CALLISTOVIEW 6.0.0.0.0.0 Version Numbering / RTU Interrogator

CallistoView 6 - Version Numbering and RTU … CallistoView Version...Version Numbering / RTU Interrogator Rev #001 3 1.0 VERSION NUMBERING With the release of CallistoView 6.0.0.0.0.0,

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: CallistoView 6 - Version Numbering and RTU … CallistoView Version...Version Numbering / RTU Interrogator Rev #001 3 1.0 VERSION NUMBERING With the release of CallistoView 6.0.0.0.0.0,

CALLISTOVIEW 6.0.0.0.0.0

Version Numbering / RTU Interrogator

Page 2: CallistoView 6 - Version Numbering and RTU … CallistoView Version...Version Numbering / RTU Interrogator Rev #001 3 1.0 VERSION NUMBERING With the release of CallistoView 6.0.0.0.0.0,

CallistoView 6.0.0.0.0.0

Version Numbering / RTU Interrogator Rev #001

1

COPYRIGHT ©2014 DAQ Electronics, LLC Revised 01/02/14 - Revision #001 This documentation is provided as a component part of DAQ Electronics. All parties or individuals who are in possession of the documentation accept in full and without exception or limitation the DAQ Electronics unrestricted rights of ownership of this material. This documentation is not available by any other means except by license which is only available from DAQ Electronics. Under no circumstances may any part or the whole of this documentation be reproduced, stored in a retrieval system, transmitted, copied, modified, distributed, displayed, sold, licensed, published or derivative works created there from in any form or by any means electronic mechanical, recording, or otherwise without the written permission of DAQ Electronics being obtained in advance of the requirement. It is expressly forbidden for the holder of this documentation to use this documentation either in its entirety or in part or any graphics to provide training or tuition, assistance or knowlEDGE transfer to any other party whatsoever, or for marketing of promotional literature or material of any type whatsoever without the prior written permission of DAQ Electronics. Use of this documentation in any manner inconsistent with the user manual and related documentation is strictly prohibited. Use of the documentation is not transferable. TRADEMARKS EntroWatch, EntroStar, Callisto, CallistoView, and StarWatch are trademarks of DAQ Electronics. All other product and company names may be the property of their respective owners. PROPRIETARY INFORMATION This documentation contains confidential and proprietary information which must be maintained in confidence and used only in a manner consistent with the documentation and may not be disclosed to any third parties. DAQ Electronics, LLC Piscataway Corporate Center 262B Old New Brunswick Road Piscataway, NJ 08854 USA T + 1.732.981.0050 F + 1.732.981.0058 www.daq.net

Page 3: CallistoView 6 - Version Numbering and RTU … CallistoView Version...Version Numbering / RTU Interrogator Rev #001 3 1.0 VERSION NUMBERING With the release of CallistoView 6.0.0.0.0.0,

CallistoView 6.0.0.0.0.0

Version Numbering / RTU Interrogator Rev #001

2

TABLE OF CONTENTS 1.0 VERSION NUMBERING ............................................................................................. 3 

1.1 VERSION FIELDS ................................................................................................. 3 

2.0 RTU INTERROGATOR .............................................................................................. 5 

2.1 ENABLING THE INTERROGATOR .............................................................................. 5 

2.2 NODE INFORMATION TABLE ................................................................................... 6 2.2.1 INFORMATION FIELDS ................................................................................................... 6 2.2.2 NODE MAPPING BY QUERY ............................................................................................. 8 

2.3 LIMITATIONS ..................................................................................................... 9 

Page 4: CallistoView 6 - Version Numbering and RTU … CallistoView Version...Version Numbering / RTU Interrogator Rev #001 3 1.0 VERSION NUMBERING With the release of CallistoView 6.0.0.0.0.0,

CallistoView 6.0.0.0.0.0

Version Numbering / RTU Interrogator Rev #001

3

1.0 VERSION NUMBERING

With the release of CallistoView 6.0.0.0.0.0, a new version number system has been implemented. This

system allows the user to identify what has changed in a given release. It also allows configuration files

to be associated with a version to help with backward compatibility.

1.1 VERSION FIELDS

CallistoView version numbers will now consist of six fields. The first two fields represent the major and

minor version number. The major version number will rarely increment. The minor version number will

increment with each standard release. The next four fields represent the CallistoView configuration

software version, the EDGE firmware version, the IoE2 firmware version and the version of

IoE1/IoG/Polaris firmware.

As changes to each of these aspects of the release occur, their version number will be incremented.

For example, if we have a release with a version number 6.1.2.3.4.5, the version number represents:

6 Major release number

1 Minor release number

2 CallistoView configuration software version

3 EDGE firmware version

4 IoE2 firmware version

5 IoE1/IoG/Polaris firmware version

Page 5: CallistoView 6 - Version Numbering and RTU … CallistoView Version...Version Numbering / RTU Interrogator Rev #001 3 1.0 VERSION NUMBERING With the release of CallistoView 6.0.0.0.0.0,

CallistoView 6.0.0.0.0.0

Version Numbering / RTU Interrogator Rev #001

4

If the next standard release after our 6.1.2.3.4.5 example incorporates a change to some aspect of the

CallistoView software, such as resolving a mapping bug in one of the server applications, and there is a

change to the EDGE firmware, the release will have a version number of 6.2.3.4.4.5, where:

6 The major release number has remained the same.

2 The minor release has been incremented to 2.

3 The CallistoView application version has incremented to 3.

4 The EDGE firmware version has incremented to 4.

4 The IoE2 firmware version remains the same.

5 The IoE1/IoG/Polaris firmware version remains the same.

Each release will contain all changes from previous versions. New versions can be installed on top of

old versions if desired. Occasionally, a release will be made where the minor version number does not

increment but one of the versions in the four latter fields will increment. This will be done for minor

bug fixes that need to be done quickly and don’t warrant a standard release increment.

Page 6: CallistoView 6 - Version Numbering and RTU … CallistoView Version...Version Numbering / RTU Interrogator Rev #001 3 1.0 VERSION NUMBERING With the release of CallistoView 6.0.0.0.0.0,

CallistoView 6.0.0.0.0.0

Version Numbering / RTU Interrogator Rev #001

5

2.0 RTU INTERROGATOR

CallistoView now incorporates a feature called the RTU interrogator. Prior to downloading a

configuration to a node, the interrogator will query the node and retrieve information about the type

of node, its IP address, a user definable node label, and information about other nodes in the Arcnet

network.

This information allows the user to verify that the node they are connected to is the intended unit. If

the user believes that they are connected to the incorrect unit, they can simply abort the download

without changing the configuration of the unit they are connected to - otherwise, they can proceed

with the download. This feature was added especially for users who configure their RTUs remotely or

through Ethernet.

2.1 ENABLING THE INTERROGATOR

To enable the RTU interrogator, call up the main CallistoView screen. Next, from the Setup menu,

choose Options and select Interrogate RTU. When this option is selected, the Interrogator will appear

when a download operation is initiated.

Page 7: CallistoView 6 - Version Numbering and RTU … CallistoView Version...Version Numbering / RTU Interrogator Rev #001 3 1.0 VERSION NUMBERING With the release of CallistoView 6.0.0.0.0.0,

CallistoView 6.0.0.0.0.0

Version Numbering / RTU Interrogator Rev #001

6

2.2 NODE INFORMATION TABLE

When the interrogator is enabled and a download action is performed in CallistoView, the RTU is

queried for information from all nodes in the configuration. This information is displayed in a table

along with information from the configuration. The user can compare expected configuration

information with what was reported by the RTU to ensure that they are connected to the correct RTU.

After the user has reviewed the displayed information, the Continue button is pressed to commence

with the download.

2.2.1 INFORMATION FIELDS

In general, the fields labeled “Expected” show information from the configuration. Fields labeled

“Reported” display information gathered from the node. The field definitions are:

Node The node number returned from the RTU.

Expected Type Displays the type of node corresponding to the given node

number in the configuration.

Reported Type Displays the type of node returned from the RTU corresponding

to the given node number.

Page 8: CallistoView 6 - Version Numbering and RTU … CallistoView Version...Version Numbering / RTU Interrogator Rev #001 3 1.0 VERSION NUMBERING With the release of CallistoView 6.0.0.0.0.0,

CallistoView 6.0.0.0.0.0

Version Numbering / RTU Interrogator Rev #001

7

Expected ID This field corresponds with the node name which can be

assigned on the main CallistoView screen. This is to be used as

an identifier, allowing the expected ID to be compared with

the reported ID from the RTU. This value can be altered by

changing the node name on the main CallistoView screen or by

clicking on the field in the interrogator. When the node

name/expected ID is changed, the point names for all points on

the node are also changed. This is because the node name is a

prefix in all point names. Most servers will automatically be re-

mapped with the new point names. Applications that contain

point selection fields are not updated and must be manually

changed after a node name/expected ID change. It is important

to check the server mapping and any point selection fields

after the node name/expected ID is changed.

Reported ID This field serves as an identifier that is stored on the node. The

interrogator reads and displays this information so the user can

confirm that they are connected to the correct unit. To change

the reported ID, click on the field in the interrogator. A dialog

will appear allowing text to be entered. When the OK button is

pressed, the text will be sent and saved to the node.

Expected IP This field corresponds with the IP address, subnet mask and

default gateway set in the configuration. This applies only to IP

capable nodes, IoE2 and EDGE.

Reported IP This field corresponds with the IP address, subnet mask and

default gateway settings on the node. The interrogator allows

the user to change the IP address of the node by clicking on the

field. A dialog appears that allows the user to enter the new IP

address, subnet mask and default gateway. When the OK

button is pressed, the new parameters are sent to the node.

The node will reboot and download will terminate. When the

node is finished booting, the new IP parameters are applied.

This applies only to IP capable nodes, IoE2 and EDGE.

Page 9: CallistoView 6 - Version Numbering and RTU … CallistoView Version...Version Numbering / RTU Interrogator Rev #001 3 1.0 VERSION NUMBERING With the release of CallistoView 6.0.0.0.0.0,

CallistoView 6.0.0.0.0.0

Version Numbering / RTU Interrogator Rev #001

8

Firmware Date/Version Displays the firmware build date and associated CallistoView

version of the firmware currently loaded on the node.

Mode Displays the current mode of the node: fully functional or

default mode.

Connections Displays the available console and download connection

interfaces available on the node. Clicking on this field will test

the IP connection on the applicable node.

2.2.2 NODE MAPPING BY QUERY

The default query for available nodes is limited to nodes present in the configuration. If the user would

like to scan for other nodes present in the Arcnet network, the Map button can be pressed. A dialog

box appears allowing the user to select the range of node numbers scanned. When the Map button is

pressed, scanning will commence.

It will take about 1 second per node to complete the scan. When scanning is complete, the detected

nodes are displayed in the interrogator RTU Nodes window. Any nodes that are not in the configuration

are marked as “UNEXPECTED”. Nodes that are in the configuration but are not present on the Arcnet

network, are marked as “Off Line” in the Reported Type field. IoA nodes may be marked “Off Line”

even if they are present.

Page 10: CallistoView 6 - Version Numbering and RTU … CallistoView Version...Version Numbering / RTU Interrogator Rev #001 3 1.0 VERSION NUMBERING With the release of CallistoView 6.0.0.0.0.0,

CallistoView 6.0.0.0.0.0

Version Numbering / RTU Interrogator Rev #001

9

2.3 LIMITATIONS

Older node types have limitations in their ability to interface with the interrogator. Please take note of

the following:

IoG nodes will be reported as IoE1 nodes. The IoG and IoE1 use identical firmware.

The interrogator cannot distinguish between IoD1, IoC1 or IoP1 nodes. These node types use

identical firmware. For these node types, the Reported Type field will display “IoC1”, “IoD1”

or “IoP1”.

IoA1 nodes may not appear or may be incorrectly marked “Off Line” in the interrogator view.

The IoA firmware has limitations in the way it can communicate with the interrogator.

Page 11: CallistoView 6 - Version Numbering and RTU … CallistoView Version...Version Numbering / RTU Interrogator Rev #001 3 1.0 VERSION NUMBERING With the release of CallistoView 6.0.0.0.0.0,

DAQ Electronics, LLC 262B Old New Brunswick RoadPiscataway, NJ 08854 USA

T+ 1.732.981.0050F+ 1.732.981.0058

www.daq.net