C044 Fire Tutorial WP Aug 05

Embed Size (px)

Citation preview

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    1/26

     

    1

    Subject: A Tutorial on Cable Fire Safety (Updated)

    From: Dr. T. C. Tan, DMTS, SYSTIMAX Labs

    B.Sc (Eng), DIC, PhD, CEng, FIEE

    Date: 9th

     March 2005

    Modified: 12th

     August 2005

    1. Introduction

    The proliferation of local area networks (LANs) and the increasing use of structured cabling

    systems in many commercial office buildings have resulted in heavy concentration of

    communication cables in ceiling and/or under-floor voids. Some of these cables have low or

    unknown fire performance since there are no requirements in Europe and Asia currently for

    marking these cables according to their fire performance. This is in contrast to the situation in North

    America and Mexico where all communication cables must meet one of four levels of fire-

    resistance requirement and bear the necessary markings. This hierarchy of cable fire requirement is

    mapped to the different installation practices. These cable markings are useful for the fire or health

    and safety inspectors and insurance surveyors because they facilitate the identification of the cable

    safety performance level and are valuable from a building inspection and risk assessment

    standpoint.

    Also, fire codes or regulations vary widely across the world. In North America, fire codes exist for

    communication cables and a large emphasis is placed on the reduction in flame spread, fire

     propagation and smoke generation. In Europe and Asia, fire codes/regulations do not exist for

    communication cables (Regulations do exist for other construction products such as wall panels,

    ceiling tiles and floor coverings). However, in some European countries, some customers do place

    more emphasis on the reduction of smoke and acid gases generation due to the existence of low

    smoke, zero halogen (LSZH) European cable standards. These standards have now been revised to

     be more generic to allow other materials to be used. This paper compares the current requirements

    in North America and internationally, and discusses new developments in Europe which could lead

    to the setting up of a hierarchy of communication cable fire performance levels that will be basedon installation practices and risk assessment. A list of the abbreviations used is given in Annex A.

    2. Standards 

    When considering the fire performance of communication cables, several criteria must be taken into

    account. These are:

    • Fire Resistance (sometimes referred to as Circuit Integrity Test)

    • Flame Spread and Fire Retardance

    • Heat Release Rate and Total Heat Release

    • Smoke Generation• Toxicity

    • Smoke Corrosivity

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    2/26

     

    2

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    Annex B provides photographs of some of the fire test methods.

    2.1 Fire Resistance

    The fire resistance or circuit integrity requirement is a special one and is required for connection to

    certain fire-life-safety control systems such as sounders/bells/sirens, combined speaker-strobe

    devices, fire-fighter phones, control and indicating equipment. The test requires cables to maintain

    circuit integrity under specific fire conditions (for example, flame test at 1000 °C for 3 hours and

    still maintaining circuit integrity). The main related standards are:

    • IEC 60331

    • EN 50200

    This requirement needs the use of cables with special construction. Typical communication cables

    cannot be used.

    2.2 Flame Spread and Fire Retardance

    The aim of choosing a communication cable with low flame spread and high fire retardance is to

     prevent the burning cables from propagating the fire to other parts of the building too quickly. This

    will allow more time for the people involved to make their escape from the fire. The main related

    standards are:

    • UL VW-1 Bunsen Burner

    • UL 1581 Vertical Tray or IEEE-383 Vertical Tray

    • CSA FT-4/IEEE-1202

    • UL 1666

    • UL 910 or NFPA 262 or CSA FT-6

    • EN 50289-4-11

    • IEC 60332-1 series or EN 50265 series

    • IEC 60332-3 series or EN 50266 series

    • FIPEC Scenario 1 and Scenario 2

    These standards require the whole finished cable(s) to be tested. Figure 1 and Table 1 provide the

    requirements in the United States (US). These requirements are set in the National Electrical Code

    (NEC) Articles 770 and 800 which are issued by the National Fire Protection Association (NFPA).

     NEC Article 800 has four levels of fire-resistance requirement. All communication cables must

    meet one of the four levels and bear the necessary markings. As an example, a cable that is rated

    CM/MP cannot be installed in the riser environment unless the cables are enclosed in metallic/non-

    combustible trunking. This will ensure that the fire does not propagate too quickly to the otherfloors even when the fire-stopping mechanism has been compromised. The NEC is revised every

    three years.

    The UL VW-1 is a small-scale test whereas the UL 1581, UL 1666 and UL 910 are all intermediate-

    scale tests. The Canadian Standards Association (CSA) FT-4 test is slightly more stringent than the

    UL 1581 due to the fact that the ignition source is angled at 20°. The UL/CSA designation for

    meeting this test is CMG/MPG.

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    3/26

     

    3

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    Fire Tests Cable rating identification

    VW-1

    Bunsen Burner

    UL 1581

    Vertical Tray

    UL 1666

    Riser Test

    UL 910

    Steiner Tunnel

    (NFPA 262)

    Low

    High

                                                                                                                                                                                 F                                                                                                                                                                                 i                                                                                                                        r                                                                                                                        e                                                                                                                                                                                P

                                                                                                                            e                                                                                                                           r                                                                                                                                                                                f                                                                                                                         o   

                                                                                                                            r                                                                                                                        m

                                                                                                                            a                                                                                                                             n                                                                                                                        c                                                                                                                            e   

    CMP/OFNP/OFCP

    CMX

    CM/OFN/OFC

    CMR/OFNR/OFCR

     

    Figure 1: US cable fire tests, hierarchy and identifications

    DESIGNATION TEST REQUIRED USE

    CMX UL VW-1 Residential

    CM/MP/OFC/OFN UL 1581 Vertical Tray

    IEEE-383 Vertical Tray

    General Purpose Except

    for Riser and Plenum

    CMR/MPR/OFCR/OFNR UL 1666 General Purpose and Riser

    CMP/MPP/OFCP/OFNP UL 910/NFPA 262 General Purpose, Riser

    and Plenum

     Note: Prefix C or M is for copper media and prefix OF is for optical fiber media.

    Table 1: US NEC Article 800 for communication cables

    EN 50289-4-11 is based on the UL 910 test method but with heat release and time-to-ignition

    measurements as mandatory requirements rather than optional and an additional test for flaming

    droplets. It is an intermediate-scale test. Note that both UL 910 and EN 50289-4-11 are test methods

    and do not have pass/fail requirements.

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    4/26

     

    4

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    Currently, IEC 60332-1 and 60332-3 series of standards1 are widely used internationally as cable

    fire test methods. These tests were originally developed for power/energy cables and have since

     being revised to cater for communication cables. The IEC 60332-1 is a small-scale test using a 1

    kW burner as the ignition source and a single cable or wire as test sample. It is similar to the UL

    VW-1 test.

    The IEC 60332-3 is an intermediate-scale test where bundles of cables are used (IEC 60332-3-10

     provides description for the test apparatus). This series of standards have five categories, namely:

    • Category A F/R NMV 7 litres per meter IEC 60332-3-21

    • Category A NMV 7 litres per meter IEC 60332-3-22

    • Category B NMV 3.5 litres per meter IEC 60332-3-23

    • Category C NMV 1.5 litres per meter IEC 60332-3-24

    • Category D NMV 0.5 litres per meter IEC 60332-3-25

     NMV stands for non-metallic volume. The number of cable samples required is calculated from the

     NMV for the different categories. Annex C provides comparison between IEC 60332-3, UL 1581

    Vertical Tray and UL 1666 test methods.

    EN 50265 and EN 50266 series of European Norms (standards) are basically the European version

    of IEC 60332-1 and IEC 60332-3 series of standards.

    FIPEC (Fire Performance of Electric Cables)  was a European Commission and industry funded

     project set up to develop methods for measuring the fire performance of cables. The test apparatus

    consisted of modifying the existing IEC 60332-3 test to include heat release and smoke

    measurement. The FIPEC project found that the most significant variable in the current IEC 60332-

    3 test was in cable mounting, and concluded that consideration of NMV does not necessarily

     provide a risk hierarchy. Changes to sample mounting, the option of a backboard with a more

     powerful ignition source and an increased airflow provide a better discrimination between cable fire performances for FIPEC test methods when compared with current IEC 60332-3 tests.

    FIPEC has two test methods, namely test method Scenario 1 and Scenario 2. Cable mounting

     procedure is determined by cable diameter. Cables having a diameter greater than 5 mm were

    mounted in a single spaced row, and smaller cables were mounted in non-twisted spaced bundles.

    Test method Scenario 1 is considered to be slightly more severe than IEC 60332-3. The ignition

    source is 20 kW and the airflow is increased to 8000 litre per minute. In test method Scenario 2,

    considered to be more severe than IEC 60332-3, the ignition source is 30 kW, the airflow is 8000

    litre per minute and a non-combustible backboard is added. The FIPEC test methods have been

    adopted for the Reaction-to-Fire Euroclassification of cables under the Construction Product

    Directive, 89/106/EEC (see Section 3.1).

    1 A few years ago, IEC revamped their fire standard documents by splitting them up into a series of documents. For

    example, the former IEC 60332-3 document consists of test apparatus description and all the test procedures andrequirements for different categories. This is now split into a series of IEC 60332-3-x documents, consisting of adocument for test apparatus description and various documents for the different categories of fire test procedure and

    requirements. This process will permit amendments and new requirements to be introduced easily.

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    5/26

     

    5

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    The UL 910, EN 50289-4-11 and FIPEC Scenario 1 and Scenario 2 are sometimes referred to as

    integrated fire tests since they measured essential fire hazard properties such as flame spread,

    smoke generation and heat release, all in the same respective tests. This is far more useful and

    realistic. The other test methods just measure only one variable, flame spread.

    Table 2 provides a comparison between IEC 60332-1, IEC 60332-3, FIPEC Scenario 1 and

    Scenario 2, UL 910 and EN 50289-4-11 test methods.

    2.3 Heat Release Rate (HRR) and Total Heat Release (THR)

    Heat is the energy output of a fire. When the aftermath of a disastrous fire is being investigated, one

    of the most common questions is: Why did the fire get so large? HRR and THR (THR is calculated

     by working out the area under the HRR curve) are useful variables for quantifying a fire size and

    are important variables in describing fire hazard (except for explosions). This is because:

    • HRR and THR are driving forces for fire, that is, heat makes more heat, which in turn

    increases the temperature of the fire. This does not occur, for instance, with carbon

    monoxide. Carbon monoxide does not make more carbon monoxide.• The generation of most other undesirable fire by-products such as smoke, toxic gases and

    temperatures, generally tends to increase with increasing HRR and THR.

    • High HRR/THR indicates high threat to life and are intrinsically dangerous. This is because

    high HRR/THR cause high temperatures and high heat flux conditions, which may prove

    lethal to occupants.

    The main related standards are:

    • EN 50289-4-11

    • FIPEC Scenarios 1 & 2

    HRR and THR are optional requirements in UL 910.

    Small-scale test methods do exist for measuring HRR and THR (e.g Cone calorimeter, ASTM

    E1354) but these tests are only useful for initial material assessment work.

    Recent EU-funded British Steel fire tests at the UK Building Research Establishment/Fire Research

    Station (BRE/FRS) indicated that temperatures exceeding 800°C can cause structural steel beams to

    severely deform2 which will render the building unsafe after the fire.

    2.4 Smoke Generation 

    Some fire fatalities are caused by the failure of people involved to make their escape from the fire in

    the time available. There are many reasons for this, but one that has attracted increasing attention is

    the effect of smoke. Dense smoke reduces visibility and causes suffocation. The aim of choosing a

    cable with low smoke generation is to allow people to escape a building fire with minimum

    suffocation and not having their visibility impaired. The main related standards are:

    2  B. R. Kirby, ‘British Steel Technical European Fire Test Programme’, Fire, Static and Dynamic Tests of Building

    Structures; G. Armer & T. O’Dell (1997), pgs 111-126, Conference Proceedings.

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    6/26

     

    IEC 60332-1

    (EN 50265 series)

    IEC 60332-3

    (EN 50266 series)

    FIPEC

    Scenarios 1 & 2

    UL 910

    Cable orientation Vertical Vertical Vertical Horizontal

    Test requirements Flame spread Flame spread,

    Oxygen index (optional)

    Flame spread,

    Heat release,

    Smoke opacity,

    Time-to-ignition

    Flame spread,

    Smoke opacity,

    Heat release (option

    Time-to-ignition (opti

    Ignition source 1 kW Burner 20.5 kW Burner

    (73.8 MJ/hr)

    (70,000 BTU/hr)

    Scenario 1: 20 kW Burner

    Scenario 2: 30 kW Burner plus

    non-combustible backboard

    (108 MJ/hr)

    (102, 364 BTU/hr)

    87.8 kW Burner

    (316.5 MJ/hr)

    (300,000 BTU/hr

    Flame application

    time

    60 s

    for cable diameter 25 mm

    2400 s for Categories A & B

    1200 s for Categories C & D

    1200 s 1200 s

    Length of test

    sample

    0.6 m (2 ft) 3.5 m (11.5 ft) 3.5 m (11.5 ft) 7.6 m (25 ft)

    Cable layers

    and spacing

    Not applicable.

    Single cable

    Number of layers depends on

    NMV.

    Touching for cable diameter6.7 mm

    Single layer spaced Single layer touchi

    Air velocity None 5000 litre/min 8000 litre/min 1.22 m/s

    (240 ft/min)

    Pass/Fail Criteria Distance between onset of

    charring and lower edge of

    top support > 50 mm and

    burning < 540 mm from lower

    edge of top support

    Charred portion < 2.5 m

    (8.2 ft) above bottom edge of

    burner (Flame extinguish

    after 1 hr).

    Depends on

    CPD Euroclassification

    Refer to CMP/MPP/O

     /OFCP requiremen

    Flame front < 1.52 m (5 f

    Peak Optical Density 0

    Average Optical Density

    Standardisation International and CENELEC International and CENELEC EU CPD

    and CENELEC

    UL, CSA and Mexi

    Table 2: Comparison between various fire test methods

    6

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    7/26

     

    7

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    • UL 1685

    • UL 910

    • EN 50289-4-11

    • EN 13823 (SBI)

    • IEC 61034 or EN 50268

    All these standards require the whole finished cable(s) to be tested.

    UL 1685 uses the UL 1581 test method but with peak smoke release rate and total smoke

    requirements added. The UL designation for meeting this test is ‘LS’ (Limited Smoke), i.e. CM-LS.

    In the US, it is a mandatory requirement in the plenum environment to install low smoke and very

    fire retardant cables. These cables must meet the CMP/MPP/OFNP/OFCP requirements with the

    UL 910 test. There is also another test method in the US known as the NBS smoke chamber and

    this is referenced in the ASTM E662 standard. The only drawback with this standard is that the test

    is carried out on the polymeric material used (i.e. cable sheath and conductor insulation materials

    are tested separately) rather than the whole finished cable(s).

    IEC 61034 or EN 50268 is sometimes referred to as the 3-meter cube test due to the size of the test

    chamber used. Part 1 provides details of the test apparatus and Part 2 defines the test procedure and

     pass/fail requirements. This test was originally developed for power/energy cables and was intended

    to simulate a cable fire in an underground train tunnel. One problem with this test method when

    applied to communication cables relates to the calculation of the number of test samples required.

    This (sample) number is dependent on the overall diameter of the cable. For a cable with an overall

    diameter of 4.8 mm (typical diameter of plenum-rated communication cables), the number of test

    samples required is 21 whereas for a cable with an overall diameter of 5.1 mm (typical diameter of

    IEC 60332-1 rated LSZH communication cables), the number of test samples required is 8. This

    massive difference in cable test samples provides massively different test results. In practice, this

    difference does not exist since the number of communication cables installed in a 9 m2 work area isthe same irrespective of the cable diameter.

    The UL 910, EN 50289-4-11 and FIPEC Scenarios 1 & 2 tests are more useful and realistic since

    they are integrated fire tests. IEC 61034 or EN 50268 only measures smoke emission.

    2.5 Toxicity

    Toxicity is also a complex subject. The toxicity issue has typically being perceived to be related to

    all halogenated cables. However, it is a known fact that all burning cables (both halogenated and

    non-halogenated) produce toxic gases. According to fire fighters and fire experts, the most common

    cause of fire fatality is due to the inhalation of carbon monoxide (CO) gas which is toxic and

    odourless. Cable fire research work 3 at the UK BRE/FRS showed that some commonly used LSZH

    data cables produce more CO gas than the CMP-rated cables when burned (see Figure 2). This work

    is co-funded by the UK Government. This is likely due to the tendency that LSZH data cables burn

    more rapidly and quickly reduce the oxygen available in the concealed space.

    3 ‘A study of Cable Insulation Fires in Hidden Voids’ - A Partners in Technology (PIT) programme for the UK

    Department of Transport, Environment and the Regions (DETR) contract reference CI 38/19/131 (cc985), March 1996.

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    8/26

     

    8

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    The US National Electrical Manufacturers Association (NEMA) has also developed toxicity data

    using the NEMA/NYS (New York State) protocol4 (see Figure 3). The data indicates that there is no

    significant difference in toxicity (LC50  values) between fluoropolymer, PVC and polyolefin (i.e.

     polyethylene and polypropylene) materials.

    Traditional material-based toxicity test methods such as the Naval Engineering Standard (NES) 713

    have been found to be unsuitable. These test methods are not realistic and are only useful for initial

    material assessment work. Toxic hazards must be assessed over a range of fire scenarios and not on

    material-based test methods only. Toxicity information should be used as part of a relevant total fire

    hazard assessment where parameters such as ignitability, fuel load, heat release, flame spread and

    smoke emission are also considered.

    Carbon Monox ide (CO) Generat ion

    -0.050

    0.000

    0.050

    0.100

    0.150

    0.200

    0.250

    0.300

    0.350

    0 500 1000 1500 2000 2500 3000 3500

    Tim e (sec)

       C  o  n  c  e  n   t  r  a   t   i  o  n   (   %   )

    LSZH

    CM P

     

    Figure 2: CO emission from CMP-rated and IEC 60332-1 rated LSZH cables

    4 National Electrical Manufacturers Association, 1987, ‘Registration Categories of the National Electrical

    Manufacturers Association for Compliance with the New York State Uniform Fire Prevention and Building Code’, R.

    Anderson, P. Kopf, pub Arthur D. Little Inc.

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    9/26

     

    9

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    Figure 3: NEMA toxicity data

    2.6 Acidity and Smoke Corrosivity

    In addition to smoke, gases are also evolved from materials involved in a fire. Depending on the

    compounds used for manufacturing the cables, some of these gases may be acidic in nature. For

    example, cables insulated and/or sheathed with PVC can generate hydrochloric acid gas when

    affected by fire. In addition, most LSZH compounds are made from ethylene-vinyl-acetate (EVA -

    this compound is a polyethylene copolymer) which generate acetic acid when affected by fire.

    There are concerns that these acidic gases may cause damage to modern electronic equipment and

     building structure. This has led to the perception that acidic gas is related to corrosivity.

    The two commonly quoted standards for testing acidic gas generation are:

    • IEC 60754-1 (EN 50267-2-1): HCL gas generation• IEC 60754-2 (EN 50267-2-2 & EN 50267-2-3): pH and Conductivity

    Both test methods call for polymeric material testing rather than testing on the whole finished

    cable(s). This means that both the cable outer sheath and the conductor insulation need to be tested.

    In the IEC 60754-2 standard, the pass/fail limit for pH is set at > 4.3 even though the pH for pure

    water (neutral) is 7. The limit of 4.3 basically ensures that most halogenated compounds will not

    meet this standard. Hence, this has resulted in the perception that corrositivity is related to

    halogenated cables only.

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    10/26

     

    10

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    Other test methods exist for measuring corrositivity in terms of metal loss. Two of these methods

    are ASTM D5485 (Cone corrosimeter) and ISO DIS 11907 but these are not commonly used.

    The perception that corrositivity is related to halogenated cables only is now being challenged.

    Several decades of research work carried out by Lucent Technologies Bell Laboratories have shown

    that modern digital equipment are particularly vulnerable to airborne particles, most of which are

     potentially corrosive ionic compounds. This work has recently been extended to include the

     possible causes of equipment failure from smoke exposure in cable fires. This is because in a fire,

    ionic contaminants associated with fillers, flame retardants, colorants or by-products of the

     polymerisation reactions may be released and deposited on circuit boards. The research showed that

    the most common cause of equipment failures following exposure to smoke from cable combustion

    is not loss in thickness of structural metals or metal circuitry from direct deposition of acidic gases

     but rather electrical shorts and arcing that cause excessive crosstalk and malfunctioning

    components. This phenomenon is known as the ‘Leakage Current Effect’. The research also showed

    that smoke contaminants from some burning LSZH data cables are as damaging as those from some

    halogenated ones5,6. This work on digital electronic equipment reliability (DEER) indicated that

    there are damage mechanisms to electronic equipment associated with fires that cannot beadequately assessed by determining the pH or conductivity or by metal loss. Hence, current

    international test methods such as IEC 60754 are not adequate for assessing DEER.

    In addition, some plenum communication cables do not have problem with DEER. This is due to

    the fact that there is virtually no propagation of fire along the length of the cable. Hence, the amount

    of compound burnt will be limited and this will result in less ionic contaminants being generated.

    In summary, acidity is not relatable to corrosivity. Further, there is no mention of corrosivity in IEC

    60754-2. Phenomenon such as leakage current and metal loss are more accurate measures of

    corrosion damage effects of fire effluents. The test methods for measuring leakage current and

    metal loss are given in IEC 60695-5-37

    . In the US, the test method for leakage current is UL Subject1985.

    3. New Developments on Communication Cable Fire Hazard

     New developments are occurring in the industry and in the regulatory environment with regard to

    cable fire hazard and risk assessment/management. These developments include the publication of a

    Design Guide8  by BRE-Loss Prevention Council (LPC), the publication of a Technical Briefing

    Report9  by the Association of British Insurers (ABI), the inclusion of cables in the European

    Construction Product Directive (CPD) and the identification of a new cable fire performance level

    known as limited combustible by the National Fire Protection Research Foundation (NFPRF) and

    UL in the US. 

    5 IWCS, Leakage Current Smoke Corrosivity Testing - Comparison of Cable and Material Data,J. T. Chapin, et al, 1996.6 NFPRF Fire Risk and Hazard Research Assessment Research Application Symposium, ‘Comparison of

    Communications LAN Cable Smoke Corrosivity by US and IEC Test Methods’, J. T. Chapin, et al, June 1997.7 IEC 60695-5-3: ‘Fire Hazard Testing – Part 5-3: Corrosion damage effects of fire effluent – Leakage current and metal

    loss test method’8 ‘The LPC Design Guide for the Fire Protection of Buildings’, Loss Prevention Council, June 1997 & Sept 1998.ISBN 0 902167 97-99 ‘Fire Hazard of Communication Cables in Ceiling, Floor and Vertical Voids’, Association of British Insurers, Nov

    2000. ISBN 1 903193 11 7

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    11/26

     

    11

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    3.1 European Construction Product Directive (CPD), 89/106/EEC

    The CPD was enacted in 1989 and applies to all construction products. One of the essential

    requirements of the CPD (Essential Requirement No. 2) relates to safety in the case of a fire. A new

    testing and classification scheme was agreed by the EC Fire Regulators Group (FRG) for the

    implementation of the CPD and in particular, relating to the harmonisation of Reaction-to-Fire

    testing of construction products. The FRG is a group of national fire regulators and their technical

    advisers/experts.

    The classification scheme comprises a table of ‘Euroclasses’ from Class A1 (highest performance)

    to Class F (no performance determined) and a range of tests and performance criteria for

    determining a Reaction-to-Fire classification for construction products, excluding flooring. To

    cover all but the highest and lowest classifications, EN 13823 SBI (Single Burning Item) test was

    developed.

    In December 1998, communication cables were accepted as construction products within the EC,

    and are, therefore subjected to the requirements for Reaction-to-Fire testing and Euroclassification.The FIPEC test methods have been adopted and Annex D provides the proposed EuroClasses for

    cables in the CPD. There are seven EuroClasses and enhanced fire performance (i.e. plenum rated)

    cables are in EuroClass B1ca. The parameters listed under main classifications are mandatory

    requirements whereas those listed under additional classifications are optional. Many member states

    are unlikely to adopt the optional acidity requirement since it is not in the CPD for all the other

    construction products. Once approved, mandatory cable fire performance marking will be required

     by the Directive, and for the first time in Europe, a ‘hierarchy’ of cable fire requirements exist.

    These cable markings are useful for the fire or health and safety inspectors and insurance surveyors

     because they facilitate the identification of the cable safety performance level and enhanced fire risk

    assessment.

    3.2 The LPC Design Guide for the Fire Protection of Buildings

    This BRE/LPC publication allows architects and building designers to take into account insurers’

    recommendations for the fire protection of buildings. These relate mainly to the protection of

     business by minimising fire and smoke damage and business interruption. The overall objective of

    the Design Guide is to assist in reducing financial loss by providing guidelines to contain the fire to

    one compartment of the building, and ensuring that when combustible materials such as cables are

    used in the construction of a building, they do not make significant contribution to the growth and

     propagation of the fire. Building regulations are concerned primarily with the escape of the building

    occupants, that is, they only address life safety issues and will not necessarily result in the provision

    of adequate property protection. The BRE/LPC Design Guide aims to complement the statutory building regulations and provides additional requirements set by the insurers. The increased

    standards required by the insurers are designed not only to provide safety for the people involved in

    the fire, but also to protect the asset of the business and to minimise the cost of fire damage to

     buildings and their contents.

    Section 4.7.2 of the Design Guide deals with cables installed in ceiling and under-floor voids and

    recommends that the cables should be ‘tested and approved to IEC 60332-3 or other specification

    acceptable to LPC’.  Section 4.7.3 deals with cables installed in communication rooms and

    recommends that ‘where cables are installed in a cavity of 300 mm or greater, then the cables used

    should be tested and approved to UL 910 or other specification acceptable to LPC and the platform

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    12/26

     

    12

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

     floor should have fire resistance of 15 min integrity and insulation when exposed to the heating

    conditions of BS 476, Part 20 (1987)’. Cables not meeting these requirements must either be sealed

    in fire retardant trunking/ducting, or the cavity where the cables are installed is protected by an

    automatic gaseous system (connected to a fire detector and alarm system) or a sprinkler system.

    The LPC Design Guide has taken a major step in setting the minimum cable fire performance

    requirements for the cabling industry. It presents the insurers’ standards for fire protection of

     buildings and is intended to assist architects and other building professional advisers in reconciling

    the provisions of national legislation standards with the recommendations of the insurance industry.

    3.3 The Association of British Insurers (ABI) Technical Briefing Report on ‘Fire Hazard

    of Communication Cables in Ceiling, Floor and Vertical Voids’

    Recently, the ABI published a Technical Briefing Report for insurers that provided further guidance

    to the insurance industry in establishing their strategy. This technical report complements the LPC

    Design Guide and is based on the cable fire safety research work carried out by SYSTIMAX

    Solutions, other cable manufacturers and polymer suppliers, and in collaboration with BRE/LPC,

    UL and the UK DETR. This report concludes with the following recommendations:• For new buildings or during major refurbishment’s, the recommendations given in part 4.7

    of the LPC Design Guide for the Fire Protection of Buildings should be followed.

    • As construction products, communication cables are included in the new developments in

    the EC Fire Regulators’ group for the harmonisation of Reaction to Fire Testing within

    Europe as required by the CPD, this will result in new requirements for testing and

    classification of cables for life safety. It is important for insurers to promote higher

    requirements than regulators, to reduce the potential business interruption exposure.

    3.4 NFPA 90A Limited Combustible Requirements

    Last year, the NFPRF and UL in the US identified a new cable fire performance level known aslimited combustible. According to NFPA Article 90A, for a product exposed to airflow in plenum

    to be classified as limited combustible, the fuel load of the product must be ≤ 8.14 MJ/kg (3500

    BTU/lb), have a flame spread index (FSI) of 25 and a maximum smoke developed index (SDI) of

    50. These numbers must be generated in accordance with procedures set forth in NFPA 259 (for

    fuel load) and NFPA 255 (for FSI and SDI). The requirements for limited combustible cables

    exceed those of CMP/MPP/OFNP/OFCP (using UL 910/NFPA 262 test). Table 3 provides a

    comparison between NFPA 255 and NFPA 262, and Table 4 provides a comparison between

    limited combustible and CMP/MPP/OFNP/OFCP rated cables.

    NFPA 255 NFPA 262

    Apparatus Steiner Tunnel Steiner Tunnel

    Test duration 10 mins 20 mins

    Position of steel rack 0.298 m (11.75 in) above

    chamber floor

    0.203 m (8 in) above

    chamber floor

    Width of steel rack 0.514 m (20.25 in)

    (80% more cable

    specimen)

    0.286 m (11.250 in)

    Table 3: Comparison between NFPA 255 and NFPA 262

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    13/26

     

    13

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    Limited Combustible

    Rating

    CMP/MPP/OFNP/OFCP

    Rating

    Test NFPA 255 UL 910/NFPA 262

    Flame spread Flame spread index of 25 1.524 m (5 ft)

    Smoke generation 50 smoke developed

    index

    Up to 10 times less severe

    than Limited CombustibleRating 

    Temperature rating Required Not required

    Heat aging Required Not required

    Humidity aging Required Not required

    Slitting Required Not required

    Fuel load limit 8.14 MJ/kg per NFPA

    259 test

    Not required

    Table 4: Comparison between Limited Combustible and CMP/MPP/OFNP/OFCP rating

    4. Conclusion 

    All these developments are major steps in setting the minimum or enhancing the cable fire

     performance requirement for the structured cabling industry. A hierarchy of fire performance levels

    mapped to the installation practices plus mandatory cable fire performance markings will definitely

    enhance risk assessment and provide an additional tool to effective risk management. The key

    message is that ‘the right cable should be installed in the right environment’ so as to reduce risk to

    fire hazard.

    SYSTIMAX®  SCS has a range of communication cables that are suitable for premise cabling.

    Tables 5 to 8 provide a summary of the fire performance properties and rating of copper cables.

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    14/26

     

    14

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    SYSTIMAX PowerSum Cable TypesProperties

    1061C-004  1061C-025  2061B-004 3051A-004 3061A-004 4061A-004

    Jacket PVC PVC LSPVC LSZH LSZH FEP

    Insulation HDPE HDPE FEP HDPE HDPE FEP

    −  −  −  −  −  − Fire Resistance

    IEC 60331  N N N N N N−  +  + +  − −  −  + + + 

    Y Y Y NT NT Y

     N

    (Y: 1061B)

    Y Y N N Y

     N N Y N N Y

     N N N N N Y

    Y Y Y Y Y Y

    Flame Spread/Fire Retardance

    CMCMR

    CMP

    Limited Comb.IEC 60332-1

    IEC 60332-3a

    Y NT Y N Y Y

    Heat ReleaseRate/Total Heat

    Release−  −  +  −  −  + + 

    − −  − −  +  +  +  + + 

     N N Y N N Y

    SmokeCMP

    IEC 61034  N N NT Y Y NT

    Toxicity −  −  −  −  −  − 

    − −  − −  −  +  +  − Acid GasIEC 60754-2  N N N Y Y N

    SmokeCorrosivityIEC 60695-5-3:

    Leakage current

    − −  − −  +  −  −  + + 

     Notes:

     N Non-compliance NT Not Tested

    a Cables that are tested to meet IEC 60332-3 are tested to meet Category A.

    Table 5: Summary of SYSTIMAX PowerSum cable fire performance properties and rating

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    15/26

     

    15

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    SYSTIMAX GigaSPEED XL Cable TypesProperties

    1071E-

    004 2071E-

    004

    3071E-

    004

    3071E3-

    004

    1081A-

    004

    2081A-

    004

    3081A-

    004

    Jacket PVC LSPVC LSZH LSZH PVC LSPVC LSZH

    Insulation HDPE FEP HDPE HDPE HDPE FEP HDPE

    −  −  −  −  −  −  − Fire ResistanceIEC 60331  N N N N N N N

    −  + +  − −  −  −  + +  − 

    Y Y NT NT Y Y NT

    Y Y N N Y Y N

     N Y N N N Y N

     N N N N N N N

    Y Y Y Y Y Y Y

    Flame Spread/

    Fire RetardanceCMCMRCMP

    Limited Comb.IEC 60332-1

    IEC 60332-3 a  NT Y N Y NT Y YHeat ReleaseRate/Total Heat

    Release−  +  −  −  −  +  − 

    − −  +  +  +  − −  +  + 

     N Y N N N Y N

    SmokeCMP

    IEC 61034  N NT Y Y N NT Y

    Toxicity −  −  −  −  −  −  − 

    −  −  +  +  −  −  + Acid GasIEC 60754-2  N N Y Y N N Y

    SmokeCorrosivityIEC 60695-5-3:

    Leakage current

    − −  +  −  −  − −  +  − 

     Note:

     N Non-compliance NT Not Tested

    a Cables that are tested to meet IEC 60332-3 are tested to meet Category A.

    Table 6: Summary of SYSTIMAX GigaSPEED XL cable fire performance properties and

    rating

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    16/26

     

    16

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    SYSTIMAX GigaSPEED X10D Cable TypesProperties

    1091A-004  2091A-004  3091A-004 

    Jacket PVC LSPVC LSZH

    Insulation HDPE FEP HDPE

    −  −  − Fire Resistance

    IEC 60331  N N N−  +  − 

    Y Y NT

    Y Y N

     N Y N

     N N N

    Y Y Y

    Flame Spread/Fire Retardance

    CMCMRCMPLimited Comb.

    IEC 60332-1

    IEC 60332-3 a

     NT Y Y

    Heat ReleaseRate/Total HeatRelease

    −  +  − 

     −

     +

     +

      N Y N

    SmokeCMPIEC 61034  N NT Y

    Toxicity −  −  − 

    −  −  + Acid GasIEC 60754-2  N N Y

    Smoke Corrosivity

    IEC 60695-5-3:Leakage current

    − −  +  − 

     Note: N Non-compliance

     NT Not Testeda Cables that are tested to meet IEC 60332-3 are tested to meet Category A.

    Table 7: Summary of SYSTIMAX GigaSPEED X10D cable fire performance properties and

    rating

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    17/26

     

    17

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    SYSTIMAX Category 3 Cable TypesProperties

    1010A-xxx  2010B-xxx  3010-xxx 

    Jacket PVC LSPVC LSZH

    Insulation PVC PVC HDPE

    −  −  − Fire Resistance

    IEC 60331  N N N−  +  − 

    Y Y NT

    Y Y N

     N Y N

     N N N

    Y Y Y

    Flame Spread/Fire Retardance

    CMCMRCMPLimited Comb.

    IEC 60332-1

    IEC 60332-3 a

    Y Y N

    Heat ReleaseRate/Total HeatRelease

    −  +  − 

     −

     +

     +

      N Y N

    SmokeCMPIEC 61034  N NT Y

    Toxicity −  −  − 

    −  −  + Acid GasIEC 60754-2  N N Y

    Smoke Corrosivity

    IEC 60695-5-3:Leakage current

    − −  +  − 

     Note: N Non-compliance

     NT Not Testeda Cables that are tested to meet IEC 60332-3 are tested to meet Category A.

    Table 8: Summary of SYSTIMAX Category 3 cable fire performance properties and rating

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    18/26

     

    18

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    Annex A

    ABBREVIATIONS 

    ABI: Association of British Insurers

    ASTM: American Society for Testing and Materials

    BRE/FRS: Building Research Establishment/Fire Research Station

    CEN: European Committee for Standardization

    CENELEC: European Committee for Electrotechnical Standardization

    CPD: Construction Product Directive

    CSA: Canadian Standards Association

    DEER: Digital Electronic Equipment Reliability

    DETR (UK): Department of Transport and the Regions (UK)

    EVA: Ethylene-Vinyl-Acetate

    FSI: Flame Spread Index

    FRG: Fire Regulators GroupHCL: HydroChLoric

    IEC: International Electrotechnical Committee

    IWCS: International Wire and Cable Symposium

    LPC: Loss Prevention Council

    LSZH: Low Smoke Zero Halogen

     NBS: National Board of Standards

     NEC: National Electrical Code

     NEMA: National Electrical Manufacturers Association

     NES: Naval Engineering Standard (UK)

     NFPA: National Fire Protection Association

     NFPRF: National Fire Protection Research Foundation NMV: Non-Metallic Volume

    PVC: PolyVinyl Chloride

    SBI: Single Burning Item

    SDI: Smoke Developed Index

    UL: Underwriters Laboratories

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    19/26

     

    19

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    Annex B

    Figure B.1: IEC 60331 Test

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    20/26

     

    20

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    Figure B.2: IEC 60332-3 Test

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    21/26

     

    21

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    Figure B.3: EN 13823 (SBI) Test

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    22/26

     

    22

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    Figure B.4: UL 910/EN 50289-4-11 Test

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    23/26

     

    23

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    Figure B.5: IEC 61034 (EN 50268) Test

    {Often referred to as the 3 metre cube smoke test}

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    24/26

     

    24

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    Figure B.6: IEC 60754-2 Test

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    25/26

     

    25

    CommScope Solutions Proprietary

    Use pursuant to Company instructions

    Annex C

    IEC 60332-3 Category A, B  UL 1666 

    Length of test sample 3.5 m (11.5 ft) 3.7 m (12 ft)

    Cable orientation Vertical Vertical

    Cable layers and

    spacing

     Number of layers depends on NMV.

    Touching for cable diameter ≤ 6.7 mm

    Single layer touching

    Ignition source 73.8 MJ/hr

    (20.5 kW or 70,000 BTU/hr)

    556 MJ/hr

    (154.4 kW or 527,000 BTU/hr)

    Flame application time 40 mins 30 mins

    Air velocity 5000 litre/min

    (0.083 m3/s)

    3.5 m/s

    Low smoke requirement None None

    Pass/Fail criteria Charred portion < 2.5 m (8.2 ft) above

     bottom edge of burner (Flame extinguish

    after 1 hr).

    Cables cannot propagate flame

    to 3.7 m (12 ft) and maximum

    temperature is not to exceed

    454.4 °C.

    Table C.1: Comparison between IEC 60332-3 Category A, B and UL 1666 (CMR/OFNR

    rating)

    IEC 60332-3 Category C, D  UL 1581 Vertical Tray 

    Length of test

    sample

    3.5 m (11.5 ft) 2.4 m (8 ft)

    Cable orientation Vertical Vertical

    Cable layers and

    spacing

     Number of layers depends on NMV.

    Touching for cable diameter ≤ 6.7 mm

    Single layer.

    1

    2 cable diameter spacing

    Ignition source 73.8 MJ/hr

    (20.5 kW or 70,000 BTU/hr)

    73.8 MJ/hr

    (20.5 kW or 70,000 BTU/hr)

    Flame application

    time

    20 mins 20 mins

    Air velocity 5000 litre/min

    (0.083 m3/s)

    5 m/s

    (0.65 m3/s)

    Low smoke

    requirement

     None None

    Pass/Fail criteria Charred portion < 2.5 m (8.2 ft) above

     bottom edge of burner (Flameextinguish after 1 hr).

    Cables damage height is to be less than

    8 ft.

    Table C.2: Comparison between IEC 60332-3 Category C, D and UL 1581 Vertical Tray

    (CM/OFN rating)

     Note: UL 1685 uses the UL 1581 test method but with peak smoke release rate and total smoke

    requirements added.

  • 8/17/2019 C044 Fire Tutorial WP Aug 05

    26/26

     

    26

    Annex D

    Class Test method(s) Classification criteria Additional

    classification

    Aca EN ISO 1716 PCS ≤ 2,0 MJ/kg (1) andPCS ≤ 2,0 MJ/kg (2) and

    FIPEC20 Scen 2 (6)

     And  

    FS ≤ 1.75 m and  

    THR 1200s ≤ 10 MJ and

    Peak HRR ≤  20 kW and  

    FIGRA ≤ 120 Ws-1

    B1ca

    EN 50265-2-1 H ≤ 425 mm

    Smoke production (3, 7) andFlaming droplets/particles

    (4) and Acidity (5)

    FIPEC20 Scen 1 (6)

     And

    FS ≤ 1.5 m; and

    THR 1200s ≤ 15 MJ; and  

    Peak HRR ≤ 30 kW; and

    FIGRA ≤ 150 Ws-1

    B2ca 

    EN 50265-2-1 H ≤ 425 mm

    Smoke production (3, 8) andFlaming droplets/particles

    (4) and Acidity (5)

    FIPEC20 Scen 1 (6)

     And

    FS ≤ 2.0 m; and

    THR 1200s ≤ 30 MJ; and  

    Peak HRR ≤ 60 kW; and

    FIGRA ≤ 300 Ws-1

    Cca

    EN 50265-2-1 H ≤ 425 mm

    Smoke production (3, 8) andFlaming droplets/particles(4) and Acidity (5)

    FIPEC20 Scen 1 (6)

     And  

    THR 1200s ≤ 70 MJ; and

    Peak HRR ≤ 400 kW; and

    FIGRA ≤ 1300 Ws-1

    Dca

    EN 50265-2-1 H ≤ 425 mm

    Smoke production (3, 8) andFlaming droplets/particles(4) and Acidity (5)

    Eca EN 50265-2-1 H ≤ 425 mm

    Fca  No performance determined

    (1) For the product as a whole, excluding metallic materials.

    (2) For any external component (i.e. sheath) of the product.(3) s1 = TSP1200 ≤ 50 m

    2 and  Peak SPR ≤ 0.25 m2/s

    s1a = s1 and transmittance in accordance with EN 50268-2 ≥ 80%s1b = s1 and transmittance in accordance with EN 50268-2 ≥ 60% < 80%

    s2 = TSP1200 ≤ 300 m2 and  Peak SPR ≤ 1.5 m2/s

    s3 = not s1 or s2

    (4) For FIPEC20 Scenarios 1 and 2: d0 = No flaming droplets/particles within 1200 s; d1 = No flaming droplets/ particles persisting longer than 10 s within 1200 s; d2 = not d0 or d1.

    (5) EN 50267-2-3 : a1 = conductivity < 2.5 µS/mm and  pH > 4.3 ; a2 = conductivity < 10 µS/mm and  pH > 4.3;

    a3 = not a1 or a2. No declaration = No Performance Determined.(6) Air flow into chamber shall be set to 8000 ± 800 l/min.

    FIPEC20 Scenario 1 = prEN 50399-2-1 with mounting and fixing according to Annex 2FIPEC20 Scenario 2 = prEN 50399-2-2 with mounting and fixing according to Annex 2

    (7) The smoke class declared for class B1ca cables must originate from the FIPEC20 Scen 2 test.(8) The smoke class declared for class B2ca, Cca, Dca cables must originate from the FIPEC20 Scen 1 test.

    Symbols used: PCS – gross calorific potential; FS – flame spread (damaged length); THR – total heat release; HRR – heat

    release rate; FIGRA – fire growth rate; TSP – total smoke production; SPR – smoke production rate; H – flame spread. 

    Table D.1: Proposed EuroClasses of reaction to fire performance for cables (as in EC

    CONSTRUCT 04/652, April 2004)