (Y4*), 0.5 A

    Type 3AX11 04 (Y6 *) fortripping pulse W 0.1 Ws inconjunction with suitable pro-tection systems

    Used where no externalauxiliary voltage is available,tripping by protection device

    Undervoltage release

    Type 3AX11 03 (Y7 *)

    Comprising: Energy store and unlatching

    mechanism Electromagnetic system,

    which is permanentlyconnected to voltage whilethe vacuum circuit-breaker isclosed; tripping is initiatedwhen this voltage drops

    Connection to voltage trans-formers possible

    Anti-pumping(mechanical and electrical)

    Function: If constant CLOSE

    1) For utilizationby thecustomer

    Abbreviations:NO = normally-open contactNC = normally-closed contact

    * Itemdesignation

    Switching rate of the vacuum interrupter

    Electrical data

    Rated voltage 24 kVRated short-circuit breaking current 25 kARated normal current 2000 A

    Breaking current (r.m.s. value)

    Perm

    issi

    ble

    oper

    atin

    gcy

    cles

    Breaking current (r.m.s. value)Electrical data

    Rated voltage 15 kVRated short-circuit breaking current 31.5 kARated normal current 2500 A

    O = OPEN operation

    CO = CLOSE operation with subsequent OPENoperation at the shortest internal close-open time of the vacuum circuit-breaker

    Vacuum circuit-breaker

    )#

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 25

    R-HA

    35-0

    47ep

    sR-

    HA35

    -040

    aep

    s

    4

    3

    2

    1

    5

    6

    7

    8

    8

    9

    Common features

    According toIEC 62 271-102 andVDE 0671-102 (forstandards refer to page 44)

    Application in hermeti-cally welded switchgearvessel in conformity withthe system

    Climate-independentcontacts in the SF6 filledswitchgear vessel

    Maintenance-free forindoor installationaccording to IEC 62 271-1and VDE 0671-1

    Individual secondaryequipment

    A metal bellows is usedfor gasketless separationof the SF6 insulation andthe operating mecha-nism as already usedwith success for over1 million vacuum inter-rupters

    Compact design due toshort contact gaps inSF6 gas

    Operation via gas-tightwelded-in metal bellowsat the front of the switch-gear vessel

    Reliable switch positionup to the operating frontof the panel

    Three-positiondisconnector

    Application in Circuit-breaker panel from

    1000 A to 2500 A (withinterlock against thecircuit-breaker)

    Disconnector panel from1000 A to 2500 A

    Bus sectionalizer from1000 A to 2500 A

    1000 mechanical operat-ing cycles for CLOSED /OPEN / READY-TO-EARTH

    Three-positionswitch-disconnector

    Application in Circuit-breaker panel 630 A

    (as disconnector withinterlock against thecircuit-breaker)

    Switch-disconnector panel Ring-main panel Contactor panel Metering panel

    1000 mechanical operat-ing cycles for CLOSED /OPEN / EARTHED

    Switching functions asgeneral-purpose switch-disconnector according to

    IEC 60 265-1 VDE 0670-301 IEC 62 271-102 VDE 0671-102

    (for standards refer topage 44)

    Designed as a multi-cham-ber switch incorporatingthe functions

    Switch-disconnector and Make-proof earthing

    switch

    Switch positions of the three-position switches

    Three-position disconnector(in OPEN position)with vacuum circuit-breaker arranged below(view into the switchgear vessel opened at the rear)

    1 Fixed contact at the busbar

    2 Swivel-mounted contact blade

    3 Fixed contact for feeder EARTHED

    4 Operating shaft

    CLOSED

    OPEN

    FeederEARTHED

    Switch positions

    Three-position switch-disconnector(exploded view)

    5 Fixed contacts to earth

    6 Rotary contact blade

    7 Operating shaft

    8 Fixed contact to the feeder

    9 Fixed contact to the busbar

    CLOSED

    OPEN

    FeederEARTHED

    Switch positions

    Three-position switch

    )#

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 200726

    1) By closing the circuit-breaker

    Interlocks

    Selection of permissibleswitching operations bymeans of a control gatewith mechanically inter-locked vacuum circuit-breaker

    Corresponding operatingshafts are not releasedat the operating frontuntil they have been pre-selected with the controlgate

    Operating lever cannotbe removed until switch-ing operation has beencompleted

    Circuit-breaker cannot beclosed until control gate isin neutral position again

    Switchgear interlockingsystem also possible withelectromechanical inter-locks if switchgear isequipped with motoroperating mechanisms(mechanical interlockingfor manual operation re-mains)

    Switch positions

    CLOSED, OPEN,EARTHED orREADY-TO-EARTH

    In circuit-breaker panels,the cable connection isearthed and short-circuited by closing thevacuum circuit-breaker

    Operatingmechanism

    Spring-operated mecha-nism operated via operat-ing lever at the operatingfront of the panel

    Separate operating shaftsfor the functionsDISCONNECTING andEARTHING or READY-TO-EARTH

    Option: Motor operatingmechanism for the func-tions DISCONNECTING andEARTHING or READY-TO-EARTH

    Spring-operated/stored-energy mechanism for theswitch-disconnector func-tion with fuses:Opening spring pre-charged (after closing)

    Maintenance-free due tonon-rusting design ofparts subjected tomechanical stress

    Bearings which require nolubrication

    Transmission principle foroperatingmechanisms(see opposite drawings)

    Transmission of operatingpower from outside intothe gas-filled switchgearvessel by means of a metalbellows

    Gas-tight

    Maintenance-free

    Transmission principle for operatingmechanisms

    Three-positiondisconnector

    1 Gas-filled switchgear vessel

    2 Gas-tight welded-in metal bellows

    Three-positionswitch-disconnector

    1 Gas-filled switchgear vessel

    2 Gas-tight welded-in metal bellows

    Endurance class of three-position disconnector

    Function Class Standard Property of NXPLUS C

    DISCONNECTING M0 IEC 62 271-102

    1000 times mechanicallywithout maintenance

    READY-TO-EARTH

    1000 times mechanicallywithout maintenance

    EARTHING E2 1) IEC 62 271-102

    50 times rated short-circuitmaking current Imawithout maintenance

    Endurance class of three-position switch-disconnector

    Function Class Standard Porperty of NXPLUS C

    DISCONNECTING M0 IEC 62 271-102

    1000 times mechanicallywithout maintenance

    LOADBREAKING

    M1

    E3

    IEC 60 265-1

    IEC 60 265-1

    1000 times mechanicallywithout maintenance100 times rated mainly ac-tive load breaking current I1without maintenance

    5 times rated short-circuitmaking current Imawithout maintenance

    EARTHING E2 IEC 62 271-102

    5 times rated short-circuitmaking current Imawithout maintenance

    Three-position switch

    )#

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 27

    Features

    Application in Switch-disconnector

    panel Contactor panel Metering panel

    HV HRC fuse linksaccording to DIN 43 625(main dimensions) withstriker in mediumversion acc. to IEC 60 282 /VDE 0670-4

    As short-circuit protectionbefore transformers inthe switch-disconnectorpanel

    As short-circuit protectionbefore motors in thecontactor panel

    As short-circuit protectionbefore voltage trans-formers in the meteringpanel

    With selectivity(depending on correctselection) to upstreamand downstreamconnected equipment

    Single-phase insulated

    Requirements accordingto IEC 62 271-105 andVDE 0671-105 fulfilledby combination of HVHRC fuses with thethree-position switch-disconnector

    Climate-independent andmaintenance-free, withfuse boxes made of castresin

    Fuse assembly connectedto the three-positionswitch-disconnector viawelded bushings andconnecting bars

    Arrangement of fuse as-sembly below the switch-gear vessel

    Fuse can only be replacedif feeder is earthed

    Option:Fuse tripped indicationfor remote electrical indi-cation with one normally-open contact (1NO)

    Mode of operation

    In the event that an HV HRCfuse link has tripped, theswitch is tripped via an arti-culation which is integratedinto the cover of the fusebox (see figure).

    In the event that the fusetripping fails, e.g. if the fusehas been inserted incorrect-ly, the fuse box is protectedby thermal protection. Theoverpressure generated byoverheating trips the switchvia the diaphragm in thecover of the fuse box and viaan articulation. This breaksthe current before the fusebox incurs irreparabledamage.

    The above thermal protec-tion works independently ofthe type and design of theHV HRC fuse used. Like thefuse itself, it is maintenance-free and independent of anyoutside climatic effects.

    Furthermore, the SiemensHV HRC fuses release thestriker independently of thetemperature and trip thethree-position switch-dis-connector as early as in thefuse overload range. Imper-missible heating of the fusebox can be avoided in thisway.

    Replacementof HV HRC fuse links

    Isolating and earthing thetransformer feeder

    Subsequent manual re-placement of the HV HRCfuse link after removingthe cable compartmentcover

    HV HRC fuse assembly

    Basic design

    1 Bushing

    2 Switchgear vessel

    3 Sealing cover with seal

    4 Tripping pin for spring-operated/stored-energy mechanism

    5 Fuse box

    6 HV HRC fuse link

    7 Striker of the HV HRC fuse link andarticulation for tripping of thespring-operated/stored-energy mechanism

    Schematic sketchesfor fuse tripping

    Fuse linkin service condition

    Fuse trippedby striker

    Fuse tripped by overpressure,e.g. if HV HRC fuse linkhas been inserted incorrectly

    HV HRC fuse assembly

    )#

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 200728

    The opposite table shows therecommended HV HRC fuselinks 3GD (electrical data validfor ambient air temperatures ofup to 40 C) for fuse protectionof transformers.

    Recommendation

    The three-position switch-dis-connector in the transformerfeeder (transformer switch)was combined with SiemensHV HRC fuse links of type 3GDand tested in accordance withIEC 62 271-105.

    Higher transformer ratings onrequest.

    Standards

    HV HRC fuse links mediumversion with strikeraccording to

    IEC 60 282

    VDE 0670-4 and 402

    DIN 43 625main dimensions

    Operatingvoltage

    kV

    Transformer Rated normal current of the HV HRC fuse

    Rating SN

    kVA

    Relative impedancevoltage uk%

    Ratedcurrent I1A

    LowestvalueA

    HighestvalueA

    6.0 to 7.2 5075

    100

    444

    4.87.29.6

    161620

    162025

    125160200

    444

    12.015.419.2

    253240

    324050

    250315400

    444

    24.030.338.4

    505063

    6380

    100

    500630

    44

    48.061.0

    63100

    100100

    10 to 12 5075

    100

    444

    2.94.35.8

    101016

    101016

    125160200

    444

    7.29.3

    11.5

    162025

    202532

    250315400

    444

    14.518.323.1

    253240

    405063

    500630800

    1000

    445 to 65 to 6

    29.036.446.258.0

    50636380

    80100100100

    13.2/13.8 5075

    100

    444

    2.13.24.2

    61010

    61010

    125160200

    444

    5.36.78.4

    161616

    162025

    250315400

    444

    10.513.216.8

    202532

    253250

    500630800

    445 to 6

    21.026.433.5

    405050

    506363

    10001250

    5 to 65 to 6

    41.952.4

    6380

    80100

    15 to 17.5 5075

    100

    444

    1.92.93.9

    61010

    61010

    125160200

    444

    4.86.27.7

    101616

    101625

    250315400

    444

    9.712.215.5

    202532

    253240

    500630800

    445 to 6

    19.324.330.9

    324050

    506350

    10001250

    5 to 65 to 6

    38.548.2

    6363

    80100

    22 to 24 5075

    100

    444

    1.52.22.9

    66

    10

    66

    10

    125160200

    444

    3.64.75.8

    101016

    101016

    250315400

    444

    7.39.2

    11.6

    162020

    202532

    500630800

    445 to 6

    14.518.223.1

    253232

    405040

    1000125016002000

    5 to 65 to 65 to 65 to 6

    29.036.046.558.0

    405063

    100

    5063

    100100

    Allocation of three-position switch-disconnector with HV HRC fuses, transformer ratings

    )#

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 29

    5

    4

    32

    1

    R-HA

    35-1

    10ep

    s

    Features

    According to IEC 60 470 andVDE 0670-501 (for standardsrefer to page 44)

    Application in hermeticallywelded switchgear vessel inconformity with the system

    Climate-independent vacuuminterrupter poles in theSF6-filled switchgear vessel

    Maintenance-free for indoorinstallation according toIEC 62 271-1 andVDE 0671-1

    Individual secondary equip-ment

    A metal bellows is used forgasketless separation of theSF6 insulation and the oper-ating mechanism as al-ready used with success forover 1 million vacuum inter-rupters

    Magnet coil for operationlocated outside the switch-gear vessel

    100,000 or 500,000 operat-ing cycles at rated normalcurrent

    Short-circuit and overloadprotection in connection withmotors

    In circuits subjected to short-circuit currents, HV HRC fuselinks protect switching deviceswithout short-circuit breakingcapacity (e.g. vacuum contac-tors).

    The max. stress for HV HRCfuses arises during motorstarting (starting currents,starting times and startingfrequency).

    Fuses must not operate or bepre-damaged during motorstarting.

    The opposite table shows thepermissible motor starting cur-rents according to the startingtime and starting frequencyof downstream connected HVmotors with the associatedHV HRC fuses.

    Vacuum contactor

    Vacuum contactor(operating mechanism open)

    1 Metal bellows

    2 Pole support

    3 Vacuum interrupter

    4 Operating mechanism box with magnet coil

    5 Base plate (welded into the switchgear vessel)

    Section through the vacuum contactor

    Motor protection table

    Numberof startsper hour

    Maximum permissible motor starting current in A

    at rated normal current of fuse

    40 A 63 A 100 A 125 A 160 A 250 A

    HV motorswith starting timesup to 5 s

    2 90 135 255 360 480 740

    4 80 120 235 330 440 675

    8 75 110 215 300 400 615

    16 65 100 190 270 360 550

    HV motorswith starting timesup to 15 s

    2 85 120 225 310 430 635

    4 75 110 205 285 400 580

    8 70 100 185 260 360 530

    16 60 90 165 235 325 475

    HV motorswith starting timesup to 30 s

    2 80 120 215 300 420 600

    4 70 105 190 265 370 530

    8 65 90 165 230 320 460

    16 55 80 145 200 280 400

    6 Fixed terminal

    7 Pole support

    8 Vacuum interrupter

    9 Moving terminal

    10 Switchgear vessel,SF6-insulated, with vacuuminterrupter

    11 Metal bellows

    12 Operating mechanism box(see figure above)

    13 Operating kinematics

    Vacuum contactor, motor protection

    )#

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 200730

    R-HA

    35-0

    51ep

    s

    Features

    Single-pole, plug-in andbolted design

    Consisting of round-barcopper, insulated by meansof silicone rubber

    Busbar joints with cross andend adapters, insulated bymeans of silicone rubber

    Field control by means ofelectrically conductive layerson the silicone-rubber insula-tion (both inside and outside)

    Safe-to-touch by earthingthe external layers with theswitchgear vessel

    Insensitive to pollution andcondensation

    Safe-to-touch as a result ofuse of metallic covers

    Switchgear extension or pa-nel replacement is possiblewithout gas work

    Possible fittings

    Current transformers

    Voltage transformers

    Surge arresters

    Cables with Straight plug or T-plug

    Fully-insulated bars(e.g. make Duresca)

    Legend

    1 Cap

    2 Busbar insulation made ofsilicone rubber

    3 Clamps

    4 Busbar (round-bar copper)

    5 End adapter or coupling endadapter

    6 Connection bolt

    7 Switchgear vessel

    8 Metal cover of busbars

    9 Cross adapter or coupling crossadapter

    10 Bushing

    11 Earthing connection

    Section of busbar 1250 A (basic design)(panel width 600 mm)

    Busbars (example)

    Busbars 1250 A, plug-in type, fully insulated(as front view of three panels, without low-voltage compartments)

    Busbars

    )#

    Section of busbar 1600 A, 2000 A or 2500 A (basic design)(panel width 600 mm)

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 31

    Features

    According to IEC 60 044-1and VDE 0414-1

    Designed as ring-core currenttransformers, single-pole

    Free of dielectrically stressedcast-resin parts (due todesign)

    Insulation class E

    Inductive type

    Certifiable

    Climate-independent

    Secondary connection bymeans of a terminal strip inthe low-voltage compart-ment of the panel

    Installation

    Arranged outside the primaryenclosure (switchgear vessel)

    Mounting locations

    At the busbar (1)

    At the panel connection (2)

    Around the cable (3)

    Current transformer types

    Busbar current transformer (1): Inside diameter of

    transformer56 mm / 1250 A and56 x 300 mm / > 1250 A

    Max. usable height 170 mm

    Feeder current transformer (2): Inside diameter of

    transformer106 mm / 1250 A and106 x 240 mm / > 1250 A

    Max. usable height 205 mm

    Cable-type current trans-former (3) for shielded cables:

    Inside diameter oftransformer 55 mm

    Max. usable height 170 mm

    Bus-type current transformer(4) underneath the panels(included in the scope ofsupply); on-site installation

    1 Busbar current transformer

    2 Feeder current transformerat the panel connection

    3 Cable-type current transformer

    4 Bus-type current transformer

    Current transformers

    Busbar current transformersExample 1250 A

    Designation Type 4MC

    Multiratio (secondary) 200 100 A to2500 1250 A

    Core data according torated primary current:Measuring Ratingcore Class

    Overcurrentfactor

    max. 3 cores

    2.5 VA to 30 VA0.2 to 1

    FS 5, FS 10

    Protection Ratingcore Class

    Overcurrentfactor

    2.5 VA to 30 VA5 P or 10 P

    10 to 30

    Permissible ambient airtemperature

    max. 60 C

    Insulation class E

    Electrical data

    Designation Type 4MC

    Operating voltage max. 0.8 kV

    Rated short-durationpower-frequency withstandvoltage (winding test)

    3 kV

    Rated frequency 50/60 Hz

    Rated continuous thermalcurrent

    max. 1.2 xrated current(primary)

    Rated thermalshort-time withstand current,max. 3 s

    max. 31.5 kA

    Rated current dynamicprimary

    secondary

    unlimited40 A to2500 A1 A and 5 A

    Front views:

    Panel with busbar1250 A

    630 A, 1000 A 2000 A, 2300 A and 2500 A Panel with busbarand 1250 A 2500 A

    Current transformer installation (basic design)

    Side views:

    Current transformers

    )#

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 200732

    R-HA

    35-1

    20ep

    s

    Voltage transformers

    Feeder voltage transformer (metal-coated)

    Features

    According to IEC 60 044-2 andVDE 0414-2

    Single-pole, plug-in design

    Connection system withplug-in contact

    Inductive type

    Safe-to-touch as a result ofuse of metallic covers

    Certifiable

    Climate-independent

    Secondary connection bymeans of plugs inside thepanel

    Cast-resin insulated

    Arranged outside the primaryenclosure (switchgear vessel)

    Mounting locations: At the busbar At the panel connection

    Voltage transformer types

    Busbar voltage transformer4MT2:

    Pluggable in the cross adap-ters of the busbar 1250 Ausing additional adapters(> 1250 A on request)

    No separate metering panelrequired

    Suitable for 80 % of therated short-duration power-frequency withstand voltageat rated frequency

    Repeat test at 80 % of therated short-duration power-frequency withstand voltagepossible with mountedvoltage transformer (also validfor higher insulation ratingsaccording to GOST and GBstandards)

    Feeder voltage transformer4MT3 at the panel connec-tion:

    Switchable through anSF6-insulated disconnectingfacility in the switchgearvessel

    Switch positions: CLOSEDand Transformer bushingEARTHED

    Operation of the disconnect-ing facility from outsidethrough a metal bellowswelded in the switchgearvessel

    Voltage testing of switchgearand cables possible withmounted and earthed voltagetransformer

    Voltage transformers

    )#

    Voltage transformer installation (basic design)

    Front view: Side view:

    Disconnecting facilityfor feeder voltage transformer(details Z)

    OPEN and EARTHED

    CLOSED

    1 Busbar voltage transformer

    2 Feeder voltage transformerat the panel connection

    3 Operating lever fordisconnecting facility

    4 Panel connection

    5 Switchgear vessel wall(earthed)

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 33

    Electrical data

    Primary data

    For types 4MT3 and 4MT2For operating voltages from 3.3 to 23 kV, rated voltage factor Un/8h = 1.9 ; Un /continuous = 1.2

    Rated voltage

    kV

    Rated short-durationpower-frequencywithstand voltage

    kV

    Rated lightning impulsewithstand voltage

    kV

    Standard Operating voltage

    kV

    3.6 10 20 IEC 3.3/ 3

    7.2 20 60 IEC 3.6/ 3; 4.8/ 3; 5.0/ 3;6.0/ 3; 6.3 / 3; 6.6/ 3

    32 60 GOST 6.0/ 3; 6.3/ 3; 6.6/ 3

    12 28 75 IEC 7.2/ 3; 10/ 3; 11/ 3

    42 75 GOST 10/ 3; 11/ 3

    42 75 GB 10/ 3; 11/ 3

    17.5 38 95 IEC 13.2/ 3; 13.8/ 3; 15/ 3

    24 50 125 IEC 17,5/ 3; 20/ 3; 23/ 3

    Secondary data

    Fortype

    Operatingvoltage

    V

    Auxiliarywinding

    V

    Thermal limitcurrent (meas-uring winding)

    A

    Rated long-timecurrent,8 h

    A

    Rating at accuracy class

    0.2 0.5 1 3

    VA VA VA VA

    4MT3 100/ 3;110/ 3;120/ 3

    100/3;110/3;120/3

    6 4 IEC

    10,15, 20, 25,30

    10, 15, 20, 25,30, 45, 50, 60,75, 90

    10, 15, 20, 25,30, 45, 50, 60,75, 90, 100,120, 150, 180

    10, 15, 20, 25,30, 45, 50, 60,75, 90, 100,120, 150, 180

    GOST 32/60 kV

    10, 15, 20, 25,30

    10, 15, 20, 25,30, 45, 50, 60,75, 90

    10, 15, 20, 25,30, 45, 50, 60,75, 90, 100,120, 150, 180

    10, 15, 20, 25,30, 45, 50, 60,75, 90, 100,120, 150, 180

    GOST 42/75 kV, GB 42/75 kV

    10, 15, 20, 25 10, 15, 20, 25,30, 45, 50, 60,75

    10, 15, 20, 25,30, 45, 50, 60,75, 90, 100,120, 150

    10, 15, 20, 25,30, 45, 50, 60,75, 90, 100,120, 150

    4MT2 100/ 3;110/ 3;120/ 3

    100/3;110/3;120/3

    8 6 IEC

    5, 10,15, 20,25

    10, 15, 20, 25,30, 45

    10, 15, 20, 25,30, 45, 50, 60,75

    10, 15, 20, 25,30, 45, 50, 60,75

    GOST 32/60 kV

    5 10, 15 10, 15, 20, 25,30

    10, 15, 20, 25,30

    GOST 42/75 kV, GB 42/75 kV

    5, 10 10, 15, 20, 25,30

    10, 15, 20, 25,30, 45, 50, 60

    10, 15, 20, 25,30, 45, 50, 60

    GOST: Russian standardGB: Chinese standard

    Voltage transformers

    )#

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 200734

    Features

    Bushings with outside cone

    With bolted contact (M16) asinterface type C accordingto EN 50 180 / EN 50 181

    Cable connection height:702 mm (for switch-discon-nector panels and contactorpanels with HV HRC fuses:450 mm)

    Max. connection depth:584 mm or 732 mm withstandard cable compartmentcover, 752 mm with deepercable compartment cover

    With cable bracket, e.g. typeC40 accord. to DIN EN 50 024

    Option: Access to the cablecompartment only if thefeeder has been isolated andearthed

    For thermoplastic-insulatedcables

    For cable T-plugs or cableelbow plugs with bolted con-tact

    For connection cross-sectionsup to 630 mm2

    Cable routing downwards,cable connection from thefront

    Option: Cable routing to thetop at the rear, cable connec-tion from the rear (only forcircuit-breaker panel 1250 A)

    For rated normal currentsup to 2500 A

    Cable plugs, cable sealingends and cable clamps arenot included in the scope ofsupply

    Surge arresters

    Can be plugged into thecable T-plug

    Surge arresters are recom-mended if, at the same time,

    The cable system is directlyconnected to the overheadline,

    The protective range of thearrester at the terminal towerof the overhead line does notcover the switchgear

    Surge limiters

    Can be plugged into thecable T-plug

    Surge limiters are recom-mended if motors withstarting currents < 600 A areconnected

    Legend

    1 Cable T-plug

    2 Coupling T-plug

    3 Screwed couplinginsert

    * Cable connection height of450 mm for switch-discon-nector panels and contactorpanels with HV HRC fuses

    Panel connection

    )#

    Panel width 600 mm Panel width 1200 mm

    Connection with 2 cables per phaseconnection with 4 cables per phase

    Connection with 3 cables per phaseconnection with 6 cables per phase

    Cable compartment

    Connectable cables

    Connection with 1 cable per phaseconnection with 2 cables per phase

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 35

    Installation possibilities for cable connections and surge arresters

    Number ofcables perpanel andphase

    Make Conductorcross-section 1)

    mm2

    Insulation Cable T-plugs

    bolted12 kV24 kV

    Coupling inserts/couplingplugs

    bolted12 kV24 kV

    Surgearresterswith coupling insertsArresters Coupling inserts

    additionally

    Circuit-breaker panel 630 A, 1000 A Switch-disconnector panel 630 A Disconnector panel 1000 A Ring-main panel 630 A Contactor panel Circuit-breaker panel with top-rear cable connection 1250 A 2)

    1 Euromold 35 to 300 EPDM 1x 400TB/G1x K400TB/G

    400PB-5(10)-SA-xxx

    35 to 300 EPDM 1x 430TB-630A1x K430TB-630A

    300SA-5(10)SA

    400 to 630 EPDM 1x 440TB/G1x K440TB/G

    400PB-5(10)-SA-xxx

    Sdkabel 50 to 30025 to 240

    Silicone 1x SET 121x SET 24

    MUT 23

    400 to 500300 to 500

    Silicone 1x SEHDT 131x SEHDT 23

    MUT 23

    nkt cables 25 to300 Silicone 1x CB 12-6301x CB 24-630

    CSA 12-xCSA 24-x

    400 to 630 Silicone 1x CB 36-630(1250)1x CB 36-630(1250)

    CSA 12-xCSA 24-x

    Tyco Electronics 25 to 300 Silicone 1x RSTI-L56xx1x RSTI-L56xx

    RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx

    25 to 300 Silicone 1x RSTI-58xx1x RSTI-58xx

    RSTI-CC-58SAxxxx

    400 to 630 Silicone 1x RSTI-36Lxx1x RSTI-56Lxx

    RSTI-L56SAxxxxRSTI-66SAxxxx

    RSTI-66CP-M16RSTI-66CP-M16

    2 3) Euromold 35 to 300 EPDM 2x 400TB/G2x K400TB/G

    1x 400CP1x K400CP

    35 to 300 EPDM 1x 430TB-630A1x K430TB-630A

    1x 300PB-630A1x K300PB-630A

    400 to 630 EPDM 2x 440TB/G2x K440TB/G

    1x 440CP1x K440CP

    Sdkabel 50 to 30025 to 240

    Silicone 1x SET 121x SET 24

    1x SEHDK 13.11x SEHDK 23.1

    50 to 30025 to 240

    Silicone 2x SET 122x SET 24

    1x KU 23.21x KU 23.2

    400 to 500300 to 500

    Silicone 2x SEHDT 132x SEHDT 23

    1x KU 231x KU 23

    nkt cables 25 to 300 Silicone 1x CB 12-6301x CB 24-630

    1x CC 12-6301x CC 24-630

    CSA 12-xCSA 24-x

    25 to 300 Silicone 2x CB 12-6302x CB 24-630

    1x CP 630-C1x CP 630-C

    CSA 12-xCSA 24-x

    400 to 630 Silicone 1x CB 36-630(1250)1x CB 36-630(1250)

    1x CC 36-630(1250)1x CC 36-630(1250)

    CSA 12-xCSA 24-x

    Tyco Electronics 25 to 300 Silicone 1x RSTI-L56xx1x RSTI-L56xx

    1x RSTI-CC-L56xx1x RSTI-CC-L56xx

    RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx

    25 to 300 Silicone 1x RSTI-58xx1x RSTI-58xx

    1x RSTI-CC-58xx1x RSTI-CC-58xx

    RSTI-CC-58SAxxxx

    400 to 630 Silicone 2x RSTI-36Lxx2x RSTI-56Lxx

    1x RSTI-66CP-M161x RSTI-66CP-M16

    RSTI-L56SAxxxxRSTI-66SAxxxx

    RSTI-66CP-M16RSTI-66CP-M16

    )#

    1) Observe the actual current and short-circuit current carrying capacity of the cables and sealing ends.

    2) For the 1250 A version, only sealing ends with silver-plated or nickel-plated cable lugs are permissible.

    3) The use of arresters is not possible for cable connection panels 1250 A with top-rear cable connection.

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 200736

    Installation possibilities for cable connections and surge arresters

    )#

    Number ofcables perpanel andphase

    Make Conductorcross-section 1)

    mm2

    Insulation Cable T-plugs

    bolted12 kV24 kV

    Coupling inserts/couplingplugs

    bolted12 kV24 kV

    Surgearresterswith coupling insertsArresters Coupling inserts

    additionally

    Circuit-breaker panel 1250 A 2) Disconnector panel 1250 A 2)

    1 Same combination options as in the previous table

    2 Euromold 35 to 300 EPDM 2x 400TB/G2x K400TB/G

    1x 400CP1x K400CP

    400PB-5(10)-SA-xxx

    35 to 300 EPDM 1x 430TB-630A1x K430TB-630A

    1x 300PB-630A1x K300PB-630A

    300SA-5(10)SA

    400 to 630 EPDM 2x 440TB/G2x K440TB/G

    1x 440CP1x K440CP

    400PB-5(10)-SA-xxx

    Sdkabel 50 to 30025 to 240

    Silicone 1x SET 121x SET 24

    1x SEHDK 13.11x SEHDK 23.1

    50 to 30025 to 240

    Silicone 2x SET 122x SET 24

    1x KU 23.21x KU 23.2

    400 to 500300 to 500

    Silicone 2x SEHDT 132x SEHDT 23

    1x KU 231x KU 23

    nkt cables 25 to 300 Silicone 1x CB 12-6301x CB 24-630

    1x CC 12-6301x CC 24-630

    CSA 12-xCSA 24-x

    25 to 300 Silicone 2x CB 12-6302x CB 24-630

    1x CP 630-C1x CP 630-C

    CSA 12-xCSA 24-x

    400 to 630 Silicone 1x CB 36-630(1250)1x CB 36-630(1250)

    1x CC 36-630(1250)1x CC 36-630(1250)

    CSA 12-xCSA 24-x

    Tyco Electronics 25 to 300 Silicone 1x RSTI-L56xx1x RSTI-L56xx

    1x RSTI-CC-L56xx1x RSTI-CC-L56xx

    RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx

    25 to 300 Silicone 1x RSTI-58xx1x RSTI-58xx

    1x RSTI-CC-58xx1x RSTI-CC-58xx

    RSTI-CC-58SAxxxx

    400 to 630 Silicone 2x RSTI-36Lxx2x RSTI-56Lxx

    1x RSTI-66CP-M161x RSTI-66CP-M16

    RSTI-L56SAxxxxRSTI-66SAxxxx

    RSTI-66CP-M16RSTI-66CP-M16

    3 Euromold 35 to 300 3) EPDM 3x 400TB/G3x K400TB/G

    2x 400CP2x K400CP

    35 to 300 EPDM 1x 430TB-630A1x K430TB-630A

    2x 300PB-630A2x K300PB-630A

    400 to 630 3) EPDM 3x 440TB/G3x K440TB/G

    2x 440CP2x K440CP

    nkt cables 25 to 300 Silicone 1x CB 12-6301x CB 24-630

    2x CC 12-6302x CC 24-630

    CSA 12-xCSA 24-x

    400 to 630 Silicone 1x CB 36-630(1250)1x CB 36-630(1250)

    2x CC 36-630(1250)2x CC 36-630(1250)

    CSA 12-xCSA 24-x

    Tyco Electronics 25 to 300 Silicone 1x RSTI-L56xx1x RSTI-L56xx

    2x RSTI-CC-L56xx2x RSTI-CC-L56xx

    RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx

    25 to 300 Silicone 1x RSTI-58xx1x RSTI-58xx

    2x RSTI-CC-58xx2x RSTI-CC-58xx

    RSTI-CC-58SAxxxx

    400 to 630 Silicone 3x RSTI-36Lxx3x RSTI-56Lxx

    2x RSTI-66CP-M162x RSTI-66CP-M16

    RSTI-L56SAxxxxRSTI-66SAxxxx

    RSTI-66CP-M16RSTI-66CP-M16

    1) Observe the actual current and short-circuit current carrying capacity of the cables and sealing ends.

    2) For the 1250 A version, only sealing ends with silver-plated or nickel-plated cable lugs are permissible.

    3) Only possible with deeper cable compartment cover.

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 37

    Installation possibilities for cable connections and surge arresters

    )#

    Number ofcables perpanel andphase

    Make Conductorcross-section 1)

    mm2

    Insulation Cable T-plugs

    bolted12 kV24 kV

    Coupling inserts/couplingplugs

    bolted12 kV24 kV

    Surge arresters with coupling insertsArresters Coupling inserts

    additionally

    Circuit-breaker panel and disconnector panel 2000 A, 2300 A, 2500 A 2)

    2 Euromold 35 to 300 EPDM 2x 400TB/G2x K400TB/G

    400PB-5(10)-SA-xxx

    35 to 300 EPDM 2x 430TB-630A2x K430TB-630A

    300SA-5(10)SA

    400 to 630 EPDM 2x 440TB/G2x K440TB/G

    400PB-5(10)-SA-xxx

    Sdkabel 50 to 30025 to 240

    Silicone 2x SET 122x SET 24

    MUT 23

    400 to 500300 to 500

    Silicone 2x SEHDT 132x SEHDT 23

    MUT 23

    nkt cables 25 to 300 Silicone 2x CB 12-6302x CB 24-630

    CSA 12-xCSA 24-x

    400 to 630 Silicone 2x CB 36-630(1250)2x CB 36-630(1250)

    CSA 12-xCSA 24-x

    Tyco Electronics 25 to 300 Silicone 2x RSTI-L56xx2x RSTI-L56xx

    RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx

    25 to 300 Silicone 2x RSTI-58xx2x RSTI-58xx

    RSTI-CC-58SAxxxx

    400 to 630 Silicone 2x RSTI-36Lxx2x RSTI-56Lxx

    RSTI-L56SAxxxxRSTI-66SAxxxx

    RSTI-66CP-M16RSTI-66CP-M16

    4 Euromold 35 to 300 EPDM 4x 400TB/G4x K400TB/G

    2x 400CP2x K400CP

    400PB-5(10)-SA-xxx

    35 to 300 EPDM 2x 430TB-630A2x K430TB-630A

    2x 300PB-630A2x K300PB-630A

    300SA-5(10)SA

    400 to 630 EPDM 4x 440TB/G4x K440TB/G

    2x 440CP2x K440CP

    400PB-5(10)-SA-xxx

    Sdkabel 50 to 30025 to 240

    Silicone 2x SET 122x SET 24

    2x SEHDK 13.12x SEHDK 23.1

    MUT 23

    50 to 30025 to 240

    Silicone 4x SET 124x SET 24

    2x KU 23.22x KU 23.2

    MUT 23

    400 to 500300 to 500

    Silicone 4x SEHDT 134x SEHDT 23

    2x KU 232x KU 23

    MUT 23

    nkt cables 25 to 300 Silicone 2x CB 12-6302x CB 24-630

    2x CC 12-6302x CC 24-630

    CSA 12-xCSA 24-x

    25 to 300 Silicone 4x CB 12-6304x CB 24-630

    2x CP 630-C2x CP 630-C

    CSA 12-xCSA 24-x

    400 to 630 Silicone 2x CB 36-630(1250)2x CB 36-630(1250)

    2x CC 36-630(1250)2x CC 36-630(1250)

    CSA 12-xCSA 24-x

    Tyco Electronics 25 to 300 Silicone 2x RSTI-L56xx2x RSTI-L56xx

    2x RSTI-CC-L56xx2x RSTI-CC-L56xx

    RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx

    25 to 300 Silicone 2x RSTI-58xx2x RSTI-58xx

    2x RSTI-CC-58xx2x RSTI-CC-58xx

    RSTI-CC-58SAxxxx

    400 to 630 Silicone 4x RSTI-36Lxx4x RSTI-56Lxx

    2x RSTI-66CP-M162x RSTI-66CP-M16

    RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx

    RSTI-66CP-M16RSTI-66CP-M16

    1) Observe the actual current and short-circuit current carrying capacity of the cables and sealing ends.

    2) For the 2000 A, 2300 A and 2500 A versions, only sealing ends with silver-plated or nickel-plated cable lugs are permissible.

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 200738

    Installation possibilities for cable connections and surge arresters

    )#

    Number ofcables perpanel andphase

    Make Conductorcross-section 1)

    mm2

    Insulation Cable T-plugs

    bolted12 kV24 kV

    Coupling inserts/couplingplugs

    bolted12 kV24 kV

    Surgearresterswith coupling insertsArresters Coupling inserts

    additionally

    Circuit-breaker panel and disconnector panel 2000 A, 2300 A, 2500 A 2)

    6 Euromold 35 to 300 3) EPDM 6x 400TB/G6x K400TB/G

    4x 400CP4x K400CP

    35 to 300 EPDM 2x 430TB-630A2x K430TB-630A

    4x 300PB-630A4x K300PB-630A

    400 to 630 3) EPDM 6x 440TB/G6x K440TB/G

    4x 440CP4x K440CP

    nkt cables 25 to 300 Silicone 2x CB 12-6302x CB 24-630

    4x CC 12-6304x CC 24-630

    CSA 12-xCSA 24-x

    400 to 630 Silicone 2x CB 36-630(1250)2x CB 36-630(1250)

    4x CC 36-630(1250)4x CC 36-630(1250)

    CSA 12-xCSA 24-x

    Tyco Electronics 25 to 300 Silicone 2x RSTI-L56xx2x RSTI-L56xx

    4x RSTI-CC-L56xx4x RSTI-CC-L56xx

    RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx

    25 to 300 Silicone 2x RSTI-58xx2x RSTI-58xx

    4x RSTI-CC-58xx4x RSTI-CC-58xx

    RSTI-CC-58SAxxxx

    400 to 630 Silicone 6x RSTI-36Lxx6x RSTI-56Lxx

    4x RSTI-66CP-M164x RSTI-66CP-M16

    RSTI-L56SAxxxxRSTI-66SAxxxx

    RSTI-66CP-M16RSTI-66CP-M16

    1) Observe the actual current and short-circuit current carrying capacity of the cables and sealing ends.

    2) For the 2000 A, 2300 A and 2500 A versions, only sealing ends with silver-plated or nickel-plated cable lugs are permissible.

    3) Only possible with deeper cable compartment cover.

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 39

    Panel connection (commercially available cable sealing ends)

    Cable type Cable sealing ends Comment

    Make Type Cross-sectionmm2

    Thermoplastic insulated cables 12 kV according to IEC 60502-2 and VDE 0276-620

    1-core cable, PE and XLPE-insulated

    N2YSY (Cu) and N2XSY (Cu)

    or

    NA2YSY (AI) and NA2XSY (AI)

    Euromold 400 TB/G 35 to 300 EPDM with semi-conductive layer

    430TB-630A 35 to 300 EPDM with semi-conductive layer

    440 TB/G 400 to 630 EPDM with semi-conductive layer

    nkt cables CB 12-630 25 to 300 Silicone with semi-conductive layer(optionally with metal housing)

    CB 36-630(1250) 400 to 630 Silicone with semi-conductive layer

    Sdkabel SET 12 50 to 300 Silicone with semi-conductive layer(optionally with metal housing)

    SEHDT 13 400 to 500 Silicone with semi-conductive layer(optionally with metal housing)

    Tyco Electronics RSTI-L56xx 25 to 300 Silicone with semi-conductive layer, with capacitivemeasuring point

    RSTI-58xx 25 to 300 Silicone with semi-conductive layer, with capacitivemeasuring point

    RSTI-36Lxx 400 to 630 Silicone with semi-conductive layer, with capacitivemeasuring point

    Thermoplastic insulated cables 15/17.5/24 kV according to IEC 60502-2 and VDE 0276-620

    1-core cable, PE and XLPE-insulated

    N2YSY (Cu) and N2XSY (Cu)

    or

    NA2YSY (AI) and NA2XSY (AI)

    Euromold K400TB/G 35 to 300 EPDM with semi-conductive layer

    K430TB-630A 35 to 300 EPDM with semi-conductive layer

    K440TB/G 400 to 630 EPDM with semi-conductive layer

    nkt cables CB 24-630 25 to 300 Silicone with semi-conductive layer(optionally with metal housing)

    CB 36-630(1250) 400 to 630 Silicone with semi-conductive layer

    Sdkabel SET 24 50 to 300 Silicone with semi-conductive layer(optionally with metal housing)

    SEHDT 23 400 to 500 Silicone with semi-conductive layer(optionally with metal housing)

    Tyco Electronics RSTI-L56xx 25 to 300 Silicone with semi-conductive layer, with capacitivemeasuring point

    RSTI-58xx 25 to 300 Silicone with semi-conductive layer, with capacitivemeasuring point

    RSTI-56Lxx 400 to 630 Silicone with semi-conductive layer, with capacitivemeasuring point

    )#

    Paper-insulated belted cables 12 kV according to GOST 18410-73

    3-core cable, paper-insulated

    ASB and ASBL

    nkt cables CB 24-630 25 to 240 Silicone with semi-conductive layer,in combination with transition sealing end type SEV 10

    Tyco Electronics RSTI-58xx 25 to 300 Silicone with semi-conductive layer, with capacitivemeasuring point, in combination with transition sealingend type SMOE

    Paper-insulated belted cables 12 kV according to IEC 60055 and VDE 0255

    3-core cable, paper-insulated

    NKBA (Cu), NKBY (Cu),NKRA (Cu) and NKFA (Cu)

    or

    NAKBA (AI), NAKBY (AI),NAKRA (AI) and NAKFA (AI)

    nkt cables CB 24-630 25 to 240 Silicone with semi-conductive layer,in combination with transition sealing end type SEV 10

    Tyco Electronics RSTI-58xx 25 to 300 Silicone with semi-conductive layer, with capacitivemeasuring point, in combination with transition sealingend type SMOE

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 200740

    Voltage detecting systemsacc. to IEC 61243-5 orVDE 0682-415

    To verify safe isolation fromsupply

    Detecting systems LRM system with plug-in

    indicator LRM system with integrated

    indicator type VOIS+, VOIS R+ LRM system with integrated

    indicator, with integratedrepeat test of the interface,with integrated function testtype CAPDIS-S1+

    LRM system with integratedindicator, with integratedrepeat test of the interface,with integrated function test,with integrated signallingrelay type CAPDIS-S2+

    LRM system

    Verification of safe isolationfrom supply phase by phasethrough insertion in eachsocket pair

    Indicator suitable forcontinuous operation

    Safe-to-touch

    Routine-tested

    Measuring system and volt-age indicator can be tested

    Voltage indicator flasheswhen high voltage is present

    VOIS+, VOIS R+

    Integrated display, withoutauxiliary power

    With indication A1 to A3,(see legend)

    Maintenance-free, repeat testrequired

    With integrated three-phasetest socket for phase compa-rison (also suitable for plug-involtage indicator)

    Degree of protection IP 67,temperature range -25 C to+55 C

    With integrated signallingrelays (only VOIS R+)

    M1: Voltage present at onephase L1, L2 or L3 as aminimum

    M2: Voltage not presentat L1, L2 and L3

    Voltage indicationvia capacitive voltage divider (principle)

    C1 Capacity integrated into bushing

    C2 Capacity of the connection leads andof the voltage indicator to earth

    R-HA

    40-1

    03ep

    sR-

    HA40

    -102

    aep

    s

    Plug-in voltage indicatorper phase atthe panel front

    Integrated voltage detecting systemCAPDIS-S1+, -S2+

    Indicators and detecting systems

    R-HA

    40-1

    04ep

    s

    Integrated voltage indicatorVOIS+, VOIS R+

    A0

    A1

    A2

    A3

    A4

    A5

    A6

    A0 CAPDIS-S2+: Operating voltagenot present

    A1 Operating voltage present

    A2 Operating voltage not present For CAPDIS-S2+:

    Auxiliary power not present

    A3 Failure in phase L1, operating voltageat L2 and L3 (for CAPDIS-Sx+ alsoearth-fault indication)

    A4 Voltage (not operating voltage)present

    A5 Indication Device-Function-Testpassed

    A6 Indication ERROR, e.g. in case ofmissing auxiliary voltage(see: error indication M4)

    CAPDIS-Sx+

    Common features

    Maintenance-free

    Integrated display, withoutauxiliary power

    Integrated repeat test of theinterfaces (self-monitoring)

    With integrated function test(without auxiliary power) bypressing the Device-Func-tion-Test pushbutton

    With integrated three-phasetest socket for phase compa-rison (also suitable for plug-involtage indicator)

    Degree of protection IP 54,temperature range 25 C to+55 C

    With circuit capacity

    With ready-for-servicemonitoring (external auxiliarypower required)

    With integrated signalling re-lay for signalling M1 to M4(auxiliary power required):

    M1: Voltage present atphases L1, L2, L3

    M2: Voltage not present atL1, L2 and L3 (= active zeroindication)

    M3: Earth fault or voltagefailure, e.g. in one phase

    M4: External auxiliarypower missing (operatingvoltage present or not)

    Features of CAPDIS-S1+

    Without auxiliary power

    With indication A1 to A5(see legend)

    Without ready-for-servicemonitoring

    Without signalling relay (thuswithout auxiliary contacts)

    Features of CAPDIS-S2+

    With indication A0 to A6(see legend)

    Only by pressing theDevice-Function-Testpushbutton: ERROR indica-tion (A6), e.g. in case ofmissing auxiliary voltage

    ULE = UN / 3 during rated operationin the three-phase system

    U2 = UA= Voltage at the capacitive interfaceof the switchgear or at the voltage indicator

    Indicating andmeasuring equipment

    )#

    Symbols shown

    VOIS+,VOISR+ CAPDIS-S1+ CAPDIS-S2+

    LRM systemplugged in

    CAPDIS/VOISinstalled

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 41

    Verification of correctterminal-phase connections

    Verification of correct termi-nal-phase connections possi-ble by means of a phasecomparison test unit(can be ordered separately)

    Safe-to-touch handling of thephase comparison test unitby inserting it into the capaci-tive taps (socket pairs) of theswitchgear

    Phase comparison test units

    R-HA

    40-0

    59ep

    s

    Phase comparison test unitMake: Pfisterer, type EPV

    R-HA

    40-0

    89ep

    s

    Phase comparison test unitMake: Horstmann, type ORION 3.0as combined test unit for: Phase comparison Interface testing at switchgear Voltage detection for LRM system

    Phase comparison test unitMake: Kries, type CAP-Phaseas combined test unit (HR and LRM)for: Voltage detection Repeat test Phase comparison Phase sequence test Self-testThe unit does not require a battery

    R-HA

    35-1

    24.e

    ps

    or other makes

    Indicating andmeasuring equipment

    )#

  • Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 200742

    Gasmonitoring

    R-HA

    35-1

    05ep

    s

    Ready-for-service indicator

    Features

    Self-monitoring; easy to read

    Independent of temperatureand pressure variations

    Independent of site altitude

    Only responds to changes ingas density

    Option: Alarm switch 1NO +1NC for remote electrical in-dication

    Mode of operation

    For the ready-for-service indi-cator, a gas-tight measurementbox is installed inside theswitchgear vessel.

    A coupling magnet, which isfitted to the bottom end of themeasurement box, transmits itsposition to an outside armat