ELECTRIC POWER RATINGS GUIDE Generator Sets For additional information or to find your nearest dealer go to: www.catelectricpowerinfo.com/rg © 2009 Caterpillar All Rights Reserved Printed in USA CAT, CATERPILLAR, their respective logos, ACERT, ADEM, “Caterpillar Yellow” the “Power Edge” trade dress, as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission. LEXE7582-02 December 2009

Cat Diesel Generators Specs

Embed Size (px)

Citation preview

Page 1: Cat Diesel Generators Specs

ELECTRIC POWER RATINGS GUIDEGenerator SetsFor additional information or to find

your nearest dealer go to: www.catelectricpowerinfo.com/rg

© 2009 Caterpillar All Rights Reserved Printed in USA CAT, CATERPILLAR, their respective logos, ACERT, ADEM, “Caterpillar Yellow” the “Power Edge” trade dress, as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.

LEXE7582-02December 2009

Page 2: Cat Diesel Generators Specs

1

CONTENTS ratings guide

Cat® Diesel Generator Sets

50 Hz Ratings 4

60 Hz Ratings 6

Rental Power Ratings 9

Definition of Diesel Ratings 10

Cat® Gas Generator Sets

50 Hz Ratings 14

60 Hz Ratings 16

Definition of Gas Ratings 19

Conversion Tables 22

Product Support Definitions 33

Product Support - Customer Support Agreements 34

Note Pages 36

Page 3: Cat Diesel Generators Specs

CAT® GENERATOR SETS diesel

Page 4: Cat Diesel Generators Specs

5

DIESEL 50 Hz

CAT 50 Hz DIESEL RATINGS, 2200 kVA - 17463 kVA

Prime

2425325048506500

1963260039255200

––

–––

––––––

Continuous

2200293844005875

177523633550472569889313

345646565238

65507638872598251309417463

Configuration––––– –––––––

–––

––––– –

Generator Set Model

3606360836123616

3606360836123616

12CM3216CM32

6CM328CM329CM32

6CM437CM438CM439CM4312CM4316CM43

1000 rpmStandby

2688357553757150

2163286343255725

––

–––

––––––

kVA

750 rpm

600 rpm

500 rpm

DIESEL 50 Hz

4

CAT® 50 Hz DIESEL RATINGS, 275 kVA - 3100 kVA

Prime

275320365365410455500545550591635680725810

10001150127513601450¹1500²160017001825200022752725

2825*

Continuous

––––––––––––––

910100012061320

––

1500–

1600175020002500

2600*

Configuration

Low BSFCLow BSFCLow BSFC

EU Stage II, Low BSFCEU Stage II, Low BSFCEU Stage II, Low BSFCEU Stage II, Low BSFC

Low BSFCEU Stage II

EU Stage II, Low BSFC, Low BSFCLow BSFCLow BSFCLow BSFC

Low BSFC, Low EmissionsLow BSFCLow BSFC

Low BSFC, Low EmissionsLow BSFC, Low EmissionsLow BSFC, Low EmissionsLow BSFC, Low EmissionsLow BSFC, Low Emissions

Low BSFCLow BSFC, Low EmissionsLow BSFC, Low Emissions

Low BSFCLow BSFC

Generator SetModel

3406C3406C3406C

C15 ACERTTM

C15 ACERTC15 ACERTC15 ACERTC18 ACERTC18 ACERTC18 ACERTC18 ACERT

3412C3412C3412C

C32 ACERT35123512

3512B3512B3512B

3512B-HD3512B-HD

35163516B

3516B-HDC175-16C175-16

1500 rpmStandby

300350400400450500550600605650700750800900

110012501400150016001600175018752000225025003000

3100*

kVA

¹ For voltages less than 5,000 volts² For voltages greater than 5,000 volts*Rating does not include package mounted radiator

Page 5: Cat Diesel Generators Specs

7

DIESEL 60 Hz

CAT 60 Hz DIESEL RATINGS, 275 ekW - 3100 ekW

Prime

275275320320365365410455–

50054559163568072591010001135127513601360160018251825

–225027252825*

Continuous

–––––––––––––––

8308901010123012301230145016401650

–205025002600*

Configuration

EPA Tier 3Low BSFCLow BSFC

EPA Tier 3, Low BSFC Low BSFC

EPA Tier 3, Low BSFC EPA Tier 3, Low BSFC EPA Tier 2, Low BSFC EPA Tier 2, Low BSFC EPA Tier 2, Low BSFC EPA Tier 2, Low BSFC EPA Tier 2, Low BSFC EPA Tier 2, Low BSFC EPA Tier 2, Low BSFC EPA Tier 2, Low BSFCEPA Tier 2, Low BSFC

Low BSFCLow BSFC

Low BSFC, Low EmissionsLow BSFC, Low Emissions

EPA Tier 2Low BSFC

Low BSFC, Low EmissionsEPA Tier 2

EPA Tier 1, Low BSFCEPA Tier 2

Low BSFC, EPA Tier 2Low BSFC, EPA Tier 2

Generator Set Model

C9 ACERTTM

3406C3406C

C15 ACERT3406C

C15 ACERTC15 ACERTC15 ACERTC15 ACERTC18 ACERTC18 ACERTC27 ACERTC27 ACERTC27 ACERTC27 ACERTC32 ACERT

35123512

3512B3512B3512C3516

3516B3516C3516B

3516C-HDC175-16C175-16

1800 rpmStandby

300300350350400400450500

550 (ESP)5506006507007508001000110012501400150015001750200020002250250030003100*

ekW

(ESP) Emergency Standby Rating *Rating does not include package mounted radiator

DIESEL 60 Hz

6

CAT 60 Hz DIESEL RATINGS, 12 ekW - 175 ekW

*All ratings at 1.0 pf **All ratings at 0.8 pf

Prime

121822273645547290

12161822273645557290

114136158

Generator SetModel

D13-4SD20-6SD25-8SD30-8SD40-6SD50-6SD60-8SD80-6S

D100-6S

D13-4D18-4D20-6D25-8

D30-10D40-6D50-6D60-6D80-6

D100-6D125-6D150-8D175-2

Engine

C1.5C2.2C2.2C2.2C4.4C4.4C4.4C4.4C4.4

C1.5C2.2C2.2C2.2C2.2C4.4C4.4C4.4C4.4C4.4C6.6C6.6C6.6

Configuration

EPA Tier 4 InterimEPA Tier 4 InterimEPA Tier 4 InterimEPA Tier 4 Interim

EPA Tier 3EPA Tier 3EPA Tier 3EPA Tier 3EPA Tier 3

EPA Tier 4 InterimEPA Tier 4 InterimEPA Tier 4 InterimEPA Tier 4 InterimEPA Tier 4 Interim

EPA Tier 3EPA Tier 3EPA Tier 3EPA Tier 3EPA Tier 3EPA Tier 3EPA Tier 3EPA Tier 3

Single Phase Output* 1800 rpmStandby

1320253040506080

100

131820253040506080

100125150175

ekW

3-Phase Output** 1800 rpm

Prime

180210225 225

Continuous

––––

Configuration

EPA Tier 3Low BSFCLow BSFCEPA Tier 3

Generator Set Model

C9 ACERTTM

3306B3306B

C9 ACERTTM

1800 rpmStandby

200230250250

ekW

CAT 60 Hz DIESEL RATINGS, 180 ekW - 250 ekW

Available only for North America

Page 6: Cat Diesel Generators Specs

9

DIESEL rental power ratings

CAT 60 Hz RENTAL POWER RATINGS, 18 ekW - 2000 ekW

Prime

1827415470901582102753655459109109101825

Continuous

–––––––––––––––

Configuration

EPA Tier 4 InterimEPA Tier 4 Interim

EPA Tier 3EPA Tier 3EPA Tier 3EPA Tier 3EPA Tier 3EPA Tier 3EPA Tier 3EPA Tier 3EPA Tier 2EPA Tier 2EPA Tier 2EPA Tier 2EPA Tier 2

Rental Generator Model

XQ20XQ30XQ45XQ60XQ80XQ100XQ175XQ230XQ300XQ400XQ600XQ1000PM1000RC1000XQ2000

1800 rpmStandby

2030456080100175

230* 300* 400*

600 1000*

100010002000*

ekW

*Also available at 50 Hz

DIESEL 60 Hz

8

CAT 60 Hz DIESEL RATINGS, 1650 ekW - 13970 ekW

Prime

1820242036404840

1525202030504040

––

–––

––––––

Continuous

1650220033004400

137518302750366055907450

276537254190

5240611069807860

1047513970

Configuration

––––

––––––––––

––––––

Generator SetModel

3606360836123616

3606360836123616

12CM3216CM32

6CM328CM329CM32

6CM437CM438CM439CM4312CM4316CM43

900 rpm

ekW

720 rpm

600 rpm

514 rpm

Standby

2000266040005320

1680220033604400

––

–––

––––––

Page 7: Cat Diesel Generators Specs

11

DIESEL ratings definitions

Prime PowerOutput available with varying load for an unlimited time. Average power output is 70% of the prime power rating. Typical peak demand of 100% of prime-rated ekW with 10% of overload capability for emergency use for a maximum of 1 hour in 12. Overload operation cannot exceed 25 hours per year. Prime power in accordance with ISO8528. Fuel stop power in accordance with ISO3046.

Continuous PowerOutput available without varying load for an unlimited time. Average power output is 70 - 100% of the continuous power rating. Typical peak demand is 100% of continuous rated ekW for 100% of operating hours. Continuous power is in accordance with ISO8528. Fuel stop power in accordance with ISO3046.

DIESEL ratings definitions

10

CAT DIESEL RATING DEFINITIONS

Emergency Standby Power (ESP)Output available with varying load for the duration of an emergency outage. Average power output is 70% of the emergency standby power rating. Typical operation is 50 hours per year with maximum expected usage of 200 hours per year. Standby power in accordance with ISO8528. Fuel stop power in accordance with ISO3046.

Standby PowerOutput available with varying load for the duration of the interruption of the normal source power. Average power output is 70% of the standby power rating. Typical operation is 200 hours per year, with maximum expected usage of 500 hours per year. Fuel stop power in accordance with ISO3046.

Page 8: Cat Diesel Generators Specs

CAT GENERATOR SETS gas

Page 9: Cat Diesel Generators Specs

15

GAS 50 Hz

CAT 50 Hz CONTINUOUS GAS RATINGS, 1606 kVA - 8150 kVA

CAT 50 Hz CONTINUOUS CHP GAS RATINGS, 1380 kVA - 2500 kVA

kVA1500 rpm

––

1944194419751986

––

24382458

––––––––

NaturalGas

G3606G3606

G3516C IM*G3516CG3516CG3516CG3608G3608

G3520CG3520C IM*

G3612G3612G3612G3612G3616G3616G3616

G16CM34

Low EnergyGas

–––––––––

G3520C†, ††, †††

––––––––

Propane––––––––––––––––––

kVA1000 rpm

16061712

––––

21432281

––

3212342535933625428145624825

kVA750 rpm

–––––––––––––––––

8150

kVA1500 rpm

13801456200025002500

NaturalGas

G3516BG3516BG3516EG3520CG3520E

Low EnergyGas

–––––

Propane–––––

kVA1000 rpm

–––––

GAS 50 Hz

14

CAT 50 Hz CONTINUOUS GAS RATINGS, 80 kVA - 1431 kVA

kVA1500 rpm

808387

106129133138156156200205215350450450600619620631637906931962963

10001200121812871287135613801431

NaturalGas

––

G3306 NAG3306 NA

––

G3306 TAG3306 TAG3406 NAG3406 TA

––

G3412 TAG3412C LE4006-23TRG3508 LEG3508 LE

4008-30TR52G3508 LEG3508 LEG3512 LEG3512 LE

–G3512 LEG3512EG3512E

G3516 TAG3516 TAG3516 LEG3516BG3516BG3516B

Low EnergyGas

G3306 NA†††

G3306 NA†††

––

G3406 NA†††

G3406 NA†††

––––

G3412 NA†††

G3412 NA†††

––

4006-23TR––

4008-30TR52––––

G3512 LE†, †††

–––––

G3516 LE†, ††

–––

Propane–––

––––––––––––––––––––––––––––

kVA1000 rpm

––––––––––––––––––––––––––––––––

*IM Island Mode

† Landfill †† Coal Mine Methane††† Non-Landfill Biogas

Page 10: Cat Diesel Generators Specs

17

GAS 60 Hz

CAT 60 Hz CONTINUOUS GAS RATINGS, 150 kW - 820 kW

kW1800 rpm

150177190191350–––

375375––––––––––––––––––––

NaturalGas

G3406 NA–

G3406 TA–

G3412 TAG3508 LEG3508 LEG3508 TAG3412 TAG3412C LEG3508 LEG3508 TAG3508 LEG3508 LEG3508 LEG3512 TAG3512 TAG3512 TAG3512 LEG3512 LEG3512 LE

––

G3516 TAG3516 TAG3516 TAG3516 LEG3516 LE

–G3516 LE

Low EnergyGas

–G3412 NA†††

–G3412 NA†††

–––––––––––––––––––––––

G3516 LE†,†††

Propane––––

G3412 TA–

G3412 TA–

G3412 TA––––––––––––

G3516 LEG3516 LE

–––––––

kW1200 rpm

–––––

360370370––

375380385390400555560570570585600695735750755770770795815820

GAS 60 Hz

16

CAT 60 Hz STANDBY GAS RATINGS, 150 kW - 1040 kW

CAT 60 Hz CONTINUOUS GAS RATINGS, 72 kW - 150 kW

kW1800 rpm

150240260275350375410435445450460470480495515

1040

NaturalGas

G3406 NAG3406 TAG3406 TAG3406 TAG3412 TAG3412C LE

–G3412 TA

–G3412 TAG3412 TAG3412 TAG3412 TAG3412 TAG3412 TAG3516 LE

Low EnergyGas

––––––––––––––––

Propane––––––

G3412 TA–

G3412 TA–––––––

kW1000 rpm

––––––––––––––––

kW1800 rpm

727585

100132135137140150

NaturalGas

––

G3306 NAG3306 NA

–G3306 TA

G3306 TAG3306 TA

Low EnergyGas

G3306 NA†††

G3306 NA†††

––

G3406 NA†††

–G3406 NA†††

––

Propane––––––

––

kW1200 rpm

–––––––––

††† Non-Landfill Biogas

† Landfill††† Non-Landfill Biogas

Page 11: Cat Diesel Generators Specs

19

GAS ratings definitions

CAT GAS RATING DEFINITIONS

Standby PowerThese ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. Natural gas ratings have been established on natural gas with net calorific Low Heat Value (LHV) of approximately 35.6 MJ/m3 (905 Btu/ft3) and 80 methane number (MN).

Continuous PowerOutput available without varying load for an unlimited time. Continuous power in accordance with ISO8528, AS2789, and BS5514. Natural gas ratings have been established on natural gas with net calorific Low Heat Value (LHV) of approximately 35.6 MJ/m3 (905 Btu/ft3) and 80 methane number (MN).

GAS 60 Hz

18

CAT 60 Hz CONTINUOUS GAS RATINGS, 1155 kW - 6520 kW

kW1200 rpm

–––––

1600––––––––––––––––

kW1800 rpm

––

13001400

–––

1660190020552055

–––––––––––

Low EnergyGas

–––––

G3520C †, †††

––––––––––––––––

NaturalGas

G3606G3606

G3516BG3516BG3608

G3520CG3608

G3516CG3520CG3520C

G3520C IM*G3612G3612G3612G3612G3612G3612G3616G3616G3616G3616

G16CM34

kW900 rpm

11551235

––

1540–

1640––––

2310231523352465259526153080310532853480

kW720 rpm

–––––––––––––––––––––

6520

*IM Island Mode

† Landfill††† Non-Landfill Biogas

Page 12: Cat Diesel Generators Specs

CONVERSIONS ratings guide

Page 13: Cat Diesel Generators Specs

23

CONVERSIONS

ELECTRICAL TABLES

Single-Phase

V x I x P.F.1000

V x I1000

kW .746 x EFF. (Gen)

HP x .746EFF. (Mot.)

HP x .746V x P.F. x EFF.

kW x 1000V x P.F.

kVA x 1000V

Poles x RPM120

V x I x 1-(P.F.)2

1000

100 (VNL-VFL)VFL

Three-Phase

1.732 x V x I x P.F.1000

1.732 x V x I1000

kW .746 x EFF. (Gen)

HP x .746EFF. (Mot.)

HP x .7461.732 x V x EFF. x P.F.

kW x 10001.732 x V x P.F.

kVA x 10001.732 x V

Poles x RPM120

1.732 x V x I x 1-(P.F.)2

1000

100 (VNL-VFL)VFL

To Obtain

kW

kVA

Horsepower required when kW known (Generator)

kW input when HP known (Motor)

Ampheres when HP known

Ampheres when kW known

Ampheres when kVA known

FrequencyHz

ReactivekVA (kVAr)

% VoltageRegulation

Direct Current

V x I1000

kW .746 x EFF. (Gen)

HP x .746EFF. (Mot.)

HP x .746V x EFF.

kW x 1000V

100 (VNL-VFL)VFL

Alternating Current

ELECTRICAL TABLE ABBREVIATIONS:

V - voltage in voltsI - current in amphereskW - power in kilowatts (actual power)kVA - kilovolt-ampheres (apparent power)HP - horsepowerRPM - revolutions per minute

kVAr - reactive kilovolt-ampheresEFF. - efficiency as a decimal factorNL - no loadFL - full loadP.F. - power factorNote: DC kW = DC kVA

CONVERSIONS

22

FUEL SYSTEM - DIESEL

Day Tank Sizing

Tank Size (gal) = Rated BSFC (lb/hp•hr) x Rated HP x Load Factor 7.076 (lb/gal)

x Hours Between Refilling+ Reserve Requirement

ORRule of Thumb for tank size with 25% reserve0.056 x Ave. BHP demand x Hours between refills x 1.25 = gal.0.27 x Ave. BKW demand x Hours between refills x 1.25 = liters.

Note: Additional tank capacity required for cooling of recirculated fuel in unit-injected engines. Tank should be located below level of injectors or nozzles.

On-Site Power RequirementsBased on 100,000 sq ft. of office bldg., etc and 40°N. Latitudes

• Electric Requirements 600 kW continuous load (Air conditioning is absorption) Use three - 300kW units (2 prime and 1 standby)

Refrigeration • One ton refrigeration = 200 Btu/min = 12,000 Btu/h • One Boiler hp = 33,475 Btu/h • One ton compressor rating = One engine hp • Auxiliary air conditioning equipment requires 1/4 hp/ton of compressor rating

Ice Plant • Complete power requires 4-5 hp per daily ton capacity

Air Compressor • hp = 1/4 x cu ft m/min at 100 psi Increase bhp 10% for 125 psi Decrease bhp 10% for 80 psi

• Air Conditioning and Compressor 400 tons prime load Use two - 200 hp engines (No Standby)

Page 14: Cat Diesel Generators Specs

25

CONVERSIONS

REDUCED VOLTAGE STARTERS

Type of Starter

Full Voltage Starter

Auto Transformer • 80% Tap • 65% Tap • 50% Tap

Resistor Starter Single Step

(adjusted for motor voltage to be 80%

of line voltage)

Reactor • 50% Tap • 45% Tap

• 37.5% Tap

Part Winding (low- speed motors only)

• 75% Winding • 80% Winding

Motor Voltage(% Line Voltage)

100

806550

80

5045

37.5

100100

Line Current (% Full Voltage)Starting Current

100

684630

80

5045

37.5

7550

Starting Torque(% of Full Voltage)

Starting Torque

100

644225

64

252014

7550

CONVERSIONS

24

THREE-PHASE CONNECTION SYSTEMS

Page 15: Cat Diesel Generators Specs

27

CONVERSIONS

ENGINE ROOM VENTILATION

Engine room ventilation can be estimated by the following formulas, assuming 100°F (38°C) ambient air temperature:

V (cfm) = H + Engine Combustion Air 0.070 x 0.24 x T

V (m3/min) = H + Engine Combustion Air 1.099 x 0.017 x T

V = Ventilation air (cfm) (m3/min).H = Heat radiation (Btu/min) (kW). T = Permissible temperature rise in engine room (°F) (°C).Density of air at 100°F = 0.070 lb/cu ft (1.099 kg/m3).Specific heat of air = 0.24 Btu/°F (0.017 kW/°C).

CONVERSIONS

26

COMPARISON OF REDUCED VOLTAGE STARTING METHODS

*Resistor starting adds considerable kW load to generator set. Total power required includes the motor kW and the kW which is lost as heat in the resistor. The series resistors account for a higher than normal starting power factor.

Characteristic

Starting Line Current at Same Motor

Terminal Voltage

Starting Power Factor

Power Draw from Line During Starting

Ease of Control

Maintenance

Line Disturbance

Autotransformer

Least

Increases slightly with speed

Motor momentarily disconnected from

line from start to run

Same

Same

Reactor

Same

Same

Two-Step Part Winding

Increases slightly with speed

Smooth

No provision for adjustment of starting current

Less than others

More than others

––– More than autotransformer type –––

––– Varies with conditions and type of load –––

––– More than autotransformer type –––

Increases rapidly with speed

Smooth. Transfer made with little change in

motor terminal voltage

Primary Resistor

Lower in small size- otherwise equal

Same

Same

Relative Cost

Smoothnessof Acceleration

Torque

Average Average Less than others

Low High* Low Low

Low

Page 16: Cat Diesel Generators Specs

29

CONVERSIONS

CONVERSION FACTORS

U.S. gal/min

1694.5448.84.40315.85

million U.S. gal/day

0.001 4401

0.06460.006 340.0228

ft3/s0.002 23

1.5471

0.009 810.0353

m3/h0.2270157.73101.9

13.60

L/s0.063143.828.320.2778

1

Flow

UnitU.S. gpm

1 million gal/dayft3/sm3/hL/s

MCFD = 1000 ft3/day MMCFD = 1,000,000 ft3/day lb/bhp-hr x 607.73 = g/kW-hr

1 Therm = 1,000,000 BtuBtu/ft2/min = 0.1220 Watts/in2

Btu/ft3 = 8.899 kg-cal/m3

Btu/lb = .5556 kg-cal/kg

Energy

UnitBTU

CalorieFoot-Pound

JouleKilocalorie

Therm

BTU1

0.003970.0012850.0009483.96825100,000

Cal2521

0.3237650.23895

1000396.8254

ft-lb778

3.088661

0.737453089

128.5347

J1055.056

4.1871.356

14185

94.78169

Kcal0.2520.001

0.0030890.000239

10.39682

Therm0.00001

–––

2.5191

CONVERSIONS

28

CONVERSION FACTORS

Unitmm2

in2

m2

ft2

mm2

1645.16

10 0000092903

in2

0.001551

1550144

m2

–0.000 645 16

10.0929

ft2

–0.006 944

10.7641

Area

mm1

25.4304.8914.41000

100 0000160 9340

in.03937

11236

39.370139 370.163 360

ft.0032810.083 33

13

3.280 843208.84

5280

yd.0010940.027 780.333 33

11.093 611093.61

1760

m.001

0.02540.30480.9144

11000

1609.34

km.0000 010.000 030.000 300.000 91

0.0011

1.609 34

mi––––

0.000 620.621 37

1

1 sq mile = 640 acres1 acre = 4840 yd2

1 cir mil = 7.854 x 10-7in2

1 cir mil = .7854 x mils21 cir mil = 5.067 x 10-6cm2

LengthUnitmminftydm

kmmi

1 grain = 0.064799 gram

––– Tons –––

Weight

Kilograms1

0.028350.4536907.21,0161,000

Unit1 Kilogram

1 Ounce1 Pound

1 Short Ton1 Long Ton

1 Metric

OuncesAvoirdupois

35.271

1632,00035,84035,300

PoundsAvoirdupois

2.2050.0625

12,0002,2402,205

Short–––1

1.121.102

Long–––

0.89291

0.9842

Metric–––

0.90721.016

1

Page 17: Cat Diesel Generators Specs

31

CONVERSIONS

CONVERSION FACTORS

CONVERSIONS

30

CONVERSION FACTORS

Unitmm/Hgin./Hgin. H20ft. H20lb/in2

kg/cm2

barkPa

mm/Hg(0°C)

125.4

1.868 2722.419251.7149735.559750.0627.500 62

in./Hg(0°C)

0.039 371

0.07 3550.882 652.036 0228.95929.530

0.295 30

in. H20(60°F)0.535713.61

112

27.70395

401.84.01835

ft. H20(60°F)

0.044641.134

0.083 331

2.30932.8433.49

0.33486

1 board-foot = 144 in3 1 bushel = 1.244 ft3 1 bushel = 4 pecks

Volume and Capacity

UnitBtu/minft-lb/min

HorsepowerJoules/minMetric hpKilowatt

Watt

Btu/min1

0.0012842.4560.0009541.827

590.05687

ft-lb/min778.2

1330000.7405325504425044.25

hp0.023580.00003

10.0000223

0.986321.341020.00134

Unitin3

ft3

yd3

mm3

m3

U.S.gallmp gal

literacre-ft

in3

11728

466566.1 x 10-5

61 023.7231

277.41961.023 7

ft3

0.000 58127

4.0 x 10-8

35.31470.133 680.160 540.035 3143 560

yd3

0.000 020.037 04

1–

1.307 950.004 950.005 950.001 311613.33

mm3

16387.128 320 000764 554 858

11,000,000,000

378542045400901000 000

Volume and Capacitym3

0.000 020.028 320.76455

–1

0.003 780.004 55

0.0011233.48

U.S. gal0.004 327.480 52201.974

2.6 x 10-7

264.1921

1.200 950.264 17325 851

lmp gal0.003 615.228 83168.178

2.2 x 10-7

219.969–1

0.219 97271 335

liter0.0163928.3169764.555

1.0 x 10-6

10003.785 414.546 09

1–

J/min1055.0001.350444791

14412759997

59.9968

Metric hp0.023910.000031.014

0.00002261

1.359620.00136

kW0.01758430.00002260.74570

0.00001660.73549

10.001

W17.58430.0226745.7

0.016668735.498

10001

Power

lb/in2

0.019 340.491 150.036 130.433 52

114.225714.504

0.145 038

kg/cm2

0.001 360.034 530.002 540.030 4790.070 31

11.019 72

0.010 1972

bar0.001 330.033 860.002 490.029 890.068 950.980 67

10.010 000

Atmospheres 101.4Pa (14.7 psi)

0.001 3150.033 420.002 460.029 500.068 050.967 840.98692

0.009 869 20

kPa––

0.2492.9896.89598.067101.325

1

Pressure and Head

Page 18: Cat Diesel Generators Specs

33

PRODUCT SUPPORT CONVERSIONS

32

CONVERSION FACTORS PRODUCT SUPPORT DEFINITIONS

Note: Code letters apply to motors up to 200 HP.

Temperature Conversion°F = (1.8 x °C) + 32

°C = 0.5555 (°F - 32)

Angle1 quadrant = 90 degrees1 quadrant = 1.57 radians1 radian = 57.3 degrees1 degree = 60 minutes

1 minute = 2.9 x 10 radians

NEMA Code Letter

ABCDEFGHJKLMNPRSTUV

Starting skVA/hp

0.00 - 3.143.15 - 3.543.55 - 3.994.00 - 4.494.50 - 4.995.00 - 5.595.60 - 6.296.30 - 7.097.10 - 7.998.00 - 8.999.00 - 9.99

10.00 - 11.1911.20 - 12.4912.50 - 13.9914.00 - 15.9916.00 - 17.9918.00 - 19.9920.00 - 22.39

22.40

Identifying Code Letters on AC Motors

Extended Service Coverage (ESC)

Depending on the engine model and application, Silver, Gold or Platinum & Platinum Plus coverage levels are available from Cat Insurance with terms extended up to 60 months and 25,000 hours.

Equipment Coverage Option New engines ESC Used engines Advantage Overhauls OPC*

Electric Power Extended Service Coverage reimburse 100% of the parts at customer list price, labor at selling rates and travel & mileage charges (less any deductibles) for covered repairs. Available worldwide, Extended Service Coverage (ESC) provides 100% of usual and customary parts and labor costs for system failures due to defects in materials and workmanship on covered components over the duration of the agreement period.

*Overhaul protection coverage

Page 19: Cat Diesel Generators Specs

35 34

A • Customer Support Agreement (CSA) is an arrangement between the end user and the Cat Dealer that helps lower the cost per unit of production.

Agreements are tailored to fit your business needs and can • range from simple Preventive Maintenance Kits to sophisticated Total Cost Performance Guarantees.

Trained dealer technicians assist you by maintaining your • equipment and driving down operating costs. Perhaps the most important feature of any CSA is flexibility.

A • Preventive Maintenance (PM) agreement covers specified maintenance at a fixed cost. You maintain reliability and efficiency because the maintenance is performed by highly skilled technicians at guaranteed costs, giving you the ability to budget more accurately.

A • Total Maintenance and Repair (TM&R) agreement covers all of the maintenance and repair costs. Instead of paying for maintenance or repairs as they are needed, you pay one flat rate to cover a broad range of parts and services.

Check with your local Cat dealer for available options with each agreement.

PM TM&R

Detailed inspections by highly skilled technicians

✔ ✔

Scheduled maintenance

✔ ✔

Labor and travel costs ✔ ✔

Use of genuine Cat parts, fluids and filters

✔ ✔

S•O•SSM Services and interpretation

✔ ✔

Component repairs ✔

All unscheduled repairs, including wear out, with no exclusions, limitations or deductibles

PRODUCT SUPPORT PRODUCT SUPPORT

CUSTOMER SUPPORT AGREEMENTSCUSTOMER SUPPORT AGREEMENTS

Page 20: Cat Diesel Generators Specs

NOTESNOTES