48
Wall hung, fan flue, room sealed, high efficiency gas boiler User manual and Installation instructions GARDA HE SYSTEM Models M96.28SR/P M96.32SR/P

Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Wall hung, fan flue, room sealed, high efficiency gas boiler

User manual andInstallation instructions

GARDA HE SYSTEMModels

M96.28SR/PM96.32SR/P

Page 2: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Congratulations on your choice.PARVA HE are condensing high efficiency sealed chamber fan flue gas boilers.They are fully electronically controlled and have electronic ignition.Thematerials they aremadeof and thecontrol systemsthey areequippedwithgive yousafety,a high level of comfort and energy savings to allow you to get the greatest benefit out ofindependent heating.PARVA HE allow a higher efficiency by reducing the flue gas temperature such that thewatervapour formed during the combustion is condensed out.This allows a gain of useful heat that otherwise would be lost.

Remember that...n The manual--- must be read thoroughly, so that you willbe able to use the boiler in a safe and sen-sible way;--- must be carefully kept. It may be necess-ary for reference in the future.n First lighting up must be carried out bycompetent and responsible engineer.

n The manufacturer--- disclaim all liability for any translations ofthe present manual from which incorrect in-terpretation may occur--- cannot be held responsible for non---ob-servance of instructions contained in thismanual or for the consequences of any pro-cedure not specifically described.

Using the boiler...n Before lighting the boiler you are ad-vised to have a professionally qualified per-son check that the installation of the gassupply--- is gas--- tight;--- is of the correct gauge for the flow to theboiler;--- is fitted with all the safety and control de-vices required by the current Regulations.n Ensure that--- the installer has connected the pressurerelief valve outlet to a drain pipe. The manu-facturers are not responsible for damagecaused by opening of the pressure relief

valve and consequent escape of water, if notconnected correctly to the drain.--- the installer has connected the conden-sate outlet to a suitable drain pipe.n On detecting the smell of gas--- don�t operate any electrical switches, thetelephone or any device that may producesparks;--- open the windows and doors at once tocreate a draught of air which will purge thearea;--- shut off the gas cocks;--- get the assistance of a qualified person.n Donot touch the appliancewith parts ofthe body that are wet or damp and/or barefeet.

n Do not block or modify the condensateoutlet and pipework

n In case of structural work or mainten-ance near the exhaust duct and/or fume ex-haust devices or their attachments, turn offthe appliance. On completion of the work,have a professionally qualified person checktheir efficiency.

n Repairs (under guarantee) must be car-ried out only by an approved engineer, usinggenuine spare parts. Thus do no more thanswitching off the boiler yourself (see the in-structions).

n Your boiler allows heating up of water toa temperature less than boiling point;--- must be connected to a central heatingsystem and/or a hot water supply system,compatible with its performance and output;

Page 3: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

--- can be used only for those purposes forwhich it has been specially designed;--- must not be touched by children or bythose unfamiliar with its operation;--- must not be exposed to weather condi-tions.

n During the operation it is quite normalthat the boiler produces a white plume ofcondensation vapour from the flue terminal.This is due to the high efficiency of the ap-pliance and may be particularly evident withlow outdoor temperatures.

Safe handling ofsubstances

These products are manufactured in accordancewith ISO 9000 and do not, and will not, contain anyhazardous materials or substances such as as-bestos, mercury or C.F.C.�s.The appliance packaging does not contain anysubstances,whichmaybe considered a hazard tohealth.

Combustion chamber panelsMaterial: mineral fibres

Known hazards --- Some people can suffer red-dening and itching of the skin. Fibre entry into theeye will cause foreign body irritation, which cancause severe irritation to people wearing contactlenses. Irritation to respiratory tract.Precautions --- Dust goggles will protect eyes.People with a history of skin complaints may beparticularly susceptible to irritation. High dust le-vels are only likely to arise following harsh ab-rasion. In general, normal handling and use willnot present high risk, follow good hygiene prac-tices,washhandsbefore, touching eyes, consum-ing food, drinking or using the toilet.First aid --- Medical attention must be sought fol-lowing eye contact or prolonged reddening of theskin.

Thermostat / Temperature gaugeDescription --- Sealed phial and capillary contain-ing liquid.Known hazards --- irritating to skin, eyes andthroat. Vapour is harmful. Inflammable --- do notextinguish with water.Precautions --- Do not incinerate. Avoid contactwith broken/leaking phials. Do not purposelypuncture.First aid medical attention must be sought follow-ing eyes/skin contact, wash with clean water.

Appliance category II2H3+ Gas G20 20 mbar, G30 29 mbar, G31 37 mbarCountry of destination: United Kingdom (GB) Ireland (IE)This appliance conformswith the EEC directive 90/396 and, consequently, it has the right tomakeuseof the brand nameMoreover, theapplianceconformswith theEECdirective87/308 relative to theprevention andelimina-tion of radio disturbances.The appliance is built to comply with the regulation now in force regarding gas appliance�s safety andthe European regulation now in force relative to safety of household and similar electrical appliances.Themanufacturer, in the continuous process to improve his products, reserves the right to modify thedata expressed in the present documentation at any time and without prior notice.The present documentation is an informative support and it cannot be considered as a contract to-wards third parties.

Page 4: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Boiler installation and commissioning tipsn The installation must be carried out bya qualified personwhowill be responsible forobserving the current Regulations.

Installing the boiler...n Do not forget to remove the transit capsand plugs from the boiler connections theseare fitted to every boiler.

n Keep the boiler clear of dust during in-stallation and in particular do not allow anydust or debris to enter the top of the boilerwhere the flue connection is made. It is rec-ommended that youput adust sheet over thetop of the boiler until you are ready to makethe flue connection.

n Because every boiler is fired and testedlive at the factory, a small amount of water re-mains within the boiler. It is possible for thiswater to initially cause the pump to seize. It istherefore recommended that the pump rotorbe manually turned to free its rotation beforeturning the boiler on.

n Remember to release the auto air purgebefore filling theboiler. See the instructions toidentify the location of this device.

n Do not remove the cap of the pressuretest points of the air switch (top left side of theboiler).

n You are strongly advised to flush out thesystem both cold and hot in order to removesystem and installation debris.

n It is also sensible to initially fire and com-mission the boiler before connecting any ex-ternal controls suchas a room thermostat. Bythis method if you have a subsequent prob-lem following the addition of an external con-trol you can eliminate the boiler from yourfault analysis.

n Do not forget to range rate the boiler tosuit the system requirements. This pro-cedure is covered in the commissioning sec-tion of the installation manual.

n If the boiler is fitted with a digital pro-grammer, when setting the times for auto-matic operation, remember that for every�ON� time theremustbean �OFF� time to fol-low and that on every occasion you enter atime you must also indicate which days thatyou want the boiler to follow the timed set-tings.

n Some products incorporate an anti cycl-ing time delay. It is normal when first switch-ing the boiler on for the boiler to operate onheating for a few seconds then switch off.After 3--- 4minutes has elapsed the boiler willthen re ignite and operate perfectly normally.The ignition delay cycle does not preventnormal operation of the boiler to provided.h.w.

n If you are in any doubts as to the installa-tion or operation of the boiler please read theinstruction manuals thoroughly and then ifnecessary contact Biasi UK for advice andassistance.

Please remember that if you are in any doubt about the installation of this product you can contact ourTechnical Helpline on tel. 0121 506 1350

Page 5: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

TABLE OF CONTENTS

1

1 Appliance description 2. . . . . . . . . .1.1 Overview 2. . . . . . . . . . . . . . . . . . . . . .1.2 Control panel 2. . . . . . . . . . . . . . . . . .1.3 Isolation valves 2. . . . . . . . . . . . . . . . .1.4 Technical data 2. . . . . . . . . . . . . . . . .1.5 Operation lights 3. . . . . . . . . . . . . . . .2 Instructions for use 4. . . . . . . . . . . .2.1 Warnings 4. . . . . . . . . . . . . . . . . . . . . .2.2 Refilling procedure 4. . . . . . . . . . . . . .2.3 Ignition 5. . . . . . . . . . . . . . . . . . . . . . . .

2.4 C.h. circuit temperature 5. . . . . . . . . .2.5 Extinguishing 6. . . . . . . . . . . . . . . . . .

3 Useful advice 7. . . . . . . . . . . . . . . . .3.1 Central heating 7. . . . . . . . . . . . . . . . .3.2 Frost protection 7. . . . . . . . . . . . . . . .3.3 Condensate drain 7. . . . . . . . . . . . . .3.4 Periodic maintenance 7. . . . . . . . . . .3.5 External cleaning 7. . . . . . . . . . . . . . .3.6 Operational faults 7. . . . . . . . . . . . . . .

4 Technical information 9. . . . . . . . . .4.1 Overview 9. . . . . . . . . . . . . . . . . . . . . .4.2 Main diagram 10. . . . . . . . . . . . . . . . . .4.3 Hydraulic specifications 11. . . . . . . . .4.4 Expansion vessel 11. . . . . . . . . . . . . . .4.5 Technical data mod. M96.28SR/... 12.4.6 Technical data mod. M96.32SR/... 14.

5 General requirements 16. . . . . . . . . .5.1 Related documents 16. . . . . . . . . . . . .5.2 Location of appliance 16. . . . . . . . . . .5.3 Flue system 16. . . . . . . . . . . . . . . . . . . .5.4 Gas supply 17. . . . . . . . . . . . . . . . . . . .5.5 Air supply 17. . . . . . . . . . . . . . . . . . . . .5.6 Ventilation 17. . . . . . . . . . . . . . . . . . . . .5.7 Condensate drain 17. . . . . . . . . . . . . .5.8 Water circulation (c.h.) 18. . . . . . . . . . .5.9 Water treatment 19. . . . . . . . . . . . . . . .5.10 Electrical supply 19. . . . . . . . . . . . . . . .

6 Installation 20. . . . . . . . . . . . . . . . . . . .6.1 Warnings 20. . . . . . . . . . . . . . . . . . . . . .6.2 Precautions for installation 20. . . . . . .6.3 Installing the bracket 20. . . . . . . . . . . .

6.4 Overall dimensions 21. . . . . . . . . . . . .6.5 Joints 21. . . . . . . . . . . . . . . . . . . . . . . . .6.6 Mounting the boiler 21. . . . . . . . . . . . .6.7 Fitting the flue system 22. . . . . . . . . . .6.8 Choice of flue 22. . . . . . . . . . . . . . . . . .6.9 Electrical connections 24. . . . . . . . . . .6.10 External frost protection 26. . . . . . . . .6.11 Connecting a system boiler

to a cylinder 26. . . . . . . . . . . . . . . . . . .

7 Commissioning 30. . . . . . . . . . . . . . .7.1 Electrical installation 30. . . . . . . . . . . .7.2 Gas supply installation 30. . . . . . . . . .7.3 Initial filling of the system 30. . . . . . . .7.4 Condensate pipe and traps 31. . . . . .7.5 Lighting the boiler 31. . . . . . . . . . . . . .7.6 Checking the gas pressure

at the burner 31. . . . . . . . . . . . . . . . . . .7.7 Checking the burner ignition 32. . . . .7.8 Adjustment of useful c.h. output 33. .7.9 Checking the ignition device 35. . . . .7.10 Checking the flue system 35. . . . . . . .7.11 Checking the condensate drain pipe 357.12 Instructing the user 35. . . . . . . . . . . . .

8 Gas conversion 36. . . . . . . . . . . . . . .8.1 Warnings 36. . . . . . . . . . . . . . . . . . . . . .8.2 Procedures 36. . . . . . . . . . . . . . . . . . . .

9 Maintenance 38. . . . . . . . . . . . . . . . . .9.1 Warnings 38. . . . . . . . . . . . . . . . . . . . . .9.2 Dismantling the external panels 38. . .9.3 Combustion analysis check 38. . . . . .

9.4 Cleaning the primary heat exchanger 389.5 Checking the pressurisation

in the expansion vessel 39. . . . . . . . . .9.6 Cleaning the burner 39. . . . . . . . . . . . .9.7 Checking the flue 39. . . . . . . . . . . . . . .9.8 Drain pipe inspection 39. . . . . . . . . . . .9.9 Visual inspection of appliance 39. . . .9.10 Gas pressures and tightness 39. . . . .

USE

INSTALLATION

MAINTENANCE

Page 6: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

1 APPLIANCE DESCRIPTION

2

1.1 Overview

2

1

3Fig. 1.1

1 Case front panel2 Control panel3 Control panel cover

1.2 Control panel4 C.h. circuit temperature and pressure gauge5 Lock---out signal lamp6 Lockout reset button7 Function selector and c.h. temp. control knob8 Service knob9 Appliance operation lights

The service knob 8 is useless for the normal oper-ation of the boiler.It must be used only by a qualified person duringcommissioning and servicing.

1.3 Isolation valves

12 1113 10Fig. 1.2 (bottom view of the boiler)

10 Condensate drain pipe11 C.h. return valve12 Gas inlet valve13 C.h. flow valve

1.4 Technical dataFor detailed technical data see sections 4.5 or 4.6of this manual.

9 78 6 5 4Fig. 1.3

USE

Page 7: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Appliance description

3

1.5 Operation lightsThree lights (9 in Fig. 1.3) give detailed indicationregarding the operation of the boiler.The following table gives the relationship betweeneach of the possible light combinations and theirmeaning.

A short pulse every 4seconds:stand---by conditionFunction selector inposition.Anti--- freeze system active1 second pulse every 2seconds: normallyoperating boiler. Functionselector in position

C.h. operation

Frost protect operation

Faulty c.h. temperatureprobe NTCFaulty flue temperatureprobe NTCFaulty primary circuit(no water or absence offlow)

Faulty air pressure switch

Lack of burner ignition (noignition signal from the fullseqence ignition device)

Safety thermostat lock out

Flue temperature probeNTC lock outLack of power supply orfauly electr. control p.c.b.

Lamp OFF

Lamp ON

Flashing lamp, alone or simultaneouslywith an other lamp.

Flashing lamp, alternate with anotherlamp.

USE

Page 8: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

2 INSTRUCTIONS FOR USE

4

2.1 WarningsOur Company supports the Benchmark in-itiative. The Benchmark Log Book is lo-cated at the back of this manual and shouldbe completed by the Installing/Commiss-sioning Engineer and handed over to theUser for future reference by other visitingEngineers. Also included is the Service In-terval Record card that should be com-pleted by the Service Engineer followingthe annual service maintenance of theboiler and system.

All CORGI Registered Installers carry aCORGI ID card, and have a registrationnumber. Both should be recorded in yourBenchmark Log Book. You can check yourinstaller is registered by calling CORGI di-rect on 01256 372300.In order to guarantee safety and correct oper-ation, it is essential that all the tests are carriedout by a competent and responsible serviceengineer before lighting up the boiler.The tests are described in the installation in-structions in section 7 commissioning.Ensure that the c.h. circuit is regularly filledwith water (even if the boiler is only used ford.h.w. supply) checking that the pressure indi-cated on the temperature and pressure gauge4 is not lower than that shown in Fig. 2.2.If the pressure reading on the pressure gaugeisbelow that shown in Fig. 2.2, then thesystemwill require toppingup.A filling loop isnormallyprovided by the installer for this purpose.

If you are in any doubt regarding this pro-cedure you are advised to contact your In-staller or an Approved Engineer.This appliance is provided with a built in anti---freeze system that operates the boiler whenthe temperature is below 5 ûCTherefore, when the boiler is not lit or used incold weather, with consequent risk of freezingdonot switch off the boiler at the fused spurisolation switch or close the gas inlet cock.When you do not expect to use the boiler for along period and the boiler is not to be used forfrost protection then follow the instructionsgiven in section 2.5 on page 6.

2.2 Refilling procedure1 Isolate the boiler from the electrical supply atthe fused spur. Reconnect the filling loop asdemonstrated in Fig. 2.1.

Temporaryconnection

Control valve

Control valve

Double check valve

Supply pipe(cold water inlet)

C.h. return pipe

Fig. 2.1

2 Open the valves of the filling loop and watchthe gauge until it reaches normal filling pres-sure as shown in Fig. 2.2.

4

Normal fillingpressure

Fig. 2.2

3 Close the valves and remove the filling loop.

If you experience any difficulty with the oper-ation of the boiler, switch off the boiler immedi-ately at the fused spur isolation switch andcontact your Installer or an approved ServiceEngineerAir introduced into the boiler during this filling pro-cess will vent through the automatic air purgerfitted to the boiler. You may also find it necessaryto vent air from your radiator circuit using yourradiator key, however be aware that excessiveventing will cause the pressure in the system todrop.Alwaysensure that thepressuregauge isset at therequired pressure.

USE

Page 9: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Instructions for use

5

2.3 Ignition1 Check that the valves located in the lower partof the boiler are open (Fig. 2.3).

Open positionFig. 2.3

2 Turn on the electricity supply to the boiler,switching on the fused spur isolation switch.The appliance operation light 9 (Fig. 2.4) willflash every 4 seconds (stand---by condition).

3 To operate the boiler, position the function se-lector 7 as in Fig. 2.4.The appliance operation light 9 will flash every2 seconds (operating boiler).

79

Fig. 2.4

2.4 C.h. circuit temperatureThe output temperature of c.h. water is adjustablefrom a minimum of about 38°C to a maximum ofabout 85°C (Fig. 2.5), by turning the function se-lector (7).Adjustment of c.h. output on the boiler is auto-matic. The greatest output pre---set in the factorycan, however, be reduced in level according toactual system requirements.

Such adjustments must be carried out by a quali-fied person; therefore we advise you to contactyour installer or Service Agent.Adjustment of the boiler temperature alters thegas flow at the burner according to the thermalde-mand in the system. So it isusual to see theburnerlit at the minimum level for more or less longperiods.

Minimum

Maximum

Fig. 2.5

AdjustmentIn order to achieve optimal settings for economyand comfort, we recommend adjusting the oper-ating temperature of the c.h. water according tothe outside temperature, positioning the knob asfollows:

Lower than---5 ûC

From 5 to 15 ûC Between---5 and +5 ûC

Fig. 2.6

Your qualified installer will be able to recommendthe most suitable adjustment for your system.The temperature and pressure gauge (4, Fig. 1.3on page 2) will allow you to check that the set tem-perature is obtained.

USE

Page 10: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Instructions for use

6

2.5 Extinguishing79

Fig. 2.7

Whenyoudonot expect to use the boiler for a longperiod:1 Switch off the electricity supply to the boiler, bymeans of the fused spur isolation switch;

2 Shut off the gas supply cock 12 and the valvesfor the water circuit fitted under the boiler(Fig. 2.8).

3 Empty the water circuit, if necessary, as shownin the installation instructions in the sectionmaintenance.

Closed position12

Fig. 2.8

USE

Page 11: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

3 USEFUL ADVICE

7

3.1 Central heatingFor reasonably economical service install a roomthermostat.Never shut off the radiator in the area where theroom thermostat is installed.If a radiator (or a convector) does not heat up,check that no air is present in it and that its valveis open.If the ambient temperature is too high, do not alterthe radiator valves. Reduce the central heatingtemperature instead by means of the room ther-mostat and the function selector (7 in Fig. 3.1).Fig. 3.1

3.2 Frost protectionThis appliance is provided with a built in anti---freeze system that operates the boiler when thetemperature is below 5 ûCTherefore, when the boiler is not lit and used incold weather, with consequent risk of freezing donot switch off the boiler at the fused spur isola-tion switch or close the gas inlet cock.

3.3 Condensate drainThe condensate drain must not be modified orblocked.Blockage of the condensate drain, caused by de-bris or freezing, can cause automatic shutdown ofthe boiler.If freezing is suspected and the pipe run isaccess-ible an attempt may be made to free the obstruc-tion by pouring hot water over the exposed pipean cleaning any blockage from the end of thepipe. If this fails to remedy the problem the assist-ance of a CORGI registered installer or in IE acom-petent person should be sought.

3.4 Periodic maintenanceFor efficient and continuous operation of theboiler, it is advisable to arrange maintenance andcleaning by an Authorised Service Centre En-gineer, at least once a year.During the service, the most important compo-nents of the boiler will be inspected and cleaned.This service can be part of a maintenance con-tract.In particular, you are advised to have the followingchecks carried out:

--- primary heat exchanger;--- burner;--- exhaust fume duct and flue;--- filling up of the central heating circuit;--- bleeding of air from thecentral heating system;--- general check of the appliance�s operation.

3.5 External cleaningBefore carrying out any cleaning, disconnect theappliance from the electrical mains, using thefused spur isolation switch fitted adjacent to theappliance.To clean the external panels, use a cloth soaked insoapy water. Do not use solvents, abrasive powd-ers or sponges.Do not carry out cleaning of the appliance and/orits parts with readily flammable substances (forexample petrol, alcohols, naphtha, etc.).

3.6 Operational faults

If the lock---out signal lamp comes onthis indicates that the safety lock---out 5 (Fig. 3.2)has stopped the boilerTo re---start the boiler, it is necessary to press theboiler reset button 6 (Fig. 3.2).Fig. 3.2

For the first lighting up and followingmaintenanceprocedures for the gas supply, it may be necess-ary to repeat the resetting operation several timesso as to remove the air present in the pipework.Safety lock---out may occour even in case of anblockage of the condensate drainage (e.g.plugged drain pipe).It is advisable to check the condensate drainagepipe and traps for cleaness.In case of persistent lock---out call a competentand responsible service engineer.

If noises due to air bubbles are heard duringoperation...you should check that the pressure on the tem-perature and pressure gauge (Fig. 2.2 on page 4)is not below the correct setting.If required, top up the system correctly, as de-scribed in the section 2.2 of this manual.Bleed any air present in the radiators, if necessary.

USE

Page 12: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Useful advice

8

If the pressure on the temperature and pres-sure gauge (4 on page 2) has gone down...it is necessary to top up the appliance with wateragain, so as to raise the pressure to an adequatelevel as described in thesection 2.2of thismanual.If topping up with water has to be done very fre-quently, have the system checked for leaks.

If water comes out of the pressure relief valveCheck on the temperature and pressure gauge (4on page 2) that the pressure in the central heatingcircuit is not close to 3 bars. In this case, tempera-ture rise in the circuit can cause the pressure reliefvalve to open.So that this does not happen and to decrease thepressure to a normal value, it is advisable to vent

some of the water in the appliance through thebleed valves present in the radiators.

If water should occasionally leak from theboiler...shut off the valves positioned under the boiler(Fig. 2.8onpage6) and call an AuthorisedServiceCentre Engineer.

If the left appliance operation light 9 (Fig. 3.3)flashes very quickly the boiler is detecting afault.Fig. 3.3

In this case or in case of problems other thanthose mentioned here, switch off the boiler, asdescribed in section 2.5 on page 6 and call acompetent and responsible service engineer.

USE

Page 13: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

4 TECHNICAL INFORMATION

9

4.1 Overview

15

26

25

23

24

20

22

16

31

21

27

17

3028

1819

14

29 32

Fig. 4.1

10 Condensate drain pipe11 C.h. return valve12 Gas inlet valve13 C.h. flow valve14 Condensate trap15 Main circuit drain valve16 Automatic air purger valve17 Pump18 Pump vent plug19 Modulation gas valve20 Primary circuit flow switch21 C.h. temperature probe NTC22 Flame---detecting electrode23 Ignition electrodes24 Burner25 Combustion chamber26 Primary heat exchanger27 Fan28 Air switch pressure test points29 Flue temperature probe NTC30 Air pressure switch31 Condensing heat exchanger32 Safety thermostat33 C.h. pressure relief valve34 Modulation operator35 Gas valve outlet pressure test point36 Gas valve inlet pressure test point37 C.h. expansion tank38 By---pass valve39 Venturi device40 Flue outlet pipe41 Air intake pipe

INSTALLATION

Page 14: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Technical information

10

4.2 Main diagram

3930

41

40

20

26

23

35

17

33

19

36

16

38

11 1312

37

27

22

21

34

32

24

15

31

14

10

29

Fig. 4.2

INSTALLATION

Page 15: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Technical information

11

4.3 Hydraulic specifications

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0 200 400 600 800 1000 1200 1400

0

10

20

30

40

kPa bar

l/h

60

50

Fig. 4.3

The hydraulic specifications in Fig. 4.3 representthe pressure (available head for the central heat-ing system) as a function of the flow rate.The load loss due to the boiler has already beensubtracted.

Output with thermostat cocks shut offThe boiler is fitted with an automatic by---passvalve (38 on page 9), which protects the primaryheat exchanger.In case of excessive reduction or total blockage ofwater circulation in the central heating systemowing to closure of the thermostatic valves or sys-

tem component cocks, the by---pass valve ensur-es a minimum flow of water through the primaryheat exchanger.

4.4 Expansion vessel

Note: this boiler is designed for operation onlyin a sealed central heating systemThe height difference between the pressure reliefvalve and the highest point in the system may be7m at most.For greater differences, increase the pre--- loadpressure in the expansion vessel (37 on page 9)and the system, when cold, by 0.1 bar for eachadditional 1m.

Capacity l 6,0

Pre--- load pressure kPabar

1001,0

Maximum volume of waterin the system *

l 132

Tab. 4.1

* Where conditions are:--- Average maximum temperature of the systemis 80°C

--- Initial temperature when filling up the system is10°C

For systems with volumes greater than 132 l, anadditional expansion vessel must be provided.

INSTALLATION

Page 16: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Technical information

12

4.5 Technical data mod.M96.28SR/...

Heat input (A)

Nominal kWBTU/h

29,098 942

Minimum kWBTU/h

13,044 353

Useful output G20

Maximum kWBTU/h

28,396 488

Minimum kWBTU/h

12,141 284

Maximum condensing kWBTU/h

30,7104 602

Minimum condensing kWBTU/h

13,244 965

Useful output G30 G31Maximum kW

BTU/h27,493 599

Minimum kWBTU/h

12,141 284

Maximum condensing kWBTU/h

30,7104 602

Minimum condensing kWBTU/h

12,944 016

Central heating

Maximum flow temp. ûC 85

Minimum flow temp. ûC 38

Minimum return temp. ûC 30

Maximum pressure kPabar

2502,5

Minimum pressure kPabar

300,3

Available head(in 1000 l/h)

kPabar

250,25

Seasonal efficiencyG20 (B)

band%

B87,7

Seasonal efficiencyG30 G31 (B)

band%

B87,1

Gas supply pressuresGas Natural

G20ButaneG30

PropaneG31

Norm. Pambar

2 00020

2 90029

3 70037

Max Pambar

2 50025

3 50035

4 50045

Min. Pambar

1 70017

2 00020

2 50025

1 mbar approximately equals 10 mm H2O

Gas pressures at the burner

Gas NaturalG20

ButaneG30

PropaneG31

Max. Pambar

100010,0

280028,0

360036,0

Min. Pambar

1601,6

5505,5

7707,7

Ignition Pambar

6006,0

120012,0

130013,0

1 mbar approximately equals 10 mm H2O

(A) referred to the net calorific value at 15 ûC and 1013,25 mbarG 20 = 34,02 MJ/m3, G 30 = 45,6 MJ/kg, G 31 = 46,4 MJ/kg(B)The value is used in the UK Government�s Standard Assessment Procedure (SAP) for energy ratingof dwellings. The test data from which it has been calculated have been certified by a notified body.

INSTALLATION

Page 17: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Technical information

13

Gas rate

Gas NaturalG20m3/h

ButaneG30kg/h

PropaneG31kg/h

Max. 3,07 2,29 2,25

Min. 1,28 1,03 1,01

InjectorsNatural G20 130

Butane G30 75

Propane G31 75

Electrical DataVoltage V~ 230

Frequency Hz 50

Power consumption W 150

Protection degree IPX4D

External fuse rating A 3

Internal fuse rating A F1---F2 3,15 AF

Flue designFlue pipe diameter

Coaxial mm 60/100

Twin split pipes mm 80

Roof mm 80/125

Nominal heat flow rate(A)(C)

kW 29,0

Exhaust temperature (C) ûC 90

Mass flow rate (C) g/s 21,1

Flue gas figures

Nominal heat input (A)(C) kW 29,0

CO2 content % 6,8

O2 content % 10,7

CO content ppm 75

Exhaust temperature (C) ûC 90

Other specificationsHeight mm 803

Width mm 400

Depth mm 350

Weight (dry) kg 44,5

Water volume in the boiler(up to 1 bar)

l (kg) 2,2

(C) Values refer to tests with a 1 m chimney working at the nominal heat input

INSTALLATION

Page 18: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Technical information

14

4.6 Technical data mod.M96.32SR/...

Heat input (A)

Nominal kWBTU/h

33,3113 624

Minimum kWBTU/h

15,753 570

Useful output G20

Maximum kWBTU/h

32,2109 870

Minimum kWBTU/h

15,051 182

Maximum condensing kWBTU/h

34,4117 377

Minimum condensing kWBTU/h

15,653 229

Useful output G30 G31Maximum kW

BTU/h32,2

109 870

Minimum kWBTU/h

15,051 182

Maximum condensing kWBTU/h

34,4117 377

Minimum condensing kWBTU/h

15,653 229

Central heating

Maximum flow temp. ûC 85

Minimum flow temp. ûC 38

Minimum return temp. ûC 30

Maximum pressure kPabar

2502,5

Minimum pressure kPabar

300,3

Available head(in 1000 l/h)

kPabar

250,25

Seasonal efficiencyG20 (B)

band%

B86,8

Seasonal efficiencyG30 G31 (B)

band%

B88,8

Gas supply pressuresGas Natural

G20ButaneG30

PropaneG31

Norm. Pambar

2 00020

2 90029

3 70037

Max Pambar

2 50025

3 50035

4 50045

Min. Pambar

1 70017

2 00020

2 50025

1 mbar approximately equals 10 mm H2O

Gas pressures at the burner

Gas NaturalG20

ButaneG30

PropaneG31

Max. Pambar

130013,0

272027,2

360036,0

Min. Pambar

2702,7

5505,5

7307,3

Ignition Pambar

6006,0

120012,0

130013,0

1 mbar approximately equals 10 mm H2O

(A) referred to the net calorific value at 15 ûC and 1013,25 mbarG 20 = 34,02 MJ/m3, G 30 = 45,6 MJ/kg, G 31 = 46,4 MJ/kg(B)The value is used in the UK Government�s Standard Assessment Procedure (SAP) for energy ratingof dwellings. The test data from which it has been calculated have been certified by a notified body.

INSTALLATION

Page 19: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Technical information

15

Gas rate

Gas NaturalG20m3/h

ButaneG30kg/h

PropaneG31kg/h

Max. 3,53 2,63 2,59

Min. 1,59 1,19 1,17

InjectorsNatural G20 130

Butane G30 80

Propane G31 80

Electrical DataVoltage V~ 230

Frequency Hz 50

Power consumption W 150

Protection degree IPX4D

External fuse rating A 3

Internal fuse rating A F1---F2 3,15 AF

Flue designFlue pipe diameter

Coaxial mm 60/100

Twin split pipes mm 80

Roof mm 80/125

Nominal heat flow rate(A)(C)

kW 33,3

Exhaust temperature (C) ûC 90

Mass flow rate (C) g/s 21,5

Flue gas figures

Nominal heat input (A)(C) kW 33,3

CO2 content % 7,0

O2 content % 9,4

CO content ppm 100

Exhaust temperature (C) ûC 90

Other specificationsHeight mm 803

Width mm 400

Depth mm 350

Weight (dry) kg 50,0

Water volume in the boiler(up to 1 bar)

l (kg) 2,2

(C) Values refer to tests with a 1 m chimney working at the nominal heat input

INSTALLATION

Page 20: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

5 GENERAL REQUIREMENTS

rev 17 09 9316

Our Company supports the Benchmark initiat-ive. The Benchmark Log Book is located at theback of this manual and should be completedby the Installing/Commisssioning Engineerand handed over to the User for future refer-ence by other visiting Engineers. Also in-cluded is the Service Interval Record card thatshould be completed by the Service Engineerfollowing the annual service maintenance ofthe boiler and system.

For Ireland (IE), it is necessary to complete a�Declaration of Conformity� to indicate com-pliance to I.S.813.2002.

This appliance must be installed by a compet-ent person in accordance with the Gas Safety(installation & Use) Regulations.

5.1 Related documentsThe installation of this appliance must be in ac-cordance with the relevant requirements of thecurrent Gas Safety (Installation & Use) Regula-tions, the Local Building Regulations, the currentI.E.E. Wiring Regulations, the Regulations andby--- laws of the local water undertaking, and inScotland, in accordance with the Building Stan-dards (Scotland) Regulation. Health and safetydocument nû 635 �Electricity at work regs.�.It should also be in accordance with the BritishStandard Codes of Practice:In Ireland (IE). The installation must be carried outby a Competent Person and installed in accord-ance with the current edition of I.S.813.2002 �Do-mestic Gas Installations� the current BuildingRegulations and reference should be made to thecurrent ETCI rules for electrical installations.

5.2 Location of applianceThe appliance may be installed in any room or in-ternal space, although particular attention isdrawn to the requirementsof thecurrent I.E.E.Wir-ing Regulations, and in Scotland, the electricalprovisions of the Building Regulations applicablein Scotland, with respect to the installation of thecombined appliance in a room containing a bathor shower.

For Ireland (IE), reference should be made to thecurrent edition of I.S.813.2002 and the currentETCI rules for electrical installations.

Where a room---sealed appliance is installed ina roomcontainingabath or shower, anyelectri-cal switch or appliance control, utilisingmainselectricity should be so situated that it cannotbe touched by a person using the bath orshower.The location must permit the provision of an ad-equate flue and termination.For unusual locations special procedures may benecessary and BS 6798 gives detailed guidanceon this aspect.A compartment used to enclose the appliancemust be designed specifically for this purpose.This appliance is not suitable for external installa-tion.

5.3 Flue systemTheprovision for satisfactory flue terminationmustbe made as described in BS 5440 part 1.For Ireland (IE), refer to I.S.813.2002.Theappliancemustbe installed so that the flue ter-minal is exposed to external air.It must not be installed so that the terminal dis-charges into an other room or space as an out-house or lean--- to. It is important that the positionof the terminal allows a free passage of air acrossat all times.The terminal should be located with due regard forthe damage or discoloration that might occur tobuilding products in the vicinity.In cold and/or humid weather water vapour maycondense on leaving the flue terminal; the effectofsuch �steaming� must be considered.Pluming may easily occur at the terminal. Wherepossible, terminal position which could cause anuisance should be avoided.

INSTALLATION

Page 21: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

General requirements

rev 17 09 9317

The minimum acceptable spacing from the ter-minal to obstructions and ventilation openings arespecified in Fig. 5.1.

A

BC

E

F

G

I

JK L

MN

H

I

O

P

QD

Fig. 5.1Terminal position mm

A Directly below a window or other opening 300. . . .B Below gutters, soil pipes or drain pipes 75. . . . . .C Below eaves 200. . . . . . . . . . . . . . . . . . . . . . . . . . . . .D Below balconies* 600. . . . . . . . . . . . . . . . . . . . . . . . .E Below car port roof NO. . . . . . . . . . . . . . . . . . . . . . . .F From vertical drain pipes and soil pipes 150. . . . .G From internal corners** 450. . . . . . . . . . . . . . . . . . .H From external corners 300. . . . . . . . . . . . . . . . . . . .I Above ground or balcony level 300. . . . . . . . . . . . . .J From a surface facing a terminal 600. . . . . . . . . . . .K From a terminal facing a terminal 1 200. . . . . . . . . .L From an opening in the car port.

(e.g. door, window) into dwelling NO. . . . . . . . . . .M Vertically from a terminal in the same wall 1 500.N Horizontally from a terminal in the same wall 300. .O Above the roof pitch with roof slope less.

than or equal to 30û 350. . . . . . . . . . . . . . . . . . . . . .Above the roof pitch with roof slopemore than 30û 600. . . . . . . . . . . . . . . . . . . . . . . . . . .

P From wall face 600. . . . . . . . . . . . . . . . . . . . . . . . . . .Q From, above or to side of an opening 300. . . . . . . .

*Wherever practicable to do so, the flue should be ex-tended beyond the perimeter of the balcony** Consideration should be given to adding protectionagainst condensate to the adjacent structure

5.4 Gas supplyTheGasmeter is connected to the service pipe bythe local gas region or a local gas region contrac-tor.If the gas supply for the boiler serves otherappliances ensure that an adequate supply is

available both to the boiler and the otherappliance when they are in use at the same time.Pipework must be of adequate size. Pipes of asmaller size than the boiler inlet connection shouldnot be used.Installation pipes should be fitted in accordancewith BS 6891 and the complete installation shouldbe tested for tightness.For Ireland (IE), refer to I.S.813.2002.

5.5 Air supplyThe room in which the boiler is installed does notrequire a purpose provided air vent.

5.6 VentilationIf installed in a cupboard or compartment, it is notnecessary to provide additional ventilation forcooling for this particular product. However con-sideration must be given to clearance require-ments for maintenance (see section 6.2) andunder nocircumstancesmust stored articles beal-lowed to come into contact with the boiler or fluepipe.

5.7 Condensate drainEnsure that the condensate discharge complieswith the national or local regulations in force.The condensate pipemust be fitted in accordancewith Building Regulations.Drainpipe material should be resistant to acid asthe condensate is slightly acid with a pH less than6.5.The boiler includes a trap (14 on page 9) that pre-vents the combustion products entering the drain,however an additional trapwith a seal of at least 75mmand an air break between the traps is required(Fig. 5.2).The length of the condensate pipe should be keptat minimum.To avoid condensate being trapped:--- thedrainpipeshould be runwith a fall of at least2.5û (45 mm/m) away from the boiler;

--- the number of bends and joints should be keptat minimum;

INSTALLATION

Page 22: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

General requirements

rev 17 09 9318

--- the drainpipe should be adequately fixed topevent pipe sagging.

If a part of the drainpipe runs externally this partshould be kept as short as possible and protectedto reduce the risk of freezing.

Condensate drain

Fig. 5.2

5.8 Water circulation (c.h.)Detailed recommendations are given in BS 6798and BS 5449; the following notes are given forgeneral guidance.For Ireland (IE), refer to I.S.813.2002.

PipeworkCopper tubing to BSEN 1057 is recommended forwater pipes. Jointing should be either with capil-lary soldered or with compression fittings.Where possible pipes should have a gradient toensure air is carried naturally to air release pointsand water flows naturally to drain taps.The appliance has a built--- in automatic air releasevalve, it should be ensured as far as possible thatthe appliance heat exchanger is not a natural col-lecting point for air.Except where providing useful heat, pipes shouldbe insulated to prevent heat loss and to avoidfreezing.Particular attention should be paid to pipes pas-sing through ventilated spaces in roofs and underfloors.

By---passThe appliance includes an automatic by---passvalve which protects the main heat exchanger incase of reduced or interrupted water circulationthrough the heating system due to the closing ofthermostatic valvesor cock--- typevalveswithin thesystem.The by---pass is calibrated to assure a minimumflow of 500---600 lts/hr through the main heat ex-changer.

If you are installing a system that includes thermo-static radiator valves (TRV) and/or small bore(8---10 mm) it may be necessary to fit an externalby---pass to facilitate correct operation of theboiler.

Air release pointsThesemust be fitted at all high pointswhere airwillnatural collect and must be sited to facilitate com-plete filling of the system.

Expansion vesselThe appliance has an integral sealed expansionvessel to accommodate the increase of water vol-ume when the system is heated.Refer to Tab. 4.1 on page 11 for its technical data.If the heating circuit has an unusually high watercontent, calculate the total expansion and add anadditional sealed expansion vessel with adequatecapacity.

Mains water feed: central heatingThere must be no direct connection to the mainswater supply even through a non return valve,without the approval of the Local Water Authority.

FillingA method for initially filling the system and replac-ing water lost during servicing must be providedand itmust comply with local water authority regu-lations.The correct method is shown in Fig. 5.3.

The temporary connection must be removedimmediately after filling.

Temporaryconnection

Control valve

Control valve

Double check valve

Supply pipe(cold water inlet)

C.h. return pipe

Fig. 5.3

The installer should ensure that no leaks existeither inside the boiler or on the system as fre-quent filling of the system could cause prematurescaling of the heat exchanger.For Ireland (IE), refer to I.S.813.2002.

INSTALLATION

Page 23: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

General requirements

rev 17 09 9319

5.9 Water treatment

Central heating circuitWhere a new boiler is fitted to a new system witheither plastic or copper pipes, it is important thesystem is fully flushed, on completion, to ensureflux residues, swarfs, oils and other installation de-bris is removed.Where a new boiler is fitted to an existing system,it is important the debris from the existing systemis fully removed in order to ensure the efficiency ofthe new appliance is maintained.Details on flushing procedure are given in the sec-tion 7.3 of this manual.

5.10 Electrical supply

Warning, this appliance must be earthed.External wiring to the appliance must be carriedout by a competent person and be in accordance

with the current I.E.E. Regulations and any localregulations which apply.Reference should be made tu the current ETCIrules for electrical installations.For Ireland (IE), refer to I.S.813.2002.The boiler is supplied for connection to a 230 V~50 Hz supply. The supply must be fused at 3A.Themethod of connection to the electricity supplymust facilitate complete electrical isolation of theappliance by the use of a fused double pole isola-tor having a contact separation of at least 3 mmbetween poles or alternatively, by the use of a 3Afused three pin plug and unswitched shutteredsocket outlet both complying with BS 1363.The point of connection to the electricity supplymust be readily accessible and adjacent to theappliance except were the appliance is installed ina bathroom this must then be sited outside thebathroom.

INSTALLATION

Page 24: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

6 INSTALLATION

20

6.1 WarningsThe use of gas appliances is subject tostatutory control; it is essential to observethe current regulations and laws in force(see also chapter 5).The appliance must discharge combustionproducts directly outside or into a suitable ex-haust duct designed for this purpose.Combustion products must be dischargedusing original flue kits only, since they are inte-gral parts of the boiler.For LPG, the appliancemustalso conformwiththe requirements of the distributors and com-ply with current Regulations and laws in force.The safety relief valve and the condensatedrainmust be connected to a suitable drain, ordischarge in a safe manner.The electrical wiringmust conformwith currentRegulations, in particular:--- the boiler must be earthed using the cor-rect bonding clamp.

--- Adjacent to the boiler a fused spur isolationswitch must be installed which permits acomplete switching off in the conditions ofthe overvoltage category III. Refer to sec-tion 6.9 in thischapter for the electrical con-nections.

In no circumstances will the manufacturerbe held responsible if the warnings and in-structions contained in this manual havenot been complied with.

6.2 Precautions for installationFor the installation proceed as follows:--- The boiler must be fixed to a strong wall.--- The dimensions for the exhaust fume duct de-tailed in section6.7 and the correctproceduresfor installing the duct, depicted in the instruc-tion leaflet included with the flue kit, must becomplied with during installation.

--- To allow maintenance procedures it is necess-ary to leave the minimum gaps indicated inFig. 6.1.

25 50

200

200

Fig. 6.1 (all dimensions in mm)

--- When installing the boiler in a cupboard, coveror alcove allow at least 50mmpermanent clear-ance from the front face of the boiler. Also en-sure sufficient clearance to allow free accessfor servicing and the lowering of the front con-trol panel.

--- If the boiler is installed outside, cover the ap-pliance to protect it against the elements andadd some special anti--- freeze (neutralised) tothe c.h. system.

--- Before installing the boiler on an existing c.h.system, flush it out thoroughly before fitting theboiler, so as to remove muddy deposits.

--- It is advisable to equip the system with a sedi-ment filter, or use awater--- treatment product inthe circulating water.The latter option in particular, not only cleansout the system, but also has an anti---corrosiveeffect by promoting formation of a protectiveskin on metal surfaces and neutralising gasespresent in the water.We recommend the use of a suitable universalinhibitory to protect the c.h. system from cor-rosion.

6.3 Installing the bracketPrecautionsBefore mounting the bracket, check that the di-mensions for fitting the exhaust fume duct arecomplied with (refer to the leaflet included with theflue kit, packed separately).Utilise the paper template supplied with the boilerto determine the fixing position for the bracket andboiler. Securely mount the bracket to the wallusing appropriate fixings suitable for the type ofwall construction and capable of supporting thetotal (wet) load. Refer to the weight given in thetechnical data tables specific for each model.

INSTALLATION

Page 25: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Installation

21

6.4 Overall dimensions

ø80 ø80

ø100

400

20047245

196

803

700

35

115 142

16

31

6060

100 257

200129117

50

73

350

190A, B and C

Boilerfront

B

A

C

GasC.h.

C.h.

return

flow

Electricconnectionarea

A --- air intake/flue outlet pipe (co---axial)B --- flue outlet pipe ø 80 mm (twin kit)C --- air intake pipe ø 80 mm (twin kit)

Condensate drainconnectionarea

Fig. 6.2 (all dimensions in mm)

6.5 Joints

Functions Pipe sizes (o.d)Gas, c.h. return, c.h. flow ø 22Pressure relief valve ø 15Condensate drain ø 25 (plastic)

Tab. 6.1 (sizes in mm o.d.)

6.6 Mounting the boiler1 Take the protective caps off the boiler pipe-work.

2 Thoroughly clean the connections.3 Mount the boiler on its bracket.4 Fix the c.h. valves A and gas cock B (¾�) to theboiler using the ¾� gaskets (Fig. 6.3)

5 Fix the ø 22mmpipes C (c.h. circuit) to the c.h.valves A and the ø 22 mm pipe D (gas) to thecock B using the ¾� gaskets.

C

A

A

B

D

C

Fig. 6.3

6 Connect the pipeE (Fig. 6.4) from thepressurerelief valve to the safety discharge pipework.

7 Fit the condensate drain 10 (Fig. 6.4) in the airbrake connected to the drainage pipework.See also section 5.7 in this manual.

INSTALLATION

Page 26: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Installation

22

10E

10EFig. 6.4

6.7 Fitting the flue systemRefer to the assembly instructions contained with-in the chosen flue kit packaging for the correct as-sembly and installation.In general, it has to be taken in consideration thatthe horizontal sections of the flue pipe must havean horizontal sloping not less than 1.5 deg. (25mm per metre) towards the boiler.In the standard horizontal flue kit (Fig. 6.6A) theflue pipe is angled within the air duct therefore theair duct must be horizontally installed.

If one or more extensions have to be used theymust be adequately supported so that there is nosag in the flue pipe and a minimum fall of 1,5 deg.(25 mm per metre) over the whole length towardsthe boiler is ensured.Before fitting the flue system, ensure that the fluegasket shown in Fig. 6.5 (given with the boiler) isfitted to the boiler.

Fig. 6.5

6.8 Choice of flueThe following flue kits are available for connectingto the boiler:

Standard horizontal flue kit (Fig. 6.6A)Co---axial 60/100mm --- nominal length 1mThiskit isnormally suppliedwith theboiler and canbe fitted to allow discharge to the rear or eitherside of the boiler via the flanged boiler adapterelbow. Minimum length required is 0.3 m. Maxi-mum equivalent length of 2,7 metres can beachieved utilising extensions. This flue systemcanonly be used to discharge horizontally, it is not de-signed to enable termination in the vertical plane.

Vertical kit with 90û elbow (Fig. 6.6B)Co---axial 60/100 mmSupplied with a straight flanged adapter a co---axial elbow and a co---axial pipe with terminal, thiskit allows for a vertical rise of 0,5 m from the boiler.In all circumstances the flue terminal must dis-charge horizontally and the equivalent flue lengthmust not exceed 2,7 metres.

Elbows 45û & 90û (Fig. 6.6C)Co---axial 60/100mm.Elbow kits enable the standard flue kits to beoffsetto overcome obstructions or ensure the correctclearances for the flue terminal. Each elbow usedin addition to the standard flanged elbow reduces

INSTALLATION

Page 27: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Installation

23

the overall acceptable length of the flue systemasfollows:45û reduce length by 0,5 m.90û reduce length by 1 m.

ø 60/100

ø 60/100

90û=---1 m

45û=---0,5 m

A

B

C

Min = 0,3 mMax = 2,7 m

Only for M96.32SR/...Min = 0,3 mMax = 1,8 m

ø 60/100

ø 60/100

90û=---1 m

45û=---0,5 m

A

B

C

Min = 0,3 mMax = 2,7 m

Fig. 6.6

Twin pipe kits ø 80 mm (Fig. 6.7)Various twin (split) pipes kits and optional acces-sories (elbows) are available to assist in the ter-mination of the flue where the boiler is installed ina location remote to an outside wall.These kits allow for separation of the air supplypipe from the pipe that discharges the exhaustgasses. Consequently it is possible to extend theflue system to a greater distance than that pro-vided by the standard horizontal co---axial flue.If either an additional 45û or 90û accessory elbowis used then the maximum permissible length ofeither pipe must be reduced by 0.90 m or 1,65 mrespectively.

90û=---1,65 m

45û=---0,90 m

Fig. 6.7

Two restrictors with different size are suppliedwith the twin pipe kit and have to be installedbetween the boiler and the air intake adapter(Fig. 6.8).

Air intake adapter

Restrictor

Gasket

Fig. 6.8

For the correct use of the restrictors with twinpipes refer to Tab. 6.2.

For M96.28SR/...

Equivalent length(air duct + flue duct)

Restrictor

Between 1 and 15 m ø 50 mm

More than 15 m up to 30 m ø 55 mm

INSTALLATION

Page 28: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Installation

24

For M96.32SR/...

Equivalent length(air duct + flue duct)

Restrictor

Between 1 and 24 m ø 50 mm

Tab. 6.2

Vertical--- roof kit (Fig. 6.9)This kit allows vertical termination of the flue pipethrough the roof. The kit is 1.2 m in length. Exten-sion pieces (Co---axial) are also available which al-lows the flue system to be extended to a totaloverall maximum permissible length.Optional 45û and90û elbowscan beused tooffsetthe flue route.Each additional elbow reduces the overall accept-able length of the flue system as follows:45û reduce length by 0,5 m.90û reduce length by 1 m.

90û=---1 m

45û=---0,5 m

max =8,5 mOnly for M96.32SR/...max = 6 m

max = 8.5 m

90û=---1 m

45û=---0,5 m

Fig. 6.9

6.9 Electrical connections

Connection to the electricity supply1 Remove the front panel of the case (see thesection 9.2 in this manual).

2 Remove the screws F and G (Fig. 6.10).3 Loosen the screws H.

F

G

H H

F

FG

GH

Fig. 6.10

4 Remove the side panels ormove the lower partof the side panels as indicated in Fig. 6.11 andpull the control panel.When completely pulled out, the panel can ro-

INSTALLATION

Page 29: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Installation

25

tate 45û downwards to facilitate the operationson the internal parts.

Fig. 6.11

5 Loosen the screws I and remove the servicepanel (Fig. 6.12).

I

I

Fig. 6.12

For the electrical connection to the boiler use elec-tricwireswhich conform to the current regulations,with flexible cord, each core having a cross sec-tion area not less than 0,75 mm2.6 Connect the electrical supply flexible cordcoming from the fused spur isolation switch tothe power supply terminal block of the boiler(Fig. 6.13) keeping the same connections forthe live (brown wire) and the neutral (bluewire). External 3 A fuseor fusedplug with samecurrent rating is recommended.Do not connect live wires to terminals towhich the room thermostat must be con-nected.

7 Connect the earth wire (yellow/green).

Connection of a room thermostatThe room thermostat must be connected to theterminal block situated next to the control panel.

When connecting any type of external control,the link J in Fig. 6.13 must be removed.

INSTALLATION

Page 30: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Installation

26

12

L N

3

To fused spurisolation switch

Power supplyterminal block

External controlsterminal block

J

Fig. 6.13

8 Connect the room thermostat between ter-minals 1 and 3 as shown in Fig. 6.14.Do not connect live wires to terminals towhich the room thermostat must be con-nected.

Power supplyterminal block

External controlsterminal block

T

Room thermostat

12

L N

3

Fig. 6.14

9 Route the electrical supply flexible cord andthe external control flexible cord as illustratedin Fig. 6.15.Lock the flexible cords in placewith the flexiblecord clamps

To the fused spurTo the externalcontrol device

isolation switch

Fig. 6.15

6.10 External frost protection10 Connect the frost thermostat between ter-minals 1 and 2 as shown in Fig. 6.16.Do not connect live wires to terminals towhich the room thermostat must be con-nected.

Power supplyterminal block

External controlsterminal block

T

Room thermostat

T

Frost thermostat

12

L N

3

Fig. 6.16

6.11 Connecting a system boilerto a cylinder

Two schematic wiring diagrams are given in thissection showing two possible ways to connect anexternal programmer to a mid---position divertervalve to provide independent timed and thermo-static control of heating and hot water.Fig. 6.17 and Fig. 6.18 are divided in two parts.The upper shows the single components used onthe diagrams with their connection to the 10 wayjunction box. The bold numbers represent the ter-

INSTALLATION

Page 31: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Installation

27

minal of the junction box where the componentmust be connected to.The lower part shows how to realize a system thatprovides independent timed and thermostaticcontrol of heating and hot water.In Fig. 6.17 the boiler is permanently connected tothemain supply. The boiler operation is controlledby the external control terminal block.In Fig. 6.18 the boiler is not permanently con-nected to the supply line. The boiler operation is

controlled by switching the mains supply.In this case, when the boiler is switched off someimportant features like the antifreeze system, themonitoring of the boiler by theoperation lights, thepost circulation of the pump, etc. are completelydeactivated.For these reasons it is advisable to use the first dia-gram (Fig. 6.17).

INSTALLATION

Page 32: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Installation

28

GYWH

OR

GRYE

321 4 5 6 7 1098

321 4 5 6 7 1098

BL

C12

Cylinderthermostat

Room thermostat

A B

MAINS230V a.c.Switched 3 Amp fused,spur

L

N

Programmer

HTG

HW OFFHW ON

L N

Power supplyL N

321

remove roomthermostat link

External controlterminal block

Room thermostatA B

5

4

Cylinderthermostat

C1

2

876

GYWH

OR

GRYEBL 2

3

8

57

MAINS230V a.c.Switched 3 Amp fused,spur

L

N 2

3

1

Programmer

HTG

HW OFFHW ON

L N 2

1

4

67

Power supplyL N

231

321External controlterminal block

8

10 wayjunction box

Valve colour key

WH --- WhiteGRYE --- Green/Yellow

GY --- GreyOR --- Orange

BL --- Blue

Mid---positiondiverter valve

HTG = HeatingHW ON = Hot Water ONHW OFF = Hot Water OFF

Fig. 6.17 --- Permanent live Y---plan

INSTALLATION

Page 33: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Installation

29

GYWH

OR

GRYE

321 4 5 6 7 1098

321 4 5 6 7 1098

BL

C12

Cylinderthermostat

Room thermostat

A B

MAINS230V a.c.Switched 3 Amp fused,spur

L

N

Programmer

HTG

HW OFFHW ON

L N

Power supplyL N

321

Do notremove roomthermostat link

Room thermostatA B

4

5

Cylinderthermostat

C1

2

876

GYWH

OR

GRYEBL 2

3

8

57

MAINS230V a.c.Switched 3 Amp fused,spur

L

N 2

3

1

Programmer

HTG

HW OFFHW ON

L N 2

1

4

67

Power supplyL N

238

External controlterminal block

10 wayjunction box

Valve colour key

WH --- WhiteGRYE --- Green/Yellow

GY --- GreyOR --- Orange

BL --- Blue

Mid---positiondiverter valve

HTG = HeatingHW ON = Hot Water ONHW OFF = Hot Water OFF

Fig. 6.18 --- Not permanent live Y---plan

INSTALLATION

Page 34: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

7 COMMISSIONING

30

WARNINGThe commissioning of this boiler and systemmust only be undertaken by a professionallyqualified person in accordance with the re-quirements of the Gas Safety Installation andUse Regulations and be approved byC.O.R.G.I.

Ensure that the Benchmark Log Book is satis-factorily completed during the commissioningprocess. The Log Book is located at the end ofthis manual. This manual should be handed tothe User following completion of the installa-tion and commissioning process. Failure tocomply with these requirements may invali-date the manufacturers guarantee.

For Ireland (IE), it is necessary to complete a�Declaration of Conformity� to indicate com-pliance to I.S.813.2002.

7.1 Electrical installationPreliminary electrical system checks to ensureelectrical safety shall be carried out by a compet-ent person. i.e. polarity, earth continuity, resis-tance to earth and short circuit.If a fault has occurred on the appliance the fault find-ing procedure should be followed as specified in theservice manual.

7.2 Gas supply installation1 Inspect the entire installation including the gasmeter, test for tightness and purge, all as de-scribed in BS 6891;

For Ireland (IE), refer to I.S.813.2002.2 Open the gas cock 12 (Fig. 7.1) on theappliance and check the gas connector on theappliance for leaks.

Open position12Fig. 7.1

7.3 Initial filling of the system1 Open the c.h. flow and return valves.2 Remove the front panel of the case (see thesection 9.2 in this manual.

3 Unscrew the cap on the automatic air purgervalve 16 (Fig. 7.2) one full turn and leave openpermanently.

4 Gradually open stopcock at the filling pointconnection to the c.h. system until water isheard to flow; do not open fully.

1618

Fig. 7.2

5 Open each radiator air vent starting at thelowest point of the system and close it onlywhen clear water, free of bubbles, flows out.

6 Purge theair from the pumpby unscrewing thepump plug 18 (Fig. 7.2); release the pumpshaft by turning in the direction indicated bythe arrow on the information plate.

7 Replace the pump plug.8 Continue filling the system. The actual readingshould ideally be 1,3 bar and not less than 0,3bar.

9 Close all air release valves on the c.h. system.10 Inspect the boiler and the system for watersoundness and remedy any leaks discovered.

11 Cold flush the system to remove any loose par-ticlesandany systemdebrisbefore starting theboiler for the first time

The flushing procedure must be in line withBS7593 Treatment of Water in d.h.w. c.h. Sys-tems.

When the installation and second filling arecompleted turn on the c.h. system and run ituntil the temperature has reached the boileroperating temperature. The system must thenbe immediately flushed through.

INSTALLATION

Page 35: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Commissioning

31

This procedure must be repeated twice more.

During this operation we highly recommendthe use of a c.h. flushing detergent in the quan-tities as specified by the appropriate manufac-turer, whose function it is to dissolve anyforeign matter which may be in the system.

The above operation could save the invalida-tion of your boilers guarantee andwill alsopre-vent problems which you may experience inthe future if an inhibitory is not used.

7.4 Condensate pipe and trapsThe full length of the condensate pipe should becheck for leaks.The boiler has a built--- in condensate trap pro-vided with a ball valve that prevents the escape ofcombustion products when the trap is empty.

It is however recommended that any other trapin the drain system is correctly filled withwaterbefore to run the boiler.

7.5 Lighting the boilerSome products incorporate an anti cycling timedelay. It isnormalwhen first switching the boiler onfor the boiler to operate on heating for a few sec-onds then switch off. After 3---4 minutes haselapsed the boiler will then re ignite and operateperfectly normally.If external controls are fitted (e. g. Timeclock, roomthermostat) ensure they �call for heat�.1 Turn on the electricity supply to the boiler,switching on the fused spur isolation switch.The appliance operation light 9 will flash every4 seconds.

2 Turn the function selector 7 as in Fig. 7.3. Theappliance operation light 9 will flash every 2seconds.

79 6 5

Fig. 7.3

The boiler will now go through an ignition se-quence and the burner will light.If during the ignition attempt period the boiler failsto light, the full sequence control p.c.b. will go tolockout and the lock---out signal lamp 5 will ap-pear.To reset the boiler press and release the boiler re-set button 6.

7.6 Checking the gas pressure atthe burner

This boiler has been tested to the highest qual-ity control standards.

Themaximumandminimumgas pressuresarealready set during this quality control processhowever the checking procedure must be fol-lowed to ensuremaximumoperatingefficiencyfrom the boiler.1 Remove the front panel of the case (see sec-tion 9.2 in this manual).

2 Loosen the internal screw 35 (Fig. 7.4) on theOutlet Pressure Test Point of theGas Valve andconnect a pressure gauge using a suitablehose.

3 Set the c.h. temperature control knob to itsmaximum position. If external controls are

INSTALLATION

Page 36: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Commissioning

32

fitted (e. g. Timeclock, room thermostat) en-sure they �call for heat�.

4 Switch on the boiler.5 Check the maximum gas pressure and com-pare the value on the gaugewith the value indi-cated in the sections 4.5 or 4.6 (gas pressuresat the burner).

6 Check the maximum gas flow at the gasmeterand compare the value indicated in the sec-tions 4.5 or 4.6 (gas rate).

7 Switch off the boiler.8 Disconnect the gas modulator coil by remov-ing the electrical connector A (Fig. 7.4).

35

A

Fig. 7.4

9 Switch on the boiler.10 Check the minimum gas pressure and com-pare the value on the gaugewith the value indi-cated in the sections 4.5 or 4.6 (gas pressuresat the burner).

11 Switch off the boiler and re---connect the elec-trical connector A to the modulator coil.

12 Switch on the boiler.13 Check that the boiler lights up uniformly.If not refer to section �Ignitiongas pressuread-justment� of theServiceManual for thenecess-ary adjustment procedures.

14 Switch off the boiler and disconnect the pres-sure gauge.

If the maximum and minimum gas pressuresmeasuredabovearenot in accordancewith thetechnical data (sections 4.5 or 4.6) then adjust-mentwill be necessary.A full explanation of thegas pressure adjustment procedure is given inthe Gas Valve section of the service manual. Ifmaximum and/or minimum gas pressures areadjusted then the ignition gas pressure mustbe checked and adjusted if necessary.

Important: after the gas pressure checks andanyadjustmentoperations,all of the testpointsand adjustment devices must be sealed. Re-place the adjustment protection cap.

7.7 Checking the burner ignition1 Turn the boiler OFF2 Open the gas valve outlet pressure test point35 (Fig. 7.4) and connect the gauge.

3 Turn the boiler ON positioning the control se-lectors 7 in the positions as shown in Fig. 7.5and ensure that the timer selector switch androom thermostat, if fitted, are set to �heat de-mand�.

79

Fig. 7.5

4 Watch the gauge and check to see if the igni-tion pressure registered corresponds to the va-lues as given in the Technical Data. Turn off theboiler and reignite it by turning the function se-lector 7 to the OFF position and then back tothat indicated in Fig. 7.5.

5 Repeat this process two to three times leaving30 second intervals between each ignition.Check the ignition pressures and visuallycheck that the burner lights uniformly and in acontrolled manner.

6 If the burner ignition is not uniformly controlledthen checks should be made to:

--- the flue installation and termination.--- that the flue gasket as shown in Fig. 6.5 page22 is in place.

INSTALLATION

Page 37: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Commissioning

33

--- that the burner and injectors are clean.--- that the boiler is set for the correct gas used(see Section Gas Conversion of this manual)

7 If the ignition pressure recorded is not as indi-cated in the TechnicalData then refer to section�Ignition gas pressure adjustment� of the Ser-vice Manual for the necessary adjustment pro-cedures.

Important: after the gas pressure checks andanyadjustmentoperations,all of the testpointsmust be sealed and replace the adjustmentprotection cap.

7.8 Adjustment of useful c.h.output

The following procedure allows the output of theboiler for central heating to be adjusted to meetthe system requirement.Refer to Fig. 7.11, Fig. 7.12 and Fig. 7.13 (de-pending on the gas used) and determine the cor-rect burner pressure appertaining to the outputrequired for the central heating requirement.1 Remove the front panel of the case.2 Open the gas valve outlet pressure test point35 (Fig. 7.4) and connect the gauge.

3 Rotate the service and installation knob 8 as inFig. 7.6.

4 Turn the boiler ON positioning the function se-lector 7 as indicated in Fig. 7.6 and ensure thatthe timer selector switch and room thermostat,if fitted, are set to �heat demand�.

79 8 56

Fig. 7.6

5 Keep pressed the reset button 6 for about 10seconds until the lock---out signal lamp 5blinks.

6 The lamps 9 should give the indication as inFig. 7.7.If not, press the resetbutton 6 repeatedly toob-tain it.

Where: Lamp OFF

Lamp ON

Fig. 7.7

7 Keep pressed the reset button 6 for about 5seconds.The boiler runsand the lamp 5 is switchedOFF.The lamps 9 give the indication as in Fig. 7.8

Where: Lamp OFF

Flashinglamp, aloneor simulta-neously withan otherlamp

Fig. 7.8

8 Rotate the service knob 8 in Fig. 7.6 to obtainthe pressure to the burner tomeetwith thecen-tral heating system requirements. Refer to thediagrams shown in Fig. 7.11, Fig. 7.12 orFig. 7.13By rotating clockwise the pressure increases.

9 Make a note of the position of the knob 8 andrecorded this in Fig. 7.9 below with an *.

10 Turn the boiler OFF and ON positioning thefunction selector 7 as indicated in Fig. 7.9

79 6 58

Fig. 7.9

11 Keep pressed the reset button 6 for about 10seconds until the lock---out signal lamp 5blinks.

Note: during the adjustment the boiler doesn�t op-erate.12 Press the reset button 6 repeatedly (2 times)until the lamps 9 give the indication as in

INSTALLATION

Page 38: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Commissioning

34

Fig. 7.10 (useful c.h. output adjustmentmode).

Where: Lamp OFF

Lamp ON

Fig. 7.10

13 Turn the knob 8 to the minimum (fully counter-clockwise) and then on the position correspon-ding to the position obtained on step 8.By turning the knob 8, the lock---out signallamp 5 blinks quickly (2 per second) indicatingthat the setting has changed and must be me-morised by keeping pressed the reset button6 for about 5 seconds until the lamps 9 all brief-ly simultaneously blink.

14 To reset the boiler to the normal operation turnit OFF andONby the function selector 7. In anycase, the boiler automatically resets to its nor-mal operation after 10 minutes.

9111315171921232527293133

1 2 3 4 5 6 7 8 9 10 11 12 13

kW

mbar

Natural (G20)

M96.28SR/...M96.32SR/...

Fig. 7.11

101214161820222426283032

5 7 9 11 13 15 17 19 21 23 25 27 29

kW

mbar

Butane (G30)

M96.28SR/...M96.32SR/...

Fig. 7.12

9111315171921232527293133

7 10 13 16 19 22 25 28 31 34 37

kW

mbar

Propane (G31)

M96.28SR/...M96.32SR/...

Fig. 7.13

INSTALLATION

Page 39: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Commissioning

35

7.9 Checking the ignition deviceWith the burner on high flame close the gas cock.After three ignition attempts (within about threeminutes), the lock---out signal lamp 5 (Fig. 1.3 onpage 2) must appear.To reset the boiler press and release the boilerreset button 6 (Fig. 1.3 on page 2).

7.10 Checking the flue systemThe flue system should be visually checked forsoundness. Check all clamps, gaskets and fixingare secure and tight.Ensure that the flue terminal is sited correctly in ac-cordance with the flue fitting instructions andFig. 5.1 on page 17 of this manual.To carry out a combustion check refer to the in-structions given in the section 9.3 of this manual.Reference figures are given in the sections 4.5 or4.6 of this manual (Flue gas figures).

7.11 Checking the condensatedrain pipe

Check the soundness and integrity of the conden-sate drain pipe.Verify the cleanness and correct filling of the con-densate traps.

7.12 Instructing the userHand over this combined User & Installation man-ual and the Servicemanual to the enduser andex-plain how to use the unit.Take the User step by step through the lighting in-structions.Show the User how to switch off the appliancequickly and indicate the position of the electricsupply isolator.Explain the proper use and adjustment of all sys-tem controls; this will ensure the greatest possiblefuel economy.Explain the function and use of the function selec-tor.Explain and demonstrate the function of time andtemperature controls (if fitted).Explain how to turn off the appliance for both shortand long periods and advise on the precautionsnecessary to prevent damage should theappliance be inoperative when freezing condi-tions may occur.Fill in the details required on the Boiler GuaranteeCertificate and hand to the User advising them toreturn the correct section for boiler Guarantee reg-istration.Finally, advise the User that, for continued safeand efficient operation, the appliancemust beser-viced by a competent person at least once a year.

INSTALLATION

Page 40: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

8 GAS CONVERSION

36

8.1 WarningsThe commissioning of this boiler and sys-tem must only be undertaken by a pro-fessionally qualified person in accordancewith the requirements of the Gas Safety In-stallation and Use Regulations and be ap-proved by C.O.R.G.I.Components used to adapt it to the type of gasavailable must be genuine parts only.

8.2 Procedures1 Check that the gas cock (12 in Fig. 9.3) fittedunder the boiler is turned off and the applianceis switched off at the mains isolating spur.

2 Remove the front panel of the case (see thesectionGeneral accessand emptyinghydrauliccircuits in the service manual).

3 Take off the lid of the sealed chamber.4 Take the front panel of the combustionchamber off and remove the burner (24 onpage 9). See section Ignition and detectionelectrodes in the servicemanual for detailed in-structions.

5 Carry out the conversion for the type of gas, re-placing the burner injectors correctly.

6 Re---assemble the burner, the front panel of thecombustion chamber and the lid of the sealedchamber.

7 Switch on the appliance at the mains isolatingspur.

8 Turn the boiler OFFpositioning the function se-lector 7 as indicated in Fig. 8.1.

79 6 58

Fig. 8.1

9 Disconnect the C.h. temperature probe NTC21 in Fig. 8.2

21

Fig. 8.2

10 Keep pressed the reset button 6 for about 10seconds until the lock---out signal lamp 5blinks.

11 Connect theC.h. temperature probeNTC 21 inFig. 8.2

12 Press the reset button 6 repeatedly (4 times)until the lamps 9 give the indication as inFig. 8.3 (gas type mode).

Where: Lamp OFF

Lamp ON

Fig. 8.3

At this step it is possible to visualize the current set-ting by keeping the reset button 6 pressed formore than 5 seconds. The lamps 9 will flash anumber of times corresponding to the setting ofthe knob 8 in Fig. 8.4.

8

L.P.G.Gas typeSetting No.

NATURALGAS

Fig. 8.4

MAINTENANCE

Page 41: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Gas conversion

37

Gassupply

Position ofknob 8

Approx. Max currentthrough the modulatordevice

Naturalgas

1 125 mA

L.P.G. 4 165 mA

Fig. 8.5

13 Tochange the setting turn theknob 8on aposi-tion corresponding to the gas used as shownin Fig. 8.4.By turning the knob 8, the lock---out signallamp 5 blinks quickly (2 per seconds) indicat-ing that the setting has changed and must bememorised.

14 To memorize the setting keep pressed thereset button 6 for about 5 seconds until thelamps 9 briefly blinks simultaneously.

15 Open the gas cock (12 in Fig. 9.3)

16 To reset the boiler to the normal operation turnit ON by the function selector 7 on the desiredoperation and checking the ignition pressureand that the burner lights up uniformly. In anycase, the boiler automatically resets to its nor-mal operation after 10 minutes.

Factory setting = Natural gas (as illustrated)17 Calibrate the gas valve according to the in-structions given in the service manual, sectionModulating gas valve --- Adjustment.

18 Set the correct gas pressure for central heatingoutput required, see section 7.8 in thismanual.

19 Stick on the inside of the left hand side paneladjacent to the data badge the self ---adhesivelabel (included with the conversion kit) indicat-ing the type of gas, and the gas pressures towhich the appliance has been set. Replace theadjustment protection cap.

20 Replace the front panels of the case.

MAINTENANCE

Page 42: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

9 MAINTENANCE

38

9.1 WarningsThe procedures detailed in this chapter mustbe carried out only by a professionallyqualified person. Thus you are advised tocontact an Authorised Service Agent.

For Ireland (IE), the servicing work must becarried out by a competent PersonFor efficient and continuous operation of theboiler you are advised to have, at least once ayear, maintenance and cleaning done by anApproved Service engineer.Isolate the appliance from the electricitysupply by turning off the fused spur isolationswitch adjacent to the appliance and turn offthe gas cock, before carrying out any pro-cedures, whatsoever, for cleaning, mainten-ance, opening or dismantling boiler panels.

9.2 Dismantling the externalpanels

Front panel1 Loosen the three screws A (Fig. 9.1).2 Lift and remove the panel.

A

Sampling pointsAir---Flue exhaust

Fig. 9.1

Side panels

3 Loosen the screws B. Bring the bottom of thepanels away from the boiler and lift them, free-ing them from the top hooks (Fig. 9.2).

BFig. 9.2

1213

11

Closed position

Fig. 9.3

9.3 Combustion analysis checkIf it is necessary tocarry out a combustion analysisremove the plugs indicated in Fig. 9.1.Reference figures are given in the sections 4.5 or4.6 of this manual (Flue gas figures).

9.4 Cleaning the primary heatexchanger

1 Take off the front of the case.

MAINTENANCE

Page 43: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

Maintenance

39

2 Take off the removable front of the air--- tightchamber and the front panelof thecombustionchamber.

If you notice dirt on the fins of the primary heat ex-changer (26 on page 9):3 cover the sloping surfaces of the burner (24 onpage 9) entirely in a protective layer (sheets ofnewspaper or similar).

4 Brush out the primary heat exchanger (26 onpage 9) with a bristle paintbrush.

9.5 Checking the pressurisationin the expansion vessel

Empty the central heating system as described insection General access and emptying hydrauliccircuits in the service manual and check that thepressure in the expansion vessel is not less than1 bar.See also section 4.4 page 11 of this manual.If the pressure is lower, take steps to correct thepressure level.

9.6 Cleaning the burnerThe sloping and multi---gas type burner (24 onpage 9) does not need special maintenance, butit is sufficient to dust it with a bristle paintbrush.To reach the burner:1 Take off the front of the case.2 Take off the removable front of the air--- tightchamber and the front panelof thecombustionchamber.

3 Brush out the burner with a bristle paintbrush.

9.7 Checking the flueHave the integrity of the flue outlet pipe (40 onpage 9) air intake pipe (41 on page 9), checkedperiodically, the venturi device* (39 on page 9)cleaned and the efficiency of the flue safety circuitchecked at least once a year.* For details see the section Fan, venturi deviceand air pressure switch in the service manual.For all the above maintenance operations it is ad-visable to call an approved Service Engineer.

9.8 Drain pipe inspectionCheck the soundness and integrity of the conden-sate drain pipe.Verify the cleaness and correct filling of the con-densate traps.

9.9 Visual inspection ofappliance

Visually inspect all water joints, seals and connec-tions for any evidence of leakage and retighten,grease or replace them as necessary.

9.10 Gas pressures and tightnessCheck appliance for gas tightness. Recheckoper-ational pressures and adjust as necessary as de-scribed in section 7.6 page 31 of this manual.

MAINTENANCE

Page 44: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety
Page 45: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety
Page 46: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety
Page 47: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety
Page 48: Biasi - Boilers, Radiators, Towel Rails & More - Wall hung, fan flue, … · 2014-10-16 · Lack of burner ignition (no ignition signal from the full seqence ignition device) Safety

*1796214040*17962.1404.0 1607 48A5 UK

Biasi UK LtdNewman Park, Western WayWednesbury, WS10 7BJSales Tel No: 0121 506 1340Sales Fax No: 0121 506 1360Service Tel No: 0121 506 1350Service Fax No: 0121 506 1370www.biasi.co.uk