Bureau of Facilities and Assets Management Brown Building 1 Gamewell-Flexalert Yes Remote Annunciator 109 Smoke Detectors 27 Pull Stations 15 Heat Detectors 9 Duct Smoke Detectors 13 Tamper Switches 10 Sprinkler Flow Switches 9 Duct Smoke Remotes Y Remote Annunciator Batteries Location Room 150 (Lobby Area) 2 Interstate BSL 1146 12v 26Ah 2 Interstate BSL 1161 12v 44Ah Brown Garage 1 Micron-FX2000 Yes Remote Annunciator 7 Smoke Detectors 60 Horn/Strobes 4 Pull Stations Y Remote Annunciator Batteries Location 4 th Floor Elevator Lobby Closet 4 Interstate BSL 1075 12v 8Ah 2 Interstate SLA1156 12v 35Ah Dolloff Building 1 Notifier DR-A4R Yes Remote Annunciator 100 Smoke Detectors 117 Horn/Strobes 20 Pull Stations

Bureau of Facilities and Assets Management 2070-18... · 25-07-2017 · MMX-1 Monitor Modules for Sprinkler Devices/Elevator Shunt Supervision 16 BGX-101L Addressable Manual Pull

Embed Size (px)

Citation preview

Bureau of Facilities and Assets Management

Brown Building

1 Gamewell-Flexalert Yes Remote Annunciator109 Smoke Detectors27 Pull Stations15 Heat Detectors9 Duct Smoke Detectors13 Tamper Switches10 Sprinkler Flow Switches9 Duct Smoke RemotesY Remote Annunciator

BatteriesLocation Room 150 (Lobby Area)

2 Interstate BSL 1146 12v 26Ah 2 Interstate BSL 1161 12v 44Ah

Brown Garage

1 Micron-FX2000 Yes Remote Annunciator7 Smoke Detectors60 Horn/Strobes4 Pull StationsY Remote Annunciator

BatteriesLocation 4th Floor Elevator Lobby Closet

4 Interstate BSL 1075 12v 8Ah 2 Interstate SLA1156 12v 35Ah

Dolloff Building

1 Notifier DR-A4RYes Remote Annunciator100 Smoke Detectors117 Horn/Strobes20 Pull Stations

2 Tamper Switches1 Sprinkler Flow Switch1 Low Air SwitchY Remote Annunicator

BatteriesLocation 1st Floor Main Lobby

2 Interstate BSL1146 12v 26Ah Location Level 2 Power Path Wheellock (& Level 3)

2 Embassy 12v 7.5Ah

Laundry Building

1 Simplex 40014 Horn/Strobes7 Pull Stations44 Heat Detectors

BatteriesLocation Level 2 Top of Steps

4 PM6100F1 12v 10Ah

Liberty House

1 Simplex 40018 Smoke Detectors3 Horn/Stobes4 Pull Stations13 Heat Detectors

BatteriesLocation Inside Main Entrance on Left

2 PM1270 12v 7.2Ah

Main Building / Bancroft Annex

1 Main Simplex 4001U Sub Panel (2) IDNET NAC Extenders (4)Yes Remote Annunciator222 Smoke Detectors

327 Horn/Strobes110 Pull Stations72 Heat Detectors23 Tamper Switches13 Sprinkler Flow Switches8 Low Air SwitchesY Remote Annunciator

BatteriesLocation 1st Floor Control Room

4 Werker WKDC12 – 55P 12v 55Ah Location Main Building Lobby

2 Werker 12v 12AhLocation Hallway outside Room 218N

2 PM12120F2 12v 12Ah2 Werker W19A12-18NB 12v 18 AH

Location Across from Room 215 South2 WKA12-12FZ 12v 12Ah

Location Plumbing Shop Entrance2 WKA12-12FZ 12v 12Ah

Location Main Lobby2 PM12260FZ 12v 26Ah

Thayer Building

1 Simplex 4001120 Smoke Detectors71 Horn/Strobes39 Pull Stations5 Heat Detectors5 Tamper Switches4 Sprinkler Flow Switches1 Low Air Switch

BatteriesLocation Basement (room w/hot water tanks)

4 PM Battery PM1233ou1 12V 33Ah

Transportation Building1 Simplex 40011 Smoke Detectors5 Horn/Strobes6 Pull Stations26 Heat Detectors

BatteriesLocation Bay 1 of Garage

3 PM6100F1 12v 10Ah

Warehouse

1 Simplex 400541 Smoke Detectors27 Horn/Strobes10 Pull Stations4 Heat Detectors

BatteriesLocation Main Lobby

2 Ultratech 12v 18Ah

Philbrook1 FX2000 1 Mircom Inx 10 Amp NAC 12 Pull stations67 Smoke Detector10 Heat Detectors22 Horn/strobes

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name DAS BFAM

Facility Location & Address to be serviced

Brown Building 129 Pleasant St. Concord NH 03301

Hours of Operation of Facility 7:30 to 4:00

Remit Address for Invoices State of NH BFAM 129 Pleasant St. Concord NH 03301 Facility Contact Person Douglas Burnham

E-mail [email protected] Telephone 603 -271-9555

Current Vendor Simplex Date of Last Inspection 10/2017

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Gamewell Flexalert

Model of panel Flexalert Date of installation 1998 Number of subpanels, if applicable 0 Number of pre-action panels, if applicable 0 Number of devices that feeds the panels Number of pull stations 27 Number of heat detectors 15 Number of smoke detectors 109 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units 105

Duct Detectors 9 C/O Detectors 0 Door Holders 0 NACs/power supplies 2

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable X

Indicate the frequency of inspection services you would like Annually at a rate of 100% X

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like visuals

tested. 7:30 to 4:00

Additional Information, if necessary

Ansul system reports to Gamewell panel

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name DAS BFAM

Facility Location & Address to be serviced

Brown Building Garage 129 Pleasant St Concord NH 03301

Hours of Operation of Facility 7:30 To 4:00

Remit Address for Invoices State of NH BFAM 129 Pleasant St Concord NH 03301 Facility Contact Person Douglas Burnham

E-mail [email protected] Telephone 603-271-9555

Current Vendor Simplex Date of Last Inspection 10/2017

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Micron

Model of panel FX2000 Date of installation 2013 Number of subpanels, if applicable 1 Number of pre-action panels, if applicable 0 Number of devices that feeds the panels Number of pull stations 15 Number of heat detectors 2 Number of smoke detectors 7 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units 60

Duct Detectors 0 C/O Detectors 0 Door Holders 0 NACs/power supplies 2

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable X

Indicate the frequency of inspection services you would like Annually at a rate of 100% X

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 7:30 to 4:00

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Manchester Community College

Facility Location & Address to be serviced

1066 Front st Manchester NH 03102

Hours of Operation of Facility 7AM TO 11PM

Remit Address for Invoices 1066 Front St Manchester NH 03102 Facility Contact Person Joshua Murphy

E-mail [email protected] Telephone 603-703-8484

Current Vendor Interstate Electric Date of Last Inspection 7/25/2017

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Notifier NFS-320

Model of panel Notifier NFS-320 Date of installation UNKNOWN Number of subpanels, if applicable 2 Number of pre-action panels, if applicable 1 Number of devices that feeds the panels 835 Number of pull stations 52 Number of heat detectors 25 Number of smoke detectors 243 Number of battery backups 3

Please include the quantity of the following peripherals: Audio-Visual Units 492

Duct Detectors 21 C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional 1

Addressable 2

Indicate the frequency of inspection services you would like Annually at a rate of 100% 1

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested.

Additional Information, if necessary

CARROLL COUNTY COURT SOUTHERN (Ossipee)

FIRE ALARM:

1 Fire Control Instrument (FCI) 7100 Series

1Control Panel (2 GENESIS NP12-12T - 12V/12 Ah Batteries) (2 GENESIS NP12-12T - 12V/12 Ah Batteries) (2 CASIL CAT050 - 12V/25Ah Batteries)

22 Manual Pull Stations99 Photo Smoke Detectors4 Duct Smoke Detectors

47 Audio/Visual Signal Devices54 Visual Only Signal1 Remote Annuciator

CONWAY CIRCUIT COURT

FIRE ALARM:

1 Fire Alarm Panel (Firelite)Sensiscan 10002-12 volt batteries10 zones

5 Horns 4 Strobes4 Manual Pull Stations

29 Smoke Detectors2 Duct Smoke Detectors1 Remote Annuciator

CONCORD CIRCUIT COURT

FIRE ALARM:

1 4100-8201 - Fire Alarm Control Panel w/ Audio

Containing:1 4100-7001 - CPU Class ‘B’

2 4100-5001 - Zone Module 8 PT Class ‘B’

1 4100-4001 - Signal module 2 CKT class ‘B’ w/o Suppression

1 4100-0210 - Single Channel Audio Control1 4100-0207 - 100 Watt Amplifier 120 volt 70 volt1 4100-0204 - Microphone Enclosure

1 4100-0206 - Redundant Tone Generator1 4100-0223 - Custom Message from Archive1 4100-0302 - 24 Point Graphic I/O1 4100-0404 - 8/16 Switch/Red-Green LED Module1 4100-0412 - 1 Channel Audio Control Switch2 4100-2002 - 4 Unit Package Size2 Duracell Ultra Batteries 12V 55AH1 2081-9212 - Battery Shelf for 2081-92111 2975-9156 - Box/2 Unit for 2400 Beige

22 9202-9732 - Speaker 4” Red ¼, ½, 1, 2 Watt22 4903-9101 - Audible Visual 24 VDC Xenon/Fire13 2099-9201 - Manual Station Single Action1 2095-9011 - Local Energy Master Box M34-561 2095-9010 - Fire Box Pendant Lamp1 2095-9041 - F/A Gas Tube LT Arrester

40 2098-9201 - Photoelectric Smoke Detector40 2098-9637 - Smoke Detector Base4 2098-9649 - Duct Housing 2 or 4 wire4 2098-9201 - Photoelectric Smoke Detector4 2098-9811 - Baffle for 2098-92014 2098-9798 - Sampling Tube 73”

4 2098-9806 - LED Alarm Indicator w/ Test key Switch

92 2098-9439 - Rate of Rise and Fixed Temperature Heat Detector 135 Degrees

5 2098-9411 - 135 Degrees Fixed Temperature Heat Detector

2 2088-9505 - 24 VDC Door Release FM998P1 XL-8 - Graphic Annunciator

2 2098-9461 - 200 Degrees Fixed Temperature Heat Detector

COOS COUNTY SUPERIOR COURT

FIRE ALARM:

1 Notifier Model AFP-400 Analog Addressable Voice Fire Alarm System

1

AFP-400 Addressable/Voice Fire Alarm Control Panel, Voice Command Center with Microphone, Voice Message Chip, LCD-80 Display, AA-30 Audio Amplifier with Speaker Circuits Main Power Supply Cabinet with Door, Battery Charger with Sealed Batteries.

2 PS12150 Battery Sets For FACP6 PS1270 Batter Set For FCPS-242 PS1270 Battery Set For Pre Action Panel1 LCD 80 Annunciator

59 SDX-551 Addressable Photoelectric Smoke Detectors with BX-501 Bases

4 FDX 551 Addressable Heat Detectors with BX-501 Bases (ELV Shunt with CMX and MR101C Relays)

3 DHX-501 Addressable Duct Detectors with Sampling Tubes, Remote Test Station and Smoke Detector Heads

8 MM-2 Monitor Modules for Grouped Conventional Devices

40 2451 Photoelectric Smoke Detectors with B401B Bases

11 MMX-1 Monitor Modules for Sprinkler Devices/Elevator Shunt Supervision

16 BGX-101L Addressable Manual Pull Stations21 CMX-2 For Auxiliary Control Functions

1 X HVAC Interface1X Security System Interface8 X Speaker Circuits4 X Elevator Recall, 2 Primary, 2 Alternate Floor3 X FCPS/Strobe Interface4 X Elevator Shunt

4 MR101C Control Relays (ELV Shunt)

3 FCPS 24 Audio/Visual Power Supply with Batteries, 6 Signal Circuits

92 Wheelock E-70 SL-24-VFR/E-70 SLM-24-VFR ADA Compliant Speaker Strobes

1 Gentex WGMS 4-/75 WR Weatherproof Horn Light with Weatherproof Back Box

1System RP1001 Fire Alarm Control Panel for Sprinkler Preaction Function. 1 Waterflow Zone, 1 Supervisory zone, 2 Conventional Detector zones

7 HD 603 135 Degree Heat Detectors5 HD 601 135 Rate of Rise Heat Detectors

DERRY CIRCUIT COURT

FIRE ALARM:

1 MFA Fire Alarm Control Panel Series 7200 (FCI Model # FC-72 Serial # 116247)

2 12V 18 AH Simplex Rechargeable Lead Acid Batteries

1 King Fisher Model FRI Annunciator1 MFA Fire Announcer

10 Audio Visual30 Smoke Detectors5 Pull Stations

29 Photo Smoke Detectors1 Duct Smoke Detectors3 Visual Only5 Audio Visual Signal Devices

DOVER CIRCUIT COURT

FIRE ALARM:

1 7100 FCI Panel1 Dialer Battery 12 V 7.5 AH 2 AFP-400 Notifier Batteries 12V 12 AH9 Double action pull stations

47 Strobes5 Thermal heat detectors

197 Smoke detectors

FRANKLIN CIRCUIT COURT

FIRE ALARM:

1 FCI FC-72 Series Alarm Panel1 Masterbox Gamewell #M 34-922 12V 18 AH Batteries2 Simplex 2098-9805 Duct Smoke Detectors

10 Simplex 4904/9001 Horn/Strobe Units3 Simplex 2099/9102 Simplex Pull stations1 Flowswitch4 Tamper Switches2 Smoke Detector1 Simplex 4602-9102RCU Remote Annunciator

HILLSBOROUGH COUNTY COURT SOUTH (NASHUA)

FIRE ALARM:

1 Notifier AM 2020 Basic Control PanelContains:a. CPU 2020 Central Processor Unitb. DIA-1 Display Interface Assemblyc. LIB-200 Loop Interface Boardd. MPS-24 Main Power Supplye. ICA-4 Interconnect Board and Chassisf. BP-1 Battery Panel

1 SIB-64 - Serial Interface Board4 LIB-200 - Loop Interface Boards1 ICA-4 - Interconnect Board and Chassis2 DP-2 - Dress Panel1 CRT-1 - Keyboard and Monitor1 P-80 - Printer2 PS12600 - 12 Volt, 55 amp hour batteries1 Remote Annunciator alarm and trouble display1 R45-24 - Battery Charger

112 SDX-551 - Intelligent Photoelectric Detectors161 FDX-551 - Intelligent Thermal Detectors

273 BX-501 - Intelligent Device Bases25 BGX102 - Addressable Manual Stations55 601 - Rate of Rise Heat Detectors17 DH2851DC - Duct Smoke Detectors17 RM851DH - Remote Test Stations17 PST851DH-3 - Sample Tubes17 A77-716-02 - End of Line Supervision Relays

6 603 - 135 Degrees Fixed Temperature Heat Detectors

4 604 - 200 Degrees Fixed Temperature Heat Detectors

35 MMX-1 - Monitor Modules13 CMX-1 - Control Modules5 ISO-X - Isolator Modules

57 554-2917 - Speaker-Strobe17 Relay Assemblies1 AE-1 - Audio Evac Control Assembly1 ATU/NY - Automatic Time Sequencer1 SBT-1 - Power Supervision Module1 ABS - Audio Buss Selector Module1 AFT - Amplifier Fail Transfer Module1 SLE - Speaker Loop Expander1 SW/BK - Switch Bank and Annunciator Module1 MCP - Microphone Control Panel

1 Gamewell - Local Energy Trip Flush Mounted Master Box

1 Digital Transmitter8 ZSR - Speaker Zone Cards2 SUP-2 - Supervisory Cards1 AVM-10 - Audio Visual Module8 AVC-1 - Audio Visual Cards2 FAX-120 - 120 Watt Amplifiers1 REC-2 - Equipment Rack1 LE-5 - Lobby Enclosure1 BL-3 - Blank Strip - 3"1 BR-175 - Blank Strip - 1.75"1 PSM-204A - Power Supply1 BCP - Chassis for Power Supply1 R-45-24 - Power Supply Charger1 LA-55 - 12 Volt - 55 amp hour

1 TM-9 - Slow Whoop Zone Module4 BR-35 - Blank Strip - 3.5"

Hillsborough County Court North (Manchester) 1 NFS-640 Fire Alarm Control Panel

10 Batteries 12V 7 AH (2 each in the five booster panels)

1 SK5104 Digital Communicator1 AES Radio Transmitter5 PS-8 Booster Panels1 LCD-80 Remote Annunciator

106 FSP Smoke Detectors8 FST Heat Detectors8 Co-12/24T Carbon Monoxide Detectors

13 NBG12LX Manual Pull Stations13 DNR w/RTS151 Duct Smoke Detectors23 Remote LED Indicators118 SPSR Speaker Strobe Units80 SR Selectiable Candelas2 500P Exterior Strobes1 RM-1 Remote Microphone w/Switches

BatteriesLocation: Main Electrical Room (off the general mechanical room)

2 YUASA Model No. NP24-12B 12v 24Ah1 Power Patrol Model No. SEC1075 12v 7AH

JAFFREY-PETERBOROUGH CIRCUIT COURT

FIRE ALARM:

1 7100 FCI Panel2 Duracell Batteries (12-35-C 35 AH)9 Double Action pull stations

47 Strobes4 Thermal Heat Detectors

37 Smoke detectors

LACONIA CIRCUIT COURT

FIRE ALARM:

2 Fire Panels-GE EST 32 Batteries, Genesis NP55-12B 12V 55 AH 8 Heat detectors

49 Smoke detectors 6 Duct smoke detectors13 Pull stations60 Strobes/lights

LEBANON CIRCUIT COURT

FIRE ALARM:

1 System 500 Fire Alarm Control Panel with Cabinet, Audio-Visual Power Supply, Initiating Circuit Module-IZ-4

2 Battery Sets for Panel, PS 12120

8 2400 2 Wire Photoelectric Smoke Detectors with Base

4 BNG Manual Fire Alarm Stations

5DH400ACDCP 4 Wire Duct Smoke Detectors with Photoelectric Sensor Heads, Remote Test Switches and Sampling Tubes

9 SHG-24-1575WR Audio Visual Horn Strobes, ADA Compliant

12 GX90S-4-1575WR Audio Visual Horn Strobes, ADA Compliant

2 FM Series 24 VDC Magnetic Door Holders1 Gamewell Master Box

MANCHESTER CIRCUIT COURT

FIRE ALARM:

1 EST #3 Main Panel1 Subpanel (Powerpath & Wheelock)1 EST Auxillary Panel1 Outside Strobe1 Outside Annunciator2 12V 7 AH Batteries4 12V 35 AH Batteries

89 Smoke Detectors25 In-duct Smoke Detectors4 In-duct Smoke Detection Stations

34 Manual Pull Stations12 Heat Detectors40 Horn/Strobes

MERRIMACK CIRCUIT COURT

FIRE ALARM:

1 Notifier Alarm Panel with associated internal equipment

1 Notifier Annunciator Alarm Panel

2 Notifier Strobe Booster sub-panels with all equipment and batteries

103 Smoke Detectors75 Horn/Strobe Evacuation Devices2 In-Duct smoke detectors2 In-Duct Smoke Detection Stations 9 Manual Pull Stations

PLYMOUTH CIRCUIT COURT

FIRE ALARM:

1 Hochiki HCP1000 fire alarm control panel 1 Hochiki HRM1008 relay expander card2 55AH 12V battery

1 Evax 50 Voice evacuation panel with 4 zone splitters

2 10AH 12V battery

1 Silent Knight #5495 Aux. power supply2 10AH 12V battery

1 2080-9024 Digital Alarm Communication Transmitter

2 2080-9022 Cords to RJ31X1 2098-9649 Duct Detector Housing1 2098-9201 Photoelectric Smoke Detector1 2098-9811 Baffle for 2098-92011 2098-9806 Remote Alarm Indicator/Test Switch1 2098-9797 Sampling Tube 49”

20 2098-9201 Photoelectric Smoke Detectors14 2098-9211 Smoke Detector Base 2-Wire6 2098-9536 Smoke Detector Base 4-Wire with Relay

1 4098-9402 Heat Detector 135 Degrees Rate of Rise

9 4098-9403 Heat Detector 200 Degrees Fixed

7 2099-9756 Double Action, Push Type, Manual Pull Stations

1 2904-9109 SL-5 Strobe Light43 4903-9301 Speaker/Strobe Units 15 CD Red3 4905-9914 Synchronized Flash Modules

PORTSMOUTH CIRCUIT COURT

FIRE ALARM:

1 FCI Fire alarm control panel2 Batteries AM12-122 Batteries 12V 12AH1 Remote annunciator 10 zone1 Gamewell master box – exterior1 Exterior horn/strobe evacuation device

10 Interior horn/strobe evacuation devices62 Heat detectors6 Smoke/heat detectors8 Manual pull stations

ROCHESTER CIRCUIT COURT

FIRE ALARM:

1 4002-8001 - Fire Alarm Control Panel

Containing:1 4002-6001 - Input power 120 VAC1 4002-7002 - CPU Class "A"2 4002-0102 - Zone Disconnect module 4 PT1 4002-2001 - 2 Unit Package

1AL602ULADA - NAC Power Extender w/2 12 Volt 12AH batteries

1 PC 1864 - Alarm Dialer Panel2 SLA 1105 - 12 Volt 12AH Batteries8 2099-9201 - Manual Station Single Action7 2098-9201 - Photoelectric Smoke Detectors5 2098-9637 - Smoke Detector Base3 2098-9738 - DET/ACC Relay SPDT2 2098-9649 - Duct Mounted Smoke Detectors2 2098-9797 - Sampling Tubes for Duct Smoke Detectors2 2098-9811 - Baffle

22098-9806 - Red Alarm LED Indicator w/Test Switch (for duct detector testing)

7 2098-9442 - 200 Degree Fixed Temperature Heat Detector28 4903-9239 - Audible/Visible Unit (Horn/Strobes)

5GT-904-1321-2 - Commander-3 24VDC Selectable CD Strobe (Horn/Strobe)

1 4602-9102 - Serial Annunciator RCU5 Visual Strobe Only (Located in Restrooms)

ROCKINGHAM COUNTY COURT

FIRE ALARM:

159 Smoke Detectors19 In-duct Smoke Detectors32 Manual Pull Stations200 Heat Detectors1 EST Panel IRC-36 Batteries 12V 44 AH AGM

ADMINISTRATIVE OFFICE OF THE COURTS

FIRE ALARM:

1 Fire Alarm Control Panel 8 IDC 4 NAC red1 2 IDC & 2 NAC Relay Module Class B1 8 Point I/O Module1 City Circuit Module1 Power Distribution Module1 Class A adapter Module2 10 Amp Hour Batteries1 Gamewell Master Box M34-921 Red Strobe Light1 Green Strobe Light1 Annunciator8 Pull Stations12 Audio Visual Units 24 VDC 15 CD Red4 Visual Only 24 VDC 15 CD red4 Low Profile Photoelectric Smoke Detectors2 4 Wire Base w/Relay

BRIDGES HOUSE

FIRE ALARM:

1 GE Firefox1 FB 4600 central station digital transmitter2 Horn/Strobe4 Smoke detectors28 Heat detectors2 Manual pull stations2 12V 7.5AH batteries

EMERGENCY OPERATION CENTER (110 SMOKEY BEAR BLVD.)

FIRE ALARM:

1 Master Box #88451 FCI E3 Series Panel3 Remote Annunciators (KDU)12 Manual Stations

18 135*F/T R/R Heat Detectors11 Sprinkler Water Flow17 Sprinkler Supervisory29 Photo Electric Smoke Detector11 Photo Electric Duct Smoke Detector3 CO2 Detector10 Remote Test Station Key Operated51 Electronic Horn/Strobe4 Sirens28 Strobe Only8 12V 12 Amp Batteries #ps121202 Red Strobe2 Green Strobe1 Fixed Red Light over Knox Box

HEALTH & HUMAN SERVICES BUILDING

FIRE ALARM:

PHASE I & II:

3 Gamewell EST-3 Addressable Analog Control Panel

3 3-CPU Central Processor Module3 3-RS485 Communication Card2 3-SSCD Analog Loop Card1 3-OPS City Tie Module8 3-ZA-30 30 Watt Amplifiers1 3-LCD Display1 3-ASU/4 Audio Controller4 3-12/S2Y Switch Modules1 3-PPS/M Primary Power Supply3 3-BPS/M Booster Power Supplies1 3-CAB-21B Wall Box Red with Cat 30 Lock1 3-CAB-21D Outer Door Red With Cat 30 Lock3 3-CHAS-7 Chassis Assemblies3 PW1260 60 Amp Hour Batteries1 70970 Battery Cabinet with Cat 30-Lock1 EST-3 Addressable Analog Control Sub Panel1 3-CPU Central Processor Module1 3-RS485 Communicator Card2 3-SSDC Analog Loop Cards6 3-ZA-30 30 Watt Amplifiers1 3-LCD Display1 SAN-MIC II Remote Mic Module

4 3-12/S2Y Switch Modules1 3-PPS/M Primary Power Supply3 3-BPS/M Booster Power Supplies1 3-CAB 21B Wall Box Red w/Cat 30 Lock1 3-CAB-21D Outer Door Red with Cat 30 Lock2 PW1260 60 Amp Hour Batteries1 70970 Battery Cabinet1 PT-1 System Printer1 M34-56 Gamewell Masterbox with AC-1 Fire Alarm Pedestal1 SL-5 Red WP Beacon Light

199 SIAG-PS Photoelectric Smoke Detectors and bases

55E-70-24110W-FR Speaker Strobes 110 Candela with Surface Boxes SBB-R

20E-70-2415W-FR Speaker Strobes 15 Candela with Surface Boxes SBB-R

72 E70-2430W-FR Speaker Strobes 30 Candela with Surface Boxes SBB-R

63 E702475W-FR Speaker Strobes 75 Candela with Surface Boxes SBB-R

18 RS2415W-FR Strobes 15 Candela with SHBB-R Surface Back Boxes

39 SIGA-278 Pull Stations with 276-RSB Surface boxes and Cat 30 Locks

26 SIGA-DH Duct Smoke Detectors26 SIGA-PS Smoke Detectors26 SIGA-DTS Remote Test Switches26 SIGA-CR Control Modules26 SIGA-LED Indication Lights26 6261-003 Sampling Tubes5 SIGA-CR Control Modules5 SIGA-CT1 Monitor Modules4 SD-240 Beam Smoke Detectors with Receivers17 SIGA-CR Control Module Damper Controls24 SIGA-CR Control Modules/Elevator Recall6 #624 200 Degree Fixed Heat Detectors for Elevator Shafts18 DSM-12/24R Synchronizing Modules

LABS:

4 3-CAB21B - Wall Box for 3 3-CHAS711 3-CAB21DR - Red Door Package for 3-CAB21B

12 3-CHAS7 - Mounting Chassis For 7 LRM or 1 CPU, 1 monitor and 4 LRM

4 3-CPU1 - Main Control for FACP or Network Node4 3-LCD - Main Display for FACP or Network Node4 3-PPS/M - Primary Power Supply w/Monitor Module8 3-BPS/M - Booster Power Supply w/Monitor Module

4 3-SSDC - Single Analog/Addressable Signature Loop Controller

18 3-ZA20A - 20 Watt Class “A/B” Network Comm Module2 3-REMICP - Panel Mount Remote Microphone4 3-RS485 - RS-485 Class “A/B” Network Comm Module8 DCS-50L - 50 AH Batteries4 BCA - Battery Cabinet

231 SIGA-PS - Analog/Addressable Photo Smoke Detector Head

40 SIGA-HFS - Analog/Addressable 135 Fixed Temp Detector Head

200 SIGAA-SB - Analog/Addressable Standard Detector Base

6 SIGA-DH - Duct Housing for Analog/Addressable Smoke Detector

6 SIGA-PS - Analog/Addressable Photo Smoke Detector Head

6 SIGA-SB - Analog/Addressable Standard Detector Base6 SIGA-DTS - Addressable Duct Function Test Module6 SIGA-CR - Addressable Form “C” Relay Module6 6261-003 - 42” Sampling Tube for SIGA-DH Duct Housing6 SIGA-LED - Remote LED for SIGA Detector40 SIGA-CT1 - Addressable Single Input Module

22 SIGA-MAB - SIGA-UIO# Addressable Class “A” Signal CKT Plug-In Module

24 SIGA-CR - Addressable Form “C” Relay Module

22 SIGA-279 - Addressable Double Action Manual Pull Station

4 SIGA-UIO6R - 6 Slot Universal Input/Output Module Board W/Riser Inputs

100 RSS24MCWFR - Multi Candela Storage

22 DSM-12/24-R - Sync Module (2) Class “B” CKT/(1) Class “A” CKT

120 E7024MCWFR - Red Speakers/Strobe1 RSSWP-2475WFR - Weather Proof Strobe1 WPSBB-R - Surface Weather Proof Box Red1 ET1010R - Weather Proof Strobe Speaker1 IOBR - Weather Proof Back Box30 1504-N5 - Flush Mounted 110 AC Door Holder

HEALTH & HUMAN SERVICES BUILDING CONT’D

PRE-ACTION SYSTEM (29 Hazen Drive):

10 Detectors in 3 Vaults L.L. West1 PS-10-2A Pressure Switch1 PS-40-2A Pressure Switch1 OSySV – 2” Valve 1 3” Deluge Valve Model E-1 1 Easy Rider Check Valve Model F-1 250PSI Flange Groove 1 Air Compressor General Air Products, Model #OL11016AC1 1Vi Viking PAR -3 Deluge B1 Pre Action Control Panel3 Speaker / Strobes Vaults

JOHNSON HALL

FIRE ALARM:

1 Simplex 4005 Main Fire Alarm Panel with Digital Transmitter SAF51 Simplex 2098-9603 Smoke Detectors76 Simplex 2098-9464 Rate of Rise Heat Detectors9 Simplex 2098-9460 Fixed Heat Detectors 135 Degrees F11 Simplex 2098-9101 Audio Visual Units9 Simplex 2099-9201 Manual Pull Stations1 Gamewell Master Box2 Remote Annunciators1 Outside Light

DEPARTMENT OF JUSTICE

FIRE ALARM:

1 Gamewell Box1 Unimode 15 Mount Back Box #4520-141 Unimode Door #4520-1111 Unimode Chassis #4520-0151 Unimode Power Supply #4520-8121 Unimode Battery Supply #4520-6381 Unimode Space Age Annunciator #M162 Unimode Water Flow Modules #4520-5291 Unimode Signal Module #4520-70125 Unimode GX 90S-4HWR Horn/Strobes13 Unimode Horn/Light Units6 Unimode Heat Detectors

80 Unimode Smoke Detectors8 Unimode 3536-611T Smoke Detectors13 Unimode Pull Stations1 Unimode Power Extender #4520-9121 Unimode Switch Module #4520-4351 Unimode Control #4520-8381 Simplex 4004 FACP

LEGISLATIVE OFFICE BUILDING

FIRE ALARM:

1 Honeywell Notifier1 Remote zone annunciator (exterior)1 Gamewell master box1 FB-4600 central station digital transmitter1 Elevator recall module

148 Heat detectors44 Smoke detectors2 Duct type smoke detectors15 Manual pull stations28 Horn/strobe evacuation devices12 Magnetic door releases2 Sprinkler water flow switches4 Gate valve tamper switches2 Gate valve tamper switches for elevator shafts

LONDERGAN HALL

FIRE ALARM:

1 Notifier NFS-3030 Main Fire Alarm Panel36 Simplex 2098-9461 Fixed Heat Detectors 200 degrees F54 Simplex 2098-9603 Smoke Detectors14 Simplex 2098-9101 Audio Visual Units32 Simplex 2098-9464 Rate of Rise Heat Detectors1 Gamewell Masterbox

M&S BUILDING

FIRE ALARM:

1 Notifier NFS-320

2 Powerpath Boosters1 Annuciator Panel21 Pull Stations

135 Photo Detectors16 Heat Detectors79 Horn & Strobes65 Strobes23 Monitior Modules11 Tamper Switches7 Pressure Switches5 Flow Switches17 Relay Modules4 Fixed Heat Detectors1 Control Module

MONADNOCK MILL

FIRE ALARM:

1 Hochiki 4127 Fire Panel1 Remote zone annunciator1 Gamewell masterbox with red light27 Heat detectors 45 Smoke detectors14 Manual pull stations17 Horn/strobe evacuation devices

MORTON BUILDING

FIRE ALARM:

Notifier AFP 406 Fire Alarm Control Panel 1 Sub Panel

Fire department connection1 Remote annunciator DR-A5R11 Remote F/A Control Panel2 1255 Batteries

2 Heat/Elevator Shaft76 Smoke Detectors17 Pull Stations

149 Horn/Strobe

PRE-ACTION SYSTEM:

1 Viking Pre-Action Fire Panel (Par 3)1 1 ½” Deluge Valve (E3)1 Asco Shutoff Actuating Valve1 Detectors in G-461 Pull Station in G-462 Batteries (12V 12AH)1 3” Deluge Valve (B-1)

STATE LIBRARY

FIRE ALARM SYSTEM:

1 Silent Knight IFP-10004 Loop Expander1 Remote Annunciator16 Manual Pull Stations

116 Photo Detectors31 Heat Detectors6 Mini Monitor Modules21 Monitor Modules3 Relay Module2 Power Expander1 Green Beacon1 Red Beacon1 Master Trip Box2 24VDC Beam Detectors

DEPARTMENT OF MOTOR VEHICLE

FIRE ALARM:

1 Control Panel – FCI E36 Batteries7 Manual Station46 ION/PHOTO Smoke Detectors8 Heat Detectors6 Duct Detectors2 Strobe/Visual Device1 Graphic Annunciator

2 Travel

OLD LABOR BUILDING

FIRE ALARM:

1 GE Firefox FX-101 Gamewell master box1 Central station transmitter72 Heat detectors12 Smoke detectors10 Horn/Strobe Units5 Manual pull stations

RECORDS AND ARCHIVES (21 Fruit Street)

FIRE ALARM:

1 4100U - Simplex Fire Panel2 4009-9201 - NAC Power Extenders14 4099-9003 - Pull Stations

170 4098-9714 - Smoke Sensors170 4098-9792 - Smoke Base2 4098-9789 - LED Sensor Base28 4098-9733 - Heat Sensor28 4098-9792 - Heat Base2 4098-9789 - LED Heat Base4 5624 - Heat Detector Fixed 194 Degrees5 2096-9796 Duct Smokes tube5 2098-9806 - Remote Test Stations5 4098-9843 - Relays (parn-sd)2 4090-9101 - Zone Adapter Modules4 2098-9808 - Remote Alarm Indicator4 4090-9002 - Individual Address Module ®27 4090-9001 - Individual Address Module (s)34 4906-9127 - Multicandella H/S Wall Mount28 4906-9128 - Multicandella H/S Ceiling Mount1 98BR-G1 - Strobe-Red1 98BG-G1 - Strobe-Green13 4906-9101 - Multicandella Strobe Wall Mount16 4906-9102 - Multicandella Strobe Ceiling Mount5 2088-9608 - Door Holders 24V dc

SAFETY BUILDING

FIRE ALARM:

Notifier panel NFS-640Central station transmitterGamewell fire department connectionRemote Annunciator

99 Heat Detectors118 Smoke Detectors24 Pull Stations95 Horn/Strobe Units3 Connection to Halon system-computer room63 Strobes

61 SOUTH SPRING STREET

FIRE ALARM:

1 4020-7003 - Simplex Fire Control Panel1 4020-7003 - Master Controller1 4020-0305 - 8 pt. I/O Module1 4020-6084 - Version 9 Software1 2190-9169 - Short Circuit Isolator1 4602-7101 - Graphic Driver I/O Board1 W.P. xL8 - Graphic Annunciator24 4903-9417 - Horn/Strobe 2 wire 15 candela8 4903-9418 - Horn/Strobe 2 wire 75 Candela20 4904-9331 - Strobe 15 Candela4 4904-9332 - Strobe 75 Candela4 4905-9938 - Smartsync Control Module1 WP-98BG-G1 - Strobe-Green 24VDC1 98BR-G1 - Strobe-Red 24VDC16 2099-9761 - Pull Stations58 4098-9714 - Smoke Sensors4 4098-9714 - Smoke Sensor LED4 4098-9756 - Duct Smoke Sensor4 2098-9797 - Tube2 4098-9733 - Heat Sensor2 4098-9789 - Heat Sensor LED Output Base7 2098-9808 - Remote Alarm Indicator4 2098-9806 - Remote Test Station4 4098-9843 - Relays11 2190-9172 - Individual Addressable Modules Supv4 2190-9163 - Zone Adapter Module

SPAULDING HALL

FIRE ALARM:

1 4002-8001 - Simplex Fire Alarm Control Panel

Containing:1 4002-6001 - 120 VAC Operation1 4002-7001 - CPU with 8 Zones, 2 SIG. CIR, Class B2 4002-0102 - 4 Point Zone Disconnect Modules1 4002-2001 - #2 Cabinet Package

2 2081-9274 - 10 AH Maint. Free System Batteries1 Mini 10 Weatherproof Annunciator42 2098-9201 - Low Profile Photoelectric Smoke Detectors35 2098-9637 - Smoke Detector Bases5 2098-9536 - Detector Bases 4-Wire w/Relay SPDT 1 AMP5 2098-9739 - E.O.L. Trouble Relays86 2098-9439 - 135 Degrees Rate of Rise Heat Detectors14 2099-9201 - Manual Stations Single Action27 4903-9101 - Audio/Visual Strobe Units 24 VDC27 2901-9838 - Horns, Red 24 VDC Surface13 2098-9461 - Heat Detectors, 200 Degrees Fixed Temp1 2098-9806 - Remote Alarm Indicator w/Test Keyswitch1 2095-9011 - Local Energy Trip Exterior Master Box1 Digital Transmitter

STATE HOUSE

FIRE ALARM:

Mircom FX-2000Gamewell master boxMircom Power Supply

2 Fire Ray Beam Detectors in Reps HallHoneywell central station transmitterRemote Annunciator

173 Heat detectors74 Smoke detectors23 Horn/Strobe Units14 Strobe Lights18 Manual pull stations6 Magnetic door holders

PRE-ACTION SYSTEM:

1 Pre-action fire alarm control panel (FCI) with batteries1 Pull station1 Duct Detector

41

Fixed temperature heat detectors (Note: approximately 2/3 of the detectors are located within the floor/ceiling spaces and will be difficult to test)

STATE HOUSE ANNEX

FIRE ALARM:

Mircom FX-2000Mircom AnnunciatorMircom Power SupplyGamewell fire department master boxHoneywell central station transmitter

253 Heat detectors73 Smoke detectors26 Manual pull stations24 Evacuation horn/strobe lights13 Strobe Units18 Magnetic door releases

Sprinkler water flow switchGate valve tamper switch FBI Dialer

SUPREME COURT

FIRE ALARM:

1 FCI FC 72 Fire alarm control panel with stand by power1 Gamewell fire department master box1 Central station transmitter1 Remote annunciator90 Heat detectors54 Smoke detectors9 Manual pull stations34 Horn/Strobe Lights

SURPLUS WAREHOUSE

FIRE ALARM:

1 Honeywell Notifier NFS-3201 PS-B Booster1 Signal/Reversing Trouble Relay1 Auxiliary Device Actuation Module1 Signal Circuit Module1 Supervisory auxiliary relay board1 Subsequent alarm module1 Relay DPDT track (10 amp)12 Single Action Pull Stations1 Photoelectric Smoke Detector50 Horn/Strobes12 Strobe Lights1 16 Zone Annunciator1 Master Box1 120 VAC Red Light w/cage1 Red Strobe 12/28 Vac

DEPARTMENT OF TRANSPORTATION MECHANICAL SERVICES (33 Smokey Bear Blvd.)

FIRE ALARM:

1 Gamewell Master Fire Alarm Signal Box1 Fire Alarm System Control Panel AFP-200 Notifier3 Fire Alarm System Remove Panel FCCPS-24S879 Audible & Visual Alarm Signal2 Exterior Flashing Signal Beacon1 Exterior Flashing Signal Green Beacon3 Visual Only Alarm Signal ADA Rated17 Notifier Manual Pull Station4 Duct Smoke Detectors w/Remote Test Switch5 Smoke Detectors w/Remote Alarm Indicator1 Heat Detector w/Remote Alarm Indicator16 Monitor Zone Adapter Module – Notifier1 Knox Box

DEPARTMENT OF TRANSPORTATION MATERIAL RESEARCH LAB (5 Hazen Drive)

FIRE ALARM:

EST Fire Alarm System Containing:

1 2-WB3R - Red Surface Extended Back Box1 2-WB3DR - Red Surface Extended Door1 2-PPS/6A - Main Power Supply 6.4 AMP1 2-CTM - Analog Loop Controller Module & Display1 2-LCX - Analog Loop Expander Module1 2-CTM - Master Box Module1 SIGA-CC1 - Master Box Interface Used with 2-CTM4 ASLA 1075 - 7 AH Batteries2 MVP-U1 - 33 AH Batteries1 BCA - Battery Cabinet

16 M16 - 16 Zone Annunciator Common Positive Switch Negative

1 SAN-CPU - Power/Comm Card for San Series Module

1 SDR-32K - 32 Point San Annunciator Driver for Lamps or Relays

1 SAN 4R - Red 4 Module +1 CPU San Ann Cabinet1 BP-A - San Blank Filler Plate

2 PS 12/24-8MP - 8 AMP Signal Panel (2 Class “A” CKTS or 4 Class “B” CKTS)

26 SIGA-PS - Analog/Addressable Photo Smoke Detector Head

4 SIGA-HFS - Analgo/Addressable 135 Fixed Temp Detector Head

30 SIGA-SB - Analog/Addressable Standard Detector Base4 SIGA-SD - Analog/Addressable Duct Detector4 SIGA-SDTRK - Duct Function Test Module4 SD-T36 - 36” Sampling Tube for Siga-DH Duct Housing9 SIGA-LED - Remote LED for Siga-Detector5 SIGA-CT2 - Addressable Dual Input Module

2 SIGA-MCC1 - Siga-UIO#Addressable Class “B” Signal CKT Plug-In Module

2 SIGA-CR - Addressable Form “C” Relay Module

9 SIGA-278 - Addressable Double Action Manual Pull Station

1 SIGA-UIO6R - 6 Slot Universal Input/Output Module Board Wriser Inputs

30 NS-24MCW-FR - Multicandella Strobe1 ASWP-2475WFR - Weather Proof Horn Strobe

UPHAM WALKER

FIRE ALARM:

1 Honeywell Firolite2 12V 7.5 AH batteries3 Simplex #2008 9502 door holders9 Simplex #2903 9101 audio/visual units12 Simplex #2098 9464 heat detectors restroom25 Simplex #2093 9603 smoke detectors1 Ademco 221 Transmitter7 Pull stations11 Fixed temperature heat detectors

WALKER BUILDING

FIRE ALARM:

1 Control Panel8 Batteries1 Digital Dialer1 LCD Annunciator43 Manual Station

288 ION/Photo Smoke Detectors2 Heat Detectors3 Duct Detectors1 Field Power Supply/FCPS

150 Horn Strobe40 Strobe/Visual Device2 Elevator Recall

Bureau of Facilities and Assets Management

Brown Building

1 Gamewell-Flexalert Yes Remote Annunciator109 Smoke Detectors27 Pull Stations15 Heat Detectors9 Duct Smoke Detectors13 Tamper Switches10 Sprinkler Flow Switches9 Duct Smoke RemotesY Remote Annunciator

BatteriesLocation Room 150 (Lobby Area)

2 Interstate BSL 1146 12v 26Ah 2 Interstate BSL 1161 12v 44Ah

Brown Garage

1 Micron-FX2000 Yes Remote Annunciator7 Smoke Detectors60 Horn/Strobes4 Pull StationsY Remote Annunciator

BatteriesLocation 4th Floor Elevator Lobby Closet

4 Interstate BSL 1075 12v 8Ah 2 Interstate SLA1156 12v 35Ah

Dolloff Building

1 Notifier DR-A4RYes Remote Annunciator100 Smoke Detectors117 Horn/Strobes20 Pull Stations2 Tamper Switches1 Sprinkler Flow Switch

1 Low Air SwitchY Remote Annunicator

BatteriesLocation 1st Floor Main Lobby

2 Interstate BSL1146 12v 26Ah Location Level 2 Power Path Wheellock (& Level 3)

2 Embassy 12v 7.5Ah

Laundry Building

1 Simplex 40014 Horn/Strobes7 Pull Stations44 Heat Detectors

BatteriesLocation Level 2 Top of Steps

4 PM6100F1 12v 10Ah

Liberty House

1 Simplex 40018 Smoke Detectors3 Horn/Stobes4 Pull Stations13 Heat Detectors

BatteriesLocation Inside Main Entrance on Left

2 PM1270 12v 7.2Ah

Main Building / Bancroft Annex

1 Main Simplex 4001U Sub Panel (2) IDNET NAC Extenders (4)Yes Remote Annunciator222 Smoke Detectors327 Horn/Strobes110 Pull Stations

72 Heat Detectors23 Tamper Switches13 Sprinkler Flow Switches8 Low Air SwitchesY Remote Annunciator

BatteriesLocation 1st Floor Control Room

4 Werker WKDC12 – 55P 12v 55Ah Location Main Building Lobby

2 Werker 12v 12AhLocation Hallway outside Room 218N

2 PM12120F2 12v 12Ah2 Werker W19A12-18NB 12v 18 AH

Location Across from Room 215 South2 WKA12-12FZ 12v 12Ah

Location Plumbing Shop Entrance2 WKA12-12FZ 12v 12Ah

Location Main Lobby2 PM12260FZ 12v 26Ah

Thayer Building

1 Simplex 4001120 Smoke Detectors71 Horn/Strobes39 Pull Stations5 Heat Detectors5 Tamper Switches4 Sprinkler Flow Switches1 Low Air Switch

BatteriesLocation Basement (room w/hot water tanks)

4 PM Battery PM1233ou1 12V 33Ah

Transportation Building1 Simplex 4001

1 Smoke Detectors5 Horn/Strobes6 Pull Stations26 Heat Detectors

BatteriesLocation Bay 1 of Garage

3 PM6100F1 12v 10Ah

Warehouse

1 Simplex 400541 Smoke Detectors27 Horn/Strobes10 Pull Stations4 Heat Detectors

BatteriesLocation Main Lobby

2 Ultratech 12v 18Ah

Philbrook1 FX2000 1 Mircom Inx 10 Amp NAC 12 Pull stations67 Smoke Detector10 Heat Detectors22 Horn/strobes

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced NHDES-Winnipesaukee River Basin Program (WRBP), North Main Pump Station, 1539 Old North Main Street Laconia, NH 03246

Hours of Operation of Facility 7:00am to 3:30pm

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person John Spadafore

E-mail [email protected] Telephone 603.528.6746

Current Vendor Setronics Corp. for Maintenance & Inspection // Total Security for Monitoring Date of Last Inspection 5/11//2017 - Setronics

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4004 Date of installation 1997 Number of subpanels, if applicable N/A Number of pre-action panels, if applicable N/A Number of devices that feeds the panels 13 Number of pull stations 1 Number of heat detectors 1 Number of smoke detectors 7 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units 4

Duct Detectors N/A C/O Detectors N/A Door Holders N/A NACs/power supplies 2

For each system (not just panel), please confirm whether conventional or addressable: Conventional Conventional

Addressable N/A

Indicate the frequency of inspection services you would like Annually at a rate of 100% 100%

Quarterly Inspection at the rate of 25% N/A Other: N/A

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 7:00am to 3:30pm

Additional Information, if necessary Total Security (current state contract #8001396) provides fire alarm monitoring services to the DES-WRBP at a negotiated cost of less than $2500/year for all 15 DES-WRBP facilities. The DES-WRBP does not require burglar alarm maintenance and inspection services at any location since DES-WRBP master electricians maintain this equipment. Depending upon the terms and transition costs associated with the proposed state contract that may require new equipment to be installed and programmed at each location, the DES-WRBP may seek a waiver under RSA 21-I:17-c to continue using this firm for fire alarm monitoring only. The current Setronics Corp. contract with the DES-WRBP provides fire alarm maintenance and inspection services for all DES-WRBP locations and includes provisions for procurement and installations of fire alarm devices by DES-WRBP master electricians. This contract also provides access to Simplex proprietary programing capabilities, if deemed necessary. The Setronics contract was approved by the G&C on 8/3/16 as item #49 and is effective through June 30, 2019. The DES-WRBP will seek a waiver under RSA 21-I:17-c to continue using the Setronics contract.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced NHDES-Winnipesaukee River Basin Program (WRBP), Ellacoya Pump Station, 280 Scenic Drive Gilford, NH 03249

Hours of Operation of Facility 7:00am to 3:30pm

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person John Spadafore

E-mail [email protected] Telephone 603.528.6746

Current Vendor Setronics Corp. for Maintenance & Inspection // Total Security for Monitoring Date of Last Inspection 5/11//2017 - Setronics

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4004 Date of installation 1997 Number of subpanels, if applicable N/A Number of pre-action panels, if applicable N/A Number of devices that feeds the panels 14 Number of pull stations 2 Number of heat detectors 1 Number of smoke detectors 6 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units 5

Duct Detectors N/A C/O Detectors N/A Door Holders N/A NACs/power supplies 2

For each system (not just panel), please confirm whether conventional or addressable: Conventional Conventional

Addressable N/A

Indicate the frequency of inspection services you would like Annually at a rate of 100% 100%

Quarterly Inspection at the rate of 25% N/A Other: N/A

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 7:00am to 3:30pm

Additional Information, if necessary Total Security (current state contract #8001396) provides fire alarm monitoring services to the DES-WRBP at a negotiated cost of less than $2500/year for all 15 DES-WRBP facilities. The DES-WRBP does not require burglar alarm maintenance and inspection services at any location since DES-WRBP master electricians maintain this equipment. Depending upon the terms and transition costs associated with the proposed state contract that may require new equipment to be installed and programmed at each location, the DES-WRBP may seek a waiver under RSA 21-I:17-c to continue using this firm for fire alarm monitoring only. The current Setronics Corp. contract with the DES-WRBP provides fire alarm maintenance and inspection services for all DES-WRBP locations and includes provisions for procurement and installations of fire alarm devices by DES-WRBP master electricians. This contract also provides access to Simplex proprietary programing capabilities, if deemed necessary. The Setronics contract was approved by the G&C on 8/3/16 as item #49 and is effective through June 30, 2019. The DES-WRBP will seek a waiver under RSA 21-I:17-c to continue using the Setronics contract.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced NHDES-Winnipesaukee River Basin Program (WRBP), Gilford Pump Station, 74 Weirs Road Gilford, NH 03249

Hours of Operation of Facility 7:00am to 3:30pm

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person John Spadafore

E-mail [email protected] Telephone 603.528.6746

Current Vendor Setronics Corp. for Maintenance & Inspection // Total Security for Monitoring Date of Last Inspection 5/11//2017 - Setronics

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4004 Date of installation 1997 Number of subpanels, if applicable N/A Number of pre-action panels, if applicable N/A Number of devices that feeds the panels 12 Number of pull stations 1 Number of heat detectors 1 Number of smoke detectors 6 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units 4

Duct Detectors N/A C/O Detectors N/A Door Holders N/A NACs/power supplies 2

For each system (not just panel), please confirm whether conventional or addressable: Conventional Conventional

Addressable N/A

Indicate the frequency of inspection services you would like Annually at a rate of 100% 100%

Quarterly Inspection at the rate of 25% N/A Other: N/A

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 7:00am to 3:30pm

Additional Information, if necessary Total Security (current state contract #8001396) provides fire alarm monitoring services to the DES-WRBP at a negotiated cost of less than $2500/year for all 15 DES-WRBP facilities. The DES-WRBP does not require burglar alarm maintenance and inspection services at any location since DES-WRBP master electricians maintain this equipment. Depending upon the terms and transition costs associated with the proposed state contract that may require new equipment to be installed and programmed at each location, the DES-WRBP may seek a waiver under RSA 21-I:17-c to continue using this firm for fire alarm monitoring only. The current Setronics Corp. contract with the DES-WRBP provides fire alarm maintenance and inspection services for all DES-WRBP locations and includes provisions for procurement and installations of fire alarm devices by DES-WRBP master electricians. This contract also provides access to Simplex proprietary programing capabilities, if deemed necessary. The Setronics contract was approved by the G&C on 8/3/16 as item #49 and is effective through June 30, 2019. The DES-WRBP will seek a waiver under RSA 21-I:17-c to continue using the Setronics contract.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced NHDES-Winnipesaukee River Basin Program (WRBP), Glendale Pump Station, 31 Dock Road Gilford, NH 03249

Hours of Operation of Facility 7:00am to 3:30pm

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person John Spadafore

E-mail [email protected] Telephone 603.528.6746

Current Vendor Setronics Corp. for Maintenance & Inspection // Total Security for Monitoring Date of Last Inspection 5/11//2017 - Setronics

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4004 Date of installation 1997 Number of subpanels, if applicable N/A Number of pre-action panels, if applicable N/A Number of devices that feeds the panels 12 Number of pull stations 1 Number of heat detectors 1 Number of smoke detectors 6 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units 4

Duct Detectors N/A C/O Detectors N/A Door Holders N/A NACs/power supplies 2

For each system (not just panel), please confirm whether conventional or addressable: Conventional Conventional

Addressable N/A

Indicate the frequency of inspection services you would like Annually at a rate of 100% 100%

Quarterly Inspection at the rate of 25% N/A Other: N/A

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 7:00am to 3:30pm

Additional Information, if necessary Total Security (current state contract #8001396) provides fire alarm monitoring services to the DES-WRBP at a negotiated cost of less than $2500/year for all 15 DES-WRBP facilities. The DES-WRBP does not require burglar alarm maintenance and inspection services at any location since DES-WRBP master electricians maintain this equipment. Depending upon the terms and transition costs associated with the proposed state contract that may require new equipment to be installed and programmed at each location, the DES-WRBP may seek a waiver under RSA 21-I:17-c to continue using this firm for fire alarm monitoring only. The current Setronics Corp. contract with the DES-WRBP provides fire alarm maintenance and inspection services for all DES-WRBP locations and includes provisions for procurement and installations of fire alarm devices by DES-WRBP master electricians. This contract also provides access to Simplex proprietary programing capabilities, if deemed necessary. The Setronics contract was approved by the G&C on 8/3/16 as item #49 and is effective through June 30, 2019. The DES-WRBP will seek a waiver under RSA 21-I:17-c to continue using the Setronics contract.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced NHDES-Winnipesaukee River Basin Program (WRBP), Jewett Brook Pump Station, 73 Strafford Street, Laconia NH 03246

Hours of Operation of Facility 7:00am to 3:30pm

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person John Spadafore

E-mail [email protected] Telephone 603.528.6746

Current Vendor Setronics Corp. for Maintenance & Inspection // Total Security for Monitoring Date of Last Inspection 5/11//2017 - Setronics

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4004 Date of installation 1997 Number of subpanels, if applicable N/A Number of pre-action panels, if applicable N/A Number of devices that feeds the panels 13 Number of pull stations 2 Number of heat detectors 1 Number of smoke detectors 5 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units 5

Duct Detectors N/A C/O Detectors N/A Door Holders N/A NACs/power supplies 2

For each system (not just panel), please confirm whether conventional or addressable: Conventional Conventional

Addressable N/A

Indicate the frequency of inspection services you would like Annually at a rate of 100% 100%

Quarterly Inspection at the rate of 25% N/A Other: N/A

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 7:00am to 3:30pm

Additional Information, if necessary Total Security (current state contract #8001396) provides fire alarm monitoring services to the DES-WRBP at a negotiated cost of less than $2500/year for all 15 DES-WRBP facilities. The DES-WRBP does not require burglar alarm maintenance and inspection services at any location since DES-WRBP master electricians maintain this equipment. Depending upon the terms and transition costs associated with the proposed state contract that may require new equipment to be installed and programmed at each location, the DES-WRBP may seek a waiver under RSA 21-I:17-c to continue using this firm for fire alarm monitoring only. The current Setronics Corp. contract with the DES-WRBP provides fire alarm maintenance and inspection services for all DES-WRBP locations and includes provisions for procurement and installations of fire alarm devices by DES-WRBP master electricians. This contract also provides access to Simplex proprietary programing capabilities, if deemed necessary. The Setronics contract was approved by the G&C on 8/3/16 as item #49 and is effective through June 30, 2019. The DES-WRBP will seek a waiver under RSA 21-I:17-c to continue using the Setronics contract.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced NHDES-Winnipesaukee River Basin Program (WRBP), Laconia Maintenance Shop, 202 Water Street, Laconia NH 03246

Hours of Operation of Facility 7:00am to 3:30pm

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person John Spadafore

E-mail [email protected] Telephone 603.528.6746

Current Vendor Setronics Corp. for Maintenance & Inspection // Total Security for Monitoring Date of Last Inspection 5/11//2017 - Setronics

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4010 Date of installation 1997 Number of subpanels, if applicable N/A Number of pre-action panels, if applicable N/A Number of devices that feeds the panels 41 Number of pull stations 6 Number of heat detectors 14 Number of smoke detectors 10 Number of battery backups 3

Please include the quantity of the following peripherals: Audio-Visual Units 11

Duct Detectors N/A C/O Detectors N/A Door Holders N/A NACs/power supplies 2

For each system (not just panel), please confirm whether conventional or addressable: Conventional Conventional

Addressable N/A

Indicate the frequency of inspection services you would like Annually at a rate of 100% 100%

Quarterly Inspection at the rate of 25% N/A Other: N/A

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 7:00am to 3:30pm

Additional Information, if necessary Total Security (current state contract #8001396) provides fire alarm monitoring services to the DES-WRBP at a negotiated cost of less than $2500/year for all 15 DES-WRBP facilities. The DES-WRBP does not require burglar alarm maintenance and inspection services at any location since DES-WRBP master electricians maintain this equipment. Depending upon the terms and transition costs associated with the proposed state contract that may require new equipment to be installed and programmed at each location, the DES-WRBP may seek a waiver under RSA 21-I:17-c to continue using this firm for fire alarm monitoring only. The current Setronics Corp. contract with the DES-WRBP provides fire alarm maintenance and inspection services for all DES-WRBP locations and includes provisions for procurement and installations of fire alarm devices by DES-WRBP master electricians. This contract also provides access to Simplex proprietary programing capabilities, if deemed necessary. The Setronics contract was approved by the G&C on 8/3/16 as item #49 and is effective through June 30, 2019. The DES-WRBP will seek a waiver under RSA 21-I:17-c to continue using the Setronics contract.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced NHDES-Dam Bureau, Lakeport Dam Operator House, 93 Elm Street, Laconia, NH 03246

Hours of Operation of Facility 24 hours per day

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person Daniel J. Mattaini, P.E.

E-mail [email protected] Telephone 603-271-8867

Current Vendor N/A Date of Last Inspection None

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment N/A

Model of panel N/A Date of installation N/A

Number of subpanels, if applicable 0 Number of pre-action panels, if applicable 0 Number of devices that feeds the panels 0 Number of pull stations 0 Number of heat detectors 0 Number of smoke detectors 2 Number of battery backups 0 Please include the quantity of the following peripherals:

Audio-Visual Units 0 Duct Detectors 0 C/O Detectors 1 Door Holders 0 NACs/power supplies 0 For each system (not just panel), please confirm whether conventional or addressable:

Conventional N/A Addressable Indicate the frequency of inspection services you would like

Annually at a rate of 100% 1 Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 8 AM – 4 PM

Additional Information, if necessary

(4) fire extinguishers on site, supplied by TriState Fire Protection On-site detectors bought at building supply outlets and installed by staff

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced NHDES-Winnipesaukee River Basin Program (WRBP), MLC Pump Station, 763 Scenic Drive Laconia, NH 03246

Hours of Operation of Facility 7:00am to 3:30pm

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person John Spadafore

E-mail [email protected] Telephone 603.528.6746

Current Vendor Setronics Corp. for Maintenance & Inspection // Total Security for Monitoring Date of Last Inspection 5/11//2017 - Setronics

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4004 Date of installation 1997 Number of subpanels, if applicable N/A Number of pre-action panels, if applicable N/A Number of devices that feeds the panels 12 Number of pull stations 1 Number of heat detectors 1 Number of smoke detectors 6 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units 4

Duct Detectors N/A C/O Detectors N/A Door Holders N/A NACs/power supplies 2

For each system (not just panel), please confirm whether conventional or addressable: Conventional Conventional

Addressable N/A

Indicate the frequency of inspection services you would like Annually at a rate of 100% 100%

Quarterly Inspection at the rate of 25% N/A Other: N/A

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 7:00am to 3:30pm

Additional Information, if necessary Total Security (current state contract #8001396) provides fire alarm monitoring services to the DES-WRBP at a negotiated cost of less than $2500/year for all 15 DES-WRBP facilities. The DES-WRBP does not require burglar alarm maintenance and inspection services at any location since DES-WRBP master electricians maintain this equipment. Depending upon the terms and transition costs associated with the proposed state contract that may require new equipment to be installed and programmed at each location, the DES-WRBP may seek a waiver under RSA 21-I:17-c to continue using this firm for fire alarm monitoring only. The current Setronics Corp. contract with the DES-WRBP provides fire alarm maintenance and inspection services for all DES-WRBP locations and includes provisions for procurement and installations of fire alarm devices by DES-WRBP master electricians. This contract also provides access to Simplex proprietary programing capabilities, if deemed necessary. The Setronics contract was approved by the G&C on 8/3/16 as item #49 and is effective through June 30, 2019. The DES-WRBP will seek a waiver under RSA 21-I:17-c to continue using the Setronics contract.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced NHDES-Dam Bureau, Murphy Dam Operator House, 11 Murphy Dam Road, Pittsburg, NH 03592

Hours of Operation of Facility 8:00-4:00

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person Daniel J. Mattaini, P.E.

E-mail [email protected] Telephone 603-271-8867

Current Vendor N/A Date of Last Inspection 8/17

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment N/A

Model of panel N/A Date of installation N/A

Number of subpanels, if applicable Number of pre-action panels, if applicable 0 Number of devices that feeds the panels 0 Number of pull stations 0 Number of heat detectors 0 Number of smoke detectors 6 Number of battery backups 0 Please include the quantity of the following peripherals:

Audio-Visual Units 0 Duct Detectors 0 C/O Detectors 2 Door Holders 0 NACs/power supplies 0 For each system (not just panel), please confirm whether conventional or addressable:

Conventional N/A Addressable Indicate the frequency of inspection services you would like

Annually at a rate of 100% 1 Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested.

Additional Information, if necessary

Inspection performed by TriState Fire Protection prior to fire extinguisher acquisitions (9) fire extinguishers on site, supplied by TriState Fire Protection On-site detectors bought at building supply outlets and installed by staff

0

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced NHDES-Winnipesaukee River Basin Program (WRBP), Paugus Pump Station, 29 Paugus Park Road Laconia, NH 03246

Hours of Operation of Facility 7:00am to 3:30pm

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person John Spadafore

E-mail [email protected] Telephone 603.528.6746

Current Vendor Setronics Corp. for Maintenance & Inspection // Total Security for Monitoring Date of Last Inspection 5/11//2017 - Setronics

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4004 Date of installation 1997 Number of subpanels, if applicable N/A Number of pre-action panels, if applicable N/A Number of devices that feeds the panels 13 Number of pull stations 1 Number of heat detectors 1 Number of smoke detectors 7 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units 4

Duct Detectors N/A C/O Detectors N/A Door Holders N/A NACs/power supplies 2

For each system (not just panel), please confirm whether conventional or addressable: Conventional Conventional

Addressable N/A

Indicate the frequency of inspection services you would like Annually at a rate of 100% 100%

Quarterly Inspection at the rate of 25% N/A Other: N/A

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 7:00am to 3:30pm

Additional Information, if necessary Total Security (current state contract #8001396) provides fire alarm monitoring services to the DES-WRBP at a negotiated cost of less than $2500/year for all 15 DES-WRBP facilities. The DES-WRBP does not require burglar alarm maintenance and inspection services at any location since DES-WRBP master electricians maintain this equipment. Depending upon the terms and transition costs associated with the proposed state contract that may require new equipment to be installed and programmed at each location, the DES-WRBP may seek a waiver under RSA 21-I:17-c to continue using this firm for fire alarm monitoring only. The current Setronics Corp. contract with the DES-WRBP provides fire alarm maintenance and inspection services for all DES-WRBP locations and includes provisions for procurement and installations of fire alarm devices by DES-WRBP master electricians. This contract also provides access to Simplex proprietary programing capabilities, if deemed necessary. The Setronics contract was approved by the G&C on 8/3/16 as item #49 and is effective through June 30, 2019. The DES-WRBP will seek a waiver under RSA 21-I:17-c to continue using the Setronics contract.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced NHDES-Winnipesaukee River Basin Program (WRBP), Pendleton Pump Station, 67 Pendleton Beach Road Laconia, NH 03246

Hours of Operation of Facility 7:00am to 3:30pm

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person John Spadafore

E-mail [email protected] Telephone 603.528.6746

Current Vendor Setronics Corp. for Maintenance & Inspection // Total Security for Monitoring Date of Last Inspection 5/11//2017 - Setronics

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4004 Date of installation 1997 Number of subpanels, if applicable N/A Number of pre-action panels, if applicable N/A Number of devices that feeds the panels 13 Number of pull stations 2 Number of heat detectors 1 Number of smoke detectors 6 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units 4

Duct Detectors N/A C/O Detectors N/A Door Holders N/A NACs/power supplies 2

For each system (not just panel), please confirm whether conventional or addressable: Conventional Conventional

Addressable N/A

Indicate the frequency of inspection services you would like Annually at a rate of 100% 100%

Quarterly Inspection at the rate of 25% N/A Other: N/A

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 7:00am to 3:30pm

Additional Information, if necessary Total Security (current state contract #8001396) provides fire alarm monitoring services to the DES-WRBP at a negotiated cost of less than $2500/year for all 15 DES-WRBP facilities. The DES-WRBP does not require burglar alarm maintenance and inspection services at any location since DES-WRBP master electricians maintain this equipment. Depending upon the terms and transition costs associated with the proposed state contract that may require new equipment to be installed and programmed at each location, the DES-WRBP may seek a waiver under RSA 21-I:17-c to continue using this firm for fire alarm monitoring only. The current Setronics Corp. contract with the DES-WRBP provides fire alarm maintenance and inspection services for all DES-WRBP locations and includes provisions for procurement and installations of fire alarm devices by DES-WRBP master electricians. This contract also provides access to Simplex proprietary programing capabilities, if deemed necessary. The Setronics contract was approved by the G&C on 8/3/16 as item #49 and is effective through June 30, 2019. The DES-WRBP will seek a waiver under RSA 21-I:17-c to continue using the Setronics contract.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced NHDES-Winnipesaukee River Basin Program (WRBP), River Street Pump Station, 101 River Street Franklin, NH 03235

Hours of Operation of Facility 7:00am to 3:30pm

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person John Spadafore

E-mail [email protected] Telephone 603.528.6746

Current Vendor Setronics Corp. for Maintenance & Inspection // Total Security for Monitoring Date of Last Inspection 5/11//2017 - Setronics

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4004 Date of installation 1997 Number of subpanels, if applicable N/A Number of pre-action panels, if applicable N/A Number of devices that feeds the panels 9 Number of pull stations 2 Number of heat detectors 1 Number of smoke detectors 3 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units 3

Duct Detectors N/A C/O Detectors N/A Door Holders N/A NACs/power supplies 2

For each system (not just panel), please confirm whether conventional or addressable: Conventional Conventional

Addressable N/A

Indicate the frequency of inspection services you would like Annually at a rate of 100% 100%

Quarterly Inspection at the rate of 25% N/A Other: N/A

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 7:00am to 3:30pm

Additional Information, if necessary Total Security (current state contract #8001396) provides fire alarm monitoring services to the DES-WRBP at a negotiated cost of less than $2500/year for all 15 DES-WRBP facilities. The DES-WRBP does not require burglar alarm maintenance and inspection services at any location since DES-WRBP master electricians maintain this equipment. Depending upon the terms and transition costs associated with the proposed state contract that may require new equipment to be installed and programmed at each location, the DES-WRBP may seek a waiver under RSA 21-I:17-c to continue using this firm for fire alarm monitoring only. The current Setronics Corp. contract with the DES-WRBP provides fire alarm maintenance and inspection services for all DES-WRBP locations and includes provisions for procurement and installations of fire alarm devices by DES-WRBP master electricians. This contract also provides access to Simplex proprietary programing capabilities, if deemed necessary. The Setronics contract was approved by the G&C on 8/3/16 as item #49 and is effective through June 30, 2019. The DES-WRBP will seek a waiver under RSA 21-I:17-c to continue using the Setronics contract.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced Subsurface Systems Bureau Gorham Regional Office 80 Glenn Rd Gorham, NH 03581

Hours of Operation of Facility

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person Rick Treiss

E-mail [email protected] Telephone 603-466-5379

Current Vendor Date of Last Inspection Unknown

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment No Alarms, 2 Fire Extinguishers Only

Model of panel N/A Date of installation N/A Number of subpanels, if applicable N/A Number of pre-action panels, if applicable N/A Number of devices that feeds the panels N/A Number of pull stations N/A Number of heat detectors N/A Number of smoke detectors N/A Number of battery backups N/A

Please include the quantity of the following peripherals: Audio-Visual Units N/A

Duct Detectors N/A C/O Detectors N/A Door Holders N/A NACs/power supplies N/A

For each system (not just panel), please confirm whether conventional or addressable: Conventional N/A

Addressable N/A

Indicate the frequency of inspection services you would like Annually at a rate of 100% YES

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 8 a.m. – 4 p.m.

Additional Information, if necessary

Office has only 2 fire extinguishers and smoke/CO2 detectors. Please Contact Rick Treiss at 603-466-5379 to be sure he will be in the office at time of inspection.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced NHDES-Winnipesaukee River Basin Program (WRBP), State School Pump Station, 1 Right Way Path Street Laconia, NH 03246

Hours of Operation of Facility 7:00am to 3:30pm

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person John Spadafore

E-mail [email protected] Telephone 603.528.6746

Current Vendor Setronics Corp. for Maintenance & Inspection // Total Security for Monitoring Date of Last Inspection 5/11//2017 - Setronics

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4004 Date of installation 1997 Number of subpanels, if applicable N/A Number of pre-action panels, if applicable N/A Number of devices that feeds the panels 8 Number of pull stations 1 Number of heat detectors 1 Number of smoke detectors 3 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units 3

Duct Detectors N/A C/O Detectors N/A Door Holders N/A NACs/power supplies 2

For each system (not just panel), please confirm whether conventional or addressable: Conventional Conventional

Addressable N/A

Indicate the frequency of inspection services you would like Annually at a rate of 100% 100%

Quarterly Inspection at the rate of 25% N/A Other: N/A

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 7:00am to 3:30pm

Additional Information, if necessary Total Security (current state contract #8001396) provides fire alarm monitoring services to the DES-WRBP at a negotiated cost of less than $2500/year for all 15 DES-WRBP facilities. The DES-WRBP does not require burglar alarm maintenance and inspection services at any location since DES-WRBP master electricians maintain this equipment. Depending upon the terms and transition costs associated with the proposed state contract that may require new equipment to be installed and programmed at each location, the DES-WRBP may seek a waiver under RSA 21-I:17-c to continue using this firm for fire alarm monitoring only. The current Setronics Corp. contract with the DES-WRBP provides fire alarm maintenance and inspection services for all DES-WRBP locations and includes provisions for procurement and installations of fire alarm devices by DES-WRBP master electricians. This contract also provides access to Simplex proprietary programing capabilities, if deemed necessary. The Setronics contract was approved by the G&C on 8/3/16 as item #49 and is effective through June 30, 2019. The DES-WRBP will seek a waiver under RSA 21-I:17-c to continue using the Setronics contract.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced NHDES-Winnipesaukee River Basin Program (WRBP), WWTP Control Bldg, 528 River Road Franklin, NH 03235

Hours of Operation of Facility 7:00am to 3:30pm

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person John Spadafore

E-mail [email protected] Telephone 603.528.6746

Current Vendor Setronics Corp. for Maintenance & Inspection // Total Security for Monitoring Date of Last Inspection 5/11//2017 - Setronics

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4100 Date of installation 1997 Number of subpanels, if applicable N/A Number of pre-action panels, if applicable N/A Number of devices that feeds the panels 183 Number of pull stations 31 Number of heat detectors 34 Number of smoke detectors 72 Number of battery backups 9

Please include the quantity of the following peripherals: Audio-Visual Units 46

Duct Detectors 1 C/O Detectors N/A Door Holders N/A NACs/power supplies 11

For each system (not just panel), please confirm whether conventional or addressable: Conventional N/A

Addressable Addressable

Indicate the frequency of inspection services you would like Annually at a rate of 100% 100%

Quarterly Inspection at the rate of 25% N/A Other: N/A

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 7:00am to 3:30pm

Additional Information, if necessary Total Security (current state contract #8001396) provides fire alarm monitoring services to the DES-WRBP at a negotiated cost of less than $2500/year for all 15 DES-WRBP facilities. The DES-WRBP does not require burglar alarm maintenance and inspection services at any location since DES-WRBP master electricians maintain this equipment. Depending upon the terms and transition costs associated with the proposed state contract that may require new equipment to be installed and programmed at each location, the DES-WRBP may seek a waiver under RSA 21-I:17-c to continue using this firm for fire alarm monitoring only. The current Setronics Corp. contract with the DES-WRBP provides fire alarm maintenance and inspection services for all DES-WRBP locations and includes provisions for procurement and installations of fire alarm devices by DES-WRBP master electricians. This contract also provides access to Simplex proprietary programing capabilities, if deemed necessary. The Setronics contract was approved by the G&C on 8/3/16 as item #49 and is effective through June 30, 2019. The DES-WRBP will seek a waiver under RSA 21-I:17-c to continue using the Setronics contract.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced NHDES-Winnispesaukee River Basin Program (WRBP), WWTP Electrical Annex, 528 River Road Franklin, NH 03235

Hours of Operation of Facility 7:00am to 3:30pm

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person John Spadafore

E-mail [email protected] Telephone 603.528.6746

Current Vendor Setronics Corp. for Maintenance & Inspection // Total Security for Monitoring Date of Last Inspection 5/11//2017 - Setronics

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel ( extension to main panel operations building ) 4100 Date of installation 1997 Number of subpanels, if applicable N/A Number of pre-action panels, if applicable N/A Number of devices that feeds the panels 2 Number of pull stations 2 Number of heat detectors

Number of smoke detectors Number of battery backups N/A

Please include the quantity of the following peripherals: Audio-Visual Units Duct Detectors N/A

C/O Detectors N/A Door Holders N/A NACs/power supplies N/A

For each system (not just panel), please confirm whether conventional or addressable: Conventional N/A

Addressable Addressable

Indicate the frequency of inspection services you would like Annually at a rate of 100% 100%

Quarterly Inspection at the rate of 25% N/A Other: N/A

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 7:00am to 3:30pm

Additional Information, if necessary Total Security (current state contract #8001396) provides fire alarm monitoring services to the DES-WRBP at a negotiated cost of less than $2500/year for all 15 DES-WRBP facilities. The DES-WRBP does not require burglar alarm maintenance and inspection services at any location since DES-WRBP master electricians maintain this equipment. Depending upon the terms and transition costs associated with the proposed state contract that may require new equipment to be installed and programmed at each location, the DES-WRBP may seek a waiver under RSA 21-I:17-c to continue using this firm for fire alarm monitoring only. The current Setronics Corp. contract with the DES-WRBP provides fire alarm maintenance and inspection services for all DES-WRBP locations and includes provisions for procurement and installations of fire alarm devices by DES-WRBP master electricians. This contract also provides access to Simplex proprietary programing capabilities, if deemed necessary. The Setronics contract was approved by the G&C on 8/3/16 as item #49 and is effective through June 30, 2019. The DES-WRBP will seek a waiver under RSA 21-I:17-c to continue using the Setronics contract.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced NHDES- Winnipesaukee River Basin Program (WRBP), WWTP UV Bldg, 528 River Road Franklin, NH 03235

Hours of Operation of Facility 7:00am to 3:30pm

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person John Spadafore

E-mail [email protected] Telephone 603.528.6746

Current Vendor Setronics Corp. for Maintenance & Inspection // Total Security for Monitoring Date of Last Inspection 5/11//2017 - Setronics

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Firelite

Model of panel MS9200UDLS Date of installation 1997 Number of subpanels, if applicable N/A Number of pre-action panels, if applicable N/A Number of devices that feeds the panels 39 Number of pull stations 5 Number of heat detectors 18 Number of smoke detectors 2 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units 7

Duct Detectors 5 C/O Detectors N/A Door Holders N/A NACs/power supplies 4

For each system (not just panel), please confirm whether conventional or addressable: Conventional Conventional

Addressable N/A

Indicate the frequency of inspection services you would like Annually at a rate of 100% 100%

Quarterly Inspection at the rate of 25% N/A Other: N/A

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 7:00am to 3:30pm

Additional Information, if necessary Total Security (current state contract #8001396) provides fire alarm monitoring services to the DES-WRBP at a negotiated cost of less than $2500/year for all 15 DES-WRBP facilities. The DES-WRBP does not require burglar alarm maintenance and inspection services at any location since DES-WRBP master electricians maintain this equipment. Depending upon the terms and transition costs associated with the proposed state contract that may require new equipment to be installed and programmed at each location, the DES-WRBP may seek a waiver under RSA 21-I:17-c to continue using this firm for fire alarm monitoring only. The current Setronics Corp. contract with the DES-WRBP provides fire alarm maintenance and inspection services for all DES-WRBP locations and includes provisions for procurement and installations of fire alarm devices by DES-WRBP master electricians. This contract also provides access to Simplex proprietary programing capabilities, if deemed necessary. The Setronics contract was approved by the G&C on 8/3/16 as item #49 and is effective through June 30, 2019. The DES-WRBP will seek a waiver under RSA 21-I:17-c to continue using the Setronics contract.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Environmental Services

Facility Location & Address to be serviced NHDES-Winnipesaukee River Basin Program (WRBP), Winnisquam Pump Station, 202 Water Street, Laconia NH 03246

Hours of Operation of Facility 7:00am to 3:30pm

Remit Address for Invoices Attn: Business Office, PO Box 95, Concord NH 03302-0095 Facility Contact Person John Spadafore

E-mail [email protected] Telephone 603.528.6746

Current Vendor Setronics Corp. for Maintenance & Inspection // Total Security for Monitoring Date of Last Inspection 5/11//2017 - Setronics

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4004 Date of installation 1997 Number of subpanels, if applicable N/A Number of pre-action panels, if applicable N/A Number of devices that feeds the panels 10 Number of pull stations 1 Number of heat detectors N/A Number of smoke detectors 6 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units 3

Duct Detectors N/A C/O Detectors N/A Door Holders N/A NACs/power supplies 2

For each system (not just panel), please confirm whether conventional or addressable: Conventional Conventional

Addressable N/A

Indicate the frequency of inspection services you would like Annually at a rate of 100% 100%

Quarterly Inspection at the rate of 25% N/A Other: N/A

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 7:00am to 3:30pm

Additional Information, if necessary Total Security (current state contract #8001396) provides fire alarm monitoring services to the DES-WRBP at a negotiated cost of less than $2500/year for all 15 DES-WRBP facilities. The DES-WRBP does not require burglar alarm maintenance and inspection services at any location since DES-WRBP master electricians maintain this equipment. Depending upon the terms and transition costs associated with the proposed state contract that may require new equipment to be installed and programmed at each location, the DES-WRBP may seek a waiver under RSA 21-I:17-c to continue using this firm for fire alarm monitoring only. The current Setronics Corp. contract with the DES-WRBP provides fire alarm maintenance and inspection services for all DES-WRBP locations and includes provisions for procurement and installations of fire alarm devices by DES-WRBP master electricians. This contract also provides access to Simplex proprietary programing capabilities, if deemed necessary. The Setronics contract was approved by the G&C on 8/3/16 as item #49 and is effective through June 30, 2019. The DES-WRBP will seek a waiver under RSA 21-I:17-c to continue using the Setronics contract.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Administration Building - John H Sununu Center

Facility Location & Address to be serviced

1056 River Road Manchester NH 03103

Hours of Operation of Facility 7:00 to 3:30

Remit Address for Invoices Facility Contact Person Ron Laflamme

E-mail [email protected] Telephone

Current Vendor Date of Last Inspection 2017

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Mircom

Model of panel FX2000 Date of installation 1/25/2017 Number of subpanels, if applicable 0 Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations 14 Number of heat detectors 64 Number of smoke detectors 60 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units 20

Duct Detectors C/O Detectors Door Holders 11 NACs/power supplies 1

For each system (not just panel), please confirm whether conventional or addressable: Conventional XX

Addressable

Indicate the frequency of inspection services you would like Annually at a rate of 100%

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested.

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name John H Sununu Center

Facility Location & Address to be serviced

1056 River Road Manchester NH 03103

Hours of Operation of Facility 7 to 3:30 Monday to Friday

Remit Address for Invoices Facility Contact Person Ron Laflamme

E-mail [email protected] Telephone 603-625-5471 ext. 311

Current Vendor Date of Last Inspection 2017

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Siemens

Model of panel MXL Date of installation 2006 Number of subpanels, if applicable 1 Number of pre-action panels, if applicable

Number of devices that feeds the panels Number of pull stations 47

Number of heat detectors Number of smoke detectors 160

Number of battery backups 18

Please include the quantity of the following peripherals: Audio-Visual Units 130 Audio and 75 visual only and 1 outside beacon

Duct Detectors 49 C/O Detectors Door Holders 25 NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable xxxx

Indicate the frequency of inspection services you would like Annually at a rate of 100% x

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested.

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection ServicesSubmit this electronically ONLY.Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this contract. Type each response in the fields provided.

REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

16 East Point Drive Bedford, NH 03110

E-mailTelephone

For fire alarm maintenance please provide an inventory of your existing system below.

Please include the quantity of the following peripherals:

For each system (not just panel), please confirm whether conventional or addressable:

Indicate the frequency of inspection services you would like

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested.

Additional Information, if necessary

System monitored by NH DOS State Police who notifies Bedford Fire Department

Current Vendor Norriss, Inc.Date of Last Inspection Jun-17

Audio-Visual Units 27Duct Detectors 0

NACs/power supplies 1

C/O Detectors 0Door Holders 0

Number of subpanels, if applicable

16 East Point Drive Bedford, NH 03110Facility Contact Person Gary S. Clifford

[email protected](603) 666-3336

Remit Address for Invoices

NH Department of Transportation Maintenance District 5Agency Name

Facility Location & Address to be serviced p 16 East Point DriveBedford, NH 03110

Hours of Operation of Facility

7 AM to 3:30 PM, scheduled in advance with proper notification and preferably early AM

Conventional noAddressable yes

Quarterly Inspection at the rate of 25% noOther: repais as needed

Number of smoke detectors 33Number of battery backups 1

Annually at a rate of 100% yes

00

Number of heat detectors 13

Number of devices that feeds the panels 58Number of pull stations 10

Number of preaction panels, if applicable

Manufacturer/Brand of Equipment Simplex-GrinnellModel of panel Simplex 4088Date of installation 2009

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection ServicesSubmit this electronically ONLY.Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this contract. Type each response in the fields provided.

REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

16 East Point Drive Bedford, NH 03110

E-mailTelephone

For fire alarm maintenance please provide an inventory of your existing system below.

Please include the quantity of the following peripherals:

For each system (not just panel), please confirm whether conventional or addressable:

Indicate the frequency of inspection services you would like

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested.

Additional Information, if necessary

(603) 666-3336

Agency NameNH Department of Transportation Maintenance District 5

Facility Location & Address to be serviced 6 East Point DriveBedford, NH 03110

Hours of Operation of Facility7 AM to 3:30 PM

Remit Address for Invoices 16 East Point Drive Bedford, NH 03110Facility Contact Person Gary S. Clifford

[email protected]

Current Vendor Norriss, Inc.Date of Last Inspection Jun-17

Manufacturer/Brand of Equipment NotifierModel of panel SPF-2404Date of installation 2008Number of subpanels, if applicable 0Number of preaction panels, if applicable 0Number of devices that feeds the panels 29Number of pull stations 7Number of heat detectors 16Number of smoke detectors 6Number of battery backups 1

Audio-Visual Units 18Duct Detectors 1C/O Detectors 2Door Holders 0NACs/power supplies 1

Conventional yes

Other: repais as needed

7 AM to 3:30 PM, scheduled in advance with proper notification and preferably early AM

System monitored by Central Alarm who notifies Bedford Fire Department

Addressable no

Annually at a rate of 100% yesQuarterly Inspection at the rate of 25% no

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection ServicesSubmit this electronically ONLY.Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this contract. Type each response in the fields provided.

REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

16 East Point Drive Bedford, NH 03110

E-mailTelephone

For fire alarm maintenance please provide an inventory of your existing system below.

Please include the quantity of the following peripherals:

For each system (not just panel), please confirm whether conventional or addressable:

Indicate the frequency of inspection services you would like

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested.

Additional Information, if necessary

(603) 666-3336

Agency NameNH Department of Transportation Maintenance District 5

Facility Location & Address to be serviced y41A Kendall Pond RoadDerry, NH 03038

Hours of Operation of Facility7 AM to 3:30 PM

Remit Address for Invoices 16 East Point Drive Bedford, NH 03110Facility Contact Person Gary S. Clifford

[email protected]

Current Vendor NoneDate of Last Inspection Jul-16

Manufacturer/Brand of Equipment On left - King-Fisher Mamoth Fire Alarms Inc.; On right - Notifier by HoneywellModel of panel On left KFRTI-8S; On right Fire Warden 100-2Date of installation 2016Number of subpanels, if applicable 2Number of preaction panels, if applicable 0Number of devices that feeds the panels 58Number of pull stations 8Number of heat detectors 0Number of smoke detectors 8Number of battery backups 2

Audio-Visual Units 34Duct Detectors 0C/O Detectors 7Door Holders 0NACs/power supplies 1

Conventional no

Other: repais as needed

7 AM to 3:30 PM, scheduled in advance with proper notification and preferably early AM

System monitored via radio fire notifier by Derry Fire Department

Addressable yes

Annually at a rate of 100% yesQuarterly Inspection at the rate of 25% no

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection ServicesSubmit this electronically ONLY.Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this contract. Type each response in the fields provided.

REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

16 East Point Drive Bedford, NH 03110

E-mailTelephone

For fire alarm maintenance please provide an inventory of your existing system below.

Please include the quantity of the following peripherals:

For each system (not just panel), please confirm whether conventional or addressable:

Indicate the frequency of inspection services you would like

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested.

Additional Information, if necessary

(603) 666-3336

Agency NameNH Department of Transportation Maintenance District 5

Facility Location & Address to be serviced 54 Shadow Lake RoadSalem, NH 03079

Hours of Operation of Facility7 AM to 3:30 PM

Remit Address for Invoices 16 East Point Drive Bedford, NH 03110Facility Contact Person Gary S. Clifford

[email protected]

Current Vendor NoneDate of Last Inspection under construction, should be installed and inspected by 1/2018

Manufacturer/Brand of Equipment On left - Silent Knight by Honeywell; On right - DigitizeModel of panel On left - IFP-100ECS; on right RAD-8LSDate of installation 2017Number of subpanels, if applicable 2Number of preaction panels, if applicable 0Number of devices that feeds the panels 54Number of pull stations 5Number of heat detectors 10Number of smoke detectors 18Number of battery backups 1

Audio-Visual Units 19Duct Detectors 2C/O Detectors 2Door Holders 4NACs/power supplies 1

Conventional no

Other: repais as needed

7 AM to 3:30 PM, scheduled in advance with proper notification and preferably early AM

System monitored via radio fire notifier by Salem Fire Department

Addressable yes

Annually at a rate of 100% yesQuarterly Inspection at the rate of 25% no

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name DNCR, Forests and Lands

Facility Location & Address to be serviced

629 B Main street Lancaster, NH 03584

Hours of Operation of Facility 08:00-4:00 M-F

Remit Address for Invoices 172 Pembroke Road, Concord, NH 03302 Facility Contact Person John Accardi

E-mail [email protected] Telephone 603-788-4157 ext. 301

Current Vendor Capitol Alarm Systems Date of Last Inspection 10-4-17

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4002 Date of installation ? Number of subpanels, if applicable Number of pre-action panels, if applicable Number of devices that feeds the panels ? Number of pull stations 5 Number of heat detectors 19 Number of smoke detectors 20 Number of battery backups

Please include the quantity of the following peripherals: Audio-Visual Units 8

Duct Detectors 0 C/O Detectors ? Door Holders 0 NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional ?

Addressable ??

Indicate the frequency of inspection services you would like Annually at a rate of 100%

Quarterly Inspection at the rate of 25% X Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 08:00-4:00 M-F

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name DAS BFAM

Facility Location & Address to be serviced

Dolloff Building 117 Pleasant St Concord NH 03301

Hours of Operation of Facility 7:30 to 4:00

Remit Address for Invoices State of NH BFAM 129 Pleasant St Concord NH 03301 Facility Contact Person Douglas Burnham

E-mail [email protected] Telephone 603-271-9555

Current Vendor Simplex Date of Last Inspection 10/2017

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Notifier

Model of panel DR-A4R Date of installation 2007 Number of subpanels, if applicable 1 Number of pre-action panels, if applicable 0 Number of devices that feeds the panels Number of pull stations 20 Number of heat detectors 2 Number of smoke detectors 100 Number of battery backups 4

Please include the quantity of the following peripherals: Audio-Visual Units 117

Duct Detectors 0 C/O Detectors 0 Door Holders 8 NACs/power supplies 4

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable X

Indicate the frequency of inspection services you would like Annually at a rate of 100% X

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 7:30 to 4:00

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Safety

Facility Location & Address to be serviced Marine Patrol 3 Higgins dr Belmont NH 03220

Hours of Operation of Facility 24

Remit Address for Invoices 33 Hazen Dr Concord 03305 Facility Contact Person Jim Minery

E-mail [email protected] Telephone 603-419-9451

Current Vendor None Date of Last Inspection None

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Notifier

Model of panel AFP 200 Number of subpanels, if applicable Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations 4 Number of heat detectors 4 Number of smoke detectors 22 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units

Duct Detectors C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable yes

Indicate the frequency of inspection services you would like Annually at a rate of 100% yes

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 8 am to 3 pm

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Safety

Facility Location & Address to be serviced DMV MRT warehouse 23 Hazen Dr Concord

Hours of Operation of Facility 8-415

Remit Address for Invoices 33 Hazen Dr Concord 03305 Facility Contact Person Jim Minery

E-mail [email protected] Telephone 603-419-9451

Current Vendor None Date of Last Inspection None

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Mircon

Model of panel FX-2000

Date of installation 12/8/2007

Number of subpanels, if applicable Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations 2 Number of heat detectors 0 Number of smoke detectors 10 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units

Duct Detectors C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable yes

Indicate the frequency of inspection services you would like Annually at a rate of 100% yes

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 8 am to 3 pm

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Safety

Facility Location & Address to be serviced Dover DMV 50 Boston Harbor rd Dover NH 03820

Hours of Operation of Facility 8-5

Remit Address for Invoices 33 Hazen Dr Concord 03305 Facility Contact Person Jim Minery

E-mail [email protected] Telephone 603-419-9451

Current Vendor None Date of Last Inspection None

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Notifier

Model of panel AFP 200 Number of subpanels, if applicable Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations 4 Number of heat detectors 4 Number of smoke detectors 22 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units 8

Duct Detectors 1 C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable yes

Indicate the frequency of inspection services you would like Annually at a rate of 100% yes

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 8 am to 3 pm

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name NH Department of Safety, Emergency Services and Communications

Facility Location & Address to be serviced

Dwinell Building; 50 Communications Drive, Laconia, NH, 03246

Hours of Operation of Facility 24/7

Remit Address for Invoices 50 Communications Drive, Laconia,NH,03246 Facility Contact Person Mike Haskell

E-mail [email protected] Telephone 603-496-9643

Current Vendor Date of Last Inspection

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Notifier

Model of panel AFP-400 Date of installation July 2000 Number of subpanels, if applicable 1 panel 2 zones Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations 10 Number of heat detectors 13 Number of smoke detectors 68 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units

Duct Detectors 5 C/O Detectors Door Holders 4 NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable Addressable

Indicate the frequency of inspection services you would like Annually at a rate of 100% Annully

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 8:15 – 4:15 Monday - Friday

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Safety

Facility Location & Address to be serviced Fire Standards and Training ARRF building 98 Smokey Bear Blvd Concord NH 03301

Hours of Operation of Facility 24

Remit Address for Invoices 33 Hazen Dr Concord 03305 Facility Contact Person Jim Minery

E-mail [email protected] Telephone 603-419-9451

Current Vendor None Date of Last Inspection None

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Firelite

Model of panel MS-5VD Number of subpanels, if applicable Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations 5 Number of heat detectors 2 Number of smoke detectors 2 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units 8

Duct Detectors 1 C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable yes

Indicate the frequency of inspection services you would like Annually at a rate of 100% yes

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 8 am to 3 pm

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Safety

Facility Location & Address to be serviced Fire Standards and Training Dormitory 98 Smokey Bear Blvd Concord NH 03301

Hours of Operation of Facility 24

Remit Address for Invoices 33 Hazen Dr Concord 03305 Facility Contact Person Jim Minery

E-mail [email protected] Telephone 603-419-9451

Current Vendor None Date of Last Inspection None

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4010 Number of subpanels, if applicable Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations 14 Number of heat detectors 13 Number of smoke detectors 37 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units 103

Duct Detectors 5 C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable yes

Indicate the frequency of inspection services you would like Annually at a rate of 100% yes

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 8 am to 3 pm

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Safety

Facility Location & Address to be serviced Fire Standards and Training Admin Building, Firehouse and Maintenance Building 98 Smokey Bear Blvd Concord NH 03301

Hours of Operation of Facility 24

Remit Address for Invoices 33 Hazen Dr Concord 03305 Facility Contact Person Jim Minery

E-mail [email protected] Telephone 603-419-9451

Current Vendor None Date of Last Inspection None

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Honeywell

Model of panel MS 900 Number of subpanels, if applicable Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations 49 Number of heat detectors 11 Number of smoke detectors 31 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units

Duct Detectors C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable yes

Indicate the frequency of inspection services you would like Annually at a rate of 100% yes

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 8 am to 3 pm

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Safety

Facility Location & Address to be serviced

Marine Patrol HQ 31 Dock Road Gilford NH

Hours of Operation of Facility 24

Remit Address for Invoices Same Facility Contact Person James Minery

E-mail [email protected] Telephone 603-419-9451

Current Vendor Date of Last Inspection

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Notifier

Model of panel NFW2-100 Date of installation 8/2016 Number of subpanels, if applicable 1 Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations 11 Number of heat detectors 9 Number of smoke detectors 48 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units 45

Duct Detectors 1 C/O Detectors 1 Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable yes

Indicate the frequency of inspection services you would like Annually at a rate of 100% yes

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested.

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Safety

Facility Location & Address to be serviced Safety Warehouse 41 Hazen DR Concord nh

Hours of Operation of Facility 8:15-4:15

Remit Address for Invoices 33 Hazen Dr Concord 03305 Facility Contact Person Jim Minery

E-mail [email protected] Telephone 603-419-9451

Current Vendor None Date of Last Inspection None

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Fire-Lite

Model of panel MS-5UD

Date of installation 2/8/2013

Number of subpanels, if applicable Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations 5 Number of heat detectors 0 1 23 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units

Duct Detectors C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable yes

Indicate the frequency of inspection services you would like Annually at a rate of 100% yes

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 8 am to 3 pm

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Safety

Facility Location & Address to be serviced

Troop A / Epping DMV 315 Calef Highway Epping

Hours of Operation of Facility 24 hours State Police 8-415 DMV

Remit Address for Invoices 33 Hazen Dr Concord 03305 Facility Contact Person Jim Minery

E-mail [email protected] Telephone 603-419-9451

Current Vendor None Date of Last Inspection None

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Notifier

Model of panel AFP 200

Date of installation 8/8/2007

Number of subpanels, if applicable Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations 4 Number of heat detectors 17 Number of smoke detectors 23 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units

Duct Detectors C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable yes

Indicate the frequency of inspection services you would like Annually at a rate of 100% yes

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 8 am to 3 pm

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Safety

Facility Location & Address to be serviced

Troop C / Keene DMV 4 Meadow Brook Rd Keene

Hours of Operation of Facility 24 hours State Police 8-415 DMV

Remit Address for Invoices 33 Hazen Dr Concord 03305 Facility Contact Person Jim Minery

E-mail [email protected] Telephone 603-419-9451

Current Vendor None Date of Last Inspection None

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Notifier

Model of panel AFP 200

Date of installation 8/8/2007

Number of subpanels, if applicable Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations 4 Number of heat detectors 17 Number of smoke detectors 23 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units

Duct Detectors C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable yes

Indicate the frequency of inspection services you would like Annually at a rate of 100% yes

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 8 am to 3 pm

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Safety

Facility Location & Address to be serviced

Troop D 139 Iron Works rd Concord

Hours of Operation of Facility 24

Remit Address for Invoices 33 hazen Dr Concord Facility Contact Person James Minery

E-mail [email protected] Telephone 603-419-9451

Current Vendor N/A Date of Last Inspection N/A

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4010 Date of installation 11/2001 Number of subpanels, if applicable 1 Number of pre-action panels, if applicable 1 Number of devices that feeds the panels Number of pull stations 9 Number of heat detectors 9 Number of smoke detectors 24 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units 32

Duct Detectors 2 C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable yes

Indicate the frequency of inspection services you would like Annually at a rate of 100% yes

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested.

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Safety

Facility Location & Address to be serviced

Troop E / Tamworth DMV 1864 White Mountain Highway Tamworth

Hours of Operation of Facility 24 hours State Police 8-415 DMV

Remit Address for Invoices 33 Hazen Dr Concord 03305 Facility Contact Person Jim Minery

E-mail [email protected] Telephone 603-419-9451

Current Vendor None Date of Last Inspection None

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Notifier

Model of panel AFP 200

Date of installation 8/8/2007

Number of subpanels, if applicable Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations 4 Number of heat detectors 17 Number of smoke detectors 23 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units

Duct Detectors C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable yes

Indicate the frequency of inspection services you would like Annually at a rate of 100% yes

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 8 am to 3 pm

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name Safety

Facility Location & Address to be serviced Troop F / Twin Mt DMV 549 Route 302 Twin Mountain, NH 03595

Hours of Operation of Facility 24 hours State Police 8-415 DMV

Remit Address for Invoices 33 Hazen Dr Concord 03305 Facility Contact Person Jim Minery

E-mail [email protected] Telephone 603-419-9451

Current Vendor None Date of Last Inspection None

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Notifier

Model of panel AFP 200

Date of installation 8/8/2007

Number of subpanels, if applicable Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations 4 Number of heat detectors 17 Number of smoke detectors 23 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units

Duct Detectors C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable yes

Indicate the frequency of inspection services you would like Annually at a rate of 100% yes

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. 8 am to 3 pm

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name NH Dept of Transportation

Facility Location & Address to be serviced

65 Dump Rd, New London, NH 03257

Hours of Operation of Facility 7:00am-3:30pm Mon-Fri

Remit Address for Invoices 8 Eastman Hill Rd Enfield, NH 03748 Facility Contact Person Jon Johnson

E-mail [email protected] Telephone 603-448-2654

Current Vendor Capitol Alarm Systems Date of Last Inspection unknown

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Honeywell Firelite

Model of panel MS-9200UDLS Date of installation 12/2014 approx. Number of subpanels, if applicable none Number of pre-action panels, if applicable none Number of devices that feeds the panels 31 Number of pull stations 2 Number of heat detectors 19 Number of smoke detectors 3 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units 5

Duct Detectors n/a C/O Detectors n/a Door Holders n/a NACs/power supplies n/a

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable ( yes )

Indicate the frequency of inspection services you would like Annually at a rate of 100% annual

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 7:00am-3:30pm ( normal work hours)

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name NH DOT Bureau of Traffic

Facility Location & Address to be serviced

18 Smokey Bear Blvd, Concord, NH 03301.

Hours of Operation of Facility 8am-4pm Monday thru Friday

Remit Address for Invoices NH DOT Bureau of Traffic P.O. Box 483, Concord NH 03302-0483 Facility Contact Person Roger Caron, Safety & Environment Coordinator

E-mail [email protected] Telephone 603-271-2292

Current Vendor Norris Inc. 2257 Broadway, South Portland Maine Date of Last Inspection Wednesday September 6th 2017.

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Building A Building B Building D

Model of panel Simplex 2001-8001 Simplex 4005 Simplex 4005 Number of subpanels, if applicable N/A N/A N/A Number of pre-action panels, if applicable N/A N/A N/A Number of devices that feeds the panels 9 9 6

Number of heat detectors N/A N/A 5 Number of smoke detectors 1 1 N/A Number of battery backups 1 1 1

Please include the quantity of the following peripherals: Audio-Visual Units 11 9 6

Duct Detectors 1 Fenwall DH-55 1 Simplex Smoke Head 4098-9681 N/A C/O Detectors N/A N/A N/A Door Holders N/A N/A N/A NACs/power supplies 3 1 1

For each system (not just panel), please confirm whether conventional or addressable: Conventional 1

Addressable 1 1

Indicate the frequency of inspection services you would like Annually at a rate of 100% 1 1 1

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. Between 8am and 4pm Monday thru Friday.

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name NH DOT District 1

Facility Location & Address to be serviced 180 Spruceville Rd 116 Brown Rd West Milan NH 03588 Groveton NH 03582

Hours of Operation of Facility 7-330

Remit Address for Invoices NH DEPT OF Transportation 641 Main St, Lancaster NH 03584

Facility Contact Person Eric Crane E-mail [email protected]

Telephone 603-788-4641 Current Vendor Capital Alarm Systems

Date of Last Inspection

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment

Model of panel Date of installation Number of subpanels, if applicable Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations Number of heat detectors Number of smoke detectors Number of battery backups

Please include the quantity of the following peripherals: Audio-Visual Units

Duct Detectors C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable

Indicate the frequency of inspection services you would like Annually at a rate of 100%

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested.

Additional Information, if necessary

These 2 alarms have been set up for many, many years and is basically for burglar alarms.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name NHDOT – District 3

Facility Location & Address to be serviced

310 Patrol Shed located at 608 Eaton Rd. (NH153), Conway, NH

Hours of Operation of Facility 7:00 am to 3:30 pm

Remit Address for Invoices NHDOT – District 3 2 Sawmill Road, Gilford, NH 03249 Facility Contact Person Brad Allan – Patrol Foreman

E-mail [email protected] Telephone 603-419-0801

Current Vendor Unknown Date of Last Inspection Unknown

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Fire Lite Alarm by Honeywell

Model of panel MS-10UD Date of installation 2010 +/- Number of subpanels, if applicable 0 Number of pre-action panels, if applicable 0 Number of devices that feeds the panels unknown Number of pull stations 8 Number of heat detectors 17 Number of smoke detectors 8 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units 15

Duct Detectors C/O Detectors 0 Door Holders 0 NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional Conventional

Addressable

Indicate the frequency of inspection services you would like Annually at a rate of 100% X

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. Between 7:00am and 3:30 pm Monday through Friday

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name NHDOT District 6

Facility Location & Address to be serviced

50 Gerrish Road Dover, NH 03820

Hours of Operation of Facility 630AM -300PM M-F and as needed for winter maintenance

Remit Address for Invoices PO Box 740 Durham, NH Facility Contact Person Doug Almon

E-mail [email protected] Telephone 603-868-1133

Current Vendor Total security Date of Last Inspection 4/18/2017

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment

Model of panel Fire Warden Date of installation Number of subpanels, if applicable Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations 2 Number of heat detectors 10 Number of smoke detectors 6 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units 12

Duct Detectors C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable

Indicate the frequency of inspection services you would like Annually at a rate of 100% annually

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. M-F---- 7-3

Additional Information, if necessary

Monitored system using Fire Warden notifier, digital, SLC, 1, class B, Central alarm

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name NHDOT District 6

Facility Location & Address to be serviced

253 Epping Road Exeter, NH

Hours of Operation of Facility 630AM -300PM M-F and as needed for winter maintenance

Remit Address for Invoices PO Box 740 Durham, NH Facility Contact Person Doug Almon

E-mail [email protected] Telephone 603-868-1133

Current Vendor Total security Date of Last Inspection 4/18/2017

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment EST FireShield Plus10-Zone Conventional

Model of panel FIX -10 Date of installation 2017 Number of subpanels, if applicable Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations 2 Number of heat detectors 9 Number of smoke detectors 2 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units 6

Duct Detectors 1 C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable

Indicate the frequency of inspection services you would like Annually at a rate of 100% annually

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. M-F---- 7-3

Additional Information, if necessary

EST FireShield Plus -10-Zone Conventional type connected Town of Exeter Master Box

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name NHDOT District 6

Facility Location & Address to be serviced

1011 Parker Mountain Road Strafford, NH 03884

Hours of Operation of Facility 630AM -300PM M-F and as needed for winter maintenance

Remit Address for Invoices PO Box 740 Durham, NH Facility Contact Person Doug Almon

E-mail [email protected] Telephone 603-868-1133

Current Vendor Total security Date of Last Inspection

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Fire Warden-100-2 (E) Rev 3

Model of panel NFW2-100 Date of installation 2017 Number of subpanels, if applicable Number of pre-action panels, if applicable Number of devices that feeds the panels Number of pull stations 4 Number of heat detectors 11 Number of smoke detectors 3 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units 12

Duct Detectors C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable YES

Indicate the frequency of inspection services you would like Annually at a rate of 100% annually

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. M-F---- 7-3

Additional Information, if necessary

Fire warden -100-2(E) Rev 3 intelligent addressable FACP notifier by Honeywell

ADMINISTRATIVE OFFICE OF THE COURTS

FIRE ALARM:

1 Fire Alarm Control Panel 8 IDC 4 NAC red1 2 IDC & 2 NAC Relay Module Class B1 8 Point I/O Module1 City Circuit Module1 Power Distribution Module1 Class A adapter Module2 10 Amp Hour Batteries1 Gamewell Master Box M34-921 Red Strobe Light1 Green Strobe Light1 Annunciator8 Pull Stations12 Audio Visual Units 24 VDC 15 CD Red4 Visual Only 24 VDC 15 CD red4 Low Profile Photoelectric Smoke Detectors2 4 Wire Base w/Relay

BRIDGES HOUSE

FIRE ALARM:

1 GE Firefox1 FB 4600 central station digital transmitter2 Horn/Strobe4 Smoke detectors28 Heat detectors2 Manual pull stations2 12V 7.5AH batteries

EMERGENCY OPERATION CENTER (110 SMOKEY BEAR BLVD.)

FIRE ALARM:

1 Master Box #88451 FCI E3 Series Panel3 Remote Annunciators (KDU)12 Manual Stations

18 135*F/T R/R Heat Detectors11 Sprinkler Water Flow17 Sprinkler Supervisory29 Photo Electric Smoke Detector11 Photo Electric Duct Smoke Detector3 CO2 Detector10 Remote Test Station Key Operated51 Electronic Horn/Strobe4 Sirens28 Strobe Only8 12V 12 Amp Batteries #ps121202 Red Strobe2 Green Strobe1 Fixed Red Light over Knox Box

HEALTH & HUMAN SERVICES BUILDING

FIRE ALARM:

PHASE I & II:

3 Gamewell EST-3 Addressable Analog Control Panel

3 3-CPU Central Processor Module3 3-RS485 Communication Card2 3-SSCD Analog Loop Card1 3-OPS City Tie Module8 3-ZA-30 30 Watt Amplifiers1 3-LCD Display1 3-ASU/4 Audio Controller4 3-12/S2Y Switch Modules1 3-PPS/M Primary Power Supply3 3-BPS/M Booster Power Supplies1 3-CAB-21B Wall Box Red with Cat 30 Lock1 3-CAB-21D Outer Door Red With Cat 30 Lock3 3-CHAS-7 Chassis Assemblies3 PW1260 60 Amp Hour Batteries1 70970 Battery Cabinet with Cat 30-Lock1 EST-3 Addressable Analog Control Sub Panel1 3-CPU Central Processor Module1 3-RS485 Communicator Card2 3-SSDC Analog Loop Cards6 3-ZA-30 30 Watt Amplifiers1 3-LCD Display1 SAN-MIC II Remote Mic Module

4 3-12/S2Y Switch Modules1 3-PPS/M Primary Power Supply3 3-BPS/M Booster Power Supplies1 3-CAB 21B Wall Box Red w/Cat 30 Lock1 3-CAB-21D Outer Door Red with Cat 30 Lock2 PW1260 60 Amp Hour Batteries1 70970 Battery Cabinet1 PT-1 System Printer1 M34-56 Gamewell Masterbox with AC-1 Fire Alarm Pedestal1 SL-5 Red WP Beacon Light

199 SIAG-PS Photoelectric Smoke Detectors and bases

55E-70-24110W-FR Speaker Strobes 110 Candela with Surface Boxes SBB-R

20E-70-2415W-FR Speaker Strobes 15 Candela with Surface Boxes SBB-R

72 E70-2430W-FR Speaker Strobes 30 Candela with Surface Boxes SBB-R

63 E702475W-FR Speaker Strobes 75 Candela with Surface Boxes SBB-R

18 RS2415W-FR Strobes 15 Candela with SHBB-R Surface Back Boxes

39 SIGA-278 Pull Stations with 276-RSB Surface boxes and Cat 30 Locks

26 SIGA-DH Duct Smoke Detectors26 SIGA-PS Smoke Detectors26 SIGA-DTS Remote Test Switches26 SIGA-CR Control Modules26 SIGA-LED Indication Lights26 6261-003 Sampling Tubes5 SIGA-CR Control Modules5 SIGA-CT1 Monitor Modules4 SD-240 Beam Smoke Detectors with Receivers17 SIGA-CR Control Module Damper Controls24 SIGA-CR Control Modules/Elevator Recall6 #624 200 Degree Fixed Heat Detectors for Elevator Shafts18 DSM-12/24R Synchronizing Modules

LABS:

4 3-CAB21B - Wall Box for 3 3-CHAS711 3-CAB21DR - Red Door Package for 3-CAB21B

12 3-CHAS7 - Mounting Chassis For 7 LRM or 1 CPU, 1 monitor and 4 LRM

4 3-CPU1 - Main Control for FACP or Network Node4 3-LCD - Main Display for FACP or Network Node4 3-PPS/M - Primary Power Supply w/Monitor Module8 3-BPS/M - Booster Power Supply w/Monitor Module

4 3-SSDC - Single Analog/Addressable Signature Loop Controller

18 3-ZA20A - 20 Watt Class “A/B” Network Comm Module2 3-REMICP - Panel Mount Remote Microphone4 3-RS485 - RS-485 Class “A/B” Network Comm Module8 DCS-50L - 50 AH Batteries4 BCA - Battery Cabinet

231 SIGA-PS - Analog/Addressable Photo Smoke Detector Head

40 SIGA-HFS - Analog/Addressable 135 Fixed Temp Detector Head

200 SIGAA-SB - Analog/Addressable Standard Detector Base

6 SIGA-DH - Duct Housing for Analog/Addressable Smoke Detector

6 SIGA-PS - Analog/Addressable Photo Smoke Detector Head

6 SIGA-SB - Analog/Addressable Standard Detector Base6 SIGA-DTS - Addressable Duct Function Test Module6 SIGA-CR - Addressable Form “C” Relay Module6 6261-003 - 42” Sampling Tube for SIGA-DH Duct Housing6 SIGA-LED - Remote LED for SIGA Detector40 SIGA-CT1 - Addressable Single Input Module

22 SIGA-MAB - SIGA-UIO# Addressable Class “A” Signal CKT Plug-In Module

24 SIGA-CR - Addressable Form “C” Relay Module

22 SIGA-279 - Addressable Double Action Manual Pull Station

4 SIGA-UIO6R - 6 Slot Universal Input/Output Module Board W/Riser Inputs

100 RSS24MCWFR - Multi Candela Storage

22 DSM-12/24-R - Sync Module (2) Class “B” CKT/(1) Class “A” CKT

120 E7024MCWFR - Red Speakers/Strobe1 RSSWP-2475WFR - Weather Proof Strobe1 WPSBB-R - Surface Weather Proof Box Red1 ET1010R - Weather Proof Strobe Speaker1 IOBR - Weather Proof Back Box30 1504-N5 - Flush Mounted 110 AC Door Holder

HEALTH & HUMAN SERVICES BUILDING CONT’D

PRE-ACTION SYSTEM (29 Hazen Drive):

10 Detectors in 3 Vaults L.L. West1 PS-10-2A Pressure Switch1 PS-40-2A Pressure Switch1 OSySV – 2” Valve 1 3” Deluge Valve Model E-1 1 Easy Rider Check Valve Model F-1 250PSI Flange Groove 1 Air Compressor General Air Products, Model #OL11016AC1 1Vi Viking PAR -3 Deluge B1 Pre Action Control Panel3 Speaker / Strobes Vaults

JOHNSON HALL

FIRE ALARM:

1 Simplex 4005 Main Fire Alarm Panel with Digital Transmitter SAF51 Simplex 2098-9603 Smoke Detectors76 Simplex 2098-9464 Rate of Rise Heat Detectors9 Simplex 2098-9460 Fixed Heat Detectors 135 Degrees F11 Simplex 2098-9101 Audio Visual Units9 Simplex 2099-9201 Manual Pull Stations1 Gamewell Master Box2 Remote Annunciators1 Outside Light

DEPARTMENT OF JUSTICE

FIRE ALARM:

1 Gamewell Box1 Unimode 15 Mount Back Box #4520-141 Unimode Door #4520-1111 Unimode Chassis #4520-0151 Unimode Power Supply #4520-8121 Unimode Battery Supply #4520-6381 Unimode Space Age Annunciator #M162 Unimode Water Flow Modules #4520-5291 Unimode Signal Module #4520-70125 Unimode GX 90S-4HWR Horn/Strobes13 Unimode Horn/Light Units6 Unimode Heat Detectors

80 Unimode Smoke Detectors8 Unimode 3536-611T Smoke Detectors13 Unimode Pull Stations1 Unimode Power Extender #4520-9121 Unimode Switch Module #4520-4351 Unimode Control #4520-8381 Simplex 4004 FACP

LEGISLATIVE OFFICE BUILDING

FIRE ALARM:

1 Honeywell Notifier1 Remote zone annunciator (exterior)1 Gamewell master box1 FB-4600 central station digital transmitter1 Elevator recall module

148 Heat detectors44 Smoke detectors2 Duct type smoke detectors15 Manual pull stations28 Horn/strobe evacuation devices12 Magnetic door releases2 Sprinkler water flow switches4 Gate valve tamper switches2 Gate valve tamper switches for elevator shafts

LONDERGAN HALL

FIRE ALARM:

1 Notifier NFS-3030 Main Fire Alarm Panel36 Simplex 2098-9461 Fixed Heat Detectors 200 degrees F54 Simplex 2098-9603 Smoke Detectors14 Simplex 2098-9101 Audio Visual Units32 Simplex 2098-9464 Rate of Rise Heat Detectors1 Gamewell Masterbox

M&S BUILDING

FIRE ALARM:

1 Notifier NFS-320

2 Powerpath Boosters1 Annuciator Panel21 Pull Stations

135 Photo Detectors16 Heat Detectors79 Horn & Strobes65 Strobes23 Monitior Modules11 Tamper Switches7 Pressure Switches5 Flow Switches17 Relay Modules4 Fixed Heat Detectors1 Control Module

MONADNOCK MILL

FIRE ALARM:

1 Hochiki 4127 Fire Panel1 Remote zone annunciator1 Gamewell masterbox with red light27 Heat detectors 45 Smoke detectors14 Manual pull stations17 Horn/strobe evacuation devices

MORTON BUILDING

FIRE ALARM:

Notifier AFP 406 Fire Alarm Control Panel 1 Sub Panel

Fire department connection1 Remote annunciator DR-A5R11 Remote F/A Control Panel2 1255 Batteries

2 Heat/Elevator Shaft76 Smoke Detectors17 Pull Stations

149 Horn/Strobe

PRE-ACTION SYSTEM:

1 Viking Pre-Action Fire Panel (Par 3)1 1 ½” Deluge Valve (E3)1 Asco Shutoff Actuating Valve1 Detectors in G-461 Pull Station in G-462 Batteries (12V 12AH)1 3” Deluge Valve (B-1)

STATE LIBRARY

FIRE ALARM SYSTEM:

1 Silent Knight IFP-10004 Loop Expander1 Remote Annunciator16 Manual Pull Stations

116 Photo Detectors31 Heat Detectors6 Mini Monitor Modules21 Monitor Modules3 Relay Module2 Power Expander1 Green Beacon1 Red Beacon1 Master Trip Box2 24VDC Beam Detectors

DEPARTMENT OF MOTOR VEHICLE

FIRE ALARM:

1 Control Panel – FCI E36 Batteries7 Manual Station46 ION/PHOTO Smoke Detectors8 Heat Detectors6 Duct Detectors2 Strobe/Visual Device1 Graphic Annunciator

2 Travel

OLD LABOR BUILDING

FIRE ALARM:

1 GE Firefox FX-101 Gamewell master box1 Central station transmitter72 Heat detectors12 Smoke detectors10 Horn/Strobe Units5 Manual pull stations

RECORDS AND ARCHIVES (21 Fruit Street)

FIRE ALARM:

1 4100U - Simplex Fire Panel2 4009-9201 - NAC Power Extenders14 4099-9003 - Pull Stations

170 4098-9714 - Smoke Sensors170 4098-9792 - Smoke Base2 4098-9789 - LED Sensor Base28 4098-9733 - Heat Sensor28 4098-9792 - Heat Base2 4098-9789 - LED Heat Base4 5624 - Heat Detector Fixed 194 Degrees5 2096-9796 Duct Smokes tube5 2098-9806 - Remote Test Stations5 4098-9843 - Relays (parn-sd)2 4090-9101 - Zone Adapter Modules4 2098-9808 - Remote Alarm Indicator4 4090-9002 - Individual Address Module ®27 4090-9001 - Individual Address Module (s)34 4906-9127 - Multicandella H/S Wall Mount28 4906-9128 - Multicandella H/S Ceiling Mount1 98BR-G1 - Strobe-Red1 98BG-G1 - Strobe-Green13 4906-9101 - Multicandella Strobe Wall Mount16 4906-9102 - Multicandella Strobe Ceiling Mount5 2088-9608 - Door Holders 24V dc

SAFETY BUILDING

FIRE ALARM:

Notifier panel NFS-640Central station transmitterGamewell fire department connectionRemote Annunciator

99 Heat Detectors118 Smoke Detectors24 Pull Stations95 Horn/Strobe Units3 Connection to Halon system-computer room63 Strobes

61 SOUTH SPRING STREET

FIRE ALARM:

1 4020-7003 - Simplex Fire Control Panel1 4020-7003 - Master Controller1 4020-0305 - 8 pt. I/O Module1 4020-6084 - Version 9 Software1 2190-9169 - Short Circuit Isolator1 4602-7101 - Graphic Driver I/O Board1 W.P. xL8 - Graphic Annunciator24 4903-9417 - Horn/Strobe 2 wire 15 candela8 4903-9418 - Horn/Strobe 2 wire 75 Candela20 4904-9331 - Strobe 15 Candela4 4904-9332 - Strobe 75 Candela4 4905-9938 - Smartsync Control Module1 WP-98BG-G1 - Strobe-Green 24VDC1 98BR-G1 - Strobe-Red 24VDC16 2099-9761 - Pull Stations58 4098-9714 - Smoke Sensors4 4098-9714 - Smoke Sensor LED4 4098-9756 - Duct Smoke Sensor4 2098-9797 - Tube2 4098-9733 - Heat Sensor2 4098-9789 - Heat Sensor LED Output Base7 2098-9808 - Remote Alarm Indicator4 2098-9806 - Remote Test Station4 4098-9843 - Relays11 2190-9172 - Individual Addressable Modules Supv4 2190-9163 - Zone Adapter Module

SPAULDING HALL

FIRE ALARM:

1 4002-8001 - Simplex Fire Alarm Control Panel

Containing:1 4002-6001 - 120 VAC Operation1 4002-7001 - CPU with 8 Zones, 2 SIG. CIR, Class B2 4002-0102 - 4 Point Zone Disconnect Modules1 4002-2001 - #2 Cabinet Package

2 2081-9274 - 10 AH Maint. Free System Batteries1 Mini 10 Weatherproof Annunciator42 2098-9201 - Low Profile Photoelectric Smoke Detectors35 2098-9637 - Smoke Detector Bases5 2098-9536 - Detector Bases 4-Wire w/Relay SPDT 1 AMP5 2098-9739 - E.O.L. Trouble Relays86 2098-9439 - 135 Degrees Rate of Rise Heat Detectors14 2099-9201 - Manual Stations Single Action27 4903-9101 - Audio/Visual Strobe Units 24 VDC27 2901-9838 - Horns, Red 24 VDC Surface13 2098-9461 - Heat Detectors, 200 Degrees Fixed Temp1 2098-9806 - Remote Alarm Indicator w/Test Keyswitch1 2095-9011 - Local Energy Trip Exterior Master Box1 Digital Transmitter

STATE HOUSE

FIRE ALARM:

Mircom FX-2000Gamewell master boxMircom Power Supply

2 Fire Ray Beam Detectors in Reps HallHoneywell central station transmitterRemote Annunciator

173 Heat detectors74 Smoke detectors23 Horn/Strobe Units14 Strobe Lights18 Manual pull stations6 Magnetic door holders

PRE-ACTION SYSTEM:

1 Pre-action fire alarm control panel (FCI) with batteries1 Pull station1 Duct Detector

41

Fixed temperature heat detectors (Note: approximately 2/3 of the detectors are located within the floor/ceiling spaces and will be difficult to test)

STATE HOUSE ANNEX

FIRE ALARM:

Mircom FX-2000Mircom AnnunciatorMircom Power SupplyGamewell fire department master boxHoneywell central station transmitter

253 Heat detectors73 Smoke detectors26 Manual pull stations24 Evacuation horn/strobe lights13 Strobe Units18 Magnetic door releases

Sprinkler water flow switchGate valve tamper switch FBI Dialer

SUPREME COURT

FIRE ALARM:

1 FCI FC 72 Fire alarm control panel with stand by power1 Gamewell fire department master box1 Central station transmitter1 Remote annunciator90 Heat detectors54 Smoke detectors9 Manual pull stations34 Horn/Strobe Lights

SURPLUS WAREHOUSE

FIRE ALARM:

1 Honeywell Notifier NFS-3201 PS-B Booster1 Signal/Reversing Trouble Relay1 Auxiliary Device Actuation Module1 Signal Circuit Module1 Supervisory auxiliary relay board1 Subsequent alarm module1 Relay DPDT track (10 amp)12 Single Action Pull Stations1 Photoelectric Smoke Detector50 Horn/Strobes12 Strobe Lights1 16 Zone Annunciator1 Master Box1 120 VAC Red Light w/cage1 Red Strobe 12/28 Vac

DEPARTMENT OF TRANSPORTATION MECHANICAL SERVICES (33 Smokey Bear Blvd.)

FIRE ALARM:

1 Gamewell Master Fire Alarm Signal Box1 Fire Alarm System Control Panel AFP-200 Notifier3 Fire Alarm System Remove Panel FCCPS-24S879 Audible & Visual Alarm Signal2 Exterior Flashing Signal Beacon1 Exterior Flashing Signal Green Beacon3 Visual Only Alarm Signal ADA Rated17 Notifier Manual Pull Station4 Duct Smoke Detectors w/Remote Test Switch5 Smoke Detectors w/Remote Alarm Indicator1 Heat Detector w/Remote Alarm Indicator16 Monitor Zone Adapter Module – Notifier1 Knox Box

DEPARTMENT OF TRANSPORTATION MATERIAL RESEARCH LAB (5 Hazen Drive)

FIRE ALARM:

EST Fire Alarm System Containing:

1 2-WB3R - Red Surface Extended Back Box1 2-WB3DR - Red Surface Extended Door1 2-PPS/6A - Main Power Supply 6.4 AMP1 2-CTM - Analog Loop Controller Module & Display1 2-LCX - Analog Loop Expander Module1 2-CTM - Master Box Module1 SIGA-CC1 - Master Box Interface Used with 2-CTM4 ASLA 1075 - 7 AH Batteries2 MVP-U1 - 33 AH Batteries1 BCA - Battery Cabinet

16 M16 - 16 Zone Annunciator Common Positive Switch Negative

1 SAN-CPU - Power/Comm Card for San Series Module

1 SDR-32K - 32 Point San Annunciator Driver for Lamps or Relays

1 SAN 4R - Red 4 Module +1 CPU San Ann Cabinet1 BP-A - San Blank Filler Plate

2 PS 12/24-8MP - 8 AMP Signal Panel (2 Class “A” CKTS or 4 Class “B” CKTS)

26 SIGA-PS - Analog/Addressable Photo Smoke Detector Head

4 SIGA-HFS - Analgo/Addressable 135 Fixed Temp Detector Head

30 SIGA-SB - Analog/Addressable Standard Detector Base4 SIGA-SD - Analog/Addressable Duct Detector4 SIGA-SDTRK - Duct Function Test Module4 SD-T36 - 36” Sampling Tube for Siga-DH Duct Housing9 SIGA-LED - Remote LED for Siga-Detector5 SIGA-CT2 - Addressable Dual Input Module

2 SIGA-MCC1 - Siga-UIO#Addressable Class “B” Signal CKT Plug-In Module

2 SIGA-CR - Addressable Form “C” Relay Module

9 SIGA-278 - Addressable Double Action Manual Pull Station

1 SIGA-UIO6R - 6 Slot Universal Input/Output Module Board Wriser Inputs

30 NS-24MCW-FR - Multicandella Strobe1 ASWP-2475WFR - Weather Proof Horn Strobe

UPHAM WALKER

FIRE ALARM:

1 Honeywell Firolite2 12V 7.5 AH batteries3 Simplex #2008 9502 door holders9 Simplex #2903 9101 audio/visual units12 Simplex #2098 9464 heat detectors restroom25 Simplex #2093 9603 smoke detectors1 Ademco 221 Transmitter7 Pull stations11 Fixed temperature heat detectors

WALKER BUILDING

FIRE ALARM:

1 Control Panel8 Batteries1 Digital Dialer1 LCD Annunciator43 Manual Station

288 ION/Photo Smoke Detectors2 Heat Detectors3 Duct Detectors1 Field Power Supply/FCPS

150 Horn Strobe40 Strobe/Visual Device2 Elevator Recall

Glencliff Fire Alarm Equipment includes but is not limited to:

401 smoke detectors

Heat detectors

Pull stations

Emergency lighting fixtures

Fire alarm panels

Chip plant panel

Single station

52 pulls

24 analog thermal detectors

178 strobes

99 horn strobes

4 duct smoke alarms

6 flow switches

11 tamper switches

7 pressure switches

6 air dampers

Mammoth (MFA) AX series devices

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name DAS BFAM

Facility Location & Address to be serviced

NHH Laundry 127 Pleasant St Concord NH 03301

Hours of Operation of Facility 7:30 to 4:00

Remit Address for Invoices State of NH BFAM 129 Pleasant St Concord NH 03301

Facility Contact Person Douglas Burnham

E-mail [email protected] Telephone 603-271-9555

Current Vendor Simplex Date of Last Inspection 10/2017

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4001 Date of installation 1988 Number of subpanels, if applicable 0 Number of pre-action panels, if applicable 0 Number of devices that feeds the panels Number of pull stations 7 Number of heat detectors 40 Number of smoke detectors 4 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units 4

Duct Detectors 0 C/O Detectors 0 Door Holders 0 NACs/power supplies 1

For each system (not just panel), please confirm whether conventional or addressable: Conventional X

Addressable

Indicate the frequency of inspection services you would like Annually at a rate of 100% X7:

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 7:30 to 4:00

Additional Information, if necessary

Please note this system is to be replaced in 2018

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name DAS BFAM

Facility Location & Address to be serviced

Liberty House 119 Pleasant St Concord NH 03301

Hours of Operation of Facility 7:30 to 4:00

Remit Address for Invoices State of NH BFAM 129 Pleasant St Concord NH 03301 Facility Contact Person Douglas Burnham

E-mail [email protected] Telephone 603-271-9555

Current Vendor Simplex Date of Last Inspection 10/2017

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplea

Model of panel 4001 Date of installation 1988 Number of subpanels, if applicable 0 Number of pre-action panels, if applicable 0 Number of devices that feeds the panels Number of pull stations 4 Number of heat detectors 13 Number of smoke detectors 0 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units 3

Duct Detectors 0 C/O Detectors 0 Door Holders 0 NACs/power supplies 1

For each system (not just panel), please confirm whether conventional or addressable: Conventional X

Addressable

Indicate the frequency of inspection services you would like Annually at a rate of 100% X

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 7:30 to 4:00

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name DAS BFAM

Facility Location & Address to be serviced

Main Annex 1 Bancroft 105 Pleasant St Concord NH 03301

Hours of Operation of Facility 7:30 to 4:00

Remit Address for Invoices State of NH BFAM 129 Pleasant St Concord NH 03301 Facility Contact Person Douglas Burnham

E-mail [email protected] Telephone 603-271-9555

Current Vendor Simplex Date of Last Inspection 10/2017

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4001U Date of installation 2002 Number of subpanels, if applicable 2 Number of pre-action panels, if applicable 0 Number of devices that feeds the panels Number of pull stations 110 Number of heat detectors 72 Number of smoke detectors 222 Number of battery backups 7

Please include the quantity of the following peripherals: Audio-Visual Units 327

Duct Detectors 0 C/O Detectors 0 Door Holders 6 NACs/power supplies 7

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable X

Indicate the frequency of inspection services you would like Annually at a rate of 100% X

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 7:30 to 4:00

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name NH Police Standards & Training

Facility Location & Address to be serviced

17 Institute Drive, Concord

Hours of Operation of Facility 7:30a – 4:30p

Remit Address for Invoices Facility Contact Person Clem Hamilton

E-mail [email protected] Telephone 603-271-3978

Current Vendor Total Security Date of Last Inspection August 5

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment MirCom

Model of panel FX-2000 Date of installation July 2008 Number of subpanels, if applicable 1 Number of pre-action panels, if applicable Number of devices that feeds the panels 219 Number of pull stations 44 Number of heat detectors 81 Number of smoke detectors 85 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units 58

Duct Detectors 3 C/O Detectors 6 Door Holders 8 NACs/power supplies 2

For each system (not just panel), please confirm whether conventional or addressable: Conventional 151

Addressable 30

Indicate the frequency of inspection services you would like Annually at a rate of 100% X

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. First Saturday of August, 8am - noon

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name DOT Dist 4

Facility Location & Address to be serviced

19 Base Hill Road, Swanzey, NH

Hours of Operation of Facility Mon-Fri 7:00 am – 4:00 pm Apr-Nov and 24 hours/7days a week Nov - April

Remit Address for Invoices NH DOT – D4 19 Base Hill Road, Swanzey, NH 03446 Facility Contact Person

E-mail Telephone 603-352-2302

Current Vendor ? Date of Last Inspection 2/9/2012

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment MIRCOM

Model of panel FX2000 Date of installation 11/17/2007 Number of subpanels, if applicable 1 Number of pre-action panels, if applicable 0 Number of devices that feeds the panels 0 Number of pull stations 7 Number of heat detectors 16 Number of smoke detectors 14 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units 20

Duct Detectors C/O Detectors Door Holders NACs/power supplies

For each system (not just panel), please confirm whether conventional or addressable: Conventional Unknown

Addressable

Indicate the frequency of inspection services you would like Annually at a rate of 100% XXX

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 8am – 3pm

Additional Information, if necessary

Information provided is to the best of my knowledge. We also have boxes like the one shown. Not sure where they fall in the list. I counted them under the Audio-Visual Units.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection ServicesSubmit this electronically ONLY.Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this contract. Type each response in the fields provided.

REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

8:00 - 4:30

E-mailTelephone

NHESAgency Name

Facility Location & Address to be serviced

45 South Fruit Street

Hours of Operation of Facility

45 South Fruit Street attention accounts payableFacility Contact Person Jesse B Propri

[email protected] 419-9757

Remit Address for Invoices

Current Vendor Simplex GrinellDate of Last Inspection November

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection ServicesSubmit this electronically ONLY.Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this contract. Type each response in the fields provided.

REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

E-mailTelephone

Current Vendor noneDate of Last Inspection

NH Fish & Game, 11 Hazen Drive, Concord, NH 03301Facility Contact Person Richard Fink, P.E.

[email protected]

Remit Address for Invoices

NH Fish And Game DepartmentAgency Name

Facility Location & Address to be serviced

17 Hazen Drive, Concord, NH 03301

Hours of Operation of Facility8AM to 4PM, Monday through Friday

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection ServicesSubmit this electronically ONLY.Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this contract. Type each response in the fields provided.

REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

E-mailTelephone

Current Vendor noneDate of Last Inspection

NH Fish & Game, 11 Hazen Drive, Concord, NH 03301Facility Contact Person Richard Fink, P.E.

[email protected]

Remit Address for Invoices

NH Fish And Game DepartmentAgency Name

Facility Location & Address to be serviced

19 Hazen Drive, Concord, NH 03301

Hours of Operation of Facility8AM to 4PM, Monday through Friday

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection ServicesSubmit this electronically ONLY.Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this contract. Type each response in the fields provided.

REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

E-mailTelephone

8AM to 4PM, Monday through Friday

NH Fish And Game DepartmentAgency Name

Facility Location & Address to be serviced

Gregg Conservation Center, 90 Depot Road, Greenland, NH

Hours of Operation of Facility

NH Fish & Game, 11 Hazen Drive, Concord, NH 03301Facility Contact Person Richard Fink, P.E.

[email protected]

Remit Address for Invoices

Current Vendor noneDate of Last Inspection

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection ServicesSubmit this electronically ONLY.Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this contract. Type each response in the fields provided.

REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

E-mailTelephone

8AM to 4PM, Monday through Friday

NH Fish And Game DepartmentAgency Name

Facility Location & Address to be serviced

Great Bay Discovery Center, 89 Depot Road, Greenland, NH

Hours of Operation of Facility

NH Fish & Game, 11 Hazen Drive, Concord, NH 03301Facility Contact Person Richard Fink, P.E.

[email protected]

Remit Address for Invoices

Current Vendor noneDate of Last Inspection

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection ServicesSubmit this electronically ONLY.Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this contract. Type each response in the fields provided.

REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

E-mailTelephone

8AM to 4PM, Monday through Friday

NH Fish And Game DepartmentAgency Name

Facility Location & Address to be serviced

11 Hazen Drive, Concord, NH 03301

Hours of Operation of Facility

NH Fish & Game, 11 Hazen Drive, Concord, NH 03301Facility Contact Person Richard Fink, P.E.

[email protected]

Remit Address for Invoices

Current Vendor noneDate of Last Inspection

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection ServicesSubmit this electronically ONLY.Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this contract. Type each response in the fields provided.

REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

E-mailTelephone

8:00 am to 4:00 pm

New Hampshire Fish & Game DepartmentAgency Name

Facility Location & Address to be serviced

Owl Brook Hunter Education Center, 387 Perch Pond Road, Holderness

Hours of Operation of Facility

NH Fish & Game, 11 Hazen Drive, Concord, NH 03301Facility Contact Person Richard Fink, P.E.

[email protected]

Remit Address for Invoices

Current Vendor noneDate of Last Inspection

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection ServicesSubmit this electronically ONLY.Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this contract. Type each response in the fields provided.

REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

E-mailTelephone

8AM to 4PM, Monday through Friday

NH Fish & Game, 11 Hazen Drive, Concord, NH 03301

NH Fish and Game Department, Region 2Agency Name

Facility Location & Address to be serviced

200 Main Street, New Hampton, NH 03256

Hours of Operation of Facility

Facility Contact Person Richard Fink, [email protected]

603-271-1134

Remit Address for Invoices

Current VendorDate of Last Inspection Sprinkler Inspection was October, 2017

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection ServicesSubmit this electronically ONLY.Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this contract. Type each response in the fields provided.

REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

E-mailTelephone

Monday - Friday 8am - 4 pm

NH Fish & GameAgency Name

Facility Location & Address to be serviced

225 Main Street, Durham, NH

Hours of Operation of Facility

11 Hazen DriveFacility Contact Person Doug Grout

[email protected]

Remit Address for Invoices

Current Vendor noneDate of Last Inspection

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection ServicesSubmit this electronically ONLY.Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this contract. Type each response in the fields provided.

REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

E-mailTelephone

For fire alarm maintenance please provide an inventory of your existing system below.

Please include the quantity of the following peripherals:

For each system (not just panel), please confirm whether conventional or addressable:

Indicate the frequency of inspection services you would like

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals teste

Additional Information, if necessary

Manufacturer/Brand of Equipment Fire Control Instrument Inc. Model of panel BMFC6Date of installation 1990

1?

Number of heat detectors 7

Number of devices that feeds the panels ?Number of pull stations 4

Number of preaction panels, if applicable

Monday - Friday 8am - 4 pm

8am & 4pm Monday - Friday

Conventional yesAddressable

Quarterly Inspection at the rate of 25% noOther: n/a

Number of smoke detectors 5Number of battery backups 0

Annually at a rate of 100% yes

NH Fish & GameAgency Name

Facility Location & Address to be serviced

15 Ash Brook Court Keene

Hours of Operation of Facility

11 Hazen DriveFacility Contact Person Teresa Cloutier

[email protected]

Remit Address for Invoices

Current Vendor noneDate of Last Inspection -

Audio-Visual Units 3Duct Detectors 0

NACs/power supplies ?

C/O Detectors 0Door Holders 0

Number of subpanels, if applicable

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection ServicesSubmit this electronically ONLY.Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this contract. Type each response in the fields provided.

REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

E-mailTelephone

Current Vendor noneDate of Last Inspection

11 Hazen Drive Concord, NH 03301Facility Contact Person Tom Paschal

[email protected]

Remit Address for Invoices

NH Fish & Game DepartmentAgency Name

Facility Location & Address to be serviced

1450 Rte 3 North, Carroll, NH

Hours of Operation of Facility8:00 am to 4:00 pm Mon.- Fri.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name DAS BFAM

Facility Location & Address to be serviced

Philbrook 121 South Fruit St Concord NH 03301

Hours of Operation of Facility 7:30 To 4:00

Remit Address for Invoices State of NH BFAM 129 Pleasant St Concord NH 03301 Facility Contact Person Douglas Burnham

E-mail [email protected] Telephone 603-271-9555

Current Vendor Simplex Date of Last Inspection 10/2017

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Mircom

Model of panel FX2000 Date of installation 2014 Number of subpanels, if applicable 0 Number of pre-action panels, if applicable 0 Number of devices that feeds the panels Number of pull stations 12 Number of heat detectors 10 Number of smoke detectors 67 Number of battery backups 2

Please include the quantity of the following peripherals: Audio-Visual Units 22

Duct Detectors 0 C/O Detectors 0 Door Holders 4 NACs/power supplies 2

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable X

Indicate the frequency of inspection services you would like Annually at a rate of 100% X

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 7:30 To 4:00

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name DAS BFAM

Facility Location & Address to be serviced

Thayer 97 Pleasant St Concord NH 03301

Hours of Operation of Facility 7:30 to 4:00

Remit Address for Invoices State of NH BFAM 129 Pleasant St Concord NH 03301 Facility Contact Person Douglas Burnham

E-mail [email protected] Telephone 603-271-9555

Current Vendor Simplex Date of Last Inspection 10/2017

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4001 Date of installation 1999 Number of subpanels, if applicable 0 Number of pre-action panels, if applicable 0 Number of devices that feeds the panels Number of pull stations 39 Number of heat detectors 6 Number of smoke detectors 130 Number of battery backups 3

Please include the quantity of the following peripherals: Audio-Visual Units 71

Duct Detectors 0 C/O Detectors 0 Door Holders 11 NACs/power supplies 3

For each system (not just panel), please confirm whether conventional or addressable: Conventional X

Addressable

Indicate the frequency of inspection services you would like Annually at a rate of 100% X

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 7:30 to 4:00

Additional Information, if necessary

Please note the A/V part of this system will be upgraded in 2018. We will be adding 20 plus horns and strobes to the system

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name DAS BFAM

Facility Location & Address to be serviced

DHHS Transportation 133 Pleasant St Concord NH 03301

Hours of Operation of Facility 7:30 to 4:00

Remit Address for Invoices State of NH BFAM 129 Pleasant ST Concord NH 03301 Facility Contact Person Douglas Burnham

E-mail [email protected] Telephone 603-271-9555

Current Vendor Simple Date of Last Inspection 10/2017

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4001 Date of installation 1988 Number of subpanels, if applicable 0 Number of pre-action panels, if applicable 0 Number of devices that feeds the panels Number of pull stations 6 Number of heat detectors 26 Number of smoke detectors 1 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units 5

Duct Detectors 0 C/O Detectors 0 Door Holders 0 NACs/power supplies 1

For each system (not just panel), please confirm whether conventional or addressable: Conventional X

Addressable

Indicate the frequency of inspection services you would like Annually at a rate of 100% X

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 7:30 to 4:00

Additional Information, if necessary

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name NH Veterans Home

Facility Location & Address to be serviced

139 Winter Street, Tilton, NH 03276

Hours of Operation of Facility Monday to Friday 7:00 to 3:30

Remit Address for Invoices 139 Winter Street, Tilton, NH 03276 Facility Contact Person Jon Bossey, Plant Maintenance Engineer IV

E-mail [email protected] Telephone (603)527-4452

Current Vendor Simplex Grinnell Date of Last Inspection 12/19/2016

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel (3) Simplex 4100U Date of installation 2003 – 2006 - 2009 Number of subpanels, if applicable 7 Number of pre-action panels, if applicable 0 Number of devices that feeds the panels 586 Number of pull stations 70 Number of heat detectors 30 Number of smoke detectors 470 Number of battery backups 3

Please include the quantity of the following peripherals: Audio-Visual Units 243

Duct Detectors 16 C/O Detectors 0 Door Holders 51 NACs/power supplies 3

For each system (not just panel), please confirm whether conventional or addressable: Conventional

Addressable All addressable

Indicate the frequency of inspection services you would like Annually at a rate of 100% 100% yearly. One test, takes approximately 3 days to complete.

Quarterly Inspection at the rate of 25%

Other: 4 year smoke and fire damper testing, 2 year sensitivity testing on smoke detectors.

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio visuals tested. M-F 7:00 to 3:30 – Audio to be completed at the end of inspection house wide.

Additional Information, if necessary Require fire damper testing and smoke damper testing in accordance with the NFPA every 4 years. We have 84 fire and smoke dampers to be tested. Sensitivity testing on smoke detectors is required every 2 years as well in accordance with the NFPA. November of each year elevators is due for annual inspection, fire devices in elevator shafts (5 elevators) are required to be tested. FA vendor is required to be onsite with State of New Hampshire contracted elevator company to perform testing of devices (smoke/heat/fire recall) of elevator equipment.

Data Collection Worksheet for Fire Alarm Maintenance, Monitoring, and Inspection Services

Submit this electronically ONLY. Submit ONE form per facility. This form is intended to collect the data necessary to specify the service you would like to have provided as a result of this

contract. Type each response in the fields provided. REMINDER: A waiver under RSA 21-I:17-c will need to be completed if the agency does not want to make use of these contracts.

Agency Name DAS BFAM

Facility Location & Address to be serviced

Warehouse 131 Pleasant St Concord NH 03301

Hours of Operation of Facility 7:30 to 4:00

Remit Address for Invoices State of NH BFAM 129 Pleasant St Concord NH 03301 Facility Contact Person Douglas Burnham

E-mail [email protected] Telephone 603-271-9555

Current Vendor Simplex Date of Last Inspection 10/2017

For fire alarm maintenance please provide an inventory of your existing system below. Manufacturer/Brand of Equipment Simplex

Model of panel 4005 Date of installation 2000 Number of subpanels, if applicable 0 Number of pre-action panels, if applicable 0 Number of devices that feeds the panels Number of pull stations 10 Number of heat detectors 4 Number of smoke detectors 41 Number of battery backups 1

Please include the quantity of the following peripherals: Audio-Visual Units 27

Duct Detectors 0 C/O Detectors 0 Door Holders 0 NACs/power supplies 1

For each system (not just panel), please confirm whether conventional or addressable: Conventional X

Addressable

Indicate the frequency of inspection services you would like Annually at a rate of 100% X

Quarterly Inspection at the rate of 25% Other:

Hours inspections are to be completed? If you do not want audio visuals to be completed during these hours, indicate when you like audio

visuals tested. 7:30 To 4:00

Additional Information, if necessary

INVENTORY OF FIRE ALARM SYSTEM DEVICES – ADJUTANT GENERAL’S DEPARTMENT

ARMY AVIATION SUPPORT FACILITY (AASF Concord Hangar) QTY

DESC

3

Edwards EST-2 Panels 1

Stand-Alone Pre-Action System with Panel

43

SIGA-PS Smoke Detectors 3

Wheelock NH-12 Horn

3

278A-REL Manual release double action 2

SIGA-HFS Addressable heat Detector (135F)

14

SIGA-DH Duct smoke detectors 36

SIGA 278 Addressable double action manual pull

36

Wheelock RSS-24MCW-FR Strobe Units 80

Wheelock NS-24MCW-FR Strobe/Horn units

4

Exterior Strobe/Horns

BERLIN ARMORY QTY

DESC

1

BK-7100-1 Gamewell Control panel 1

MCOM Master Box Module

1

EVAX 100-R Voice Evacuation System with 4 Zone splitter 5

MS-7AF Addressable Manual Station

7

ASD-PL2F Addressable Photoelctronic Smoke Detectors 32

ATD-L2F Addressable Heat Detector (135F)

4

ATD-HL2F Addressable Heat Detector (190F) 3

AMM-4F Addressable Monitor Module

2

22310-18-01 Beam Detector 24

5604 Conventional Heat Detector (194F)

12

RSS-24MCW-FR Strobe Units 29

E50-MCW-FR Speaker/Strobe unit

1

FF8 Strobe Booster panel 1

500P-1228R Exterior Strobe Beacon

1

M34-56 Local Energy Master box *Berlin location will be Divested to the City of Berlin year 2220.

CONCORD STATE MILITARY RESERVATION BLDG 1 (Joint Force Headquarters) (Simplex System)

QTY

DESC

1

Fire Alarm Control Panel 1

Remote Annunciator

3

Shunt Circuit Breaker 4

Duct smoke detectors

1

Addressable FA Panel 1

Fire Alarm Control Panel Rm117

12

Photoelectric Smoke Detector

12

Smoke Detector In Duct

20

Strobe Subscript 100

Strobe With Speaker

3

Strobe With Horn 12

Heat Detectors

3

Shunt trips 4

ECP (SKIF)

1 Pull Station 1 Horn/Strobe

2 Smokes

BLDG A (Simplex System) QTY

DESC

1

4100U Fire alarm control panel 2

Duct smoke detectors

3

4099-9003 Manual pull stations 35

Speaker/Strobes

1

Photo sensor 2

Local operating console

2

Remote microphones 1

Basic audio microphone

2

External strobes

BLDG B/C (Simplex System) QTY

DESC

1

Fire Alarm control panel 48

Heat detectors

10

Manual pull stations 10

Horn/Strobes

2

Duct smoke detectors

BLDG F (Simplex System) QTY

DESC

1

4100U Control panel 12

4099-9003 Double action pull station

9

4098-9714 Photo smoke sensor 1

4098-9733 Heat sensor

2

4098-9756 Duct smoke detector 2

Strobes

26

Horn/Strobe 2

External strobes

BLDG G (Simplex System) QTY

DESC

1

4100U Fire alarm control panel 3

Manual pull stations

2

Heat detectors 2

Strobes

3

Horn/Strobes 2 External Strobes 1 External Annunciator

BLDG H (Simplex) QTY

DESC

1

4100U Fire alarm control panel 10

Manual pull stations

10

Horn/Strobes 1

Duct smoke detector

2

External strobes 1 External Annunciator

BLDG L (Gamewell) QTY

DESC

1

Intelligent Addressable Fire Alarm Control NFS2-640 1 Digital Voice Command Center 4 Addressable Duct Smoke Detector w/FSP-851R with DST-3 Sampling Tube 8

Pull stations

1

Photo Smoke Detector 31

Horn/Strobes

3

Supervised AIM 2 External Strobes

BLDG M QTY

DESC

1

Simplex 4100U Control Panel Master Box 1

Gamewell M34-92

1

Graphic Annunciator 32

MIX/2251B Photo Detector

52

MIX/5251RB Thermal Rate of Rise Sensor (135F) 4

MIX/5251B Thermal Sensor, Fixed Temp (135F)

13

MIX/5251H Thermal Sensor High Temp (190F) 3

DH200RP Duct Smoke Detector

9

MS610ADU Double Action Fire Alarm Station

FRANKLIN ARMORY QTY

DESC

1

BK-7100-1 Gamewell Control panel 1

MCOM Master Box Module

1

EVAX 100/4Z-R Voice Evacuation System with 4 Zones 7

MS-7AF Addressable Manual Station

5

ASD-PL2F Addressable Photoelctronic Smoke Detectors 20

ATD-L2F Addressable Heat Detector (135F)

4

ATD-HL2F Addressable Heat Detector (190F) 3

AMM-4F Addressable Monitor Module

2

22310-18-01 Beam Detector 24

5604 Conventional Heat Detector (194F)

8

RSS-24MCW-FR Strobe Units 21

E50-MCW-FR Speaker/Strobe unit

1

FF8 Strobe Booster panel 1

500P-1228R Exterior Strobe Beacon

1

M34-56 Local Energy Master box

HILLSBORO ARMORY QTY

DESC

1

BK-7100-1 Gamewell Control panel 1

MCOM Master Box Module

1

EVAX 100/4Z-R Voice Evacuation System with 4 Zones 7

MS-7AF Addressable Manual Station

3

ASD-PL2F Addressable Photoelctronic Smoke Detectors 10

ATD-L2F Addressable Heat Detector (135F)

4

ATD-HL2F Addressable Heat Detector (190F) 3

AMM-4F Addressable Monitor Module

2

22310-18-01 Beam Detector 15

5604 Conventional Heat Detector (194F)

4

RSS-24MCW-FR Strobe Units 15

E50-MCW-FR Speaker/Strobe unit

1

E60-MCW-FR Speaker/Strobe unit (Ceiling Mount) 1

500P-1228R Exterior Strobe Beacon

1

M34-56 Local Energy Master box HILLSBORO FMS

1 Fire Alarm Control Panel 4 Photo Smoke Detectors 4 Heat Sensors 8 Heat Detectors 8 Smoke Detectors

LANCASTER ARMORY QTY

DESC

1

BK-7100-1 Gamewell Control panel 1

EVAX 100/4Z-R Voice Evacuation System with 4 Zones

5

MS-7AF Addressable Manual Station 4

ASD-PL2F Addressable Photoelctronic Smoke Detectors

17

ATD-L2F Addressable Heat Detector (135F) 4

ATD-HL2F Addressable Heat Detector (190F)

3

AMM-4F Addressable Monitor Module 2

22310-18-01 Beam Detector

15

5604 Conventional Heat Detector (194F) 4

RSS-24MCW-FR Strobe Units

19

E50-MCW-FR Speaker/Strobe unit 1

500P-1228R Exterior Strobe Beacon

1

5104B Fire Control Communicator (DACT)

LEBANON ARMORY QTY

DESC

1

BK-7100-1 Gamewell Control panel 1

MCOM Master Box Module

1

EVAX 100/4Z-R Voice Evacuation System with 4 Zones 5

MS-7AF Addressable Manual Station

3

ASD-PL2F Addressable Photoelctronic Smoke Detectors 11

ATD-L2F Addressable Heat Detector (135F)

4

ATD-HL2F Addressable Heat Detector (190F)

3

AMM-4F Addressable Monitor Module 2

22310-18-01 Beam Detector

15

5604 Conventional Heat Detector (194F) 2

RSS-24MCW-FR Strobe Units

16

E50-MCW-FR Speaker/Strobe unit 1

500P-1228R Exterior Strobe Beacon

1

M34-56 Local Energy Master box 1

47375G Master Box Indicating Light

LEBANON CHP QTY

DESC

1 Fire Control Panel 16 Heat Detectors

3 Photoeletronic Sensors 5 Smoke Detectors 1 Exterior Strobe

LITTLETON ARMORY

QTY

DESC 1

BK-7100-1 Gamewell Control panel

1

EVAX 100/4Z-R Voice Evacuation System with 4 Zones 5

MS-7AF Addressable Manual Station

4

ASD-PL2F Addressable Photoelctronic Smoke Detectors 13

ATD-L2F Addressable Heat Detector (135F)

4

ATD-HL2F Addressable Heat Detector (190F) 3

AMM-4F Addressable Monitor Module

2

22310-18-01 Beam Detector 15

5604 Conventional Heat Detector (194F)

3

RSS-24MCW-FR Strobe Units 16

E50-MCW-FR Speaker/Strobe unit

1

ET70WP-2475W Weatherproof Speaker/Strobe 1

500P-1228R Exterior Strobe Beacon

1

5104B Fire Control Communicator (DACT)

LITTLETON FMS This is a Mircon System

QTY

DESC 1

Fire Alarm Control Panel

4

Manual pull stations 6

Smoke detectors

30

High heat (200F)

2

Low heat (135F) 8

Alarm/Strobes

8

Strobes 1

Exterior strobe

LITTLETON CHP

1 Fire Alarm Control Panel 12 Heat Detectors

3 Photoeletronic Sensor 5 Smoke Detectors 1 Exterior Strobe

MANCHESTER ARMORY

QTY

DESC 1

BK-7100-1 Gamewell Control panel

1

EVAX 100/4Z-R Voice Evacuation System with 4 Zones 25

MS-7AF Addressable Manual Station

76

ASD-PL2F Addressable Photoelctronic Smoke Detectors 149

ATD-L2F Addressable Heat Detector (135F)

4

ATD-HL2F Addressable Heat Detector (194F) 69

5604 Conventional Heat Detector (194F)

1

FCI-AD-PF Duct Smoke Detector 2

AMM-4F Addressable Monitor Module

3

22310-18-01 Beam Detector 121

ET70/E50-MCW-FR Speaker/Strobe unit

97

E60-MCW-FR Wall Mount Strobe Unit 1

47375G Master Box Indicating Light

1

Silent Knight 1504B Digital Dialer 1

Tomar 500P-1228R Exterior Strobe Beacon

MILFORD ARMORY QTY

DESC

1

BK-7100-1 Gamewell Control panel 1

MCOM Master Box Module

1

EVAX 100/4Z-R Voice Evacuation System with 4 Zones 5

MS-7AF Addressable Manual Station

3

ASD-PL2F Addressable Photoelctronic Smoke Detectors 11

ATD-L2F Addressable Heat Detector (135F)

6

ATD-HL2F Addressable Heat Detector (190F) 3

AMM-4F Addressable Monitor Module

2

22310-18-01 Beam Detector 15

5604 Conventional Heat Detector (194F)

3

RSS-24MCW-FR Strobe Units 20

E50-MCW-FR Speaker/Strobe unit

1

500P-1228R Exterior Strobe Beacon

NASHUA ARMORY QTY

DESC

1

FX2003/12KU Mircom FACP 1/SLC4/NAC 12A 1

PR/100 Master Box Module

9

MS610ADU Double Action Fire Alarm Station 2

M500R Relay Control Module

29

MIX/5251RB Thermal Rate of Rise Sensor (135F) 16

MIX/5251H Thermal Sensor High Temp (190F)

4

MIX/5251B Thermal Sensor, Fixed Temp (135F) 1

RTS/451 KEY Remote test Station

25

GEC324WR75 Red Horn/Strobe (75CD) 9

GES324WR15 Red Strobe (15CD)

3

AVS/44 Sync Module 1

495S/1280R Red 12-80VDC Red Strobe

NASHUA CHP

1 Fire Alarm Control Panel 12 Heat Detectors

3 Photoeletronic Sensor 5 Smoke Detectors 1 Exterior Strobe 1 Fire Alarm Control Panel

12

Heat Detectors

PLYMOUTH ARMORY QTY

DESC

1

FX2003/12KU Mircom FACP 1/SLC4/NAC 12A 1

UDACT/100AP Digital Alarm Communication MFA 1008K

7

MS610ADU Double Action Fire Alarm Station 2

M500X Fault Isolator Module

1

M500R Relay Control Module 10

MIX/5251RB Thermal Rate of Rise Sensor (135F)

14

MIX/5251H Thermal Sensor High Temp (190F) 6

MIX/5251B Thermal Sensor, Fixed Temp (135F)

13

MIX/2251B Photo Detector 1

RTS/451 KEY Remote test Station

5

GEC324WR75 Red Horn/Strobe (75CD) 17

GES324WR15 Red Strobe (15CD)

3

AVS/44 Sync Module 1

495S/1280R Red 12-80VDC Red Strobe

PORTSMOUTH ARMORY QTY

DESC

1

BK-7100-1 Gamewell Control panel 1

EVAX 100/4Z-R Voice Evacuation System with 4 Zones

5

MS-7AF Addressable Manual Station 10

ASD-PL2F Addressable Photoelectric Smoke Detectors

33

ATD-L2F Addressable Heat Detector (135F) 5

ATD-HL2F Addressable Heat Detector (190F)

3

AMM-4F Addressable Monitor Module 2

22310-18-01 Beam Detector

24

5604 Conventional Heat Detector (194F) 8

RSS-24MCW-FR Strobe Units

21

E50-MCW-FR Speaker/Strobe unit 1

FF8 Strobe Booster panel

1

500P-1228R Exterior Strobe Beacon 1

5104B Fire Control Communicator (DACT)

SOMERSWORTH ARMORY QTY

DESC

1

BK-7100-1 Gamewell Control panel 1

EVAX 100/4Z-R Voice Evacuation System with 4 Zones

5

MS-7AF Addressable Manual Station 3

ASD-PL2F Addressable Photo electronic Smoke Detectors

18

ATD-L2F Addressable Heat Detector (135F) 4

ATD-HL2F Addressable Heat Detector (190F)

3

AMM-4F Addressable Monitor Module 2

22310-18-01 Beam Detector

15

5604 Conventional Heat Detector (194F) 6

RSS-24MCW-FR Strobe Units

17

E50-MCW-FR Speaker/Strobe unit 1

500P-1228R Exterior Strobe Beacon

RAYMOND BISSON

QTY DESC 2 MS600UDLS Firelite Alarm Panel W/ 12v/18a Batteries 6 Pull Stations

12 Horn Horn/Strobes

14 Heat Detectors 2 External Strobes 6 Photoelectric Smokes

SOMERSWORTH FMS QTY DESC

1 NFW2-10R Fire Alarm Panel 2 Addressable Monitor Modules 2 Class A Modules 2 Addressable Control Modules 1 Photo Smoke Detector

11 Heat Sensors 1 FSEX-24-PMR Explosion Proof Strobe 4 10AHR Batteries 1 Exterior Strobe

NGNH-TS CENTER STRAFFORD (SIMPLEX DEVICES)

QTY DESC BLDH 1 ADMIN 1 41OOU w/two 12v/10a Batteries 3 Mass Notification 7 Pull Stations 7 Heat Detectors

49 Smokes 24 Horn/Strobes

8 Strobes 6 Horns 1 Annunciator

QTY DECS BLDG 2 (UPPER FOSS)

1 41OOU w/two 12v/10a Batteries 1 Mass Notification 4 Pull Stations 5 Pull Stations 5 Heats

13 Smokes 21 Strobes

6 Horns 5 Smoke/COs 1 Annunciator

QTY DECS BLDG 3 (MCLEAN)

1 4100U w/two 12v/110a Batteries 1 Mass Notification 4 Pull Stations 5 Heats

25 Smokes 15 Strobes

4 Horns 4 Smoke/COs 1 Annunciator

QTY DECS BLDG 4 (LOWER FOSS)

1 4100U w/two 12v/110a Batteries 5 Mass Notification 5 Pull Stations 5 Heats

15 Smokes 15 Strobes 15 Horns

7 Smoke/COs 1 Annunciator

QTY DECS BLDG 5 (DEFAC)

1 4100U w/two 12v/110a Batteries 3 Mass Notification 9 Pull Stations 1 Heats

17 Smokes 6 Strobes 6 Horns 7 Horn/Strobes 1 Annunciator 2 Duct Heat Detectors 2 Duct Smoke Detectors

QTY DECS BLDG 6 (THOMAS HALL)

1 4100U w/two 12v/110a Batteries 4 Mass Notification

10 Pull Stations 14 Heats 56 Smokes

7 Strobes 4 Horns

38 Horn/Strobes

1 Annunciator

QTY DECS BLDG 7 (THOMAS HALL) 1 4100U w/two 12v/110a Batteries 2 Mass Notification 2 Pull Stations 5 Heats

15 Smokes 7 Strobes 4 Horns 7 Horn/Strobes 1 Annunciator

QTY DECS BLDG 8 (GYM)

1 4100U w/two 12v/110a Batteries 1 Mass Notification 2 Pull Stations 5 Smokes 8 Strobes 5 Horns 1 Annunciator

QTY DECS BLDG 9 (MAINTENANCE)

1 4009 NAC EXT 2 Pull Stations

14 Heat 2 Strobes 2 Horns/Strobes

QTY DECS BLDG 10 (SHOOT HOUSE)

1 4100U w/two 12v/110a Batteries 2 Mass Notification 3 Pull Stations 4 Heats 8 Smokes

12 Strobes 12 Horns

1 Annunciator

QTY DECS BLDG 11 (SHOOT HOUSE) 1 4100U w/two 12v/110a Batteries 2 Mass Notification 2 Pull Stations

4 Heats 8 Smokes

12 Strobes 12 Horns

1 Annunciator RTI PEMBROKE

QTY DESC 1 Fire Alarm Control Panel 1 Main CPU Module (3-CPU3) 1 RS-485 Class "A" Network Comm. Module (3-RS485) 2 Boost Power Supply (3-BPS/M) 1 Audio Source W/Local Mic +C7:C23(3-ASU/4) 3 95W Zoned Amplifier (3-ZA95) 1 Digital Dialer (3-MODCOM) 4 12v/24a 24 AH Batteries 2 Remote Annunciators W/ Controls (3-LCDANN) 1 Enclosure Heater (SPACEAGELCD) 3 Remote Microphones W/ Sw. LOC 3- ANNCPU3) 3 Remote LCD CPU (4ANN/B) 3 Remote Mics (3-REMICA)

21 Addressable Pull Stations (SIGS-278) 19 Addressable Smoke Detectors (SIGA2-PS)

1 Addressable Heat Detector (SIGA2-HFS) 10 Addressable Duct Smoke Detectors (SIGA-SD) 10 Remote Test Sw. (SD-TRK)

2 Universal IN/Output Motherboards (SIGA-UIO6) 106 Speaker/Strobes (G4RF-S2VM) 15 Weatherproof Speaker/Strobes (WG4RN-S

7 6Amp Signal Panels (BPS-6A) 14 7AH Batteries (12V6A5) 12 Surface Mount Door Holders (1508 AQN5

3 Lighting Arrestors (DTK-2MHLP) BARRACKS BLDG

QTY DESC 1 Main CPU Module (3-CPU3) 1 3-RS485 Class "A" Network Comm. Module ( 3-RS485) 2 Booster Power Supply (3-BPS/M) 1 Audio Source Unit W/Local Mic. (3-ASU/4) 1 Digital Dialer (3-MODCOM) 2 24 AH Batteries (12V24A) 1 Remote Annunciator W/ Controls (3-LCDANN)

2 Remote LCD CPU (3-ANNCPU3) 2 Remote Microphones (3-REMICA)

15 Addressable Pull Stations (SIGA-278) 54 Addressable Smoke Detectors (SGA2-PS)

2 Addressable Heat Detectors (SIGA2-HFS) 4 Addressable Duct Smoke Detectors (SIGA-SD) 4 Remote Test Sw./LEDs (SD-TRK) 2 Universal Input/output Motherboard (SIGA-UIO6)

171 Addressable Speaker/Strobe Units (G4RF-S2VM) 9 Weatherproof Speaker Units (WG4RN-S)

10 6Amp Signal Panel (BPS-6A) 20 7.2AH Batteries (12V6A5) 12 Surface Mount Door Holders (1508 AQN5)