    BOILER JUNCTION BOX

    FEATURES

    Simplified wiring.

    One wire per terminal.

    Cable clamps.

    Strong fire retardant ABS box.

    Designed to comply with BS3955 and

    its partial replacement – BS EN 60730

    and BS EN 61058.

     APPLICATION

    The Boiler Junction Box allows simplified wiring and IEE

    compliance when connecting mains, boiler and pump to the

    system. When the mains, boiler and pump are located a

    considerable distance from the Base Unit, it allows either two

    twin and earth cables or a single three core and earth cable to

    be run from the boiler junction box to the Base Unit. This reduces

    the number of cable runs required and also the potential for

    errors to be introduced in the system wiring.

    1.5

     S MA 

    RT  F I   T  

  • 8/17/2019 Boiler Junction Box

    2/2

    BOILER JUNCTION BOX

     Installation

    The location should be convenient forinstallation components wiring and bereadily accessible.

    If fitted on a wall, the box may bemounted either way up to allow for top orbottom cable entry; the lid is reversibleon the base.

    All information for the wiring is providedon a label in the lid.

    An optional sub base adaptor is availablefor mini trunking, which comes with fullinstallation instructions.

    Ordering Specification

    42009699-001Boiler Junction Box

    42005749-001Mini trunking sub base adaptor completewith sub base to Boiler Junction Box andfixing screws.

    Dimensions

     Specification

    BOILER JUNCTION BOX

    Number of Terminals : 17

    Nominal Terminal Capacity : 2 x 1.5mm2

    Maximum Current – Terms : 10 amp 230V 50Hz

    Maximum Current – PCB : 5 amp 230V 50Hz

    Cable Clamp Capacity : 4 x 2.5mm2 twin and E

    : (max) per clamp (2 off)

    Ambient Temperature Rating : 10˚C to 90˚C

    Fixing : 3 fixing holes in base for

    : No. 8 woodscrews

    MINI TRUNKING SUB BASE ADAPTOR

    Mini Trunking Breakouts : 13 breakouts distributed around the four

    : sides of the adaptorCable Clamp Capacity : 4 x 2.5mm2 twin and E (max) per clamp

    : (2 off) from Boiler Junction Box

    Fixing : 3 fixing holes in base for No. 8 woodscrews.

    : 3 off 4BA screws provided to fit adaptor to

    : Boiler Junction Box

    EC Directive : Conforms to 89/336/EEC

    A B C D E F  

    101 30 170 106 93 185