18
> Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting conductor screen, high dielectric strength EPR insulation, thermosetting semiconducting insulation screen, helically applied bare copper tape screen, cabled with fillers and ground conductors, overall binder tape, foamed polymeric layer for superior mechanical protection, longitudinally applied aluminium tape, extruded oil and hydrocarbon resistant polymeric layer, and overall sun resistant PVC jacket. > Conductors Plain annealed stranded copper wires according to IEC 60228, Class 2 > Conductor Screen Extruded semi conducting layer > Insulation EPR (Ethylene Propylene Rubber) insulation in accordance with IEC 60092-351 > Insulation Screen Extruded semi conducting layer > Metallic Screen Uncoated copper tape helically applied with a nominal 15% overlap > Earth conductors Plain annealed stranded copper wires according to IEC 60228, Class 2 > Assembly The cable interstices are filled with either an extruded halogen free non hydroscopic polymeric bedding or non hydroscopic filler yarns > Armour System An layer is extruded around the cable assembly. On top of this is a longitudinally applied aluminium tape with a nominal 10% overlap combined with an extruded oil and hydrocarbon resistant polymeric layer > Sheath A low temperature, flame retardant, moisture and sunlight resistant PVC jacket, ST2 quality. Standard colour red, other colours available on request. An optional LSOH outer jacket compound ST8 quality is also available Cable construction IEC 60332-3C VERY GOOD VERY GOOD -40 °C +90 °C GOOD r R=10D OFFSHORE & INDUSTRIAL THE RIGHT CHOICE AIR BAG TM 20 kV 3 Core Copper Conductors 90 °C rated, 3 Earth Conductors AIRGUARD TM CABLE SYSTEM Description

CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

  • Upload
    others

  • View
    22

  • Download
    0

Embed Size (px)

Citation preview

Page 1: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

> Three conductor cable with stranded copper conductors,extruded insulation system consisting of a thermosettingsemiconducting conductor screen, high dielectricstrength EPR insulation, thermosetting semiconductinginsulation screen, helically applied bare copper tapescreen, cabled with fillers and ground conductors, overallbinder tape, foamed polymeric layer for superiormechanical protection, longitudinally applied aluminiumtape, extruded oil and hydrocarbon resistant polymericlayer, and overall sun resistant PVC jacket.

> ConductorsPlain annealed stranded copper wires according toIEC 60228, Class 2

> Conductor ScreenExtruded semi conducting layer

> InsulationEPR (Ethylene Propylene Rubber) insulation in accordancewith IEC 60092-351

> Insulation ScreenExtruded semi conducting layer

> Metallic ScreenUncoated copper tape helically applied with a nominal15% overlap

> Earth conductorsPlain annealed stranded copper wires according toIEC 60228, Class 2

> AssemblyThe cable interstices are filled with either an extrudedhalogen free non hydroscopic polymeric bedding or nonhydroscopic filler yarns

> Armour SystemAn layer is extruded around the cable assembly.On top of this is a longitudinally applied aluminium tapewith a nominal 10% overlap combined with an extrudedoil and hydrocarbon resistant polymeric layer

> SheathA low temperature, flame retardant, moisture andsunlight resistant PVC jacket, ST2 quality. Standardcolour red, other colours available on request. Anoptional LSOH outer jacket compound ST8 quality isalso available

Cable construction

IEC 60332-3C VERYGOOD

VERYGOOD

-40 °C+90 °C

GOOD

r

R=10D

OFFSHORE& INDUSTRIAL

THE RIGHT CHOICE

AIR BAGTM

20 kV

3 Core Copper Conductors 90 °C rated,

3 Earth Conductors

AIRGUARDTM

C A B L E S Y S T E M

Description

Page 2: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

DATA SHEET

OFFSHORE& INDUSTRIAL

Prysmian Cavi e Sistemi SrlViale Sarca 222, 20126 Milano, Italy - tel. +39 02 6449 1, fax +39 02 6449 2931 - www.prysmian.com

THE RIGHT CHOICE

deg

a d

esig

n gr

oup

APPLICABLE STANDARDS AND APPROVALS• IEEE 45• IEC 60092-354 Design Guidelines• IEC 332-3 Cat C Fire Performance• Meets CSA-C22.2 No. 3 cold impact test (-40 °C) and cold

bend test (-40 °C)• BV witness of accessories testing to IEEE 48 & 404• ABS approved for offshore applications• US Coast Guard Approved

PRODUCT FEATURES• Cable is rated 90 °C continuous operating temperature,

130 °C emergency rating, 250 °C short circuit rating• Lighter, smaller and more flexible than equivalent rated

conventional armoured cable• Improved impact performance compared with the

conventional armoured cable• Improved lateral pressure performances compared with

conventional armoured cable• Compatible with standard jointing technology

RG7H1O(AR)H5R 3x35+3x6 19,2 44,0 53,5 2,7 60 4680 169 0,669 5,17RG7H1O(AR)H5R 3x50+3x10 20,3 46,2 55,9 2,8 62 5380 200 0,494 7,35RG7H1O(AR)H5R 3x70+3x10 22,0 49,9 60,5 2,9 67 6430 246 0,343 10,2RG7H1O(AR)H5R 3x95+3x10 23,6 53,3 63,9 3,0 71 6940 296 0,247 13,8RG7H1O(AR)H5R 3x120+3x10 25,1 56,5 67,2 3,1 74 8660 339 0,196 17,4RG7H1O(AR)H5R 3x150+3x16 26,4 59,4 70,1 3,2 77 9891 382 0,160 21,8RG7H1O(AR)H5R 3x185+3x16 28,0 62,9 73,5 3,3 81 11360 433 0,128 26,8RG7H1O(AR)H5R 3x240+3x16 30,4 68,1 78,7 3,5 86 13720 505 0,0982 34,7RG7H1O(AR)H5R 3x400+3x25 35,5 79,1 89,7 3,9 98 19530 644 0,0635 57,8

cabledescription

(mm) (mm) (mm) (mm) (in) (kg/km) (A) (Ω/km) (kA)

conductorsize

approxinsulationdiameter

approximatediameter

overlaying up

approxdiameter

overprotective

layers

jacketthickness

approxoverall

diameter

approxweight

currentrating in air

at 30 °C

max conductorA.C.

resistance at90 °C

conductorshort circuitcurrent for1 second

(mm2)

Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.

APPLICATIONS• Directly buried or embedded in concrete• Offshore applications • Suitable for variable frequency drive applications• Suitable for vertical installation• Economical alternative to traditional conduit systems• Suitable for harsh chemical and industrial environments • For direct burial, use in cable tray, indoor and outdoor

applications

Page 3: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

> Three conductor cable with stranded copper conductors,extruded insulation system consisting of a thermosettingsemiconducting conductor shield, high dielectricstrength EPROTENAX™ EPR insulation, thermosettingsemiconducting insulation shield, helically applied barecopper tape shield, cabled with fillers and groundingconductors, overall binder tape, foamed polymeric layerfor superior mechanical protection, longitudinally appliedaluminium tape, extruded oil and hydrocarbon resistantpolymeric layer, and overall sun resistant PVC jacket.

> ConductorsClass B Compact concentric strand soft drawn annealedcopper as per ASTM requirements

> Conductor ShieldExtruded thermosetting semiconducting shield which is freestripping from the conductor and bonded to the insulation

> InsulationNatural high dielectric strength EPROTENAX™ EPR-basedinsulation, combined with other materials and agents thatenhance the electrical and mechanical characteristicsassuring extended cable life

> Insulation ShieldExtruded thermoset semi-conducting stress control layer, free stripping from the EPR insulation.Meets ICEA S-93-639/NEMA WC74 and UL1072

> Metallic ShieldHelically applied non-magnetic copper tape(s) over the insulationshield with a minimum overlap of 15%. A Mylar ribbon islongitudinally applied under the copper tape shield for phaseidentification - 1C w/ Red, 1C w/ Blue, and 1C w/ Black

> Ground ConductorsBare stranded copper conductor, one in each interstice, as perUL, ICEA, and ASTM requirements

> AssemblyBare stranded copper conductor, one in each interstice,as per UL, ICEA, and ASTM requirements

> Mechanical ProtectionHigh strength and high crush resistant layerextruded over the core assembly

> Chemical ProtectionA longitudinal aluminium tape with a nominal 10% overlapoverwhich a chemical resistant extruded polymer layer is applied

> JacketA low temperature, flame retardant moisture and sunlightresistant PVC jacket. UL listed as type MV-105. An optional LSOH outer jacket is available on request

Cable construction

IEC 60332-3CIEEE 383

IEEE 1202

VERYGOOD

VERYGOOD

-40 °C+105 °C

GOOD

r

r=12D

OFFSHORE& INDUSTRIAL

THE RIGHT CHOICE

5 kV/8 kV, UL Type MV-105

3 Core Copper Conductors 105 °C Rating,

5 kV-133%, 8 kV-100% Insulation Level

AIRGUARDTM

C A B L E S Y S T E M

Description

AIR BAGTM

Page 4: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

DATA SHEET

OFFSHORE& INDUSTRIAL

Prysmian Cables and SystemsViale Sarca 222, 20126 Milano, Italy - tel. +39 02 6449 1, fax +39 02 6449 2931 - www.prysmian.com

THE RIGHT CHOICE

deg

a d

esig

n gr

oup

APPLICABLE STANDARDS AND APPROVALS• UL listed Type MV-105 “For CT Use” in accordance with UL 1072• CSA FT4 Flame Test, IEEE 383 Flame Test, and IEEE 1202

Flame Test• ICEA T-29-520 at 210,000 BTU/hr• CSA 22.2 cold impact test (-40°C) and cold bend test (-40°C)• ABS approved for offshore applications• BV witness of accessories testing to IEEE 48 & 404• US Coast Guard Approved• Oil Resistant I & II

PRODUCT FEATURES• Cable is rated 105 °C as defined in UL1072• Chemical and oil resistant to a wide range of fluids• Suitable for direct burial as defined in NEC section 310-7

and 300-50• Lighter, smaller and more flexible than equivalent rated

Continuous Corrugated Welded Aluminium cable• Improved impact performance compared with the Continuous

Corrugated Welded Aluminium cable• Compatible with standard jointing technology

Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.

21212 3 x 8 AWG CU 3 12 0,13 3,42 115 2,92 0,39 10,03 0,44 11,30 1,42 36 1270 1890 64 6621123 3 x 6 AWG CU 3 10 0,17 4,31 115 2,92 0,43 10,92 0,48 12,19 1,49 38 1490 2220 84 8821125 3 x 4 AWG CU 3 10 0,21 5,44 115 2,92 0,48 12,07 0,53 13,34 1,59 40 1760 2620 110 11521126 3 x 2 AWG CU 3 10 0,27 6,83 115 2,92 0,53 13,46 0,58 14,73 1,76 45 2280 3390 145 15421127 3 x 1 AWG CU 3 8 0,30 7,65 115 2,92 0,56 14,22 0,61 15,49 1,84 47 2590 3850 165 18021128 3 x 1/0 AWG CU 3 8 0,34 8,59 115 2,92 0,59 15,11 0,64 16,38 1,91 49 2910 4330 190 20521129 3 x 2/0 AWG CU 3 8 0,38 9,63 115 2,92 0,64 16,13 0,69 17,40 2,00 51 3310 4930 220 24021213 3 x 4/0 AWG CU 3 7 0,48 12,19 115 2,92 0,74 18,67 0,79 19,94 2,22 56 4420 6580 285 32021131 3 x 250 MCM CU 3 7 0,52 13,31 115 2,92 0,79 20,07 0,84 21,34 2,34 59 4990 7430 315 35521132 3 x 350 MCM CU 3 6 0,62 15,80 115 2,92 0,89 22,48 0,94 23,75 2,55 65 6330 9420 380 44021133 3 x 500 MCM CU 3 5 0,74 18,85 115 2,92 1,01 25,53 1,07 27,18 2,94 75 8570 12750 460 54521134 3 x 750 MCM CU 3 4 0,91 23,19 115 2,92 1,19 30,23 1,26 31,88 3,38 86 11940 17770 570 68521242 3 x 1000 MCM CU 3 4 1,06 26,90 115 2,92 1,34 34,04 1,41 35,69 3,69 94 14990 22310 645 790

product number

conductor ground wiresAWG

Ampacities are based on the followingDuct: Cable in underground electrical ducts; one cable per duct; based on an ambient temperature of 20°C; per NEC Table 310.79Air: Cable isolated in air and an ambient temperature of 40°C; per NEC Table 310.71

quantity

APPLICATIONS• Installations in both exposed and concealed locations in

accordance with NEC• Wet and dry locations in accordance with NEC • Directly buried or embedded in concrete• Installations on cable trays, troughs, metal racks, aerial

installations and continuous rigid cable supports inaccordance with NEC

• Economical alternative to traditional conduit systems• Suitable for variable frequency drive applications (VFD)• Suitable for vertical risers

size

conductor diameter

(in) (mm)

insulation thickness

(mils) (mm)

insulation diameter

(in) (mm)

insulation shield

diameter

(in) (mm)

approx jacket

diameter

(in) (mm)

approx cable

weight

(lbs/kft) (kg/km)

ampacity(amps)

105°C in duct

105°C in air

Page 5: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

> Three conductor cable with stranded copper conductors,extruded insulation system consisting of a thermosettingsemiconducting conductor screen, high dielectric strengthEPR insulation, thermosetting semiconducting insulationscreen, helically applied bare copper tape screen, cabledwith fillers and ground conductors, overall binder tape,foamed polymeric layer for superior mechanical protection,longitudinally applied aluminium tape, extruded oil andhydrocarbon resistant polymeric layer, and overall sunresistant PVC jacket.

> ConductorsPlain annealed stranded copper wires according toIEC 60228, Class 2

> Conductor ScreenExtruded semi conducting layer

> InsulationEPR (Ethylene Propylene Rubber) insulation inaccordance with IEC 60092-351

> Insulation ScreenExtruded semi conducting layer

> Metallic ScreenUncoated copper tape helically applied with a nominal15% overlap

> Earth ConductorsPlain annealed stranded copper wires according toIEC 60228, Class 2

> AssemblyThe cable interstices are filled with either an extrudedhalogen free non hydroscopic polymeric bedding or nonhydroscopic filler yarns.

> Armour SystemAn layer is extruded around the cable assembly.On top of this is a longitudinally applied aluminium tapewith a nominal 10% overlap combined with an extrudedoil and hydrocarbon resistant polymeric layer

> SheathA low temperature, flame retardant, moisture andsunlight resistant PVC jacket, ST2 quality.Standard colour red, other colours available onrequest. An optional LSOH outer jacket compoundST8 quality is also available

Cable construction

IEC 60332-3C VERYGOOD

VERYGOOD

-40 °C+90 °C

GOOD

r

R=10D

OFFSHORE& INDUSTRIAL

THE RIGHT CHOICE

AIR BAGTM

6 kV

3 Core Copper Conductors 90 °C rated,

3 Earth Conductors

AIRGUARDTM

C A B L E S Y S T E M

Description

Page 6: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

DATA SHEET

OFFSHORE& INDUSTRIAL

Prysmian Cables and SystemsViale Sarca 222, 20126 Milano, Italy - tel. +39 02 6449 1, fax +39 02 6449 2931 - www.prysmian.com

THE RIGHT CHOICE

deg

a d

esig

n gr

oup

APPLICABLE STANDARDS AND APPROVALS• IEEE 45• IEC 60092-354 Design Guidelines• IEC 332-3 Cat C Fire Performance• Meets CSA-C22.2 No. 3 cold impact test (-40 °C) and

cold bend test (-40 °C)• BV witness of accessories testing to IEEE 48 & 404• ABS approved for offshore applications• US Coast Guard Approved

PRODUCT FEATURES• Cable is rated 90 °C continuous operating temperature,

130 °C emergency rating, 250 °C short circuit rating• Lighter, smaller and more flexible than equivalent rated

conventional armoured cable• Improved impact performance compared with the

conventional armoured cable• Improved lateral pressure performances compared with

conventional armoured cable• Compatible with standard jointing technology

RG7H1O(AR)H5R 3x35+3x6 13,1 30,8 39,6 2,2 45 3000 164 0,668 5,17RG7H1O(AR)H5R 3x50+3x10 14,2 33,1 42,8 2,3 48 3660 193 0,494 7,35RG7H1O(AR)H5R 3x70+3x10 15,9 36,7 46,5 2,4 52 4520 240 0,342 10,2RG7H1O(AR)H5R 3x95+3x10 17,5 40,2 49,9 2,6 56 5620 291 0,247 13,8RG7H1O(AR)H5R 3x120+3x10 19,0 43,4 53,3 2,7 59 6580 334 0,196 17,4RG7H1O(AR)H5R 3x150+3x16 20,3 46,3 56,1 2,8 62 7720 377 0,160 21,8RG7H1O(AR)H5R 3x185+3x16 21,9 49,8 60,5 2,9 67 9130 425 0,128 26,8RG7H1O(AR)H5R 3x240+3x16 24,6 55,6 66,3 3,1 73 11360 496 0,0989 34,7RG7H1O(AR)H5R 3x300+3x25 27,7 62,1 72,9 3,3 80 13060 561 0,0800 43,4RG7H1O(AR)H5R 3x400+3x25 30,5 68,3 79,0 3,5 87 17200 637 0,0642 57,8

cabledescription

(mm) (mm) (mm) (kg/km) (A) (Ω/km) (kA)

conductorsize

approxinsulationdiameter

approxdiameter

overlaying up

approxdiameter over

protectivelayers

jacketthickness

approxoverall

diameter

approxweight

currentrating in air

at 30 °C

max conductorA.C.

resistance at90 °C

conductorshort circuitcurrent for1 second

(mm2) (mm) (in)

APPLICATIONS• Directly buried or embedded in concrete• Offshore applications • Suitable for variable frequency drive applications• Suitable for vertical installation• Economical alternative to traditional conduit systems• Suitable for harsh chemical and industrial environments• For direct burial, use in cable tray, indoor and outdoor

applications

Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.

Page 7: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

> Three conductor cable with stranded copper conductors,extruded insulation system consisting of a thermosettingsemiconducting conductor screen, high dielectric strengthEPR insulation, thermosetting semiconducting insulationscreen, helically applied bare copper tape screen, cabledwith fillers and ground conductors, overall binder tape,foamed polymeric layer for superior mechanical protection,longitudinally applied aluminium tape, extruded oil andhydrocarbon resistant polymeric layer, and overall sunresistant PVC jacket.

> ConductorsPlain annealed stranded copper wires according toIEC 60228, Class 2

> Conductor ScreenExtruded semi conducting layer

> InsulationEPR (Ethylene Propylene Rubber) insulation inaccordance with IEC 60092-351

> Insulation ScreenExtruded semi conducting layer

> Metallic ScreenUncoated copper tape helically applied with a nominal15% overlap

> Earth ConductorsPlain annealed stranded copper wires according toIEC 60228, Class 2

> AssemblyThe cable interstices are filled with either an extrudedhalogen free non hydroscopic polymeric bedding or nonhydroscopic filler yarns

> Armour SystemAn layer is extruded around the cable assembly.On top of this is a longitudinally applied aluminium tapewith a nominal 10% overlap combined with an extrudedoil and hydrocarbon resistant polymeric layer

> SheathA low temperature, flame retardant, moisture andsunlight resistant PVC jacket, ST2 quality.Standard colour red, other colours available onrequest. An optional LSOH outer jacket compoundST8 quality is also available

Cable construction

IEC 60332-3C VERYGOOD

VERYGOOD

-40 °C+90 °C

GOOD

r

R=10D

OFFSHORE& INDUSTRIAL

THE RIGHT CHOICE

10 kV

3 Core Copper Conductors 90 °C rated,

3 Earth Conductors

AIRGUARDTM

C A B L E S Y S T E M

AIR BAGTM

Description

Page 8: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

DATA SHEET

OFFSHORE& INDUSTRIAL

Prysmian Cables and SystemsViale Sarca 222, 20126 Milano, Italy - tel. +39 02 6449 1, fax +39 02 6449 2931 - www.prysmian.com

THE RIGHT CHOICE

deg

a d

esig

n gr

oup

APPLICABLE STANDARDS AND APPROVALS• IEEE 45• IEC 60092-354 Design Guidelines• IEC 332-3 Cat C Fire Performance• Meets CSA-C22.2 No. 3 cold impact test (-40 °C) and cold

bend test (-40 °C)• BV witness of accessories testing to IEEE 48 & 404• ABS approved for offshore applications• US Coast Guard Approved

PRODUCT FEATURES• Cable is rated 90 °C continuous operating temperature,

130 °C emergency rating, 250 °C short circuit rating• Lighter, smaller and more flexible than equivalent rated

conventional armoured cable• Improved impact performance compared with the

conventional armoured cable• Improved lateral pressure performances compared with

conventional armoured cable• Compatible with standard jointing technology

RG7H1O(AR)H5R 3x35+3x6 15,0 34,9 44,6 2,4 50 3500 164 0,668 5,17RG7H1O(AR)H5R 3x50+3x10 16,1 37,2 46,9 2,5 52 4140 196 0,494 7,35RG7H1O(AR)H5R 3x70+3x10 17,8 40,8 50,6 2,6 57 5070 243 0,342 10,2RG7H1O(AR)H5R 3x95+3x10 19,4 44,3 54,0 2,7 60 6150 294 0,247 13,8RG7H1O(AR)H5R 3x120+3x10 20,9 47,5 57,2 2,8 64 7140 338 0,196 17,4RG7H1O(AR)H5R 3x150+3x16 22,2 50,4 61,2 2,9 68 8390 378 0,160 21,8RG7H1O(AR)H5R 3x185+3x16 23,8 53,8 64,6 3,0 71 9760 427 0,128 26,8RG7H1O(AR)H5R 3x240+3x16 26,2 59,0 69,7 3,2 77 11950 500 0,0986 34,7RG7H1O(AR)H5R 3x300+3x25 28,9 64,7 75,4 3,4 83 14280 563 0,0798 43,4RG7H1O(AR)H5R 3x400+3x25 31,3 70,0 80,7 3,6 89 17950 638 0,0641 57,8

cabledescription

(mm) (mm) (mm) (kg/km) (A) (Ω/km) (kA)

conductorsize

approxinsulationdiameter

approxdiameter

overlaying up

approxdiameter over

protectivelayers

jacketthickness

approxoverall

diameter

approxweight

currentrating in air

at 30 °C

max conductorA.C.

resistance at90 °C

conductorshort circuitcurrent for1 second

(mm2) (mm) (in)

APPLICATIONS• Directly buried or embedded in concrete• Offshore applications • Suitable for variable frequency drive applications• Suitable for vertical installation• Economical alternative to traditional conduit systems• Suitable for harsh chemical environments • For direct burial, use in cable tray, indoor and

outdoor applications

Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.

Page 9: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

> Three conductor cable with stranded copper conductors,extruded insulation system consisting of a thermosettingsemiconducting conductor screen, high dielectric strengthEPR insulation, thermosetting semiconducting insulationscreen, helically applied bare copper tape screen, cabledwith fillers and ground conductors, overall binder tape,foamed polymeric layer for superior mechanical protection,longitudinally applied aluminium tape, extruded oil andhydrocarbon resistant polymeric layer, and overall sunresistant PVC jacket.

> ConductorsPlain annealed stranded copper wires according toIEC 60228, Class 2

> Conductor ScreenExtruded semi conducting layer

> InsulationEPR (Ethylene Propylene Rubber) insulation inaccordance with IEC 60092-351

> Insulation ScreenExtruded semi conducting layer

> Metallic ScreenUncoated copper tape helically applied with a nominal 15% overlap

> Earth ConductorsPlain annealed stranded copper wires according toIEC 60228, Class 2

> AssemblyThe cable interstices are filled with either an extrudedhalogen free non hydroscopic polymeric bedding or nonhydroscopic filler yarns

> Armour SystemAn layer is extruded around the cable assembly.On top of this is a longitudinally applied aluminium tapewith a nominal 10% overlap combined with an extrudedoil and hydrocarbon resistant polymeric layer

> SheathA low temperature, flame retardant, moisture andsunlight resistant PVC jacket, ST2 quality.Standard colour red, other colours available onrequest. An optional LSOH outer jacket compoundST8 quality is also available

IEC 60332-3C VERYGOOD

VERYGOOD

-40 °C+90 °C

GOOD

r

R=10D

OFFSHORE& INDUSTRIAL

THE RIGHT CHOICE

15 kV

3 Core Copper Conductors 90 °C rated,

3 Earth Conductors

AIRGUARDTM

C A B L E S Y S T E M

AIR BAGTM

Description

Cable construction

Page 10: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

DATA SHEET

OFFSHORE& INDUSTRIAL

Prysmian Cables and SystemsViale Sarca 222, 20126 Milano, Italy - tel. +39 02 6449 1, fax +39 02 6449 2931 - www.prysmian.com

THE RIGHT CHOICE

deg

a d

esig

n gr

oup

APPLICABLE STANDARDS AND APPROVALS• IEEE 45• IEC 60092-354 Design Guidelines• IEC 332-3 Cat C Fire Performance• Meets CSA-C22.2 No. 3 cold impact test (-40 °C) and cold

bend test (-40 °C)• BV witness of accessories testing to IEEE 48 & 404• ABS approved for offshore applications• US Coast Guard Approved

PRODUCT FEATURES• Cable is rated 90 °C continuous operating temperature,

130 °C emergency rating, 250 °C short circuit rating• Lighter, smaller and more flexible than equivalent rated

conventional armoured cable• Improved impact performance compared with the

conventional armoured cable• Improved lateral pressure performances compared with

conventional armoured cable• Compatible with standard jointing technology

RG7H1O(AR)H5R 3x35+3x6 17,2 39,6 49,3 2,5 55 4100 167 0,669 5,17RG7H1O(AR)H5R 3x50+3x10 18,3 41,9 51,6 2,6 58 4770 198 0,494 7,35RG7H1O(AR)H5R 3x70+3x10 20,0 45,6 55,2 2,7 61 5710 246 0,343 10,2RG7H1O(AR)H5R 3x95+3x10 21,6 49,0 59,7 2,9 66 6920 295 0,247 13,8RG7H1O(AR)H5R 3x120+3x10 23,1 52,2 62,9 3,0 69 7950 337 0,196 17,4RG7H1O(AR)H5R 3x150+3x16 24,4 55,1 65,8 3,1 73 9160 379 0,160 21,8RG7H1O(AR)H5R 3x185+3x16 26,0 58,6 69,2 3,2 76 10590 431 0,128 26,8RG7H1O(AR)H5R 3x240+3x16 28,4 63,7 74,4 3,4 82 12840 503 0,0984 34,7RG7H1O(AR)H5R 3x400+3x25 33,5 74,7 85,4 3,7 94 18540 642 0,0637 57,8

cabledescription

(mm) (mm) (mm) (kg/km) (A) (Ω/km) (kA)

conductorsize

approxinsulationdiameter

approxdiameter

overlaying up

approxdiameter over

protectivelayers

jacketthickness

approxoverall

diameter

approxweight

currentrating in air

at 30 °C

max conductorA.C.

resistance at90 °C

conductorshort circuitcurrent for1 second

(mm2) (mm) (in)

Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.

APPLICATIONS• Directly buried or embedded in concrete• Offshore applications • Suitable for variable frequency drive applications• Suitable for vertical installation• Economical alternative to traditional conduit systems• Suitable for harsh chemical and industrial environments • For direct burial, use in cable tray, indoor and outdoor

applications

Page 11: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

> Three conductor cable with stranded copper conductors,extruded insulation system consisting of a thermosettingsemiconducting conductor shield, high dielectri strengthEPROTENAX™ EPR insulation, thermosetting semiconductinginsulation shield, helically applied bare copper tape shield,cabled with fillers and grounding conductors, overallbinder tape, foamed polymeric layer for superior mechanicalprotection, longitudinally applied aluminium tape, extrudedoil and hydrocarbon resistant polymeric layer, andoverall sun resistant PVC jacket.

> ConductorsClass B Compact concentric strand soft drawn annealedcopper as per ASTM requirements

> Strand ShieldExtruded thermosetting semiconducting shield which isfree stripping from the conductor and bonded to theinsulation

> InsulationNatural high dielectric strength EPROTENAX™ EPR-basedinsulation, combined with other materials and agents thatenhance the electrical and mechanical characteristicsassuring extended cable life

> Insulation ShieldExtruded thermosetting semiconducting shield withcontrolled adhesion to the insulation providing therequired balance between electrical integrity and easeof stripping

> Metallic ShieldHelically applied non-magnetic copper tape(s) over theinsulation shield with a minimum overlap of 15%. AMylar ribbon is longitudinally applied under the coppertape shield for phase identification - 1C w/ Red, 1C w/Blue, and 1C w/ Black

> Ground conductorsBare stranded copper conductor, one in each interstice,as per UL, ICEA, and ASTM requirements

> AssemblyPhase identified shielded conductors cabled with fillersand grounding conductors (as specified), forming a firmand cylindrical cable core. A binder tape is applied tomaintain core symmetry and mechanical stability

> Mechanical ProtectionHigh strength and high crush resistant layerextruded over the core assembly

> Chemical ProtectionA longitudinal aluminium tape with a nominal 10% overlapover which a chemical resistant extruded polymer layeris applied

> JacketA low temperature, flame retardant moisture and sunlightresistant PVC jacket. UL listed as type MV-105. Anoptional LSOH outer jacket is available on request

Cable construction

IEC 60332-3CIEEE 383

IEEE 1202

VERYGOOD

VERYGOOD

-40 °C+105 °C

GOOD

r

R=12D

OFFSHORE& INDUSTRIAL

THE RIGHT CHOICE

15 kV, UL Type MV-105

3 Core Copper Conductors 90 °C Rating,

133% Insulation Level

AIRGUARDTM

C A B L E S Y S T E M

Description

AIR BAGTM

Page 12: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

DATA SHEET

OFFSHORE& INDUSTRIAL

Prysmian Cables and SystemsViale Sarca 222, 20126 Milano, Italy - tel. +39 02 6449 1, fax +39 02 6449 2931 - www.prysmian.com

THE RIGHT CHOICE

deg

a d

esig

n gr

oup

APPLICABLE STANDARDS AND APPROVALS• UL listed Type MV-105 “For CT Use” in accordance with

UL 1072• CSA FT4 Flame Test, IEEE 383 Flame Test, and IEEE 1202

Flame Test• ICEA T-29-520 at 210,000 BTU/hr• CSA 22.2 cold impact test (-40°C) and cold bend test (-40°C)• ABS approved for offshore applications• BV witness of accessories testing to IEEE 48 & 404• US Coast Guard Approved• Oil Resistant I & II

PRODUCT FEATURES• Cable is rated 105 °C as defined in UL1072• Chemical and oil resistant to a wide range of fluids• Suitable for direct burial as defined in NEC section 310-7

and 300-50• Lighter, smaller and more flexible than equivalent rated

Continuous Corrugated Welded Aluminium cable• Improved impact performance compared with the Continuous

Corrugated Welded Aluminium cable• Compatible with standard jointing technology

APPLICATIONS• Installations in both exposed and concealed locations in

accordance with NEC• Wet and dry locations in accordance with NEC• Directly buried or embedded in concrete• Installations on cable trays, troughs, metal racks, aerial

installations and continuous rigid cable supports in accordancewith NEC

• Economical alternative to traditional conduit systems• Suitable for variable frequency drive applications (VFD)• Suitable for vertical risers

21136 3 x 2 AWG CU 3 10 0,27 6,83 220 5,59 0,74 18,80 0,79 20,07 2,21 56 3200 4760 160 18521137 3 x 1 AWG CU 3 8 0,30 7,65 220 5,59 0,77 19,56 0,82 20,83 2,28 58 3540 5270 185 21021138 3 x 1/0 AWG CU 3 8 0,34 8,59 220 5,59 0,81 20,46 0,86 21,72 2,36 60 3900 5800 210 24021139 3 x 2/0 AWG CU 3 8 0,38 9,63 220 5,59 0,84 21,46 0,89 22,73 2,45 62 4330 6440 235 27521140 3 x 4/0 AWG CU 3 7 0,48 12,19 220 5,59 0,94 24,00 0,99 25,27 2,73 69 5730 8530 305 36021141 3 x 250 MCM CU 3 7 0,52 13,31 220 5,59 1,00 25,40 1,05 26,67 2,85 72 6350 9450 335 40021142 3 x 350 MCM CU 3 6 0,62 15,80 220 5,59 1,09 27,81 1,16 29,46 3,18 81 8070 12010 400 49021143 3 x 500 MCM CU 3 5 0,74 18,85 220 5,59 1,21 30,86 1,28 32,51 3,44 87 10150 15110 485 60021144 3 x 750 MCM CU 3 4 0,91 23,19 220 5,59 1,40 35,56 1,46 37,21 3,83 97 13560 20180 585 74521214 3 x 1000 MCM CU 3 4 1,06 26,90 220 5,59 1,55 39,37 1,64 41,66 4,20 107 16910 25170 660 860

product number

conductor ground wiresAWG

Ampacities are based on the followingDuct: Cable in underground electrical ducts; one cable per duct; based on an ambient temperature of 20°C; per NEC Table 310.79Air: Cable isolated in air and an ambient temperature of 40°C; per NEC Table 310.71

quantity size

conductor diameter

(in) (mm)

insulation thickness

(mils) (mm)

insulation diameter

(in) (mm)

insulation shield

diameter

(in) (mm)

approx jacket

diameter

(in) (mm)

approx cable

weight

(lbs/kft) (kg/km)

ampacity(amps)

105°C in duct

105°C in air

Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.

Page 13: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

> Three conductor cable with stranded copper conductors,extruded insulation system consisting of a thermosettingsemiconducting conductor shield, high dielectric strengthEPROTENAX™ EPR insulation, thermosetting semiconducting insulation shield, helically applied bare coppertape shield, cabled with fillers and grounding conductors,overall binder tape, foamed polymeric layer for superiormechanical protection, longitudinally applied aluminiumtape, extruded oil and hydrocarbon resistant polymericlayer, and overall sun resistant PVC jacket.

> ConductorsClass B Compact concentric strand soft drawn annealedcopper as per ASTM requirements

> Strand ShieldExtruded thermosetting semiconducting shield which is freestripping from the conductor and bonded to the insulation

> InsulationNatural high dielectric strength EPROTENAX™ EPR-basedinsulation, combined with other materials and agentsthat enhance the electrical and mechanical characteristicsassuring extended cable life

> Insulation ShieldExtruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the requiredbalance between electrical integrity and ease of stripping

> Metallic ShieldHelically applied non-magnetic copper tape(s) over theinsulation shield with a minimum overlap of 15%. A Mylarribbon is longitudinally applied under the copper tape shield forphase identification - 1C w/ Red, 1C w/ Blue, and 1C w/ Black

> Ground ConductorsBare stranded copper conductor, one in each interstice,as per UL, ICEA, and ASTM requirements

> AssemblyPhase identified shielded conductors cabled with fillersand grounding conductors (as specified), forming a firmand cylindrical cable core. A binder tape is applied tomaintain core symmetry and mechanical stability

> Mechanical ProtectionHigh strength and high crush resistant layerextruded over the core assembly

> Chemical ProtectionA longitudinal aluminium tape with a nominal 10% overlapover which a chemical resistant extruded polymer layeris applied

> JacketA low temperature, flame retardant moisture and sunlightresistant PVC jacket. UL listed as type MV-105. Anoptional LSOH outer jacket is available on request

Cable construction

IEC 60332-3CIEEE 383

IEEE 1202

VERYGOOD

VERYGOOD

-40 °C+105 °C

GOOD

r

R=12D

OFFSHORE& INDUSTRIAL

THE RIGHT CHOICE

AIR BAGTM

25 kV, UL Type MV-105

3 Core Copper Conductors 90 °C Rating,

133% Insulation Level

AIRGUARDTM

C A B L E S Y S T E M

Description

Page 14: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

DATA SHEET

OFFSHORE& INDUSTRIAL

Prysmian Cables and SystemsViale Sarca 222, 20126 Milano, Italy - tel. +39 02 6449 1, fax +39 02 6449 2931 - www.prysmian.com

THE RIGHT CHOICE

deg

a d

esig

n gr

oup

APPLICABLE STANDARDS AND APPROVALS• UL listed Type MV-105 “For CT Use” in accordance with

UL 1072• CSA FT4 Flame Test, IEEE 383 Flame Test, and IEEE 1202

Flame Test• ICEA T-29-520 at 210,000 BTU/hr• CSA 22.2 cold impact test (-40°C) and cold bend test (-40°C)• ABS approved for offshore applications• BV witness of accessories testing to IEEE 48 & 404• US Coast Guard Approved• Oil Resistant I & II

PRODUCT FEATURES• Cable is rated 105 °C as defined in UL1072• Chemical and oil resistant to a wide range of fluids• Suitable for direct burial as defined in NEC section 310-7

and 300-50• Lighter, smaller and more flexible than equivalent rated

Continuous Corrugated Welded Aluminium cable• Improved impact performance compared with the

Continuous Corrugated Welded Aluminium cable• Compatible with standard jointing technology

APPLICATIONS• Installations in both exposed and concealed locations in

accordance with NEC• Wet and dry locations in accordance with NEC• Directly buried or embedded in concrete• Installations on cable trays, troughs, metal racks, aerial

installations and continuous rigid cable supports inaccordance with NEC

• Economical alternative to traditional conduit systems• Suitable for variable frequency drive applications (VFD)• Suitable for vertical risers

21216 3 x 1 AWG CU 3 8 0,30 7,65 345 8,76 1,02 25,91 1,09 27,56 2,96 75 5260 7830 185 21021218 3 x 1/0 AWG CU 3 8 0,34 8,59 345 8,76 1,06 26,80 1,12 28,45 3,09 78 5810 8650 210 24021220 3 x 2/0 AWG CU 3 8 0,38 9,63 345 8,76 1,09 27,81 1,16 29,46 3,17 81 6310 9390 235 27521222 3 x 4/0 AWG CU 3 7 0,48 12,19 345 8,76 1,19 30,35 1,26 32,00 3,39 86 7660 11400 305 36021223 3 x 250 MCM CU 3 7 0,52 13,31 345 8,76 1,26 32,00 1,33 33,66 3,51 89 8370 12460 335 40021224 3 x 350 CM CU 3 6 0,62 15,80 345 8,76 1,36 34,42 1,42 36,07 3,72 94 9950 14810 400 49021225 3 x 500 MCM CU 3 5 0,74 18,85 345 8,76 1,48 37,47 1,54 39,12 3,98 101 12150 18080 485 60021226 3 x 750 MCM CU 3 4 0,91 23,19 345 8,76 1,66 42,16 1,75 44,45 4,33 110 15950 23740 585 74521227 3 x 1000 MCM CU 3 4 1,06 26,90 345 8,76 1,81 45,97 1,90 48,26 4,65 118 19330 28770 660 860

product number

conductor ground wiresAWG

Ampacities are based on the followingDuct: Cable in underground electrical ducts; one cable per duct; based on an ambient temperature of 20°C; per NEC Table 310.79Air: Cable isolated in air and an ambient temperature of 40°C; per NEC Table 310.71

quantity size

conductor diameter

(in) (mm)

insulation thickness

(mils) (mm)

insulation diameter

(in) (mm)

insulation shield

diameter

(in) (mm)

approx jacket

diameter

(in) (mm)

approx cable

weight

(lbs/kft) (kg/km)

ampacity(amps)

105°C in duct

105°C in air

Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.

Page 15: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

> Three conductor cable with stranded copper conductors,extruded insulation system consisting of a thermosettingsemiconducting conductor shield, high dielectricstrength EPROTENAX™ EPR insulation, thermosettingsemiconducting insulation shield, helically applied barecopper tape shield, cabled with fillers and groundingconductors, overall binder tape, foamed polymeric layerfor superior mechanical protection, longitudinally appliedaluminium tape, extruded oil and hydrocarbon resistantpolymeric layer, and overall sun resistant PVC jacket.

> ConductorsClass B Compact concentric strand soft drawn annealedcopper as per ASTM requirements

> Strand ShieldExtruded thermosetting semiconducting shield which is freestripping from the conductor and bonded to the insulation

> InsulationNatural high dielectric strength EPROTENAX™ EPR-basedinsulation, combined with other materials and agents thatenhance the electrical and mechanical characteristicsassuring extended cable life

> Insulation ShieldExtruded thermosetting semiconducting shield with controlledadhesion to the insulation providing the required balancebetween electrical integrity and ease of stripping

> Metallic ShieldHelically applied non-magnetic copper tape(s) over the insulationshield with a minimum overlap of 15%. A Mylar ribbon is longitudinally applied under the copper tape shield for phaseidentification - 1C w/ Red, 1C w/ Blue, and 1C w/ Black

> Ground conductorsBare stranded copper conductor, one in each interstice,as per UL, ICEA, and ASTM requirements

> AssemblyPhase identified shielded conductors cabled with fillersand grounding conductors (as specified), forming a firmand cylindrical cable core. A binder tape is applied tomaintain core symmetry and mechanical stability

> Mechanical ProtectionHigh strength and high crush resistant layer extruded over the core assembly

> Chemical ProtectionA longitudinal aluminium tape with a nominal 10% overlapover which a chemical resistant extruded polymer layer is applied

> JacketA low temperature, flame retardant moisture and sunlightresistant PVC jacket. UL listed as type MV-105. Anoptional LSOH outer jacket is available on request

Cable construction

IEC 60332-3CIEEE 383

IEEE 1202

VERYGOOD

VERYGOOD

-40 °C+105 °C

GOOD

r

R=12D

OFFSHORE& INDUSTRIAL

THE RIGHT CHOICE

AIR BAGTM

35 kV, UL Type MV-105

3 Core Copper Conductors 90 °C Rating,

133% Insulation Level

AIRGUARDTM

C A B L E S Y S T E M

Description

Page 16: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

DATA SHEET

OFFSHORE& INDUSTRIAL

Prysmian Cables and SystemsViale Sarca 222, 20126 Milano, Italy - tel. +39 02 6449 1, fax +39 02 6449 2931 - www.prysmian.com

THE RIGHT CHOICE

deg

a d

esig

n gr

oup

APPLICABLE STANDARDS AND APPROVALS• UL listed Type MV-105 “For CT Use” in accordance with

UL 1072• CSA FT4 Flame Test, IEEE 383 Flame Test, and IEEE 1202

Flame Test• ICEA T-29-520 at 210,000 BTU/hr• CSA 22.2 cold impact test (-40°C) and cold bend test (-40°C)• ABS approved for offshore applications• BV witness of accessories testing to IEEE 48 & 404• US Coast Guard Approved• Oil Resistant I & II

PRODUCT FEATURES• Cable is rated 105 °C as defined in UL1072• Chemical and oil resistant to a wide range of fluids• Suitable for direct burial as defined in NEC section 310-7

and 300-50• Lighter, smaller and more flexible than equivalent rated

Continuous Corrugated Welded Aluminium cable• Improved impact performance compared with the Continuous

Corrugated Welded Aluminium cable• Compatible with standard jointing technology

APPLICATIONS• Installations in both exposed and concealed locations in

accordance with NEC• Wet and dry locations in accordance with NEC• Directly buried or embedded in concrete• Installations on cable trays, troughs, metal racks, aerial

installations and continuous rigid cable supports inaccordance with NEC

• Economical alternative to traditional conduit systems• Suitable for variable frequency drive applications (VFD)• Suitable for vertical risers

Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.

21228 3 x 1/0 AWG CU 3 8 0,34 8,59 420 10,67 1,21 30,61 1,27 32,26 3,41 87 6800 10120 210 24021229 3 x 2/0 AWG CU 3 8 0,38 9,63 420 10,67 1,24 31,62 1,31 33,27 3,50 89 7330 10910 235 27521230 3 x 4/0 AWG CU 3 7 0,48 12,19 420 10,67 1,34 34,16 1,41 35,81 3,72 94 8740 13010 305 36021231 3 x 350 MCM CU 3 6 0,62 15,80 420 10,67 1,51 38,35 1,59 40,39 4,04 103 11120 16550 400 49021232 3 x 500 MCM CU 3 5 0,74 18,85 420 10,67 1,63 41,40 1,72 43,69 4,25 108 13560 20180 485 60021233 3 x 750 MCM CU 3 4 0,91 23,19 42 10,67 1,81 46,10 1,90 48,39 4,65 118 17350 25820 585 74521234 3 x 1000 MCM CU 3 4 1,06 26,90 420 10,67 1,96 49,91 2,05 52,20 5,00 127 20790 30940 660 860

productnumber

conductor ground wiresAWG

Ampacities are based on the followingDuct: Cable in underground electrical ducts; one cable per duct; based on an ambient temperature of 20°C; per NEC Table 310.79Air: Cable isolated in air and an ambient temperature of 40°C; per NEC Table 310.71

quantity size

conductor diameter

(in) (mm)

insulation thickness

(mils) (mm)

insulation diameter

(in) (mm)

insulation shield

diameter

(in) (mm)

approx jacket

diameter

(in) (mm)

approx cable

weight

(lbs/kft) (kg/km)

ampacity(amps)

105°Cin duct

105°Cin air

Page 17: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

> Three or four conductor cable with stranded copperconductors, extruded insulation system consisting ofhigh dielectric strength crosslinked polyethylene, cabledwith fillers and grounding conductors, foamed polymericlayer for superior mechanical protection, longitudinallyapplied aluminium tape, extruded oil and hydrocarbonresistant polymeric layer, and overall moisture and sunresistant black PVC jacket.

> ConductorsClass B compact concentric strand soft drawn annealedcopper as per ASTM requirements

> InsulationHigh dielectric strength cross link polyethylene insulationto ICEA S-95-658/NEMA WC70 and UL Standard 44 fortype XHHW-2

> Grounding ConductorsBare stranded copper conductor, one in each interstice,as per UL, ICEA, and ASTM requirements

> AssemblyPhase identified shielded conductors cabled with fillersand grounding conductors (as specified), forming a firmand cylindrical cable core

> Mechanical ProtectionHigh strength and high crush resistant layerextruded over the core assembly

> JacketA low temperature, flame retardant moisture and sunlightresistant black PVC jacket in accordance with UL standards.An optional LSOH outer jacket is available on request

Cable construction

IEC 60332-3CIEEE 383 - IEEE 1202

FT4

VERYGOOD

VERYGOOD

-40 °C+90 °C

GOOD

r

R=7xOD

OFFSHORE& INDUSTRIAL

THE RIGHT CHOICE

AIR BAGTM

600 V, Type TC Cable (XHHW-2)

3 and 4 Conductor Copper

90 °C Wet or Dry Rating

AIRGUARDTM

C A B L E S Y S T E M

Description

Page 18: CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting

DATA SHEET

conductor insulation thickness

ground wires

OFFSHORE& INDUSTRIAL

Prysmian Cables and SystemsViale Sarca 222, 20126 Milano, Italy - tel. +39 02 6449 1, fax +39 02 6449 2931 - www.prysmian.com

THE RIGHT CHOICE

deg

a d

esig

n gr

oup

APPLICABLE STANDARDS AND APPROVALS• UL listed as Type TC cable, UL 44• Single Conductor listed as XHHW-2• Fire performance rated IEEE 1202, IEEE 383 and IEC 332-3 Cat C• ICEA T-29-520 at 210,000BTU/hr• Meets CSA-C22.2 No. 3 cold impact and cold bend test (-40 °C)• ER "Exposed Run" Rated• ABS approved for offshore applications• US Coast Guard Approved• Oil Resistant I & II

PRODUCT FEATURES• Cable is rated 90°C as defined in UL44• Chemical and oil resistant to a wide range of fluids• Lighter, smaller and more flexible than equivalent rated

Continuous Corrugated Welded Aluminium cable• Improved impact performance compared with the Continuous

Corrugated Welded Aluminium cable• Compatible with standard jointing technology

sizequantity

APPLICATIONS• Replacement for MC cables• Installation in wet and dry locations in accordance with NEC• Installed directly buried or embedded in concrete• Installations on cable trays, troughs, metal racks, aerial

installations and continuous rigid cable supports inaccordance with NEC

• Economical alternative to traditional conduit systems• Suitable for variable frequency drive applications (VFD)• Suitable for vertical risers

(mils)

conductordiameter

(in)(A)

insulationdiameter

(in)(B)

jacketdiameter

(in)(D)

cableweight

minimumbendingradius

ampacity(amps)

90°Cin duct

14 AWG CU 30 3 18 AWG 0,073 0,13 0,57 244 6 2512 AWG CU 30 3 16 AWG 0,092 0,15 0,62 302 6 3010 AWG CU 30 3 14 AWG 0,116 0,18 0,68 380 7 40

8 AWG CU 45 3 14 AWG 0,146 0,24 0,81 529 8 556 AWG CU 45 3 12 AWG 0,184 0,27 0,94 748 9 754 AWG CU 45 3 12 AWG 0,232 0,32 1,04 968 10 952 AWG CU 45 3 10 AWG 0,292 0,38 1,18 1340 12 1301 AWG CU 55 3 10 AWG 0,332 0,44 1,32 1640 13 150

1/0 AWG CU 55 3 10 AWG 0,372 0,48 1,41 1918 14 1702/0 AWG CU 55 3 10 AWG 0,418 0,53 1,52 2292 15 1954/0 AWG CU 55 3 8 AWG 0,528 0,64 1,83 3450 18 260250 MCM CU 65 3 8 AWG 0,575 0,7 1,98 4024 20 290350 MCM CU 65 3 7 AWG 0,681 0,81 2,22 5312 22 350500 MCM CU 65 3 6 AWG 0,813 0,94 2,53 7194 25 430750 MCM CU 80 3 5 AWG 0,998 1,16 3,08 10705 31 535

1000 MCM CU 80 1 1/0 AWG 1,152 1,31 3,43 13644 34 615

Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.

Ampacities are based on the followingDuct: Not more than three current caryying conductors in raceway, cable, or earth (directly buried), Based on ambient temperature of 30°C (86°F) Per NEC Table 310.16

(Ibs/kft) (in)

Three conductor 600 VAIRGUARDTM