Protection and control
Smart earth leakage protection
P.1/2
8/11/2019 Ca_P1_03
2/42
Smart earth leakage protection
P.1/2
/2-2
Introduction 5
P.1 - Industrial earth leakage protection
Product selection table 13
WG
Earth leakage transformers, WG series 15
RGE / RGE-R
Electronic earth leakage relay with external transformer of the WGSeries 16
RGU-10 / RGU-10 C
Electronic earth leakage relay with external transformer of the WGSeries 18
CBS-4 / CBS-4 C
Earth leakage monitoring and signaling unit of the external transformer of the WGSeries 20
CBS-8
Earth leakage monitoring and signaling unit of the external transformer of the WG / WGPSeries 22
WGP
Earth leakage Transformers of the WGPSeries (only for CBS-8) 24
WN
Earth leakage transformers, WN series 25
RN / RN-R
Electronic earth leakage relay with external transformer of the WNSeries 26
RN-10
Electronic earth leakage relay with external transformer of the WNSeries 28
WRU
Earth leakage relay with built-in transformer (type A) 30
WGBUTransformer with built-in earth leakage relay 32
WRN-22
Earth leakage relay with built-in transformer 35
Relation between products and accessories 37
P2- Self-reclosing overload and earth leakage protection
Earth leakage protection and self-reclosing
REC2
Self-reclosing earth leakage relay P2-47
8/11/2019 Ca_P1_03
3/42
Earth leakage protection P.1/2
P1/2-5
The "protection" and "continuity" of the
electrical power supply are two terms
that must not be separated if we wish to
guarantee the safety of users and elec-
trical installations.
The recent addition of receivers or loads
that generate distortion in the electricity
grid (speed variators, electronic start-
up units, computer equipment, lighting
with electronic ballasts, etc.) has made
necessary the use of protection systems
that can distinguish between defects in
the installation and the electrical altera-
tions that cause the unwanted tripping
of protection systems.
The new range of earth leakage pro-
tection products offers state-of-the-art
performance to guarantee the continuity
and safety requirements:
Smart earth leakage protection
} Monitoring in true root mean square.
} High frequency ltering
} Inverse curve delay (instantaneous
and selective)
} Adjustment of the nominal sensitivity
trigger
} Display of the fault current (monitor-
ing of protection systems)
Monitoring the status of protections al-
lows us to do the following in the electri-
cal installation:
} Analyse the insulation conditions.
} Preventive and corrective mainte-
nance.
} Reduce production downtime. De-crease maintenance costs. Quick loca-
tion of faults.
P.1/2
Protection
Immunised protection
Immunised protection
Monitoring
Immunised protection
Monitoring
Remote control
Reset
4 earth leakage protection methods
SAFETY OF
PERSONS AND
MATERIALS
SAFETY OF
PERSONS AND
MATERIALS
CONTINUITY
ELECTRICAL
POWER SUPPLY
8/11/2019 Ca_P1_03
4/42
.1/2 Earth leakage protectionP
1/2-6
When the earth leakage protection sys-
tem detects a fault current, it acts on the
electrical installation being protected,
opening the circuit while interrupting
the supply of electrical energy, thus pre-
venting the danger of electrocution for
persons when the fault current reaches
dangerous values, either as a result of
direct or indirect contact, including any
potential damage caused to goods and
materials.
An earth leakage protection system is
composed of three clearly different parts:
} Detecting element or sensor
} Relay} Circuit breaker
Detecting element or sensor: Cur-
rent transformer that detects the earth
leakage current of active conductors in
an installation, sending a proportional
signal to the relay. It can have a toroidal
or rectangular geometry, depending on
the arrangement of plates or the wiring
of the installation location.
The correct operation of the sensor re-
quires the path of capacitors to be as
perfectly aligned as possible.
Relay: Smart protection element. It
measures and treats the signal received
Denition
Nowadays, "sympathy" or unwanted
triggers are quite common in modern in-
stallations. In these cases, one or more
earth leakage switches are triggered si-multaneously, protecting an installation
from the leakage currents sent to earth
as a result of capacitive effects caused
by the installation.
Said capacitive effects can explained by
two reasons:
} The installation's cables cause earth-
ing condensation effects. The longer the
cable, the greater the capacity effect
} The capacitors of EMI lters in the
equipment with electronic power regula-
tion
Immunised earth leakage protection
by the sensor and either sends the trigger
signal to the associated circuit breaker
or not, depending on the sensitivity and
delay time values programmed.
Circuit breaker: This element acts as
the current interrupting element. It can
be a circuit breaker (with trigger coil), a
contact, etc.
These three elements can be found in
CIRCUTOR's products with different
congurations:
} All elements separately
} Relay with internal transformer
The different loads or consumption of an
installation can be classied in two main
groups, depending on the type of insula-
tion from earth:
Loads with no earthed capacitors
The insulation existing between the unit
and the earthing elements can be rep-
resented with a pure Ohmic resistance.
If the resistance is not high enough, no
current will pass through the earthing
elements. The leakage current is zero
(current passing to earth under normal
conditions).
In case there is an insulation fault, cur-
rent will pass through earthing elements,
the so-called fault earthed current, Id.
8/11/2019 Ca_P1_03
5/42
Earth leakage protection P.1/2
P1/2-7
In this case, we must simply adjust the
sensitivity and delay time to guarantee
the adequate protection.
Loads with earthed capacitors
The current passes through the earthing
elements as a result of the unit's opera-
tions through its capacitors. In addition,
the length of cables in an electrical in-
stallation can lead to capacitive earthing
faults, which would lead to this situation.
The current can be injected with two
methods:
Permanent Leakages.
The unit injects current in the earthingelements permanently. This type of be-
haviour is closely tied to the use of EMI
lters, which are installed in most ma-
chines or loads with electronic power
regulation, in order to comply with the
electromagnetic compatibility directives.
This type of lter prevents the high fre-
quency distortion generated by the re-
ceiver from being returned to the grid.
However, it is transferred through the
earthing capacitors. It also transfers in-
directly the fundamental frequency and
its corresponding harmonics, so that the
leakage is usually a set of overlapping
high and low frequency signals. There-
fore, it increases the risk of an earth
leakage trip with no real earth leakage
current.
Transient Leakages.
It has the same capacitive effects of ca-
bles and the lters mentioned above for
transient overvoltages caused by grid
switching effects, the connection-dis-
connection of circuits or effects that are
simply caused by atmospheric agents.
In case of loads with earthed capaci-
tors, the basic problem for the protec-
tion of the system is to distinguish whichearthed current is part of the unit's op-
eration and which is part of an insulation
defect. Electromechanical earth leak-
age relays do not usually solve these
situations.
The immunised earth leakage protection offered by CIRCUTORhas evolved in relation
to ve factors, in order to satisfy the needs of our customers, catering for the current
demand as regards the safety and continuity of the supply of electricity:
} MEASUREMENT IN TRUE ROOT MEAN SQUARE (TRMS) AND CLASS A
} IMMUNE TO TRANSIENT LEAKAGES
} HIGH FREQUENCY FILTERING
} ADJUSTMENT OF THE TRIGGER OF In
} INVERSE CURVE
8/11/2019 Ca_P1_03
6/42
.1/2 Earth leakage protectionP
1/2-8
Measurement in TRMS and Class A
The voltage and current wave shapes
have stopped being complete sine
waves since the loads distributed in the
installations are not linear. The continu-
ous and harmonic components can dis-
tort the wave shapes, whereby it will be
necessary to take more accurate meas-
urements.
The current range of electronic earth
leakage switches measures the root-
mean-square-value (TRMS) of leakage
currents by sampling it.
The wave shapes in installations with
linear resistive loads are pure sine-
waves. However, the gure shows howthe mean value will not work to measure
the root-mean-square-value with ac-
curacy when it stops being a complete
sine-wave.
In accordance with these problems,
the IEC 61008-1 Earth Leakage Switch
Standard determines the types of op-
eration, depending on the type of wave.
Two types are dened, Class AC and
Class A.
CLASS AC
The earth leakage devices used in do-
mestic installations or that protect loads
that do not cause distortions can be of
the AC Type. These devices are marked
with a symbol, in compli-
ance with the IEC 61008-1
Standard.
CLASS A
In the presence of non-linear receivers,
Type A earth leakage protection sys-
tems must be used, which means that
rectied currents can be measured with
a continuous component of up to 6 mA,
including non-distorted currents (AC
type), marked by the cor-
responding IEC 61008-1
Standard.
The IEC61008-1Standard denes two
types of ray-type curves to check thecorrect operation of an earth leakage
device: an overload and an overvolt-
age wave. The overload wave shows
the effects caused in the measurement
of the earth leakage device and the ov-
ervoltage wave shows the effects in the
power supply.
Immunity against transient leakages
The behaviour of earth leakage pro-
tection units in the case of transientoverloads and overvoltages is vital to
maintain the continuity in the supply of
electricity. Therefore, the immunised
earth leakage protection relays manu-
factured by CIRCUTOR can support
very high peaks.
Voltage: Curve 1.2 / 50 s: 4 kV
Current: Curve 8 / 20 s: 5 kA
8/11/2019 Ca_P1_03
7/42
Earth leakage protection P.1/2
P1/2-9
High-frequency current
Adjustments of In
The IEC 479-1/ UNE 20-572-92Stand-
ard describes the effects of currents
passing through the human body for
a frequency of 50 Hz. As you can see,
the effect depends on the root-mean-
square-value of the current passing
through the body and the time it takes
to pass through. In accordance with the
effects, we can establish zones 1 (zone
with no perception) and 2 (perception
zone) as safe work zones. Therefore, in
terms of the protection of persons, earth
leakage protection systems must act on
those zones.
When the frequency increases, the
curves are displaced to the right of the
a.Perception threshold
b."No-drop" threshold
c1 / c2 / c3. Fibrilation threshold
1.No perception
2.Perception
3.Reversible effects. Muscle tetany
4.Potentially irreversible effectsDelaytime
Sensitivity
FrequencyfactorF
f
Frequency f
The following graphs show that with an
identical evolution of the fault earthed
current in the same installation, the be-
haviour of the earth leakage switch is
different, even when the sensitivity level
of Inis the same in both cases.
This adjustment of In
allows us to con-
centrate more loads that incorporate
earthed capacitors within the same line
being protected. For example, in a com-
puter installation: Each unit diverts a
current, Ileakage
, of 2 mA through the EMI
lter capacitors included. At a sensitiv-
ity of (In
) 30 mA, you can install 7 com-
puters with the electromechanical earth
leakage switches. However, if you use
CIRCUTOR's electronic switches youcan install a total of 12.
FaultearthedcurrentI
d
100 % In
50 % In
Time, t
Faultea
rthedcurrentI
d
100 % In
85 % In
Time, t
The IEC 61008-1 Standard species
that earth leakage switches must be
triggered when the fault earthed current
is between 50% and 100% of the sen-
sitivity value (In
) selected. This means
that the values that exceed 50% canset off the earth leakage switch trig-
ger. This type of case is common with
electromechanical switches. In the case
of electrical energy installations, these
have evolved in such a way that the ad-
justment of protection can cause great
problems, since it is too low. The elec-
tronic earth leakage protection systems
offered by CIRCUTOR determine the
trigger near 100 % of In
.
Therefore, we have a lower risk of trig-gers and less interruptions in the instal-
lation's supply than when the fault cur-
rent is lower than In
.
previous graph, which indicates that the
current is less dangerous.See the table
attached, in accordance with IEC 479-2/
UNE 20-572-93, where a fault current
of, for example, 45 mA at 500 Hz has
the same effect as a fault current of 30
mA at 50 Hz. In the case of receivers
with EMI lters, we can consider that
these inject a high-frequency earthed
current (>2 kHz) and a low frequency
current. The use of type A earth leakage
protection systems is specied in these
cases.
8/11/2019 Ca_P1_03
8/42
.1/2 Earth leakage protectionP
/2-10
Inverse curve
Monitoring protection elements
Remote control and reset
The IEC 61008-1Standard allows us to
incorporate a circuit opening delay for
the circuit being protected, which will
depend on the leakage current level.
Therefore, the greater the fault current,
the lower the delay.
Two types of curves are specied, as
shown on the following table of values:
} Instantaneous
} Selective
The application of these curves to our
earth leakage systems can be used to
increase the continuity in the installa-
tion's power supply and avoid unwantedtrips.
The leakage current value must be
available at all times in many applica-
tions. This information is quite useful for
the installation's preventive and correc-
tive maintenance tasks, since we can
act before triggers are set off.
For example, if the insulation degree of
a machine is reduced, the earth leakage
current increases, and since we have
the said information, we can implement
the appropriate corrective actions to
avoid the trigger from being set off.
The idea is to integrate the earth leaka-
ge currents in the installation's energy
control system, thus controlling an addi-
tional quantity.
Depending on the type of product, the
information can be presented as fo-
llows:
} In the earth leakage relay, through
the display.
} Through the RS-485 communica-
tions system.
} With an auxiliary measurement unit.
In addition, records and logs of the in-
sulation behaviour of the installation can
be taken.
In the case of earth leakage protection
systems in installations that require a
continuous supply of energy, with no
maintenance staff present, the remotecontrol and reset (or self-reclosing)
functions are very useful.
Remote control functions can be carried
out through communications systems
(RS-485, Ethernet, etc.), using the Power-
Studio Scada software. This function cancontrol the status of protection systems
and perform a set of actions through a
computer and communications systems.
Type Instantaneous Selective
In
(A) All values > 0,03
S
tandardisedoperatingtimevalues(s)
In
0,3 0,5
2 . In
0,15 0,2
5 . In
0,04 0,15
500 A 0,04 0,15
Maximum
t
Id In
8/11/2019 Ca_P1_03
9/42
Earth leakage protection P.1/2
P1/2-11
Earth leakage protection systems with self-reclosing
Given the current efcient personal and
material protection requirements and
obligations, and the complexity of some
installations that require the continuous
supply of electrical energy with the use
of overload and earth leakage protection
systems, CIRCUTOR has developed a
wide range of units that make safety and
service continuity compatible.
Self-reclosing systems are an ideal solu-
tion for installations that need a constant
supply of electrical energy, without the
need for the usual maintenance staff:
} Rural installations} Refrigeration chambers
} Public lighting
} Mobile telephony repeaters
} Trafc lights
} Lighting of tunnels
} ATMs
} Cable television
} Etc.
The type of protection element installed,
those that can be reclosed and under
which reclosing conditions must be known
by all self-reclosing systems.
Self-reclosing systems act in accord-
ance with the following:
} Earth leakage current (earth leakage)
} Earth leakage current (earth leakage) +
overload and short-circuit (circuit breaker).
Elements that form an self-reclosing system
Earth leakage transformer
The earth leakage transformer detects
the earth leakage. It can be built-in on a
relay or as an external element.
Self-reclosing relay
Self-reclosing relays add a series of
performance features (self-reclosing,
thermal or overload protection) to the
proven reliability and security of non-re-
closing earth leakage protection relays.
It performs the following functions:
} Detection of anomalies (earth leak-
age or overload) through the signal gen-
erated by the transducer.
} They analyse the anomaly to see if it
must generate an alarm, depending on
the parameters programmed.
}They also act on power elements,
which perform the grid load connection-
disconnection tasks.
Circuit breaker
The circuit breaker always interrupts the
ow of power, which supports the power
in the line protected and is an external
element of the relay.
The circuit breakers that can be asso-
ciated to self-reclosing relays are as
follows:
} Motorized circuit breaker (MT)
} Contact circuit breaker with remotecontrol (MCB), with a dual circuit break-
er and contact function (the function of
the contact is bistable).
Features of the circuit breaker:
} Nominal current (in contacts)
} Nominal current and thermal protec-
tion curve (in circuit breakers)
} Features of the control inputs of the
operational element
}Circuit-breaking power} Auxiliary NO or NC signalling of the
circuit breaker's status
TRANSFORMER
RELAY
Treatment of the signal,
measurement and t rigger
CIRCUIT BREAKER
monitored
8/11/2019 Ca_P1_03
10/42
.1/2 Earth leakage protectionP
/2-12
Parameters related to self-reclosing relays
Relay status indicator
The indications are associated to the
type of protection, distinguishing be-
tween instantaneous triggers and inter-
lockings. The indications are sent by the
relay (LED) and, optionally, by auxiliary
contacts.
Another type of visualisation, depending
on the relay, is the instantaneous trigger
value and the number of total reclosures.
Nominal trigger point of protec-
tions
Standard values:
} Earth leakage protection 30 mA - 3 A
} Overload protection 6 A - 63 A
Timer (delay)
Minimum time that the earth leakage
must last before setting off a relay trig-
ger.
Standard values: 20 ms - 1s.
Relay power supply and tolerance
Self-reclosing relays need a permanent
form of auxiliary power supply in order to
manage the self-reclosing operations.
} Standardised value: 230 Vac 15 %
} Optional: 48, 110 or 400 Vac
Reclosing meter reset time.
To avoid the accumulation of triggers thatdo not correspond to the same anomaly,
a reset time is dened for the reclos-
ing meters, provided that the maximum
number of reclosures is not exceeded.
Example: The WRU-25 RArelay has a
maximum number of reclosures available
before being pushed to its interlocking.
In installations with a transient earth leak-
age fault that lasts 50 seconds, the relay
is triggered 4 times and reclosed 3 times(8 s + 16 s + 30 s). During the timing of
the third self-reclosing, the fault disap-
pears, so that the relay will remain in the
ON position. This is when the reset timer
of the reclosing meter will be set off.
The RESET option starts the relay, reset-
ting the reclosing meters.
Local (with the keys) and remote
test and reset
Self-reclosing earth leakage relays offer
the same performance as non-reclosing
relays. It enables the verication of the
correct operation of the relay with local
TEST and RESET functions, using the
keys on the relay, including remote func-
tions with specic inputs.
The RESET option resets the relay and
the reclosing meters.
Number of reclosures, distin-
guished by type and number of
self-reclosing
Each relay enables a maximum number
of reclosures before setting off the in-
terlocking. The meter will be reset au-
tomatically if the maximum number of
reclosures is not exceeded within a pre-
established period of time (reset time of
reclosing meters).
This number will be different, in accord-
ance with the type of self-reclosing.
Output relay
} Number of relays
} With interlocking
} NO or NC Output contact
Time between reclosures
Time the relay takes between the trigger
and the self-reclosing. It can be linear or
exponential.
8/11/2019 Ca_P1_03
11/42
.1Industrial earth leakage protection P
P1-13
Product selection table
Equipment External toroidal Internal toroidal No. of outputs Indications Communications In(A) Page
RG1
M16
RGE/RGE-R Type WG
- 1 LEDs -Dependingon the type0.03 ... 5 A
18
RGU-10/
Type WG
- 1 + pre-alarm DisplayOnly for typeRGU-10 C
0.03 ... 3 A0.3 ... 30 A 20
CBS-4/
Type WG
- 4 + pre-alarm DisplayOnly for type
CBS-4 C0.03 ... 3 A0.3 ... 30 A 22
CBS-8
Type WG-WGP
- 8 + pre-alarm Display Yes0.03 ... 6.3 A0.3 ... 63 A 24
RN1M 28
RN/RN-R
Type WN
- 1 LEDs -Depending on thetype 0.03 ... 5 A 30
RN-10
Type WN
- 1 + pre-alarm LEDs - 0.03 ... 3 A 32
WRU-10
-Dependingon the type25 - 35 mm
1 LEDs - 0.03 ... 3 A 34
WGBU/
- 35 ... 210 mm 1 LEDs - 0.03 ... 3 A 38
WRN-22
- 22 mm 1 LEDs -0.01 A
0.03 A0.3 A 41
8/11/2019 Ca_P1_03
12/42
.1 Industrial earth leakage protectionP
-14
8/11/2019 Ca_P1_03
13/42
.1Industrial earth leakage protection P
P1-15
Useful diameter(mm)
Weight(g) I
n(A) Type Code
20 76 acc. relay WGS-20 P10131
30 95 acc. relay WGS-30 P10132
35 181 acc. relay WG-35 P10111
70 274 acc. relay WG-70 P10112
105 545 acc. relay WG-105 P10113
140 1 222 acc. relay WG-140 P10114
210 2 040 acc. relay WG-210 P10115
70 x 175 2 400 acc. relay WG-70x175 P10116
115 x 305 5 450 acc. relay WG-115x305 P10117
150 x 350 7 400 acc. relay WG-150x350 P10118
200 x 500 13 400 acc. relay WG-200x500 P10119
References
WG Series Earth Leakage transformers
WG
WGS Dimensions
WG Dimensions
Type A B C D E
WG-35 100 79 26 48,5 35
WG-70 130 110 32 66 70
WG-105 170 146 38 94 105
WG-140 220 196 48,5 123 140
WG-210 299 284 69 161 210
Type A B C D E F G H I
WG-70X175 70 175 225 85 22 46 261 176 7,5
WG-115X305 115 305 360 116 25 55 402 240 8
WG-150X350 150 350 415 140 28 55 460 285 8
Type A B C D E F G H I
WG-200X500 200 500 - 140 - 62 585 285 -
WGS-20
WGS-30
WG Series
Description
The earth leakage transformers of the WGSeries have been designed
to work with the relays of the WGSeries. The sensitivity (trigger current)
of the transformer-relay set is established by the associated relay.
8/11/2019 Ca_P1_03
14/42
.1/2 Earth leakage protectionP
1-16
Electronic earth leakage relay with externaltransformer of the WG Series
RG1M
Proteccin
Class A superimmunized
Measurement True root mean square (TRMS)
Sensitivity 30 or 300 mA
Delay 20 ms
Earth leakage transformer External WGSeries
Test and Reset With built-in buttons, T & R
Remote Control External Test Option
Associated circuit breakerContactor or automatic circuit breaker using a coiltrigger
LED indicator Power supply voltage Leakage trigger Disconnection of external transformer
Circuit breaker controlThrough a NO/NC switched relay, dependingon the connection with the circuit breaker
Features
Auxiliary power supply 230 Vac ( 20 %) 50 / 60 Hz
Output contacts 250 Vac, 6 A
Operating temperature -10 ... +65 C
Construction f eatures
Fixing DIN Rail 46277 (EN 50022)
Dimensions 1 module
Weight 85 g
Degree of protection IP 20 terminals
Standards
IEC 60947-2, IEC 60755, IEC 62020, IEC 61008
Application
The RG1M relays combined with the WG
transformer provides complete differential
protection, both on single-phase and three-
phase lines.
FeaturesDescription
WG series electronic differential protection
relay for connection to external WG/WGSse-
ries toroidal transformers
} These are highly reliable electronic relays
with the option of a xed or adjustable sensi-
tivity and delay
} Measurement using true root mean squa-
re (TRMS) value
} DIN 46277 (En50022) Rail mounting
} Reduced one module size.
} LED status indication.
y Power ON LED.
y Leakage led ON. Tripped relay.
y Power LED ashing and leakage LED
ON. Detection of a transformer continuity
fault
WG Series
8/11/2019 Ca_P1_03
15/42
Earth leakage protection P.1/2
P1-17
Size Attachment In(A) Delay Type Code
1 modules DIN rail 0.03 0.02 s RG1M-0.03 P12204
1 modules DIN rail 0.3 0.02 s RG1M-0.3 P12214
References
Dimensions
Connections
Electronic earth leakage relay with externaltransformer of the WG Series
RG1M
WG Series
66 mm
72 mm 17.5 mm
45mm
64mm
90mm
TypeWG
1S11S2
7 8
1 2
3 4
5 6
RG1M
230V;5A
50/60 Hz230 V20%
Test / Reset
NL1 L2 L3
TypeWG
1S11S2
7 8
1 2
3 4
5 6
RG1M
230V;5A
50/60 Hz230 V20%
Test / Reset
NL1L2 L3
- Rearme manual.Disparo por BOBINA DE MNIMA
CARGA
Disparo por BOBINA DE EMISIN
CARGA
- Rearme manual.
8/11/2019 Ca_P1_03
16/42
.1 Industrial earth leakage protectionP
-18
Electronic earth leakage relay with externaltransformer of the WG Series
RGE/ RGE-R
Protection
Class A superimmunized
Measurement True root mean square (TRMS)
Sensitivity0.03 A / 0.3 A / 0.5 A / 0.03 ... 3
A (R1) / 0.03 ... 5 A (R)
Delay 0.02 / 0.02 ... 1 s (R1) / 0.02 ... 5 s (R)
Earth leakage transformer External, TRANSFORMERS WG
Test and Reset With built-in buttons, T & R
Remote Control External Test Option
Associated circuit breaker Contact or Circuit breaker + trigger coil
LED indicator Power supply voltage Trip due to leakageDisconnection of theexternal transformerPre-alarm (R-R1)
Display View -
Remote signaling -
Circuit breaker controlThrough an NO/NC switched relay, dependingon the connection with the circuit breaker
Features
Auxiliary power supply230 Vac ( 20 %) 50 / 60 Hz(other values on demand)
Output contacts 250 Vac, 6 AOperating temperature -10 ... +50 C
Construction f eatures
Fixing DIN Rail 46277 (EN 50022)
Dimensions 2 modules
Weight 163 g
Degree of protection IP 20 Terminals, IP 41 back panel
Standards
IEC 664, VDE 0110, IEC 801, UL 94, IEC 348, IEC 571-1, EN 61000-6-3, 61000-6-1, 61010-1Application
The relays of the RGEseries and the trans-
former of the WG series enable a full earth
leakage protection for both single and three-phase lines. They guarantee maximum se-
curity and continuity of the electrical service,
avoiding unwanted tripping.
FeaturesDescription
Electronic earth leakage protection relay,
used to connect to the earth leakage trans-
formers WG Series
} These electronic relays offer a high reli-
ability, with the option of a xed or adjustable
sensitivity and delay
} Type A relay with high frequency current
ltering and high immunity. Monitoring of the
true root mean square (TRMS)
} Assembly on DIN rail 46277
} Reduced size: 2 modules
} LED indicators:
y Permanently lit leak indicator
y LED: Trigger relay
y Flashing power LED and lit leak LED:
detection of faults in the transformer's con-
tinuity
y Flashing leak LED indicator (only RGE-R
and RGE-R1): Leak with a value under the
value selected
y 1 ash every 2 s: 25 ... 50 % of the leak-
age current
y 1 ash every 1 s: 50 ... 75 %
y 2 ashes every 1 s: 75 ...
8/11/2019 Ca_P1_03
17/42
.1Industrial earth leakage protection P
P1-19
Size Fixing In(A) Delay Type Code
2 modules DIN rail 0,03 0.02 s RGE-0.03 P12201
2 modules DIN rail 0,3 0.02 s RGE-0.3 P12211
2 modules DIN rail 0,03 ... 3 0.02 ... 1 s RGE-R1 P12231
2 modules DIN rail 0,03 ... 5 0.02 ... 5 s RGE-R P12232
References
Dimensions
Connections
Shunt coil tripping Undervoltage coil tripping
Electronic earth leakage relay with externaltransformer of the WG Series
RGE / RGE-R
WG Series
EXTERNAL RESET
SHUNT
COIL
LOAD
I
EXTERNAL RESET
I
LOAD
UNDERVOLTAGE
COIL
8/11/2019 Ca_P1_03
18/42
.1 Industrial earth leakage protectionP
-20
Electronic earth leakage relay with externaltransformer of the WG Series
RGU-10/ RGU-10 C
Protection
Class A superimmunized
Measurement True root mean square (TRMS)
Sensitivity0.03 ... 3 A0.03 ... 30 A(PROGRAMMING)
DelayTime dened: 0,02 ... 10 sInverse curve: Instantaneous or selective
Earth leakage transformer External, TRANSFORMERS WGTest and Reset With built-in buttons, T & R
Remote Control External Test Option
Associated circuit breaker Contact or Circuit breaker + trigger coil
LED indicator
Power supply voltage Trip due to leakage Disconnection of the external transformer Pre-alarm
Display View
Current trip (red display when triggered) Programming parameters Instantaneous leakage current Disconnection of the external transformer
Remote signaling Pre-alarm Display of parameters with RS-485communications (RGU-10 C)
Circuit breaker controlThrough an NO/NC switched relay, dependingon the connection with the circuit breaker
Features
Auxiliary power supply230 Vac ( 20 %) 50 / 60 Hz(other values on demand)
Output contacts 250 Vac, 6 A
Operating temperature -10 ... +50 C
Construction f eatures
Fixing DIN Rail 46277 (EN 50022)
Dimensions 3 modules
Weight 236 g
Degree of protection IP 20 Terminals, IP 41 back panel
Standards
IEC 61008-1, IEC 755, IEC 255-5
Application
The RGU-10 relays associated to the trans-
formers of the WG series allow an smart
earth leakage protection. Their design fea-
tures guarantee maximum security and con-
tinuity of the electrical service, avoiding un-
wanted tripping.
Showing the value of the leak instantane-
ously on the display with the pre-alarm in-
dications provides the information about the
state of lines being protected, thus allowing
the implementation of an adequate preven-
tive maintenance approach.
In addition, version RGU-10 Cwith RS-485
communications is used with the Power Stu-
dio software, which allows the centralisedsupervision of the system in real time, with a
record log that can be analysed later on.
FeaturesDescription
Electronic earth leakage protection relay,
used to connect to the earth leakage trans-
formers WG Series
} Superimmunized Type A relay with high
frequency current ltering and high immunity
} Monitoring of the true root mean square
(TRMS)
} Display of data on the screenTwo inde-
pendent programmable outputs (main and
pre-alarm)
} External input for remote control functions
( 230 Vac).
WG Series
8/11/2019 Ca_P1_03
19/42
.1Industrial earth leakage protection P
P1-21
Size Communications In(A) Delay Type Code
3 modules -0.03 ... 3 A0.03 ... 30 A(PROGRAMMING)
0.02...10 s, INS, SEL RGU-10 P11941
3 modules RS-4850.03 ... 3 A0.03 ... 30 A(PROGRAMMING)
0.02...10 s, INS, SEL RGU-10 C P11944
References
Dimensions
Connections
Electronic earth leakage relay with externaltransformer of the WG Series
RGU-10 / RGU-10 C
WG Series
Shunt coil Undervoltage coil
8/11/2019 Ca_P1_03
20/42
.1 Industrial earth leakage protectionP
-22
Earth leakage monitoring and signaling unitof the external transformer of the WG Series
CBS-4/ CBS-4 C
Protection
No. of protections 4
Class A superimmunized
Measurement True root mean square (TRMS)
Sensitivity 0.03 A ... 30 A
DelayTime dened: 0,02 ... 10 sInverse curve: instantaneous or selective
Earth leakage transformer External, TRANSFORMERS WG/WGP
Test and Reset With built-in buttons, T & R
Associated circuit breaker Contact or Circuit breaker + trigger coil
Self-reclosing
No. of reclosures 0 Programming option ... 10
Time between reclosures 0 Programming option ... 900 s
Partial counter reset time Double the reclosing time
LED indicator
Power supply voltage Leakage trip Pre-alarm Interlocked earth leakage self-reclosing
Display View
Current trip (red display when triggered) Instantaneous leak level indicator in each channel Parameter programming
State of the self-reclosing- Disconnected externaltrans. indicator- Automatic self-reclosing enabled
Features
Auxiliary power supply 230 Vac ( 20 %) 50 ... 60 Hz
Output contacts 250 Vac, 5 A
Operating temperature -10 ... +50 C
Construction f eatures
Fixing DIN Rail 46277 (EN 50022)
Dimensions 3 modules
Weight 236 g
Degree of protection IP 20 Terminals, IP 41 back panel
Standards
IEC 664, VDE 0110, IEC 801, UL 94, IEC 348, IEC 571-1, EN 61000-6-3, 61000-6-1, 61010-1
Application
FeaturesDescription
} Unit equivalent to 4 earth leakage protec-
tion networks. 4 independent programmable
relays available
} Four inputs to connect the external toroidal
transformers of the WG
} Superimmunized Type A relay with high
frequency current ltering and high immunity.
Monitoring in true root mean square (TRMS)
} Reduced size, with 3 modules
} 5 independent programmable outputs
(4 earth leakage trip relays and 1 pre-alarm
trip).
The CBS-4earth leakage unit associated to
the transformers of the WGSeries allows an
smart earth leakage protection. Its design
features guarantee maximum security and
continuity of the electrical service, avoiding
unwanted tripping.
Showing the value of the leak instantane-
ously on the display with the pre-alarm in-
dications provides the information about the
state of lines being protected, thus allowing
the implementation of an adequate preven-
tive maintenance approach.
In addition, version CBS-4 C with RS-485
communications is used with the PowerStu-dio software, which allows the centralised
supervision of the system in real time, with a
record log that can be analysed later on.
WG Series
8/11/2019 Ca_P1_03
21/42
.1Industrial earth leakage protection P
P1-23
Size Communications No. of Relays In(A) Type Code
3 modules - 4 0.03 ... 30 s CBS-4 P12711
3 modules RS-485 4 0.03 ... 30 s CBS-4 C P12712
References
Dimensions
Connections
Earth leakage monitoring and signaling unitof the external transformer of the WG Series
CBS-4 / CBS-4 C
WG Series
8/11/2019 Ca_P1_03
22/42
.1 Industrial earth leakage protectionP
-24
Earth leakage monitoring and signaling unitof the external transformer of the WG / WGPSeries
CBS-8
Protection
No. of protections 8
Class A superimmunized
Measurement True root mean square (TRMS)
Sensitivity0.03 A ... 6.3 A external transformers WG/WGS0.03 A ... 63 A external transformers WGP/WGSP
DelayTime dened: 0,02 ... 10 sInverse curve: instantaneous or selective
Earth leakage transformer External, TRANSFORMERS WG/WGP
Test and Reset With built-in buttons, T & R
Associated circuit breaker Contact or Circuit breaker + trigger coil
Self-reclosing
No. of reclosures 0 Programming option ... 10
Time between reclosures 0 Programming option ... 900 s
Partial counter reset time Double the reclosing time
LED indicator
Power supply voltage Leakage trip Pre-alarm Interlocked earth leakage reclosing Automatic self-reclosing enabled
Display View
Instantaneous leak level indicator in each channel
Parameter programming Self-reclosing status
Features
Auxiliary power supply 230 Vac ( 20 %) 50 ... 60 Hz
Output contacts 250 Vac, 5 A
Operating temperature -10 ... +50 C
Construction features
Fixing DIN Rail 46277 (EN 50022)
Dimensions 8 modules
Weight 609 g
Degree of protection IP 20 Terminals, IP 41 back panel
Standards
IEC 664, VDE 0110, IEC 801, UL 94, IEC 348, IEC 571-1, EN 61000-6-3, 61000-6-1, 61010-1
Application
FeaturesDescription
} Unit equivalent to 8 earth leakage protec-
tion networks. 8 independent programmable
relays available
} 8 inputs to connect the external toroidal
transformers of the WG /WGP
} Superimmunized Type A relay with high
frequency current ltering and high immunity.
Monitoring in true root mean square (TRMS)
} Size adapted for 8 modules
} 9 independent programmable outputs
(8 earth leakage trip relays and 1 pre-alarm
trip).
The CBS-8earth leakage station associated
to the transformers of the WG / WGPSeries
allows an smart earth leakage protection. Its
design features guarantee maximum security
and continuity of the electrical service, avoid-
ing unwanted tripping.
Showing the value of the leak instantane-
ously on the display with the pre-alarm in-
dications provides the information about the
state of lines being protected, thus allowing
the implementation of an adequate preven-
tive maintenance approach.
In addition, RS-485 communications are
used with the Power Studio software, whichallows the centralised supervision of the sys-
tem in real time, with a record log that can be
analysed later on.
WG Series
8/11/2019 Ca_P1_03
23/42
.1Industrial earth leakage protection P
P1-25
References
Dimensions
Connections
Earth leakage monitoring and signaling unitof the external transformer of the WG Series
CBS-8
WG Series
45
110
140 70
Size Communications No. of Relays In(A) Type Code
8 modules RS-485 8 0.03 ... 63 A CBS-8(*) P12811
(*) In the case of the 0.3 ... 63 A scale, use earth leakage transformers of the WGP/ WGSP
8/11/2019 Ca_P1_03
24/42
.1 Industrial earth leakage protectionP
-26
References
Earth leakage Transformers of the WGPSeries (only for CBS-8)
WGP
WGSP Dimensions
WGP Dimensions
Type A B C D E
WGP-35 100 79 26 48,5 35
WGP-70 130 110 32 66 70
WGP-105 170 146 38 94 105
WGP-140 220 196 48,5 123 140
WGP-210 299 284 69 161 210
Type A B C D E F G H I
WGP-70X175 70 175 225 85 22 46 261 176 7,5
WGP-115X305 115 305 360 116 25 55 402 240 8
WGP-150X350 150 350 415 140 28 55 460 285 8
WGSP-20
WGSP-30
Useful diameter(mm) Weight (g) I
n(A) Type Code
20 76 0,3 ... 63 WGSP-20 P10141
30 95 0,3 ... 63 WGSP-30 P10142
35 181 0,3 ... 63 WGP-35 P10121
70 274 0,3 ... 63 WGP-70 P10122
105 545 0,3 ... 63 WGP-105 P10123
140 1 222 0,3 ... 63 WGP-140 P10124
210 2 040 0,3 ... 63 WGP-210 P10125
70 x 175 2 400 0,3 ... 63 WGP-70x175 P10126
115 x 305 5 450 0,3 ... 63 WGP-115x305 P10127
150 x 350 7 400 0,3 ... 63 WGP-150x350 P10128
WG Series
Description
The earth leakage transformers of the WGP Series have been de-
signed to work only with the CBS-8relay unit and a sensitivity of 0.3 ...
63 A. These transformers have a 1/5000 ratio.
8/11/2019 Ca_P1_03
25/42
.1Industrial earth leakage protection P
P1-27
Usefuldiameter(mm)
Weight(g) I
n(A) Type Code
20 82 acc. relay WNS-20 P10221
30 100 acc. relay WNS-30 P10222
35 148 acc. relay WN-35 P10211
70 281 acc. relay WN-70 P10212
105 433 acc. relay WN-105 P10213
140 574 acc. relay WN-140 P10214
210 1 201 acc. relay WN-210 P10215
References
WN Series Earth leakage transformers
WN
WNS DimensionsWN Dimensions
Type A B C D E
WN-35 100 79 26 48,5 35
WN-70 130 110 32 66 70
WN-105 170 146 38 94 105
WN-140 220 196 48,5 123 140
WN-210 299 284 69 161 210
WNS-20
WNS-30
WN Series
Description
The earth leakage transformers of the WNSeries have been designed
to work with the relays of the WNSeries.
The sensitivity (trigger current) of the transformer-relay set is estab-
lished by the associated relay.
8/11/2019 Ca_P1_03
26/42
.1/2 Earth leakage protectionP
1-28
Electronic earth leakage relay with externaltransformer of the WN Series
RN1M
Application
The RN1Mrelays combined with the WNtrans-
former provides complete differential protection,
both on single-phase and three-phase lines.
FeaturesDescription
WN series electronic differential protection
relay for connection to external WN/WNSse-
ries toroidal transformers
} These are highly reliable electronic relays
with the option of a xed or adjustable sensi-
tivity and delay
} Measurement using true root mean squa-
re (TRMS) value
} DIN 46277 (En50022) Rail mounting
} Reduced one module size.
} LED status indication.
y Power ON LED.
y Leakage led ON. Tripped relay.
y Power LED ashing and leakage LED
ON. Detection of a transformer continuity
fault
Protection
Class A superimmunized
Measurement True root mean square (TRMS)
Sensitivity 30 or 300 mA
Delay 20 ms
Earth leakage transformer External WNSeries
Test and Reset With built-in buttons, T & R
Remote Control External Test Option
Associated circuit breakerContactor or automatic circuit breaker using a coiltrigger
LED indicator Power supply voltage Leakage trigger Disconnection of external transformer
Circuit breaker controlThrough a NO/NC switched relay, dependingon the connection with the circuit breaker
Features
Auxiliary power supply 230 V c.a. ( 20 %) 50 / 60 Hz
Output contacts 250 V c.a., 6 A
Operating temperature -10 ... +65 C
Construction f eatures
Fixing DIN Rail 46277 (EN 50022)
Dimensions 1 module
Weight 85 g
Degree of protection IP 20 terminals
Standards
IEC 60947-2, IEC 60755, IEC 62020, IEC 61008
WN Series
8/11/2019 Ca_P1_03
27/42
Earth leakage protection P.1/2
P1-29
Size Attachment In(A) Delay Type Code
1 modules DIN rail 0,03 0,02 s RN1M-0,03 P12104
1 modules DIN rail 0,3 0,02 s RN1M-0,3 P12114
References
Dimensions
Connections
Bobina de emisin
Bobina mnima
Electronic earth leakage relay with externaltransformer of the WN Series
RN1M
WN Series
66 mm
72 mm 17.5 mm
45mm
64mm
90mm
TypeWN
S1
S2
7 8
1 2
3 4
5 6
RN1M
230V,5A
50/60Hz230V20%
Test / Reset
NL1 L2 L3
TypeWN
S1
S2
7 8
1 2
3 4
5 6
RN1M
230V,5A
50/60Hz230V20%
Test / Reset
NL1L2 L3
Disparo por BOBINA DE MNIMA- Rearme manual.
CARGA
- Rearme manual.Disparo por BOBINA DE EMISIN
CARGA
8/11/2019 Ca_P1_03
28/42
.1 Industrial earth leakage protectionP
-30
Electronic earth leakage relay with externaltransformer of the WN Series
RN/ RN-R
Application
The relays of the RN series and the trans-
former of the WN series enable a full earth
leakage protection for both single and three-
phase lines.
FeaturesDescription
} Electronic earth leakage protection relay,
used to connect the transformers of the WN
/ WNS Series
} These electronic relays offer a high relia-
bility, with the option of a xed or adjustable
sensitivity and delay
} Monitoring of the true root mean square
(TRMS)
} Assembly on DIN rail 46277 (EN 50022)
} Reduced size, with 2 modules
} LED status indicator:
y Permanently lit leak LED: Tripped relay.
y Flashing Power LED and lit leak LED:
Detection of a continuity fault in the trans-
former.
y Flashing leak indicator LED (only RN-R
and RN-R1): Leak with a value that is lower
than the value selected.
Protection
Class A immunised
Measurement True root mean square (TRMS)
Sensitivity0.03 A / 0.3 A / 0.5 A / 0.03 ... 3 A (R1) /0.03 ... 5 A (R)
Delay 0.02 / 0.02 ... 1 s (R1) / 0.02 ... 5 s (R)
Earth leakage transformer External, TRANSFORMERS WN
Test and Reset With built-in buttons, T & R
Remote Control External Test Option
Associated circuit breaker Contact or Circuit breaker + trigger coil
LED indicator
Power supply voltage Trip due to leakage Disconnection of the external transformer Pre-alarm (R-R1)
Circuit breaker controlThrough an NO/NC switched relay, dependingon the connection with the circuit breaker
Remote Control External Test Option
Features
Auxiliary power supply 230 Vac ( 20 %) 50 / 60 Hz
Output contacts 250 Vac, 6 A
Operating temperature -10 ... +50 CConstruction f eatures
Fixing DIN Rail 46277 (EN 50022)
Dimensions 2 modules
Weight 163 g
Degree of protection IP 20 Terminals, IP 41 back panel
Standards
IEC 61008-1, IEC 755, IEC 255-5
WN Series
8/11/2019 Ca_P1_03
29/42
.1Industrial earth leakage protection P
P1-31
Size Indicator In(A) Delay Type Code
2 modules LED 0,03 0.02 s RN-0.03 P12101
2 modules LED 0,3 0.02 s RN-0.3 P12111
2 modules LED 0,03 ... 3 0.02 ... 1 s RN-R1 P12131
2 modules LED 0,03 ... 5 0.02 ... 5 s RN-R P12132
References
Dimensions
Connections
Shunt coil Undervoltage coil
Electronic earth leakage relay with externaltransformer of the WN Series
RN / RN-R
WN Series
EXTERNAL RESET
SHUNT
COIL
LOAD
EXTERNAL RESET
LOAD
UNDERVOLTAGE
COIL
8/11/2019 Ca_P1_03
30/42
.1 Industrial earth leakage protectionP
-32
Electronic earth leakage relay with externaltransformer of the WN Series
RN-10
Protection
Class A superimmunized
Measurement True root mean square (TRMS)
Sensitivity0.03 ... 3 A(PROGRAMMING)
DelayTime dened: 0,02 ... 1 sInverse curve: Instantaneous or selective
Earth leakage transformer External, TRANSFORMERS WN
Test and Reset With built-in buttons, T & R
Remote Control External Test Option
Associated circuit breaker Contact or Circuit breaker + trigger coil
LED indicator
Power supply voltage Trip due to leakage Disconnection of the external transformer Pre-alarm
Display View
Current trip (red display when triggered) Programming parameters Instantaneous leakage current Disconnection of the external transformer
Remote signaling Pre-alarm Display of parameters with RS-485 communications
Circuit breaker controlThrough an NO/NC switched relay, depending
on the connection with the circuit breakerFeatures
Auxiliary power supply230 Vac ( 20 %) 50 / 60 Hz(other values on demand)
Output contacts 250 Vac, 6 A
Operating temperature -10 ... +50 C
Construction f eatures
Fixing DIN Rail 46277 (EN 50022)
Dimensions 3 modules
Weight 236 g
Degree of protection IP 20 Terminals, IP 41 back panel
Standards
IEC 664, VDE 0110, IEC 801, UL 94, IEC 348, IEC 571-1, EN 61000-6-3, 61000-6-1, 61010-1
Application
The RN-10 relays associated to the trans-
formers of the WN series allow an smart
earth leakage protection. Their design fea-
tures guarantee maximum security and con-
tinuity of the electrical service, avoiding un-
wanted tripping.
The instantaneous leakage value is shown
on the display with the pre-alarm indicators,providing all information required about the
status of lines being protected, as required
for the preventive maintenance operations.
FeaturesDescription
Electronic earth leakage protection relay s,
used to connect the transformers of the WN
/ WNSSeries
} Superimmunized Type A relay with high
frequency current ltering and high immunity.
Monitoring in true root mean square (TRMS)
} Visualization of data on the display
} Sensitivity can be programmed between
30 mA and 3 A
} Adjustable delay: instantaneous, selective
or timed, up to 1 s
} Two independent programmable outputs
(main and pre-alarm relay)
} External input for remote control functions
(230 Vac)
} Automatic verication of the connection
and status of the external transformer with an
inductive test
} Reduced size, with 3 modules
WN Series
8/11/2019 Ca_P1_03
31/42
.1Industrial earth leakage protection P
P1-33
References
Dimensions
Connections
Electronic earth leakage relay with externaltransformer of the WN Series
RN-10
Size Indicator In(A) Delay Type Code
3 modules LED 0,03 ... 3 0.02 ... 1 s RN-10 P12140
WN Series
Shunt coil Undervoltage coil
8/11/2019 Ca_P1_03
32/42
.1/2 Earth leakage protectionP
1-34
Rel diferencial con transformadorincorporado con display (tipo A)
WRU-10
Proteccin
Clase A superinmunizada
Medida Verdadero valor ecaz, TRMS
Sensibilidad PROGRAMABLE 0,03 ... 3 A, ampliable hasta 30 A por SETUP
Retardo PROGRAMABLETiempo denido: 0,02 ...1 s, ampliablehasta 10s por SETUP. Curva inversa:INStantnea / SELectiva. (IEC 60947-2)
Test y Reset Mediante pulsadores T y R
Control RemotoPosibilidad de TEST externo, disparo por entrada librede tensin.
Elemento de corte asociado Contactor o interruptor automtico con bobina de disparo
Indicacin por LED/DISPLAY
- Tensin de alimentacin- Disparo por fuga- Prealarma
- Parmetros de proteccin- Lectura corriente de fuga/disparo.- Estados de TEST y disparoexterno.
Control de elemento de corteRel de contacto conmutado NA/NC segn elementode corte
Caractersticas elctricas
Alimentacin auxiliar 230 V c.a. ( 30 %) 50 / 60 Hz
Contactos salida disparo/prealarma 250 V c.a., 5 A / 230 V c.a., 250 mA
Temperatura de uso -20 ...+70 CCaractersticas mecnicas
Fijacin Carril DIN 46722 (EN 50022)
Dimensiones 3 mdulos
Peso 275 g
Grado de proteccin IP 20, transcuadro IP 41
Normas
IEC 60947-2, IEC 60755, IEC 62020, IEC 61008
Application
FeaturesDescription
Electronic differential protection relay with built-
in 28 mm transformer, constituting one unit.
} Type A high-insulation, with high-frequency
current lter and high insulation. Monitoring
using true root mean square.
} Display with LEDs and display:
- differential protection settings.
- protection trigger current.
- protection status messages, etc.
} Units with three programmable output con-
tact relays, one switched and two simple. The
main relay is for the protection provided by the
contact or trigger relay of the automatic switch
while the two others are for the pre-alarm.
} It also has a voltage input for external trigge-
ring and re-arming.
} Assembly on DIN Rail 46277 (EN 50022)
} Reduced three-module size.
} Connection by pluggable terminals.
Los rels WRU-10 permiten una proteccin
difencial inteligente. Por sus caractersticas de
diseo aseguran la mxima seguridad t conti-
nuidad en el servicio elctrico, evitndose dis-
paros intempestivos.
El poder visualizar el valor de fuga instantnea
en el display, conjuntamente con las indicacio-
nes de prealarma, permite tener informacin
del estado de las lneas que protegen, y reali-
zar un buen mantenimiento preventivo.
8/11/2019 Ca_P1_03
33/42
Earth leakage protection P.1/2
P1-35
References
Dimensions
Connections
WRU-10 WRU-10
Differential relay with bui lt-in transformer anddisplay (type A)
WRU-10
Size Net section (mm) In(A) Delay Type Code
3 modules 28 0.03 ... 3 A extendibleto 30 A
0.02 ... 1 s extendible to 10s Curve(Inverse): INS/SEL
WRU-25P2
8/11/2019 Ca_P1_03
34/42
.1 Industrial earth leakage protectionP
-36
Earth leakage relay with built-in transformer(type A)
WRU
Protection
Class A superimmunized
Measurement True root mean square (TRMS)
Sensitivity 0.03 ... 3 A
Delay 0.02 ... 1 s
Earth leakage transformer Internal
Test and Reset With built-in buttons, T & R
Remote Control (inputs) External test
Associated circuit breaker Contact or Circuit breaker + trigger coil
Relay signaling Power supply voltage Trip due to leakage Pre-alarm
Remote signaling (outputs)Leak control signal (proportional alternatingvoltage) (only in WRU-25)
Circuit breaker controlThrough an NO/NC switched relay, dependingon the connection with the circuit breaker
Features
Auxiliary power supply 230 Vac ( 20 %) 50 / 60 Hz
Output contacts 250 Vac, 6 A
Operating temperature -10 ... +50 CConstruction f eatures
Fixing DIN rail
Dimensions 4 modules (WRU-25), 6 modules (WRU-35)
Weight 228 g (WRU-25), 403 g (WRU-35)
Degree of protection IP 20 Terminals, IP 41 back panel
Standards
IEC 1008, IEC 255-5, UNE 801-2, UNE 801-3, UNE 801-4, UNE 60730-1
Application
FeaturesDescription
Electronic earth leakage protection relay with
built-in transformer, with a diameter of 25 or
35 mm , depending on the type, creating a
single set.
} Type A relay with high frequency current
ltering and high immunity. Monitoring in true
root mean square.
} The sensitivity can be adjusted to 0.03 ... 3 A
} The delay in the trigger can be adjusted
to 0.02 ... 1 s
} LED indicator of the leak level (% sensi-
tivity):
y 1 ash every 2 s: between 25 and 50 %
y 1 ash every 1 s: between 50 and 75 %
y 1 ash every 0.5 s: between 75 and 90 %
} Adjustable to the DIN prole 46277 (EN
50022)
The WRU Series allows a reliable and im-
munised form of earth leakage protection,
saving installation time. Its assembly is very
simple, offering an adequate solution for all
types of single and three-phase installations,
since it offers compact earth leakage protec-
tion, with the optional adjustment of the sen-
sitivity and time.
8/11/2019 Ca_P1_03
35/42
.1Industrial earth leakage protection P
P1-37
References
Dimensions
Connections
WRU-25 WRU-35
Earth leakage relay with built-in transformer(type A)
WRU
SizeUseful diameter
(mm) In(A) Delay Type Code
4 modules 25 0,03 ... 3 0.02 ... 1 s WRU-25 P14011
6 modules 35 0,03 ... 3 0.02 ... 1 s WRU-35 P14021
The delay is cancelled in all relays with a sensitivity adjustment of 0.03 A.
WRU-25
WRU-35
1
1
22
8/11/2019 Ca_P1_03
36/42
.1 Industrial earth leakage protectionP
-38
Transformer with built-in earth leakage relay
WGBU
Earth leakage Protection
Class A superimmunized
Measurement True root mean square (TRMS)
Sensitivity 0.03 ... 3 A
Delay 0.02 ... 1 s
Earth leakage transformer Built-in transformers of the WG
Test and Reset With built-in buttons, T & R
Associated circuit breaker Contact or Circuit breaker + trigger coil
LED indicator Power supply voltage Trip due to leakage Pre-alarm
Remote Control (inputs) External Test Option
Circuit breaker controlThrough an NO/NC switched relay, dependingon the connection with the circuit breaker
Features
Auxiliary power supply 230 Vac ( 20 %) 50 / 60 Hz
Output contacts 250 Vac, 6 A
Operating temperature -10 ... +50 C
Construction f eatures
Fixing DIN Panel / Rail
Dimensions Depending on the type
Weight Depending on the type
Degree of protection IP 20 Terminals, IP 41 back panel
Standards
IEC 61008-1, IEC 755, IEC 255-5
Application
The WGBU series offers a reliable earth
leakage protection, with simpler cabling and
savings in the assembly time. In addition, in-
stallation is very simple, thanks to its compact
dimensions.
FeaturesDescription
The WGBUSeries is a compact earth leak-
age protection system. It is composed of a
toroidal transformer with a built-in earth leak-
age relay.
} Multi-range electronic relay
y The sensitivity can be adjusted to 0.03 ... 3 A
y Trigger delay of 0.02 ... 1 ws, adjustable
} Type A relay with high frequency current
ltering and high immunity. Monitoring in true
root mean square (TRMS).
} LED indicators:
y Grid connection LED
y Pre-alarm and trigger LED: 1 ash every 2
s, leak between 25 and 50 % of the sensitiv-
ity selected; 1 ash every 1 s, leak between
50 and 75 % of the sensitivity selected; 1
ash every 0.5 s, leak exceeding 75 % of
the sensitivity selected; permanently lit, trig-
ger of the earth leakage protection.
8/11/2019 Ca_P1_03
37/42
.1Industrial earth leakage protection P
P1-39
References
Dimensions
Transformer with built-in earth leakage relay
WGBU
Weight (g)Useful diameter(mm) I
n(A) Delay (s) Type Code
380 35 0,03 ... 3 0,02 ... 1 WGBU-35 P16011
474 70 0,03 ... 3 0,02 ... 1 WGBU-70 P16012
744 105 0,03 ... 3 0,02 ... 1 WGBU-105 P16013
1422 140 0,03 ... 3 0,02 ... 1 WGBU-140 P16014
2240 210 0,03 ... 3 0,02 ... 1 WGBU-210 P16015
380 35 0,03 ... 3 0,02 ... 1 WGBU-90-35 P16021
474 70 0,03 ... 3 0,02 ... 1 WGBU-90-70 P16022
744 105 0,03 ... 3 0,02 ... 1 WGBU-90-105 P16023
1422 140 0,03 ... 3 0,02 ... 1 WGBU-90-140 P16024
2240 210 0,03 ... 3 0,02 ... 1 WGBU-90-210 P16025
The delay is cancelled in all relays with a sensitivity adjustment of 0.03 A.
WGBU
WGBU-90
Type A1 A2 B C D E
WGBU-35 (A1) / WGBU-90-35 (A2) 166 100 79 26 48,5 35
WGBU-70 (A1) / WGBU-90-70 (A2) 196 130 110 332 66 70
WGBU-105 (A1) / WGBU-90-105 (A2) 236 170 146 38 94 105
WGBU-140 (A1) / WGBU-90-140 (A2) 286 220 196 48,5 123 140
WGBU-210 (A1) / WGBU-90-210 (A2) 365 299 284 69 161 210
8/11/2019 Ca_P1_03
38/42
.1 Industrial earth leakage protectionP
-40
Shunt coil
Undervoltage coil
Connections
Transformer with built-in earth leakage relay
WGBU
8/11/2019 Ca_P1_03
39/42
.1Industrial earth leakage protection P
P1-41
Earth leakage relay wi th built-in transformer
WRN-22
Protection
Class A
Measurement True root mean square (TRMS)
Sensitivity 0,01 A / 0,03 A / 0,30 A (depending on the type)
Delay 0.02 s
Earth leakage transformer Internal
Test With built-in button, TEST
Associated circuit breaker Circuit breaker + trigger coil
Relay signaling Power supply voltage Leakage trigger
Remote signaling (outputs) -
Remote Control (inputs) External test
Circuit breaker control Voltage 230 Vac
Features
Auxiliary power supply 230 Vac ( 20 %) 50 / 60 Hz
Output contacts -
Operating temperature -10 ... +50 C
Construction f eatures
Fixing DIN rail
Dimensions 3 modules
Weight 146 g
Degree of protection IP 20 Terminals, IP 41 back panel
Standards
IEC 1008, IEC 255-5, UNE 801-2, UNE 801-3, UNE 801-4, UNE 60730-1
Application
The WRN-22 earth leakage protection is a
very interesting solution for small-scale in-
stallations with reduced space.
FeaturesDescription
The WRN-22relay is an earth leakage relay
with a built-in earth leakage transformer, with
a diameter 22 mm
} DIN 46277 Symmetrical prole coupling
(EN 50022)
} The leakage is detected by means of
sampling the earth leakage intensity and cal-
culating its true root mean square (TRMS)
} Detection of the presence of voltage with
LEDs
} TEST button.
8/11/2019 Ca_P1_03
40/42
.1 Industrial earth leakage protectionP
-42
References
Dimensions
Connections
Earth leakage relay wi th built-in transformer
WRN-22
SizeUseful diameter
(mm) In(A) Delay (s) Type Code
3 modules 22 0,03 0,02 WRN-22-0.03 P14211
3 modules 22 0,3 0,02 WRN-22-0.3 P14212
3 modules 22 0,01 0,02 WRN-22-0.01 P14214
8/11/2019 Ca_P1_03
41/42
.1Industrial earth leakage protection P
P1-43
Relation between products and accessories
Adaptor p anel PA-TC/WG TT
Adaptor for 72 x 72 panel Accessory for assembly on DIN rail Core balance shield tube
M5ZZF1 P19921
TT-35 P19911
TT-70 P19912
TT-105 P19913
TT-140 P19914
TT-210 P19915
WG --
only for WG-35up to WG-210
WGP
--
only for WGP-35up to WGP-210
RGU-10
-- --
CBS
only CBS-4-- --
WN --
only for WN-35up to WN-210
RN-10
-- --
WGBU
-- --
8/11/2019 Ca_P1_03
42/42
.1 Industrial earth leakage protectionP