Upload
ngonhan
View
234
Download
2
Embed Size (px)
Citation preview
Saudi Aramco: Company General UseSaudi Aramco: Company General Use
BY
AHSAN Z ANSARI, PE
SAUDI ARAMCO
Saudi Aramco: Company General Use
OBJECTIVEOptimize Design to Control Cost,
Reduce O&M and Minimize Loss in Water Resources
Saudi Aramco: Company General Use
OUTLINEDISTRIBUTION NETWORK COMPONENTS
HYDRAULIC CONCEPTS
HYDRAULIC ANALYSIS
DESIGN METHODOLOGY
NETWORK MANAGEMENT
Saudi Aramco: Company General Use
DISTRIBUTION NETWORK COMPONENTS
Source• Surface Water• Groundwater
Treatment / Pumping
Storage
Distribution• Piping• Valves• Hydrants
Saudi Aramco: Company General Use
HYDRAULIC CONCEPTS
Energy Equation
Elevation Head ( Z)
Pressure Head ( p/γ)
Velocity Head ( V2/2g)
Head Loss or Energy Loss ( hL)
Saudi Aramco: Company General Use
ANALYSISApplicable Standards
AWWA- M31 & M32
10 State Standard
Saudi Aramco Standards
Identify Type of Users
20 Year Population Projection
Saudi Aramco: Company General Use
ANALYSISESTIMATE FLOW
100 Gallons per Capita per Day ( Typ. Res.) Average Day Maximum Day
1.5 x Avg. day (Typ.)
Maximum Hour 1.5 X Max. Day (Typ.)
Design Flow Max. Day + Fire Flow Or Max. Hour Flow
Minimum Pressure Average Flow Conditions- 35 psi-50 psi Peak Flow Conditions - 20 psi
Saudi Aramco: Company General Use
ANALYSIS AVAILABLE SOFTWARE
- Hydraulic Modelling (Water CAD, Water GEMS)
- Multi Platform
- Geo Spatial
- Asset Management
Saudi Aramco: Company General Use
ANALYSIS HYDRAULIC MODELLING
Step-1: Identify Network Components
Step-2: Build Network Skeleton
Draw from Scratch OR Import CAD/GIS Model from Utility Database
Assign Pipe Sizes, Node Elevations
Pipe Properties ( Roughness, C- Value)
Assign Flow Demand
Saudi Aramco: Company General Use
ANALYSIS Step-3: Define Source
Reservoir-Constant Level/Head
Tanks –Varying Operating Levels
Pumps- Pump Characteristic Curve
Single Design Point
3-Point Curve
VFD
Saudi Aramco: Company General Use
ANALYSIS Step-4: Steady State Simulation
• Hydraulic Analysis at Peak Conditions
• Simple Solution for Small Network
Step-5: Calibration• Flow Meters
• Pressure Sensors
Ref: Bentley
Saudi Aramco: Company General Use
ANALYSIS Step-6: Extended Period Simulation
Diurnal Pattern Simulation
Optimum Design
Saudi Aramco: Company General Use
ANALYSIS Surge Consideration
Pipes > 12”
Flow > 1000 gpm
Valve Closure Time
Pump Failure
Solution
Soft Start or VFD
MOV
Hydro-Pneumatic Tanks
Saudi Aramco: Company General Use
DESIGN METHODOLOGYLooped System
Reliable
Eliminate Dead Ends
Reduce Water Age
Valves at Intersection
Min. 6” Main for Hydrants
Saudi Aramco: Company General Use
DESIGN METHODOLOGYDirect Pumping
Direct to Distribution System
Speed Controls to Match Demand
PumpsDemand Area
Storage TankHyd
. Gra
die
nt
In Direct Pumping
Uniform Pumping
Demand Managed by Tank Level
Saudi Aramco: Company General Use
DESIGN METHODOLOGYRELIABILITY Standby Pumps
Emergency Power
Emergency Fuel for Generator
Saudi Aramco: Company General Use
NETWORK MANAGEMENT
GOAL: Minimize Water Losses/Revenue
Real Time Monitoring (SCADA)
Maintain Supply During Peak Condition
Regulate Flow/Pressure
Leak Detection
Routine Maintenance Programs
Continuous Database Update ( GIS)
Saudi Aramco: Company General UseSaudi Aramco: Company General Use
BY
AHSAN Z ANSARI, PE
SAUDI ARAMCO
Saudi Aramco: Company General Use
DESIGN METHODOLOGYDIRECT PUMPING SYSTEM
Pumps Directly to Distribution System
Needs Variable Speed Pumping
Example Ref: AWWA M32