Upload
others
View
17
Download
0
Embed Size (px)
Citation preview
Relion® 650 series
Busbar protection REB650Product Guide
Contents
1. 650 series overview........................................................3
2. Application.....................................................................3
3. Available functions..........................................................5
4. Differential protection....................................................12
5. Current protection........................................................12
6. Voltage protection........................................................13
7. Secondary system supervision.....................................14
8. Control.........................................................................14
9. Logic............................................................................15
10. Monitoring...................................................................16
11. Metering......................................................................18
12. Human Machine interface............................................19
13. Basic IED functions.....................................................19
14. Station communication................................................20
15. Hardware description..................................................21
16. Connection diagrams Customized...............................23
17. Connection diagrams Configured................................28
18. Technical data.............................................................35
19. Ordering for Customized IED.......................................59
20. Ordering for Configured IED........................................62
21. Ordering for Accessories.............................................64
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
© Copyright 2012 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
2 ABB
1. 650 series overviewThe 650 series IEDs provide both customized andconfigured solutions. With the customized IEDsyou have the freedom to completely adapt thefunctionality according to your needs.
The 650 series IEDs provide optimum 'off-the-shelf', ready-to-use solutions. It is configured withcomplete protection functionality and defaultparameters to meet the needs of a wide range ofapplications for generation, transmission and sub-transmission grids.
The 650 series IEDs include:• Customized versions providing the possibility to
adapt the functionality to the application needs.• Configured solutions are completely ready to
use solutions optimized for a wide range ofapplications for generation, transmission andsub-transmission grids.
• Support for user-defined names in the locallanguage for signal and function engineering.
• Minimized parameter settings based on defaultvalues and ABB's new global base valueconcept. You only need to set thoseparameters specific to your own application,such as the line data.
• GOOSE messaging for horizontalcommunication.
• Extended HMI functionality with 15 dynamicthree-color-indication LEDs per page, on up tothree pages, and configurable push-buttonshortcuts for different actions.
• Programmable LED text-based labels.• Settable 1A/5A -rated current inputs.
2. ApplicationThe numerical busbar protection REB650 IEDprovides its users with a wide variety of
application opportunities. Designed primarily forthe protection of single busbars with or withoutsectionalizers in high impedance basedapplications, it also offers high impedancedifferential protection for generators,autotransformers, shunt reactors and capacitorbanks. Its I/O capability allows you to protect upto three 3-phase high impedance differentialprotection zones with a single IED.
A number of additional protection functions areavailable for the protection of the bus couplerbay. The additional protection functions includedifferent types of phase and earth faultovercurrent protection and overvoltage/undervoltage protection.
One pre-configured package has been defined forthe following application:
• Complete busbar protection for two busbarsections (zone 1 and 2), with the possibilityfor check zone (A03)
For the high impedance differential protection, thedifferential current process is made in theanalogue current transformer circuits where thedifferential current is connected to the IED via ahigh ohmic resistor. In REB650, a current input isused for each phase and protection zone.
The package is configured and ready for directuse. Analogue inputs and binary input/outputcircuits are pre-defined.
The pre-configured IED can be changed andadapted to suit specific applications with thegraphical configuration tool.
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2 Issued: June 2012Revision: -
ABB 3
REB650-A03
YYY
ROV2 PTOV
59N 3Uo>UV2 PTUV
27 3U<
OV2 PTOV
59 3U>
ROV2 PTOV
59N 3Uo>
UV2 PTUV
27 3U<
OV2 PTOV
59 3U>
HZ PDIF
87N IdN
HZ PDIF
87N IdN
HZ PDIF
87N IdN
EF4 PTOC
67NOC4 PTOC
67
DNS PTOC
67Q
CC RPLD
52PD PD
CC RBRF
50BF 3I> BF
Zone 1
Zone 2
Zone 3 (used in this example as check zone)
Bus 1
Bus Coupler
Feeder Bays Feeder Bays
TRM module with 6I+4U AIM module with 6I+4U
Bus 2
VT1 VT2
IEC61850
ANSI IEC
Function Enabled in Settings
IEC61850
ANSI IEC
Function Disabled in Settings
IEC10000341-1-en.vsd
Y
3I> I2> IN>
IEC10000341 V1 EN
Figure 1. A typical busbar protection for two busbar sections with the possibility of a check zone
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
4 ABB
3. Available functions
Main protection functions
IEC 61850/Function blockname
ANSI Function description Busbar
RE
B65
0
RE
B65
0 (A
03)
HiZ
/3P
h
Differential protection
HZPDIF 87 1Ph High impedance differential protection 1–9 9
Back-up protection functions
IEC 61850/Functionblock name
ANSI Function description Busbar
RE
B65
0
RE
B65
0 (A
03)
HiZ
/3P
h
Current protection
OC4PTOC 51 Four step phase overcurrent protection, 3–phase output 0–1 1
EF4PTOC 51N/67N Four step residual overcurrent protection, zero/negative sequence direction
0–1 1
TRPTTR 49 Thermal overload protection, two time constants 0–1 1
CCRBRF 50BF Breaker failure protection, 3–phase activation andoutput
0–1 1
CCRPLD 52PD Pole discordance protection 0–1 1
DNSPTOC 46 Negative sequence based overcurrent function 0–1 1
Voltage protection
UV2PTUV 27 Two step undervoltage protection 0–2 2
OV2PTOV 59 Two step overvoltage protection 0–2 2
ROV2PTOV 59N Two step residual overvoltage protection 0–2 2
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 5
Control and monitoring functions
IEC 61850/Functionblock name
ANSI Function description Busbar
RE
B65
0
RE
B65
0 (A
03)
HiZ
/3P
h
Control
QCBAY Bay control 1 1
LOCREM Handling of LR-switch positions 1 1
LOCREMCTRL LHMI control of Permitted Source To Operate(PSTO)
1 1
CBC3 Circuit breaker for 3CB 1 1
SLGGIO Logic Rotating Switch for function selection andLHMI presentation
15 15
VSGGIO Selector mini switch extension 20 20
DPGGIO IEC 61850 generic communication I/O functionsdouble point
16 16
SPC8GGIO Single point generic control 8 signals 5 5
AUTOBITS AutomationBits, command function for DNP3.0 3 3
I103CMD Function commands for IEC60870-5-103 1 1
I103IEDCMD IED commands for IEC60870-5-103 1 1
I103USRCMD Function commands user defined forIEC60870-5-103
4 4
I103GENCMD Function commands generic for IEC60870-5-103 50 50
I103POSCMD IED commands with position and select forIEC60870-5-103
50 50
Secondary system supervision
SDDRFUF Fuse failure supervision 0–2 2
TCSSCBR Breaker close/trip circuit monitoring 3 3
Logic
SMPPTRC 94 Tripping logic, common 3–phase output 1–6 6
TMAGGIO Trip matrix logic 12 12
OR Configurable logic blocks, OR gate 283 283
INVERTER Configurable logic blocks, Inverter gate 140 140
PULSETIMER Configurable logic blocks, Pulse timer 40 40
GATE Configurable logic blocks, Controllable gate 40 40
XOR Configurable logic blocks, exclusive OR gate 40 40
LOOPDELAY Configurable logic blocks, loop delay 40 40
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
6 ABB
IEC 61850/Functionblock name
ANSI Function description Busbar
RE
B65
0
RE
B65
0 (A
03)
HiZ
/3P
h
TIMERSET Configurable logic blocks, timer function block 40 40
AND Configurable logic blocks, AND gate 280 280
SRMEMORY Configurable logic blocks, set-reset memory flip-flop gate
40 40
RSMEMORY Configurable logic blocks, reset-set memory flip-flop gate
40 40
FXDSIGN Fixed signal function block 1 1
B16I Boolean 16 to Integer conversion 16 16
B16IFCVI Boolean 16 to Integer conversion with logic noderepresentation
16 16
IB16A Integer to Boolean 16 conversion 16 16
IB16FCVB Integer to Boolean 16 conversion with logic noderepresentation
16 16
Monitoring
CVMMXN Measurements 6 6
CMMXU Phase current measurement 10 10
VMMXU Phase-phase voltage measurement 6 6
CMSQI Current sequence component measurement 6 6
VMSQI Voltage sequence measurement 6 6
VNMMXU Phase-neutral voltage measurement 6 6
AISVBAS Function block for service values presentation ofthe analog inputs
1 1
TM_P_P2 Function block for service values presentation ofprimary analog inputs 600TRM
1 1
AM_P_P4 Function block for service values presentation ofprimary analog inputs 600AIM
1 1
TM_S_P2 Function block for service values presentation ofsecondary analog inputs 600TRM
1 1
AM_S_P4 Function block for service values presentation ofsecondary analog inputs 600AIM
1 1
CNTGGIO Event counter 5 5
DRPRDRE Disturbance report 1 1
AxRADR Analog input signals 4 4
BxRBDR Binary input signals 6 6
SPGGIO IEC 61850 generic communication I/O functions 64 64
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 7
IEC 61850/Functionblock name
ANSI Function description Busbar
RE
B65
0
RE
B65
0 (A
03)
HiZ
/3P
h
SP16GGIO IEC 61850 generic communication I/O functions16 inputs
16 16
MVGGIO IEC 61850 generic communication I/O functions 16 16
MVEXP Measured value expander block 66 66
SPVNZBAT Station battery supervision 0–1 1
SSIMG 63 Insulation gas monitoring function 0–2 2
SSIML 71 Insulation liquid monitoring function 0–2 2
SSCBR Circuit breaker condition monitoring 0–1 1
I103MEAS Measurands for IEC60870-5-103 1 1
I103MEASUSR Measurands user defined signals forIEC60870-5-103
3 3
I103AR Function status auto-recloser for IEC60870-5-103 1 1
I103EF Function status earth-fault for IEC60870-5-103 1 1
I103FLTPROT Function status fault protection for IEC60870-5-103 1 1
I103IED IED status for IEC60870-5-103 1 1
I103SUPERV Supervison status for IEC60870-5-103 1 1
I103USRDEF Status for user defined signals for IEC60870-5-103 20 20
Metering
PCGGIO Pulse counter logic 16 16
ETPMMTR Function for energy calculation and demandhandling
3 3
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
8 ABB
Communication
IEC 61850/Functionblock name
ANSI Function description Busbar
RE
B65
0
RE
B65
0 (A
03)
HiZ
/3P
h
Station communication
IEC61850-8-1 IEC 61850 communication protocol 1 1
DNPGEN DNP3.0 for TCP/IP communication protocol 1 1
RS485DNP DNP3.0 for EIA-485 communication protocol 1 1
CH1TCP DNP3.0 for TCP/IP communication protocol 1 1
CH2TCP DNP3.0 for TCP/IP communication protocol 1 1
CH3TCP DNP3.0 for TCP/IP communication protocol 1 1
CH4TCP DNP3.0 for TCP/IP communication protocol 1 1
OPTICALDNP DNP3.0 for optical serial communication 1 1
MSTSERIAL DNP3.0 for serial communication protocol 1 1
MST1TCP DNP3.0 for TCP/IP communication protocol 1 1
MST2TCP DNP3.0 for TCP/IP communication protocol 1 1
MST3TCP DNP3.0 for TCP/IP communication protocol 1 1
MST4TCP DNP3.0 for TCP/IP communication protocol 1 1
RS485GEN RS485 1 1
OPTICALPROT Operation selection for optical serial 1 1
RS485PROT Operation selection for RS485 1 1
DNPFREC DNP3.0 fault records for TCP/IPcommunication protocol
1 1
OPTICAL103 IEC60870-5-103 Optical serial communication 1 1
RS485103 IEC60870-5-103 serial communication forRS485
1 1
GOOSEINTLKRCV Horizontal communication via GOOSE forinterlocking
59 59
GOOSEBINRCV GOOSE binary receive 4 4
ETHFRNTETHLAN1GATEWAY
Ethernet configuration of front port, LAN1 portand gateway
1 1
GOOSEDPRCV GOOSE function block to receive a doublepoint value
32 32
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 9
IEC 61850/Functionblock name
ANSI Function description Busbar
RE
B65
0
RE
B65
0 (A
03)
HiZ
/3P
h
GOOSEINTRCV GOOSE function block to receive an integervalue
32 32
GOOSEMVRCV GOOSE function block to receive ameasurand value
16 16
GOOSESPRCV GOOSE function block to receive a singlepoint value
64 64
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
10 ABB
Basic IED functions
IEC 61850/Functionblock name
Function description
Basic functions included in all products
INTERRSIG Self supervision with internal event list 1
SELFSUPEVLST Self supervision with internal event list 1
TIMESYNCHGEN Time synchronization 1
SNTP Time synchronization 1
DTSBEGIN, DTSEND,TIMEZONE
Time synchronization, daylight saving 1
IRIG-B Time synchronization 1
SETGRPS Setting group handling 1
ACTVGRP Parameter setting groups 1
TESTMODE Test mode functionality 1
CHNGLCK Change lock function 1
TERMINALID IED identifiers 1
PRODINF Product information 1
SYSTEMTIME System time 1
RUNTIME IED Runtime comp 1
PRIMVAL Primary system values 1
SMAI_20_1 -SMAI_20_12
Signal matrix for analog inputs 2
3PHSUM Summation block 3 phase 12
GBASVAL Global base values for settings 6
ATHSTAT Authority status 1
ATHCHCK Authority check 1
SPACOMMMAP SPA communication mapping 1
FTPACCS FTP access with password 1
DOSFRNT Denial of service, frame rate control for front port 1
DOSLAN1 Denial of service, frame rate control for LAN1 1
DOSSCKT Denial of service, socket flow control 1
SAFEFILECOPY Safe file copy function 1
SPATD Date and time via SPA protocol 1
BCSCONF Basic communication system 1
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 11
4. Differential protection
1Ph High impedance differential protectionHZPDIFThe 1Ph High impedance differential protection(HZPDIF) function can be used when the involvedCT cores have the same turns ratio and similarmagnetizing characteristics. It utilizes an externalsummation of the currents in the interconnectedCTs, a series resistor, and a voltage dependentresistor which are mounted externally connectedto the IED.
Three instances of 1Ph High impedancedifferential protection function (HZPDIF) can beused to provide a three phase differentialprotection function to be used for example asbusbar protection. One instance of HZPDIF canalso be used as high impedance REF protection.
5. Current protection
Four step phase overcurrent protection, 3-phaseoutput OC4PTOCThe four step phase overcurrent protectionfunction OC4PTOC has an inverse or definite timedelay independent for step 1 and 4 separately.Step 2 and 3 are always definite time delayed.
All IEC and ANSI inverse time characteristics areavailable.
The directional function is voltage polarized withmemory. The function can be set to be directionalor non-directional independently for each of thesteps.
A 2nd harmonic blocking can be set individuallyfor each step.
Four step residual overcurrent protection, zerosequence and negative sequence directionEF4PTOCThe four step residual overcurrent protection,zero or negative sequence direction (EF4PTOC)has a settable inverse or definite time delayindependent for step 1 and 4 separately. Step 2and 3 are always definite time delayed.
All IEC and ANSI inverse time characteristics areavailable.
EF4PTOC can be set directional or non-directional independently for each of the steps.
The directional part of the function can be set tooperate on following combinations:• Directional current (I3PDir) versus Polarizing
voltage (U3PPol)• Directional current (I3PDir) versus Polarizing
current (I3PPol)• Directional current (I3PDir) versus Dual
polarizing (UPol+ZPol x IPol) where ZPol = RPol+ jXPol
IDir, UPol and IPol can be independently selectedto be either zero sequence or negative sequence.
Second harmonic blocking restraint level can beset for the function and can be used to blockeach step individually.
Thermal overload protection, two time constantTRPTTRIf a power transformer or generator reaches veryhigh temperatures the equipment might bedamaged. The insulation within the transformer/generator will have forced ageing. As aconsequence of this the risk of internal phase-to-phase or phase-to-earth faults will increase. Hightemperature will degrade the quality of thetransformer/generator insulation.
The thermal overload protection estimates theinternal heat content of the transformer/generator(temperature) continuously. This estimation ismade by using a thermal model of the transformer/generator with two time constants, which isbased on current measurement.
Two warning levels are available. This enablesactions in the power system to be done beforedangerous temperatures are reached. If thetemperature continues to increase to the tripvalue, the protection initiates a trip of theprotected transformer/generator.
Breaker failure protection, 3-phase activation andoutputCCRBRF can be current based, contact based, oran adaptive combination of these two conditions.
Breaker failure protection, 3-phase activation andoutput (CCRBRF) ensures fast back-up tripping ofsurrounding breakers in case the own breakerfails to open. CCRBRF can be current based,
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
12 ABB
contact based, or an adaptive combination ofthese two conditions.
Current check with extremely short reset time isused as check criterion to achieve high securityagainst unnecessary operation.
Contact check criteria can be used where thefault current through the breaker is small.
Breaker failure protection, 3-phase activation andoutput (CCRBRF) current criteria can be fulfilledby one or two phase currents the residual current,or one phase current plus residual current. Whenthose currents exceed the user defined settings,the function is triggered. These conditionsincrease the security of the back-up tripcommand.
CCRBRF function can be programmed to give athree-phase re-trip of the own breaker to avoidunnecessary tripping of surrounding breakers.
Pole discordance protection CCRPLDCircuit breakers and disconnectors can end upwith thes in different positions (close-open), dueto electrical or mechanical failures. An openphase can cause negative and zero sequencecurrents which cause thermal stress on rotatingmachines and can cause unwanted operation ofzero sequence or negative sequence currentfunctions.
Normally the own breaker is tripped to correctsuch a situation. If the situation persists thesurrounding breakers should be tripped to clearthe unsymmetrical load situation.
The pole discordance function operates based oninformation from the circuit breaker logic withadditional criteria from unsymmetrical phasecurrents when required.
Negative sequence based overcurrent functionDNSPTOCNegative sequence based overcurrent function(DNSPTOC) is typically used as sensitive earth-fault protection of power lines, where incorrectzero sequence polarization may result frommutual induction between two or more parallellines.
Additionally, it is applied in applications oncables, where zero sequence impedancedepends on the fault current return paths, but the
cable negative sequence impedance is practicallyconstant.
The directional function is current and voltagepolarized. The function can be set to forward,reverse or non-directional independently for eachstep.
DNSPTOC protects against all unbalanced faultsincluding phase-to-phase faults. The minimumstart current of the function must be set to abovethe normal system unbalance level in order toavoid unwanted operation.
6. Voltage protection
Two step undervoltage protection UV2PTUVUndervoltages can occur in the power systemduring faults or abnormal conditions. Two stepundervoltage protection (UV2PTUV) function canbe used to open circuit breakers to prepare forsystem restoration at power outages or as long-time delayed back-up to primary protection.
UV2PTUV has two voltage steps, where step 1 issettable as inverse or definite time delayed. Step2 is always definite time delayed.
Two step overvoltage protection OV2PTOVOvervoltages may occur in the power systemduring abnormal conditions such as suddenpower loss, tap changer regulating failures, openline ends on long lines etc.
Two step overvoltage protection (OV2PTOV)function can be used to detect open line ends,normally then combined with a directional reactiveover-power function to supervise the systemvoltage. When triggered, the function will causean alarm, switch in reactors, or switch outcapacitor banks.
OV2PTOV has two voltage steps, where step 1can be set as inverse or definite time delayed.Step 2 is always definite time delayed.
OV2PTOV has an extremely high reset ratio toallow settings close to system service voltage.
Two step residual overvoltage protectionROV2PTOVResidual voltages may occur in the power systemduring earth faults.
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 13
Two step residual overvoltage protectionROV2PTOV function calculates the residualvoltage from the three-phase voltage inputtransformers or measures it from a single voltageinput transformer fed from an open delta orneutral point voltage transformer.
ROV2PTOV has two voltage steps, where step 1can be set as inverse or definite time delayed.Step 2 is always definite time delayed.
7. Secondary system supervision
Fuse failure supervision SDDRFUFThe aim of the fuse failure supervision function(SDDRFUF) is to block voltage measuringfunctions at failures in the secondary circuitsbetween the voltage transformer and the IED inorder to avoid unwanted operations thatotherwise might occur.
The fuse failure supervision function basically hasthree different algorithms, negative sequence andzero sequence based algorithms and anadditional delta voltage and delta currentalgorithm.
The negative sequence detection algorithm isrecommended for IEDs used in isolated or high-impedance earthed networks. It is based on thenegative-sequence measuring quantities, a highvalue of negative sequence voltage 3U2 without
the presence of the negative-sequence current3I2.
The zero sequence detection algorithm isrecommended for IEDs used in directly or lowimpedance earthed networks. It is based on thezero sequence measuring quantities, a high valueof zero sequence voltage 3U0 without the
presence of the zero sequence current 3I0.
For better adaptation to system requirements, anoperation mode setting has been introducedwhich makes it possible to select the operatingconditions for negative sequence and zerosequence based function. The selection ofdifferent operation modes makes it possible tochoose different interaction possibilities betweenthe negative sequence and zero sequence basedalgorithm.
A criterion based on delta current and deltavoltage measurements can be added to the fusefailure supervision function in order to detect athree phase fuse failure, which in practice is moreassociated with voltage transformer switchingduring station operations.
Breaker close/trip circuit monitoring TCSSCBRThe trip circuit supervision function TCSSCBR isdesigned to supervise the control circuit of thecircuit breaker. The invalidity of a control circuit isdetected by using a dedicated output contactthat contains the supervision functionality.
The function operates after a predefinedoperating time and resets when the faultdisappears.
8. Control
Bay control QCBAYThe Bay control QCBAY function is used togetherwith Local remote and local remote controlfunctions to handle the selection of the operatorplace per bay. QCBAY also provides blockingfunctions that can be distributed to differentapparatuses within the bay.
Local remote LOCREM /Local remote controlLOCREMCTRLThe signals from the local HMI or from an externallocal/remote switch are applied via the functionblocks LOCREM and LOCREMCTRL to the Baycontrol (QCBAY) function block. A parameter infunction block LOCREM is set to choose if theswitch signals are coming from the local HMI orfrom an external hardware switch connected viabinary inputs.
Circuit breaker control for circuit breaker, CBC3The CBC3 consists of 3 functions:
• SCILO - The Logical node for interlocking.SCILO function is used to enable a switchingoperation if the interlocking conditionspermit. SCILO function itself does notprovide any interlocking functionality. Theinterlocking conditions are generated inseparate function blocks containing theinterlocking logic.
• SCSWI - The Switch controller initializes andsupervises all functions to properly selectand operate switching primary apparatuses.
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
14 ABB
The Switch controller may handle andoperate on one three-phase device.
• SXCBR - The purpose of SXCBR is toprovide the actual status of positions and toperform the control operations, that is, passall the commands to primary apparatuses inthe form of circuit breakers via output boardsand to supervise the switching operation andposition.
Logic rotating switch for function selection andLHMI presentation SLGGIOThe logic rotating switch for function selectionand LHMI presentation (SLGGIO) (or the selectorswitch function block) is used to get a selectorswitch functionality similar to the one provided bya hardware selector switch. Hardware selectorswitches are used extensively by utilities, in orderto have different functions operating on pre-setvalues. Hardware switches are however sourcesfor maintenance issues, lower system reliabilityand an extended purchase portfolio. The logicselector switches eliminate all these problems.
Selector mini switch VSGGIOThe Selector mini switch VSGGIO function blockis a multipurpose function used for a variety ofapplications, as a general purpose switch.
VSGGIO can be controlled from the menu or froma symbol on the single line diagram (SLD) on thelocal HMI.
IEC 61850 generic communication I/O functionsDPGGIOThe IEC 61850 generic communication I/Ofunctions (DPGGIO) function block is used tosend double indications to other systems orequipment in the substation. It is especially usedin the interlocking and reservation station-widelogics.
Single point generic control 8 signals SPC8GGIOThe Single point generic control 8 signals(SPC8GGIO) function block is a collection of 8single point commands, designed to bring incommands from REMOTE (SCADA) to those partsof the logic configuration that do not needextensive command receiving functionality (forexample, SCSWI). In this way, simple commandscan be sent directly to the IED outputs, withoutconfirmation. Confirmation (status) of the result ofthe commands is supposed to be achieved by
other means, such as binary inputs and SPGGIOfunction blocks. The commands can be pulsed orsteady.
AutomationBits AUTOBITSThe Automation bits function (AUTOBITS) is usedto configure the DNP3 protocol commandhandling.
9. Logic
Tripping logic common 3-phase output SMPPTRCA function block for protection tripping isprovided for each circuit breaker involved in thetripping of the fault. It provides pulse prolongationto ensure a three-phase trip pulse of sufficientlength, as well as all functionality necessary forcorrect co-operation with autoreclosing functions.
The trip function block also includes functionalityfor breaker lock-out.
Trip matrix logic TMAGGIOThe Trip matrix logic TMAGGIO function is usedto route trip signals and other logical outputsignals to the tripping logics SMPPTRC andSPTPTRC or to different output contacts on theIED.
TMAGGIO output signals and the physical outputsallows the user to adapt the signals to thephysical tripping outputs according to the specificapplication needs.
Configurable logic blocksA number of logic blocks and timers are availablefor the user to adapt the configuration to thespecific application needs.
• OR function block.
• INVERTER function blocks that inverts the inputsignal.
• PULSETIMER function block can be used, forexample, for pulse extensions or limiting ofoperation of outputs, settable pulse time.
• GATE function block is used for whether or nota signal should be able to pass from the inputto the output.
• XOR function block.
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 15
• LOOPDELAY function block used to delay theoutput signal one execution cycle.
• TIMERSET function has pick-up and drop-outdelayed outputs related to the input signal. Thetimer has a settable time delay and must be Onfor the input signal to activate the output withthe appropriate time delay.
• AND function block.
• SRMEMORY function block is a flip-flop thatcan set or reset an output from two inputsrespectively. Each block has two outputs whereone is inverted. The memory setting controls ifthe block's output should reset or return to thestate it was, after a power interruption. The SETinput has priority if both SET and RESET inputsare operated simultaneously.
• RSMEMORY function block is a flip-flop thatcan reset or set an output from two inputsrespectively. Each block has two outputs whereone is inverted. The memory setting controls ifthe block's output should reset or return to thestate it was, after a power interruption. TheRESET input has priority if both SET andRESET are operated simultaneously.
Boolean 16 to Integer conversion B16IBoolean 16 to integer conversion function (B16I)is used to transform a set of 16 binary (logical)signals into an integer.
Boolean 16 to Integer conversion with logic noderepresentation B16IFCVIBoolean 16 to integer conversion with logic noderepresentation function (B16IFCVI) is used totransform a set of 16 binary (logical) signals intoan integer.
Integer to Boolean 16 conversion IB16AInteger to boolean 16 conversion function (IB16A)is used to transform an integer into a set of 16binary (logical) signals.
Integer to Boolean 16 conversion with logic noderepresentation IB16FCVBInteger to boolean conversion with logic noderepresentation function (IB16FCVB) is used totransform an integer to 16 binary (logic) signals.
IB16FCVB function can receive remote valuesover IEC61850 depending on the operatorposition input (PSTO).
10. Monitoring
IEC61850 generic communication I/O functionSPGGIOIEC61850 generic communication I/O functions(SPGGIO) is used to send one single logical signalto other systems or equipment in the substation.
IEC61850 generic communication 1/O function 16inputsIEC 61850 generic communication I/O functions16 inputs (SP16GGIO) function is used to send upto 16 logical signals to other systems orequipment in the substation.
Measurements CVMMXN, CMMXU, VNMMXU,VMMXU, CMSQI, VMSQIThe measurement functions are used to get on-line information from the IED. These servicevalues make it possible to display on-lineinformation on the local HMI and on theSubstation automation system about:
• measured voltages, currents, frequency,active, reactive and apparent power andpower factor
• primary and secondary phasors• current sequence components• voltage sequence components
Event counter CNTGGIOEvent counter (CNTGGIO) has six counters whichare used for storing the number of times eachcounter input has been activated.
Disturbance report DRPRDREComplete and reliable information aboutdisturbances in the primary and/or in thesecondary system together with continuous event-logging is accomplished by the disturbance reportfunctionality.
Disturbance report DRPRDRE, always included inthe IED, acquires sampled data of all selectedanalog input and binary signals connected to thefunction block with a, maximum of 40 analog and96 binary signals.
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
16 ABB
The Disturbance report functionality is a commonname for several functions:
• Event list• Indications• Event recorder• Trip value recorder• Disturbance recorder
The Disturbance report function is characterizedby great flexibility regarding configuration, startingconditions, recording times, and large storagecapacity.
A disturbance is defined as an activation of aninput to the AxRADR or BxRBDR function blocks,which are set to trigger the disturbance recorder.All signals from start of pre-fault time to the endof post-fault time will be included in the recording.
Every disturbance report recording is saved in theIED in the standard Comtrade format. The sameapplies to all events, which are continuouslysaved in a ring-buffer. The local HMI is used toget information about the recordings. Thedisturbance report files may be uploaded toPCM600 for further analysis using the disturbancehandling tool.
Event list DRPRDREContinuous event-logging is useful for monitoringthe system from an overview perspective and is acomplement to specific disturbance recorderfunctions.
The event list logs all binary input signalsconnected to the Disturbance report function. Thelist may contain up to 1000 time-tagged eventsstored in a ring-buffer.
Indications DRPRDRETo get fast, condensed and reliable informationabout disturbances in the primary and/or in thesecondary system it is important to know, forexample binary signals that have changed statusduring a disturbance. This information is used inthe short perspective to get information via thelocal HMI in a straightforward way.
There are three LEDs on the local HMI (green,yellow and red), which will display statusinformation about the IED and the Disturbancereport function (triggered).
The Indication list function shows all selectedbinary input signals connected to the Disturbancereport function that have changed status during adisturbance.
Event recorder DRPRDREQuick, complete and reliable information aboutdisturbances in the primary and/or in thesecondary system is vital, for example, time-tagged events logged during disturbances. Thisinformation is used for different purposes in theshort term (for example corrective actions) and inthe long term (for example functional analysis).
The event recorder logs all selected binary inputsignals connected to the Disturbance reportfunction. Each recording can contain up to 150time-tagged events.
The event recorder information is available for thedisturbances locally in the IED.
The event recording information is an integratedpart of the disturbance record (Comtrade file).
Trip value recorder DRPRDREInformation about the pre-fault and fault values forcurrents and voltages are vital for the disturbanceevaluation.
The Trip value recorder calculates the values of allselected analog input signals connected to theDisturbance report function. The result ismagnitude and phase angle before and during thefault for each analog input signal.
The trip value recorder information is available forthe disturbances locally in the IED.
The trip value recorder information is anintegrated part of the disturbance record(Comtrade file).
Disturbance recorder DRPRDREThe Disturbance recorder function supplies fast,complete and reliable information aboutdisturbances in the power system. It facilitatesunderstanding system behavior and relatedprimary and secondary equipment during andafter a disturbance. Recorded information is usedfor different purposes in the short perspective (forexample corrective actions) and long perspective(for example functional analysis).
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 17
The Disturbance recorder acquires sampled datafrom selected analog- and binary signalsconnected to the Disturbance report function(maximum 40 analog and 96 binary signals). Thebinary signals available are the same as for theevent recorder function.
The function is characterized by great flexibilityand is not dependent on the operation ofprotection functions. It can record disturbancesnot detected by protection functions. Up to threeseconds of data before the trigger instant can besaved in the disturbance file.
The disturbance recorder information for up to100 disturbances are saved in the IED and thelocal HMI is used to view the list of recordings.
Measured value expander block MVEXPThe current and voltage measurements functions(CVMMXN, CMMXU, VMMXU and VNMMXU),current and voltage sequence measurementfunctions (CMSQI and VMSQI) and IEC 61850generic communication I/O functions (MVGGIO)are provided with measurement supervisionfunctionality. All measured values can besupervised with four settable limits: low-low limit,low limit, high limit and high-high limit. Themeasure value expander block has beenintroduced to enable translating the integer outputsignal from the measuring functions to 5 binarysignals: below low-low limit, below low limit,normal, above high-high limit or above high limit.The output signals can be used as conditions inthe configurable logic or for alarming purpose.
Station battery supervision SPVNZBATThe station battery supervision functionSPVNZBAT is used for monitoring battery terminalvoltage.
SPVNZBAT activates the start and alarm outputswhen the battery terminal voltage exceeds the setupper limit or drops below the set lower limit. Atime delay for the overvoltage and undervoltagealarms can be set according to definite timecharacteristics.
In the definite time (DT) mode, SPVNZBAToperates after a predefined operate time andresets when the battery undervoltage orovervoltage condition disappears after reset time.
Insulation gas monitoring function SSIMGInsulation gas monitoring function SSIMG is usedfor monitoring the circuit breaker condition. Binaryinformation based on the gas pressure in thecircuit breaker is used as input signals to thefunction. In addition, the function generatesalarms based on received information.
Insulation liquid monitoring function SSIMLInsulation liquid monitoring function SSIML isused for monitoring the circuit breaker condition.Binary information based on the oil level in thecircuit breaker is used as input signals to thefunction. In addition, the function generatesalarms based on received information.
Circuit breaker monitoring SSCBRThe circuit breaker condition monitoring functionSSCBR is used to monitor different parameters ofthe circuit breaker. The breaker requiresmaintenance when the number of operations hasreached a predefined value. The energy iscalculated from the measured input currents as a
sum of Iyt values. Alarms are generated when thecalculated values exceed the threshold settings.
The function contains a blocking functionality. It ispossible to block the function outputs, if desired.
11. Metering
Pulse counter logic PCGGIOPulse counter (PCGGIO) function countsexternally generated binary pulses, for instancepulses coming from an external energy meter, forcalculation of energy consumption values. Thepulses are captured by the BIO (binary input/output) module and then read by the PCGGIOfunction. A scaled service value is available overthe station bus.
Function for energy calculation and demandhandling ETPMMTROutputs from the Measurements (CVMMXN)function can be used to calculate energyconsumption. Active as well as reactive values arecalculated in import and export direction. Valuescan be read or generated as pulses. Maximumdemand power values are also calculated by thefunction.
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
18 ABB
12. Human Machine interface
Local HMI
IEC12000175 V1 EN
Figure 2. Local human-machine interface
The LHMI of the IED contains the followingelements:• Display (LCD)• Buttons• LED indicators• Communication port
The LHMI is used for setting, monitoring andcontrolling.
The Local human machine interface, LHMIincludes a graphical monochrome LCD with aresolution of 320x240 pixels. The character sizemay vary depending on selected language. Theamount of characters and rows fitting the viewdepends on the character size and the view thatis shown.
The LHMI is simple and easy to understand. Thewhole front plate is divided into zones, each witha well-defined functionality:
• Status indication LEDs• Alarm indication LEDs which can indicate
three states with the colors green, yellowand red, with user printable label. All LEDsare configurable from the PCM600 tool
• Liquid crystal display (LCD)• Keypad with push buttons for control and
navigation purposes, switch for selectionbetween local and remote control and reset
• Five user programmable function buttons• An isolated RJ45 communication port for
PCM600
13. Basic IED functions
Self supervision with internal event listThe Self supervision with internal event list(INTERRSIG and SELFSUPEVLST) function reacts
to internal system events generated by thedifferent built-in self-supervision elements. Theinternal events are saved in an internal event list.
Time synchronizationUse a common global source for example GPStime synchronization inside each substation aswell as inside the area of the utility responsibilityto achieve a common time base for the IEDs in aprotection and control system. This makescomparison and analysis of events anddisturbance data between all IEDs in the powersystem possible.
Time-tagging of internal events and disturbancesare an excellent help when evaluating faults.Without time synchronization, only the eventswithin the IED can be compared to one another.With time synchronization, events anddisturbances within the entire station, and evenbetween line ends, can be compared duringevaluation.
In the IED, the internal time can be synchronizedfrom a number of sources:
• SNTP• IRIG-B• DNP• IEC60870-5-103
Parameter setting groups ACTVGRPUse the four different groups of settings tooptimize the IED operation for different powersystem conditions. Creating and switchingbetween fine-tuned setting sets, either from thelocal HMI or configurable binary inputs, results ina highly adaptable IED that can cope with avariety of power system scenarios.
Test mode functionality TESTMODEThe protection and control IEDs may have manyincluded functions. To make the testingprocedure easier, the IEDs include the featurethat allows individual blocking of all functionsexcept the function(s) the shall be tested.
There are two ways of entering the test mode:
• By configuration, activating an input signal ofthe function block TESTMODE
• By setting the IED in test mode in the localHMI
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 19
While the IED is in test mode, all protectionfunctions are blocked.
Any function can be unblocked individuallyregarding functionality and event signaling. Thisenables the user to follow the operation of one orseveral related functions to check functionalityand to check parts of the configuration, and soon.
Change lock function CHNGLCKChange lock function (CHNGLCK) is used toblock further changes to the IED configurationand settings once the commissioning is complete.The purpose is to block inadvertent IEDconfiguration changes beyond a certain point intime.
Authority status ATHSTATAuthority status (ATHSTAT) function is anindication function block for user log-on activity.
Authority check ATHCHCKTo safeguard the interests of our customers, boththe IED and the tools that are accessing the IEDare protected, by means of authorizationhandling. The authorization handling of the IEDand the PCM600 is implemented at both accesspoints to the IED:
• local, through the local HMI• remote, through the communication ports
14. Station communication
IEC 61850-8-1 communication protocolThe IED supports the communication protocolsIEC 61850-8-1 and DNP3 over TCP/IP. Alloperational information and controls are availablethrough these protocols. However, somecommunication functions, for example, horizontalcommunication (GOOSE) between the IEDs, isonly enabled by the IEC 61850-8-1communication protocol.
The IED is equipped with an optical Ethernet rearport for the substation communication standard
IEC 61850-8-1. IEC 61850-8-1 protocol allowsintelligent electrical devices (IEDs) from differentvendors to exchange information and simplifiessystem engineering. Peer-to-peer communicationaccording to GOOSE is part of the standard.Disturbance files uploading is provided.
Disturbance files are accessed using the IEC61850-8-1 protocol. Disturbance files areavailable to any Ethernet based application viaFTP in the standard Comtrade format. Further,the IED can send and receive binary values,double point values and measured values (forexample from MMXU functions), together withtheir quality bit, using the IEC 61850-8-1 GOOSEprofile. The IED meets the GOOSE performancerequirements for tripping applications insubstations, as defined by the IEC 61850standard. The IED interoperates with other IEC61850-compliant IEDs, tools, and systems andsimultaneously reports events to five differentclients on the IEC 61850 station bus.
The event system has a rate limiter to reduceCPU load. The event channel has a quota of 10events/second. If the quota is exceeded the eventchannel transmission is blocked until the eventchanges is below the quota, no event is lost.
All communication connectors, except for thefront port connector, are placed on integratedcommunication modules. The IED is connected toEthernet-based communication systems via thefibre-optic multimode LC connector (100BASE-FX).
The IED supports SNTP and IRIG-B timesynchronization methods with a time-stampingresolution of 1 ms.
• Ethernet based: SNTP and DNP3• With time synchronization wiring: IRIG-B
The IED supports IEC 60870-5-103 timesynchronization methods with a time stampingresolution of 5 ms.
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
20 ABB
Table 1. Supported station communication interfaces and protocols
Protocol Ethernet Serial
100BASE-FX LC Glass fibre (ST connector) EIA-485
IEC 61850–8–1 ● - -
DNP3 ● ● ●
IEC 60870-5-103 - ● ●● = Supported
Horizontal communication via GOOSE forinterlockingGOOSE communication can be used forexchanging information between IEDs via the IEC61850-8-1 station communication bus. This istypically used for sending apparatus positionindications for interlocking or reservation signalsfor 1-of-n control. GOOSE can also be used toexchange any boolean, integer, double point andanalog measured values between IEDs.
DNP3 protocolDNP3 (Distributed Network Protocol) is a set ofcommunications protocols used to communicatedata between components in process automationsystems. For a detailed description of the DNP3protocol, see the DNP3 Communication protocolmanual.
IEC 60870-5-103 communication protocolIEC 60870-5-103 is an unbalanced (master-slave)protocol for coded-bit serial communicationexchanging information with a control system,
and with a data transfer rate up to 19200 bit/s. InIEC terminology, a primary station is a master anda secondary station is a slave. Thecommunication is based on a point-to-pointprinciple. The master must have software that caninterpret IEC 60870-5-103 communicationmessages.
IEC 60870-5-103 protocol can be configured touse either the optical serial or RS485 serialcommunication interface on the COM05communication module. The functions Operationselection for optical serial (OPTICALPROT) andOperation selection for RS485 (RS485PROT) areused to select the communication interface.
The functions IEC60870-5-103 Optical serialcommunication (OPTICAL103) andIEC60870-5-103 serial communication for RS485(RS485103) are used to configure thecommunication parameters for either the opticalserial or RS485 serial communication interfaces.
15. Hardware description
Layout and dimensionsMounting alternativesThe following mounting alternatives are available(IP40 protection from the front):
• 19” rack mounting kit
See ordering for details about available mountingalternatives.
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 21
Rack mounting a single 3U IED
B
A C
D
IEC11000248 V1 EN
Figure 3. Rack mounted 3U IED
A 224 mm + 12 mm with ring-lug connectors
B 22.5 mm
C 482 mm
D 132 mm, 3U
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
22 ABB
16. Connection diagrams Customized
Connection diagrams for 650 series
IEC12000593 V1 EN
Figure 4. Designation for 3U, 1/1x19" casing with 1 TRM
IEC12000594 V1 EN
Figure 5. Designation for 3U, 1/1x19" casing with 1 TRM and 1 AIM
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 23
IEC12000595 V1 EN
Figure 6. Communication module (COM)
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
24 ABB
IEC12000596 V1 EN
Figure 7. Power supply module (PSM) 48-125V DC
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 25
IEC12000597 V1 EN
Figure 8. Power supply module (PSM) 110-250V DC, 100–240V AC
IEC12000598 V1 EN
Figure 9. Transformer module (TRM)
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
26 ABB
IEC12000599 V1 EN
Figure 10. Analog input (AIM)
IEC12000600 V1 EN
Figure 11. Binary input/output (BIO) option
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 27
17. Connection diagrams Configured
IEC12000464 V1 EN
Figure 12. Designation for3U, 1/1x19" casing with 1 TRM and 1 AIM
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
28 ABB
Connection diagrams for REB650 A03
IEC12000465 V1 EN
Figure 13. Communication module (COM)
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 29
IEC12000466 V1 EN
Figure 14. Power supply module (PSM) 48-125V DC
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
30 ABB
IEC12000467 V1 EN
Figure 15. Power supply module (PSM) 110-250V DC, 100–240V AC
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 31
IEC12000468 V1 EN
Figure 16. Transformer module (TRM)
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
32 ABB
IEC12000469 V1 EN
Figure 17. Analog input (AIM)
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 33
IEC12000470 V1 EN
Figure 18. Binary input/output (BIO) option
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
34 ABB
18. Technical data
General
Definitions
Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions,the equipment meets the specified requirements
Operative range The range of values of a given energizing quantity for which the equipment, under specifiedconditions, is able to perform its intended functions according to the specified requirements
Energizing quantities, rated values and limitsAnalog inputs
Table 2. Energizing inputs
Description Value
Rated frequency 50/60 Hz
Operating range Rated frequency ± 5 Hz
Current inputs Rated current, In 0.1/0.5 A1) 1/5 A2)
Thermal withstand capability:
• Continuously 4 A 20 A
• For 1 s 100 A 500 A *)
• For 10 s 20 A 100 A
Dynamic current withstand:
• Half-wave value 250 A 1250 A
Input impedance <100 mΩ <20 mΩ
Voltage inputs Rated voltage, Un 100 V AC/ 110 V AC/ 115 V AC/ 120 V AC
Voltage withstand:
• Continuous 420 V rms
• For 10 s 450 V rms
Burden at rated voltage <0.05 VA
*) max. 350 A for 1 s when COMBITEST test switch is included.
1) Residual current2) Phase currents or residual current
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 35
Auxiliary AC and DC voltage
Table 3. Power supply
Description 600PSM02 600PSM03
Uauxnominal 48, 60, 110, 125 V DC 100, 110, 120, 220, 240 V AC, 50and 60 Hz
110, 125, 220, 250 V DC
Uauxvariation 80...120% of Un (38.4...150 V DC) 85...110% of Un (85...264 V AC)
80...120% of Un (88...300 V DC)
Maximum load of auxiliary voltagesupply
35 W for DC40 W for AC
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 and 120 Hz)
Maximum interruption time in theauxiliary DC voltage without resettingthe IED
50 ms at Uaux
Binary inputs and outputs
Table 4. Binary inputs
Description Value
Operating range Maximum input voltage 300 V DC
Rated voltage 24...250 V DC
Current drain 1.6...1.8 mA
Power consumption/input <0.38 W
Threshold voltage 15...221 V DC (parametrizable in the range in steps of 1% ofthe rated voltage)
Table 5. Signal output and IRF output
IRF relay change over - type signal output relay
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry for 3.0 s 10 A
Make and carry 0.5 s 30 A
Breaking capacity when the control-circuit time constant L/R<40 ms, at U< 48/110/220 V DC
≤0.5 A/≤0.1 A/≤0.04 A
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
36 ABB
Table 6. Power output relays without TCS function
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 8 A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit time constant L/R<40 ms, at U< 48/110/220 V DC
≤1 A/≤0.3 A/≤0.1 A
Table 7. Power output relays with TCS function
Description Value
Rated voltage 250 V DC
Continuous contact carry 8 A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit time constant L/R<40 ms, at U< 48/110/220 V DC
≤1 A/≤0.3 A/≤0.1 A
Control voltage range 20...250 V DC
Current drain through the supervision circuit ~1.0 mA
Minimum voltage over the TCS contact 20 V DC
Table 8. Ethernet interfaces
Ethernet interface Protocol Cable Data transfer rate
100BASE-TX - CAT 6 S/FTP or better 100 MBits/s
100BASE-FX TCP/IP protocol Fibre-optic cable with LCconnector
100 MBits/s
Table 9. Fibre-optic communication link
Wave length Fibre type Connector Permitted path
attenuation1)
Distance
1300 nm MM 62.5/125 μmglass fibre core
LC <8 dB 2 km
1) Maximum allowed attenuation caused by connectors and cable together
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 37
Table 10. X8/IRIG-B and EIA-485 interface
Type Protocol Cable
Screw terminal, pin rowheader
IRIG-B Shielded twisted pair cableRecommended: CAT 5, Belden RS-485 (9841- 9844) orAlpha Wire (Alpha 6222-6230)
Screw terminal, pin rowheader
Shielded twisted pair cableRecommended: DESCAFLEX RD-H(ST)H-2x2x0.22mm2,Belden 9729, Belden 9829
Table 11. IRIG-B
Type Value Accuracy
Input impedance 430 Ohm —
Minimum input voltageHIGH
4.3 V —
Maximum input voltageLOW
0.8 V —
Table 12. EIA-485 interface
Type Value Conditions
Minimum differential driveroutput voltage
1.5 V —
Maximum output current 60 mA —
Minimum differentialreceiver input voltage
0.2 V —
Supported bit rates 300, 600, 1200, 2400,4800, 9600, 19200, 38400,57600, 115200
—
Maximum number of 650IEDs supported on thesame bus
32 —
Max. cable length 925 m (3000 ft) Cable: AWG24 or better, stub lines shall be avoided
Table 13. Serial rear interface
Type Counter connector
Serial port (X9) Optical serial port, type ST for IEC 60870-5-103 and DNPserial
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
38 ABB
Table 14. Optical serial port (X9)
Wave length Fibre type Connector Permitted path attenuation1)
820 nm MM 62,5/125 µmglass fibre core
ST 6.8 dB (approx. 1700m length with 4 db / kmfibre attenuation)
820 nm MM 50/125 µm glassfibre core
ST 2.4 dB (approx. 600m length with 4 db / kmfibre attenuation)
1) Maximum allowed attenuation caused by fibre
Influencing factors
Table 15. Degree of protection of rack-mounted IED
Description Value
Front side IP 40
Rear side, connection terminals IP 20
Table 16. Degree of protection of the LHMI
Description Value
Front and side IP40
Table 17. Environmental conditions
Description Value
Operating temperature range -25...+55ºC (continuous)
Short-time service temperature range -40...+70ºC (<16h)Note: Degradation in MTBF and HMI performanceoutside the temperature range of -25...+55ºC
Relative humidity <93%, non-condensing
Atmospheric pressure 86...106 kPa
Altitude up to 2000 m
Transport and storage temperature range -40...+85ºC
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 39
Table 18. Environmental tests
Description Type test value Reference
Cold tests operation storage
96 h at -25ºC16 h at -40ºC 96 h at -40ºC
IEC 60068-2-1/ANSI C37.90-2005(chapter 4)
Dry heat tests operation storage
16 h at +70ºC 96 h at +85ºC
IEC 60068-2-2/ANSI C37.90-2005(chapter 4)
Damp heat tests steady state cyclic
240 h at +40ºChumidity 93% 6 cycles at +25 to +55ºChumidity 93...95%
IEC 60068-2-78 IEC 60068-2-30
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
40 ABB
Type tests according to standards
Table 19. Electromagnetic compatibility tests
Description Type test value Reference
100 kHz and 1 MHz burstdisturbance test
IEC 61000-4-18, level 3IEC 60255-22-1ANSI C37.90.1-2002
• Common mode 2.5 kV
• Differential mode 2.5 kV
Electrostatic discharge test IEC 61000-4-2, level 4IEC 60255-22-2ANSI C37.90.3-2001
• Contact discharge 8 kV
• Air discharge 15 kV
Radio frequency interference tests
• Conducted, common mode 10 V (emf), f=150 kHz...80 MHz IEC 61000-4-6 , level 3IEC 60255-22-6
• Radiated, amplitude-modulated 20 V/m (rms), f=80...1000 MHz andf=1.4...2.7 GHz
IEC 61000-4-3, level 3IEC 60255-22-3ANSI C37.90.2-2004
Fast transient disturbance tests IEC 61000-4-4IEC 60255-22-4, class AANSI C37.90.1-2002
• Communication ports 4 kV
• Other ports 4 kV
Surge immunity test IEC 61000-4-5, level 3/2IEC 60255-22-5
• Communication 1 kV line-to-earth
• Other ports 2 kV line-to-earth, 1 kV line-to-line
Power frequency (50 Hz) magneticfield
IEC 61000-4-8, level 5
• 3 s 1000 A/m
• Continuous 100 A/m
Pulse magnetic field immunity test 1000A/m IEC 61000–4–9, level 5
Power frequency immunity test IEC 60255-22-7, class AIEC 61000-4-16
• Common mode 300 V rms
• Differential mode 150 V rms
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 41
Table 19. Electromagnetic compatibility tests, continued
Description Type test value Reference
Voltage dips and short interruptionscon DC power supply
Dips:40%/200 ms70%/500 msInterruptions:0-50 ms: No restart0...∞ s : Correct behaviour at powerdown
IEC 60255-11IEC 61000-4-11
Voltage dips and interruptions on ACpower supply
Dips:40% 10/12 cycles at 50/60 Hz70% 25/30 cycles at 50/60 HzInterruptions:0–50 ms: No restart0...∞ s: Correct behaviour at powerdown
IEC 60255–11IEC 61000–4–11
Electromagnetic emission tests EN 55011, class AIEC 60255-25
• Conducted, RF-emission (mainsterminal)
0.15...0.50 MHz < 79 dB(µV) quasi peak< 66 dB(µV) average
0.5...30 MHz < 73 dB(µV) quasi peak< 60 dB(µV) average
• Radiated RF-emission
30...230 MHz < 40 dB(µV/m) quasi peak, measuredat 10 m distance
230...1000 MHz < 47 dB(µV/m) quasi peak, measuredat 10 m distance
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
42 ABB
Table 20. Insulation tests
Description Type test value Reference
Dielectric tests: IEC 60255-5ANSI C37.90-2005
• Test voltage 2 kV, 50 Hz, 1 min1 kV, 50 Hz, 1 min, communication
Impulse voltage test: IEC 60255-5ANSI C37.90-2005
• Test voltage 5 kV, unipolar impulses, waveform1.2/50 μs, source energy 0.5 J1 kV, unipolar impulses, waveform1.2/50 μs, source energy 0.5 J,communication
Insulation resistance measurements IEC 60255-5ANSI C37.90-2005
• Isolation resistance >100 MΏ, 500 V DC
Protective bonding resistance IEC 60255-27
• Resistance <0.1 Ώ (60 s)
Table 21. Mechanical tests
Description Reference Requirement
Vibration response tests (sinusoidal) IEC 60255-21-1 Class 2
Vibration endurance test IEC60255-21-1 Class 1
Shock response test IEC 60255-21-2 Class 1
Shock withstand test IEC 60255-21-2 Class 1
Bump test IEC 60255-21-2 Class 1
Seismic test IEC 60255-21-3 Class 2
Product safety
Table 22. Product safety
Description Reference
LV directive 2006/95/EC
Standard EN 60255-27 (2005)
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 43
EMC compliance
Table 23. EMC compliance
Description Reference
EMC directive 2004/108/EC
Standard EN 50263 (2000)EN 60255-26 (2007)
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
44 ABB
Differential protection
Table 24. 1Ph High impedance differential protection HZPDIF
Function Range or value Accuracy
Operate voltage (20-400) VI=U/R
± 1.0% of Ir
Reset ratio >95% -
Maximum continuous power U>Trip2/SeriesResistor ≤200 W -
Operate time 10 ms typically at 0 to 10 x Ud -
Reset time 105 ms typically at 10 to 0 x Ud -
Critical impulse time 2 ms typically at 0 to 10 x Ud -
Current protection
Table 25. Four step phase overcurrent protection, 3-phase output OC4PTOC
Function Setting range Accuracy
Operate current (5-2500)% of lBase ± 1.0% of Ir at I ≤ Ir± 1.0% of I at I > Ir
Reset ratio > 95% -
Min. operating current (1-10000)% of lBase ± 1.0% of Ir at I ≤ Ir±1.0% of I at I > Ir
2nd harmonic blocking (5–100)% of fundamental ± 2.0% of Ir
Independent time delay (0.000-60.000) s ± 0.5% ±25 ms
Minimum operate time forinverse characteristics
(0.000-60.000) s ± 0.5% ±25 ms
Inverse characteristics, seetable 56, table 57 and table 58
17 curve types 1) ANSI/IEEE C37.112IEC 60255–151±3% or ±40 ms0.10 ≤ k ≤ 3.001.5 x Iset ≤ I ≤ 20 x Iset
Operate time, nondirectionalstart function
25 ms typically at 0 to 2 x Iset -
Reset time, nondirectional startfunction
30 ms typically at 2 to 0 x Iset -
Operate time, directional startfunction
50 ms typically at 0 to 2 x Iset -
Reset time, directional startfunction
35 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Impulse margin time 15 ms typically -
1) Note: Timing accuracy only valid when 2nd harmonic blocking is turned off
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 45
Table 26. Four step residual overcurrent protection EF4PTOC
Function Range or value Accuracy
Operate current (1-2500)% of lBase ± 1.0% of Ir at I < Ir± 1.0% of I at I > Ir
Reset ratio > 95% -
Operate current for directionalcomparison, Zero sequence
(1–100)% of lBase ± 2.0% of Ir
Operate current for directionalcomparison, Negative sequence
(1–100)% of lBase ± 2.0% of Ir
Min. operating current (1-10000)% of lBase ± 1.0% of Ir at I < Ir± 1.0% of I at I >Ir
Minimum operate time forinverse characteristics
(0.000-60.000) s ± 0.5% ± 25 ms
Timers (0.000-60.000) s ± 0.5% ±25 ms
Inverse characteristics, see table56, table 57 and table 58
17 curve types 1) ANSI/IEEE C37.112IEC 60255–151±3% or ±40 ms0.10 ≤ k ≤ 3.001.5 x Iset ≤ I ≤ 20 x Iset
Minimum polarizing voltage, Zerosequence
(1–100)% of UBase ± 0.5% of Ur
Minimum polarizing voltage,Negative sequence
(1–100)% of UBase ± 0.5% of Ur
Minimum polarizing current, Zerosequence
(2–100)% of IBase ±1.0% of Ir
Minimum polarizing current,Negative sequence
(2–100)% of IBase ±1.0% of Ir
Real part of source Z used forcurrent polarization
(0.50-1000.00) W/phase -
Imaginary part of source Z usedfor current polarization
(0.50–3000.00) W/phase -
Operate time, non-directionalstart function
30 ms typically at 0.5 to 2 x Iset -
Reset time, non-directional startfunction
30 ms typically at 2 to 0.5 x Iset -
Operate time, directional startfunction
30 ms typically at 0,5 to 2 x IN -
Reset time, directional startfunction
30 ms typically at 2 to 0,5 x IN -
1) Note: Timing accuracy only valid when 2nd harmonic blocking is turned off.
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
46 ABB
Table 27. Thermal overload protection, two time constants TRPTTR
Function Range or value Accuracy
Base current 1 and 2 (30–250)% of IBase ± 1.0% of Ir
Operate time:
2 2
2 2ln p
b
I It
I It
æ ö-ç ÷= ×ç ÷-è ø
EQUATION1356 V1 EN (Equation 1)
I = Imeasured
Ip = load current before overloadoccursTime constant τ = (1–500)minutes
IEC 60255–8, ±5% + 200 ms
Alarm level 1 and 2 (50–99)% of heat content tripvalue
± 2.0% of heat content trip
Operate current (50–250)% of IBase ± 1.0% of Ir
Reset level temperature (10–95)% of heat content trip ± 2.0% of heat content trip
Table 28. Breaker failure protection, 3-phase activation and output CCRBRF
Function Range or value Accuracy
Operate phase current (5-200)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir
Reset ratio, phase current > 95% -
Operate residual current (2-200)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir
Reset ratio, residual current > 95% -
Phase current level for blocking ofcontact function
(5-200)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir
Reset ratio > 95% -
Timers (0.000-60.000) s ± 0.5% ±10 ms
Operate time for current detection 35 ms typically -
Reset time for current detection 10 ms maximum -
Table 29. Pole discordance protection CCRPLD
Function Range or value Accuracy
Operate value, currentasymmetry level
(0-100) % ± 1.0% of Ir
Reset ratio >95% -
Time delay (0.000-60.000) s ± 0.5% ± 25 ms
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 47
Table 30. Negative sequence based overcurrent function DNSPTOC
Function Range or value Accuracy
Operate current (2.0 - 5000.0) % of IBase ± 1.0% of Ir at I <Ir± 1.0% of I at I > Ir
Reset ratio > 95 % -
Low voltage level for memory (0.0 - 5.0) % of UBase < ± 0.5% of Ur
Relay characteristic angle (-180 - 180) degrees ± 2.0 degrees
Relay operate angle (1 - 90) degrees ± 2.0 degrees
Timers (0.00 - 6000.00) s ± 0.5% ± 25 ms
Operate time, non-directional 30 ms typically at 0 to 2 x Iset
20 ms typically at 0 to 10 x Iset
-
Reset time, non-directional 40 ms typically at 2 to 0 x Iset -
Operate time, directional 30 ms typically at 0 to 2 x Iset
20 ms typically at 0 to 10 x Iset
-
Reset time, directional 40 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset
2 ms typically at 0 to 10 x Iset
-
Impulse margin time 15 ms typically -
Dynamic overreach < 10% at t = 300 ms -
Voltage protection
Table 31. Two step undervoltage protection UV2PTUV
Function Range or value Accuracy
Operate voltage, low and high step (1–100)% of UBase ± 0.5% of Ur
Reset ratio <105% -
Inverse time characteristics for lowand high step, see table 60
- See table 60
Definite time delay, step 1 (0.00 - 6000.00) s ± 0.5% ± 25 ms
Definite time delays, step 2 (0.000-60.000) s ± 0.5% ±25 ms
Minimum operate time, inversecharacteristics
(0.000–60.000) s ± 0.5% ± 25 ms
Operate time, start function 30 ms typically at 1.2 to 0.5 x Uset -
Reset time, start function 40 ms typically at 0.5 to 1.2 xUset -
Critical impulse time 10 ms typically at 1.2 to 0.8 x Uset -
Impulse margin time 15 ms typically -
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
48 ABB
Table 32. Two step overvoltage protection OV2PTOV
Function Range or value Accuracy
Operate voltage, low and high step (1-200)% of UBase ± 0.5% of Ur at U < Ur
± 0.5% of U at U > Ur
Reset ratio >95% -
Inverse time characteristics for lowand high step, see table 59
- See table 59
Definite time delay, step 1 (0.00 - 6000.00) s ± 0.5% ± 25 ms
Definite time delays, step 2 (0.000-60.000) s ± 0.5% ± 25 ms
Minimum operate time, Inversecharacteristics
(0.000-60.000) s ± 0.5% ± 25 ms
Operate time, start function 30 ms typically at 0 to 2 x Uset -
Reset time, start function 40 ms typically at 2 to 0 x Uset -
Critical impulse time 10 ms typically at 0 to 2 x Uset -
Impulse margin time 15 ms typically -
Table 33. Two step residual overvoltage protection ROV2PTOV
Function Range or value Accuracy
Operate voltage, step 1 (1-200)% of UBase ± 0.5% of Ur at U < Ur
± 0.5% of U at U > Ur
Operate voltage, step 2 (1–100)% of UBase ± 0.5% of Ur at U < Ur
± 0.5% of U at U > Ur
Reset ratio >95% -
Inverse time characteristics for lowand high step, see table 61
- See table 61
Definite time setting, step 1 (0.00–6000.00) s ± 0.5% ± 25 ms
Definite time setting, step 2 (0.000–60.000) s ± 0.5% ± 25 ms
Minimum operate time for step 1inverse characteristic
(0.000-60.000) s ± 0.5% ± 25 ms
Operate time, start function 30 ms typically at 0 to 2 x Uset -
Reset time, start function 40 ms typically at 2 to 0 x Uset -
Critical impulse time 10 ms typically at 0 to 1.2 xUset -
Impulse margin time 15 ms typically -
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 49
Secondary system supervision
Table 34. Fuse failure supervision SDDRFUF
Function Range or value Accuracy
Operate voltage, zero sequence (1-100)% of UBase ± 1.0% of Ur
Operate current, zero sequence (1–100)% of IBase ± 1.0% of Ir
Operate voltage, negative sequence (1–100)% of UBase ± 0.5% of Ur
Operate current, negative sequence (1–100)% of IBase ± 1.0% of Ir
Operate voltage change level (1–100)% of UBase ± 5.0% of Ur
Operate current change level (1–100)% of IBase ± 5.0% of Ir
Operate phase voltage (1-100)% of UBase ± 0.5% of Ur
Operate phase current (1-100)% of IBase ± 1.0% of Ir
Operate phase dead line voltage (1-100)% of UBase ± 0.5% of Ur
Operate phase dead line current (1-100)% of IBase ± 1.0% of Ir
Table 35. Breaker close/trip circuit monitoring TCSSCBR
Function Range or value Accuracy
Operate time delay (0.020 - 300.000) s ± 0,5% ± 110 ms
Logic
Table 36. Tripping logic common 3-phase output SMPPTRC
Function Range or value Accuracy
Trip action 3-ph -
Timers (0.000-60.000) s ± 0.5% ± 10 ms
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
50 ABB
Table 37. Configurable logic blocks
Logic block Quantity with cycle time Range or value Accuracy
5 ms 20 ms 100 ms
AND 60 60 160 - -
OR 60 60 160 - -
XOR 10 10 20 - -
INVERTER 30 30 80 - -
SRMEMORY 10 10 20 - -
RSMEMORY 10 10 20 - -
GATE 10 10 20 - -
PULSETIMER 10 10 20 (0.000–90000.000) s ± 0.5% ± 25 ms for20 ms cycle time
TIMERSET 10 10 20 (0.000–90000.000) s ± 0.5% ± 25 ms for20 ms cycle time
LOOPDELAY 10 10 20
Monitoring
Table 38. Technical datacovering measurement functions:CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU
Function Range or value Accuracy
Voltage (0.1-1.5) ×Ur ± 0.5% of Ur at U£Ur
± 0.5% of U at U > Ur
Connected current (0.2-4.0) × Ir ± 0.5% of Ir at I £ Ir± 0.5% of I at I > Ir
Active power, P 0.1 x Ur< U < 1.5 x Ur
0.2 x Ir < I < 4.0 x Ir± 1.0% of Sr at S ≤ Sr
± 1.0% of S at S > Sr
Reactive power, Q 0.1 x Ur< U < 1.5 x Ur
0.2 x Ir < I < 4.0 x Ir± 1.0% of Sr at S ≤ Sr
± 1.0% of S at S > Sr
Apparent power, S 0.1 x Ur < U < 1.5 x Ur
0.2 x Ir< I < 4.0 x Ir± 1.0% of Sr at S ≤ Sr
± 1.0% of S at S > Sr
Apparent power, S Three phasesettings
cos phi = 1 ± 0.5% of S at S > Sr
± 0.5% of Sr at S ≤ Sr
Power factor, cos (φ) 0.1 x Ur < U < 1.5 x Ur
0.2 x Ir< I < 4.0 x Ir< 0.02
Table 39. Event counter CNTGGIO
Function Range or value Accuracy
Counter value 0-10000 -
Max. count up speed 10 pulses/s -
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 51
Table 40. Disturbance report DRPRDRE
Function Range or value Accuracy
Current recording - ± 1,0% of Ir at I ≤ Ir± 1,0% of I at I > Ir
Voltage recording - ± 1,0% of Ur at U ≤ Ur
± 1,0% of U at U > Ur
Pre-fault time (0.05–3.00) s -
Post-fault time (0.1–10.0) s -
Limit time (0.5–8.0) s -
Maximum number of recordings 100, first in - first out -
Time tagging resolution 1 ms See time synchronizationtechnical data
Maximum number of analog inputs 30 + 10 (external + internallyderived)
-
Maximum number of binary inputs 96 -
Maximum number of phasors in the Trip Valuerecorder per recording
30 -
Maximum number of indications in a disturbance report 96 -
Maximum number of events in the Event recording perrecording
150 -
Maximum number of events in the Event list 1000, first in - first out -
Maximum total recording time (3.4 s recording timeand maximum number of channels, typical value)
340 seconds (100 recordings) at50 Hz, 280 seconds (80recordings) at 60 Hz
-
Sampling rate 1 kHz at 50 Hz1.2 kHz at 60 Hz
-
Recording bandwidth (5-300) Hz -
Table 41. Event list DRPRDRE
Function Value
Buffer capacity Maximum number of events in the list 1000
Resolution 1 ms
Accuracy Depending on time synchronizing
Table 42. Indications DRPRDRE
Function Value
Buffer capacity Maximum number of indications presented for singledisturbance
96
Maximum number of recorded disturbances 100
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
52 ABB
Table 43. Event recorder DRPRDRE
Function Value
Buffer capacity Maximum number of events in disturbance report 150
Maximum number of disturbance reports 100
Resolution 1 ms
Accuracy Depending on timesynchronizing
Table 44. Trip value recorder DRPRDRE
Function Value
Buffer capacity
Maximum number of analog inputs 30
Maximum number of disturbance reports 100
Table 45. Disturbance recorder DRPRDRE
Function Value
Buffer capacity Maximum number of analog inputs 40
Maximum number of binary inputs 96
Maximum number of disturbance reports 100
Maximum total recording time (3.4 s recording time and maximum numberof channels, typical value)
340 seconds (100 recordings) at 50 Hz280 seconds (80 recordings) at 60 Hz
Table 46. Station battery supervision SPVNZBAT
Function Range or value Accuracy
Lower limit for the battery terminalvoltage
(60-140) % of Ubat ± 1.0% of set battery voltage
Reset ratio, lower limit <105 % -
Upper limit for the battery terminalvoltage
(60-140) % of Ubat ± 1.0% of set battery voltage
Reset ratio, upper limit >95 % -
Timers (0.000-60.000) s ± 0.5% ± 110 ms
Table 47. Insulation gas monitoring function SSIMG
Function Range or value Accuracy
Pressure alarm 0.00-25.00 -
Pressure lockout 0.00-25.00 -
Temperature alarm -40.00-200.00 -
Temperature lockout -40.00-200.00 -
Timers (0.000-60.000) s ± 0.5% ± 110 ms
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 53
Table 48. Insulation liquid monitoring function SSIML
Function Range or value Accuracy
Alarm, oil level 0.00-25.00 -
Oil level lockout 0.00-25.00 -
Temperature alarm -40.00-200.00 -
Temperature lockout -40.00-200.00 -
Timers (0.000-60.000) s ± 0.5% ± 110 ms
Table 49. Circuit breaker condition monitoring SSCBR
Function Range or value Accuracy
Alarm levels for open and close traveltime
(0-200) ms ± 0.5% ± 25 ms
Alarm levels for number of operations (0 - 9999) -
Setting of alarm for spring chargingtime
(0.00-60.00) s ± 0.5% ± 25 ms
Time delay for gas pressure alarm (0.00-60.00) s ± 0.5% ± 25 ms
Time delay for gas pressure lockout (0.00-60.00) s ± 0.5% ± 25 ms
Metering
Table 50. Pulse counter PCGGIO
Function Setting range Accuracy
Cycle time for report of countervalue
(1–3600) s -
Table 51. Function for energy calculation and demand handling ETPMMTR
Function Range or value Accuracy
Energy metering MWh Export/Import, MVArhExport/Import
Input from MMXU. No extra error at steady load
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
54 ABB
Station communication
Table 52. Communication protocol
Function Value
Protocol TCP/IP Ethernet
Communication speed for the IEDs 100 Mbit/s
Protocol IEC 61850–8–1
Communication speed for the IEDs 100BASE-FX
Protocol DNP3.0/TCP
Communication speed for the IEDs 100BASE-FX
Protocol, serial IEC 60870–5–103
Communication speed for the IEDs 9600 or 19200 Bd
Protocol, serial DNP3.0
Communication speed for the IEDs 300–19200 Bd
HardwareIED
Table 53. Degree of protection of rack-mounted IED
Description Value
Front side IP 40
Rear side, connection terminals IP 20
Table 54. Degree of protection of the LHMI
Description Value
Front and side IP40
Dimensions
Table 55. Dimensions of the IED - 3U full 19" rack
Description Value
Width 442 mm (17.40 inches)
Height 132 mm (5.20 inches), 3U
Depth 249.5 mm (9.82 inches)
Weight box 10 kg (<22.04 lbs)
Weight LHMI 1.3 kg (2.87 lbs)
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 55
Inverse time characteristics
Table 56. ANSI Inverse time characteristics
Function Range or value Accuracy
Operating characteristic:
( )1= + ×
-
æ öç ÷ç ÷è ø
P
At B k
I
EQUATION1249-SMALL V1 EN
I = Imeasured/Iset
k = (0.05-999) in steps of 0.01 -
ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0
ANSI Very inverse A=19.61, B=0.491, P=2.0
ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02, tr=0.46
ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02
ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0
ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0
ANSI Long Time Inverse A=0.086, B=0.185, P=0.02
Table 57. IEC Inverse time characteristics
Function Range or value Accuracy
Operating characteristic:
( )1= ×
-
æ öç ÷ç ÷è ø
P
At k
I
EQUATION1251-SMALL V1 EN
I = Imeasured/Iset
k = (0.05-999) in steps of 0.01 -
IEC Normal Inverse A=0.14, P=0.02
IEC Very inverse A=13.5, P=1.0
IEC Inverse A=0.14, P=0.02
IEC Extremely inverse A=80.0, P=2.0
IEC Short time inverse A=0.05, P=0.04
IEC Long time inverse A=120, P=1.0
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
56 ABB
Table 58. RI and RD type inverse time characteristics
Function Range or value Accuracy
RI type inverse characteristic
1
0.2360.339
= ×
-
t k
IEQUATION1137-SMALL V1 EN
I = Imeasured/Iset
k = (0.05-999) in steps of 0.01
RD type logarithmic inverse characteristic
5.8 1.35= - ×æ öç ÷è ø
tI
Ink
EQUATION1138-SMALL V1 EN
I = Imeasured/Iset
k = (0.05-999) in steps of 0.01
Table 59. Inverse time characteristics for overvoltage protection
Function Range or value Accuracy
Type A curve:
=- >
>
æ öç ÷è ø
tk
U U
U
EQUATION1436-SMALL V1 EN
U> = Uset
U = Umeasured
k = (0.05-1.10) in steps of 0.01 ±5% +60 ms
Type B curve:
2.0
480
32 0.5 0.035
=×
- >× - -
>
æ öç ÷è ø
tk
U U
U
EQUATION1437-SMALL V1 EN
k = (0.05-1.10) in steps of 0.01
Type C curve:
3.0
480
32 0.5 0.035
=×
- >× - -
>
æ öç ÷è ø
tk
U U
U
EQUATION1438-SMALL V1 EN
k = (0.05-1.10) in steps of 0.01
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 57
Table 60. Inverse time characteristics for undervoltage protection
Function Range or value Accuracy
Type A curve:
=< -
<
æ öç ÷è ø
kt
U U
UEQUATION1431-SMALL V1 EN
U< = Uset
U = UVmeasured
k = (0.05-1.10) in steps of 0.01 ±5% +60 ms
Type B curve:
2.0
4800.055
32 0.5
×= +
< -× -
<
æ öç ÷è ø
kt
U U
U
EQUATION1432-SMALL V1 EN
U< = Uset
U = Umeasured
k = (0.05-1.10) in steps of 0.01
Table 61. Inverse time characteristics for residual overvoltage protection
Function Range or value Accuracy
Type A curve:
=- >
>
æ öç ÷è ø
tk
U U
U
EQUATION1436-SMALL V1 EN
U> = Uset
U = Umeasured
k = (0.05-1.10) in steps of0.01
±5% +70 ms
Type B curve:
2.0
480
32 0.5 0.035
=×
- >× - -
>
æ öç ÷è ø
tk
U U
U
EQUATION1437-SMALL V1 EN
k = (0.05-1.10) in steps of0.01
Type C curve:
3.0
480
32 0.5 0.035
=×
- >× - -
>
æ öç ÷è ø
tk
U U
U
EQUATION1438-SMALL V1 EN
k = (0.05-1.10) in steps of0.01
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
58 ABB
19. Ordering for Customized IED
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functionscan only be ordered in combination with other functions and that some functions require specific hardware selections.
Product specification
Basic IED 650 platform and common functions housed in 3U 1/1 sized 19” casing
REB650 Quantity: 1MRK 006 520-AC
Option:
Customer specific configuration On request
Connection type for Analog modules
Rule: One connection type must be selected
Compression terminals 1MRK 002 960-CA
Ring lug terminals 1MRK 002 960-DA
Connection type for Power supply, Input/Output and communication modules
Rule: One connection type must be selected
Compression terminals 1MRK 002 960-EA
Ring lug terminals 1MRK 002 960-FA
Power supply module
Rule: One Power supply module must be specified
Power supply module(PSM) 48-125 VDC 1KHL178073R0001
110-250 VDC, 100–240V AC 1KHL178082R0001
Differential protection
Rule: One 1Ph High impedance differential protection must be ordered
1Ph High impedance differential protection (HZPDIF)
Qty:
1 2 3 4 5
6 7 8 9
1MRK 004 904-DA
Logic
Rule: One Tripping logic must be ordered
Tripping logic, common 3–phase output (SMPPTRC)
Qty:
1 2 3 4 5 6 1MRK 004 922-AA
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 59
Optional functionsCurrent protection
Four step phase overcurrent protection, 3–phase output(OC4PTOC)
Qty: 1MRK 004 908-BB
Four step residual overcurrent protection, zero/negativesequence direction (EF4PTOC)
Qty: 1MRK 004 908-FA
Thermal overload protection, two time constants (TRPTTR Qty: 1MRK 004 908-KA
Breaker failure protection, 3–phase activation and output(CCRBRF)
Qty: 1MRK 004 908-LA
Pole discordance protection (CCRPLD) Qty: 1MRK 004 908-NA
Negative sequence based overcurrent function(DNSPTOC)
Qty: 1MRK 004 908-TA
Voltage protection
Two step undervoltage protection (UV2PTUV)
Qty:
1 2 1MRK 004 910-AB
Two step overvoltage protection (OV2PTOV)
Qty:
1 2 1MRK 004 910-BB
Two step residual overvoltage protection (ROV2PTOV)
Qty:
1 2 1MRK 004 910-CB
Secondary system supervision
Fuse failure supervision (SDDRFUF)
Qty:
1 2 1MRK 004 914-BA
Monitoring
Station battery supervision (SPVNZBAT) Qty: 1MRK 004 925-HB
Insulation gas monitoring function (SSIMG)
Qty:
1 2 1MRK 004 925-KA
Insulation liquid monitoring function (SSIML)
Qty:
1 2 1MRK 004 925-LA
Circuit breaker condition monitoring (SSCBR) Qty: 1MRK 004 925-MA
First local HMI user dialogue language
HMI language, English IEC Always included
Additional local HMI user dialogue language
HMI language, English US 1MRK 002 940-MA
Optional hardware
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
60 ABB
Human machine interface
Rule: One must be ordered.
Display type Keypad symbol Case size
Local human machine interface (LHMI) IEC 3U 1/1 19" 1KHL160055R0001
Local human machine interface (LHMI) ANSI 3U 1/1 19" 1KHL160042R0001
Analog system
Rule: One Transformer input module must be ordered
Transformer module (TRM) 6I+4U, 1/5A,100/220V Qty: 1KHL178083R0001
Transformer module (TRM) 8I+2U, 1/5A, 100/220V Qty: 1KHL178083R0013
Transformer module (TRM) 4I, 1/5A+1I, 0.1/0.5A+5U, 100/220V Qty: 1KHL178083R0016
Transformer module (TRM) 4I+6U, 1/5A, 100/220V Qty: 1KHL178083R0003
Rule: Only one Analog input module can be ordered
Analog input module (AIM) 6I+4U, 1/5A, 100/220V Qty: 1KHL178083R5001
Analog input module (AIM) 4I, 1/5A+1I, 0.1/0.5A+5U, 100/220V Qty: 1KHL178083R5016
Binary input/output modules
Note: If analog input module (AIM) is ordered only 2 BIO modulescan be ordered
Binary input/output module (BIO) Qty: 1 2 3 4 1KHL178074R0001
Rack mounting kit
Rack mounting kit for 3U 1/1 x 19” case Quantity: 1KHL400352R0001
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 61
20. Ordering for Configured IED
GuidelinesCarefully read and follow the set of rules to ensure problem-free order management.Please refer to the available functions table for included application functions.
To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Example code: REB650*1.2-A03X00-X00-B1A5-B-A-SA-AB1-SA1B1-AA-E. Using the code of each position #1-11specified as REB650*1-2 2-3-4 4-5-6-7 7-8 8-9 9 9-10 10-11
# 1 - 2 - 3 - 4 - 5 6 - 7 - 8 - 9 - 10 - 11
REB650* - - - - - - - - -
P
osi
tion
SOFTWARE #1 Notes and Rules
Version number
Version no 1.2
Selection for position #1. 1.2
Configuration alternatives #2 Notes and Rules
High impedance busbar protection A03
ACT configuration
ABB standard configuration X00
Selection for position #2. X00
Software options #3 Notes and Rules
No option X00
Selection for postition #3 X00
First HMI language #4 Notes and Rules
English IEC B1
Selection for position #4.
Additional HMI language #4
No second HMI language X0
Selection for position #4. B1 X0
Casing #5 Notes and Rules
Rack casing, 3U 1/1 x 19" D
Selection for position #5. D
Mounting details with IP40 of protection from the front #6 Notes and Rules
No mounting kit included X
Rack mounting kit for 3U 1/1 x 19" H
Selection for position #6.
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
62 ABB
Connection type for Power supply, Input/output andCommunication modules
#7 Notes and Rules
Compression terminals S
Ringlug terminals R
Power supply
Slot position:
pPSM
100-240V AC, 110-250V DC, 9BO A
48-125V DC, 9BO B
Selection for position #7.
Human machine interface #8 Notes and Rules
Local human machine interface, OL8000, IEC3U 1/1 x 19", Basic
E
Detached LHMI
No detached mounting of LHMI X0
Selection for position #8. E X0
Connection type for Analog modules #9 Notes and Rules
Compression terminals S
Ringlug terminals R
Analog system
Slot position: p2
Transformer module, 6I + 4U, 1/5A, 100/220V A1 Included as basic
Slot position: p4
Analog input module, 6I + 4U, 1/5A, 100/220V B1 Included as basic
Selection for position #9. A1 B1
Binary input/output module #10 Notes and Rules
Slot position (rear view) p5 p6 p5 basic, p6 optional
Available slots in 1/1 case
No board in slot A X
Binary input/output module 9 BI, 3 NO Trip, 5 NOSignal, 1 CO Signal
A A
Selection for position #10. A
Communication and processing module #11 Notes and Rules
Slot position (rear view)
pCO
M
12BI, IRIG-B, RS485, Ethernet, LC optical, ST serial F
Selection for position #11. F
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 63
21. Ordering for Accessories
External resistor unit
High impedance resistor unit 1-ph with resistor and voltagedependent resistor for 20-100V operating voltage
Quantity:
1 2 3 4 5
6 7 8 9
RK795101-MA
High impedance resistor unit 3-ph with resistor and voltagedependent resistor for 20-100V operating voltage
Quantity:
1 2 3 RK795101-MB
High impedance resistor unit 1-ph with resistor and voltagedependent resistor for 100-400V operating voltage
Quantity:
1 2 3 4 5
6 7 8 9
RK795101-CB
High impedance resistor unit 3-ph with resistor and voltagedependent resistor for 100-400V operating voltage
Quantity:
1 2 3 RK795101-DC
Configuration and monitoring tools
Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA
LED Label special paper A4, 1 pc Quantity: 1MRK 002 038-CA
LED Label special paper Letter, 1 pc Quantity: 1MRK 002 038-DA
Manuals
Note: One (1) IED Connect DVD containing user documentationOperation manualTechnical manualInstallation manualCommissioning manualApplication manualCommunication protocol manual, DNP3Communication protocol manual, IEC61850-8-1Communication protocol manual, IEC60870-5-103Cyber security deployment guidelinesType test certificateEngineering manualPoint list manual, DNP3Connectivity packages and LED label template is always included for each IED
Rule: Specify additional quantity of IED Connect DVD requested
User documentation Quantity: 1MRK 003 500-AA
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
64 ABB
Rule: Specify the number of printed manuals requested
Operation manual IEC Quantity: 1MRK 500 095-UEN
Technical manual IEC Quantity: 1MRK 505 277-UEN
Commissioning manual IEC Quantity: 1MRK 505 278-UEN
Application manual IEC Quantity: 1MRK 505 276-UEN
Communication protocol manual, DNP3 IEC Quantity: 1MRK 511 257-UEN
Communication protocol manual, IEC 61850-8-1 IEC Quantity: 1MRK 511 258-UEN
Communication protocol manual, IEC 60870-5-103 IEC Quantity: 1MRK 511 259-UEN
Engineering manual IEC Quantity: 1MRK 511 261-UEN
Installation manual IEC Quantity: 1MRK 514 015-UEN
Point list manual, DNP3 IEC Quantity: 1MRK 511 260-UEN
Cyber Security deployment guidelines IEC Quantity: 1MRK 511 268-UEN
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
Country: End user:
Station name: Voltage level: kV
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
ABB 65
Related documents
Documents related to REB650 Identity number
Application manual 1MRK 505 276-UEN
Technical manual 1MRK 505 277-UEN
Commissioning manual 1MRK 505 278-UEN
Product Guide, configured 1MRK 505 279-BEN
Type test certificate 1MRK 505 279-TEN
Application notes for Circuit Breaker Control 1MRG006806
650 series manuals Identity number
Communication protocol manual, DNP3 1MRK 511 257-UEN
Communication protocol manual, IEC 61850–8–1 1MRK 511 258-UEN
Communication protocol manual, IEC 60870-5-103 1MRK 511 259-UEN
Cyber Security deployment guidelines 1MRK 511 268-UEN
Point list manual, DNP3 1MRK 511 260-UEN
Engineering manual 1MRK 511 261-UEN
Operation manual 1MRK 500 095-UEN
Installation manual 1MRK 514 015-UEN
Busbar protection REB650 1MRK 505 279-BEN -
Product version: 1.2
66 ABB
67
Contact us
ABB ABSubstation Automation ProductsSE-721 59 Västerås, SwedenPhone +46 (0) 21 32 50 00Fax +46 (0) 21 14 69 18
www.abb.com/substationautomation
1MR
K 5
05 2
79-B
EN
-©
Cop
yrig
ht 2
012
AB
B. A
ll rig
hts
rese
rved
.