S
S
W
G I
GP
F
B
CT
M
FIRE ALARM
XX
XXXX
XX
XX
SMOKE DETECTOR/SENSOR FOR DUCT
XXGAS DETECTOR/SENSOR
XX=TYPECO2 = CARBON DIOXIDECO = CARBON MONOXIDEHCL = HYDROGEN CHLORIDECH4 = METHANE
XXFLAME DETECTOR/SENSOR
XX=TYPEUV = ULTRAVIOLETIR = INFRAREDUV/IR = COMBINATION UV /
INFRAREDVR = VISIBLE RADIATION
XXWATER DETECTOR
FH
HORN ONLY
FM
MINI-HORN
FCH
CHIME - ELECTRONIC
S SPEAKER ONLY
COMBINATION HORN/STROBE
cdCOMBINATION SPEAKER/VISIBLEcd = CANDELA RATING/SETTING
Mcd
EMERGENCY SPEAKER/VISIBLEcd = CANDELA RATING/SETTING
FV
BELL - VIBRATING
FSS
BELL - SINGLE STROKE
FT
BELL - TROUBLE
FG
BELL - GONG
FCH
BELL - CHIME
FOR THE ABOVE SYMBOLS:C=CEILING MOUNTEDW=WALL MOUNTED
VISIBLE ONLY (STROBE)WALL MOUNTcd = CANDELA RATING/SETTING
cd
VISIBLE ONLY (STROBE)CEILING MOUNTcd = CANDELA RATING/SETTING
cd
NOTES:1. WALL MOUNTED NOTIFICATION DEVICES MOUNTING HEIGHT: 80" AFF TO BOTTOM OF
FACEPLATE OR 6" FROM TOP OF FACEPLATE TO CEILING, WHICH EVER IS LOWER.
2. ALL CEILING MOUNTED DEVICES MOUNTED ON ACOUSTICAL CEILING TILE TO BECENTERED ON TILE, UNO.
3. ALL CEILING MOUNTED DEVICES MOUNTED IN HARD LID CEILING TO BE CENTERALIGNED WITH OTHER NEARBY CEILING EQUIPMENT, UNO.
4.PULL STATIONS TO BE MOUNTED 44" AFF, UNO.
MANUAL FIRE ALARM BOX TYPESXX=TYPE
CO2 = CARBON DIOXIDEDC = DRY CHEMICALDH = DOOR HOLDERHL = HALONF = PULL STATION/FIRE ALARM
BOXFO = FOAMWC = WET CHEMICALCA = CLEAN AGENTWM = WATER MISTDL = DELUGE FIRE SPRINKLERPRE = PREACTIONMB = FIRE ALARM MASTER BOXDK = DRILL KEYDS = DOOR HOLDER W/
SMOKE DETECTOR
HEAT DETECTOR/SENSORXX=TYPE
R/F = COMBINATION RATE OFRISE / FIXED TEMPERATURE
R/C = RATE COMPENSATIONF = FIXED TEMPERATURER = RATE OF RISE ONLY
SMOKE DETECTOR/SENSORXX=TYPE
AS = AIR SAMPLINGP = PHOTOELECTRICI = IONIZATIONR = RELAY BASESS = SINGLE STATIONSB = SOUNDER BASEID = IN DUCTBT = BEAM TRANSMITTERBR = BEAM RECEIVER
XXXX=TYPEFATC = FIRE ALARM TERMINAL
CABINETBATT = FIRE ALARM BATTERY
CABINETFACU = FIRE ALARM CONTROL UNITFAC = FIRE ALARM
COMMUNICATORWCU = WIRELESS CONTROL UNITGAP = GRAPHIC ANNUNCIATOR
PANELARCR = AREA OF REFUGE REMOTE
UNIT
CONTROL PANELS/UNITS
RECEPTACLES
DUPLEX RECEPTACLE
LOCKING RECEPTACLE
DUPLEX RECEPTACLE,UPPER HALF SWITCHED,LOWER HALF HOT
FIXED EQUIPMENT CONNECTION
FIXED EQUIPMENTCONNECTION,WALL MOUNT
MOUNTING LOCATION: WALLMOUNTING HEIGHT: 1'-6"
DUPLEX RECEPTACLE,EMERGENCY CIRCUIT
SINGLE RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE,EMERGENCY CIRCUIT
ABOVE CASEWORK MOUNTINGLOCATION: WALLMOUNTING HEIGHT: +44"
DUPLEX RECEPTACLE
DUPLEX RECEPTACLE,EMERGENCY CIRCUIT
DOUBLE DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE,EMERGENCY CIRCUIT
DUPLEX RECEPTACLE
MOUNTING LOCATION: CEILING
DUPLEX RECEPTACLE,EMERGENCY CIRCUIT
DOUBLE DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE,EMERGENCY CIRCUIT
RECEPTACLE TYPE DESIGNATION CHARTX = TYPE
AF = AFCI RECEPTACLECR = CONTROLLED RECEPTACLECH = CONTROLLED TOP HALF OFRECEPTACLEDR = DEDICATED RECEPTACLEGF = GFCI RECEPTACLETR = TAMPER RESISTANT RECEPTACLEUS = USB RECEPTACLEWP = WEATHERPROOF, GFCI RECEPTACLE
X
X
Xa
X
X
X
X
X
X
X
X
X
X
X
FIXED EQUIPMENT CONNECTIONMOUNTING HEIGHT/LOCATION:COORDINATE W/ EQUIPMENT
FIXED EQUIPMENT CONNECTION,EMERGENCY CIRCUIT
FIXED EQUIPMENT CONNECTION,WALL MOUNT, EMERGENCY CIRCUIT
X = RECEPTACLE TYPE, REFER TO CHART BELOWY = NEMA CONFIGURATION, REFER TO CHART BELOW
EQUIPMENT AND WIRINGMOTOR SURFACE JUNCTION BOX
SURFACE JUNCTION BOX - WALL
PANELBOARDSURFACE MOUNTED
PANEL DIVISION ARROW
REMOTE GROUND INDICATOR
ROOM REFERENCE GROUND POINT
AIR TERMINAL
PANEL DIVISION LINE
GROUND CONNECTION
T TRANSFORMER
PANELBOARDFLUSH MOUNTED
DISTRIBUTION PANELBOARD(NOT TO SCALE)
J
J
FLUSH JUNCTION BOX - CEILINGJ
FLUSH JUNCTION BOX - WALLJ
FLUSH JUNCTION BOX - FLOORJ
RELAY - TYPE AS NOTEDR
KIRK KEY INTERLOCKK
MOTOR CONTROL CENTERMCC NON-FUSED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
ENCLOSED CIRCUIT BREAKER
MAGNETIC MOTOR STARTER
COMBINATION MOTOR STARTER
CABLE TAP BOX
BUSWAY PLUG-IN UNIT
PUSH BUTTON
PUSH BUTTON - DOUBLE
REMOTE GENERATORANNUNCIATOR
GEN
AUTOMATIC TRANSFERSWITCH
VARIABLE FREQUENCY DRIVE
GROUND ROD
GROUND ROD WITH TEST WELL
XX-XX
VFD
ATS
LIGHTING CONTROLX
C
y
Z
y
ZS
SWITCHMOUNTING LOCATION: WALLMOUNTING HEIGHT: 3'-8"y=SWITCH DESIGNATION (lower
case)X=TYPE DEFINITION (SEE BELOW)
LIGHTING CONTACTORMOUNTING LOCATION: WALLMOUNTING HEIGHT: AS NOTED
SENSOR FOR LIGHTING CONTROLMOUNTING LOCATION: CEILING
y = SWITCH DESIGNATION (lower case)Z = SENSOR TYPE DESIGNATION
(SEE BELOW)SENSOR FOR LIGHTING CONTROL
MOUNTING LOCATION: WALLMOUNTING HEIGHT: 8'-0"
y = SWITCH DESIGNATION (lower case)
Z = SENSOR TYPE DESIGNATION(SEE BELOW)
SENSOR SWITCH FOR LIGHTINGCONTROL
MOUNTING LOCATION: WALLMOUNTING HEIGHT: 3'-8"y = SWITCH DESIGNATION (lower case)Z = SENSOR TYPE DESIGNATION
(SEE BELOW)
SENSOR TYPE DEFINITION:
Z = SENSOR TYPE DESIGNATION
OCCUPANCY MODE: AUTO ON, AUTO OFFPIR = PASSIVE INFRAREDPIR/D = PASSIVE INFRARED WITH DIMMER2P = 2 POLE, DUAL RELAYDT = DUAL TECHNOLOGY
VACANCY MODE: MANUAL ON, AUTO OFFVPIR = PASSIVE INFRAREDVPIR/D = PASSIVE INFRARED WITH
DIMMERVPIRA = PASSIVE INFRARED WITH
AMBIENT LIGHTVDT = DUAL TECHNOLOGY
TYPE DEFINITION:
X=TYPE DEFINITION= SINGLE POLE
3 = THREE-WAY SWITCH4 = FOUR-WAY SWITCH2 = TWO POLE SWITCH2P = 2 POLE, DUAL RELAYI = INDICATORK = KEY SWITCHMC = MOMENTARY CONTACTD = DIMMERP = SWITCH WITH PILOT LIGHTTS = TIMER SWITCHLV,LV# = LOW VOLTAGELV-M = LOW VOLTAGE "M"-
MASTER SWITCHDM = REMOTE CONTROL FOR
MOTORIZED DAMPER
y
ZS
LIGHTING
SHADED REGION DESIGNATES LUMINAIRE FOR LIFE SAFETY OPERATION
UNSHADED REGION DESIGNATES LUMINAIRE FOR NORMAL OPERATION
##/xx
X#
ARROW ADDED TO LUMINAIRESYMBOL TO INDICATEDIRECTION TOWARDS WHICHTHE LUMINAIRE IS TO POINT.
SUFFIX DESCRIPTION
E BATTERY PACK/INVERTER
LUMINAIRE SYMBOLS - REFER TO LUMINAIRE SCHEDULE FOR MOREINFORMATIONCEILING MOUNTED LUMINAIRES
RECESSED
SURFACE MOUNTED
SURFACE MOUNTED
SINGLE FACE DOUBLE FACE
EXIT SIGNS - WALL MOUNTED
EXIT SIGNS - CEILING MOUNTED
SINGLE FACE DOUBLE FACE DIRECTIONALARROW
DIRECTIONALARROW
CIRCUIT/SWITCH
LUMINAIRE ID - SEE LUMINAIRE SCHEDULE
BRANCH CIRCUIT SCHEDULE
SINGLE POLE - SINGLE PHASE
TWO POLE - SINGLE PHASE
TWO POLE - SINGLE PHASEWITH NEUTRAL
THREE POLE - THREE PHASE
THREE POLE - THREE PHASE4-WIREWITH NEUTRAL
BREAKER SIZE WIRE CONDUIT
20A-1P
30A-1P
40A-1P
50A-1P
60A-1P
2#12+1#12G 3/4"C
2#10+1#10G
2#8+1#10G
2#6+1#10G
2#4+1#10G
3/4"C
3/4"C
3/4"C
1 1/4"C
20A-2P
30A-2P
40A-2P
50A-2P
60A-2P
3/4"C
3/4"C
3/4"C
3/4"C
1 1/4"C
20A-2P
30A-2P
40A-2P
50A-2P
60A-2P
3/4"C
3/4"C
3/4"C
3/4"C
1 1/4"C
20A-3P
30A-3P
40A-3P
50A-3P
60A-3P
3/4"C
3/4"C
3/4"C
3/4"C
1 1/4"C
20A-3P
30A-3P
40A-3P
50A-3P
60A-3P
3/4"C
3/4"C
3/4"C
1"C
1 1/4"C
2#12+1#12G
2#10+1#10G
2#8+1#10G
2#6+1#10G
2#4+1#10G
3#12+1#12G
3#10+1#10G
3#8+1#10G
3#6+1#10G
3#4+1#10G
3#12+1#12G
3#10+1#10G
3#8+1#10G
3#6+1#10G
3#4+1#10G
4#12+1#12G
4#10+1#10G
4#8+1#10G
4#6+1#10G
4#4+1#10G
BRANCH CIRCUIT
ONE LINE DIAGRAM
METER WITH CURRENTTRANSFORMER
TRANSFORMER
PANELBOARD
#
P#
---
MOLDED CASE CIRCUIT BREAKER
GROUNDED "Y" SYSTEM
FEEDER TAG
SWITCHGEAR,SWITCHBOARD,DISTRIBUTION BOARDENCLOSURE
ELECTRICAL AND TECHNOLOGY SYMBOLS AND ABBREVIATIONS
SHEET SYMBOLS
ROOM NAME & NUMBERDESIGNATION
REVISION REFERENCE.REFER TO SHEET REVISIONBLOCK
SHEET KEYNOTE REFERENCE
SCHEDULED EQUIPMENT DESIGNATION.-TOP INDICATES EQUIPMENT ABBREVIATION-BOTTOM INDICATES EQUIPMENT NUMBER
REFER TO EQUIPMENT SCHEDULES1
EQ#
1
101ROOM NAME
ELECTRICAL ABBREVIATIONSA - AMPERESAC - ABOVE CEILING /
ALTERNATING CURRENTAF - AMPERE FRAMEAFCI - ARC FAULT CIRCUIT
INTERRUPTERAFF - ABOVE FINISHED FLOORAIC - AMP INTERRUPTING CAPACITYALT - ALTERNATEAP - ACCESS POINTAT - AMPERE TRIPATC - ASTRONOMIC TIME CLOCKATS - AUTOMATIC TRANSFER SWITCHAUTO - AUTOMATICAV - AUDIOVISUALAVC - AUDIOVISUAL CONTRACTORAWG - AMERICAN WIRE GAUGE
BAS - BUILDING AUTOMATION SYSTEMBC - BARE COPPERBCS - BUILDING CONTROL SYSTEMBEF - BUILDING ENTRANCE FACILITYBFC - BELOW FINISH CEILINGBFL - BELOW FLOOR LEVELBLDG - BUILDINGBMS - BUILDING MANAGEMENT
SYSTEMBRKR - BREAKER
C - CONDUITCAT - CATEGORYCB - CIRCUIT BREAKERCCTV - CLOSED CIRCUIT TELEVISIONCFCI - CONTRACTOR FURNISHED,
CONTRACTOR INSTALLEDCLG - CEILINGCKT - CIRCUITCO - CONDUIT ONLYCONTR - CONTRACTORCORR - CORRIDORCR - CONTROL RELAYCT - CURRENT TRANSFORMER/
CABLE TRAYCU - COPPER
D - DATADB - DIRECT BURIALDC - DIRECT CURRENTDED - DEDICATEDDET - DETAILDIA - DIAMETERDISC - DISCONNECTDN - DOWNDP - DISTRIBUTION PANELDS - DISCONNECT SWITCH
EC - ELECTRICAL CONTRACTOREF - ENTRANCE FACILITYEG - EQUIPMENT GROUNDEGC - EQUIPMENT GROUND
CONDUCTOREJ - EXPANSION JOINTELEC - ELECTRIC / ELECTRICALELEV - ELEVATOREM/EMER - EMERGENCYEMT - ELECTRICAL METALLIC TUBINGEQ - EQUALEQUIP - EQUIPMENTER - EQUIPMENT ROOMESM - ELECTRIC STRIP MOLDET - ELAPSED TIMERETR - EXISTING TO REMAIN
F/FC - FLUSH WITH FINISHED CEILINGF/FF - FLUSH WITH FINISHED FLOORF/FW - FLUSH WITH FINISHED WALLFA - FIRE ALARMFACP - FIRE ALARM CONTROL PANELFATC - FIRE ALARM TERMINAL CABINETFB - FLOOR BOXFCU - FAN COIL UNITFDR - FEEDERFDS - FUSED DISCONNECT SWITCHFIXT - FIXTUREFL - AT FLOOR LINEFLA - FULL LOAD AMPERESFLEX - FLEXIBLEFLR - FLOORFLUOR - FLUORESCENTFS - FLOW SWITCH
G - GROUNDGC - GENERAL CONTRACTORGEN - GENERATORGFCI - GROUND FAULT
CIRCUIT INTERRUPTERGFI - GROUND FAULT INTERRUPTERGFP - GROUND FAULT PROTECTIONGND - GROUNDGRC - GALVANIZED RIGID CONDUITGTB - GROUND TERMINAL BOX
HH - HANDHOLEHOA - HAND OFF AUTOMATICHP - HORSE POWERHT - HEIGHT / HEAT TRACEHV - HIGH VOLTAGE
IC - INSTALLED BY CONTRACTORIDF - INTERMEDIATE DISTRIBUTION
FACILITYIH - IMAGE HEIGHTIMC - INTERMEDIATE METAL CONDUITINV - INVERTERIT - INFORMATION TECHNOLOGYIW - IMAGE WIDTH
J or JB - JUNCTION BOXKO - KNOCK-OUTKV - KILOVOLTKVA - KILOVOLT-AMPERESKW - KILOWATTSKWH - KILOWATT HOURS
LED - LIGHT EMITTING DIODELI - LONG-TIME/INSTANTANEOUSLSI - LONG-TIME/SHORT-TIME/
INSTANTANEOUSLSIA - LONG-TIME/SHORT-TIME/
INSTANTANEOUS/GROUNDLSIG - LONG-TIME/SHORT-TIME/
INSTANTANEOUS/GROUNDLTG - LIGHTINGLTS - LIGHTSLV - LOW VOLTAGE
MC - MECHANICAL CONTRACTORMCB - MAIN CIRCUIT BREAKERMCP - MOTOR CIRCUIT PROTECTORMDF - MAIN DISTRIBUTION FACILITYMER - MECHANICAL EQUIPMENT ROOM/
MAIN EQUIPMENT ROOMMH - MANHOLE/MAINTENANCE HOLEMLO - MAIN LUGS ONLYMM - MULTIMODEMTD - MOUNTEDMTG - MOUNTINGMTG HGT - MOUNTING HEIGHTMTR - MOTOR / METERMV - MEDIUM VOLTAGE
NA - NOT APPLICABLENAC - NOTIFICATION APPLIANCE
CIRCUITNC - NORMALLY CLOSED/ NEW
CONNECTIONNEC - NATIONAL ELECTRICAL CODENIC - NOT IN CONTRACTNO - NORMALLY OPENNTS - NOT TO SCALE
OC - ON CENTEROFCI - OWNER FURNISHED,
CONTRACTOR INSTALLEDOFOI - OWNER FURNISHED,
OWNER INSTALLED
P - POLEP-P - POINT TO POINTPA - PUBLIC ADDRESSPB - PULL BOX / PUSHBUTTONPBX - PRIVATE BRANCH EXCHANGEPDU - POWER DISTRIBUTION UNITPF - POWER FACTORPH - PHASEPIR - PASSIVE INFRARED DETECTORPLBG - PLUMBINGPNL - PANELPR - PAIRPRT - PORTPS - POWER SUPPLYPT - POTENTIAL TRANSFORMERPWR - POWER
QTY - QUANTITY
RC - RELAY CONTACTREC - RECESSEDRECEP - RECEPTACLEREL - RELOCATEREQD - REQUIREDRGBHV - RED, GREEN, BLUE,HORIZONTAL, SYNC, VERTICAL SYNCRMC - RIGID METAL CONDUITRS - RECOMMENDED STANDARDRSVD - RESERVEDRVAT - REDUCED VOLTAGE
AUTO TRANSFORMER
SCCR - SHORT CIRCUIT CURRENT RATING
SHT - SHEETSIG - SIGNALSIM - SIMILARSIO - STANDARD INFORMATION
OUTLETSM - SINGLE MODESPD - SURGE PROTECTIVE DEVICESPEC - SPECIFICATIONSS - SAFETY SWITCHSSBJ - SUPPLY SIDE BONDING JUMPERSTA - STATIONSTD - STANDARDSTR - STARTERSW - SWITCHSWBD - SWITCHBOARDSYS - SYSTEM
TBB - TELECOMMUNICATIONSBACKBONETEL - TELEPHONETELE - TELECOMMUNICATIONSTELECOM- TELECOMMUNICATIONST(M)GB - TELECOMMUNICATIONS (MAIN)
GROUND BUSBAR.TO - TELECOMMUNICATIONS OUTLETTP - TAMPER PROOFTR - TELECOM ROOMTS - TAMPER SWITCH / TIME SWITCHTV - TELEVISIONTVTC - TELEVISION TERMINAL CABINETTYP - TYPICAL
UG - UNDERGROUNDUH - UNIT HEATERUNO - UNLESS NOTED OTHERWISEUSB - UNIVERSAL SERIAL BUSV - VOLTAGEVFD - VARIABLE FREQUENCY DRIVEVoIP - VOICE OVER INTERNET
PROTOCOLW - WIRE/WALL/WATTW/ - WITHWAP - WIRELESS ACCESS POINTWP - WEATHERPROOFWS - WALL SURFACEWT - WATER TIGHT
X - EXISTINGXFMR - TRANSFORMERXP - EXPLOSION PROOF
NOTE: SYMBOLS INDICATED HERE AND NOT USED IN THE CONTRACT DOCUMENTS DO NOT APPLY TO THIS PROJECT. ADDITIONAL SYMBOLS MAY BE INDICATED IN THE CONTRACTDOCUMENTS. UNLESS OTHERWISE NOTED, DIMENSIONS LISTED ARE MEASURED FROM FINISHED FLOOR TO CENTERLINE.
EXIT SIGNS - WALL MOUNTED
DOUBLE HEAD EMERGENCY FIXTUREWITH BATTERY PACK
ELECTRICAL SHEET INDEX - CONSTRUCTION DOCUMENTSSHEET TITLESHEET NO.
ELECTRICAL SYMBOLS AND ABBREVIATIONSE0
ELECTRICAL POWER AND LIGHTING PLANSE3
ELECTRICAL ONE-LINE DIAGRAM
E5 ELECTRICAL SCHEDULES
E4
ELECTRICAL SITE PLANE2
ELECTRICAL SITE DEMOLITION PLANE1
March 18, 2021
2
1
5 4
3 9
10
'L1'GFCI
GFCI
EUH1 EUH
2 EF1
GFCIWP
GFCI
1,3
2
2
2
2
5,7
9
8
6 7
8
6
A A
A
A
BEM
B
4
4
4
4
4
4
SCALE:1 1/4" = 1' - 0"ELECTRICAL POWER FLOOR PLAN
1
2
3
4
5
6
SCALE:2 1/4" = 1' - 0"LIGHTING FLOOR PLAN
7
8
9
10
1.
2.
3.
GENERAL NOTESREFER TO SHEET E0 FOR SYMBOLS AND ABBREVIATIONSAND ADDITIONAL GENERAL NOTES.
REFER TO SHEET E4 FOR ONE LINE DIAGRAM.
REFER TO SHEET M1 FOR MECHANICAL PLANS ANDINFORMATION.
CONTRACTOR SHALL COORDINATE WITH THE CONTRACTINGOFFICER TO KEEP AS MUCH OF THE PARK OPERATIONAL ASPOSSIBLE AS WORK IS BEING CARRIED OUT.
NEW 100A 120/240V, SINGLE PHASE ELECTRICAL PANEL..
NEW TANK LEVEL RTU CONTROL PANEL. VERIFY EXACTLOCATION WITH THE CONTRACTING OFFICER PRIOR TOROUGH-IN.
RELOCATED FLOW METER READOUT/TRANSMITTER. VERIFYEXACT LOCATION WITH THE CONTRACTING OFFICER PRIORTO ROUGH-IN.
PROVIDE GFCI RECEPTACLE IN NEMA 4X ENCLOSURE ANDPVC COATED RIGID METAL CONDUIT IN CHLORINATIONROOM. ELECTRICAL INFRASTRUCTURE IN CHLORINATIONROOM SHALL BE RATED FOR CORROSIVE ENVIRONMENTS.SEE SPECIFICATION SECTIONS 262726 AND 260533.
PROVIDE WEATHER PROOF GFCI RECEPTACLE WITH IN-USEWET RATED COVER ASSEMBLY.
PROVIDE EXTERIOR WALL PACK LUMINAIRE WITH INTEGRALMOTION SENSOR CONTROL. REFER TO LUMINAIRESCHEDULE FOR ADDITIONAL INFORMATION.
PROVIDE DOUBLE HEAD EMERGENCY FIXTURE WITH90-MINUTE BATTERY PACK. REFER TO LUMINAIRESCHEDULE FOR ADDITIONAL INFORMATION.
CHLORINATION ROOM LIGHT SWITCH. SWITCH SHALL BECORROSION RESISTANT IN A NEMA 4X ENCLOSURE.
GROUND TRIAD. REFER TO SPECIFICATION 26 05 26 ANDDRAWING E4 FOR ADDITIONAL INFORMATION.
GROUND ROD TEST WELL. 8" DIAMETER, PVC WELL WITHSCREW IN CAP. EXTEND WELL DOWN TO EXPOSE GROUNDROD AND CONNECTION TO GROUND RING.
SHEET KEYNOTES
4.
March 18, 2021
M
SCALE:1 NTSDEMOLITION - ELECTRICAL ONE-LINE DIAGRAM
SCALE:2 NTSNEW EQUIPMENT BUILDING - ELECTRICAL ONE-LINE DIAGRAM
23
1
4 5
6
7M
(E) EQUIPMENT BUILDINGEXTERIOR INTERIOR
TO (E) UTILITYSECTIONALIZING CABINET
(E)200 AMP
PANEL H1
(E)10 KVA 7200V
PRIMARY;120/240VSECONDARY
TRANSFORMER
(E)UTILITY METERPEDESTAL TO
REMAIN
(E)BUILDING
DISCONNECT(E)
LEVELCONTROL
PANEL
(E)ROSEMOUNTTRANSDUCERTRANSMITTER
EXISTING BUILDINGDISCONNECT TO BE REMOVED.
EXISTING 200 AMP ELECTRICALPANEL TO BE REMOVED.
EXISTING LEVEL CONTROL PANELTO BE REMOVED.
EXISTING FLOW METERREADOUT/TRANSMITTER PANEL TO BESALVAGED AND RELOCATED.
EXISTING TRANSDUCERTRANSMITTER TO BE REMOVED.
EXISTING UTILITYTRANSFORMER TO REMAIN.
EXISTING FEEDERCONDUCTORS AND CONDUIT
TO BE REMOVED
EXISTING CONNECTION TO (E)PRESSURE TRANSDUCER TO BE
REMOVED
(E)PRESSURE
TRANSDUCER
EXISTING CONNECTION TO (E)SINGER VALVE TO BE REMOVED
EXISTING CONTROL WIRING TO(E) VALVES TO BE REMOVED
EXISTING PRESSURETRANSDUCER TO BE REMOVED
(E) FLOW METER
READOUT/TRANSMITTER
PANEL
PANEL 'L1' 100A 120/240V, 1P
EQUIPMENT BUILDINGEXTERIOR INTERIOR
20A/
1P
20A/
1P
LTG
TANKLEVELRTU
CONTROLPANEL(3-#2/0; #6 GND) 2" C
BURIEDMETALWATER
PIPE
CONCRETEENCASED
ELECTRODE
1-#6 CU 1-#6 CU1-#6 CU
1-#6 CU
15A/
1P
20A/
1P
EXH
AUST
FAN
20A/
1P
TO (E) UTILITYSECTIONALIZING CABINET
25A/
2P
15A/
2PEL
ECTR
IC H
EAT
ELEC
TRIC
HEA
T(E)10 KVA 7200V
PRIMARY;120/240VSECONDARY
TRANSFORMEREXISTING UTILITY
TRANSFORMER TO REMAIN.
30A/
2P
SPD
(3-#2/0; #6 GND) 2" C
REC
EPTA
CLE
S
NEW ROSEMONTPRESSURE
TRANSMITTER
TO LTEANTENNA
LOCATED ONTOP OF NEWWATER TANK
(E) FLOW METER
READOUT/TRANSMITTER
PANEL
CHLORINATION ROOM
NEW MAG FLOWSENSOR
20A/
1P
20A/
1P
20A/
1P
20A/
1P
SPARES
Isc-1
BLDSTEEL
Isc-2
1-#6 CU
MAIN GROUND BAR(BONDING TERMINAL)
TO (E) SINGER VALVE
GROUNDINGTRIAD
LIGHTNING ARRESTER. SEESPECIFICATION SECTION 230901FOR ADDITIONAL INFORMATION
1-#6 CU
LIGHTNINGARRESTER
GROUNDINGROD
EXISTING UTILITYMETER TO REMAIN.
100/2
SSD
LIGHTNINGPROTECTIONGROUNDING
RING
1-#6 CU
SEE SPECIFICATION SECTION230901 FOR DESIGN AND
SUBMITTAL REQUIREMENTS
NG
(E)UTILITY METERPEDESTAL TO
REMAINEXISTING UTILITYMETER TO REMAIN.
100/2NG
100A/2PMCB
1
2
3
4
5
6
7
1.
2.
3.
4.
GENERAL NOTESREFER TO SHEET E0 FOR SYMBOLS AND ABBREVIATIONSAND ADDITIONAL GENERAL NOTES.
ALL EXISTING BRANCH CIRCUIT WIRING SHALL BE REMOVEDAND REPLACED AS PART OF THE SCOPE OF THIS PROJECT.
CONTRACTOR SHALL OBTAIN WRITTEN PERMISSION FROMTHE CONTRACTING OFFICER TO SHUT OFF SERVICES ORSYSTEMS WHICH WILL AFFECT AREAS WITHIN THEBUILDING. SUCH PERMISSION WILL BE COORDINATED WITHTHE CONTRACTING OFFICER TO STATE THE DURATION OFTHE OUTAGE AND THE AREAS AFFECTED.
CONTRACTOR SHALL COORDINATE WITH THECONTRACTING OFFICER TO KEEP AS MUCH OF THE PARKOPERATIONAL AS POSSIBLE AS WORK IS BEING CARRIEDOUT.
EXISTING UTILITY TRANSFORMER TO REMAIN.
EXISTING SERVICE ENTRANCE AT EXISTING METERPEDESTAL.
NEW 100A 120/240V SINGLE-PHASE PANEL.
NEW TANK LEVEL RTU CONTROL PANEL. VERIFY EXACTLOCATION WITH OWNER PRIOR TO ROUGH-IN.
RELOCATED FLOW METER READOUT/TRANSMITTER. VERIFYEXACT LOCATION WITH OWNER PRIOR TO ROUGH-IN.
EXTERNALLY MOUNTED SURGE PROTECTION DEVICE.
SURGE SUPPRESSION DEVICE. SEE SPECIFICATION SECTION230901 FOR ADDITIONAL INFORMATION.
SHEET KEYNOTES
March 18, 2021
TOTAL AMPS 33 A 39 ATOTAL LOAD 7.92 kVA 9.37kVA
HEATING 5.40 kVA 125% 6.75 kVARECEPTACLE 0.72 kVA 100% FIRST 10KVA, 50% OTHER 0.72 kVA
MOTOR 0.10 kVA 125% LARGEST, 100% OTHER 0.13 kVALIGHTING 0.30 kVA 125% 0.37 kVA
POWER 1.40 kVA 100% 1.40 kVALOAD CLASSIFICATION CONNECTED (KVA) DEMAND FACTOR DEMAND (KVA)
PHASE SUBTOTAL (AMPS): 31 A 35 APHASE SUBTOTAL (kVA): 3.72 4.20
A BTOTAL PHASE SUMMARY
SPACE -- -- -- 29 0.00 0.00 30 -- -- -- SPACESPACE -- -- -- 27 0.00 0.00 28 -- -- -- SPACESPACE -- -- -- 25 0.00 0.00 26 -- -- -- SPACESPACE -- -- -- 23 0.00 0.00 24 -- -- -- SPACESPACE -- -- -- 21 0.00 0.00 22 -- -- -- SPACESPACE -- -- -- 19 0.00 0.00 20 -- -- -- SPACESPARE 20 A 1 17 0.00 0.00 18 -- -- -- SPACESPARE 20 A 1 15 0.00 0.00 16 -- -- -- SPACE-- -- -- -- 13 0.00 0.00 14 -- -- -- SPACESPD 30 A 2 11 0.00 0.00 12 1 20 A SPAREEF-1 15 A 1 9 0.10 0.00 10 1 20 A SPARE-- -- -- -- 7 0.90 1.20 8 1 20 A TANK LEVEL RTU CONTROL PANELEUH-2 15 A 2 5 0.90 0.20 6 1 20 A EXISTING SINGER VALVE-- -- -- -- 3 1.80 0.30 4 1 20 A LIGHTINGEUH-1 20 A 2 1 1.80 0.72 2 1 20 A RECEPTACLE
DESCRIPTION BRKRNOTES
BRKRAMP,
POLESCKTNO A B A B CKT NO
BRKRAMP,
POLESBRKRNOTES DESCRIPTION
LEFT SIDE, kVA RIGHT SIDE, kVA
REMARKS:
ENCLOSURE NEMA 1 CALCULATED AVAILABLE FAULT... kABUS RATING 100 A MOUNTING SURFACE SCCR 10 kA
MAIN RATING 100 A 1 PHASE 3 WIRE FED FROMMAIN TYPE MCB VOLTAGE 120/240 Single LOCATION LEVEL 1,
L1
MECHANICAL EQUIPMENT SCHEDULE
EQUIPMENT MOTOR/EQUIPMENT DATA CIRCUIT INFORMATION CONDUIT AND WIRE REQUIREMENTS CONTROLLER/DISCONNECT INFORMATION
EQ. TAG EQ. ID DESCRIPTION LEVEL VOLTAGE PH QTYAPPARENTLOAD (kVA) FLA (A) MCA (A) PANEL CIRCUIT # CB SIZE # SETS
# OFCONDUCTORS
CONDUCTORSIZE
GROUNDCONDUCTOR
SIZECONDUIT
SIZE
PROVISION OFCONTROLS/CONTROLLER PROVISION OF DISCONNECTING MEANS
DIV 26 OTHER DIVISION BY DIV 26 OTHER DIVISION
EF 1 EXHAUST FAN LEVEL 1 120 V 1 1 0.10 kVA 1 A 1 A L1 9 15 A 1 SET 1 + NEUTRAL #12 #12 G 3/4" C - DIV 23 -
EUH 1 ELECTRIC UNIT HEATER LEVEL 1 240 V 1 1 3.60 kVA 15 A 19 A L1 1,3 20 A 1 SET 2 #12 #12 G 3/4" C - DIV 23 -EUH 2 ELECTRIC UNIT HEATER LEVEL 1 240 V 1 1 1.80 kVA 8 A 9 A L1 5,7 15 A 1 SET 2 #12 #12 G 3/4" C - DIV 23 -
2.0
-
--
VOLTAGE DROP AT DEMAND LOAD
VOLTAGE DROP AT 80% OF PANEL RATING - FOR FUTURE REFERENCE ONLY
March 18, 2021
ABBREVIATIONS - EQUIPMENT
EF - EXHAUST FANEUH - ELECTRIC UNIT HEATER
ADJ - ADJUSTABLEAFF - ABOVE FINISHED FLOORAL - ALUMINUMALT - ALTERNATEAP - ACCESS PANELAVG - AVERAGE
BE - BATTERY EXHAUSTBHP - BRAKE HORSEPOWERBOD - BOTTOM OF DUCTBOP - BOTTOM OF PIPEBTU - BRITISH THERMAL UNITBTUH - BRITISH THERMAL UNITS
PER HOURBWE - BAKED WHITE ENAMEL
CA - COMBUSTION AIRCAP - CAPACITYCAV - CONSTANT AIR VOLUMECE - CAGEWSH EXHAUSTCFCI - CONTRACTOR FURNISHED,
CONTRACTOR INSTALLEDCFH - CUBIC FEET PER HOURCFM - CUBIC FEET PER MINUTECL - CENTERLINECLG - CEILINGCOND - CONDENSATE /
CONDENSERCONN - CONNECTIONCOP - CENTER OF PIPECS - CARBON STEELCU - COPPER
DAT - DISCHARGE AIR TEMPERATUREDB - DRY BULBDDC - DIRECT DIGITAL CONTROLDE - DISHWASHER EXHAUSTDIA - DIAMETERDIM - DIMENSIONDP - DEW POINTDX - DIRECT EXPANSION
EA - EXHAUST AIR / EACHEAT - ENTERING AIR TEMPERATUREEC - ELECTRICAL CONTRACTOREDR - EQUIVALENT DIRECT RADIATIONEFF - EFFICIENCYEG - ETHYLENE GLYCOLEL - ELEVATIONESP - EXTERNAL STATIC PRESSUREETR - EXISTING TO REMAINEWT - ENTERING WATER
TEMPERATUREEXH - EXHAUST
FA - FIELD ADJUSTABLEFAT - FINAL AIR TEMPERATUREFC - FAIL CLOSEDFE - FUME HOOD EXHAUSTFLA - FULL LOAD AMPSFLP - FAIL LAST POSITIONFLR - FLOORFO - FAIL OPENFPI - FINS PER INCHFPM - FEET PER MINUTEFPS - FEET PER SECONDFT - FEET
GA - GAUGEGAL - GALLONSGC - GENERAL CONTRACTORGE - GENERAL EXHAUSTGPM - GALLONS PER MINUTEGR - GRAINSGS - GALVANIZED STEEL
H - HEIGHTHP - HORSE POWER /
HIGH POINTHR - HUMIDITY RATIO /
HOURHZ - HERTZ
IA - INSTRUMENT AIRIE - INVERT ELEVATIONIN - INCH
KE - KITCHEN EXHAUSTKO - KNOCK-OUTKW - KILOWATTKWH - KILOWATT - HOUR
L - LENGTHLAT - LEAVING AIR TEMPERATURELB - POUNDLBS - POUNDSLEA - LABORATORY EXHAUST AIRLP - LOW POINTLSA - LABORATORY SUPPLY AIRLWT - LEAVING WATER TEMPERATURE
MAX - MAXIMUMMBH - THOUSANDS OF BTU PER HOURMC - MECHANICAL CONTRACTORMEP - MECHANICAL, ELECTRICAL,
AND PIPINGMER - MECHANICAL EQUIPMENT ROOMMIN - MINIMUM
NA - NOT APPLICABLENC - NORMALLY CLOSEDNIC - NOT IN CONTRACTNO - NORMALLY OPENNOM - NOMINALNPS - NOMINAL PIPE SIZENPT - NATIONAL PIPE THREADNTS - NOT TO SCALE
OA - OUTSIDE AIROC - ON CENTEROED - OPEN END DUCTOFCI - OWNER FURNISHED,
CONTRACTOR INSTALLEDOFOI - OWNER FURNISHED,
OWNER INSTALLEDOV - OUTLET VELOCITY
PA - PLANT AIRPC - PLUMBING CONTRACTORPCF - POUNDS PER CUBIC FOOTPD - PRESSURE DROPPG - PROPYLENE GLYCOLPH - PHASEPP - POLYPROPYLENEPPH - POUNDS PER HOURPSF - POUNDS PER SQUARE FOOTPSI - POUNDS PER SQUARE INCHPSIA - POUNDS PER SQUARE INCH
ABSOLUTEPSIG - POUNDS PER SQUARE INCH
GAUGE
QTY - QUANTITY
RA - RETURN AIRRH - RELATIVE HUMIDITYRPM - REVOLUTIONS PER MINUTE
SA - SUPPLY AIRSCCR - SHORT CIRCUIT CURRENT RATINGSCH - SCHEDULESOG - SLAB ON GRADESP - STATIC PRESSURESQ - SQUARESS - STAINLESS STEEL
TA - TRANSFER AIRTBR - TO BE REMOVEDTCC - TEMPERATURE CONTROL
CONTRACTORTE - TOILET EXHAUSTTOB - TOP OF BEAMTOD - TOP OF DUCT /
TOP OF DECKTOJ - TOP OF JOISTTOP - TOP OF PIPETOS - TOP OF SLABTSP - TOTAL STATIC PRESSURE
V - VOLTSVAV - VARIABLE AIR VOLUMEVEA - VIVARIUM EXHAUST AIRVEL - VELOCITYVP - VELOCITY PRESSUREVSA - VIVARIUM SUPPLY AIRVTR - VENT THRU ROOF
W - WATT / WIDTH
WB - WET BULBWC - WATER COLUMNWG - WATER GAUGEWMG - WIRE MESH GRILLEWPD - WATER PRESSURE DROPWWM - WELDED WIRE MESH
X - EXISTING
ABBREVIATIONS - GENERAL
SYMBOLS INDICATED HERE AND NOT USED IN THE CONTRACT DOCUMENTS DO NOTAPPLY TO THIS PROJECT. ADDITIONAL SYMBOLS MAY BE INDICATED IN THE CONTRACT
DOCUMENTS.
MECHANICAL SYMBOLS ANDABBREVIATIONS
G - RETURN OR EXHAUST GRILLESD - SUPPLY GRILLELD - LINEAR DIFFUSERLG - LINEAR RET/EXH GRILLETG - TRANSFER GRILLE
25012x6 G-112x6 EA
EXHAUST AIR DUCTRETURN AIR DUCT (RA)
NECK SIZE IN INCHES
AIR QUANTITY (CFM)DUCT SIZE IN INCHES(NET INSIDE DIMENSIONS)FIRST FIGURE: SIDE SHOWNSECOND FIGURE: SIDE NOTSHOWN
GRILLE, REGISTER NOTATION
EXHAUST OR RETURNREGISTER OR GRILLE(VERTICAL MOUNT)
SUPPLY REGISTER ORGRILLE (VERTICALMOUNT)
DOUBLE LINE-HARD ORFLEXIBLE CONNECTION
DUCTWORK AT DIFFUSERS & GRILLES
T THERMOSTAT OR TEMPERATURE SENSOR
FIELD MOUNTED CONTROLS
SHEET SYMBOLS
SHEET KEYNOTE REFERENCESCHEDULED EQUIPMENT DESIGNATION.
-TOP INDICATES EQUIPMENT ABBREVIATION-BOTTOM INDICATES EQUIPMENT NUMBER
REFER TO EQUIPMENT SCHEDULES
1EQ#
BDD - BACKDRAFT DAMPER
G - GRILLE
MECHANICAL SHEET INDEX - CONSTRUCTION DOCUMENTSSHEET TITLESHEET NO.
MECHANICAL SYMBOLS AND ABBREVIATIONSM0
MECHANICAL PLANM1
March 18, 2021
EUH1
EUH2
EF1
10x10 EA
T
BACKDRAFTDAMPER
T
SCALE:1 1/4" = 1' - 0"MECHANICAL FLOOR PLAN
1
2
1
3
3
2
GENERAL NOTES1. REFER TO SHEET M0 FOR SYMBOLS AND ABBREVIATIONS.
2. CONTRACTOR SHALL COORDINATE WITH THE PARK STAFF TOKEEP AS MUCH OF THE PARK OPERATIONAL AS POSSIBLE ASWORK IS BEING CARRIED OUT.
FAN SHALL BE PROVIDED WITH DOOR CLOSURESWITCH AND TIMER DIAL.
PROVIDE 10x10 EA DUCT DOWN WITH 45° ELBOW ATOPENING LOCATED WITHIN 12" OF FINISHED FLOOR.PROVIDE 12" 316 SS BIRD SCREEN AT OPENING.DUCTWORK AND ACCESSORIES SHALL BE 316STAINLESS STEEL.
PROVIDE 12x8 ACCESS DOOR IN SIDE OF DUCT.
SHEET KEYNOTES
March 18, 2021