Building Management System - BMS 1

  • Upload
    jaffna

  • View
    237

  • Download
    1

Embed Size (px)

Citation preview

  • 8/12/2019 Building Management System - BMS 1

    1/31

    Building Management System

    integrates various services in a facility

    with a computerized control system.

    User benefits by

    Optimum functionality

    Energy savings

    Better information systems

  • 8/12/2019 Building Management System - BMS 1

    2/31

    Automatic controls help in

    Energy consumptionOptimization of man power

    Accuracy & precision

    Easy maintenance and trouble shooting

    Longer plant life

    Hygiene & cleanliness

  • 8/12/2019 Building Management System - BMS 1

    3/31

    Sensor- A Sensor is a device that converts a physical

    property such as temperature, pressure, relative humidity,

    flow etc. into an electrically or mechanically measurable

    signal.

    Transducer- A transducer is a device that converts oneform of energy to another form of energy such as

    pneumatic to electric or vice versa.

    Transmitter- Output from a sensor or a transducer may

    not be strong enough to be transmitted over long distances.Transmitter is a device used to amplify the signal.

    Controller- It is a device that compares the signal from a

    Sensor, Transducer or Transmitter with the desired value

    and generates a signal based on error.

    Actuator- It is an electric, pneumatic or a mechanicaldevice which generally converts a low value signal to a

    signal with sufficient force to overcome the forces acting on

    control device and to actuate it.

  • 8/12/2019 Building Management System - BMS 1

    4/31

    Controlled Device- It receives signal from controller and

    varies the flow of control agent like water, air. It may be a

    damper or a valve connected to an actuator.

    Stat- Combination of sensor and controller functioning in

    one device is often called a stat like thermostat,

    humidistat, etc.

    Set-Point- It is desired value of the controlled variable.

    Process & Controlled Variable- In an air-conditioning

    system, parameter being controlled such as temperature,RH, pressure etc. is controlled variable and the changes in

    these parameters is due to influencing factors in process.

    Control Medium- It is the air, steam or water the flow

    regulation of which influences the process to get thedesired value of controlled variable

  • 8/12/2019 Building Management System - BMS 1

    5/31

    TYPES OF INPUT DEVICES

    Analog Input- Any input that varies with time

    for e.g. Temperature, humidity , Pressure

    Digital Input- Any input that works on a twostate mode ( 0 or 1)like on or off ,

    clean/dirty.

    Pulse input- Any input incremental in nature

    and totalizes over a period of time , KWH

    meter, water meter

  • 8/12/2019 Building Management System - BMS 1

    6/31

    Control Loop

    The process of controlling an HVAC

    system involves three steps. These steps

    include first measuring data, then

    processing the data with other informationand finally causing a control action. These

    three functions make up what is known as

    a control loop

  • 8/12/2019 Building Management System - BMS 1

    7/31

    Feed Back Control Loop

    OutputController

    Feedback

    Input

    Comparator

  • 8/12/2019 Building Management System - BMS 1

    8/31

    BASIC CONTROL LOOP

  • 8/12/2019 Building Management System - BMS 1

    9/31

    DDC CONTROL LOOP

  • 8/12/2019 Building Management System - BMS 1

    10/31

    Controller

    The controller processes data that is input fromthe sensor, applies the logic of control andcauses an output action to be generated. Thissignal may be sent directly to the controlleddevice or to other logical control functions andultimately to the controlled device. Thecontrollers function is to compare its input (fromthe sensor) with a set of instructions such as

    setpoint, throttling range and action, thenproduce an appropriate output signal. This is thelogic of control.

  • 8/12/2019 Building Management System - BMS 1

    11/31

    Controller Responses

    Control responses are typically one the

    following:

    Two-Position

    Floating

    Proportional (P only)

    Proportional plus Integral (PI) Proportional plus Integral plus Derivative

    (PID)

  • 8/12/2019 Building Management System - BMS 1

    12/31

    Two Position Control

    Two-Position ControlTwo-position control compares the value of an analog orvariable input with instructions and generates a digital (two-

    position) output. The instructions involve the definition of anupper and lower limit. The output changes its value as the

    input crosses these limit values. There are no standards fordefining these limits. The most common terminology used issetpoint and differential. The setpoint indicates the point wherethe output pulls-in, energizes or is true. The outputchanges back or drops-out after the input value crosses

    through the value equal to the difference between the setpointand the differential.

  • 8/12/2019 Building Management System - BMS 1

    13/31

    COOLING

    OFF

    COOLING

    ON

    Figure shows an example of two-position control where the thermostat is set

    to energize the Cooling system when the space temperature rises above 72

    F and turn off when the temperature drops to 70F in the space. This is an

    example of a setpoint of 70F with a two-degree differential.

  • 8/12/2019 Building Management System - BMS 1

    14/31

    Two Position Control-- Contd

    Two-position control can be used for simplecontrol loops (temperature control) or limitcontrol (e.g. Antifreeze thermostat). The analogvalue can be any measured variable includingtemperature, relative humidity, pressure, currentand liquid levels.

    Time can also be the input to a two-positioncontrol response. This control responsefunctions like a time clock with pins. The outputpulls-in when the time is in the defined ontime and drops out during the defined off time.

  • 8/12/2019 Building Management System - BMS 1

    15/31

    Floating Control

    Floating control is a control response thatproduces two possible digital outputs based on achange in a variable input. One output increasesthe signal to the controlled device, while theother output decreases the signal to thecontrolled device. This control response alsoinvolves an upper and lower limit with the outputchanging as the variable input crosses these

    limits. Again, there are no standards for definingthese limits, but the terms setpoint anddeadband are common. The setpoint sets amidpoint and the deadband sets the difference

    between the upper and lower limits

  • 8/12/2019 Building Management System - BMS 1

    16/31

  • 8/12/2019 Building Management System - BMS 1

    17/31

    Proportional Control

    A proportional control response produces an analog or variable outputchange in proportion to a varying input. In this control response, there is alinear relationship between the input and the output.

    A setpoint, throttling range and action typically define this relationship. In aproportional control response, there is a unique value of the measured

    variable that corresponds to full travel of the controlled device and a uniquevalue that corresponds to zero travel on the controlled device.

    The change in the measured variable that causes the controlled device tomove from fully closed to fully open is called the throttling range. It iswithin this range that the control loop will control, assuming that thesystem has the capacity to meet the requirements.

    The action dictates the slope of the control response.

    In a direct acting proportional control response, the output will rise with anincrease in the measured variable.

    In a reverse acting response, the output will decrease as the measuredvariable increases

  • 8/12/2019 Building Management System - BMS 1

    18/31

  • 8/12/2019 Building Management System - BMS 1

    19/31

    Proportional plus Integral (PI)

    Control

    PI control involves the measurement of the

    offset or error over time. This error is integrated

    and a final adjustment is made to the outputsignal from the proportional part of this model.

    This type of control response will use the control

    loop to reduce the offset to zero. A well set-up PI

    control loop will operate in a narrow band closeto the setpoint. It will not operate over the entire

    throttling range

  • 8/12/2019 Building Management System - BMS 1

    20/31

    Proportional plus Integral

    plus Derivative (PID) Control

    PID control adds a predictive element to thecontrol response. In addition to the proportionaland integral calculation, the derivative or slopeof the control response will be computed. Thiscalculation will have the effect of dampening acontrol response that is returning to setpoint soquickly that it will overshoot the setpoint.

    PID is a precision process control response andis not always required for HVAC applications.The routine application of PID control to everycontrol loop is labor intensive and its application

    should be selective.

  • 8/12/2019 Building Management System - BMS 1

    21/31

    Direct Digital Control (DDC

    DDC control consists of microprocessor-

    based controllers with the control logic

    performed by software. Analog-to-Digital

    (A/D) converters transform analog valuesinto digital signals that a microprocessor

    can use. Analog sensors can be

    resistance, voltage or current generators

  • 8/12/2019 Building Management System - BMS 1

    22/31

    Air Handling Unit and

    ChillersINPUT OUTPUT

    1. RA temp sensor 3- way valve

    2. RA humidity sensor Heater

    3. Pressure switch across filter Fire dampers4. Smoke sensor VFD for fan motor

    5. ADP sensor Dampers at RA

    6. Temp Dampers at fresh air

    7. Flow meter/sensor

    (Pulse input)

    Humidifier

    8. Fan status Dampers at exhaust

  • 8/12/2019 Building Management System - BMS 1

    23/31

    INPUT OUTPUT

    1. Pressure sensors across the

    chiller

    VFD of pump motor

    2. Pressure sensors across thecondenser Cooling tower fans

    3. Inlet and outlet temperature of

    chilled water

    Makeup water tank

    4. Inlet and outlet temperature of

    cooling water

    Pump on/off

    5. Outlet temperature of cooling

    tower

    Chiller on/off

    6. Flow switch at

    condenser/chiller

    Dampers at fresh air

    7. Flow meter/sensor

    (Pulse input)

    8. Current transformer

    9. Voltmeter ,PF, Frequency

    meter

  • 8/12/2019 Building Management System - BMS 1

    24/31

    Power Requirements

    1. The DDC units require UPS 24v acGenerally the VA ratings are very low and of the order of 4-6va

    2. The Analog sensors also require UPS Power of 24v ac.

    Output of sensors is 0 to 10v DC or 4 to 20 ma

    3. VAV boxes may also have Controllers and they will needUPS power and this will be 24v ac.

    4. The ups vendor may agree to provide 230v ac UPS

    power and we need to step down this voltage to 24v

    5. Chillers and Precision units will also have Cards that

    demand 24 v ac UPS power.

    Some Chillers will have inbuilt CVTs and UPS power may

    not be required for the cards in such Chillers

  • 8/12/2019 Building Management System - BMS 1

    25/31

    COMMUNICATION

    At the lowest level, bits are encoded in electrical, light or radio signals

    by the Physical layer. Some examples include RS-232,RS 485

    A somewhat higher Data link layer such as the point-to-point protocol

    (PPP) may detect errors and configure the transmission system.

    An even higher protocol may perform network functions. One verycommon protocol is the Internet protocol (IP), which implements

    addressing for large set of protocols.

    A common associated protocol is the Transmission control protocol

    (TCP) which implements error detection and correction (byretransmission). TCP and IP are often paired, giving rise to the familiar

    acronym TCP/IP.

  • 8/12/2019 Building Management System - BMS 1

    26/31

    Twisted-Pair Cable

    Twisted-pair cableis a type of cabling that is used for

    telephone communications and most modern Ethernet

    networks. A pair of wires forms a circuit that can transmit

    data. The pairs are twisted to provide protection against

    crosstalk, the noise generated by adjacent pairs. When

    electrical current flows through a wire, it creates a small,

    circular magnetic field around the wire. When two wires in

    an electrical circuit are placed close together, theirmagnetic fields are the exact opposite of each other. Thus,

    the two magnetic fields cancel each other out. They also

    cancel out any outside magnetic fields. Twisting the wires

    can enhance this cancellation effect. Using cancellationtogether with twisting the wires, cable designers can

    effectively provide self-shielding for wire pairs within the

    network media.

    Two basic types of twisted-pair cable exist: unshielded

    twisted pair (UTP) and shielded twisted pair (STP).

  • 8/12/2019 Building Management System - BMS 1

    27/31

    When used as a networking medium, UTP cable has four pairs of either

    22- or 24-gauge copper wire. UTP used as a networking medium has

    an impedance of 100 ohms Commonly used types of UTP cabling are

    as follows:

    Category 1Used for telephone communications. Not suitable

    for transmitting data.

    Category 2Capable of transmitting data at speeds up to 4

    megabits per second (Mbps).

    Category 3Can transmit data at speeds up to 10 Mbps.

    Category 4Can transmit data at speeds up to 16 Mbps. Category 5Can transmit data at speeds up to 100 Mbps.

    Category 5e Used in networks running at speeds up to 1000

    Mbps (1 gigabit per second [Gbps]).Bandwidth 100mhz

    Category 6More stringent standards on noise and

    crosstalk.Bandwidth 250 mhz

    UTP cable often is installed using a Registered Jack 45 (RJ-45)

    connector . The RJ-45 is an eight-wire connector used commonly to

    connect computers onto a local-area network (LAN).

    C i i C bl

  • 8/12/2019 Building Management System - BMS 1

    28/31

    Communication Cable

    ATC 2C Twisted shielded cable is generally used

    The comm. Route connecting Comm ports is also called

    a. C BUS

    b. J BUS

    c. N2 BUSd. Field BUS

    Comm Cable Limitations

    a. RS 232 :- 50 FT15Mb. RS 485 :- 1200 M

    c. TCP/IP :- NO LIMIT

  • 8/12/2019 Building Management System - BMS 1

    29/31

    PROTOCOLS

    BACnet

    Building Automation Control NetworksBacNETBACnet is anetwork communications protocol for building automation andcontrol systems. BACnet, the ASHRAE building automation and

    control networking protocol, has been designed specifically to meetthe communication needs of building automation and controlsystems for applications such as heating, ventilating, and air-conditioning control, lighting control, access control, and firedetection systems and their associated equiptment. The BACnetprotocol provides mechanisms by which computerized equipment ofarbitrary function may exchange information, regardless of theparticular building service it performs

    M dB

  • 8/12/2019 Building Management System - BMS 1

    30/31

    ModBusModbusis a serial communications protocol published by Modicon in

    1979 for use with its programmable logic controllers (PLCs). It had

    become a de facto standard communications protocol in industry, andwas the most commonly available means of connecting industrial

    electronic devices. The main reasons for the extensive use of Modbus

    over other communications protocols are:

    1. it is openly published and royalty-free

    2. it can be implemented in days, not months

    3. it moves raw bits or words without placing many restrictions onvendors

    Modbus allows for communication between many devices connected to

    the same network, for example a system that measures temperature

    and humidity and communicates the results to a computer. Modbus is

    often used to connect a supervisory computer with a remote terminalunit (RTU) in supervisory control and data acquisition (SCADA)

    systems.

  • 8/12/2019 Building Management System - BMS 1

    31/31

    LON WORKS and Zigbee

    LonTalk is a protocol created by EchelonCorporation for networking devices.Also

    called Lon Works

    ZigBee is a short range, low-poweredwireless communication standard targeted

    at Building Automation.