Trianon Design Group
Telephone 239 390 1203
9990 Coconut RoadBonita Springs, Florida 34135
16111 Lee Road, Fort Myers, Florida, 33912
Gerald J. Yurk, AIA ARCHITECTAR 0005621
Project Description
Use of DocumentsDRAWINGS, SPECIFICATIONS AND OTHER DOCUMENTS PREPAREDBY GERALD J. YURK A.I.A. ARCHITECT TRIANON DESIGN GROUP(TDG), AND HIS CONSULTANTS,ARE INSTRUMENTS OF TDG'SSERVICE AND ARE FOR THE OWNER'S USE SOLELY WITH RESPECTTO THIS PROJECT. TDG SHALL RETAIN ALL COMMON LAW,STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THECOPYRIGHT. UPON COMPLETION OR TERMINATION OF THE PROJECT,ALL PARTIES, WITH THE EXCEPTION OF TDG'S, RIGHTS TO USETHESE INSTRUMENTS OF SERVICE SHALL CEASE. WHENTRANSMITTING COPYRIGHT-PROTECTED INFORMATION FOR USE ONTHE PROJECT, THE TRANSMITTING PARTY REPRESENTS THAT IT HASPERMISSION FROM THE TDG TO TRANSMIT THE INFORMATION FORITS USE ON THE PROJECT. QUESTIONS ARISING DURINGCONSTRUCTION OR REVIEW OF THE DRAWINGS SHALL BEADDRESSED TO THE ARCHITECT.
for Permit5-16-2018
New Construction - Industrial Building
PROPOSED MASONRY BUILDING WITH A PREFAB METAL BUILDINGSUB STRUCTURE
Alico Business Park
COVER SHEET
ALICO BUSINESS PARK TRACT 67
Building #7
16111 Lee Road
Fort Myers, Florida 33912
LOCATION MAP
SITE LOCATION:
SITE MAP
BUILDING #7
EXISTING
LEE COUNTY, FLORIDA
SECTION 04, TOWNSHIP 46S, RANGE 25E
Parcel Id # 04462505000670000
DOS2006-00242
ZONING IPD
FUTURE
EXISTING
FUTURE
EXISTING
EXISTING
PROPOSED
DRAWING LIST
SHEET
NO.SHEET NAME
GENERAL
T-001 BUILDING DATA, ABBREVIATIONS, GENERAL LEGEND & NOTES
ARCHITECTURAL
A-100 BUILDING FLOOR PLAN
A-101 PARTIAL FLOOR PLAN (WEST)
A-103 ROOF PLAN
A-200 EXTERIOR BUILDING ELEVATIONS
A-300 BUILDING SECTIONS
A-400 WALL SECTIONS
A-500 TYPICAL DETAILS
A-600 WINDOW AND DOOR SCHEDULES & DETAILS
T-002 LIFE SAFETY PLAN, ADA DETAILS
T-000 COVER SHEET
A-102 PARTIAL FLOOR PLAN (EAST)
STRUCTURAL
S-000 STRUCTURAL NOTES AND TYPICAL DETAILS
S-100 BUILDING FOUNDATION & FLOOR PLAN
S-101 PARTIAL FOUNDATION & FLOOR PLAN
S-102 PARTIAL FOUNDATION & FLOOR PLAN
S-200 TYPICAL STRUCTURAL SECTIONS & DETAILS
ELECTRICAL
PLUMBING
E-000
P-100
P-101
P-102
P-200
P-201
BUILDING PLUMBING PLAN, NOTES & LEGENDPARTIAL PLUMBING PLANPARTIAL PLUMBING PLANDOMESTIC WATER ISOMETRICSANITARY ISOMETRIC
ELECTRICAL LEGEND, NOTES, INDEX & ABBREVIATIONSE-100 OVERALL ELECTRICAL PLANE-101 PARTIAL ELECTRICAL PLANE-102 PARTIAL ELECTRICAL PLANE-200 LOAD CALCULATIONS, PANEL & RISER
ABBREVIATIONS
AB. ANCHOR BOLT
ACT ACOUSTICAL CEILING TILE
A.F.F. ABOVE FINISHED FLOOR
AGGR. AGGREGATE
AL. ALUMINUM
ALT. ALTERNATE
APPROX. APPROXIMATE
ARCH. ARCHITECTURAL
BD. BOARD
BLDG. BUILDING
BLOCK BLK
BLK'G. BLOCKING
BEAM BM.
BOTTOM BOT.
BTWN. BETWEEN
B.U.R. BUILT UP ROOFING
B.W. BOTH WAYS
C.J. CONTROL JT.
CEILING CLG.
CLKG. CAULKING
CLEAR CLR.
C.M.U. CONCRETE MASONRY UNIT
COLUMN COL.
CONC. CONCRETE
CONN. CONNECTION
CONSTR. CONSTRUCTION
CONT. CONTINUOUS
C.T. CERAMIC TILE
DEGREE DEG.
DETAIL DET./DTL.
D.F. DRINKING FOUNTAIN
DIAG. DIAGONAL
DIA. DIAMETER Ø
DOWN DN.
DS. DOWNSPOUT
DWG. DRAWING
EAST E
(E) EXISTING
EACH EA.
E.J. EXPANSION JOINT
E.I.F.S. EXTERIOR INSULATION AND FINISH SYSTEM
EL. ELEV. ELEVATION
ELEC. ELECTRICAL
ELEV. ELEVATION
EMER EMERGENCY
ENCL. ENCLOSURE
EQUAL EQ.
EQUIP. EQUIPMENT
E.W. EACH WAY
E.W.C. ELECTRIC WATER COOLER
EXP. EXPANSION
EXT. EXTERIOR
F.A. FIRE ALARM
F.D. FLOOR DRAIN
F.D.C. FIRE DEPARTMENT CONNECTION
FDN. FOUNDATION
F.A. FIRE EXTINGUISHER
F.A.C. FIRE EXTINGUISHER CABINET
F.F. FINSH FLOOR
F.H.C. FIRE HOSE CABINET
FINISH FIN.
F.L. FLOW LINE
FLOOR FLR.
FLUOR. FLUORESCENT
FND. FOUNDATION
.O.B. FACE OF BRICK
F.O.C. FACE OF CONCRETE
F.S. FULL SIZE
FT. FOOT OR FEET
FTG. FOOTING
FURR. FURRING
GA. GAUGE
GALV. GALVINIZED
G.C. GENERAL CONTRACTOR
G.L. GLASS
GR. GRADE
GYP. GYPSUM
GYP. BD. GYPSUM BOARD
H.B. HOSE BIBB
H.C. HOLLOW CORE
H/C HANDICAPPED
HDWD. HARDWOOD
HDWE. HARDWARE
H.M. HOLLOW METAL
HR. HOUR
HT. HEIGHT
HVAC HEATING, VENTILATION AND AIR CONDITIONING
I.D. INSIDE DIAMETER
INSUL. INSULATION
INT. INTERIOR
JAN. JANITOR
JNT. JOINT
JST. JOIST
KIT. KITCHEN
LAB. LABORATORY
LAM. LAMINATE
LAV. LAVATORY
LT. LIGHT
MAX. MAXIMUM
MECH. MECHANICAL
MEMB. MEMBRANE
MFR. MANUFACTURER
M.H. MANHOLE
MIN. MINIMUM
MISC. MISCELLANEOUS
M.O. MASONRY OPENING
MTL. METAL
MUL. MULLION
N NORTH
N.I.C. NOT IN CONTRACT
NO. NUMBER
NOM. NOMINAL
N.T.S. NOT TO SCALE
A
PARTITION/WALL TYPE
AND GRID LINE
COLUMN BUBBLE
DOOR TAG
WINDOW TAG
DRAWING
SCALE
Room Name
DRAWING
NUMBER
ROOM TAG & NUMBER
DRAWING OR
DETAIL TITLE
ELEVATION MARKER
DRAWING NAME
1/4" = 1'-0"
DRAWING SYMBOLS
=100'-0"
REFERENCE ELEV.
=
KEYNOTE
ENLARGED DETAIL
sheet
INT. & EXT. ELEV. TAG
WALL SECTION, BLDG. SECTION, INT. &
EXT. ELEV. TAG (DETAIL NUMBER,
SHEET NUMBER)
sheet
1
1
100
P#
OD. OUTSIDE DIAMETER
OH. OVERHEAD
OPG. OPENING
OPP. OPPOSITE
PCT. PRE-CAST
P.L. PROPERTY LINE
P.LAM. PLASTIC LAMINATE
PLAS. PLASTER
PLYWD. PLYWOOD
PR. PAIR
Q.T. QUARRY TILE
R. RISER
R.D. ROOF DRAIN
RE: REFER TO ...
REFR. REFRIGERATOR
REINF. REINFORCED
REQ'D. REQUIRED
RM ROOM
R.O. ROUGH OPENING
S SOUTH
S.C. SOLID CORE
SCHED. SCHEDULE
SECT. SECTION
S.F. SQUARE FOOT
SHT. SHEET
SIM. SIMILAR
SPEC. SPECIFICATION
SQ. SQUARE
S.S. STAINLESS STEEL
STAGG. STAGGERED
STD. STANDARD
STIFF STIFFENER
STL. STEEL
STRUC. STRUCTURAL
SUSP. SUSPENDED
TR TREAD
T & B TOP AND BOTTOM
TER. TERRAZZO
T & G TONGUE & GROOVE
THK. THICK
T/ TOP OF
TYP. TYPICAL
U.O.N. UNLESS OTHERWISE NOTED
U/G UNDERGROUND
VCT VINYL COMPOSTION TILE
VER VERIFY
VERT. VERTICAL
W WEST
W/ WITH
W.C. WATER CLOSET
WD. WOOD
W/O WITHOUT
℄ CENTERLINE
⅊ PLATE
Trianon Design Group
Telephone 239 390 1203
9990 Coconut RoadBonita Springs, Florida 34135
16111 Lee Road, Fort Myers, Florida, 33912
Gerald J. Yurk, AIA ARCHITECTAR 0005621
Project Description
Use of DocumentsDRAWINGS, SPECIFICATIONS AND OTHER DOCUMENTS PREPAREDBY GERALD J. YURK A.I.A. ARCHITECT TRIANON DESIGN GROUP(TDG), AND HIS CONSULTANTS,ARE INSTRUMENTS OF TDG'SSERVICE AND ARE FOR THE OWNER'S USE SOLELY WITH RESPECTTO THIS PROJECT. TDG SHALL RETAIN ALL COMMON LAW,STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THECOPYRIGHT. UPON COMPLETION OR TERMINATION OF THE PROJECT,ALL PARTIES, WITH THE EXCEPTION OF TDG'S, RIGHTS TO USETHESE INSTRUMENTS OF SERVICE SHALL CEASE. WHENTRANSMITTING COPYRIGHT-PROTECTED INFORMATION FOR USE ONTHE PROJECT, THE TRANSMITTING PARTY REPRESENTS THAT IT HASPERMISSION FROM THE TDG TO TRANSMIT THE INFORMATION FORITS USE ON THE PROJECT. QUESTIONS ARISING DURINGCONSTRUCTION OR REVIEW OF THE DRAWINGS SHALL BEADDRESSED TO THE ARCHITECT.
for Permit5-16-2018
New Construction - Industrial Building
PROPOSED MASONRY BUILDING WITH A PREFAB METAL BUILDINGSUB STRUCTURE
Alico Business Park
BUILDING DATA,
ABBREVIATIONS, GENERAL
LEGEND & NOTES
FLAMESPREAD INFORMATION
CARPET:
FRP PANEL SYSTEM:
ARMSTRONG ACOUSTIC CEILING TILES AND GRID:
ARMSTRONG ACOUSTIC CEILING TILES AND GRID:
ASTM E-84, FLAMESPREAD RATING, 25 OR LESS. (CLASS I) ASTM-E-84, SMOKE
DEVELOPED (10), 50 OR LESS.
ASTM E-1264, FLAMESPREAD RATING, 25 OR LESS. (CLASS I) ASTM E-1264, SMOKE
DEVELOPED, 50 OR LESS. A FIRE RESISTIVE CEILING WHEN USED IN APPLICABLE UL
ASSEMBLIES.
ASTM E-648, CLASS I - EXCEEDS .45 WATTS WATTS PER CM (DIRECT GLUE METHOD)
ASTM E-662-79, SMOKE DEVELOPED 450 OR LESS.
ASTM E-89a, FLAMESPREAD RATING (20), 25 OR LESS. (CLASS I) ASTM E-89a, SMOKE
DEVELOPED (425), 450 OR LESS.
PAINT:
ASTM E-84-79a, FLAMESPREAD RATING (15), 25 OR LESS. (CLASS I) ASTM E-84-79a,
SMOKE DEVELOPED (5), 50 OR LESS.
ARMSTRONG VINYL FLOOR TILES:
ASTM E-662, SMOKE DEVELOPED 450 OR LESS.
ASTM E-648, FLAMESPREAD RATING 25 OR LESS. (CLASS I)
ARMSTRONG VINYL BASE:
CERAMIC TILE FLOORING:
SINGLE FIRING CERAMIC TILES HAVE BEEN FOUND TO BE ABSOLUTELY INERT TO FIRE IN
PARTICULAR. THEY ARE NONFLAMMABLE.
ASTM E-648, CLASS I - EXCEEDS .45 WATTS WATTS/CM OR MORE
* = ADDITIONAL FLAME SPREAD INFORMATION REGARDING FIXTURES
* GENERAL FIRE RETARDANT COATING FOR SALES AREA ELEMENTS:
ASTM E-84, FLAMESPREAD RATING (20) - CLASS I RECOMMENDED USE: INTERIOR CLASS
A RATING. A FIRE RETARDANT AND WOOD PRESERVATIVE. IT CAN BE USED ON ANY
TYPE OF WOOD, POROUS OR NON-POROUS MATERIALS.
C
A
B
FLORIDA BUILDING CODE
SECTION 803.1.1
76 - 200
26 - 75
0 - 25
FLAME SPREAD
INDEX (FSI)
CLASSIFICATION
0-450
0-450
0-450
SMOKE-DEVELOPED
INDEX
SCOPE OF WORK
1.) EXISTING APPROVED SITE DEVELOPMENT PLAN
2.) NEW CONSTRUCTION PRE-FABRICATED METAL BUILDING WITH MASONRY SHELL.
APPLICABLE CODE REFERENCES:
FLORIDA BUILDING CODE - BUILDING 2017 6TH EDITION
FLORIDA BUILDING CODE - EXISTING 2017 6TH EDITION
FLORIDA PLUMBING CODE - 2017 6TH EDITION
FLORIDA MECHANICAL CODE - 2017 6TH EDITION
FLORIDA FUEL GAS CODE - 2017 6TH EDITION
FLORIDA FIRE PREVENTION CODE - 2017 6TH EDITION
FLORIDA ACCESSIBILITY CODE - 2017 6TH EDITION
NFPA 10, 2010 "STANDARDS FOR PORTABLE FIRE EXTINGUISHERS"
NFPA 70, 2014 "NATIONAL ELECTRIC CODE"
GROSS FLOOR AREA:
TYPICAL UNIT @ 2,400 SF EA (2) x 2,400 = 4,800
TYPICAL UNIT @ 2,200 SF EA (2) x 2,200 = 4,400
TYPICAL UNIT @ 2,000 SF EA (3) x 2,000 = 6,000
TOTAL BUILDING 15,200
I ) BUILDING CLASSIFICATION:
GROUP "S2" STORAGE (FBC SECTION 311)
II ) TYPE OF CONSTRUCTION:
BUILDING TYPE V-B, COMBUSTIBLE MATERIALS, S1-SPRINKLERED
III ) DESIGN CONSIDERATIONS PER WIND SPEED REQUIREMENTS:
THIS PROJECT SITE IS LOCATED IN A 160 MPH, EXPOSURE C, CATEGORY II ZONE.
THIS BUILDING HAS BEEN DESIGNED IN ACCORDANCE WITH THE FLORIDA BUILDING
CODE 6TH EDITION CHAPTER 16 FOR A DESIGN PRESSURE GENERATED BY A DESIGN
WIND VELOCITY OF 160 MPH. REFER TO STRUCTURAL DRAWINGS FOR ADDITIONAL
INFORMATION.
IV ) ALLOWABLE BUILDING HEIGHTS AND AREAS PER FBC TABLE 503
DESCRIPTION PERMITTED PROPOSED
BUILDING HT. 3- STORIES 1 - STORIES
60 FT 28'-0" ABOVE GRADE PLANE
54,000 S.F. 15,200 S.F.
IV ) FIRE RATINGS OF STRUCTURAL ELEMENTS PER FBC TABLE 601:
ELEMENT PERMITTED PROPOSED
STRUCTURAL FRAME 0 0
BEARING WALLS
EXTERIOR 0 0
INTERIOR 0 0
NONBEARING EXT. WALLS SEE TABLE 602
NONBEARING INT. WALLS 0 0
FLOOR CONSTRUCTION 0 0
ROOF CONSTRUCTION 0 0
V ) FIRE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION
DISTANCE PER TABLES 602 & 705.8
PERMITTED PROPOSED
EXT. WALL OPENINGS WALL RATING % OPEN WALL RATING %OPEN
EXT. BEARING WALLS
NORTH SIDE(> 30' TO ⅊)0- HR 0- HR NL 0- HR NL
SOUTH SIDE(> 30' TO ⅊)0- HR 0- HR NL 0- HR NL
EAST SIDE(> 30' TO ⅊) 0- HR NL 0- HR NL
WEST SIDE(> 30' TO ⅊) 0- HR NL 0- HR NL
NC = NON-COMBUSTIBLE
NL = NO LIMIT
VI ) OCCUPANT LOAD PER TABLE 1104.1.2
15,300 SQUARE FEET / 300 GROSS = 51 PERSONS
VII ) EGRESS REQUIREMENTS: FBC 1005.3.2
EXITS REQUIRED: 2 (PER FBC 1015.1 & 1021.2)
EXITS PROVIDED 14
MINIMUM EXIT WIDTH REQUIRED: (51 PERSONS X 0.2) = 10.2"
(MIN 32" CLEAR PER FBC 1008.1.1)
TOTAL EXIT WIDTH PROVIDED (14 X 36") = 504"
PROJECT DATA CHART
5. THE ENTIRE BUILDING SHALL BE PROTECTED WITH A FULLY AUTOMATIC FIRE
PROTECTION SYSTEM PER NFPA 13.
1. THE INTENT OF THE CONTRACT DOCUMENTS IS TO PRESENT A COMPLETE SET
OF DOCUMENTS FOR FACILITIES TO PRODUCE A COMPLETE AND FINISHED
PROJECT WITHIN THE SCOPE AS GENERALLY SHOWN IN THE DRAWINGS AND
SPECIFICATIONS. HOWEVER, THE ARCHITECT ACKNOWLEDGES THAT SPECIFIC
PARTS MAY NOT BE INCLUDED, AND CONTRACTOR AGREES TO ACCEPT ANY
NECESSARY ADDITIONAL INFORMATION AND INCLUDE AS AN INTEGRAL PART OF
THE CONTRACT DOCUMENTS WITHOUT ANY ADDITIONAL COST.
2. THE CONTRACTOR IS FURTHER CAUTIONED TO VERIFY ANY EXISTING
CONDITIONS WHICH MAY BE BELOW GROUND OR PART OF EXISTING CONDITIONS
WHICH WILL INTERFERE WITH THE CONSTRUCTION AS INDICATED ON THE
DRAWINGS AND DOCUMENTS. NO ADDITIONAL COMPENSATION WILL BE
APPROVED BY THE OWNER DUE TO FIELD CONDITIONS WHICH ARE NOT NOTED ON
THE DRAWINGS BUT WHICH COULD HAVE BEEN OBSERVED OR DETERMINED BY
SITE VISITATION AND THE REQUIREMENTS OF VERIFICATION CONTAINED AND
INHERENT IN THIS PARAGRAPH.
3. THE CONTRACTOR SHALL REPLACE ALL DAMAGED MATERIAL AND EQUIPMENT
WITH THOSE OF LIKE QUALITY SIZE AND TEXTURE, INCLUDING FINISHES ON ALL
SURFACES OF THE FACILITY W/ALL NEW PRODUCTS SO AS TO PRESENT A
FINISHED FACILITY TO THE OWNER.
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SECURITY AND LOSSES
DURING CONSTRUCTION.
GENERAL NOTES:
WIND EXPOSURE
THIS STRUCTURE HAS BEEN DESIGNED IN ACCORDANCE WITH THE
FLORIDA BUILDING CODE 5TH EDITION FOR THE FOLLOWING DESIGN
CRITERIA
WIND SPEED..........................................................................Vult = 160 MPH
Vasd = 124 MPH
BUILDING RISK CATEGORY = 2
WIND EXPOSURE = C
MEAN ROOF HEIGHT LESS THAN OR EQUAL TO 31 FEET
INTERNAL PRESSURE COEFFICIENT = 0.18 (enclosed)
ENCLOSED STRUCTURE IMPACT PROTECTION FOR BUILDING
OPENINGS SHALL BE PROVIDED BY IMPACT RESISTANT WINDOWS.
6. SEPERATE PERMITS SHALL BE REQUIRED AND SUPPLIED BY OTHERS FOR THE
FOLLOWING ITEMS
a. SPRINKLER SYSTEM
b. FIRE ALARM
c. TRASH ENCLOSURES
Corrections 10-30-18 clouded see project
data and signature
Corrections 1-22-19 clouded 15,200
SCORED STUCCO TYPICAL
8" STUCCO BAND TYPICAL8" STUCCO BAND TYPICAL
(1) 12" AND (1) 6"
STUCCO BAND TYPICAL
1'-4"x1'-4" PRECAST
MEDALION TYPICAL
T/ WALL
T/ STL
GRADE
T/ WALL
FOUNDATION SLAB ON GRADE
SEE STRUCTURAL DRAWINGS
STUCCO FINISH TYPICAL
SCORED STUCCO TYPICAL SCORED STUCCO TYPICAL
STUCCO FINISH TYPICAL
SEE SHEET A-5.00 FOR
SCORED STUCCO DETAILS
2 23 3
(1) 12" AND (1) 6"
STUCCO BAND TYPICAL
T/ WALL
T/ STL
GRADE
T/ WALL
STUCCO FINISH TYPICALSTUCCO FINISH TYPICAL
2233
PAINTED STUCCO FINISH AT INSIDE OF PARAPET WALL TYPICAL
SLOPED METAL ROOF DECKING BY STEEL BUILDING MANUFACTURER
8" DOWNSPOUT TYPICAL 8" DOWNSPOUT TYPICAL
T/ STL
GRADE
8" STUCCO BAND TYPICAL
T/ WALL
T/ STL
GRADE
T/ WALL
T/ STL
GRADE
SCORED STUCCO TYPICAL
1
STUCCO FINISH TYPICAL
SCORED STUCCO TYPICAL
8" STUCCO BAND TYPICAL
T/ WALL
T/ STL
GRADE
T/ WALL
T/ STL
GRADE
STUCCO FINISH TYPICAL
1
Trianon Design Group
Telephone 239 390 1203
9990 Coconut RoadBonita Springs, Florida 34135
16111 Lee Road, Fort Myers, Florida, 33912
Gerald J. Yurk, AIA ARCHITECTAR 0005621
Project Description
Use of DocumentsDRAWINGS, SPECIFICATIONS AND OTHER DOCUMENTS PREPAREDBY GERALD J. YURK A.I.A. ARCHITECT TRIANON DESIGN GROUP(TDG), AND HIS CONSULTANTS,ARE INSTRUMENTS OF TDG'SSERVICE AND ARE FOR THE OWNER'S USE SOLELY WITH RESPECTTO THIS PROJECT. TDG SHALL RETAIN ALL COMMON LAW,STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THECOPYRIGHT. UPON COMPLETION OR TERMINATION OF THE PROJECT,ALL PARTIES, WITH THE EXCEPTION OF TDG'S, RIGHTS TO USETHESE INSTRUMENTS OF SERVICE SHALL CEASE. WHENTRANSMITTING COPYRIGHT-PROTECTED INFORMATION FOR USE ONTHE PROJECT, THE TRANSMITTING PARTY REPRESENTS THAT IT HASPERMISSION FROM THE TDG TO TRANSMIT THE INFORMATION FORITS USE ON THE PROJECT. QUESTIONS ARISING DURINGCONSTRUCTION OR REVIEW OF THE DRAWINGS SHALL BEADDRESSED TO THE ARCHITECT.
for Permit5-16-2018
New Construction - Industrial Building
PROPOSED MASONRY BUILDING WITH A PREFAB METAL BUILDINGSUB STRUCTURE
Alico Business Park
EXTERIOR ELEVATIONS
EXTERIOR ELEVATION
1
EXTERIOR ELEVATION
2
EXTERIOR ELEVATION
4
EXTERIOR ELEVATION
3
CORRECTIONS 10-31-18 CHANGED HT TO 30'-0"
1
2
1
CORRECTIONS 1-22-19 CHANGED HT TO 30'-0"
2
CONCRETE FOOTING SEE
STRUCTURAL PLANS
5" CONC. MONO. SLAB - 3000 PSI
W/ 6 X 6 X 2.9/2.9 W.W.M OR
SUBSTITUTE 3000 PSI FIBERMESH
CONCRETE FOR W.W.M .006 POLY
VAPOR BARRIER, SOIL POISONING
(95%) MECH. COMPACTED FILL
STEEL BUILDING
BY OTHERS
8" CMU WALL W/ VERT. REINF.
SEE STRUCTIURAL DRAWINGS
UNFINISHED WALL
SCORED STUCCO FINISH SEE
EXTERIOR ELEVATIONS FOR
LOCATIONS AND DETAILS
INTERMEDIATE TIE BEAM SEE
STRUCTIURAL DRAWINGS
0'-0"
TOP OF SLAB
27'-11 1/4"
TOP OF WALL
TOP OF WALL FLASHING
SEE DETAIL @ ROOF PLAN
VARIES
TOP OF STEEL
3/4"x8" RECESS IN SLAB
TYPICAL AT PERIMETER
PROVIDE HORIZ. REINF. EVERY
OTHER COURSE TYPICAL
STEEL BUILDING
BY OTHERS
8" CMU WALL W/ VERT. REINF.
SEE STRUCTIURAL DRAWINGS
UNFINISHED WALL
INTERMEDIATE TIE BEAM SEE
STRUCTIURAL DRAWINGS
PROVIDE HORIZ. REINF. EVERY
OTHER COURSE TYPICAL
STEEL BUILDING &
ROOF BY OTHERS
CONCRETE FOOTING SEE
STRUCTURAL PLANS
5" CONC. MONO. SLAB - 3000 PSI
W/ 6 X 6 X 2.9/2.9 W.W.M OR
SUBSTITUTE 3000 PSI FIBERMESH
CONCRETE FOR W.W.M .006 POLY
VAPOR BARRIER, SOIL POISONING
(95%) MECH. COMPACTED FILL
5/8" STUCCO
FINISH
5/8" STUCCO FINISH
TOP OF WALL FLASHING
SEE DETAIL @ ROOF PLAN
CONT. FLASHING BEHIND STUCCO
PARAPET WALL
STUCCO FINISH
0'-0"
TOP OF SLAB
27'-11 1/4"
TOP OF WALL
25'-0"
TOP OF STEEL
30'-0"
TOP OF WALL
3/4"x8" RECESS IN SLAB
TYPICAL AT PERIMETER
PRECAST LINTEL
SEE STRUCTURAL
OPEN
METAL ROOF DECKING AND
SUPPORTS TO BE SUPPLIED BY
STEEL BUILDING MFR
TOP OF WALL FLASHING
SEE DETAIL @ ROOF PLAN
STUCCO TRIM BANDING SEE
EXTERIOR ELEVATIONS FOR
LOCATIONS AND DETAILS
3
5
8
" METAL STUDS
WITH
5
8
" DENSEGLAS @ 12'
a.f.f.
AND STUCCO PAINT TO
MATCH
EXTERIOR PAINT
OVERHEAD DOOR
SEE DOOR SCHEDULE
8" GUTTER
CONTINUOUS
8" DOWNSPOUT 25' ON
CENTER SEE ROOF PLAN
5/8" STUCCO FINISH
STEEL BUILDING
BY OTHERS
8" CMU WALL W/ VERT. REINF.
SEE STRUCTIURAL DRAWINGS
UNFINISHED WALL
INTERMEDIATE TIE BEAM SEE
STRUCTIURAL DRAWINGS
PROVIDE HORIZ. REINF. EVERY
OTHER COURSE TYPICAL
5" CONC. MONO. SLAB - 3000 PSI
W/ 6 X 6 X 2.9/2.9 W.W.M OR
SUBSTITUTE 3000 PSI FIBERMESH
CONCRETE FOR W.W.M .006 POLY
VAPOR BARRIER, SOIL POISONING
(95%) MECH. COMPACTED FILL
STEEL BUILDING &
ROOF BY OTHERS
CONT. FLASHING BEHIND STUCCO
PARAPET WALL
STUCCO FINISH
TOP OF WALL FLASHING
SEE DETAIL @ ROOF PLAN
0'-0"
TOP OF SLAB
27'-11 1/4"
TOP OF WALL
21'-8"
TOP OF STEEL
3/4"x8" RECESS IN SLAB
TYPICAL AT PERIMETER
STEEL BUILDING
BY OTHERS
8" CMU WALL W/ VERT. REINF.
SEE STRUCTIURAL DRAWINGS
UNFINISHED WALL
INTERMEDIATE TIE BEAM SEE
STRUCTIURAL DRAWINGS
PROVIDE HORIZ. REINF. EVERY
OTHER COURSE TYPICAL
STEEL BUILDING &
ROOF BY OTHERS
CONCRETE FOOTING SEE
STRUCTURAL PLANS
5" CONC. MONO. SLAB - 3000 PSI
W/ 6 X 6 X 2.9/2.9 W.W.M OR
SUBSTITUTE 3000 PSI FIBERMESH
CONCRETE FOR W.W.M .006 POLY
VAPOR BARRIER, SOIL POISONING
(95%) MECH. COMPACTED FILL
5/8" STUCCO
FINISH
TOP OF WALL FLASHING
SEE DETAIL @ ROOF PLAN
CONT. FLASHING BEHIND STUCCO
PARAPET WALL
STUCCO FINISH
0'-0"
TOP OF SLAB
27'-11 1/4"
TOP OF WALL
25'-0"
TOP OF STEEL
30'-0"
TOP OF WALL
STUCCO TRIM BANDING SEE
EXTERIOR ELEVATIONS FOR
LOCATIONS AND DETAILS
Trianon Design Group
Telephone 239 390 1203
9990 Coconut RoadBonita Springs, Florida 34135
16111 Lee Road, Fort Myers, Florida, 33912
Gerald J. Yurk, AIA ARCHITECTAR 0005621
Project Description
Use of DocumentsDRAWINGS, SPECIFICATIONS AND OTHER DOCUMENTS PREPAREDBY GERALD J. YURK A.I.A. ARCHITECT TRIANON DESIGN GROUP(TDG), AND HIS CONSULTANTS,ARE INSTRUMENTS OF TDG'SSERVICE AND ARE FOR THE OWNER'S USE SOLELY WITH RESPECTTO THIS PROJECT. TDG SHALL RETAIN ALL COMMON LAW,STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THECOPYRIGHT. UPON COMPLETION OR TERMINATION OF THE PROJECT,ALL PARTIES, WITH THE EXCEPTION OF TDG'S, RIGHTS TO USETHESE INSTRUMENTS OF SERVICE SHALL CEASE. WHENTRANSMITTING COPYRIGHT-PROTECTED INFORMATION FOR USE ONTHE PROJECT, THE TRANSMITTING PARTY REPRESENTS THAT IT HASPERMISSION FROM THE TDG TO TRANSMIT THE INFORMATION FORITS USE ON THE PROJECT. QUESTIONS ARISING DURINGCONSTRUCTION OR REVIEW OF THE DRAWINGS SHALL BEADDRESSED TO THE ARCHITECT.
for Permit5-16-2018
New Construction - Industrial Building
PROPOSED MASONRY BUILDING WITH A PREFAB METAL BUILDINGSUB STRUCTURE
Alico Business Park
WALL SECTIONS
WALL SECTION WALL SECTION WALL SECTION WALL SECTION
corrections 10-31-18 changed ht of wall to 30'-0"
soffit at section 2
GARAGE DOOR OPENERGDO
ELECTRICAL SPECIFICATIONS
25. THIS CONTRACTOR SHALL TOUCH UP OR REFINISH THE FACTORY FINISH OFEQUIPMENT MARRED DURING SHIPMENT OR INSTALLATION.
24. NOMINAL MOUNTING HEIGHT OF DEVICES IN EXPOSED CONCRETE BLOCK,TILE OR BRICK WALLS SHALL ALL OCCUR WITHIN A STRUCTURAL COURSE. AMINIMUM AMOUNT OF BLOCK, TILE OR BRICK WALLS SHALL BE CUT.
23. ALL ELECTRICAL DEVICES SHALL BE NEW, SPECIFICATION GRADE AND BELISTED FOR USE BY U.L. OR AN EQUAL TESTING LABORATORY.
27. SERIES-RATING OF CIRCUIT BREAKERS SHALL BE PERMITTED WHERE LISTEDFOR USE WITH SAME MANUFACTURER. FULLY-RATED CIRCUIT BREAKERSSHALL BE USED WITH MIXING MANUFACTURER TYPES. CIRCUIT BREAKERSPROTECTING HVAC EQUIPMENT SHALL BE HACR RATED. (EQUIPMENT ISSPECIFIED TO MEET THESE REQUIREMENTS)
26. CONNECTIONS TO ELECTRICAL EQUIPMENT EXPOSED TO WEATHER SHALL BEMADE WITH WATER TIGHT FITTINGS AND BE NEMA 3R RATED.
28. VERIFY AND COMPLY WITH ALL REQUIREMENTS OF POWER COMPANY,TELEPHONE & CABLE COMPANIES PRIOR TO INSTALLATION.
29. ALL MATERIALS SHALL BE NEW AND BEAR UNDERWRITER'S LABELS, WHEREAPPLICABLE.
30. ALL CIRCUIT BREAKERS, TWO AND THREE POLE, TO BE COMMON TRIP NO TIEHANDLES, TANDEMS OR "WAFER BREAKERS" WILL NOT BE ACCEPTED.
CONDUITS AND ENCLOSURES
EMT CONDUIT
EMT CONDUIT HOMERUNS, MC CABLE BEYOND SWITCH FOR LIGHTING
EMT/PVC SCHEDULE 40 CONDUIT FEEDERS, MC CABLE BRANCH CIRCUITRY
PVC SCHEDULE 40 UNDER SLAB OR GRADE AND WITHIN MASONRY WALLS WITHLISTED FITTINGS (3/4" TRADE SIZE MINIMUM)
PVC SCHEDULE 80 (SERVICE ENTRANCE)
MC CABLE, PLENUM RATED
MC CABLE WITH HVAC CIRCUITS IN OUTSIDE DWELLING UNIT IN CONDUIT
PVC SCHEDULE 40 ABOVE SLAB OR GRADE DUE TO CORROSIVE ELEMENTS
RIGID STEEL OR IMC CONDUIT
NMB NON-METALLIC, UF AND SER, CABLE TYPES
RACEWAY AND WIRING METHODS FOR DATA AND COMMUNICATIONS:
EMT CONDUIT FROM 4" SQ OUTLET BOX TO ACCESSIBLE CEILING AREA
EMT CONDUIT FROM 4" SQ OUTLET BOX TO CABLE TRAY
PVC SCHEDULE 40 UNDER SLAB FROM OUTLET BOX TO TERMINAL BACKBOARD
FREE WIRE IN WALLS AND CEILING
RACEWAY AND WIRING METHODS FOR FIRE ALARM SYSTEM:
EMT CONDUIT WITH FITTINGS LISTED FOR USE
EMT CONDUIT FROM 4" SQ OUTLET BOX TO ACCESSIBLE CEILING AREA, FREEWIRE ABOVE CEILINGS.
PVC SCHEDULE 40 UNDER SLAB FROM OUTLET BOX TO OUTLET BOX WITHLISTED FITTINGS
EMT CONDUIT IN WALLS, FREE WIRE ABOVE CEILINGS
FREE WIRE IN WALLS AND CEILINGS
CONDUCTORS USED ON THIS PROJECT:
COPPER CONDUCTORS , 75°C RATED, THWN INSULATION (MIN. #14 AWG)
COMPACT ALUMINUM CONDUCTORS, 75°C RATED, XHHW INSULATION (AS NOTED)
COMPACT ALUMINUM CONDUCTORS, TYPE USE-2 / RHH / RHW-2 DIRECT BURIALRATED, USED FOR 'TEMPORARY POWER ONLY'
SUBMIT CLEAN, MARKED IN RED INK OR YELLOW HIGHLIGHTER, AS ONE PDF SETOF SHOP DRAWING(S) FOR APPROVAL, FOR THE FOLLOWING APPLICABLE 1995DIVISIONS:
16110 - RACEWAYS, BOXES, FITTINGS HARDWARE AND SUPPORTS16120 - WIRE , CABLE, TERMINATIONS AND MARKERS16140 - WIRING DEVICES, PLATES AND COVERS16150 - DISCONNECTS, STARTERS, CONTACTORS, SURGE PROTECTION DEVICES, & FUSES16430 - SERVICE EQUIPMENT AND METERING16450 - GROUNDING SYSTEM16470 - DISTRIBUTION, PANELBOARDS AND TRANSFORMERS16510 - LIGHTING FIXTURES AND ACCESSORIES16860 - AUTOMATIC TRANSFER SWITCHES16880 - GENERATOR16990 - UNDERGROUND CONDUIT DRAWING WITH TRADE SIZES (THIS MAY BE PROVIDED SEPARATELY AS A DWG FILE OR LEGIBLY MARKED IN RED INK
ON 24" X 36" SHEET)
AMPS OR AMPERE
AMPERE INTERRUPTING CAPACITY
ABOVE BASE FLOOD ELEVATION
ABOVE FINISHED FLOORARC FAULT CIRCUIT INTERRUPTER
ALUMINUM
AMERICAN WIRE GAUGEAIR HANDLING UNIT
CIRCUIT BREAKERCONDENSING UNIT
BREAKER
AUTOMATIC TRANSFER SWITCH
AABFE
AFFAFCI
ALAIC
AHUATS
BKRCB
AWG
CU
GENERATOR
GROUNDGROUND FAULT CIRCUIT INTERRUPTERGALVANIZED RIGID STEEL
KILOWATTSKILOVOLT AMPERES
GEN
GRSGFCI
KWKVA
GRD
MAXIMUM
MOTOR CONTROL CENTERMAXIMUM OVER-CURRENT PROTECTION DEVICEMINIMUM
NEUTRALNORMALLY CLOSED
MANUAL TRANSFER SWITCHMAIN LUGS ONLY
NOT IN CONTRACT
MEDIUM VOLTAGE
MAX
MCCMOCP
MLOMIN
N
MTSMV
NC
NIC
OVERHEAD
PHASE
PRIMARY
NOT TO SCALE
PANEL, PANELBOARD OR LOADCENTER
QUANTITYRECEPTACLE
POLYVINYL CHLORIDE
NTSOH
PH
PRI
PNL
PVC
RECPTQTY
NO NORMALLY OPEN OR NUMBER
SOLID NEUTRAL
STAINLESS STEEL
SECONDARY
SWITCHSWITCHBOARD
TELEPHONE
TIME TO CLOSE OR TRAY CABLE
TELEPHONE BACKBOARD
SN
SS
SEC
SW
TCSWBD
TBBDTEL
ABBREVIATIONS
TYPICAL
VOLTS
UNDERGROUND
WEATHERPROOF
VOLT AMPERESVARIABLE FREQUENCY DRIVEWIRE, WATTS, WITH, WIDTH
UNINTERRUPTIBLE POWER SUPPLY
WEATHER RESISTANT
UG
V
TYP
UPS
VA
WPWVFD
WR
SURGE SUPPRESSION DEVICESPD
DISCONNECTDISC
ELECTRICELECELEVATIONELEVEMERGENCYEM
ELECTRICAL METALLIC CONDUITEMTELECTRIC WATER COOLEREWCEXITEXEXISTING(E)
EXHAUST FANEF
EQUIPMENT GROUND(EG)FLEXIBLE METALLIC TUBINGFMT
ABOVE COUNTER TOPACT
HEATING VENTILATION AIR CONDITIONINGHVACHOMERUNHRHEATERHTRHERTZHZ
JUNCTION BOXJ
1000 CIRCULAR MILSKCMIL
LIGHTINGLGTS
HIGH VOLTAGEHV
LIQUIDTIGHT FLEXIBLE NON-METALLIC CONDUITLFNC
HEATING, AIR-CONDITIONING, REFRIGERATIONHACR
MINIMUM CIRCUIT AMPACITYMCAMETAL-CLAD MC
PUSHBUTTONPB
NATIONAL ELECTRICAL MANUF ASSOCIATIONNEMA
PHOTO-ELECTRIC CELLP/C
TRANSFORMERXFMR
UNDERCOUNTERUC
GROUNDING ELECTRODE CONDUCTORGEC
DISCONNECT
SINGLE POLE SWITCH
3 WAY SWITCH
ELECTRICAL LEGEND
DUPLEX RECEPTACLE 125V
PANELBOARD 20" WIDE
SWITCH WIRING
RECESSED DOWNLIGHT
WALL MOUNT LIGHTING FIXTURE
SMOKE DETECTOR
DUPLEX GFCI 15A, 125V RECEPTACLE
DUPLEX RECEPTACLE 15A, 125V (HALF SWITCHED)
SINGLE RECEPTACLE 125/250V, 4-WIRE
DUPLEX FLOOR RECEPTACLE 15A, 125V
BATHROOM EXHAUST FAN
PHONE/DATA OUTLET
CATV / SATELLITE TELEVISION OUTLET
EXTERIOR SECURITY LIGHTS
COMPUTER/DATA (POINT OF ENTRY)
QUAD RECEPTACLE 15A, 125V
PENDANT / CHANDELIER
RECESSED DOWNLIGHT (WALL WASHER)
4 WAY SWITCH
SINGLE RECEPTACLE 20A, 125V
HOMERUN
SURFACE MOUNT LIGHTING FIXTURE
PANEL (CIRCUIT) DESIGNATIONA-1
S
DOOR JAMB SWITCH EQUAL TO LEVITON 1865
DEADFRONT GFCI 20A, 125V
DOOR CHIME
PUSH BUTTON
TRANSFORMER - 50V OR LESS
FLUORESCENT CLOUD FIXTURE
SCONCE OR STEP LIGHTING FIXTURE
RACEWAY & WIRING METHODS
NON FUSENF
THE METHODS IDENTIFIED BELOW SHALL BE USED FOR THIS PROJECT:
TRANSFORMER - GREATER THAN 50V
5. DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO SHOW APPROXIMATELOCATIONS. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY ANDALL DETAILS OF CONSTRUCTION. THE ELECTRICAL CONTRACTOR SHALLFURNISH AND INSTALL ALL ITEMS TO PROVIDE A COMPLETE ELECTRICALINSTALLATION WITH ALL EQUIPMENT IN PROPER WORKING ORDER.
1. THE GENERAL CONDITIONS OF THE CONTRACT, CURRENT EDITION,PUBLISHED IN STANDARD FORM BY THE AMERICAN INSTITUTE OFARCHITECTS SHALL BE PART OF THIS CONTRACT.
31. THE FIRE ALARM CONTRACTOR SHALL PROVIDE SHOP DRAWINGS, PERMIT(S)AND PAY ALL FEES ASSOCIATED WITH HIS WORK.
7. BIDDERS SHALL VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH ALLCONDITIONS SURROUNDING THE WORK. IN SOME AREAS, EXISTING PLANSARE NON-EXISTENT OR VAGUE. IT SHALL BE THE RESPONSIBILITY OF THEBIDDERS TO VISIT THE SITE OF THE WORK AND ACQUAINT THEMSELVES WITHALL AVAILABLE INFORMATION REGARDING THE LOCATION OF ALL EXISTINGFACILITIES. FAILURE OF THE BIDDERS TO SO INFORM THEMSELVES OFEXISTING CONDITIONS AND TO INCLUDE IN THEIR PROPOSALS A SUMSUFFICIENT TO COVER SAME WILL NOT ENTITLE THEM TO AN EXTRA.
4. THE CONTRACTOR SHALL REFERRED TO THE ARCHITECTURAL, STRUCTURALAND MECHANICAL PLANS AND SPECIFICATIONS. SUCH PLANS ANDSPECIFICATIONS ARE CONTRACT DOCUMENTS. VERIFY ALL MECHANICALREQUIREMENTS PRIOR TO INSTALLATION.
8. SHOULD ELECTRICAL WORK BE INSTALLED WHICH INTERFERES WITHCLEARANCES REQUIRED FOR GENERAL CONSTRUCTION OR WORK WITHOTHER TRADES, SUCH WORK SHALL BE CORRECTED AT NO ADDITIONAL COSTTO THE OWNER.
13. UPON COMPLETION OF THE WORK, THIS CONTRACTOR SHALL REMOVE ALLRUBBISH CAUSED BY HIS WORK AND SHALL THOROUGHLY CLEAN ALLELECTRIC EQUIPMENT.
15. ALL WORK SHALL BE GUARANTEED FREE FROM DEFECTS FOR A PERIOD OFONE YEAR FROM DATE OF CERTIFICATE OF OCCUPANCY.
12. CONTRACTOR SHALL BE RESPONSIBLE TO SEAL PENETRATIONS IN RATEDWALLS OR FLOORS WITH LISTED SMOKE/FIRE RATED ASSEMBLIES.
16. MOTOR STARTERS AND CONTROLS FURNISHED BY THE MECHANICALCONTRACTOR SHALL BE INSTALLED BY THE ELECTRICAL CONTRACTOR. ALLCONTROL WIRING OF MECHANICAL CONTRACTORS EQUIPMENT SHALLINSTALLED AND TERMINATED BY THE MECHANICAL CONTRACTOR. THE E.C.SHALL PROVIDE POWER SUPPLY WIRING.
6. DO NOT SCALE THE ELECTRICAL DRAWINGS. REFER TO ARCHITECTURALPLANS AND ELEVATIONS FOR EXACT LOCATION OF ALL EQUIPMENT, CONFIRMWITH OWNER'S REPRESENTATIVE.
2. THE CONTRACTOR SHALL BE A LICENSED MASTER ELECTRICIAN, ANDSHALL SUPERVISE THE ENTIRE INSTALLATION TO BE PERFORMED IN A'NEAT AND WORKMANLIKE' MANNER, PLUMB AND LEVEL, COORDINATEDWITH ALL OTHER TRADES, IN COMPLIANCE WITH THE 2008 EDITION OF THENFPA 70 NATIONAL ELECTRIC CODE, THE 2009 NFPA 70E STANDARD FORELECTRICAL SAFETY IN THE WORK PLACE, FLORIDA BUILDING CODE 2010EDITION, FLORIDA FIRE PREVENTION CODE 2010 EDITION, POWER UTILITYAND INSPECTION AUTHORITY.
17. THE CONTRACTOR SHALL PROVIDE DISCONNECT SWITCHES, EXCEPT WHENFACTORY INSTALLED.
11. EQUIPMENT SHALL BE INSTALLED ABOVE THE BASE FLOOD ELEVATION.SERVICE DISCONNECT(S) AND BREAKERS USED AS SWITCHES ABOVE 6'-7"SHALL BE ACCESSIBLE FROM FLOOR OR WORKING PLATFORM 30" WIDTH, 36"DEPTH WORK SPACE IN FRONT OF EQUIPMENT.
18. ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY POWER FORCONSTRUCTION WITH GFCI PROTECTION.
14. PROVIDE AUTOCAD COMPATIBLE AS-BUILT DRAWINGS AT COMPLETION OFPROJECT.
3. THE 'CONTRACTOR' IN THESE SPECIFICATIONS SHALL REFER TO THEELECTRICAL CONTRACTOR, UNLESS NOTED OTHERWISE.
9. ALL REQUIRED INSURANCE SHALL BE PROVIDED FOR PROTECTION AGAINSTLIABILITY OF PROPERTY DAMAGE FOR THE DURATION OF THE WORK.
10. THE ENGINEER SHALL NOTIFY THE AUTHORITY HAVING JURISDICTION ANDTHE CONTRACTOR OF INSTALLATIONS THAT DO NOT QUALIFY AS 'NEAT ANDWORKMANLIKE', TO BE CORRECTED PRIOR TO SUBSEQUENT INSPECTION.
19. DISTRIBUTION PANELS, PANELBOARDS, AND TRANSFORMERS SHALL BEIDENTIFIED USING ENGRAVED, LAMINATED ACRYLIC OR MELAMINE LABELWHITE LETTERS ON DARK BACKGROUND, LETTER HEIGHT TO BE 3/8" AFFIXEDTO COVER.
21. JUNCTION AND PULL BOXES SHALL HAVE PANEL/CIRCUIT NUMBER MARKEDON FACE OF COVER.
22. DISCONNECTS, STARTERS, MOTOR CONTROL CENTERS SHALL BE IDENTIFIEDWITH EQUIPMENT SERVED AND CIRCUIT ORIGINATION.
{EXAMPLE: AHU-1 (B-26,28)}
20. DISCONNECTS, STARTERS, MOTOR CONTROL CENTERS SHALL BE IDENTIFIEDWITH EQUIPMENT SERVED AND PANEL/CIRCUIT NUMBER. {EXAMPLE: AHU-1(B-26,28)}
NOTE: LISTED FITTINGS FOR METALLIC ENCLOSURES ARE PVC MALE ADAPTORSWITH LOCKNUTS. SEE UL-651 SECTION
1.5.1 JUNCTION-BOX ADAPTORS COVERED BY THESE REQUIREMENTS AREFITTINGS INTENDED TO CONNECT A LENGTH OF RIGID PVC CONDUIT, A PVCELBOW TO A RIGID PVC BOX (NOT LIMITED TO JUNCTION BOXES) WITH ACOUPLING.
1.5.2 INTERNALLY-THREADED ADAPTORS COVERED BY THESE REQUIREMENTSARE FITTINGS INTENDED FOR JOINING A LENGTH OF RIGID PVC CONDUIT, APVC ELBOW TO RIGID METAL CONDUIT OR OTHER EXTERNALLY THREADEDDEVICES.
1.5.2 EXTERNALLY-THREADED ADAPTORS (ALSO REFERRED TO AS TERMINALADAPTORS) COVERED BY THESE REQUIREMENTS ARE FITTINGS INTENDEDTO JOIN A LENGTH OF RIGID PVC CONDUIT OR ELBOW TO:
a) THE KNOCKOUT AREA OF A METAL BOX WITH A METAL LOCKNUT,b) A THREADED METAL HUB OR FITTING OF A METAL BOX,c) A THREADED HUB ON A PHENOLIC BOXd) A KNOCKOUT IN A PHENOLIC BOX
S3
S4
SPECIAL RECEPTACLE
LOADCENTER 16" WIDE
EQUIPMENT GROUNDING CONDUCTOREG
CHIME
EF
F FAN RATED OUTLET BOX, FAN SWITCH LEG ONLY
J JUNCTION BOX
F FAN RATED OUTLET BOX WITH LIGHT/FAN DESIGNATIONL F
FLUORESCENT WRAP-AROUND FIXTURE
ILLUMINATED EXIT SIGN
EGRESS DIRECTIONAL CHEVRONS
EXIT SIGN / EMERGENCY LIGHTING FIXTURE COMBO
BATTERY BACKUP EMERGENCY EGRESS FIXTURE
UNDERCOUNTER LIGHTING FIXTURE
UTILITY METER
TRACK LIGHTING FIXTURE
COMBINATION MOTOR STARTER
VAPORTITE ENCLOSED & GASKETED LIGHTING FIXTURE
CONDUIT OPENINGS. CONDUIT OPENINGS SHALL BE MADE BY ECCENTRIC ANDCONCENTRIC MANUFACTURED OPENINGS AND TRADE CONDUIT SIZE FIELDKNOCKOUT PUNCH. OPENINGS SHALL NOT BE MADE BY FRACTIONAL HOLEENLARGING DRILL BITS.
USE OF PVC CONDUIT AND FITTINGS IN NEMA 3, 3R, 4, 4X & 12 METALLICENCLOSURES.THE FOLLOWING METHODS OF INSTALLATION SHALL BE PERMITTED WITH PVCCONDUIT AND FITTINGS IN (a), (b), (c) or (d) BELOW.
a) CONDUIT ENTRIES IN BOTTOM OF ENCLOSURES (BOXES, WIREWAYS ANDAUXILIARY GUTTERS) SHALL BE MADE WITH MALE ADAPTOR, AND LOCKNUTSECURED TO THE ENCLOSURE (UL 651, SECTION 1.5), PLASTIC BUSHING
b) CONDUIT ENTRIES IN THE TOP OR SIDE OF ENCLOSURES (BOXES, WIREWAYSAND AUXILIARY GUTTERS) SHALL BE MADE WITH MALE ADAPTOR, FLAT SEALINGWASHER (EXTERNAL TO ENCLOSURE) AND LOCKNUT WITHIN THE ENCLOSURE,PLASTIC BUSHING.
c) CONDUIT ENTRIES IN THE SIDE OF ENCLOSURES ABOVE THE LEVEL OFUNINSULATED LIVE PARTS (SEE NFPA 70, SECTION 312) SHALL BE MADE WITHACCEPTABLE RAINTIGHT HUB. (AN ACCEPTABLE RAINTIGHT HUB IS A HUB MADEBY THE ENCLOSURE MANUFACTURER OR A WATER TIGHT THREADED HUB)
d) CONDUIT ENTRIES IN THE BOTTOM OF AN ENCLOSURE WITH UNINSULATEDLIVE PARTS SHALL BE MADE WITH A PVC MALE ADAPTOR, FLAT SEALINGWASHER (EXTERNAL TO ENCLOSURE) AND LOCKNUT WITHIN THE ENCLOSURE,PLASTIC BUSHING.
NO ENTRIES SHALL BE MADE IN THE TOP OF ENCLOSURES WITH UNINSULATEDLIVE PARTS
PVC JUNCTION BOX ADAPTERS ARE NOT PERMITTED (UL 651, SECTION 1.5.1)
OTHER CONDUIT ENTRIES IN NEMA 3, 3R, 4, 4X & 12 METALLIC ENCLOSURES .
THE FOLLOWING METHODS OF INSTALLATION SHALL BE PERMITTED FORCONDUITS AND FITTINGS OTHER THAN PVC CONDUIT.
a) CONDUIT ENTRIES IN BOTTOM OF ENCLOSURES SHALL BE MADE WITHRAINTIGHT COMPRESSION CONNECTORS AND LOCKNUT SECURED TIGHTLY TOTHE ENCLOSURE.
b) ENTRIES IN THE SIDE OF ENCLOSURES (BOXES, WIREWAYS AND AUXILIARYGUTTERS) SHALL BE MADE WITH A CONNECTOR, FLAT SEALING WASHER(EXTERNAL TO ENCLOSURE) AND LOCKNUT WITHIN THE ENCLOSURE, PLASTICBUSHING. OTHER APPROVED MEANS ARE:
1) EMT RAINTIGHT COMPRESSION CONNECTORS EQUAL TO BRIDGEPORT 'RT2'SERIES
2) RIGID STEEL AND IMC CONDUIT AND NIPPLES WITH SEALING LOCKNUTSINSTALLED OUTSIDE OF ENCLOSURE AND LOCKNUT WITHIN ENCLOSURE,PLASTIC BUSHING.
3) ENTRIES IN THE TOP AND SIDE OF ENCLOSURES ABOVE THE LEVEL OFUNINSULATED LIVE PARTS (SEE NFPA 70, SECTION 312) SHALL BE MADE WITHACCEPTABLE RAINTIGHT HUB. AN ACCEPTABLE RAINTIGHT HUB IS A HUB MADEBY THE ENCLOSURE MANUFACTURER OR A WATER TIGHT THREADED HUB.
a) NEMA 3 AND 3R STEEL ENCLOSURE SHALL USE THREADED HUBS EQUAL TOCOOPER CROUSE-HINDS SCRU-TITE HUB 'ST' SERIES, OR GROUND HUB 'STG'ZINC OR MALLEABLE IRON CONDUIT HUB
b) NEMA 3 AND 3R ALUMINUM ENCLOSURE SHALL USE THREADED HUBS EQUALTO COOPER CROUSE-HINDS SCRU-TITE HUB 'STA' SERIES, OR GROUND HUB'STGA' ALUMINUM HUB
c) NEMA 4X STAINLESS STEEL ENCLOSURE SHALL USE THREADED HUBS EQUALTO COOPER CROUSE-HINDS SCRU-TITE HUB 'STTG' SERIES
ELECTRICAL ROUGH FOR COMMERCIAL SHELL BUILDING
SCOPE OF WORK
FLORIDA POWER & LIGHTFPL
LOW VOLTAGELV
EXIT SIGN
DRAWING INDEX
E-0.00A ELECTRICAL LEGEND, NOTES, INDEX & ABBREVIATIONSE-1.00A OVERALL ELECTRICAL PLANE-1.01A PARTIAL ELECTRICAL PLANE-1.02A PARTIAL ELECTRICAL PLANE-2.00A LOAD CALCULATIONS, PANEL & RISER
E-0.00 A
ELECTRICAL LEGEND,NOTES, INDEX &ABBREVIATIONS
Trianon Design Group
Telephone 239 289 2629
8831 Business Park Drive Building 3Fort Myers, Florida 33912
16111 Lee Road, Fort Myers, Florida, 33912
Gerald J. Yurk, AIA ARCHITECTAR 0005621
Building and Code DataAPPLICABLE CODES
Project Description
Use of DocumentsDRAWINGS, SPECIFICATIONS AND OTHER DOCUMENTS PREPAREDBY GERALD J. YURK A.I.A. ARCHITECT TRIANON DESIGN GROUP(TDG), AND HIS CONSULTANTS,ARE INSTRUMENTS OF TDG'SSERVICE AND ARE FOR THE OWNER'S USE SOLELY WITH RESPECTTO THIS PROJECT. TDG SHALL RETAIN ALL COMMON LAW,STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THECOPYRIGHT. UPON COMPLETION OR TERMINATION OF THE PROJECT,ALL PARTIES, WITH THE EXCEPTION OF TDG'S, RIGHTS TO USETHESE INSTRUMENTS OF SERVICE SHALL CEASE. WHENTRANSMITTING COPYRIGHT-PROTECTED INFORMATION FOR USE ONTHE PROJECT, THE TRANSMITTING PARTY REPRESENTS THAT IT HASPERMISSION FROM THE TDG TO TRANSMIT THE INFORMATION FORITS USE ON THE PROJECT. QUESTIONS ARISING DURINGCONSTRUCTION OR REVIEW OF THE DRAWINGS SHALL BEADDRESSED TO THE ARCHITECT.
for Permit7-1-2016
2014 FLORIDA BUILDING CODE-BUILDING, 5TH EDITION 2014 FLORIDA PLUMBING CODE, 5TH EDITION 2014 FLORIDA MECHANICAL CODE, 5TH EDITION 2014 FLORIDA FUEL GAS CODE, 5TH EDITION 2014 FLORIDA ENERGY CONSERVATION CODE, 5TH EDITION 2014 FLORIDA FIRE PREVENTION CODE, 5TH EDITION 2002-01 BUILDING CONSTRUCTION ADMINISTRATIVE CODE CHAPTER 16 SAFEGUARDS DURING CONSTRUCTION ALTERATION
AND DEMOLITION OPERATIONS WITH LOCAL FIRE MARSHALL 2011 NFPA 70 NATIONAL ELECTRICAL CODE
New Construction - Industrial Building
PROPOSED MASONRY BUILDING WITH A PREFAB METAL BUILDINGSUB STRUCTURE
Alico Business Park
NOT FOR CONSTRUCTION
WP
A
B
C
D
E
G
F
1 2 3 84 5 6 7
UNIT7-100
UNIT7-101
UNIT7-102
UNIT7-103
UNIT7-104
UNIT7-105
UNIT7-106
ENTRY7-000
ENTRY7-001
C C
C C
C
C
C
C
C
C
C
C
C
C
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
A A
EXIT SIGN
EXIT SIGN
EXIT SIGN EXIT SIGN EXIT SIGN
EXIT SIGN EXIT SIGN EXIT SIGN EXIT SIGN EXIT SIGN EXIT SIGN
CW CW CW
CW CW
CW CW
J J J JJ J J
EXM EXM EXM EXM EXM EXM EXM
EXM EXM EXM EXM
WP(SIGN)
J
WP(SIGN)
J
1 1 1 1 1 1 1
WP WP WP WPWP WP
J
WP(SIGN)
2
2 2
WP(SIGN)
J
2
3
J
3
J
3
J
3
J
3
J
3
J
3
J
3
J
TELEPHONE SERVICE
CATV SERVICE
ELECTRICALSERVICE
HOUSEPANEL
PROVIDE (2) 3/4" PVC W/ PULLSTRING ABOVE CEILING TO MIDBAY OF EACH UNIT FOR TELE /CATV
A A
EXIT SIGN EXIT SIGN
EXM EXM
WP(SIGN)
J J
WP(SIGN)
2 2
3
J
3
J
3
J
WP(SIGN)
J
2
EXIT SIGN
EXM3
J
3
J
3
J
CW
CW CW
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
H 5,7
H4
H 5,7 H 5,7
H 5,7
H 5,7
H 5,7
H 5,7
H 5,7H9 H9 H9 H9
H 5,7H 5,7
H2 H2 H2 H2 H2 H2 H2
H2H2H2H2H2H2H2
E-1.00 A
OVERALLELECTRICAL PLAN
Trianon Design Group
Telephone 239 289 2629
8831 Business Park Drive Building 3Fort Myers, Florida 33912
16111 Lee Road, Fort Myers, Florida, 33912
Gerald J. Yurk, AIA ARCHITECTAR 0005621
Building and Code DataAPPLICABLE CODES
Project Description
Use of DocumentsDRAWINGS, SPECIFICATIONS AND OTHER DOCUMENTS PREPAREDBY GERALD J. YURK A.I.A. ARCHITECT TRIANON DESIGN GROUP(TDG), AND HIS CONSULTANTS,ARE INSTRUMENTS OF TDG'SSERVICE AND ARE FOR THE OWNER'S USE SOLELY WITH RESPECTTO THIS PROJECT. TDG SHALL RETAIN ALL COMMON LAW,STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THECOPYRIGHT. UPON COMPLETION OR TERMINATION OF THE PROJECT,ALL PARTIES, WITH THE EXCEPTION OF TDG'S, RIGHTS TO USETHESE INSTRUMENTS OF SERVICE SHALL CEASE. WHENTRANSMITTING COPYRIGHT-PROTECTED INFORMATION FOR USE ONTHE PROJECT, THE TRANSMITTING PARTY REPRESENTS THAT IT HASPERMISSION FROM THE TDG TO TRANSMIT THE INFORMATION FORITS USE ON THE PROJECT. QUESTIONS ARISING DURINGCONSTRUCTION OR REVIEW OF THE DRAWINGS SHALL BEADDRESSED TO THE ARCHITECT.
for Permit7-1-2016
2014 FLORIDA BUILDING CODE-BUILDING, 5TH EDITION 2014 FLORIDA PLUMBING CODE, 5TH EDITION 2014 FLORIDA MECHANICAL CODE, 5TH EDITION 2014 FLORIDA FUEL GAS CODE, 5TH EDITION 2014 FLORIDA ENERGY CONSERVATION CODE, 5TH EDITION 2014 FLORIDA FIRE PREVENTION CODE, 5TH EDITION 2002-01 BUILDING CONSTRUCTION ADMINISTRATIVE CODE CHAPTER 16 SAFEGUARDS DURING CONSTRUCTION ALTERATION
AND DEMOLITION OPERATIONS WITH LOCAL FIRE MARSHALL 2011 NFPA 70 NATIONAL ELECTRICAL CODE
New Construction - Industrial Building
PROPOSED MASONRY BUILDING WITH A PREFAB METAL BUILDINGSUB STRUCTURE
Alico Business Park
NOT FOR CONSTRUCTION
BUILDING ELECTRICAL PLAN
UNIT7-100
UNIT7-101
UNIT7-102
UNIT7-103
UNIT7-104
UNIT7-105
UNIT7-106
ENTRY7-000
ENTRY7-001
KEY PLAN
WP
A
B
C
D
E
G
F
1 2 3 4 5
UNIT7-100
UNIT7-101
UNIT7-102
UNIT7-103
UNIT7-104
ENTRY7-000
C C
C C
C
C
C
C
C
C
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
A A
EXIT SIGN
EXIT SIGN
EXIT SIGN EXIT SIGN EXIT SIGN
EXIT SIGN EXIT SIGN EXIT SIGN EXIT SIGN
CW CW
CW
CW
J J JJ J
EXM EXM EXM EXM EXM
EXM EXM EXM EXM
WP(SIGN)
J
WP(SIGN)
J
1 1 1 1 1
WP WP WP WP
J
WP(SIGN)
2
2 2
WP(SIGN)
J
2
3
J
3
J
3
J
3
J
3
J
3
J
3
J
3
J
3
J
CW
CW
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
H 5,7
H4
H 5,7
H 5,7
H 5,7
H 5,7H9 H9
H 5,7
H2 H2 H2 H2 H2
H2H2H2H2
E-1.01 A
PARTIALELECTRICAL PLAN
Trianon Design Group
Telephone 239 289 2629
8831 Business Park Drive Building 3Fort Myers, Florida 33912
16111 Lee Road, Fort Myers, Florida, 33912
Gerald J. Yurk, AIA ARCHITECTAR 0005621
Building and Code DataAPPLICABLE CODES
Project Description
Use of DocumentsDRAWINGS, SPECIFICATIONS AND OTHER DOCUMENTS PREPAREDBY GERALD J. YURK A.I.A. ARCHITECT TRIANON DESIGN GROUP(TDG), AND HIS CONSULTANTS,ARE INSTRUMENTS OF TDG'SSERVICE AND ARE FOR THE OWNER'S USE SOLELY WITH RESPECTTO THIS PROJECT. TDG SHALL RETAIN ALL COMMON LAW,STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THECOPYRIGHT. UPON COMPLETION OR TERMINATION OF THE PROJECT,ALL PARTIES, WITH THE EXCEPTION OF TDG'S, RIGHTS TO USETHESE INSTRUMENTS OF SERVICE SHALL CEASE. WHENTRANSMITTING COPYRIGHT-PROTECTED INFORMATION FOR USE ONTHE PROJECT, THE TRANSMITTING PARTY REPRESENTS THAT IT HASPERMISSION FROM THE TDG TO TRANSMIT THE INFORMATION FORITS USE ON THE PROJECT. QUESTIONS ARISING DURINGCONSTRUCTION OR REVIEW OF THE DRAWINGS SHALL BEADDRESSED TO THE ARCHITECT.
for Permit7-1-2016
2014 FLORIDA BUILDING CODE-BUILDING, 5TH EDITION 2014 FLORIDA PLUMBING CODE, 5TH EDITION 2014 FLORIDA MECHANICAL CODE, 5TH EDITION 2014 FLORIDA FUEL GAS CODE, 5TH EDITION 2014 FLORIDA ENERGY CONSERVATION CODE, 5TH EDITION 2014 FLORIDA FIRE PREVENTION CODE, 5TH EDITION 2002-01 BUILDING CONSTRUCTION ADMINISTRATIVE CODE CHAPTER 16 SAFEGUARDS DURING CONSTRUCTION ALTERATION
AND DEMOLITION OPERATIONS WITH LOCAL FIRE MARSHALL 2011 NFPA 70 NATIONAL ELECTRICAL CODE
New Construction - Industrial Building
PROPOSED MASONRY BUILDING WITH A PREFAB METAL BUILDINGSUB STRUCTURE
Alico Business Park
NOT FOR CONSTRUCTION
PARTIAL ELECTRICAL PLAN
UNIT7-100
UNIT7-101
UNIT7-102
UNIT7-103
UNIT7-104
UNIT7-105
UNIT7-106
ENTRY7-000
ENTRY7-001
KEY PLAN
84 5 6 7
UNIT7-102
UNIT7-103
UNIT7-104
UNIT7-105
UNIT7-106
ENTRY7-001
C
C
C
C
C
C
C
C
C
C
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
EXIT SIGN
EXIT SIGN EXIT SIGN EXIT SIGN EXIT SIGN
CW CW
CW
CW
J JJ J
EXM EXM EXM EXM
EXM
1 1 1 1
WP WPWP WP
WP(SIGN)
J
2
3
J
3
J
3
J
TELEPHONE SERVICE
CATV SERVICE
ELECTRICSERVICE
HOUSEPANEL
PROVIDE (2) 3/4" PVC W/ PULLSTRING ABOVE CEILING TO MIDBAY OF EACH UNIT FOR TELE /CATV
A A
EXIT SIGN EXIT SIGN
EXM EXM
WP(SIGN)
J J
WP(SIGN)
2 2
3
J
3
J
3
J
WP(SIGN)
J
2
EXIT SIGN
EXM3
J
3
J
3
J
CW
CW
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
1" x 12" THREADEDRIGID NIPPLE THRUROOF (TYP OF 5)
H 5,7 H 5,7
H 5,7
H 5,7
H 5,7H9 H9
H 5,7
H2 H2 H2 H2
H2H2H2H2
E-1.02 A
Trianon Design Group
Telephone 239 289 2629
8831 Business Park Drive Building 3Fort Myers, Florida 33912
16111 Lee Road, Fort Myers, Florida, 33912
Gerald J. Yurk, AIA ARCHITECTAR 0005621
Building and Code DataAPPLICABLE CODES
Project Description
Use of DocumentsDRAWINGS, SPECIFICATIONS AND OTHER DOCUMENTS PREPAREDBY GERALD J. YURK A.I.A. ARCHITECT TRIANON DESIGN GROUP(TDG), AND HIS CONSULTANTS,ARE INSTRUMENTS OF TDG'SSERVICE AND ARE FOR THE OWNER'S USE SOLELY WITH RESPECTTO THIS PROJECT. TDG SHALL RETAIN ALL COMMON LAW,STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THECOPYRIGHT. UPON COMPLETION OR TERMINATION OF THE PROJECT,ALL PARTIES, WITH THE EXCEPTION OF TDG'S, RIGHTS TO USETHESE INSTRUMENTS OF SERVICE SHALL CEASE. WHENTRANSMITTING COPYRIGHT-PROTECTED INFORMATION FOR USE ONTHE PROJECT, THE TRANSMITTING PARTY REPRESENTS THAT IT HASPERMISSION FROM THE TDG TO TRANSMIT THE INFORMATION FORITS USE ON THE PROJECT. QUESTIONS ARISING DURINGCONSTRUCTION OR REVIEW OF THE DRAWINGS SHALL BEADDRESSED TO THE ARCHITECT.
for Permit7-1-2016
2014 FLORIDA BUILDING CODE-BUILDING, 5TH EDITION 2014 FLORIDA PLUMBING CODE, 5TH EDITION 2014 FLORIDA MECHANICAL CODE, 5TH EDITION 2014 FLORIDA FUEL GAS CODE, 5TH EDITION 2014 FLORIDA ENERGY CONSERVATION CODE, 5TH EDITION 2014 FLORIDA FIRE PREVENTION CODE, 5TH EDITION 2002-01 BUILDING CONSTRUCTION ADMINISTRATIVE CODE CHAPTER 16 SAFEGUARDS DURING CONSTRUCTION ALTERATION
AND DEMOLITION OPERATIONS WITH LOCAL FIRE MARSHALL 2011 NFPA 70 NATIONAL ELECTRICAL CODE
New Construction - Industrial Building
PROPOSED MASONRY BUILDING WITH A PREFAB METAL BUILDINGSUB STRUCTURE
Alico Business Park
NOT FOR CONSTRUCTION
PARTIALELECTRICAL PLAN
PARTIAL ELECTRICAL PLAN
UNIT7-100
UNIT7-101
UNIT7-102
UNIT7-103
UNIT7-104
UNIT7-105
UNIT7-106
ENTRY7-000
ENTRY7-001
KEY PLAN
A
B
C
D
E
G
F
1 2 3 84 5 6 7
UNIT7-100
UNIT7-101
UNIT7-102
UNIT7-103
UNIT7-104
UNIT7-105
UNIT7-106
ENTRY7-000
ENTRY7-001
6" SANITARY SEWER LINE,PROVIDE Y FOR FUTURETENANT WORK LOCATE ATMIDBAY, SLOPE 1/8" PER FT
WATER METER ANDGATE VALVE 1" LINEINTO BUILDING
H.B.H.B.H.B.
C.O. C.O.C.O.
H.B.
3" VTR3" VTR
HOSE BIBB 1/2" COOPERLINE DOWN WALLINTERIOR SIDE
TYPICAL SANITARY CLEANOUT,FLUSH WITH TOP OF FLOOR W/BRASS LID MAX. 100' SPACING
TYPICAL SANITARY CLEANOUT,FLUSH WITH TOP OF FLOOR W/BRASS LID MAX. 100' SPACING
HOSE BIBB 1/2" COOPERLINE DOWN WALLINTERIOR SIDE
H.B.
TIE INTOEXISTING 6"SANITARYSEWER LINE
3" VTR3" VTR 3" VTR3" VTR 3" VTR
HOSE BIBB 1/2" COOPERLINE DOWN WALLINTERIOR SIDE
HOSE BIBB 1/2" COOPERLINE DOWN WALLINTERIOR SIDE
6" SANITARY SEWER LINE,PROVIDE Y FOR FUTURETENANT WORK LOCATE ATMIDBAY, SLOPE 1/8" PER FT
3" VTR3" VTR 3" VTR3" VTR 3" VTR3" VTR 3" VTR
1" COPPER WATER SERVICE LINEOVERHEAD (IN JOIST SPACE)PROVIDE 3/4" GATE VALVE LOCATEAT MIDBAY FOR TENANTCONNECTION & CAP
1" COPPER WATER SERVICE LINEOVERHEAD (IN JOIST SPACE)PROVIDE 3/4" GATE VALVE LOCATEAT MIDBAY FOR TENANTCONNECTION & CAP
FLORIDA STATUTES471.003 QUALIFICATIONS FOR PRACTICE; EXEMPTIONS.—
(1) NO PERSON OTHER THAN A DULY LICENSED ENGINEER SHALL PRACTICE ENGINEERING ORUSE THE NAME OR TITLE OF “LICENSED ENGINEER,” “PROFESSIONAL ENGINEER,” OR ANYOTHER TITLE, DESIGNATION, WORDS, LETTERS, ABBREVIATIONS, OR DEVICE TENDING TOINDICATE THAT SUCH PERSON HOLDS AN ACTIVE LICENSE AS AN ENGINEER IN THIS STATE.
(2) THE FOLLOWING PERSONS ARE NOT REQUIRED TO BE LICENSED UNDER THE PROVISIONSOF THIS CHAPTER AS A LICENSED ENGINEER:
(h) ANY ELECTRICAL, PLUMBING, AIR-CONDITIONING, OR MECHANICAL CONTRACTOR WHOSE PRACTICE INCLUDES THE DESIGN AND FABRICATION OF ELECTRICAL, PLUMBING, AIR-CONDITIONING, OR MECHANICAL SYSTEMS, RESPECTIVELY, WHICH SHE OR HE INSTALLS BY VIRTUE OF A LICENSE ISSUED UNDER CHAPTER 489, UNDER PART I OF CHAPTER 553, OR UNDER ANY SPECIAL ACT OR ORDINANCE WHEN WORKING ON ANY CONSTRUCTION PROJECT WHICH:
1. REQUIRES AN ELECTRICAL OR PLUMBING OR AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE OF $125,000 OR LESS; AND
2. a. REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600 AMPERES (240 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL SYSTEM OR 800 AMPERES (240 VOLTS) OR
LESS ON A COMMERCIAL OR INDUSTRIAL ELECTRICAL SYSTEM;
b. REQUIRES A PLUMBING SYSTEM WITH FEWER THAN 250 FIXTURE UNITS; OR c. REQUIRES A HEATING, VENTILATION, AND AIR-CONDITIONING SYSTEM NOT TO
EXCEED A 15-TON-PER-SYSTEM CAPACITY, OR IF THE PROJECT IS DESIGNED TO ACCOMMODATE 100 OR FEWER PERSONS.
BUILDING PLUMBING PLAN
P-1.00 A
BUILDINGPLUMBING PLAN,NOTES & LEGEND
Trianon Design Group
Telephone 239 289 2629
8831 Business Park Drive Building 3Fort Myers, Florida 33912
16111 Lee Road, Fort Myers, Florida, 33912
Gerald J. Yurk, AIA ARCHITECTAR 0005621
Building and Code DataAPPLICABLE CODES
Project Description
Use of DocumentsDRAWINGS, SPECIFICATIONS AND OTHER DOCUMENTS PREPAREDBY GERALD J. YURK A.I.A. ARCHITECT TRIANON DESIGN GROUP(TDG), AND HIS CONSULTANTS,ARE INSTRUMENTS OF TDG'SSERVICE AND ARE FOR THE OWNER'S USE SOLELY WITH RESPECTTO THIS PROJECT. TDG SHALL RETAIN ALL COMMON LAW,STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THECOPYRIGHT. UPON COMPLETION OR TERMINATION OF THE PROJECT,ALL PARTIES, WITH THE EXCEPTION OF TDG'S, RIGHTS TO USETHESE INSTRUMENTS OF SERVICE SHALL CEASE. WHENTRANSMITTING COPYRIGHT-PROTECTED INFORMATION FOR USE ONTHE PROJECT, THE TRANSMITTING PARTY REPRESENTS THAT IT HASPERMISSION FROM THE TDG TO TRANSMIT THE INFORMATION FORITS USE ON THE PROJECT. QUESTIONS ARISING DURINGCONSTRUCTION OR REVIEW OF THE DRAWINGS SHALL BEADDRESSED TO THE ARCHITECT.
for Permit7-1-2016
2014 FLORIDA BUILDING CODE-BUILDING, 5TH EDITION 2014 FLORIDA PLUMBING CODE, 5TH EDITION 2014 FLORIDA MECHANICAL CODE, 5TH EDITION 2014 FLORIDA FUEL GAS CODE, 5TH EDITION 2014 FLORIDA ENERGY CONSERVATION CODE, 5TH EDITION 2014 FLORIDA FIRE PREVENTION CODE, 5TH EDITION 2002-01 BUILDING CONSTRUCTION ADMINISTRATIVE CODE CHAPTER 16 SAFEGUARDS DURING CONSTRUCTION ALTERATION
AND DEMOLITION OPERATIONS WITH LOCAL FIRE MARSHALL 2011 NFPA 70 NATIONAL ELECTRICAL CODE
New Construction - Industrial Building
PROPOSED MASONRY BUILDING WITH A PREFAB METAL BUILDINGSUB STRUCTURE
Alico Business Park
NOT FOR CONSTRUCTION
UNIT7-100
UNIT7-101
UNIT7-102
UNIT7-103
UNIT7-104
UNIT7-105
UNIT7-106
ENTRY7-000
ENTRY7-001
KEY PLAN
A
B
C
D
E
G
F
1 2 3 4 5
UNIT7-100
UNIT7-101
UNIT7-102
UNIT7-103
UN7-10
ENTRY7-000
H.B.H.B.
C.O. C.O.
3" VTR3" VTR
HOSE BIBB 1/2" COOPERLINE DOWN WALLINTERIOR SIDE
TYPICAL SANITARY CLEANOUT,FLUSH WITH TOP OF FLOOR W/BRASS LID MAX. 100' SPACING
TYPICAL SANITARY CLEANOUT,FLUSH WITH TOP OF FLOOR W/BRASS LID MAX. 100' SPACING
HOSE BIBB 1/2" COOPERLINE DOWN WALLINTERIOR SIDE
H.B.
3" VTR3" VTR
6" SANITARY SEWER LINE,PROVIDE Y FOR FUTURETENANT WORK LOCATE ATMIDBAY, SLOPE 1/8" PER FT
3" VTR3" VTR 3" VTR3" VTR
1" COPPER WATER SERVICE LINEOVERHEAD (IN JOIST SPACE)PROVIDE 3/4" GATE VALVE LOCATEAT MIDBAY FOR TENANTCONNECTION & CAP
PARTIAL PLUMBING PLAN
P-1.01 A
PARTIAL PLUMBINGPLAN
Trianon Design Group
Telephone 239 289 2629
8831 Business Park Drive Building 3Fort Myers, Florida 33912
16111 Lee Road, Fort Myers, Florida, 33912
Gerald J. Yurk, AIA ARCHITECTAR 0005621
Building and Code DataAPPLICABLE CODES
Project Description
Use of DocumentsDRAWINGS, SPECIFICATIONS AND OTHER DOCUMENTS PREPAREDBY GERALD J. YURK A.I.A. ARCHITECT TRIANON DESIGN GROUP(TDG), AND HIS CONSULTANTS,ARE INSTRUMENTS OF TDG'SSERVICE AND ARE FOR THE OWNER'S USE SOLELY WITH RESPECTTO THIS PROJECT. TDG SHALL RETAIN ALL COMMON LAW,STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THECOPYRIGHT. UPON COMPLETION OR TERMINATION OF THE PROJECT,ALL PARTIES, WITH THE EXCEPTION OF TDG'S, RIGHTS TO USETHESE INSTRUMENTS OF SERVICE SHALL CEASE. WHENTRANSMITTING COPYRIGHT-PROTECTED INFORMATION FOR USE ONTHE PROJECT, THE TRANSMITTING PARTY REPRESENTS THAT IT HASPERMISSION FROM THE TDG TO TRANSMIT THE INFORMATION FORITS USE ON THE PROJECT. QUESTIONS ARISING DURINGCONSTRUCTION OR REVIEW OF THE DRAWINGS SHALL BEADDRESSED TO THE ARCHITECT.
for Permit7-1-2016
2014 FLORIDA BUILDING CODE-BUILDING, 5TH EDITION 2014 FLORIDA PLUMBING CODE, 5TH EDITION 2014 FLORIDA MECHANICAL CODE, 5TH EDITION 2014 FLORIDA FUEL GAS CODE, 5TH EDITION 2014 FLORIDA ENERGY CONSERVATION CODE, 5TH EDITION 2014 FLORIDA FIRE PREVENTION CODE, 5TH EDITION 2002-01 BUILDING CONSTRUCTION ADMINISTRATIVE CODE CHAPTER 16 SAFEGUARDS DURING CONSTRUCTION ALTERATION
AND DEMOLITION OPERATIONS WITH LOCAL FIRE MARSHALL 2011 NFPA 70 NATIONAL ELECTRICAL CODE
New Construction - Industrial Building
PROPOSED MASONRY BUILDING WITH A PREFAB METAL BUILDINGSUB STRUCTURE
Alico Business Park
NOT FOR CONSTRUCTION
UNIT7-100
UNIT7-101
UNIT7-102
UNIT7-103
UNIT7-104
UNIT7-105
UNIT7-106
ENTRY7-000
ENTRY7-001
KEY PLAN
84 5 6 7
UNIT7-102
UNIT7-103
UNIT7-104
UNIT7-105
UNIT7-106
ENTRY7-001
6" SANITARY SEWER LINE,PROVIDE Y FOR FUTURETENANT WORK LOCATE ATMIDBAY, SLOPE 1/8" PER FT
WATER METER ANDGATE VALVE 1" LINEINTO BUILDING
H.B.H.B.
C.O.C.O.
H.B.
TYPICAL SANITARY CLEANOUT,FLUSH WITH TOP OF FLOOR W/BRASS LID MAX. 100' SPACING TIE INTO
EXISTING 6"SANITARYSEWER LINE
3" VTR3" VTR 3" VTR3" VTR 3" VTR
HOSE BIBB 1/2" COOPERLINE DOWN WALLINTERIOR SIDE
HOSE BIBB 1/2" COOPERLINE DOWN WALLINTERIOR SIDE
3" VTR3" VTR 3" VTR3" VTR 3" VTR
1" COPPER WATER SERVICE LINEOVERHEAD (IN JOIST SPACE)PROVIDE 3/4" GATE VALVE LOCATEAT MIDBAY FOR TENANTCONNECTION & CAP
PARTIAL PLUMBING PLAN
P-1.02 A
PARTIAL PLUMBINGPLAN
Trianon Design Group
Telephone 239 289 2629
8831 Business Park Drive Building 3Fort Myers, Florida 33912
16111 Lee Road, Fort Myers, Florida, 33912
Gerald J. Yurk, AIA ARCHITECTAR 0005621
Building and Code DataAPPLICABLE CODES
Project Description
Use of DocumentsDRAWINGS, SPECIFICATIONS AND OTHER DOCUMENTS PREPAREDBY GERALD J. YURK A.I.A. ARCHITECT TRIANON DESIGN GROUP(TDG), AND HIS CONSULTANTS,ARE INSTRUMENTS OF TDG'SSERVICE AND ARE FOR THE OWNER'S USE SOLELY WITH RESPECTTO THIS PROJECT. TDG SHALL RETAIN ALL COMMON LAW,STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THECOPYRIGHT. UPON COMPLETION OR TERMINATION OF THE PROJECT,ALL PARTIES, WITH THE EXCEPTION OF TDG'S, RIGHTS TO USETHESE INSTRUMENTS OF SERVICE SHALL CEASE. WHENTRANSMITTING COPYRIGHT-PROTECTED INFORMATION FOR USE ONTHE PROJECT, THE TRANSMITTING PARTY REPRESENTS THAT IT HASPERMISSION FROM THE TDG TO TRANSMIT THE INFORMATION FORITS USE ON THE PROJECT. QUESTIONS ARISING DURINGCONSTRUCTION OR REVIEW OF THE DRAWINGS SHALL BEADDRESSED TO THE ARCHITECT.
for Permit7-1-2016
2014 FLORIDA BUILDING CODE-BUILDING, 5TH EDITION 2014 FLORIDA PLUMBING CODE, 5TH EDITION 2014 FLORIDA MECHANICAL CODE, 5TH EDITION 2014 FLORIDA FUEL GAS CODE, 5TH EDITION 2014 FLORIDA ENERGY CONSERVATION CODE, 5TH EDITION 2014 FLORIDA FIRE PREVENTION CODE, 5TH EDITION 2002-01 BUILDING CONSTRUCTION ADMINISTRATIVE CODE CHAPTER 16 SAFEGUARDS DURING CONSTRUCTION ALTERATION
AND DEMOLITION OPERATIONS WITH LOCAL FIRE MARSHALL 2011 NFPA 70 NATIONAL ELECTRICAL CODE
New Construction - Industrial Building
PROPOSED MASONRY BUILDING WITH A PREFAB METAL BUILDINGSUB STRUCTURE
Alico Business Park
NOT FOR CONSTRUCTION
UNIT7-100
UNIT7-101
UNIT7-102
UNIT7-103
UNIT7-104
UNIT7-105
UNIT7-106
ENTRY7-000
ENTRY7-001
KEY PLAN
P-2.00 A
DOMESTIC WATERISOMETRIC
Trianon Design Group
Telephone 239 289 2629
8831 Business Park Drive Building 3Fort Myers, Florida 33912
16111 Lee Road, Fort Myers, Florida, 33912
Gerald J. Yurk, AIA ARCHITECTAR 0005621
Building and Code DataAPPLICABLE CODES
Project Description
Use of DocumentsDRAWINGS, SPECIFICATIONS AND OTHER DOCUMENTS PREPAREDBY GERALD J. YURK A.I.A. ARCHITECT TRIANON DESIGN GROUP(TDG), AND HIS CONSULTANTS,ARE INSTRUMENTS OF TDG'SSERVICE AND ARE FOR THE OWNER'S USE SOLELY WITH RESPECTTO THIS PROJECT. TDG SHALL RETAIN ALL COMMON LAW,STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THECOPYRIGHT. UPON COMPLETION OR TERMINATION OF THE PROJECT,ALL PARTIES, WITH THE EXCEPTION OF TDG'S, RIGHTS TO USETHESE INSTRUMENTS OF SERVICE SHALL CEASE. WHENTRANSMITTING COPYRIGHT-PROTECTED INFORMATION FOR USE ONTHE PROJECT, THE TRANSMITTING PARTY REPRESENTS THAT IT HASPERMISSION FROM THE TDG TO TRANSMIT THE INFORMATION FORITS USE ON THE PROJECT. QUESTIONS ARISING DURINGCONSTRUCTION OR REVIEW OF THE DRAWINGS SHALL BEADDRESSED TO THE ARCHITECT.
for Permit7-1-2016
2014 FLORIDA BUILDING CODE-BUILDING, 5TH EDITION 2014 FLORIDA PLUMBING CODE, 5TH EDITION 2014 FLORIDA MECHANICAL CODE, 5TH EDITION 2014 FLORIDA FUEL GAS CODE, 5TH EDITION 2014 FLORIDA ENERGY CONSERVATION CODE, 5TH EDITION 2014 FLORIDA FIRE PREVENTION CODE, 5TH EDITION 2002-01 BUILDING CONSTRUCTION ADMINISTRATIVE CODE CHAPTER 16 SAFEGUARDS DURING CONSTRUCTION ALTERATION
AND DEMOLITION OPERATIONS WITH LOCAL FIRE MARSHALL 2011 NFPA 70 NATIONAL ELECTRICAL CODE
New Construction - Industrial Building
PROPOSED MASONRY BUILDING WITH A PREFAB METAL BUILDINGSUB STRUCTURE
Alico Business Park
NOT FOR CONSTRUCTION
DOMESTIC WATER ISOMETRIC
P-2.01 A
SANITARYISOMETRIC
Trianon Design Group
Telephone 239 289 2629
8831 Business Park Drive Building 3Fort Myers, Florida 33912
16111 Lee Road, Fort Myers, Florida, 33912
Gerald J. Yurk, AIA ARCHITECTAR 0005621
Building and Code DataAPPLICABLE CODES
Project Description
Use of DocumentsDRAWINGS, SPECIFICATIONS AND OTHER DOCUMENTS PREPAREDBY GERALD J. YURK A.I.A. ARCHITECT TRIANON DESIGN GROUP(TDG), AND HIS CONSULTANTS,ARE INSTRUMENTS OF TDG'SSERVICE AND ARE FOR THE OWNER'S USE SOLELY WITH RESPECTTO THIS PROJECT. TDG SHALL RETAIN ALL COMMON LAW,STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THECOPYRIGHT. UPON COMPLETION OR TERMINATION OF THE PROJECT,ALL PARTIES, WITH THE EXCEPTION OF TDG'S, RIGHTS TO USETHESE INSTRUMENTS OF SERVICE SHALL CEASE. WHENTRANSMITTING COPYRIGHT-PROTECTED INFORMATION FOR USE ONTHE PROJECT, THE TRANSMITTING PARTY REPRESENTS THAT IT HASPERMISSION FROM THE TDG TO TRANSMIT THE INFORMATION FORITS USE ON THE PROJECT. QUESTIONS ARISING DURINGCONSTRUCTION OR REVIEW OF THE DRAWINGS SHALL BEADDRESSED TO THE ARCHITECT.
for Permit7-1-2016
2014 FLORIDA BUILDING CODE-BUILDING, 5TH EDITION 2014 FLORIDA PLUMBING CODE, 5TH EDITION 2014 FLORIDA MECHANICAL CODE, 5TH EDITION 2014 FLORIDA FUEL GAS CODE, 5TH EDITION 2014 FLORIDA ENERGY CONSERVATION CODE, 5TH EDITION 2014 FLORIDA FIRE PREVENTION CODE, 5TH EDITION 2002-01 BUILDING CONSTRUCTION ADMINISTRATIVE CODE CHAPTER 16 SAFEGUARDS DURING CONSTRUCTION ALTERATION
AND DEMOLITION OPERATIONS WITH LOCAL FIRE MARSHALL 2011 NFPA 70 NATIONAL ELECTRICAL CODE
New Construction - Industrial Building
PROPOSED MASONRY BUILDING WITH A PREFAB METAL BUILDINGSUB STRUCTURE
Alico Business Park
NOT FOR CONSTRUCTION
SANITARY ISOMETRIC
Florida Building Code, Sixth Edition (2017) - Energy Conservation
EnergyGauge Summit® Fla/Com-2017, Effective Date: Dec 31, 2017
IECC 2015 - Total Building Performance Compliance Option
Check List
Applications for compliance with the Florida Building Code, Energy Conservation shall
include:
This Checklist
The full compliance report generated by the software that contains the project
summary, compliance summary, certifications and detailed component compliance
reports.
The compliance report must include the full input report generated by the software as
contigous part of the compliance report.
Boxes appropriately checked in the Mandatory Section of the complaince report.
WARNING: INPUT REPORT NOT GENERATED.
To include input report in final submission, go to the Project Form, Settings Tab and check
the box - "Append Input Report to Compliance Output Report"
Then rerun your calculation
EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017
Florida Building Code, Sixth Edition (2017) - Energy Conservation IECC 2015 - Total Building Performance Compliance Option5/30/2018 Page 1 of 14
PROJECT SUMMARY
Short Desc: Bldg7 Description: Alico Business Park Bldg 7 - Shell
Owner:
Address1: 16111 Lee Rd City: Fort Myers
Address2: State: FL
Zip: 33912
Type: Workshop Class: New Shell building
Jurisdiction: FORT MYERS, LEE COUNTY, FL (461200)
Conditioned Area: 15200 SF Conditioned & UnConditioned Area: 15200 SF
No of Stories: 1 Area entered from Plans 15200 SF
Permit No: 0 Max Tonnage 5
If different, write in: ______________________
EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017
Florida Building Code, Sixth Edition (2017) - Energy Conservation IECC 2015 - Total Building Performance Compliance Option5/30/2018 Page 2 of 14
ResultCriteriaDesignComponent
Compliance Summary
Gross Energy Cost (in $) 18,983.0 27,590.0 PASSED
LIGHTING CONTROLS PASSES
EXTERNAL LIGHTING No Entry
HVAC SYSTEM PASSES
PLANT No Entry
WATER HEATING SYSTEMS No Entry
PIPING SYSTEMS No Entry
Met all required compliance from Check List? Yes/No/NA
IMPORTANT MESSAGE
Info 5009 -- -- -- An input report of this design building must be submitted along with this
Compliance Report
EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017
Florida Building Code, Sixth Edition (2017) - Energy Conservation IECC 2015 - Total Building Performance Compliance Option5/30/2018 Page 3 of 14
CERTIFICATIONS
I hereby certify that the plans and specifications covered by this calculation are in compliance with the
Florida Energy Code
Prepared By: __________________ Building Official: __________________
Date: _________________ Date: __________________
I certify that this building is in compliance with the FLorida Energy Efficiency Code
Owner Agent: __________________ Date: __________________
If Required by Florida law, I hereby certify (*) that the system design is in compliance with the Florida Energy
Efficiency Code
Architect: Trianon Design Group Reg No: __________________
Electrical Designer: __________________ Reg No: __________________
Lighting Designer: __________________ Reg No: __________________
Mechanical Designer: __________________ Reg No: __________________
Plumbing Designer: __________________ Reg No: __________________
(*) Signature is required where Florida Law requires design to be performed by registered design
professionals. Typed names and registration numbers may be used where all relevant information is
contained on signed/sealed plans.
EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017
Florida Building Code, Sixth Edition (2017) - Energy Conservation IECC 2015 - Total Building Performance Compliance Option5/30/2018 Page 4 of 14
May 30, 2018
Project: Bldg7
Title: Alico Business Park Bldg 7 - Shell
Type: Workshop
(WEA File: FL_FORT_MYERS_PAGE_FIELD.tm3)
1) Proposed 2) Baseline
Total 1,173.80
$18,983
2,021.50
$32,459
ELECTRICITY(MBtu/kWh/$) 1,173.80
343903
$18,983
2,021.50
592309
$32,459
AREA LIGHTS 3.80
1103
$61
252.60
74013
$4,056
MISC EQUIPMT 76.00
22270
$1,229
76.00
22270
$1,220
PUMPS & MISC 0.00
7
$0
0.00
6
$0
SPACE COOL 752.30
220421
$12,167
1,250.20
366310
$20,074
SPACE HEAT 31.00
9077
$501
17.20
5035
$276
VENT FANS 310.70
91025
$5,025
425.50
124675
$6,832
Building End Uses
Credits Applied: None
Passing Criteria = 27590
Design (including any credits) = 18983
Passing requires Proposed Building cost to be at most 85% of
Baseline cost. This Proposed Building is at 58.5%
PASSES
EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017
Florida Building Code, Sixth Edition (2017) - Energy Conservation IECC 2015 - Total Building Performance Compliance Option5/30/2018 Page 5 of 14
CLP
(W)
Area or Length
or No. of Units
(Sqft or ft)
Allowance
(W/Unit)
CategoryDescription
External Lighting Compliance
ELPA
(W)
Tradable?
None
Project: Bldg7
Title: Alico Business Park Bldg 7 - Shell
Type: Workshop
(WEA File: FL_FORT_MYERS_PAGE_FIELD.tm3)
Compli-
ance
Design
CP
Min
CP
DescriptionAcronym
Lighting Controls Compliance
Ashrae
ID
Area
(sq.ft)
31,001 Workshop 15,200 2 6 PASSESPr0Zo1Sp1
PASSES
Project: Bldg7
Title: Alico Business Park Bldg 7 - Shell
Type: Workshop
(WEA File: FL_FORT_MYERS_PAGE_FIELD.tm3)
System Report Compliance
Pr0Sy8 System 8 Constant Volume Air Cooled
Split System < 65000 Btu/hr
Component Category Capacity Design
Eff
Eff
Criteria
Design
IPLV
IPLV
Criteria
Comp-
liance
No. of Units1
Cooling System Air Conditioners Air Cooled
Split System < 65000 Btu/h
Cooling Capacity
60000 14.00 13.00 12.80 PASSES
Heating System Electric Furnace 34100 1.00 1.00 PASSES
Air Handling
System -Supply
Air Handler (Supply) -
Constant Volume
2000 0.80 0.82 PASSES
PASSES
EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017
Florida Building Code, Sixth Edition (2017) - Energy Conservation IECC 2015 - Total Building Performance Compliance Option5/30/2018 Page 6 of 14
Comp
liance
CategoryMin
IPLV
Min
Eff
Design
IPLV
Design
Eff
SizeInstalled
No
Description
Plant Compliance
None
Comp
liance
Design
Loss
Design
Eff
Max
Loss
Min
EffCategoryTypeDescription
Water Heater Compliance
None
Piping System Compliance
Category Pipe Dia
[inches]
Ins Cond
[Btu-in/hr
.SF.F]
Operating
Temp
[F]
Is
Runout?
Ins
Thick [in]
ComplianceReq Ins
Thick [in]
None
EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017
Florida Building Code, Sixth Edition (2017) - Energy Conservation IECC 2015 - Total Building Performance Compliance Option5/30/2018 Page 7 of 14
Topic Section Component Description Yes N/A Exempt
Mandatory Requirements (as applicable) Mandatory requirements compiled by US Department
of Energy and Pacific Northwest National Laboratory.
Adopted with permission
1. To be checked by Designer or Engineer
Insulation C303.2 Envelope Below-grade wall insulation installed per
manufacturer's instructions.
Insulation C303.2 Envelope Slab edge insulation installed per manufacturer's
instructions.
Insulation C303.2 Envelope Above-grade wall insulation installed per
manufacturer's instructions.
Insulation C402.3 Envelope High-albedo roofs satisfy one of the following:
3-year-aged solar reflectance >= 0.55 and thermal
emittance >= 0.75 or 3-year-aged solar
reflectance index >= 64.0.
Fenestration C402.4.4 Envelope U-factor of opaque doors associated with the
building thermal envelope meets requirements.
SYSTEM_SPECIFIC C403.2.12.1 Mechanical HVAC fan systems at design conditions do not
exceed allowable fan system motor nameplate hp
or fan system bhp.
SYSTEM_SPECIFIC C403.2.12.2 Mechanical HVAC fan motors not oversized beyond allowable
limits.
SYSTEM_SPECIFIC C403.2.3(8) Table Mechanical Heat Rejection Equipment: Minimum Efficiency
Requirement meet those listed in Table
C403.2.3(8)
HVAC C403.2.7 Mechanical Exhaust air energy recovery on systems meeting
Table C403.2.7(1) and C403.2.7(2).
SYSTEM_SPECIFIC C403.3 Mechanical Air economizers provided where required, meet
the requirements for design capacity, control
signal, ventilation controls, high-limit shut-off,
integrated economizer control, and provide a
means to relieve excess outside air during
operation.
SYSTEM_SPECIFIC C403.3.2 Mechanical Economizer operation will not increase heating
energy use during normal operation.
SYSTEM_SPECIFIC C403.3.4,
C403.3.4.1,
C403.3.4.2,
C403.3.1
Mechanical Water economizers provided where required,
meet the requirements for design capacity,
maximum pressure drop and integrated
economizer control.
SYSTEM_SPECIFIC C403.4.2.1 Mechanical Three-pipe hydronic systems using a common
return for hot and chilled water are not used.
SYSTEM_SPECIFIC C403.4.2.3.1 Mechanical Hydronic heat pump systems connected to a
common water loop meet heat rejection and heat
addition requirements.
SYSTEM_SPECIFIC C403.4.3.4 Mechanical Open-circuit cooling towers having water cooled
chiller systems and multiple or vairable speed
condenser pumps, are designed so that tower
cells can run in parallel with larger of flow crtieria.
SYSTEM_SPECIFIC C404.2 Mechanical Service water heating equipment meets efficiency
requirements.
Wattage C405.3 Interior Lighting Exit signs do not exceed 5 watts per face.
2. To be checked by Plan Reviewer
Plan Review C103.2 Envelope Plans and/or specifications provide all information
with which compliance can be determined for the
building envelope and document where
exceptions to the standard are claimed.
EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017
Florida Building Code, Sixth Edition (2017) - Energy Conservation IECC 2015 - Total Building Performance Compliance Option5/30/2018 Page 8 of 14
Plan Review C103.2 Mechanical Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the mechanical systems and
equipment and document where exceptions to the
standard are claimed. Load calculations per
acceptable engineering st
Plan Review C103.2 Mechanical Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the service water heating systems
and equipment and document where exceptions
to the standard are claimed. Hot water system
sized per manufact
Plan Review C103.2 Interior Lighting Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the interior lighting and electrical
systems and equipment and document where
exceptions to the standard are claimed.
Information provided shoul
Plan Review C103.2 Exterior Lighting Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the exterior lighting and electrical
systems and equipment and document where
exceptions to the standard are claimed.
Information provided shoul
Insulation C402.2.5 Envelope Slab edge insulation depth/length. Slab insulation
extending away from building is covered by
pavement or >= 10 inches of soil.
Insulation C402.2.6 Project Radiant heating systems panels insulated to
>=R-3.5 on face opposite space being heated.
HVAC C402.2.6 Mechanical Thermally ineffective panel surfaces of sensible
heating panels have insulation >= R-3.5.
Insulation C402.2.6 Envelope Radiant panels and associated components,
designed for heat transfer from the panel surfaces
to the occupants or indoor space are insulated
with a minimum of R-3.5.
Air Leakage C402.5.7 Envelope Vestibules are installed on all building entrances .
Doors have self-closing devices.
SYSTEM_SPECIFIC C403.2.12.3 Mechanical Fans have efficiency grade (FEG) >= 67. The total
efficiency of the fan at the design point of
operation <= 15% of maximum total efficiency of
the fan.
HVAC C403.2.13 Mechanical Unenclosed spaces that are heated use only
radiant heat.
HVAC C403.2.4.2 Mechanical Each zone equipped with setback controls using
automatic time clock or programmable control
system.
SYSTEM_SPECIFIC C403.2.4.4 Mechanical Zone isolation devices and controls installed
where applicable.
SYSTEM_SPECIFIC C403.2.4.7 Mechanical Fault detection and diagnostics installed with
air-cooled unitary DX units having economizers.
SYSTEM_SPECIFIC C403.2.5 Mechanical Hot water boilers supplying heat via one- or
two-pipe systems include outdoor setback control.
HVAC C403.2.6.1 Mechanical Demand control ventilation provided for spaces
>500 ft2 and >25 people/1000 ft2 occupant
density and served by systems with air side
economizer, auto modulating outside air damper
control, or design airflow >3,000 cfm.
SYSTEM_SPECIFIC C403.4.1.1 Mechanical Hydronic and multizone HVAC system controls
areVAV fans driven by mechanical or electrical
variable speed drive per Table C403.4.1.1.
SYSTEM_SPECIFIC C403.4.1.3 Mechanical Reset static pressure setpoint for DDC controlled
VAV boxes reporting to central controller based on
the zones requiring the most pressure.
SYSTEM_SPECIFIC C403.4.2 Mechanical Temperature reset by representative building
loads in pumping systems for chiller and boiler
systems >500,000 Btu/h.
EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017
Florida Building Code, Sixth Edition (2017) - Energy Conservation IECC 2015 - Total Building Performance Compliance Option5/30/2018 Page 9 of 14
SYSTEM_SPECIFIC C403.4.2.3.2.1 Mechanical Closed-circuit cooling tower within heat pump loop
have either automatic bypass valve or lower
leakage positive closure dampers. Open-circuit
tower within heat pump loop have automatic valve
to bypass all heat pump water flow around the
tower. Open- or cl
SYSTEM_SPECIFIC C403.4.2.4 Mechanical Hydronic systems greater than 500,000 Btu/h
designed for variable fluid flow.
SYSTEM_SPECIFIC C403.4.2.5 Mechanical System turndown requirement met through
multiple single-input boilers, one or more
modulating boilers, or a combination of
single-input and modulating boilers.
Boiler input between 1.0 MBtu/h and 5 MBtu/h
has 3:1 turndown ratio, boiler input between 5.0
SYSTEM_SPECIFIC C403.4.2.6 Mechanical Chilled water plants with multiple chillers have
capability to reduce flow automatically through the
chiller plant when a chiller is shut down.
Boiler plants with multiple boilers have the
capability to reduce flow automatically through the
boiler plant
SYSTEM_SPECIFIC C403.4.3,
C403.4.3.2
Mechanical Fan systems with motors >=7.5 hp associated
with heat rejection equipment to have capability to
operate at 2/3 of full-speed and auto speed
controls to control the leaving fluid temperature or
condensing temp/pressure of heat rejection
device.
SYSTEM_SPECIFIC C403.4.4.5 Mechanical Multiple zone HVAC systems have supply air
temperature reset controls.
SYSTEM_SPECIFIC C403.4.4.6 Mechanical Multiple zone VAV systems with DDC of individual
zone boxes have static pressure setpoint reset
controls.
SYSTEM_SPECIFIC C404.2.1 Mechanical Gas-fired water-heating equipment installed in
new buildings: where a singular piece of
water-heating equipment >= 1,000 kBtu/h serves
the entire building, thermal efficiency >= 90 Et.
Where multiple pieces of water-heating
equipment serve the building wi
SYSTEM_SPECIFIC C404.4 Mechanical All piping insulated in accordance with section
details and Table C403.2.10.
SYSTEM_SPECIFIC C404.5, C404.5.1,
C404.5.2
Mechanical Heated water supply piping conforms to pipe
length and volume requirements. Refer to section
details.
SYSTEM_SPECIFIC C404.6.3 Mechanical Pumps that circulate water between a heater and
storage tank have controls that limit operation
from startup to <= 5 minutes after end of heating
cycle.
SYSTEM_SPECIFIC C404.7 Mechanical Water distribution system that pumps water from
a heated-water supply pipe back to the
heated-water source through a cold-water supply
pipe is
a demand recirculation water system. Pumps
within this system have controls that start the
pump upon receiving
Wattage C405.5.1 Exterior Lighting Exterior lighting power is consistent with what is
shown on the approved lighting plans,
demonstrating proposed watts are less than or
equal to allowed watts.
Plan Review C405.6 Project Group R-2 dwelling units have separate electrical
meters.
Plan Review C406 Project Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the additional energy efficiency
package options.
SYSTEM_SPECIFIC C408.2.2.2 Mechanical HVAC hydronic heating and cooling coils have
means to balance and have pressure test
connections.
SYSTEM_SPECIFIC C408.2.2.2 Mechanical HVAC hydronic heating and cooling coils have
means to balance and have pressure test
connections.
EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017
Florida Building Code, Sixth Edition (2017) - Energy Conservation IECC 2015 - Total Building Performance Compliance Option5/30/2018 Page 10 of 14
3. To be checked by Inspector
Insulation C303.1 Envelope Roof insulation installed per manufacturer’s
instructions. Blown or poured loose-fill insulation
is installed only where the roof slope is <=3 in 12.
Insulation C303.1 Envelope Building envelope insulation is labeled with
R-value or insulation certificate providing R-value
and other relevant data.
Fenestration C303.1.3 Envelope Fenestration products rated in accordance with
NFRC.
Fenestration C303.1.3 Envelope Fenestration products are certified as to
performance labels or certificates provided.
Insulation C303.2, C402.2.4 Envelope Floor insulation installed per manufacturer's
instructions. Cavity or structural slab insulation
installed in permanent contact with underside of
decking or structural slabs.
Insulation C303.2.1 Envelope Exterior insulation protected against damage,
sunlight, moisture, wind, landscaping and
equipment maintenance activities.
Insulation C303.2.1 Envelope Exterior insulation is protected from damage with
a protective material. Verification for exposed
foundation insulation may need to occur during
Foundation Inspection.
Insulation C402.1.3 Envelope Non-swinging opaque doors have R-4.75
insulation.
Insulation C402.2.2 Envelope Skylight curbs are insulated to the level of roofs
with insulation above deck or R-5.
Insulation C402.2.2 Envelope Insulation intended to meet the roof insulation
requirements cannot be installed on top of a
suspended ceiling. Mark this requirement
compliant if insulation is installed accordingly.
Air Leakage C402.5 Envelope Building envelope contains a continuous air
barrier that has been tested and deemed to limit
air leakage <= 0.40 cfm/ft2.
Air Leakage C402.5.1 Envelope The building envelope contains a continuous air
barrier that is sealed in an approved manner and
either constructed or tested in an approved
manner. Air barrier penetrations are sealed in an
approved manner.
Air Leakage C402.5.1.1 Envelope All sources of air leakage in the building thermal
envelope are sealed, caulked, gasketed, weather
stripped or wrapped with moisture
vapor-permeable wrapping material to minimize
air leakage.
Air Leakage C402.5.1.2.1 Envelope The building envelope contains a continuous air
barrier that is sealed in an approved manner and
material permeability <= 0.004 cfm/ft2. Air barrier
penetrations are sealed in an approved manner.
Air Leakage C402.5.1.2.2 Envelope The building envelope contains a continuous air
barrier that is sealed in an approved manner and
average assembly air leakage <= 0.04 cfm/ft2.
Air barrier penetrations are sealed in an approved
manner.
Air Leakage C402.5.2, C402.5.4 Envelope Factory-built fenestration and doors are labeled
as meeting air leakage requirements.
Air Leakage C402.5.3 Envelope Where open combustion air ducts provide
combustion air to open combustion fuel burning
appliances, the appliances and combustion air
opening are located outside the building thermal
envelope or enclosed in a room, isolated from
inside the thermal envelope
Air Leakage C402.5.5,
C403.2.4.3
Envelope Stair and elevator shaft vents have motorized
dampers that automatically close.
Air Leakage C402.5.5,
C403.2.4.3
Envelope Outdoor air and exhaust systems have motorized
dampers that automatically shut when not in use
and meet maximum leakage rates. Check gravity
dampers where allowed.
Air Leakage C402.5.6 Envelope Weatherseals installed on all loading dock cargo
doors.
EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017
Florida Building Code, Sixth Edition (2017) - Energy Conservation IECC 2015 - Total Building Performance Compliance Option5/30/2018 Page 11 of 14
Air Leakage C402.5.8 Envelope Recessed luminaires in thermal envelope to limit
infiltration and be IC rated and labeled. Seal
between interior finish and luminaire housing.
HVAC C403.2.1 Mechanical HVAC systems and equipment design loads
calculated in accordance with
ANSI/ASHRAE/ACCA Standard 183 or by an
approved equivalent computational procedure
SYSTEM_SPECIFIC C403.2.10 Mechanical HVAC piping insulation thickness. Where piping
is installed in or under a slab, verification may
need to occur during Foundation Inspection.
HVAC C403.2.3 Mechanical HVAC equipment efficiency verified.
SYSTEM_SPECIFIC C403.2.3 Mechanical PTAC and PTHP with sleeves 16 in. by 42 in.
labeled for replacement only as per Footnote b to
Table C403.2.3(3).
SYSTEM_SPECIFIC C403.2.4.1 Mechanical Heating and cooling to each zone is controlled by
a thermostat control. Minimum one humidity
control device per installed
humidification/dehumidification system.
SYSTEM_SPECIFIC C403.2.4.1.1 Mechanical Heat pump controls prevent supplemental electric
resistance heat from coming on when not needed.
HVAC C403.2.4.1.2 Mechanical Thermostatic controls have a 5 °F deadband.
HVAC C403.2.4.1.2 Mechanical Thermostatic controls have a 5 °F deadband.
HVAC C403.2.4.1.3 Mechanical Temperature controls have setpoint overlap
restrictions.
HVAC C403.2.4.2.1,
C403.2.4.2.2
Mechanical Automatic Controls: Setback to 55°F (heat) and
85°F (cool); 7-day clock, 2-hour occupant
override, 10-hour backup
SYSTEM_SPECIFIC C403.2.4.2.3 Mechanical Systems include optimum start controls.
HVAC C403.2.4.5,
C403.2.4.6
Mechanical Snow/ice melting system sensors for future
connection to controls. Freeze protection systems
have automatic controls installed.
HVAC C403.2.6.2 Mechanical Enclosed parking garage ventilation has
automatic contaminant detection and capacity to
stage or modulate fans to 50% or less of design
capacity.
HVAC C403.2.9 Mechanical HVAC ducts and plenums insulated. Where ducts
or plenums are installed in or under a slab,
verification may need to occur during Foundation
Inspection.
SYSTEM_SPECIFIC C403.2.9.1.3 Mechanical Ductwork operating >3 in. water column requires
air leakage testing.
SYSTEM_SPECIFIC C403.4.1.2 Mechanical VAV fans have static pressure sensors located so
controller setpoint <=1.2 w.c..
SYSTEM_SPECIFIC C403.4.2.2 Mechanical Two-pipe hydronic systems using a common
distribution system have controls to allow a
deadband >=15ºF, allow operation in one mode
for at least 4 hrs before changeover, and have
rest controls to limit heating and cooling supply
temperature to <=30 ºF.
SYSTEM_SPECIFIC C403.4.2.3.3 Mechanical Two-position automatic valve interlocked to shut
off water flow when hydronic heat pump with
pumping system >10 hp is off.
SYSTEM_SPECIFIC C403.4.4.5,
C403.4.4.5.1-4
Mechanical Zone controls can limit simultaneous heating and
cooling and sequence heating and cooling to each
zone.
SYSTEM_SPECIFIC C403.4.5 Mechanical Condenser heat recovery system that can heat
water to 85ºF or provide 60% of peak heat
rejection is installed for preheating of service hot
water.
SYSTEM_SPECIFIC C403.4.6 Mechanical Hot gas bypass limited to:
<=240 kBtu/h - 50% capacity,
>240 kBtu/h - 25% capacity
SYSTEM_SPECIFIC C404.3 Mechanical Heat traps installed on non-circulating storage
water tanks.
EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017
Florida Building Code, Sixth Edition (2017) - Energy Conservation IECC 2015 - Total Building Performance Compliance Option5/30/2018 Page 12 of 14
SYSTEM_SPECIFIC C404.3 Mechanical Heat traps installed on supply and discharge
piping of non-circulating systems.
SYSTEM_SPECIFIC C404.3 Mechanical Heat traps installed on supply and discharge
piping of non-circulating systems.
SYSTEM_SPECIFIC C404.6.1 Mechanical Controls are installed that limit the operation of a
recirculation pump installed to maintain
temperature of a storage tank. System return pipe
is a dedicated return pipe or a cold water supply
pipe.
SYSTEM_SPECIFIC C404.6.1, C404.6.2 Mechanical Automatic time switches installed to automatically
switch off the recirculating hot-water system or
heat trace.
SYSTEM_SPECIFIC C404.9.1 Mechanical Pool heaters are equipped with on/off switch and
no continuously burning pilot light.
SYSTEM_SPECIFIC C404.9.2 Mechanical Time switches are installed on all pool heaters
and pumps.
SYSTEM_SPECIFIC C404.9.2 Mechanical Time switches are installed on all pool heaters
and pumps.
SYSTEM_SPECIFIC C404.9.3 Mechanical Vapor retardant pool covers are provided for
heated pools and permanently installed spas.
Controls C405.2.1 Interior Lighting Lighting controls installed to uniformly reduce the
lighting load by at least 50%.
Controls C405.2.1 Interior Lighting Occupancy sensors installed in required spaces.
Controls C405.2.1,
C405.2.2.3
Interior Lighting Independent lighting controls installed per
approved lighting plans and all manual controls
readily accessible and visible to occupants.
Controls C405.2.2.1 Interior Lighting Automatic controls to shut off all building lighting
installed in all buildings.
Controls C405.2.3 Interior Lighting Daylight zones provided with individual controls
that control the lights independent of general area
lighting.
Controls C405.2.3,
C405.2.3.1,
C405.2.3.2
Interior Lighting Primary sidelighted areas are equipped with
required lighting controls.
Controls C405.2.3,
C405.2.3.1,
C405.2.3.3
Interior Lighting Enclosed spaces with daylight area under
skylights and rooftop monitors are equipped with
required lighting controls.
Controls C405.2.4 Interior Lighting Separate lighting control devices for specific uses
installed per approved lighting plans.
Wattage C405.2.4 Interior Lighting Additional interior lighting power allowed for
special functions per the approved lighting plans
and is automatically controlled and separated
from general lighting.
Controls C405.2.5 Exterior Lighting Automatic lighting controls for exterior lighting
installed. Controls will be daylight controlled, set
based on business operation time-of-day, or
reduce connected lighting > 30%.
Wattage C405.4.1 Interior Lighting Interior installed lamp and fixture lighting power is
consistent with what is shown on the approved
lighting plans, demonstrating proposed watts are
less than or equal to allowed watts.
Mandatory Additional Efficiency PackageC406.4 Project Enhanced digital lighting controls efficiency
package: Interior lighting has following enhanced
lighting controls in accordance with Section
C405.2.2:
Luminaires capable of continuous dimming and
being addressed individually, <= 8 luminaires
controlled in
Mandatory Additional Efficiency PackageC406.6 Project Dedicate outdoor air system efficiency package:
Buildings with hydronic and/or multiple-zone
HVAC systems are equipped with an independent
ventilation system designed to provide >=
100-percent outdoor air to each individual
occupied space, as specified by
EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017
Florida Building Code, Sixth Edition (2017) - Energy Conservation IECC 2015 - Total Building Performance Compliance Option5/30/2018 Page 13 of 14
Mandatory Additional Efficiency PackageC406.7, C406.7.1 Project Enhanced Service Water Heat System efficiency
package. One of the following SWH system
enhancements must satisfy 60 percent of hot
water requirements, or 100 percent if the building
otherwise complies with heat recovery per Section
C403.4.5: Waste heat re
HVAC C408.2.2.1 Mechanical Air outlets and zone terminal devices have means
for air balancing.
HVAC C408.2.2.1 Mechanical Air outlets and zone terminal devices have means
for air balancing.
Testing C408.2.3.2 Mechanical HVAC control systems have been tested to
ensure proper operation, calibration and
adjustment of controls.
4. To be checked by Inspector at Project Completion and Prior to Issuance of
Certificate of OccupancyPost Construction C303.3, C408.2.5.2 Interior Lighting Furnished O&M instructions for systems and
equipment to the building owner or designated
representative.
Post Construction C303.3, C408.2.5.3 Mechanical Furnished O&M manuals for HVAC systems
within 90 days of system acceptance.
Fenestration C402.4.2.2 Envelope Skylights in office, storage, automotive service,
manufacturing, non-refrigerated warehouse, retail
store, and distribution/sorting area have a
measured haze value > 90 percent unless
designed to exclude direct sunlight.
Post Construction C408.2.1 Mechanical Commissioning plan developed by registered
design professional or approved agency.
Post Construction C408.2.3.1 Mechanical HVAC equipment has been tested to ensure
proper operation.
Post Construction C408.2.3.3 Mechanical Economizers have been tested to ensure proper
operation.
Post Construction C408.2.4 Mechanical Preliminary commissioning report completed and
certified by registered design professional or
approved agency.
Post Construction C408.2.5.1 Mechanical Furnished HVAC as-built drawings submitted
within 90 days of system acceptance.
Post Construction C408.2.5.1 Interior Lighting Furnished as-built drawings for electric power
systems within 90 days of system acceptance.
Post Construction C408.2.5.3 Mechanical An air and/or hydronic system balancing report is
provided for HVAC systems.
Post Construction C408.2.5.4 Mechanical Final commissioning report due to building owner
within 90 days of receipt of certificate of
occupancy.
Post Construction C408.3 Interior Lighting Lighting systems have been tested to ensure
proper calibration, adjustment, programming, and
operation.
EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017
Florida Building Code, Sixth Edition (2017) - Energy Conservation IECC 2015 - Total Building Performance Compliance Option5/30/2018 Page 14 of 14
EnergyGauge Summit® v6.00
INPUT DATA REPORT
Bldg7Project Name:
16111 Lee RdAddress:
Owner:
FLState:
Zip:
WorkshopBuilding Type:
New Shell buildingBuilding Classification:
1No.of Stories:
Orientation:
15200GrossArea:
Project Information
33912
0 Deg Clockwise. Walls & Windows will
be rotated accordinglyAlico Business Park Bldg 7 - ShellProject Title:
SF
Type DescriptionAcronym
Zones
Area
[sf]
Multiplier Total Area
[sf]
No
Pr0Zo1 Zone 1 CONDITIONED 15200.0 1 15200.0 1
Width
[ft]
Depth
[ft]
Description
Spaces
Acronym Height
[ft]
No Multi
plier
Total Area
[sf]
Total Volume
[cf]
Type
15/30/2018 EnergyGauge Summit® v6.00
Pr0Zo1In Zone:
Zo0Sp1 80.00 190.00 22.00 Pr0Zo1Sp1 1 15200.0 334400.0Workshop 1
Control TypePower
[W]
Type
Lighting
No.of
Ctrl pts
No Category No. of
Luminaires
Watts per
Luminaire
In Zone: Pr0Zo1
In Space: Pr0Zo1Sp1
1 LED 360 Manual On/Off 6General Lighting 30 12
OrientationNo
Walls (Walls will be rotated clockwise by building rotation value)
Description Width
[ft]
H (Effec)
[ft]
Multi
plier
Area
[sf]
Conductance
[Btu/hr. sf. F]
Dens.
[lb/cf]
Heat
Capacity
[Btu/sf.F]
R-Value
[h.sf.F/Btu]
Type
In Zone: Pr0Zo1
1 Pr0Zo1Wa1 80.00 23.00 1 1840.0 0.1491 5.653 37.15 6.7 5/8" stucco
/8"CMU/R4.1
FiFoil/BTWN24"oc/
.5" Gyp
North
2 Pr0Zo1Wa1 190.00 25.00 1 4750.0 0.1491 5.653 37.15 6.7 5/8" stucco
/8"CMU/R4.1
FiFoil/BTWN24"oc/
.5" Gyp
East
3 Pr0Zo1Wa1 80.00 23.00 1 1840.0 0.1491 5.653 37.15 6.7 5/8" stucco
/8"CMU/R4.1
FiFoil/BTWN24"oc/
.5" Gyp
South
4 Pr0Zo1Wa1 190.00 21.00 1 3990.0 0.1491 5.653 37.15 6.7 5/8" stucco
/8"CMU/R4.1
FiFoil/BTWN24"oc/
.5" Gyp
West
25/30/2018 EnergyGauge Summit® v6.00
No UOrientation
Windows (Windows will be rotated clockwise by building rotation value)
Description
[Btu/hr sf F]
SHGCShaded Vis.Tra W
[ft]
H (Effec)
[ft]
Multi
plier [sf]
Total Area
Pr0Zo1In Zone:
East WallIn Wall:
1 Pr0Zo1Wa1Wi1 East 1.0700 0.52 0.76 3.00 3.00 1 9.0No
2 Pr0Zo1Wa1Wi2 East 1.0700 0.52 0.76 6.00 8.00 8 384.0No
North WallIn Wall:
1 Pr0Zo1Wa1Wi1 North 1.0700 0.52 0.76 3.00 3.00 6 54.0No
South WallIn Wall:
1 Pr0Zo1Wa1Wi1 South 1.0700 0.52 0.76 3.00 3.00 6 54.0No
Doors
No Description Area
[sf]
Multi
plier
H (Effec)
[ft]
Width
[ft]
Shaded? Cond.
[Btu/hr. sf. F]
Dens.
[lb/cf]
Heat Cap.
[Btu/sf. F]
R-Value
[h.sf.F/Btu]
Type
In Zone: Pr0Zo1
In Wall: West Wall
24.0 8 8.00 3.00 Pr0Zo1Wa6Dr1 1 0.3504 0.00 0.00 2.85 Solid core flush
(2.25)
No
168.0 8 14.00 12.00 Pr0Zo1Wa6Dr2 2 0.3504 0.00 0.00 2.85 Solid core flush
(2.25)
No
Roofs
No Description Width
[ft]
Tilt
[deg]
Area
[sf]
Multi
plier
H (Effec)
[ft]
Type Cond.
[Btu/hr. Sf. F]
Dens.
[lb/cf]
Heat Cap
[Btu/sf. F]
R-Value
[h.sf.F/Btu]
In Zone: Pr0Zo1
1 Pr0Zo1Rf2 190.00 80.00 1 15200.0 0.00 0.0868 11.5 12.01 0.93 Sngl
Ply/3"Iso/1/2"WD
Deck/WD Truss/Gyp
Br
35/30/2018 EnergyGauge Summit® v6.00
UType DescriptionNo
Skylights
SHGC
[Btu/hr sf F]
Vis.Trans W
[ft]
H (Effec)
[ft]
Area
[Sf]
Multiplier Total Area
[Sf]
In Zone:
In Roof:
Floors
No Description Area
[sf]
Multi
plier
H (Effec)
[ft]
Width
[ft]
Type Cond.
[Btu/hr. sf. F]
Dens.
[lb/cf]
Heat Cap.
[Btu/sf. F]
R-Value
[h.sf.F/Btu]
In Zone: Pr0Zo1
1 Pr0Zo1Fl2 190.00 15200.0 1 80.00 1 ft. soil, concrete
floor, carpet and
rubber pad
0.2681 34.00 113.33 3.73
Systems
Pr0Sy8 System 8 Constant Volume Air Cooled Split
System < 65000 Btu/hr
Component Category Capacity Efficiency IPLV
1No. Of Units
1 Cooling System 60000.00 14.00 12.80
2 Heating System 34100.00 1.00
3 Air Handling System -Supply 2000.00 0.80
Eff.Inst.NoSizeCategory Equipment IPLV
Plant
45/30/2018 EnergyGauge Summit® v6.00
LossEfficiencyI/P Rt.Cap.UnitCapacityW-Heater Description
Water Heaters
WattageArea/Len/No. of unitsCategory Description
[sf/ft/No] [W]
Ext-Lighting
No. of
Luminaires
Watts per
Luminaire
Control Type
Insulation
Thickness
[in]
Nomonal pipe
Diameter
[in]
Insulation
Conductivity
[ Btu-in/h.sf.F]
Operating
Temperature
[F]
Type
Piping
Is Runout?No
VLTSHGCGlass
Conductance
[Btu/h.sf.F]
No. of
Panes
Glass Type
Fenestration Used
Name
User Defined 1 1.0700 0.5200 0.7600 ApLbWnd13
55/30/2018 EnergyGauge Summit® v6.00
RValue
[h.sf.F/Btu]
SpecificHeat
[Btu/lb.F]
Density
[lb/cf]
Conductivity
[Btu/h.ft.F]
Thickness
[ft]DescriptionAcronymMat No
Materials Used
Only R-Value
Used
187 Matl187 GYP OR PLAS
BOARD,1/2IN
0.0417 0.0920 50.00 0.2000 0.4533 No
178 Matl178 CARPET W/RUBBER PAD 1.2300 Yes
265 Matl265 Soil, 1 ft 1.0000 0.5000 100.00 0.2000 2.0000 No
48 Matl48 6 in. Heavyweight concrete 0.5000 1.0000 140.00 0.2000 0.5000 No
268 Matl268 0.625" stucco 0.0521 0.4000 16.00 0.2000 0.1302 No
42 Matl42 8 in. Lightweight concrete
block
0.6670 0.3300 38.00 0.2000 2.0212 No
12 Matl12 3 in. Insulation 0.2500 0.0250 2.00 0.2000 10.0000 No
279 Matl279 Solid core flush (2.25") 2.8537 Yes
244 Matl244 PLYWOOD, 1/2IN 0.0417 0.0660 34.00 0.2900 0.6318 No
82 Matl82 ASPHALT-SHINGLE AND
SIDING
0.4400 Yes
1002 ApLbMat1002 R-4.1 Fi Foil Insulatrion 4.1000 Yes
Constructs Used
1011 5/8" stucco /8"CMU/R4.1
FiFoil/BTWN24"oc/.5" Gyp
0.15 5.65 37.15 6.7
No NameConductance
[Btu/h.sf.F]
Heat Capacity
[Btu/sf.F]
Density
[lb/cf]
RValue
[h.sf.F/Btu]
Layer Material
No.
Material Thickness
[ft]
Framing
Factor
No
Simple
Construct
No
Massless
Construct
1 268 0.625" stucco 0.0521 0.000
2 42 8 in. Lightweight concrete block 0.6670 0.000
3 1002 R-4.1 Fi Foil Insulatrion 0.1746 0.000
4 187 GYP OR PLAS BOARD,1/2IN 0.0417 0.000
65/30/2018 EnergyGauge Summit® v6.00
1042 Sngl Ply/3"Iso/1/2"WD Deck/WD Truss/Gyp
Br
0.09 0.93 12.01 11.5
No NameConductance
[Btu/h.sf.F]
Heat Capacity
[Btu/sf.F]
Density
[lb/cf]
RValue
[h.sf.F/Btu]
Layer Material
No.
Material Thickness
[ft]
Framing
Factor
No
Simple
Construct
No
Massless
Construct
1 82 ASPHALT-SHINGLE AND SIDING 0.000
2 244 PLYWOOD, 1/2IN 0.0417 0.000
3 12 3 in. Insulation 0.2500 0.000
4 187 GYP OR PLAS BOARD,1/2IN 0.0417 0.000
1057 1 ft. soil, concrete floor, carpet and rubber pad 0.27 34.00 113.33 3.7
No NameConductance
[Btu/h.sf.F]
Heat Capacity
[Btu/sf.F]
Density
[lb/cf]
RValue
[h.sf.F/Btu]
Layer Material
No.
Material Thickness
[ft]
Framing
Factor
No
Simple
Construct
No
Massless
Construct
1 265 Soil, 1 ft 1.0000 0.000
2 48 6 in. Heavyweight concrete 0.5000 0.000
3 178 CARPET W/RUBBER PAD 0.000
1058 Solid core flush (2.25) 0.35 2.9
No NameConductance
[Btu/h.sf.F]
Heat Capacity
[Btu/sf.F]
Density
[lb/cf]
RValue
[h.sf.F/Btu]
Layer Material
No.
Material Thickness
[ft]
Framing
Factor
No
Simple
Construct
Yes
Massless
Construct
1 279 Solid core flush (2.25") 0.000
75/30/2018 EnergyGauge Summit® v6.00
2018-May-30 11:34:19Right-Suite® U niv ersal 2018 18.0.08 RSU25198 Page 1
...lico Business Park Bldg 7 - Shell 5.30.2018.rup Calc = MN5 Front Door faces: W
Alico Business Park Bld...Job:Right-Suite® Universal 2018 Load SummaryMay 30, 2018Date:
Entire Building Eric StrubleBy:
E-Calcs Plus, Inc.
9250 Corkscrew Rd, Suite 8, Estero, FL 33928 Phone: 239.810.6106 Email: [email protected] Web: www.ecalcsplus.com
Project InformationAlico Business Park Bldg 7 - Shell, Trianon Design GroupFor:16111 Lee Rd, Fort Myers, FL 33912
COOLING LOADEntire BuildingZone:
Peak load at Jul 1700 LDTat Jul 1700 LDT1. DESIGN CONDITIONSInside: °F75 Outside: °F92 TD: °F17RH: 50 % MoistDiff: gr/lb50.0 Mult: 1.0 Ins.wb °F63
Sensible Latent208232. SOLAR RADIATION THROUGH GLASS -
3. TRANSMISSION GAINS Sensible 101435 -Walls: 29388 - -Glass: 10278 - -Doors: 27880 - -Partitions: 0 - -Floors: 0 - -Ceilings: 33889 - -
4. INTERNAL HEAT GAIN Sensible Latent 1900079058Occupants: 1900010830 - -Lights: 68228 - - -Motors: 0 - - -Appliances: 00 - -
5. INFILTRATION: 699Outside air cfm: 13446 237406. SUBTOTAL: Space load Sensible Latent 42740214762
Envelope 42740214762 - -Less external 0 - - -Redistribution 00 - -
460687. SUPPLY DUCT -8. SUBTOTAL: Space load + supply duct 260830 -
1550Actual cfm: at supply TD: 20 - -Make-up air cfm:9. VENTILATION: 17539912 30966
10. RETURN AIR LOAD: Lighting + plenum (net) 0 -3928111. RETURN DUCT -
9323731764912. TOTAL LOADS ON EQUIPMENT
HEATING LOAD
13. DESIGN CONDITIONS Mult: 1.0Inside: °F70 Outside: °F47 TD: °F23
14. TRANSMISSION LOSSES 102618Walls: 29405 -Glass: 15888 -Doors: 21344 -Partitions: 0 -Floors: 14656 -Ceilings: 21326 -
15. INFILTRATION: 338861340Outside air cfm:16. SUBTOTAL: Space load 136504
Envelope 136504 -Less external 0 -Less transfer 0 -Redistribution 0 -
17. SUPPLY DUCT: 3483318. VENTILATION: 23060912Make-up air cfm:19. HUMIDIFICATION 12229
Piping 020. RETURN DUCT 855121. TOTAL HEATING LOAD ON EQUIPMENT 215177
Job #: Alico Business Park Bldg 7 - Shell Performed by Eric Struble for:
Alico Business Park Bldg 7 - Shell 16111 Lee Rd
Fort Myers, FL 33912
E-Calcs Plus, Inc.
9250 Corkscrew Rd, Suite 8 Estero, FL 33928
Phone: 239.810.6106 www.ecalcsplus.com [email protected]
Scale: 1 : 317
Page 1 Right-Suite® Universal 2018
18.0.08 RSU25198 2018-May-30 11:35:18
...ark Bldg 7 - Shell 5.30.2018.rup
N
Ground Level
Building Shell
GENERAL STRUCTURAL NOTES
GENERAL: DETAILS AND SECTIONS SHOWN ON THE DRAWINGS ARE TYPICAL AND APPLY TO SIMILARSITUATIONS ELSEWHERE, EXCEPT AS OTHERWISE INDICATED. ADAPT REQUIREMENTS OF DETAILS,SECTIONS, PLANS, AND NOTES AT LOCATIONS WHERE CONDITIONS ARE SIMILAR. CENTER ALL FOOTINGSAND PIERS UNDER COLUMNS ABOVE UNLESS SPECIFICALLY DIMENSIONED OTHERWISE.
STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS ANDARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND SITE DRAWINGS. CONSULT THESEDRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN ON STRUCTURAL DRAWINGS.
CONTRACTOR SHALL LOCATE ALL BURIED UTILITIES PRIOR TO EXCAVATION FOR BUILDING FOUNDATIONS.THE STRUCTURAL ENGINEER SHALL BE NOTIFIED OF POTENTIAL CONFLICTS BETWEEN FOUNDATIONS ANDBURIED UTILITIES.
CODE REQUIREMENTS: THE BUILDING STRUCTURE IS DESIGNED IN ACCORDANCE WITH THE2017 EDITION OF THE FLORIDA BUILDING CODE 6th EDITION. FOLLOW ALL APPLICABLE PROVISIONS FORALL PHASES OF CONSTRUCTION.
TEMPORARY CONDITIONS: THE STRUCTURAL INTEGRITY OF THE COMPLETED STRUCTURE DEPENDS ONINTERACTION OF VARIOUS CONNECTED COMPONENTS. PROVIDE ADEQUATE BRACING, SHORING, ANDOTHER TEMPORARY SUPPORTS AS REQUIRED TO SAFELY COMPLETE THE WORK. THE STRUCTURESHOWN ON THE DRAWINGS HAS BEEN DESIGNED FOR STABILITY UNDER FINAL CONFIGURATION ONLY.
RETAINING WALLS WHICH TIE TO UPPER SLABS SHALL NOT BE BACKFILLED UNTIL THE UPPER SLABSREACH FULL STRENGTH, UNLESS ADEQUATE BRACING IS PROVIDED AT THE TOP OF THE WALL.
EXISTING CONDITIONS: ADDITIONS ARE IN COMPLIANCE WITH THE 2017 EDITION OF THE FLORIDAEXISTING BUILDING CODE.
ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS SHALL BE FIELD VERIFIED. THE CONTRACTORSHALL NOTIFY THE ENGINEER OF ANY SIGNIFICANT DISCREPANCIES FROM CONDITIONS SHOWN ON THEDRAWINGS.
EXERCISE EXTREME CARE AND CAUTION WHEN EXCAVATING AND FILLING ADJACENT TO EXISTINGSTRUCTURES. UNDER NO CIRCUMSTANCES SHALL THE STRUCTURAL INTEGRITY OF THE EXISTINGSTRUCTURES BE IMPAIRED IN ANY WAY BY CONSTRUCTION OPERATIONS AND PROCEDURES. DO NOTEXCAVATE OR DISTURB SOIL ADJACENT TO OR BENEATH EXISTING FOOTINGS.
DESIGN CRITERIA: DESIGN WAS BASED ON STRENGTH AND DEFLECTION CRITERIA OF THE2017 6th Ed FLORIDA BUILDING CODE. IN ADDITION TO THE DEAD LOADS, THE FOLLOWING LOADS ANDALLOWABLE'S WERE USED FOR DESIGN, WITH LIVE LOADS REDUCED PER THE 2017 FBC:
ROOF: 20 PSF LL 30 PSF SDL FLOORS:STORAGE: 125 PSF LL 20 PSF SDL NOTE: LOADING ABOVE INCLUDES 5 PSF FOR SPRINKLER PIPING
WIND SPEED 160 MPH ULTIMATE PER CHAPTER 26 ASCE 7-16124 MPH NOMINAL
RISK CATEGORY IIEXPOSURE: BINTERNAL PRESSURE COEFF +- 0.18 ENCLOSED
OPENINGS BELOW 60 FEET SHALL BE PROTECTED FROM WIND BORNE DEBRIS PER FBC 2017 ANDASCE 7-16 REQUIREMENTS.
FOUNDATIONS: FOUNDATIONS ARE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,500 PSFON COMPACTED FILL. BEFORE CONSTRUCTION COMMENCES, SOIL BEARING CAPACITY SHALL BE VERIFIEDBY A SUBSURFACE INVESTIGATION, AS WELL AS FIELD AND LABORATORY TESTS PERFORMED BY ACERTIFIED TESTING LABORATORY, WHO'S REPORT SHALL INCLUDE ANALYSIS AND RECOMMENDATIONSFOR SITE PREPARATION IN ORDER TO BEAR THE FOUNDATION LOADS. ABOVE REPORT SHALL BESUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW BEFORE FOUNDATION CONSTRUCTION BEGINS.
SUBMITTALS: SHOP DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT PRIOR TO FABRICATION ANDCONSTRUCTION REGARDING ALL STRUCTURAL ITEMS INCLUDING THE FOLLOWING:
CONCRETE MIX DESIGNS,CONCRETE AND MASONRY REINFORCING, STEEL DECK.
SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO THEARCHITECTENGINEER. DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED.
IF THE SHOP DRAWINGS DIFFER FROM OR ADD TO THE DESIGN OF THE STRUCTURAL DRAWINGS, THEYSHALL BEAR THE SEAL AND SIGNATURE OF A STRUCTURAL ENGINEER REGISTERED IN THE STATE OFFLORIDA. ANY CHANGES TO THE STRUCTURAL DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT ANDARE SUBJECT TO THE REVIEW AND ACCEPTANCE OF THE ENGINEER.
DESIGN DRAWINGS, SHOP DRAWINGS, AND CALCULATIONS FOR THE DESIGN AND FABRICATION OF ITEMSTHAT ARE DESIGNED BY OTHERS, INCLUDING:
COLD FORMED METAL STUDS,
SHALL BEAR THE SEAL AND SIGNATURE OF A STRUCTURAL ENGINEER REGISTERED IN THE STATE OFFLORIDA, AND SHALL BE SUBMITTED TO THE ARCHITECT PRIOR TO FABRICATION. CALCULATIONS SHALLBE INCLUDED FOR ALL CONNECTIONS TO THE STRUCTURE,CONSIDERING LOCALIZED EFFECTS ON THESTRUCTURAL ELEMENTS INDUCED BY THE CONNECTION LOADS. DESIGN SHALL BE BASED ON THEREQUIREMENTS OF THE 2017 FBC.
SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNINTENT OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THECONTRACTOR TO VERIFY COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH,ELEVATIONS, DIMENSIONS, ETC. CONTRACTOR SHALL NOT BE RELIEVED FROMRESPONSIBILITY FOR ERRORS OR OMISSIONS IN SHOP DRAWINGS OR MIX DESIGNS BY THE ENGINEER'SREVIEW.
CONCRETE: REINFORCED CONCRETE CONSTRUCTION SHALL CONFORM TO THE FBC AND ACI318 "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE". CONCRETE STRENGTHSSHALL BE VERIFIED BY STANDARD 28-DAY CYLINDER TESTS PER ASTM C39, AND SHALL BEAS FOLLOWS:
CABS WCUSE3000 PSI0.58 FOUNDATIONS SLAB ON GRADE 4000 PSI0.44 ALL USES, U.N.O.5000PSI 0.40FLOOR ROOF
CEMENT SHALL CONFORM TO ASTM C150, TYPE 1. FLY ASH CONFORMING TO ASTM C618,TYPE F OR TYPE C, MAY BE USED TO REPLACE UP TO 20 OF THE CEMENT CONTENT,PROVIDED THAT THE MIX STRENGTH IS SUBSTANTIATED BY TEST DATA. COARSE AGGREGATESHALL CONFORM TO ASTM C33 WITH A MAXIMUM SIZE OF 34". FINE AGGREGATE SHALL BECLEAN, DURABLE, NATURAL SAND CONFORMING TO ASTM C33.
A WATER-REDUCING ADMIXTURE, IF USED, SHALL CONFORM TO ASTM C494 AND USED INSTRICT ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS, SHALL BEINCORPORATED IN CONCRETE DESIGN MIXES. A HIGH-RANGE WATER-REDUCING ADMIXTURECONFORMING TO ASTM C494, TYPE F OR G, MAY BE USED IN CONCRETE MIXES, PROVIDINGTHAT THE SLUMP DOES NOT EXCEED 8”. SLEEVES, OPENINGS, CONDUIT, AND OTHER EMBEDDED ITEMSNOT SHOWN ON THE STRUCTURAL DRAWINGS SHALL BE APPROVED BY THE STRUCTURAL ENGINEERBEFORE POURING. NO SLEEVE, OPENING, OR INSERT MAY BE PLACED IN BEAMS, JOISTS, ORCOLUMNS UNLESS APPROVED BY THE ENGINEER. CONDUITS EMBEDDED IN SLABS SHALL NOT BELARGER IN OUTSIDE DIMENSION THAN ONE THIRD OF THE THICKNESS OF THE SLAB AND SHALL NOTBE SPACED CLOSER THAN THREE DIAMETERS ON CENTER.
PROVIDE 3/4” CHAMFERS ON ALL EXPOSED CONCRETE EDGES, UNLESS NOTED OTHERWISE. WHEREINDICATED OR REQUIRED, SLOPE CONCRETE SLABS TO DRAINS SHOWN ON PLUMBING AND ORARCHITECTURAL DRAWINGS.
ALL CONCRETE SHALL BE CURED IMMEDIATELY AFTER FINISHING OPERATIONS.
SHORING AND RESHORING: SHORING AND RESHORING SHALL CONFORM TO ACI 347R-04.SHORING AND SUPPORTING FORMWORK SHALL NOT BE REMOVED FROM HORIZONTAL MEMBERSBEFORE CONCRETE STRENGTH IS AT LEAST 70 PERCENT OF DESIGN STRENGTH, AS DETERMINED BYFIELD CURE CYLINDERS. IN ADDITION, SHORING SHALL NOT BE REMOVED SOONER THAN RECOMMENDEDBY ACI 347R-04, SECTION 3.7.2.3. FORMWORK SHALL NOTBE REMOVED IN LESS THAN TEN (10) DAYS.
REINFORCING STEEL: REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60, FORDEFORMED BAR AND ASTM A1064 FOR SMOOTH WELDED WIRE FABRIC (WWF), UNLESSOTHERWISE NOTED. REINFORCING STEEL TO BE WELDED SHALL CONFORM TO ASTM A706.REINFORCING STEEL SHALL BE SECURELY TIED IN PLACE WITH 16 ANNEALED IRON WIRE.
ALL DETAILING AND ACCESSORIES SHALL CONFORM TO ACI DETAILING MANUAL SP-66.PROVIDE CHAIRS, SPACERS, BOLSTERS, AND ITEMS IN CONTACT WITH FORMS WITH HOT-DIPGALVANIZED LEGS OR PLASTIC LEGS. ACCURATELY POSITION, SUPPORT, AND SECUREREINFORCEMENT AGAINST DISPLACEMENT BY FORMWORK CONSTRUCTION OR CONCRETEPLACEMENT OPERATIONS. "WET-STICKING" OF REINFORCING IS PROHIBITED.REQUIRED CONCRETE COVER FOR REINFORCING STEEL (UNLESS NOTED OTHERWISE):
FOOTINGS: 3" BOTTOM AND SIDES, 2" TOPSLABS: 3/4"COLUMNS: 1-1/2" TO TIES, 2"TOP BEAMS: 1-1/2" TO STIRRUPSWALLS 1-1/2”
LAP SPLICE CONTINUOUS VERTICAL OR HORIZONTAL BARS IN CONCRETE MEMBERS INACCORDANCE WITH ACI 318, LATEST EDITION, FOR CLASS "B" TENSION LAP SPLICES. DONOT SPLICE CONTINUOUS TOP BARS IN BEAMS AT ENDS OF CLEAR SPANS. DO NOT SPLICECONTINUOUS BOTTOM BARS IN BEAMS IN CLEAR SPANS BETWEEN SUPPORTS. SHOW ALLSPLICES ON SHOP DRAWINGS. SPLICE LOCATIONS AND METHODS SUBJECT TO APPROVAL OFSTRUCTURAL ENGINEER.
AT SLAB RE-ENTRANT CORNERS, PROVIDE (2) #5 X 4'-0” DIAGONAL BARS. AT SLAB AND WALL OPENINGSPROVIDE A MINIMUM OF (2) 5 BARS ALL FOUR SIDES AND DIAGONALLY; EXTEND THESE BARSA LAP DISTANCE OR A MINIMUM OF 24” PAST THE OPENING OR HOOK BARS IF DISCONTINUOUS.
DOWEL ALL WALLS AND COLUMNS TO FOOTINGS WITH BAR SIZE AND SPACING TO MATCHVERTICAL REINFORCING UNLESS OTHERWISE SHOWN.
SLABS ON GRADE: PREPARE SUBGRADE AS PER THE RECOMMENDATIONS OUTLINED IN THEGEOTECHNICAL REPORT. CHAIR WIRE FABRIC DURING CONCRETE PLACEMENT TO INSUREPROPER POSITION IN SLAB. USE VAPOR RETARDED UNDER ALL ENCLOSED INTERIOR SPACES,
PER ARCHITECTURAL DRAWINGS.
PLACE CRACK CONTROL JOINTS AS SHOWN ON PLAN OR AT 12 FEET MAXIMUM FOR 4” SLAB, OR 15 FEETMAXIMUM FOR 6” SLAB.JOINT SPACING SHALL NOT EXCEED A 2 TO 1 WIDTH TO LENGTH RATIO.CONTRACTOR SHALL SUBMIT A CONTROL JOINT LAYOUT FOR ENGINEER'S AND ARCHITECT'SREVIEW PRIOR TO CONCRETE PLACEMENT. LOCATE CONTROL JOINTS AT COLUMN LINES ANDRE-ENTRANT CORNERS TYPICAL.
FOR 4” THICK SLABS ON GRADE, PROVIDE 6X6 W1.4XW1.4 WELDED WIRE FABRIC OR 1.5POUNDS PER CUBIC YARD OF MICRO SYNTHETIC FIBERS (FRC MONO-150 OR EQUAL),UNLESS NOTED OTHERWISE.FOR 6” THICK SLABS ON GRADE, PROVIDE 6X6 W2.9XW2.9 WELDED WIRE FABRICPLACED 2' BELOW TOP OF SLAB OR 3 POUNDS PER CUBIC YARD OF MACRO SYNTHETICFIBERS (FORTA FERRO OR EQUAL), UNLESS NOTED OTHERWISE.
MECHANICAL ANCHORS: MECHANICAL ANCHORS SHALL HAVE THE ICC ES EVALUATIONREPORT INDICATING CONFORMANCE WITH CURRENT APPLICABLE ICC ES ACCEPTANCECRITERIA. MECHANICAL ANCHORS SHALL BE EXPANSION TYPE OR SCREW TYPE AS NOTED ON THEDRAWINGS.
EXPANSION STYLE ANCHORS SHALL BE TORQUE-CONTROLLED, WITH IMPACT SECTION TOPREVENT THREAD DAMAGE COMPLETE WITH REQUIRED NUTS AND WASHERS. PROVIDEANCHORS WITH LENGTH IDENTIFICATION MARKINGS CONFORMING TO ICC ES AC01 OR ICC ESAC193. TYPE AND SIZE AS INDICATED ON DRAWINGS.
SCREW STYLE ANCHORS SHALL BE ONE PIECE CARBON STEEL SCREW ANCHOR WITHFINISHED HEX HEAD WITH INTEGRAL WASHER, DOUBLE LEAD THREAD, CHAMFERED TIP,RATCHET TEETH ON UNDERSIDE OF HEAD. PROVIDE ANCHORS WITH HEAD STAMPED WITHDIAMETER AND LENGTH. TYPE AND SIZE AS INDICATED ON DRAWINGS.
Trianon Design Group
Telephone 239 390 1203
9990 Coconut RoadBonita Springs, Florida 34135
16111 Lee Road, Fort Myers, Florida, 33912
Gerald J. Yurk, AIA ARCHITECTAR 0005621
DRAWINGS, SPECIFICATIONS AND OTHER DOCUMENTS PREPAREDBY GERALD J. YURK A.I.A. ARCHITECT TRIANON DESIGN GROUP(TDG), AND HIS CONSULTANTS,ARE INSTRUMENTS OF TDG'SSERVICE AND ARE FOR THE OWNER'S USE SOLELY WITH RESPECTTO THIS PROJECT. TDG SHALL RETAIN ALL COMMON LAW,STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THECOPYRIGHT. UPON COMPLETION OR TERMINATION OF THE PROJECT,ALL PARTIES, WITH THE EXCEPTION OF TDG'S, RIGHTS TO USETHESE INSTRUMENTS OF SERVICE SHALL CEASE. WHENTRANSMITTING COPYRIGHT-PROTECTED INFORMATION FOR USE ONTHE PROJECT, THE TRANSMITTING PARTY REPRESENTS THAT IT HASPERMISSION FROM THE TDG TO TRANSMIT THE INFORMATION FORITS USE ON THE PROJECT. QUESTIONS ARISING DURINGCONSTRUCTION OR REVIEW OF THE DRAWINGS SHALL BEADDRESSED TO THE ARCHITECT.
for Permit5-16-2018
New Construction - Industrial Building
PROPOSED MASONRY BUILDING WITH A PREFAB METAL BUILDINGSUB STRUCTURE
JOSEPH C. KOSINSKI P.E.052288
15598 BEACH PEBBLE WAYFORT MYERS, FLORIDA 33908
239−872−2179
STRUCTURAL NOTESAND TYPICAL DETAILS
CORRECTIONS 10-31-18 CHANGE NOTESADDED 2 SHEETS AND UPDATED SEAL
CORRECTION COMMENTS DATED 1-17-19
UNLESS OTHERWISE NOTED, PROVIDE CARBON STEEL ANCHORS, ZINC PLATED INACCORDANCE WITH ASTM B633 OR HOT-DIPPED GALVANIZED ACCORDING TO ASTM A153. PERMANENTLYEXPOSED ANCHORS SHALL BE STAINLESS STEEL. USE 316 STAINLESS STEEL FORMECHANICAL EQUIPMENT AND FOR ALUMINUM AND FIBERGLASS STRUCTURES ANDASSEMBLIES.
ACCEPTABLE MECHANICAL ANCHORS FOR ANCHORAGE TO CONCRETE SHALL BE ASFOLLOWS, OR AS NOTED ON THE DRAWINGS:
1. HILTI KWIK HUS EZ AND KWIK HUS EZ-I SCREW ANCHORS PER ICC ESR-30272. HILTI KWIK BOLT-TZ EXPANSION ANCHORS PER ICC ESR-19173. HILTI KWIK BOLT 3 EXPANSION ANCHORS PER ICC ESR-2302
4. POWERS WEDGE BOLT SCREW ANCHOR PER ICC ESR-25265. POWERS POWER STUD+SD1 EXPANSION ANCHOR PER ICC ESR-28186. SIMPSON TITEN HD SCREW ANCHOR PER ICC ESR-27137. SIMPSON WEDGE ALL STRONG BOLT 2 PER ICC ESR-3037
MINIMUM EMBEDMENT FOR CONCRETE ANCHORS SHALL BE AS FOLLOWS, OR AS NOTED ONTHE DRAWINGS:1. 1/2” DIAMETER - 3 3/4” EMBEDMENT2. 5/8” DIAMETER - 5” EMBEDMENT3. 3/4" DIAMETER - 5 3/4” EMBEDMENT
FOR ANCHORAGE TO SOLID GROUTED CMU PROVIDE ONE OF THE FOLLOWING ANCHORS, ORAS NOTED ON THE DRAWINGS:1. HILTI KWIK BOLT 3 EXPANSION ANCHORS PER ICC ESR-13852. POWERS WEDGE BOLT SCREW ANCHOR PER ICC ESR-16783. POWERS POWER STUD+SD1 EXPANSION ANCHOR PER ICC ESR-29664. SIMPSON TITEN HD SCREW ANCHOR PER ICC ESR-1056
MINIMUM EMBEDMENT FOR SOLID GROUTED CMU ANCHORS SHALL BE AS FOLLOWS, OR ASNOTED ON THE DRAWINGS: ANCHORS NOT ALLOWED WITHIN 1 1/2" OF HEAD JOINTS1. 1/2” DIAMETER - 3 3/4” EMBEDMENT2. 5/8” DIAMETER - 5” EMBEDMENT3. 3/4" DIAMETER - 5 3/4” EMBEDMENT
IDENTIFY POSITION OF REINFORCING STEEL AND OTHER EMBEDDED ITEMS PRIOR TO DRILLINGHOLES FOR ANCHORS. EXERCISE CARE IN CORING OR DRILLING TO AVOID DAMAGINGEXISTING REINFORCING OR EMBEDDED ITEMS. NOTIFY THE ENGINEER IF REINFORCING STEELOR OTHER EMBEDDED ITEMS ARE ENCOUNTERED DURING DRILLING.
SUBSTITUTION REQUESTS FOR ALTERNATE PRODUCTS MUST BE APPROVED IN WRITING BYTHE STRUCTURAL ENGINEER OF RECORD PRIOR TO USE. SUBSTITUTIONS WILL BE EVALUATED BYTHEIR ICC ESR. INSTALL ANCHORS PER THE MANUFACTURER INSTRUCTIONS
MASONRY WALLS: CONSTRUCTION AND ACCESORIES SHALL CONFORM TO THE FBC AND TMS602 ACI 530.1 ASCE 6 IN ADDTION TO TMS 602 ACI 530.1 ASCE 5.
MASONRY UNITS SHALL MEET ASTM C90, TYPE 2. ASSEMBLIES SHALL HAVE A MINIMUM COMPRESSIVESTRENGTH OF f'm= 1500. MORTAR SHALL BE TYPE "M" OR "S" AND MEET ASTM C270.GROUT SHALL BE 2000 PSI MINIMUM COMPRESSIVE STRENGTH AND MEET ASTM C476. GROUT SHALLCONSIST OF A MIXTURE OF CEMENTITIOUS MATERIALS AND AGGREGATE TO WHICH SUFFICIENT WATERHAS BEEN ADDED TO CAUSE THE MIXTURE TO FLOW WITHOUT SEGREGATION OF THECONSTITUENTS. ALL CELLS CONTAINING VERTICAL BARS, BOND BEAMS, AND ALL CELLSBELOW GRADE SHALL BE FILLED WITH GROUT. MAXIMUM HEIGHT OF GROUT POUR ALLOWEDIS 4'-0" UNLESS CLEAN_OUT OPENING IS PROVIDED AT BOTTOM OF CELLS TO BE FILLED.LOCATE CLEAN-OUT OPENINGS IN AREAS NOT EXPOSED TO VIEW.
UNLESS NOTED OTHERWISE EIGHT INCH MASONRY WALLS SHALL BE PARTIALLY REINFORCEDMASONRY WALL CONSTRUCTION WITH 5 AT 48 INCH O.C. IN GROUT FILLED CELLS. ADD (1) 5REINFORCING BAR EACH SIDE OF OPENINGS EXCEEDING 3 FEET.
PROVIDE REINFORCING BARS AT CORNERS, INTERSECTIONS, AND EACH SIDE OF OPENINGS.PROVIDE (2) REINFORCING BARS EACH SIDE OF OPENINGS OVER 4 FEET WIDE, AND ASSHOWN ON THE PLANS. PROVIDE HOOKED DOWELS INTO FOOTINGS AND STRUCTURE ABOVE ANDORBELOW TO PROVIDE CONTINUITY. PROVIDE 9 GAGE GALVANIZED HORIZONTAL JOINTREINFORCING (DUR-O_WAL OR ENGINEER-APPROVED EQUAL) AT 16” O.C.
DO NOT PLACE CONDUITS, PIPES, ETC., IN CELLS WITH VERTICAL REINFORCING.DO NOT RUN CONDUITS, PIPES, ETC., HORIZONTALLY IN CMU WALLS PARALLEL TO LENGTH OF WALL.WHERE MASONRY WALLS ABUT CONCRETE COLUMNS TO BE PLACED PRIOR TO ERECTION OFMASONRY WALLS, PROVIDE DOVETAIL SLOTS BETWEEN COLUMN AND WALLS AND GROUT THE CMU CELLCONTAINING THE DOVETAIL ANCHORS. OTHERWISE, EXTEND CMU HORIZONTAL JOINTREINFORCING THROUGH CONCRETE COLUMN.
CONTROL JOINTS SHALL BE PROVIDED IN ALL CONCRETE MASONRY CONSTRUCTION ATLOCATIONS INDICATED ON THE ARCHITECTURAL DRAWINGS. HORIZONTAL WALL REINFORCINGSHALL BE STOPPED EACH SIDE OF CONTROL JOINTS. SEE ARCHITECTURAL DRAWINGS FORSEALANT REQUIREMENTS AT CONTROL JOINTS.
USE METAL LATH OR WIRE SCREEN FOR CAVITY CAPS. SHEET METAL, FELT, BUILDINGPAPER, OR LIKE MATERIALS ARE PROHIBITED.
TIE BEAMS: TIE BEAMS SHALL BE CONCRETE, POURED AFTER THE BLOCK WALLS BELOWARE IN PLACE. REINFORCING SHALL BE CONTINUOUS THROUGH TIE BEAMS WITH MINIMUM LAPSPLICES OF 48 BAR DIAMETERS AND BENT BARS AT CORNERS. USE METAL LATH, MORTAR,OR SPECIAL UNITS TO CONFINE CONCRETE TO AREA REQUIRED, IN ACCORDANCE WITH ACI530.1, SECTION 3.5 B. SOLID METAL OR FELT CAVITY CAPS ARE PROHIBITED.
PRECAST CONCRETE LINTELS: UNLESS INDICATED OTHERWISE, ALL LINTELS TO BE "U" TYPEPRECAST CONCRETE UNITS EQUAL TO UNITS MANUFACTURED BY CAST_CRETE CORP. ANDPRESTRESSED (AND ADDITIONALLY REINFORCED AS REQUIRED) IN ACCORDANCE WITHCAST_CRETE CORP. ''DESIGN MANUAL", LATEST EDITION, FOR THE SPAN AND LOADINGCONDITION RELATIVE TO LINTEL LOCATION.
LINTEL SIZE IF NOT SHOWN ON THE PLANS SHALL BE 8F8 FOR OPENINGS LESS THAN 6FEET,8F16-1B1T FOR OPENINGS 6 FEET TO 10 FEET, AND 8F24-1B2T FOR OPENINGS 10 FEET TO14FEET. PROVIDE 8" MINIMUM BEARING FOR LINTELS UNLESS NOTED OTHERWISE.
ANCHOR RODS: UNLESS INDICATED OTHERWISE ON THE DRAWINGS, ANCHOR RODS SHALLBE ASTM F1554 GRADE 36 AND THE SIZE SHALL BE 34 DIA. AND SHALL EMBED INTO THECONCRETE FOUNDATION A DISTANCE OF 1'-0” WITH A HEAVY HEX NUT AT THE EMBEDDED END.
STEEL ROOF DECK: STEEL ROOF DECK SHALL BE GALVANIZED AND CONFORM TO ASTMA653, STRUCTURAL QUALITY. THE GALVANIZED COATING SHALL CONFORM TO ASTM A653G60; OR G90 WHERE LEFT PERMANENTLY EXPOSED TO WEATHER. ATTACHMENTS, CLOSURESETC. SHALL BE IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.
DECK WELDING SHALL BE 5/8” EFFECTIVE DIAMETER PUDDLE WELDS AT 12”O.C. AT TRANSVERSE ANDPERIMETER SUPPORTS, 16” O.C. AT LONGITUDINAL SUPPORTS, AND MECHANICALLY FASTEN SIDE LAPCONNECTIONS USING #10 SELF TAPPING SCREW AT 16” O.C. UNLESS NOTED OTHERWISE ON THEDRAWINGS.
LIGHT-GAGE STEEL STUDS: STEEL STUDS SHALL BE C-STUDS WITH A MINIMUM YIELD OF33,000 PSI FOR 18 AND 20 GAUGE, AND 50,000 PSI FOR 14 AND 16 GAUGE. STUDS SHALLBE OF THE SIZE, GAUGE, AND SPACING SHOWN ON THE DRAWINGS. PROVIDE BRIDGING INCONFORMANCE WITH THE MANUFACTURER'S RECOMMENDATIONS ADEQUATE FORDEVELOPMENT OF THE FULL MOMENT CAPACITY OF THE STUDS. FOR LOAD-BEARING STUDS, TRACKSHALL BE OVERSIZE TO PROVIDE FULL STUD BEARING. SCREWS SHALL BE ELCODRIL-FLEX, HILTI KWIK-FLEX, OR APPROVED.
PRE-ENGINEERED METAL BUILDING: THE PRE-ENGINEERED METAL BUILDING SHALL CONSISTOF ROOF DECK, RIGID FRAMES, METAL WALL PANELS ON FRAMING, CANOPY FRAMING,GUTTERS AND DOWNSPOUTS, AND FLASHING. THE DESIGN SHALL BE IN ACCORDANCE TOAISC AND AISI SPECIFICATIONS AND MBMA "METAL BUILDING SYSTEMS MANUAL" DESIGNPRACTICES. METAL BUILDING SYSTEM TO BE DESIGNED TO SUPPORT THE SELFWEIGHT OFTHE METAL BUILDING SYSTEM, 5 PSF SUPERIMPOSED DEAD LOAD, AND INDICATED LIVE LOADAND WIND LOAD. FOR UPLIFT CONSIDERATIONS, THE RESISTING DEAD LOAD SHALL BE THESELFWEIGHT OF THE METAL BUILDING ONLY.
SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A STRUCTURAL ENGINEER REGISTEREDIN THE STATE OF FLORIDA. SHOP DRAWINGS SHALL INDICATE THE DESIGN LOADS ANDJOB NAME AND NUMBER. THEY SHALL INCLUDE DRAWINGS OF THE FRAMING MEMBERS WITHTHE CONNECTIONS, THE ANCHOR BOLT PLAN AND REACTIONS. STANDARD CUT SHEETS OFTHE ABOVE ARE NOT ACCEPTABLE. STANDARD CUT SHEETS MAY BE SUBMITTED FORSECONDARY FRAMING CONNECTION DETAILS, FLASHING AND SHEETING DETAILS, ETC.
Trianon Design Group
Telephone 239 390 1203
9990 Coconut RoadBonita Springs, Florida 34135
16111 Lee Road, Fort Myers, Florida, 33912
Gerald J. Yurk, AIA ARCHITECTAR 0005621
DRAWINGS, SPECIFICATIONS AND OTHER DOCUMENTS PREPAREDBY GERALD J. YURK A.I.A. ARCHITECT TRIANON DESIGN GROUP(TDG), AND HIS CONSULTANTS,ARE INSTRUMENTS OF TDG'SSERVICE AND ARE FOR THE OWNER'S USE SOLELY WITH RESPECTTO THIS PROJECT. TDG SHALL RETAIN ALL COMMON LAW,STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THECOPYRIGHT. UPON COMPLETION OR TERMINATION OF THE PROJECT,ALL PARTIES, WITH THE EXCEPTION OF TDG'S, RIGHTS TO USETHESE INSTRUMENTS OF SERVICE SHALL CEASE. WHENTRANSMITTING COPYRIGHT-PROTECTED INFORMATION FOR USE ONTHE PROJECT, THE TRANSMITTING PARTY REPRESENTS THAT IT HASPERMISSION FROM THE TDG TO TRANSMIT THE INFORMATION FORITS USE ON THE PROJECT. QUESTIONS ARISING DURINGCONSTRUCTION OR REVIEW OF THE DRAWINGS SHALL BEADDRESSED TO THE ARCHITECT.
for Permit5-16-2018
New Construction - Industrial Building
PROPOSED MASONRY BUILDING WITH A PREFAB METAL BUILDINGSUB STRUCTURE
JOSEPH C. KOSINSKI P.E.052288
15598 BEACH PEBBLE WAYFORT MYERS, FLORIDA 33908
239−872−2179
STRUCTURAL NOTESAND TYPICAL DETAILS
CORRECTIONS 10-31-18 CHANGE NOTESADDED 2 SHEETS AND UPDATED SEAL
CORRECTION COMMENTS DATED 1-17-19
Trianon Design Group
Telephone 239 390 1203
9990 Coconut RoadBonita Springs, Florida 34135
16111 Lee Road, Fort Myers, Florida, 33912
Gerald J. Yurk, AIA ARCHITECTAR 0005621
DRAWINGS, SPECIFICATIONS AND OTHER DOCUMENTS PREPAREDBY GERALD J. YURK A.I.A. ARCHITECT TRIANON DESIGN GROUP(TDG), AND HIS CONSULTANTS,ARE INSTRUMENTS OF TDG'SSERVICE AND ARE FOR THE OWNER'S USE SOLELY WITH RESPECTTO THIS PROJECT. TDG SHALL RETAIN ALL COMMON LAW,STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THECOPYRIGHT. UPON COMPLETION OR TERMINATION OF THE PROJECT,ALL PARTIES, WITH THE EXCEPTION OF TDG'S, RIGHTS TO USETHESE INSTRUMENTS OF SERVICE SHALL CEASE. WHENTRANSMITTING COPYRIGHT-PROTECTED INFORMATION FOR USE ONTHE PROJECT, THE TRANSMITTING PARTY REPRESENTS THAT IT HASPERMISSION FROM THE TDG TO TRANSMIT THE INFORMATION FORITS USE ON THE PROJECT. QUESTIONS ARISING DURINGCONSTRUCTION OR REVIEW OF THE DRAWINGS SHALL BEADDRESSED TO THE ARCHITECT.
for Permit5-16-2018
New Construction - Industrial Building
PROPOSED MASONRY BUILDING WITH A PREFAB METAL BUILDINGSUB STRUCTURE
JOSEPH C. KOSINSKI P.E.052288
15598 BEACH PEBBLE WAYFORT MYERS, FLORIDA 33908
239−872−2179
STRUCTURAL NOTESAND TYPICAL DETAILS
CORRECTIONS 10-31-18 CHANGE NOTESADDED 2 SHEETS AND UPDATED SEAL
CORRECTION COMMENTS DATED 1-17-19
CONTROL JOINT1-#6 EACH SIDE OFJOINT THEN @ 48"
y" Z-PLATE @ 3'-4" VERTICALLYSTARTING AT TIE BEAM LOCATION.PROVIDE s"Ø HD ANCHOR BOLTS(6" EMBED.)
SCALE: 1"=1'-0"5
LINTEL SECTION OVER DOORS AND WINDOWS
CONT.REINF. WITH 2-#6FILLED WITH GROUT,VERT. BOND BEAM,
758"
BLOCK SOLID ATREINFORCING
#6 AT 48" GROUT
SEE ARCH. DWGS.
#3 @ 8"
SCALE: 1"=1'-0"4
C.M.U. CONTROL JOINT DETAIL AT COLUMN
2'-0
"G
RO
UT
ALL
CE
LLS
SO
LID
BY OTHERSEXTERNAL SLAB
FIN. FL.
FOOTING SECTION AT ENTRY
2'-0"
SCALE: 1"=1'-0"3
4-#5 CONT.
#5 @ 12"
5"4"
1'-6
"
2'-6
"
FINISH GRADEFIN. FL.
MIN
.
2
2'-0"
TYPICAL TURNDOWN SLAB SECTIONSCALE: 1"=1'-0"
1'-4
"
8"
OR SURFACE
NOTE:1. PROVIDE 16" MIN. BRG. FOR BOND BEAM AT EACH END.2. SEE 9/S-0.00 FOR WALL REINF. AT OPENINGS.
ALTERNATE TIE BEAM:16" x 8" CONCRETE W/2-#5 T & B AND #3TIES @ 8"
4-#5 CONT.0N #5 @ 12"
6"
Trianon Design Group
Telephone 239 390 1203
9990 Coconut RoadBonita Springs, Florida 34135
16111 Lee Road, Fort Myers, Florida, 33912
Gerald J. Yurk, AIA ARCHITECTAR 0005621
DRAWINGS, SPECIFICATIONS AND OTHER DOCUMENTS PREPAREDBY GERALD J. YURK A.I.A. ARCHITECT TRIANON DESIGN GROUP(TDG), AND HIS CONSULTANTS,ARE INSTRUMENTS OF TDG'SSERVICE AND ARE FOR THE OWNER'S USE SOLELY WITH RESPECTTO THIS PROJECT. TDG SHALL RETAIN ALL COMMON LAW,STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THECOPYRIGHT. UPON COMPLETION OR TERMINATION OF THE PROJECT,ALL PARTIES, WITH THE EXCEPTION OF TDG'S, RIGHTS TO USETHESE INSTRUMENTS OF SERVICE SHALL CEASE. WHENTRANSMITTING COPYRIGHT-PROTECTED INFORMATION FOR USE ONTHE PROJECT, THE TRANSMITTING PARTY REPRESENTS THAT IT HASPERMISSION FROM THE TDG TO TRANSMIT THE INFORMATION FORITS USE ON THE PROJECT. QUESTIONS ARISING DURINGCONSTRUCTION OR REVIEW OF THE DRAWINGS SHALL BEADDRESSED TO THE ARCHITECT.
for Permit5-16-2018
New Construction - Industrial Building
PROPOSED MASONRY BUILDING WITH A PREFAB METAL BUILDINGSUB STRUCTURE
JOSEPH C. KOSINSKI P.E.052288
15598 BEACH PEBBLE WAYFORT MYERS, FLORIDA 33908
239−872−2179
SECTIONS & DETAILS
CORRECTIONS 10-31-18 UPDATED SEAL
SCALE: 1"=1'-0"
NOMINAL WIND PRESSURES
SCALE: 1"=1'-0"
ULTIMATE WIND PRESSURES
CORRECTION COMMENTS DATED 1-17-19