18
Benchmark systems for ElectroMagnetic Transient (EMT) and Transient Stability (TS) hybrid simulation IEEE PES General Meeting July 2017 Qiuhua (Tony) Huang Pacific Northwest National Laboratory, USA [email protected] Liwei Wang, Xuekun Meng University of British Columbia Okanagan Campus, Canada [email protected] Shuqing Zhang, Yanan Zhu Tsinghua University Beijing, China [email protected]

Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39

  • Upload
    phambao

  • View
    220

  • Download
    3

Embed Size (px)

Citation preview

Page 1: Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39

Benchmark systems for ElectroMagnetic Transient (EMT) and Transient Stability (TS) hybrid simulation

IEEE PES General Meeting July 2017

Qiuhua (Tony) Huang

Pacific Northwest National Laboratory, [email protected]

Liwei Wang, Xuekun Meng

University of British Columbia Okanagan Campus, [email protected]

Shuqing Zhang, Yanan Zhu 

Tsinghua UniversityBeijing, [email protected]

Page 2: Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39

Need of benchmark systems

Comparison helps selection and improvementEMT vs EMT-TS hybrid simulation vs others ( e.g, TS, frequency shifting)Different interfacing (or network equivalent) models and interaction protocols in EMT-TS hybrid simulation area

Benchmarks systems are important for transparent, “apple-to-apple” comparison

Power flow, transient stability, small-signal stabilityHVDC CIGRE model

However, in EMT and EMT-TS hybrid simulation research areasIn most of previous publication, the developed approaches were tested on a “customized” test systems and compared with full EMT simulation Moreover, test systems were described at a relatively high level, not detailed enough for replicating the models and results.

A set of open, well-documented benchmark systems is needed

July 15, 2017 2

Page 3: Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39

Considerations for selecting the benchmark systems

ApplicationsAC/DC power systems: LCC-HVDC, VSC-HVDC (MMC, 2-Level)Specific or detailed studies: single-phase motors and power electronic loads

Key issues of hybrid simulation

July 15, 2017 3

EMT‐TS

Boundary selection

Interfacing model

Harmonic or frequency dependent effects

Fault (or voltage sag) point on 

wave effects

Interaction protocol

Simulation efficiency

Page 4: Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39

What are included for one benchmark system

DocumentationOne-line-diagramBenchmark system raw data (simulation tool agnostic)

Benchmark system data in exiting tool formatsPower flow data (e.g., PSS/E raw format)Dynamic data (e.g., PSS/E dyr format)EMT data (e.g., PSCAD)Negative and zero sequence data (if available)

July 15, 2017 4

Page 5: Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39

Benchmark systems in the first release

July 15, 2017 5

Benchmark systems

Key issues of hybrid simulation

Boundary selection

Interfacing model

Interaction protocol

Simulation efficiency

Harmonics or frequency 

dependent effects

Fault (or voltage sag) point on wave 

effectIEEE 9‐bus system + single phase motor loads Y Y Y N Y YIEEE 14‐bus system + LCC HVDC system Y Y Y N N NIEEE 39‐bus system + MMC VSC‐HVDC system N Y Y N N NIEEE 39‐bus system + 2 Level VSC‐HVDC system Y Y Y N N N

Page 6: Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39

Benchmark System # 1: IEEE 9-bus system (+ motor loads)

With (and without) motor loadsSingle-phase air-conditioner induction motor model [1].Fault point-on-wave (POW) and voltage sag ramping effects [2]Unbalanced faults in the external systemOriginal source [3]

July 15, 2017 6

EMT‐TS

Boundary selection

Interfacing model

Harmonic or 

frequency dependent effectsFault (or 

voltage sag) point on wave effects

Interaction protocol

Simulation efficiency

Detailed modeling of bus 5 including distribution system and detailed load models

Fault point‐on‐waveEffects [2]

Page 7: Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39

Benchmark System # 2: IEEE 14-bus system + LCC HVDC system

The original AC line from bus 6 to bus 13 is replaced by a LCC HVDCThe LCC HVDC is a modified CIGRE HVDC model, with a smaller rating

July 15, 2017 7

EMT‐TS

Boundary selection

Interfacing model

Harmonic or frequency dependent effects

Fault (or voltage sag) point on 

wave effects

Interaction protocol

Simulation efficiency

G

G

G

G

G

1

6

7

11 10 9

8

5 4

32

13

12

14

Page 8: Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39

Benchmark System # 3: IEEE 39-bus system + MMC VSC-HVDC system

July 15, 2017 8

The  MMC VSC‐HVDC System • Bus 6 and Bus 13 as interfacing terminals• Adapted from OPAL‐RT CPU based Half‐Bridge 

MMC model• Switching‐based, 40 cells per arm• Original source [4]

EMT‐TS

Boundary selection

Interfacing model

Harmonic or frequency dependent effects

Fault (or voltage sag) point on 

wave effects

Interaction protocol

Simulation efficiency

Page 9: Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39

Benchmark System # 4: IEEE 39-bus system + 2-level VSC-HVDC system

Two-level VSC HVDC, PWM decoupled dq control (carrier frequency is 1980 Hz) Rectifier: constant active and reactive power controls Inverter: DC voltage control and an AC voltage controlSource [5]

July 15, 2017 9

A modified IEEE 39 bus system interfaced with a VSC-HVDC system

EMT‐TS

Boundary selection

Interfacing model

Harmonic or frequency dependent effects

Fault (or voltage sag) point on 

wave effects

Interaction protocol

Simulation efficiency

Page 10: Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39

Benchmark System # 5 ( release cycle-2)Large AC system + HVDC system

We are looking for such a benchmark system, and your contribution is welcome and much appreciated!

July 15, 2017 10

Page 11: Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39

References

[1] Y. Liu, V. Vittal, J. Undrill, and J. H. Eto, "Transient Model of Air-Conditioner Compressor Single Phase Induction Motor," IEEE Transactions on Power Systems, vol. 28, pp. 4528-4536, 2013.[2] B. Lesieutre. Simulation Models for Single Phase Compressor Motors. NERC FIDVR and Dynamic Load Modeling Workshop, September 30, 2015.[3] Q. Huang, V. Vittal, “Application of Electromagnetic Transient-Transient Stability Hybrid Simulation to FIDVR Study,” IEEE Trans. Power Systems, vol.31, issue 4, 2016[4] W. Li, J. Belanger, “An equivalent circuit method for modelling and simulation of modular multilevel converters in real-time HIL test bench”, IEEE Transactions on Power Delivery, vol. 31. No. 5, Oct. 2016.[5] Q. Huang and V. Vittal, "OpenHybridSim: An open source tool for EMT and phasor domain hybrid simulation,“ in Proc. of 2016 IEEE PES General Meeting, Boston, MA, 2016, pp. 1-5.

July 15, 2017 11

Page 12: Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39

• The New England 10‐Gen 39‐Bus System

• Select Bus 6 and Bus 13 to be interfacing terminals

• Fault applied on Bus 3, fault cleared after 0.1 second

• Adapted from OPAL‐RT CPU based Half‐Bridge MMC model

• Switching‐Based• 40 cells per arm• PQ control in MMC station 1• VQ control in MMC station 2

Page 13: Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39

• Operation

Time Action0.25 Pulse on at MMC1 and MMC2, Pref and Qref = 0

0.5 Step PQ at MMC1, Pref=0.1 Qref=‐0.1

at MMC2, Qref=0

1.2 Fault applied at bus 3 in AC system

1.3 Fault cleared

• Hardware and Software– CPU i5‐6300 HQ RAM 8.00GB– Matlab 2014b 64‐bits

Page 14: Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39

• Bus 6, Terminal 1 • Bus 13, Terminal 2

Page 15: Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39

• Bus 6, Terminal 1 • Bus 13, Terminal 2

Page 16: Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39
Page 17: Benchmark systems for ElectroMagnetic ... - sites.ieee.orgsites.ieee.org/pes-itst/files/2017/07/2017-TF-2.pdf · One-line-diagram Benchmark system raw data ... A modified IEEE 39