Biocide injection schematic + recomendation

  • Upload
    hossein

  • View
    235

  • Download
    0

Embed Size (px)

Citation preview

  • 8/11/2019 Biocide injection schematic + recomendation

    1/54

    TA821

    Bactirem 455

    TA822

    Bactirep 4018

    GX821 GX822GX821-2A GX821-2B

    GX822B

    WATERINJECTION

    WATER

    INJECTION

    DA-350

    GX722 Suction

    DS300 W t O tl t

    GX721 Suction

  • 8/11/2019 Biocide injection schematic + recomendation

    2/54

    22,443 sbopd

    149 m3/h

    324 sbwpd

    2.1 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 821-2A 0.89 500 0.44 5 2.2

    U/S DS301 GX 822B 2.15 2,000 4.30 5 21.5

    GX722 discharge

    to DS-320GX 822B 5.20 500 2.60 5 13.0

    Oily water 8''header

    GX 822B 10 500 5.0 1 5.0

    DA350 GX 821-2A 14.5 1,000 0.60 24 14.5

    LOCATION PUMPBIOCIDE

    Considering the line length, better to inject slowly

    but during long time. 1,000 ppm because of

    bacteria detected

    To be started first

    2,000 ppm due to low water production rate

    To be done after injection in DS301

    1 hour is enough to replace 3 times the 8" linevolume, to be done after discharge to DS320

    WATER

    OIL

    REMARK

  • 8/11/2019 Biocide injection schematic + recomendation

    3/54

    30,574 sbopd

    203 m3/h

    361 sbwpd

    2.4 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 821-2A 0.89 500 0.44 5 2.2 2

    U/S DS301 GX 822B 2.39 2,000 4.78 5 23.9 3

    GX722 discharge

    to DS-320GX 822B 7.09 500 3.54 5 17.7 1

    Oily water 8''header

    GX 822B 10 500 5.0 1 5.0 4

    DA350 GX 821-2A 14.5 500 0.60 12 7.3 5

    OIL

    LOCATION PUMPBIOCIDE

    ORDER

    WATER

    Considering the line length, better to inject slowly but

    during long time.

    2,000 ppm due to low water production rate

    1 hour is enough to replace 3 times the 8" line volume,to be done after discharge to DS320

    REMARK

  • 8/11/2019 Biocide injection schematic + recomendation

    4/54

    30,849 sbopd

    204 m3/h

    1,000 sbwpd

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 821-2A 0.89 500 0.44 5 2.2 2

    U/S DS301 GX 822B 6.63 1,000 6.63 5 33.1 3

    GX722 discharge

    to DS-320GX 822B 7.15 500 3.58 5 17.9 1

    Oily water 8''header

    GX 822B 10 500 5.0 1 5.0 4

    DA350 GX 822B 14.5 1,000 2.90 5 14.5 5

    LOCATION PUMPBIOCIDE

    ORDER

    1,000 ppm due to bad DS-401 outlet

    1,000 ppm due to low water production rate

    1 hour is enough to replace 3 times the 8" line volume

    WATER

    OIL

    REMARK

  • 8/11/2019 Biocide injection schematic + recomendation

    5/54

    30,849 sbopd

    204 m3/h

    1,000 sbwpd

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 821-2A 0.89 1,000 0.89 5 4.4 2

    U/S DS301 GX 822B 6.63 1,500 9.94 5 49.7 3

    GX722 discharge

    to DS-320GX 822B 7.15 750 5.36 5 26.8 1

    Oily water 8''header

    GX 822B 10 750 7.5 1 7.5 4

    DA350 GX 822B 14.5 1,500 4.35 5 21.8 5

    WATER

    OIL

    Increase injection rate to be sure to kill all bacteria in

    case of TRB detection problem in Lab

    REMARKLOCATION PUMPBIOCIDE

    ORDER

  • 8/11/2019 Biocide injection schematic + recomendation

    6/54

    30,849 sbopd

    204 m3/h

    1,000 sbwpd

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 821-2A 0.89 1,000 0.89 5 4.4 2

    U/S DS301 GX 822B 6.63 1,500 9.94 5 49.7 3

    GX722 discharge

    to DS-320GX 822B 7.15 750 5.36 5 26.8 1

    Oily water 8''header

    GX 822B 10 750 7.5 1 7.5 4

    DA350 GX 822B 14.5 1,500 4.35 5 21.8 5

    DS301 oil outlet

    (PSV 3130 A/B

    treatment)

    GX 822B 2.00 2 4.0 7

    TA 360 GX 822B 50 1 50 6

    LOCATION PUMPBIOCIDE

    ORDER

    WATER

    OIL

    Increase injection rate to be sure to kill all bacteria

    REMARK

  • 8/11/2019 Biocide injection schematic + recomendation

    7/54

    30,849 sbopd

    204 m3/h

    1,000 sbwpd

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 821-2A 0.89 500 0.44 5 2.2 2

    U/S DS301 GX 822B 6.63 1,000 6.63 5 33.1 3

    GX722 discharge

    to DS-320 and oily

    water header

    GX 822B 17.50 500 8.75 5 43.8 1

    DA350 GX 822B 14.5 1,000 2.90 5 14.5 4

    DS301 oil outlet

    (PSV 3130 A/B

    treatment)

    GX 822B 2.00 2 4.0 5

    TA 360 GX 822B 50 1 50 6

    dead legs careful to not inject more than 4 l in order to

    protect PSV from local high concentration biocide

    which can damage PSV gasket

    WATER

    1,000 ppm due to low water production rate

    Open 2 hours the by pass to oily water header

    1000 ppm because we often detect bacteria in DA 350

    LOCATION PUMPBIOCIDE

    ORDER

    OIL

    REMARK

  • 8/11/2019 Biocide injection schematic + recomendation

    8/54

    30,849 sbopd

    204 m3/h

    1,000 sbwpd

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 821-2A 0.89 500 0.44 5 2.2 2

    U/S DS301 GX 822B 6.63 1,000 6.63 5 33.1 3

    GX722 discharge

    to DS-320 (wash

    water)

    GX 822B 7.15 500 3.58 5 17.9 1

    DA350 GX 822B 14.5 1,000 2.90 5 14.5 4

    DS301 oil outlet

    (PSV 3130 A/B

    treatment)

    GX 822B 2.00 2 4.0 5

    TA 360 GX 822B 50 1 50 6

    OIL

    REMARKLOCATION PUMPBIOCIDE

    ORDER

    dead legs careful to not inject more than 4 l in order to

    protect PSV from local high concentration biocide

    which can damage PSV gasket

    WATER

    1,000 ppm due to low water production rate

    1000 ppm because we often detect bacteria in DA 350

  • 8/11/2019 Biocide injection schematic + recomendation

    9/54

    30,849 sbopd

    204 m3/h

    1,000 sbwpd

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 821-2A 0.89 500 0.44 5 2.2 2

    U/S DS301 GX 822B 6.63 1,000 6.63 5 33.1 3

    GX722 discharge

    to DS-320 (wash

    water)

    GX 822B 25.00 500 12.50 5 62.5 1

    DA350 GX 822B 14.5 1,000 2.90 5 14.5 4

    TA 360 GX 822B 50 1 50 5

    WATER

    1,000 ppm due to low water production rate

    1000 ppm because we often detect bacteria in DA 350

    LOCATION PUMPBIOCIDE

    ORDER

    OIL

    REMARK

  • 8/11/2019 Biocide injection schematic + recomendation

    10/54

    21,404 sbopd

    142 m3/h

    633 sbwpd

    4.2 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 821-2A 1.96 500 0.98 5 4.9 2

    U/S DS301 GX 822B 4.19 1,000 4.19 5 21.0 3

    GX722 discharge

    to DS-320 (wash

    water)

    GX 822B 25.00 500 12.50 5 62.5 1

    DA350 GX 822B 14.5 1,000 2.90 5 14.5 4

    TA 360 GX 822B 50 1 50 5

    TRAITEMENT

    455

    OIL

    REMARKLOCATION PUMPBIOCIDE

    ORDER

    WATER

    1,000 ppm due to low water production rate

    1000 ppm because we often detect bacteria in DA 350

  • 8/11/2019 Biocide injection schematic + recomendation

    11/54

    32,085 sbopd

    164 m3/h OIL 7294 SBOPD

    1,000 sbwpd WATER 4 SBWPD

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 2.61 500 1.31 5 6.5 2

    U/S DS301 GX 822B 6.63 1,000 6.63 5 33.1 3

    GX722 discharge to

    DS-320 (wash water)GX 822B 25 500 12.50 5 62.5 1

    Flushing of Oily water8'' header

    GX 822B 20 500 10.0 1 10.0 4

    DA350 GX 822B 14.5 1,000 2.90 5 14.5 5

    TA 360 50 6

    TRAITEMENT

    4018

    To use a bucket to tranfer the biocide directly in the

    open drain

    WATER

    1,000 ppm due to low water production rate

    To inject at the outlet of GX722

    1000 ppm because we often detect bacteria in DA 35

    To inject at the outlet of GX722

    LOCATION PUMPBIOCIDE

    ORDER

    OIL

    REMARK

    From D1 + D2

  • 8/11/2019 Biocide injection schematic + recomendation

    12/54

    43,902 sbopd

    158 m3/h OIL 20000 SBOPD

    1,500 sbwpd WATER 500 SBWPD

    9.9 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 500 0.50 5 2.5 2

    U/S DS301 GX 822B 9.94 1,000 9.9 5 49.7 3

    GX722 discharge to

    DS-320 (wash water)GX 822B 15 500 7.50 5 37.5 1

    Flushing of Oily water8'' header

    GX 822B 20 500 10.0 1 10.0 4

    DA350 GX 822B 14.5 1,000 2.90 5 14.5 5

    TA 360 GX 822B 50 1 50 6

    TRAITEMENT 455

    OIL

    REMARK

    From D1 + D2

    LOCATION PUMPBIOCIDE

    ORDER

    WATER

    1,000 ppm due to low water production rate

    To inject at the outlet of GX722

    1000 ppm because we often detect bacteria in DA 35

    To inject at the outlet of GX722

  • 8/11/2019 Biocide injection schematic + recomendation

    13/54

    78,138 sbopd

    521 m3/h OIL 48000 SBOPD

    3,300 sbwpd WATER 2300 SBWPD

    21.9 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.00 5 5.0 2

    U/S DS301 GX 822B 21.86 1,000 21.9 5 109.3 3

    GX722 discharge to

    DS-320 (wash water)GX 822B 15 500 7.50 5 37.5 1

    Flushing of Oily water8'' header

    GX 822B 20 500 10.0 1 10.0 4

    DA350 GX 822B 14.5 500 1.45 5 7.3 5

    TA 360 GX 822B 50 1 50 6

    TRAITEMENT

    4018

    WATER

    To inject at the outlet of GX722

    To inject at the outlet of GX722

    LOCATION PUMPBIOCIDE

    ORDER

    OIL

    REMARK

    From D1 + D2

  • 8/11/2019 Biocide injection schematic + recomendation

    14/54

    30,138 sbopd

    201 m3/h

    1,000 sbwpd

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.00 5 5.0 2

    U/S DS301 GX 822B 6.63 1,000 6.6 5 33.1 3

    GX722 discharge to

    DS-320 (wash water)GX 822B 20 500 10.00 5 50.0 1

    DA350 GX 822B 14.5 500 1.45 5 7.3 4

    TA 360 GX 822B 50 1 50 5

    TRAITEMENT

    455

    OIL

    REMARKLOCATION PUMPBIOCIDE

    ORDER

    WATER

    Open 2 hours the by pass to oily water header for

    Flushing of Oily water 8'' header

  • 8/11/2019 Biocide injection schematic + recomendation

    15/54

    23,664 sbopd

    158 m3/h

    1,000 sbwpd

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.00 5 5.0 2

    U/S DS301 GX 822B 6.63 1,000 6.6 5 33.1 3

    GX722 discharge to

    DS-320 (wash water)GX 822B 20 500 10.00 5 50.0 1

    DA350 GX 822B 14.5 500 1.45 5 7.3 4

    TA 360 GX 822B 50 1 50 5

    TRAITEMENT

    4018

    WATER

    Open 2 hours the by pass to oily water header for

    Flushing of Oily water 8'' header

    LOCATION PUMPBIOCIDE

    ORDER

    OIL

    REMARK

  • 8/11/2019 Biocide injection schematic + recomendation

    16/54

    53,664 sbopd

    358 m3/h OIL 30000 SBOPD

    2,500 sbwpd WATER 1500 SBWPD

    16.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.00 5 5.0 2

    U/S DS301 GX 822B 16.56 1,000 16.6 5 82.8 3

    GX722 discharge to

    DS-320 (wash water)GX 822B 40 500 20.00 5 100.0 1

    DA350 GX 822B 14.5 500 1.45 5 7.3 4

    TRAITEMENT

    455

    OIL

    REMARK

    WATER

    LOCATION PUMPBIOCIDE

    ORDER

    From D1 + D2

    DO NOT CLOSE 2'' FLUSHING LINE

  • 8/11/2019 Biocide injection schematic + recomendation

    17/54

    73,664 sbopd

    491 m3/h OIL 50000 SBOPD

    3,500 sbwpd WATER 2500 SBWPD

    23.2 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS301 GX 822B 23.19 1,000 23.2 5 115.9 2

    GX722 discharge to

    DS-320 (wash water)GX 822B 20 500 10.00 5 50.0 1

    DA350 GX 822B 14.5 500 1.45 5 7.3 3

    TRAITEMENT

    4018

    OIL

    REMARK

    WATER

    From D1 + D2

    LOCATION PUMPBIOCIDE

    ORDER

    Open 2 hours the 2'' flushing line to 8'' inch oily wate

    header

  • 8/11/2019 Biocide injection schematic + recomendation

    18/54

    65,875 sbopd

    439 m3/h OIL 40000 SBOPD

    2,600 sbwpd WATER 1600 SBWPD

    17.2 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS301 GX 822B 17.23 1,000 17.2 5 86.1 2

    GX722 discharge to

    DS-320 (wash water)GX 822B 20 500 10.00 5 50.0 1

    DA350 GX 822B 14.5 500 1.45 5 7.3 3

    TRAITEMENT

    455

    OIL

    REMARK

    WATER

    LOCATION PUMPBIOCIDE

    ORDER

    From D1 + D2

    Open 2 hours the 2'' flushing line to 8'' inch oily wate

    header

  • 8/11/2019 Biocide injection schematic + recomendation

    19/54

    68,168 sbopd

    454 m3/h OIL 38000 SBOPD

    2,520 sbwpd WATER 1520 SBWPD

    16.7 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.20 1,000 1.2 5 6.0 3

    U/S DS301 GX 822B 16.70 1,000 16.7 5 83.5 2

    GX722 discharge to

    DS-320 (wash water)GX 822B 20 500 10.00 5 50.0 1

    DA350 GX 822B 14.5 500 1.45 5 7.3 4

    TRAITEMENT

    4018

    OIL

    REMARK

    WATER

    From D1 + D2

    LOCATION PUMPBIOCIDE

    ORDER

    Open 2 hours the 2'' flushing line to 8'' inch oily wate

    header

  • 8/11/2019 Biocide injection schematic + recomendation

    20/54

    23,476 sbopd

    157 m3/h OIL 0 SBOPD

    1,000 sbwpd WATER 0 SBWPD

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.05 1,000 1.1 5 5.3 3

    U/S DS301 GX 822B 6.63 1,000 6.6 5 33.1 2

    GX722 discharge to

    DS-320 (wash water)GX 822B 10 500 5.00 5 25.0 1

    DA350 GX 822B 14.5 500 1.45 5 7.3 4

    TRAITEMENT

    455

    OIL

    REMARK

    WATER

    LOCATION PUMPBIOCIDE

    ORDER

    From D1 + D2

    Open 2 hours the 2'' flushing line to 8'' inch oily wate

    header

  • 8/11/2019 Biocide injection schematic + recomendation

    21/54

    23,122 sbopd

    154 m3/h OIL 0 SBOPD

    1,000 sbwpd WATER 0 SBWPD

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.05 1,000 1.1 5 5.3 3

    U/S DS301 GX 822B 6.63 1,000 6.6 5 33.1 2

    GX722 discharge to

    DS-320 (wash water)GX 822B 10 500 5.00 5 25.0 1

    DA350 GX 822B 14.5 500 1.45 5 7.3 4

    TRAITEMENT

    455

    OIL

    REMARK

    WATER

    From D1 + D2

    LOCATION PUMPBIOCIDE

    ORDER

    Open 2 hours the 2'' flushing line to 8'' inch oily wate

    header

  • 8/11/2019 Biocide injection schematic + recomendation

    22/54

    23,122 sbopd

    154 m3/h OIL 0 SBOPD

    1,000 sbwpd WATER 0 SBWPD

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.05 1,000 1.1 5 5.3 3

    U/S DS301 GX 822B 6.63 1,000 6.6 5 33.1 2

    GX722 discharge to

    DS-320 (wash water)GX 822B 10 500 5.00 5 25.0 1

    DA350 GX 822B 14.5 500 1.45 5 7.3 4

    TRAITEMENT

    4018

    OIL

    REMARK

    WATER

    LOCATION PUMPBIOCIDE

    ORDER

    From D1 + D2

  • 8/11/2019 Biocide injection schematic + recomendation

    23/54

    23,122 sbopd

    154 m3/h OIL 0 SBOPD

    1,000 sbwpd WATER 0 SBWPD

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.05 1,000 1.1 5 5.3 3

    U/S DS301 GX 822B 6.63 1,000 6.6 5 33.1 2

    GX722 discharge to

    DS-320 (wash water)GX 822B 15 500 7.50 5 37.5 1

    DA350 GX 822B 14.5 500 1.45 5 7.3 4

    TRAITEMENT

    455

    OIL

    REMARK

    WATER

    From D1 + D2

    LOCATION PUMPBIOCIDE

    ORDER

  • 8/11/2019 Biocide injection schematic + recomendation

    24/54

    25,753 sbopd

    172 m3/h OIL 0 SBOPD

    1,000 sbwpd WATER 0 SBWPD

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.05 1,000 1.1 5 5.3 3

    U/S DS301 GX 822B 6.63 1,000 6.6 5 33.1 2

    GX722 discharge to

    DS-320 (wash water)GX 822B 15 500 7.50 5 37.5 1

    DA350 GX 822B 14.5 500 1.45 5 7.3 4

    TRAITEMENT

    4018

    OIL

    REMARK

    WATER

    LOCATION PUMPBIOCIDE

    ORDER

    From D1 + D2

  • 8/11/2019 Biocide injection schematic + recomendation

    25/54

    20,291 sbopd

    135 m3/h OIL 0 SBOPD

    1,000 sbwpd WATER 0 SBWPD

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS301 GX 822B 6.63 2,000 13.3 5 66.3 2

    GX722 discharge to

    DS-320 (wash water)GX 822B 15 1,000 15.00 5 75.0 1

    DA350 GX 822B 14.5 1,000 2.90 5 14.5 3

    TRAITEMENT

    455

    OIL

    REMARK

    WATER

    From D1 + D2

    LOCATION PUMPBIOCIDE

    ORDER

    Open 2 hours the 2'' flushing line to 8'' inch oily wate

    header

  • 8/11/2019 Biocide injection schematic + recomendation

    26/54

    20,563 sbopd

    137 m3/h OIL 0 SBOPD

    1,000 sbwpd WATER 0 SBWPD

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.05 1,000 1.1 5 5.3 3

    U/S DS301 GX 822B 6.63 1,000 6.6 5 33.1 2

    GX722 discharge to

    DS-320 (wash water)GX 822B 15 500 7.50 5 37.5 1

    DA350 GX 822B 14.5 500 1.45 5 7.3 4

    TRAITEMENT

    4018

    OIL

    REMARK

    WATER

    Double concentration because was not done last w

    LOCATION PUMPBIOCIDE

    ORDER

    From D1 + D2

    Double concentration because of low water cut

    Open 2 hours the 2'' flushing line to 8'' inch oily wa

    header

  • 8/11/2019 Biocide injection schematic + recomendation

    27/54

    20,870 sbopd

    139 m3/h OIL 0 SBOPD

    1,200 sbwpd WATER 0 SBWPD

    8.0 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.05 1,000 1.1 5 5.3 3

    U/S DS301 GX 822B 7.95 1,000 8.0 5 39.8 2

    GX722 discharge to

    DS-320 (wash water)GX 822B 15 500 7.50 5 37.5 1

    DA350 GX 822B 14.5 500 1.45 5 7.3 4

    TRAITEMENT

    455

    Double concentration because of low water cut

    OIL

    REMARK

    WATER

    Double concentration because of low water cut

    From D1 + D2

    LOCATION PUMPBIOCIDE

    ORDER

    Open 2 hours the 2'' flushing line to 8'' inch oily wa

    header

  • 8/11/2019 Biocide injection schematic + recomendation

    28/54

    21,310 sbopd

    142 m3/h OIL 0 SBOPD

    1,200 sbwpd WATER 0 SBWPD

    8.0 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.05 1,000 1.1 5 5.3 3

    U/S DS301 GX 822B 7.95 1,000 8.0 5 39.8 2

    GX722 discharge to

    DS-320 (wash water)GX 822B 15 500 7.50 5 37.5 1

    DA350 GX 822B 14.5 500 1.45 5 7.3 4

    TRAITEMENT

    4018

    OIL

    REMARK

    WATER

    Double concentration because of low water cut

    LOCATION PUMPBIOCIDE

    ORDER

    From D1 + D2

    Double concentration because of low water cut

    Open 2 hours the 2'' flushing line to 8'' inch oily wa

    header

  • 8/11/2019 Biocide injection schematic + recomendation

    29/54

    21,310 sbopd

    142 m3/h OIL 0 SBOPD

    1,200 sbwpd WATER 0 SBWPD

    8.0 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.05 1,000 1.1 5 5.3 3

    U/S DS301 GX 822B 7.95 1,000 8.0 5 39.8 2

    GX722 discharge to

    DS-320 (wash water)GX 822B 40 500 20.00 5 100.0 1

    DA350 GX 822B 14.5 500 1.45 5 7.3 4

    TRAITEMENT

    455

    Double concentration because of low water cut

    OIL

    REMARK

    WATER

    Double concentration because of low water cut

    From D1 + D2

    LOCATION PUMPBIOCIDE

    ORDER

    2'' flushing line open all the time

  • 8/11/2019 Biocide injection schematic + recomendation

    30/54

    21,310 sbopd

    142 m3/h OIL 0 SBOPD

    1,200 sbwpd WATER 0 SBWPD

    8.0 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.05 1,000 1.1 5 5.3 3

    U/S DS301 GX 822B 7.95 1,000 8.0 5 39.8 2

    GX722 discharge to

    DS-320 (wash water)GX 822B 35 700 24.50 5 122.5 1

    DA350 GX 822B 14.5 500 1.45 5 7.3 4

    TRAITEMENT

    4018

    OIL

    REMARK

    WATER

    Double concentration because of low water cut

    LOCATION PUMPBIOCIDE

    ORDER

    From D1 + D2

    Double concentration because of low water cut

    2'' flushing line open all the time

  • 8/11/2019 Biocide injection schematic + recomendation

    31/54

    21,310 sbopd

    142 m3/h OIL 0 SBOPD

    1,200 sbwpd WATER 0 SBWPD

    8.0 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.05 1,000 1.1 5 5.3 3

    U/S DS301 GX 822B 7.95 1,000 8.0 5 39.8 2

    DA350 GX 822B 14.5 500 1.45 5 7.3 4

    U/S Sand filter GX822B 800 600 480.00 5 2400.0 1

    TRAITEMENT

    455

    OIL

    REMARK

    WATER

    From D1 + D2

    Double concentration because of low water cut

    It will allow to treat water injection system as well as

    water package ( via GX722)

    LOCATION PUMPBIOCIDE

    ORDER

    Double concentration because of low water cut

  • 8/11/2019 Biocide injection schematic + recomendation

    32/54

    21,429 sbopd

    143 m3/h OIL 0 SBOPD

    1,200 sbwpd WATER 0 SBWPD

    8.0 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.05 1,000 1.1 5 5.3 3

    U/S DS301 GX 822B 7.95 1,000 8.0 5 39.8 2

    DA350 GX 822B 14.5 500 1.45 5 7.3 4

    U/S Sand filter GX822B 800 700 560.00 5 2800.0 1

    TRAITEMENT

    4018

    It will allow to treat water injection system as well as

    water package ( via GX722). Please open 2'' flushline in order to reach 30 m3/h (15 m3/h wash water

    m3/h flushing line)

    LOCATION PUMPBIOCIDE

    ORDER

    OIL

    REMARK

    WATER

    From D1 + D2

  • 8/11/2019 Biocide injection schematic + recomendation

    33/54

    21,629 sbopd

    144 m3/h OIL 0 SBOPD

    1,000 sbwpd WATER 0 SBWPD

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.05 1,000 1.1 5 5.3 1

    U/S DS301 GX 822B 6.63 1,000 6.6 5 33.1 2

    DA350 GX 822B 14.5 500 1.45 5 7.3 3

    TRAITEMENT4018 AND 455

    1,000 ppm dur to low water flowrate

    1,000 ppm dur to low water flowrate

    LOCATION PUMPBIOCIDE

    ORDER

    OIL

    REMARK

    WATER

    From D1 + D2

  • 8/11/2019 Biocide injection schematic + recomendation

    34/54

    25,024 sbopd

    167 m3/h OIL 2000 SBOPD

    1,000 sbwpd WATER 80 SBWPD

    6.6 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS301 GX 822B 6.63 1,000 6.6 5 33.1 2

    DA350 GX 822B 14.5 500 7.25 1 7.25 3

    U/S Sand filter GX822B 800 500 400 5 2000 1

    TRAITEMENT

    4018

    Open 2'' flushing line discharge of GX722 in order

    reach 30 m3/h (15 m3/h wash water+15 m3/h flushline) + run continuously GX721 and GX600.

    LOCATION PUMPBIOCIDE

    ORDER

    1 hour to treat the DA-350 is enough as there is no

    1,000 ppm due to low water flowrate

    OIL

    REMARK

    WATER

    From D1 + D2

  • 8/11/2019 Biocide injection schematic + recomendation

    35/54

    50,808 sbopd

    339 m3/h OIL 25000 SBOPD

    1,500 sbwpd WATER 1000 SBWPD

    9.9 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 2

    U/S DS301 GX 822B 9.94 1,000 9.9 5 49.7 3

    DA350 GX 822B 14.5 500 7.25 1 7.25 4

    U/S Sand filter GX822B 800 500 400 5 2000 1

    TRAITEMENT

    455

    OIL

    REMARK

    WATER

    From D1 + D2

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in order to

    reach 30 m3/h (15 m3/h wash water+15 m3/h flushin

    line) + run continuously GX721 and GX600.

    LOCATION PUMPBIOCIDE

    ORDER

    1 hour to treat the DA-350 is enough as there is no

    1,000 ppm due to low water flowrate

  • 8/11/2019 Biocide injection schematic + recomendation

    36/54

    50,808 sbopd

    339 m3/h OIL 25000 SBOPD

    2,400 sbwpd WATER 1250 SBWPD

    15.9 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 15.90 1,000 15.9 5 79.5 4

    DA350 GX 822B 14.5 500 7.25 1 7.25 5

    GX722 discharge to

    DS-320 (wash

    water)

    GX 822B 30 800 24.00 5 120.0 2

    U/S Sand filter GX822B 800 500 400 5 2000 1

    TRAITEMENT

    4018

    run continuously GX721 and GX600 + Flush during o

    hours the PSV collector of the deareation tower (new

    purged line installed)

    LOCATION PUMPBIOCIDE

    ORDER

    1 hour to treat the DA-350 is enough as there is no

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in orde

    reach 30 m3/h (15 m3/h wash water+15 m3/h flus

    line) +

    1,000 ppm due to low water flowrate

    OIL

    REMARK

    WATER

    From D1 + D2

  • 8/11/2019 Biocide injection schematic + recomendation

    37/54

    52,312 sbopd

    349 m3/h OIL 25000 SBOPD

    2,400 sbwpd WATER 1250 SBWPD

    15.9 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 15.90 1,000 15.9 5 79.5 4

    DA350 GX 822B 14.5 500 7.25 1 7.25 5

    GX722 discharge to

    DS-320 (wash

    water)

    GX 822B 35 800 28.00 5 140.0 2

    U/S Sand filter GX822B 800 500 400 5 2000 1

    TRAITEMENT

    455

    OIL

    REMARK

    WATER

    From D1 + D2

    1,000 ppm due to low water flowrate

    run continuously GX721 and GX600 + Flush during o

    hours the PSV collector of the deareation tower (new

    purged line installed)

    LOCATION PUMPBIOCIDE

    ORDER

    1 hour to treat the DA-350 is enough as there is no

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in orde

    reach 35 m3/h (24 m3/h wash water+11 m3/h flus

    line) +

  • 8/11/2019 Biocide injection schematic + recomendation

    38/54

    27,312 sbopd

    182 m3/h OIL 0 SBOPD

    1,500 sbwpd WATER 0 SBWPD

    9.9 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 9.94 1,000 9.9 5 49.7 4

    DA350 GX 822B 14.5 500 7.25 1 7.25 5

    GX722 discharge to

    DS-320 (wash

    water)

    GX 822B 30 700 21.00 5 105.0 2

    U/S Sand filter GX822B 800 500 400 5 2000 1

    TRAITEMENT

    4018

    run continuously GX721 and GX600 + Flush during o

    hours the PSV collector of the deareation tower (new

    purged line installed)

    LOCATION PUMPBIOCIDE

    ORDER

    1 hour to treat the DA-350 is enough as there is no

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in orde

    reach 30 m3/h (24 m3/h wash water+6 m3/h flush

    line) +

    1,000 ppm due to low water flowrate

    OIL

    REMARK

    WATER

    From D1 + D2

  • 8/11/2019 Biocide injection schematic + recomendation

    39/54

    46,091 sbopd

    307 m3/h OIL 20000 SBOPD

    2,495 sbwpd WATER 1000 SBWPD

    16.5 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 16.53 1,000 16.5 5 82.7 4

    DA350 GX 822B 14.5 500 7.25 1 7.25 5

    GX722 discharge to

    DS-320 (wash

    water)

    GX 822B 30 800 24.00 5 120.0 2

    U/S Sand filter GX822B 800 500 400 5 2000 1

    TRAITEMENT

    455

    OIL

    REMARK

    WATER

    From D1 + D2

    1,000 ppm due to low water flowrate

    run continuously GX721 and GX600 + Flush during o

    hours the PSV collector of the deareation tower (new

    purged line installed)

    LOCATION PUMPBIOCIDE

    ORDER

    1 hour to treat the DA-350 is enough as there is no

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in orde

    reach 30 m3/h (24 m3/h wash water+6 m3/h flush

    line) +

  • 8/11/2019 Biocide injection schematic + recomendation

    40/54

    48,181 sbopd

    321 m3/h OIL 20000 SBOPD

    2,586 sbwpd WATER 1000 SBWPD

    17.1 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 17.13 1,000 17.1 5 85.7 4

    DA350 GX 822B 14.5 500 7.25 1 7.25 5

    GX722 discharge toDS-320 (wash water)

    GX 822B 25 800 20.00 5 100.0 2

    U/S Sand filter GX822 800 500 400 5 2000 1

    TRAITEMENT

    4018

    run continuously GX721 and GX600 + Flush during o

    hours the PSV collector of the deareation tower (new

    purged line installed)

    LOCATION PUMPBIOCIDE

    ORDER

    1 hour to treat the DA-350 is enough as there is no

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in order to

    reach 25 m3/h (18 m3/h wash water+7 m3/h flushing

    line)

    1,000 ppm due to low water flowrate

    OIL

    REMARK

    WATER

    From D1 + D2

  • 8/11/2019 Biocide injection schematic + recomendation

    41/54

    48,261 sbopd

    322 m3/h OIL 20000 SBOPD

    2,575 sbwpd WATER 1000 SBWPD

    17.1 m3/h

    To be treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 17.06 1,000 17.1 5 85.3 4

    DA350 GX 822B 14.5 1,000 7.25 2 14.50 5

    GX722 discharge toDS-320 (wash water)

    GX 822B 25 500 12.50 5 62.5 2

    U/S Sand filter GX821 800 500 400 5 2000 1

    TRAITEMENT

    455

    OIL

    REMARK

    WATER

    From D1 + D2

    1,000 ppm due to low water flowrate

    run continuously GX721 and GX600 + Flush during o

    hours the PSV collector of the deareation tower (new

    purged line installed)

    LOCATION PUMPBIOCIDE

    ORDER

    1,000 ppm in 2 hour for the dead leg of GX-200

    discharg

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in order to

    reach 25 m3/h (18 m3/h wash water+7 m3/h flushing

    line)

  • 8/11/2019 Biocide injection schematic + recomendation

    42/54

    45,280 sbopd

    302 m3/h OIL 16000 SBOPD

    2,196 sbwpd 4.6% WATER 640 SBWPD

    14.6 m3/h

    To be

    treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 14.55 1,000 14.6 5 72.8 4

    DA350 GX 822B 14.5 1,000 7.25 2 14.50 5

    GX722

    discharge toDS-320 (wash

    water)

    GX 822B 25 500 12.50 5 62.5 2

    U/S Sand filter GX822 800 500 400 5 2000 1

    TRAITEMENT

    4018

    run continuously GX721 and GX600 + Flush during one

    hours the PSV collector of the deareation tower (new

    purged line installed) + the 7 sand f ilters to be treated at leat

    1h30.

    LOCATION PUMPBIOCIDE

    ORDER

    1,000 ppm in 2 hour for the dead leg of GX-200 discharg

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in order to reach25 m3/h (18 m3/h wash water+7 m3/h flushing line)

    1,000 ppm due to low water flowrate

    OIL

    REMARK

    WATER

    From D1 + D2

  • 8/11/2019 Biocide injection schematic + recomendation

    43/54

    53,430 sbopd

    356 m3/h OIL 20000 SBOPD

    2,375 sbwpd 4.3% WATER 800 SBWPD

    15.7 m3/h

    To be

    treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 15.73 1,000 15.7 5 78.7 4

    DA350 GX 822B 14.5 1,000 7.25 2 14.50 5

    GX722

    discharge toDS-320 (wash

    water)

    GX 822B 25 500 12.50 5 62.5 2

    U/S Sand filter GX821 800 500 400 5 2000 1

    TRAITEMENT

    455

    OIL

    REMARK

    WATER

    From D1 + D2

    1,000 ppm due to low water flowrate

    run continuously GX721 and GX600 + Flush during one

    hours the PSV collector of the deareation tower (new

    purged line installed) + the 7 sand f ilters to be treated at leat

    1h30. On line Analyser to be isolated

    LOCATION PUMPBIOCIDE

    ORDER

    1,000 ppm in 2 hour for the dead leg of GX-200 discharg

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in order to reach25 m3/h (18 m3/h wash water+7 m3/h flushing line)

  • 8/11/2019 Biocide injection schematic + recomendation

    44/54

    53,430 sbopd

    356 m3/h OIL 20000 SBOPD

    2,375 sbwpd 4.3% WATER 800 SBWPD

    15.7 m3/h

    To be

    treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 15.73 1,000 15.7 5 78.7 4

    DA350 GX 822B 14.5 1,000 7.25 2 14.50 5

    GX722

    discharge toDS-320 (wash

    water)

    GX 822B 25 800 20.00 5 100.0 2

    U/S Sand filter GX822 800 500 400 5 2000 1

    TRAITEMENT

    4018

    run continuously GX721 and GX600 + Flush during one

    hours the PSV collector of the deareation tower (new

    purged line installed) + the 7 sand f ilters to be treated at leat

    1h30. On line Analyser to be isolated

    LOCATION PUMPBIOCIDE

    ORDER

    1,000 ppm in 2 hours for the dead leg of GX-200 discharge

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in order to reach25 m3/h (18 m3/h wash water+7 m3/h flushing line)

    1,000 ppm due to low water flowrate

    OIL

    REMARK

    WATER

    From D1 + D2

  • 8/11/2019 Biocide injection schematic + recomendation

    45/54

    53,430 sbopd

    356 m3/h OIL 20000 SBOPD

    2,375 sbwpd 4.3% WATER 800 SBWPD

    15.7 m3/h

    To be

    treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 15.73 1,000 15.7 5 78.7 4

    DA350 GX 822B 14.5 1,000 7.25 2 14.50 5

    GX722

    discharge toDS-320 (wash

    water)

    GX 822B 25 800 20.00 5 100.0 2

    U/S Sand filter GX821 800 500 400 5 2000 1

    TRAITEMENT

    455

    OIL

    REMARK

    WATER

    From D1 + D2

    1,000 ppm due to low water flowrate

    run continuously GX721 and GX600 + Flush during one

    hours the PSV collector of the deareation tower (new

    purged line installed) + the 7 sand f ilters to be treated at leat

    1h30. On line Analyser to be isolated

    LOCATION PUMPBIOCIDE

    ORDER

    1,000 ppm in 2 hours for the dead leg of GX-200 discharge

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in order to reach25 m3/h (18 m3/h wash water+7 m3/h flushing line)

  • 8/11/2019 Biocide injection schematic + recomendation

    46/54

    53,430 sbopd

    356 m3/h OIL 20000 SBOPD

    2,375 sbwpd 4.3% WATER 800 SBWPD

    15.7 m3/h

    To be

    treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 15.73 1,000 15.7 5 78.7 4

    DA350 GX 822B 14.5 1,000 7.25 2 14.50 5

    GX722

    discharge toDS-320 (wash

    water)

    GX 822B 25 800 20.00 5 100.0 2

    U/S Sand filter GX822 800 500 400 5 2000 1

    TRAITEMENT

    4018

    run continuously GX721 and GX600 + Flush during one

    hours the PSV collector of the deareation tower (new

    purged line installed) + the 7 sand f ilters to be treated at leat

    1h30. On line Analyser to be isolated

    LOCATION PUMPBIOCIDE

    ORDER

    1,000 ppm in 2 hours for the dead leg of GX-200 discharge

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in order to reach25 m3/h (18 m3/h wash water+7 m3/h flushing line)

    1,000 ppm due to low water flowrate

    OIL

    REMARK

    WATER

    From D1 + D2

  • 8/11/2019 Biocide injection schematic + recomendation

    47/54

    53,430 sbopd

    356 m3/h OIL 20000 SBOPD

    2,375 sbwpd 4.3% WATER 800 SBWPD

    15.7 m3/h

    To be

    treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 15.73 1,000 15.7 5 78.7 4

    DA350 GX 822B 14.5 1,000 7.25 2 14.50 5

    GX722

    discharge toDS-320 (wash

    water)

    GX 822B 25 800 20.00 5 100.0 2

    U/S Sand filter GX821 800 500 400 5 2000 1

    TRAITEMENT

    455

    run continuously GX721 and GX600 + Flush during one

    hours the PSV collector of the deareation tower (new

    purged line installed) + the 7 sand f ilters to be treated at leat

    1h30. On line Analyser to be isolated

    LOCATION PUMPBIOCIDE

    ORDER

    1,000 ppm in 2 hours for the dead leg of GX-200

    discharge

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in order to reach25 m3/h (18 m3/h wash water+7 m3/h flushing line)

    1,000 ppm due to low water flowrate

    OIL

    REMARK

    WATER

    From D1 + D2

  • 8/11/2019 Biocide injection schematic + recomendation

    48/54

    50,143 sbopd

    334 m3/h OIL 17000 SBOPD

    2,193 sbwpd 4.2% WATER 680 SBWPD

    14.5 m3/h

    To be

    treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 14.53 1,000 14.5 5 72.7 4

    DA350 GX 822B 14.5 1,000 7.25 2 14.50 5

    GX722

    discharge toDS-320 (wash

    water)

    GX 822B 25 800 20.00 5 100.0 2

    U/S Sand filter GX822 800 500 400 5 2000 1

    TRAITEMENT

    4018

    OIL

    REMARK

    WATER

    From D1 + D2

    1,000 ppm due to low water flowrate

    run continuously GX721 and GX600 + Flush during one

    hours the PSV collector of the deareation tower (new

    purged line installed) + the 7 sand f ilters to be treated at leat

    1h30. On line Analyser to be isolated

    LOCATION PUMPBIOCIDE

    ORDER

    1,000 ppm in 2 hours for the dead leg of GX-200 discharge

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in order to reach25 m3/h (18 m3/h wash water+7 m3/h flushing line)

  • 8/11/2019 Biocide injection schematic + recomendation

    49/54

    54,463 sbopd

    363 m3/h OIL 22000 SBOPD

    2,324 sbwpd 4.1% WATER 660 SBWPD

    15.4 m3/h

    To be

    treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 15.40 1,000 15.4 5 77.0 4

    DA350 GX 822B 14.5 1,000 7.25 2 14.50 5

    GX722

    discharge toDS-320 (wash

    water)

    GX 822B 25 500 12.50 5 62.5 2

    U/S Sand filter GX821 800 500 400 5 2000 1

    TRAITEMENT

    455

    run continuously GX721 and GX600 + the 7 sand filters to

    be treated at leat 1h30. On line Analyser to be isolated

    LOCATION PUMPBIOCIDE

    ORDER

    1,000 ppm in 2 hours for the dead leg of GX-200 discharge

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in order to reach25 m3/h (18 m3/h wash water+7 m3/h flushing line)

    1,000 ppm due to low water flowrate

    OIL

    REMARK

    WATER

    From D1 + D2

  • 8/11/2019 Biocide injection schematic + recomendation

    50/54

    59,647 sbopd

    398 m3/h OIL 24000 SBOPD

    2,377 sbwpd 3.8% WATER 720 SBWPD

    15.7 m3/h

    To be

    treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 15.75 1,000 15.7 5 78.7 4

    DA350 GX 822B 14.5 1,000 7.25 2 14.50 5

    GX722

    discharge toDS-320 (wash

    water)

    GX 822B 25 500 12.50 5 62.5 2

    U/S Sand filter GX821 800 500 400 5 2000 1

    TRAITEMENT

    4018

    OIL

    REMARK

    WATER

    From D1 + D2

    1,000 ppm due to low water flowrate

    run continuously GX721 and GX600 + the 7 sand filters to

    be treated at leat 1h30. On line Analyser to be isolated

    LOCATION PUMPBIOCIDE

    ORDER

    1,000 ppm in 2 hours for the dead leg of GX-200 discharge

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in order to reach25 m3/h (18 m3/h wash water+7 m3/h flushing line)

  • 8/11/2019 Biocide injection schematic + recomendation

    51/54

    59,776 sbopd

    399 m3/h OIL 23000 SBOPD

    2,481 sbwpd 4.0% WATER 690 SBWPD

    16.4 m3/h

    To be

    treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 16.44 1,000 16.4 5 82.2 4

    DA350 GX 822B 14.5 1,000 7.25 2 14.50 5

    GX722

    discharge toDS-320 (wash

    water)

    GX 822B 25 500 12.50 5 62.5 2

    U/S Sand filter GX821 800 500 400 5 2000 1

    TRAITEMENT

    455

    run continuously GX721 and GX600 + the 7 sand filters to

    be treated at leat 1h30. On line Analyser to be isolated

    LOCATION PUMPBIOCIDE

    ORDER

    1,000 ppm in 2 hours for the dead leg of GX-200 discharge

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in order to reach25 m3/h (18 m3/h wash water+7 m3/h flushing line)

    1,000 ppm due to low water flowrate

    OIL

    REMARK

    WATER

    From D1 + D2

  • 8/11/2019 Biocide injection schematic + recomendation

    52/54

    59,647 sbopd

    398 m3/h OIL 24000 SBOPD

    2,377 sbwpd 3.8% WATER 720 SBWPD

    15.7 m3/h

    To be

    treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 15.75 1,000 15.7 5 78.7 4

    DA350 GX 822B 14.5 1,000 7.25 2 14.50 5

    GX722

    discharge toDS-320 (wash

    water)

    GX 822B 25 800 20.00 5 100.0 2

    U/S Sand filter GX822 800 500 400 5 2000 1

    TRAITEMENT

    4018

    run continuously GX721 and GX600 + the 7 sand filters to

    be treated at leat 1h30. On line Analyser to be isolated+

    CA712 dead legs to be performed

    LOCATION PUMPBIOCIDE

    ORDER

    1,000 ppm in 2 hours for the dead leg of GX-200 discharge

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in order to reach25 m3/h (20 m3/h wash water+5 m3/h flushing line)

    1,000 ppm due to low water flowrate

    OIL

    REMARK

    WATER

    From D1 + D2

  • 8/11/2019 Biocide injection schematic + recomendation

    53/54

    36,876 sbopd

    246 m3/h OIL 0 SBOPD

    1,792 sbwpd 4.6% WATER 0 SBWPD

    11.9 m3/h

    To be

    treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 11.87 1,000 11.9 5 59.4 4

    DA350 GX 822B 14.5 1,000 7.25 2 14.50 5

    GX722

    discharge toDS-320 (wash

    water)

    GX 822B 25 800 20.00 5 100.0 2

    U/S Sand filter GX821 800 500 400 5 2000 1

    TRAITEMENT

    455

    OIL

    REMARK

    WATER

    From D1 + D2

    1,000 ppm due to low water flowrate

    run continuously GX721 and GX600 + the 7 sand filters to

    be treated at leat 1h30. On line Analyser to be isolated+

    CA712 dead legs to be performed

    LOCATION PUMPBIOCIDE

    ORDER

    1,000 ppm in 2 hours for the dead leg of GX-200 discharge

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in order to reach25 m3/h (18 m3/h wash water+7 m3/h flushing line)

  • 8/11/2019 Biocide injection schematic + recomendation

    54/54

    37,483 sbopd

    250 m3/h OIL 0 SBOPD

    1,597 sbwpd 4.1% WATER 0 SBWPD

    10.6 m3/h

    To be

    treated

    m3/h ppm l/h hours l/batch

    U/S DS300 GX 822B 1.00 1,000 1.0 5 5.0 3

    U/S DS301 GX 822B 10.58 1,000 10.6 5 52.9 4

    DA350 GX 822B 14.5 1,000 7.25 2 14.50 5

    GX722

    discharge toDS-320 (wash

    water)

    GX 822B 25 800 20.00 5 100.0 2

    U/S Sand filter GX821 800 500 400 5 2000 1

    TRAITEMENT

    4018

    run continuously GX721 and GX600 + the 7 sand filters to

    be treated at leat 1h30. On line Analyser to be isolated+

    CA712 dead legs to be performed

    LOCATION PUMPBIOCIDE

    ORDER

    1,000 ppm in 2 hours for the dead leg of GX-200 discharge

    1,000 ppm due to low water flowrate

    Open 2'' flushing line discharge of GX722 in order to reach25 m3/h (18 m3/h wash water+7 m3/h flushing line)

    1,000 ppm due to low water flowrate

    OIL

    REMARK

    WATER

    From D1 + D2