Breaker Failure Protection BFP

Embed Size (px)

Citation preview

  • 7/30/2019 Breaker Failure Protection BFP

    1/2

    Page 1

    BFPBreaker failure protection

    1MRK 580 024-BEN

    Issued: January 2001Status: New

    Data subject to change without notice

    Features Adaptive signal detecting algorithm fordetection even during CT saturation

    10 ms reset time of current detection ele-

    ments during all conditions Phase segregated current measurement

    Single or three phase start and retrip

    Independent timers for each phase

    Three phase backup trip with independent

    timer

    Application In many protection applications local redun-dancy is used. One part of the fault clearancesystem is however never duplicated, namelythe circuit breaker. Therefor a breaker failureprotection can be used.

    The breaker failure protection is initiatedfrom trip signals from protection functionswithin or outside the protection terminal.

    When a trip signal is sent to the breaker fail-ure protection first, with no or a very shortdelay, a re-trip signal can be sent to the pro-tected breaker. If fault current is flowingthough the breaker still after a setting time aback-up trip signal is sent to the back-upbreakers. This will ensure fault clearance alsoif the circuit breaker is out of order.

    Design The breaker failure protection function is ini-tiated by the trip commands from protectionfunctions placed either inside the same termi-nal or externally, by connection to appropri-ate binary inputs. Three separate functionalinputs are available for single-phase starting.A dedicated input is available also for three-phase starting.

    The operate value of the phase segregatedcurrent measuring elements is settable withina wide range. Three independent timers t2 are

    available for phase segregated breaker failuredetection.

    An additional timer t1 for retrip command isavailable. Dedicated setting allow to enableor disable the retrip or to perform it by cur-rent check or not. Retrip to the faulty circuitbreaker can be issued single phase or threephase.

    Special adaptive algorithm (ASD), togetherwith RMS measurement, allow a fast reset-ting time of the current measuring elements.The current measurement is stabilised againstdc-transients which can cause unwanted oper-

    ation with saturated current transformers.

    Function blockBFP

    BLOCK

    START

    STL1

    STL2

    STL3

    TRBU

    TRRET

    TRRETL1

    TRRETL2

    TRRETL3

    xx00000200.vsd

  • 7/30/2019 Breaker Failure Protection BFP

    2/2

    Breaker failure protection BFP1MRK 580 024-BEN

    Page 2

    Input and outputsignals

    Table 1: Input signals for the breaker failure protection (BFP--) function block

    Table 2: Output signals for the breaker failure protection BFP (BFP--) functionblock

    Technical data Table 3: Breaker failure protection

    Manufacturer

    Signal Description

    BLOCK Block function

    START Start function

    STL1 Start phase L1

    STL2 Start phase L2

    STL3 Start phase L3

    Signal Description

    TRBU Backup trip

    TRRET Retrip

    TRRETL1 Retrip by phase L1

    TRRETL2 Retrip by phase L2

    TRRETL3 Retrip by phase L3

    Parameter Setting range Accuracy

    Operate current (one mea-

    suring element per phase)

    5-200% of Ir in steps of 1% +/-2.5% of Ir at I Ir

    +/-2.5% of I at I > Ir

    Retrip time delay t1 0-60 s in steps of 1 ms +/-0.5% of setting +/-10 ms

    Back-up trip time delay t2 0-60 s in steps of 1 ms +/-0.5% of setting +/-10 ms

    Parameter Value

    Trip operate time Max 18 ms

    Reset time Max 10 ms

    ABB Automation Products AB

    Substation Automation Division

    SE-721 59 Vsters

    Sweden

    Tel: +46 (0) 21 34 20 00

    Fax: +46 (0) 21 14 69 18