Click here to load reader
Upload
ricardo-fuentes
View
214
Download
0
Embed Size (px)
DESCRIPTION
override
Citation preview
Cascade, Override, Constraint, Ratio, Split Range Refer to DeltaV books on-line as well as your text
Cascade Control p. 310 to 322
Two Controllers, two process transmitters, one valve working toward a master control objective. Experiment 1 demonstrates the need, cascade controllers are used in Experiment 2, but not tested there.
A primary, (a.k.a. outer, master loop) controller output is used to set the set point of a secondary, (a.k.a. inner, slave loop) controller
Frequently used to prevent utility disturbances from affecting the process
Rule of 5, (see McMillan's rule of five) inner loop should be 5 times faster than the outer loop
Note example on p.319, 320
Override or Constraint p. 340 – 346
Override - Two controllers, two transmitters, one valve, working to control to two different objectives.
In Experiment 1, our objective is to control the level at some valve as well as prevent the flow from exceeding a controlled rate. We configure an override control using the control selector block, CTLSL.
This method allows one controller to "take control" over the other.
Constraint Control – In Experiment 3 we will control the valve position of the maximum % open valve of both flow loops at 90% by controlling the pressure controller's set point. Method used for energy reduction, if we had a variable speed pump as a supply, subject of future lecture.
Constraint Control Examples
TemperatureControl
UtilityReturn
Cooling Utility
SGSL
FC
IVP
Variable Speed Control
Fed Batch Constraint Control
Ratio Control p. 333 Permits a second controller to follow a ratio of a master flow controller..
Example: pH control, pH controller output setting a ratio of the reagent flow to the effluent flow. Effluent flow disturbances can adjust the reagent flow rather than have the pH change and adjust the reagent flow.
Split Range - The Splitter (SPLTR) function block This block is used to define the action of two valves from a single controller.
Example: A vessel that needs heating and cooling, half of the output action is devoted to cooling while half is devoted to heating. Also called "Split Range" Can be set by valve position control settings.
TemperatureControl
JacketUtility
Supply
UtilityReturn
Steam
Cooling Water
SPLTR