Progress Energy 2/25/2003 1

i

Page 2: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing

Agenda- -.

* Introduction

* Presentation

David Hinds

o Licensing Basis Lenny Belier

o Present Concern Roger

Rogero Resolution

* Conclusion

Sims Sims

David Hinds

SlProgress Energy 2

2/25/2003

EZZ

Page 3: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing

Licensing Bases i March 1981: Exemption Requested for

Automatic Suppression in Control Room (CR)and CSRs

* November 1981: Exemption Granted for CRo CSR Addressed Separately

* July 1982: NRC-CP&L Meeting

9 November 1982: NRC Denied ExemptionRequest

SsProgress Energy 32/25/2003

Page 4: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing

Licensing Bases

e May 1983 Exemption Request o "We propose the installation of a manually

operated, fixed sprinkler system located below the cable trays for these zones. The suppression systems will be designed to extinguish a transient combustible fire. We believe the proposed manually operated, fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R."

C Progress Energy 2/25/2003 4

Page 5: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing

Licensing Bases

* July 1983 SER o "However, you have proposed to install a manually

operated sprinkler system in the cable spreading room of each Brunswick unit. This type of fixed fire suppression meets the requirements of Section III.G.3 and therefore, an exemption is not needed.... Based on this discussion, we understand that you will begin modification of the Diesel Generator Building equipment hatches and the installation of fixed floor-mounted suppression systems in the Cable Spreading Rooms within six months."

SvProgress Energy 2/25/2003 5

Page 6: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing

Licensing Bases

. Resident Inspector ConsideredConfiguration a Risk Concern

* Task Interface Agreement Sent to NRC Headquarters

* Violation Proposed Against GDC 3

Progress Energy 62/25/2003

Page 7: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing

Present Concern - Initial Response

. Technical Study Performedi Correlated Sprinkler

Damage TimeResponse Vs. Cable

* Due to Lack of Validated Analysis Study Assumed Sprinkler System Actuate for Fire between Heads.

D Resident Inspector Provided a [ of Study

Method Would Not

Draft Copy

SJProgress Energy 72/25/2003

I-

Page 8: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing

Plan View

Sprinkler Heads

SJProgress Energy 82/25/2003

ISO=Islam

Page 9: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing

Section ViewN a- m,, - -.

TraysPlume

y _-------Sprinkler Head

Fire

Progress Energy 92/25/2003

Page 10: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing

Present Concern - Study Results

o 146 kW FireP No Cable Damage in 30 Minutes

o639 SCi

o783

kW Fire tble Damage in 30 Minutes

kW FireI Cable

9 In NoDamage in

Cases20 Minutes

Were both TrainsDamaged Due to a Single Fire

Progress Energy 102/25/2003

47,

8

Page 11: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing

Present Concern

* 10/2/02 NRC Inspection Report 02-03 o The licensee failed to install fixed fire suppression

systems that were capable of minimizing damage to safe shutdown cabling caused by floor level transient combustible fires in the Unit 1 and Unit 2 Cable Spreading Rooms (CSRs). The systems were determined to be unable to fulfill their intended function of limiting fire damage to the preferred trains of safe shutdown cables and safety-related cables in the CSRs.

SProgress Energy 2/25/2003 11

Page 12: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing

Alternatives for ResolutionEZZ.

* Install C System

,ode Compliant Sprinklerabove and within Cable Trays

Code )ssible

o May Not Satisfy FSAR Commitment

8 Progress Energy 2/25/2003 12

SSprinkler Contractor Stated Compliance May Not Be Pc

Page 13: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing

Alternatives for Resolution

* Remove Sprinkler Links o System Will Not Support All Heads Flowing

Hydraulically

Drainage Is a Problem

Progress Energy 132/25/2003

rzzz

I

Page 14: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing

Alternatives for Resolution

. Strengthen Other Areas of Defense-In-Depth P Requires NRC Approval

o No Physical Changes to Sprinkler System

Progress Energy 142/25/2003

Page 15: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing

Resolution- 1,. - 4.....�

"* Restrict Transient Combustibles below that Analyzed as Capable of Causing Cable Damage

"* Install Incipient Fire Detection System

"* Convert System from Manual to Automatic

. Submit Change to Licensing BasisRemove Term "and Extinguish"

Progress Energy 152/25/2003

LITI

to

Page 16: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing

Conclusions77-E

. Questions?

SJProgress Energy 162/25/2003