2
VERIFICACION DE REDES EN PUNTO MAS DESFAVORABLE DE CISTERNA (C1) y TANQUE ELEVADO TRAMO UH Q(LT/SG) D(") v(M/SG) L(MT) Lequiv Ltotal hf(mt) P(mt) O1 0 O1 - A 520 4.83 4 0.60 12.00 2.4 14.40 0.06 14.94 A - B 305 3.33 3 0.73 24.00 4.8 28.80 0.23 14.72 B - C 295 3.24 3 0.71 11.00 2.2 13.20 0.10 14.62 C - C1 210 2.53 2.5 0.80 8.00 1.6 9.60 0.11 14.51 C1 - D 174 2.25 2.5 0.71 11.00 2.2 13.20 0.12 14.39 D - E 82 1.47 2 0.73 11.00 2.2 13.20 0.15 14.24 E - F´ 75 1.41 2 0.70 3.00 0.6 3.60 0.04 14.20 F´- F 41 0.93 1.5 0.82 3.60 0.72 4.32 0.08 10.52 F - G 34 0.82 1.5 0.72 2.65 0.53 3.18 0.05 10.77 G - H 12 0.38 0.75 1.33 1.00 0.2 1.20 0.13 10.64 H - I 10 0.36 0.75 1.26 0.91 0.182 1.09 0.10 10.54 I - J 8 0.29 0.75 1.02 0.91 0.182 1.09 0.07 10.47 J - K 6 0.25 0.75 0.88 0.91 0.182 1.09 0.05 10.42 K - L 4 0.16 0.5 1.26 2.85 0.57 3.42 0.48 7.94 A - A1 215 2.56 3 0.56 54.00 10.8 64.80 0.30 14.64 A1 - A2 127 1.88 2.5 0.59 5.00 1 6.00 0.04 14.61 A2 - M 117 1.8 2 0.89 3.00 0.6 3.60 0.06 14.54 M - N 78 1.43 2 0.71 1.00 0.2 1.20 0.01 14.53 N - O 71 1.37 2 0.68 2.00 0.4 2.40 0.02 14.50 O - O´ 46 1.03 1.5 0.90 3.60 0.72 4.32 0.10 10.80 O´- P 32 0.79 1.5 0.69 2.65 0.53 3.18 0.05 10.76 P - Q 10 0.36 0.75 1.26 1.10 0.22 1.32 0.12 10.63 Q - R 8 0.29 0.75 1.02 0.90 0.18 1.08 0.07 10.57 R - S 6 0.25 0.75 0.88 0.90 0.18 1.08 0.05 10.52 S - T 4 0.16 0.5 1.26 3.06 0.612 3.67 0.52 8.00 HFT= 3.10 Para la perdidas de carga se utilizo la formula de Darcy: f = 0.022 Punto mas desfavorable son las duchas del 2do. Nivel del pabellon C y SS.HH (alumnado) (punto T y punto L) La altura del tanque elevado es de 15.00 mt, restando 0.06 mt, que es la perdida de carga, nos da una pres igual a 14.94 mt. A partir de alli va disminuyendo la presion en funcion de la distancia. La cota de terreno donde se ubica el tanque elevado es de 56.55 mt La cota de terreno donde se ubican los 02 puntos mas desfavorables es de 56.45 mt, es decir habra 0.10 mt a los valores de presion calculados

calculo hidraulicoredesc1-colegiodebarranca

Embed Size (px)

DESCRIPTION

HOJA EXCEL PARA CALCULO HIDRAULICO EN EDIFICACIONES

Citation preview

c2VERIFICACION DE REDES EN PUNTO MAS DESFAVORABLE DE CISTERNA (C1) y TANQUE ELEVADOTRAMOUHQ(LT/SG)D(")v(M/SG)L(MT)LequivLtotalhf(mt)P(mt)O10O1 - A5204.8340.6012.002.414.400.0614.94A - B3053.3330.7324.004.828.800.2314.72B - C2953.2430.7111.002.213.200.1014.62C - C12102.532.50.808.001.69.600.1114.51C1 - D1742.252.50.7111.002.213.200.1214.39D - E821.4720.7311.002.213.200.1514.24E - F751.4120.703.000.63.600.0414.20F- F410.931.50.823.600.724.320.0810.52F - G340.821.50.722.650.533.180.0510.77G - H120.380.751.331.000.21.200.1310.64H - I100.360.751.260.910.1821.090.1010.54I - J80.290.751.020.910.1821.090.0710.47J - K60.250.750.880.910.1821.090.0510.42K - L40.160.51.262.850.573.420.487.94A - A12152.5630.5654.0010.864.800.3014.64A1 - A21271.882.50.595.0016.000.0414.61A2 - M1171.820.893.000.63.600.0614.54M - N781.4320.711.000.21.200.0114.53N - O711.3720.682.000.42.400.0214.50O - O461.031.50.903.600.724.320.1010.80O- P320.791.50.692.650.533.180.0510.76P - Q100.360.751.261.100.221.320.1210.63Q - R80.290.751.020.900.181.080.0710.57R - S60.250.750.880.900.181.080.0510.52S - T40.160.51.263.060.6123.670.528.00HFT=3.10Para la perdidas de carga se utilizo la formula de Darcy: f = 0.022Punto mas desfavorable son las duchas del 2do. Nivel del pabellon C y SS.HH (alumnado) (punto T y punto L)La altura del tanque elevado es de 15.00 mt, restando 0.06 mt, que es la perdida de carga, nos da una presion enigual a 14.94 mt.A partir de alli va disminuyendo la presion en funcion de la distancia.La cota de terreno donde se ubica el tanque elevado es de 56.55 mtLa cota de terreno donde se ubican los 02 puntos mas desfavorables es de 56.45 mt, es decir habra 0.10 mt adicionala los valores de presion calculados