    White Paper

    Table of contents

    Why you should care 2

    How it works 2

    Loss-length testing procedures 2

    Additional fber best practice resources 2

    Introduction to fber best practices

    The Fiber Best Practice Series was designed by Fluke

    Networks to educate about important optical fber

    best practices, including:

    Fiber inspection and cleaning

    Loss-length (Tier 1) fber certifcation

    Fiber plant characterization and troubleshooting

    (Tier 2 certifcation)

    This white paper details the best practice o fber

    plant characterization and troubleshooting

    (Tier 2 certifcation).

    With 40 G/100 G inrastructure deployments in the

    datacenter quickly becoming reality, the shrinking

    loss budgets o optical fber cabling due to increasing

    bandwidth demands mean that reliable and efcient

    initial installations are now more important than

    ever. To minimize costly installer or contractor

    callbacks, network technician troubleshooting time,

    and unnecessary network downtimes, fber-handling

    best practices should always be ollowed.

    Fiber Best Practice:

    Fiber Plant Characterization and

    Troubleshooting (Tier 2 Certifcation)

  • 8/3/2019 Best Practices Fluke

    2/2

    White Paper

    Fluke Networks www.flukenetworks.com2

    N E T W O R K S U P E R V I S I O N

    Fluke NetworksP.O. Box 777, Eve rett, WA USA 98206-0777

    Fluke Networks operates in more than 50 countriesworldwide. To nd your local oce contact details,go to www.fukenetworks.com/contact .

    2010 Fluke Corporation. All rights reserved.Printed in U.S.A. 2/2010 3672932A D-ENG-N

    Why you should care

    In gaining ull visibility into the ber plants attenuation, insertion loss, and refectance at connectors, splice locations, and unantici-

    pated loss events, an optical time domain refectometer (OTDR) provides valuable insight into a ber installation that cannot be obtained

    rom an optical loss test set (OLTS). Such an ability to pinpoint events is critical or troubleshooting and rooting out potential cabling

    component problems in the ber plant to prevent or minimize costly network downtime. Although currently considered a complementary

    test by industry standards such as Telecommunication Industry Associations (TIA) TIA-568-C.0 and International Organization or

    Standardizations (ISO) ISO 14763-3, it has long been considered a best practice by ber experts.

    How it works

    An OTDR iners loss, refectance, and locations o events by shooting pulses o light into

    one end o a ber link and using a photodetector to sense refections rom loss-causing

    incidents such as connectors, splices, and bends. These incidents are oten reerred to

    as events - some o which are expected and others, unexpected. When a pulse o light

    travels down the ber, most o it continues in the direction o the ber. However, due to

    the inherent composition o the glass ber, a small raction o the light, called backscat-

    ter, is dispersed in dierent directions. Some o this backscatter makes its way back to

    the sensitive detectors at the OTDR source, which is analyzed beore being graphicallydisplayed to depict the link-under-test. Such a characterization o the ber link is called

    a trace, and plots the measured refectance and loss over time. See Figure 1 or an

    example. Legacy OTDRs used to require years o technical experience in order to read

    and interpret traces; however, the majority o present-day OTDRs contain comprehensive

    sotware that automate trace analysis and test parameter set-up, among other advanced

    analytical capabilities (see Figure 2).

    Fiber plant characterization and troubleshooting procedures

    Connect 1 the OTDR to one end o the ber link-under-test.

    Congure or select the appropriate limits to test against.

    Shoot a trace o the ber link-under-test.

    Review the testing results or any passes or ailures. Results are typically

    conveyed in a graphical plot or event chart ormat. As shown in Figure 1, the OTDR

    trace should decrease gradually rom let to right because o loss rom scattering and events such as connections and splices.

    Refections, in the orm o spikes on the trace, can be caused by breaks, cracks, splices, connections, and sharp bends.

    Compare to the limits being tested against to ensure that the component measurements are within the specied limits. Certain

    events such as splices, connectors, and the end o the ber are expected on OTDR traces and thus actored into overall loss

    budgets. However, their loss must still conorm to specications, whether they are industry standards or determined by the

    user. Based on the guidelines being compared to, OTDRs can return PASS or FAIL results or each event.

    1 Similar to using test reerence cords when using an OLTS, ensure a launch ber is used to connect the OTDR to the link-under-test. Launch bers are test leads that

    enable the tester to overcome deadzone limitations to measure the loss and refectance o the rst connector in the cabling. To test the last connector on the ar

    end o the link, attach a receive ber on the opposite end o the link-under-test.

    Additional fber best practice resources

    To download other Fiber Best Practice white papers and or additional resources,

    visit www.fukenetworks.com/FiberBP

    Contact Fluke Networks: Phone 800-283-5853 (US/Canada) or 425-446-4519 (other locations).

    Email: [email protected].

    Figure 1. Depiction o a typical OTDR trace.

    Figure 2. Advanced troubleshooting capability,

    such as highlighting questionable connectors

    in the link-under-test.