BFPBreaker failure protection
1MRK 580 024-BEN
Issued: January 2001Status: New
Data subject to change without notice
Features Adaptive signal detecting algorithm fordetection even during CT saturation
10 ms reset time of current detection ele-
ments during all conditions Phase segregated current measurement
Single or three phase start and retrip
Independent timers for each phase
Three phase backup trip with independent
timer
Application In many protection applications local redun-dancy is used. One part of the fault clearancesystem is however never duplicated, namelythe circuit breaker. Therefor a breaker failureprotection can be used.
The breaker failure protection is initiatedfrom trip signals from protection functionswithin or outside the protection terminal.
When a trip signal is sent to the breaker fail-ure protection first, with no or a very shortdelay, a re-trip signal can be sent to the pro-tected breaker. If fault current is flowingthough the breaker still after a setting time aback-up trip signal is sent to the back-upbreakers. This will ensure fault clearance alsoif the circuit breaker is out of order.
Design The breaker failure protection function is ini-tiated by the trip commands from protectionfunctions placed either inside the same termi-nal or externally, by connection to appropri-ate binary inputs. Three separate functionalinputs are available for single-phase starting.A dedicated input is available also for three-phase starting.
The operate value of the phase segregatedcurrent measuring elements is settable withina wide range. Three independent timers t2 are
available for phase segregated breaker failuredetection.
An additional timer t1 for retrip command isavailable. Dedicated setting allow to enableor disable the retrip or to perform it by cur-rent check or not. Retrip to the faulty circuitbreaker can be issued single phase or threephase.
Special adaptive algorithm (ASD), togetherwith RMS measurement, allow a fast reset-ting time of the current measuring elements.The current measurement is stabilised againstdc-transients which can cause unwanted oper-
ation with saturated current transformers.
Function blockBFP
BLOCK
START
STL1
STL2
STL3
TRBU
TRRET
TRRETL1
TRRETL2
TRRETL3
xx00000200.vsd
7/30/2019 Breaker Failure Protection BFP
2/2
Breaker failure protection BFP1MRK 580 024-BEN
Page 2
Input and outputsignals
Table 1: Input signals for the breaker failure protection (BFP--) function block
Table 2: Output signals for the breaker failure protection BFP (BFP--) functionblock
Technical data Table 3: Breaker failure protection
Manufacturer
Signal Description
BLOCK Block function
START Start function
STL1 Start phase L1
STL2 Start phase L2
STL3 Start phase L3
Signal Description
TRBU Backup trip
TRRET Retrip
TRRETL1 Retrip by phase L1
TRRETL2 Retrip by phase L2
TRRETL3 Retrip by phase L3
Parameter Setting range Accuracy
Operate current (one mea-
suring element per phase)
5-200% of Ir in steps of 1% +/-2.5% of Ir at I Ir
+/-2.5% of I at I > Ir
Retrip time delay t1 0-60 s in steps of 1 ms +/-0.5% of setting +/-10 ms
Back-up trip time delay t2 0-60 s in steps of 1 ms +/-0.5% of setting +/-10 ms
Parameter Value
Trip operate time Max 18 ms
Reset time Max 10 ms