Upload
gaurav1972
View
219
Download
0
Embed Size (px)
Citation preview
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
1/29
Wind Session
Effective Grounding of Wind Farm Collector Circuits
Byen u , . .
Doug Jones, P.E.
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
2/29
What is transient overvoltage (TOV)?
What is the cause of TOV?
How is TOV mitigated?
Do all types of WTGs have problems with TOV?An o a mitigation tec niques wor or a types?
How is TOV mitigating equipment specified?
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
3/29
Must design an economical grounding system that:
controls TOV to acceptable levels limits fault current while enabling secure ground fault
rotection
Transient Overvoltages (TOV) can lead to surge
arrester and other equipment failure roun ng rans ormers or g spee groun ng
switches usually provide adequate mitigation
Different wind turbine t es can mean differentgrounding methods
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
4/29
69/92/115
MVA
230 kV
34.5 kV
34.5 kV Main Bus
52F1 52F2 52F3 52F452CAP
Collector
1
Collector
2
Collector
3
Collector
4DVAR
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
5/29
Typically 34.5kV
Approximately 30MVA per circuit
capacitive
MOV t e sur e arrestors installed at each end of thecable system
Pad mount or nacelle mounted generator step up
trans ormers (35kV) solidly GndY primary (1kV-480V) solidly GndY
secondary -
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
6/29
Type 1 squirrel-cage induction generators
Type 2 wound rotor induction generator withcon ro e ro or res s ance
doubly-fed induction generator
Type 4 generator interfaced to the grid totallythrough a variable speed power electronic drives stem.
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
7/29
yp ca au t contr ut on range o to perunit
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
8/29
Typical fault contribution range of 4 to 9 perunit
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
9/29
Typical fault contribution less than 2 per unitfor remote faults before crowbar
er crow ar engages resem es a ype
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
10/29
yp ca au t contr ut on s very ow andependant upon pre-fault loading
Usually Type 3 and 4 WTG short circuitcurrent contributions dont matter that much
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
11/29
Ground fault
Inadvertent opening of circuit during generation
Capacitor bank switching
Collection cable ca acitance
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
12/29
Ground reference primarily derived by Substationtrans ormer
ground fault
Overvoltage of non-fault phases depends ongrounding/generator type
A new ground reference must be derived fromcircuit to be effectively grounded
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
13/29
Very small Neutral to Ground Impedance
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
14/29
100
50
75
[kV]
-25
0
-100
-75
-50
(file Cable.pl4; x-var t) v:G5NCA -X0004A v:G5NCB -X0004B v:G5NCC -X0004C
. . . . . . . .
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
15/29
Neutral potential & ground potential are coupledon y y t e ne-to-groun capac tances:
A
Gnd = 0 V
A-Gnd Fault on
Ungrounded System
N
VL-G = 1 p.u.
VL-G VL-L
A
C B = . p.u.
Un-faulted System
C B
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
16/29
100
50
75
[kV]
-25
0
-100
-75
-50
(file Cable.pl4; x-var t) v:NGNCA -X0070A v:NGNCB -X0070B v:NGNCC -X0070C
. . . . . . . .
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
17/29
Definition of Effectively Grounded
Effectively grounded when the coefficient ofgrounding (COG) is less than 80%
COG = VLG/VLL
Effectively grounded: VLG < 80% of VLL
nom na LL s . , e un- au e p asesmust be VLG < 27.6 kV
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
18/29
An effectively grounded system can beapprox mate w en system:
X0 & X1 are both are inductive
R0/X1 < 1
To obtain effective ground either reduce R0 & X0, orincrease X1
Increase X1 = Increase Load Losses
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
19/29
Install high speed ground switch
Requires very fast switching, < 1 cycle
Mechanical interlocks do the job well
Electric interlocks have not proven reliable, fast
enough
Install grounding transformer
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
20/29
Wye-Delta or Zig-Zag
Equally effective for limiting TOV
Zig-Zag will be physically smaller but are specialty
built transformers available from a limited numberof manufacturers with generally long lead times andhigh pricing due to one-off design
Wye-Delta available pad-mount type are readilyavailable from multiple manufacturers
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
21/29
Primary Voltage
Rated KVA (if needed)
Continuous Neutral Current Continuous non- .
Neutral Fault current and duration
Impedance Primary winding connection
Secondary connection
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
22/29
Ohms per phase
Rated time 10 second, 1 minute, 10 minute, or extended (less then 90
Generally a 10 second rating for a WPP with an effectivelygrounded system due to fast and sensitive protectionre uirements
Continuous rated current Based on rated time (IEEE 32) = Example: 3500 amps for 10 sec = 3500 * 0.03 =105 amps
continuous
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
23/29
Model the system
oose some yp ca parame ers , . - . ,
use 6.2%) Simulate ground fault
Determine VLG-unfaulted < 0.8 * VLL ess t an 27.6 V
Modify transformer parameters as needed, repeat
Once youve reached desired performance, calculate: ohms per phase
Maximum fault current from grounding transformer
One size does not fit all must consider the s stem
Check with transformer manufacturer to ensurebuildability/availability
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
24/29
Its a good idea to limit TOV due to ground faults,an re uce trans ents ue to , resonance, etc.
asynchronous system
Must verify surge arresters, cables, and otherequipment will withstand the TOV during ground
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
25/29
For Type 1 & 2 WTGs grounding transformers and
fast ground switch breakers are both effective in
mitigating TOV
TOV results whether the step-up transformers are
connected /Yg or Yg/Yg Generators are ungrounded, therefore do not provide zero
sequence fault current
Ensure the generator will trip off quickly if thesubstation breaker opens inadvertently
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
26/29
Both roundin transformers and round switch
breakers can be effective in mitigating TOV Ground switch breaker ma be the referred o tion
as it forces the crowbar to engage and doesnt
require a full transient analysis Transient analysis may be needed
Transient analysis adds design time, costs and
complexity
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
27/29
Type 4 machines should have low fault currentcontr ut ons to a au t
Verify fault current contribution from WTG
For SLG faults on the system the Type 4 power
electronic controller switches out ver uicklthereby not sourcing voltage to a SLG fault. As aresult no significant energy is provided that would
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
28/29
Questions
8/10/2019 Ben Guth and Doug Jones - Wind Farm Grounding
29/29
Chong Han, Don E. Martin, Member, IEEE, and Modesto R. lezama, Transient Over-Voltage (TOV) andIts Suppression For a Large Farm interconnection.
Eaton Application White Paper, Transient Over voltages on Ungrounded Systems from Intermittent
Ground Faults.
Pacific Crest Transformers Article, Grounding Transformers April, 02 2009.
even . ay ors, . ., arge n an o ec or es gn n arm o ec or ys em roun ng,PES Transmission and Distribution Conference 2008.
Mike Reichard, Fault Current Contributions From Variable Speed (Type 3 and 4) Wind Turbine
Generators Texas A&M Protective Relaying Conference Fault Current Contributions from Wind PlantsA ril 1 2009.
ANSI/IEEE Std 32-1972 IEEE Standard Requirements, Terminology, and Test Procedures for NeutralGrounding Devices.
Reigh A. Walling, Michael L. Reichard, Short Circuit Behavior of Wind Turbine Generators
EMA VDH/GSMI brochure (Combined 34.5 kV Vacuum Circuit Breaker & Mechanically Interlocked),available online at: http://www.ema-sa.com.ar
IEEE Standard C62.22-1997, Guide for the Application of Metal-Oxide Surge Arresters for Alternating-Current Systems.