Specifiers Reference
Project Type Model No.
Comments
L200002504/21/08 © The Bodine Company
P.O. Box 460 Collierville, TN USA 38027-0460 Sales 800-223-5728 FAX 901-853-5009
Tech. Support 888-263-4638www.bodine.com
A Division Of Philips Electronics North America Corporation
UL LISTEDFactory or Field Installation(Indoor and Damp)
Illumination Time90 Minutes (Standard)120 Minutes (One 32 W T8)
Initial Light Output300 - 700 Lumens
Full Warranty3 Years (NOT pro-rata)
Universal Input Voltage120 Through 277 VAC, 50 or 60 Hz
AC Input Current60 mA
AC Input Power Rating5.0 Watts
Test SwitchDouble Pole
BatteryHigh-Temperature, Maintenance-FreeNickel-Cadmium Battery7- to 10-Year Life Expectancy
Battery Charging Current280 mA
Recharge Time24 Hours
Charging Indicator LightLED
Temperature Rating (Ambient)0°C to +50°C(32°F to 122°F)
Dimensions9.4” x 2.4” x 1.5”(238 mm x 60 mm x 38 mm)Mounting Center 8.9” (226 mm)
Weight2.5 lbs. (1.13 kg)
Product Summary
Emergency ballasts can be modified to accomodate longer run times.
APPLICATIONThe BDL60U Universal Input fluorescent emergency ballast works in conjunction with an AC ballast to convert fluorescent fixtures into emergency lighting. The emergency ballast handles a wide range of input voltages and frequencies and consists of a high-temperature nickel-cadmium battery, char-ger and electronic circuitry in one compact red case. The BDL60U can be used with most 13 - 215 W (2’ - 8’) T8, T10 or T12 fluorescent lamps without integral starters, including U-shaped, HO, VHO, circline and energy-saving, and (4-pin) long compacts (see Table 1). It is also compatible with most 120 through 277 VAC (50 or 60 Hz) one-, two-, three- and four-lamp electronic, standard, energy-saving and dimming AC ballasts. If used in an emergency-only fixture, no AC ballast is necessary. The BDL60U is suitable for indoor and damp locations and for sealed & gasketed fixtures, including fixtures rated for wet locations. It is not suitable for air handling heated air outlets or wet or hazard-ous locations. For information about specific lamp and ballast compatibility, please call the factory. Recommended applications include: international line voltages from 120 through 277 VAC (50 or 60 Hz); drilling rigs where generators are the primary source of power; and other applications requiring higher tolerance of line voltage variation or harmonic distortion.
OPERATIONWhen AC power fails, the BDL60U immediately switches to the emergency mode, operating either one or two lamps at a reduced lumen output for a minimum of 90 minutes. Two-hour duration may be selected with one 32 W T8 fluorescent lamp. When AC power is restored, the BDL60U automati-cally returns to the charging mode.
INSTALLATIONThe BDL60U does not affect normal fixture operation and may be used with either a switched or unswitched fixture. If a switched fixture is used, an unswitched hot lead must be connected to the emergency ballast. The emergency ballast must be fed from the same branch circuit as the AC ballast. The emergency ballast may be installed inside, on top of or remote from the fixture. The BDL60U may be remotely installed up to half the distance the AC ballast manufacturer recommends remoting the AC ballast from the lamp or up to 50 feet, whichever is less. Installation is not recommended with fixtures where the ambient temperature may fall below 0°C.
UL and CODE COMPLIANCEThe BDL60U has been tested by Underwriters Laboratories in accordance with the standards set forth in UL 924, "Emergency Lighting and Power Equipment,” and is UL Listed for factory or field installation. Emergency illumination time exceeds the National Electrical Code (NEC), Life Safety Code (NFPA–LSC) and UL 90-minute requirements.
One- or two-lamp emergency;Universal input voltage:120 through 277 VAC, 50 or 60 Hz;Replaces B60U
Bdl60uFluorescent Emergency Ballast
L200002504/21/08 © The Bodine CompanyP.O. Box 460 Collierville, TN USA 38027-0460 Sales 800-223-5728 FAX 901-853-5009Tech. Support 888-263-4638www.bodine.com
Table 1 - Lamp CompatibilityLAMP
DIAMETERBASE WATTAGE
(Length)NO. of LAMPS(EMERGENCY)
1", 1¼", 1½"T8, T9, T10, T12
Single orBipin
17-40 W (2'-4')1
2
40-215 W (5'-8') 1
Long Compact 4-pin (2G11) 18-40 W 1
Table 2 - Initial Lumen Output
LAMP LUMENS
1 Lamp 2 Lamps
FO32, FBO31 T8 575 625
FO25, FB024 T8 450 575
FO17, FB016 T8 375 550
FO96 T8 700
F40T12, F40/U 350 375
F40T12/ES (34 W) 350 375
F96T12 HO, VHO 575
PL-L 40W, F40/30BX, Dulux L 40 W 625
PL-L 36W, F39/36BX, Dulux L 36 W 525
PL-L 24W, F27/24BX/RS, Dulux L 24 W 375 475
PL-L 18W, F18BX, Dulux L 24 W 375
F382D/4P 625
F282D/4P 450
F212D/4P 375 500
F162D/4P 300 375
EMERGENCY ILLUMINATIONDepending on the number (one or two), wattage and type of lamps selected, the BDL60U pro-duces 300 to 700 lumens initial emergency light output (see Table 2). If two-lamp operation is selected, light output is evenly divided between the lamps for better distribution of emergency illumination.
SPECIFICATIONEmergency lighting shall be provided by using a standard fluorescent fixture equipped with a Bodine BDL60U Universal Input fluorescent emergency ballast. This emergency ballast shall con-sist of a high-temperature, maintenance-free nickel-cadmium battery, charger and electronic cir-cuitry contained in one 9 3/8” x 2 3/8” x 1 1/2” red metal case. A solid-state charging indicator light to monitor the charger and battery, a double-pole test switch and installation hardware shall be provided. The emergency ballast shall be capable of operating [one or two] _________ fluorescent lamp(s) at _______ lumens (see Table 2) initial light output in the emergency mode for a minimum of 90 minutes or one 32 W T8 fluorescent lamp at reduced illumination in the emergency mode for a minimum of 120 minutes. It shall be suitable for indoor and damp loca-tions and for sealed & gasketed fixtures, including fixtures rated for wet locations. The BDL60U shall have 5 Watts of input power and a 14.4 Watt-hour battery capacity and shall comply with emergency standards set forth by the current NEC. The emergency ballast shall be UL Listed for installation inside, on top of or remote from the fixture and shall be warranted for a full three years from date of purchase.
WARRANTYModel BDL60U is warranted for three (3) full years from date of purchase. This warranty covers only properly installed Bodine emergency ballasts used under normal conditions. For the warranty period, Bodine will, at its option, repair or replace without charge a defective emergency ballast, provided it is returned to the factory transportation prepaid and our inspection determines it to be defective under terms of the warranty. Repair or replacement, as stated above, shall constitute the purchaser’s exclusive warranty, which does not extend to transportation, installation, labor or any other charges; nor does it apply to any equipment of another manufacturer used in conjunction with the emergency ballast.
Bdl60uFluorescent Emergency Ballast
One- or two-lamp emergency;Universal input voltage:
120 through 277 VAC, 50 or 60 Hz; Replaces B60U
Fluorescent Emergency BallastsBDL Series
L0000026
The BDL Series Ballasts are Rated for Damp Location, Vapor-Tight Applications
bodine®
© 2007 The Bodine Company
Sales 800.223.5728 Fax 901.853.5009 www.bodine.com2
Recommended uses include warehouses, covered walkways,
parking garages, aircraft hangars, exterior stairways and any other
location with damp rated or vapor-type fixtures.
Emergency lighting equipment is included in building designs to provide backup
lighting along the path of egress during loss of power so that occupants can exit the building quickly and safely. Because the path of egress often continues outside of a building to a partially protected public way and may include interior areas exposed to moisture, some local codes or building plans require emergency lighting with more than an indoor-dry location rating.
Damp Locations:Partially protected exterior locations under canopies, marquees, roofed open porches and the like, as well as interior locations subject to moderate degrees of moisture such as some basements, barns or cold storage houses. [1]
Source:[1] Rea, Mark S. Lighting Handbook-Reference & Application. Illuminating Engineering Society of North America: 1993.
For more information on the codes applicable to damp locations, see the National Electrical Code, Chapter 14, Codes and Standards.
When Conditions Are Less Than Perfect . . .
BDL Series Fluorescent Backup Ballasts
236 Mt. Pleasant Rd. Collierville, TN 380173
BatteryAll damp location models contain high-temperature nickel-cadmium batteries. These batteries are maintenance free, can be safely installed inside the ballast channel and have a life expectancy of 7 to 10 years.
Code Compliance Damp location models have been tested by Underwriters Laboratories in
accordance with the standards set forth in UL 924, “Emergency Lighting and Power
Equipment - Supplement C,” and are UL LISTED for installation inside of or on top
of the fixture. Emergency illumination exceeds the 90-minute requirement of the
National Fire Protection Association’s Life Safety Code (NFPA-LSC), the National
Electrical Code (NEC) and UL.
Damp location models are compatible with a variety of fluorescent
lamps, including U-shaped, HO,
VHO, circline and energy-saving tubular
fluorescent lamps, as well as with 2-pin and 4-pin compact fluorescent lamps.
Application Bodine damp location emergency ballasts convert partially protected exterior and interior fluorescent fixtures subject to moderate degrees of moisture into unobtrusive emergency lighting fixtures. These emergency ballasts are UL LISTED for damp locations where the ambient temperature for the emergency ballast is 0°C minimum, +50°C maximum.
Damp location models are compatible with a variety of fluorescent lamps, including U-shaped, HO, VHO, circline and energy-saving tubular fluorescent lamps, as well as with 2-pin and 4-pin compact fluorescent lamps.
Damp location ballasts are compatible with most electronic, standard, energy-saving and dimming AC ballasts. Models for one- or two-lamp operation are available. For questions concerning specific lamp/ballast compatibility, please call Tech Support at 888-263-4638.
Select Bodine damp location models are UL LISTED for use in sealed and gasketed fixtures.
Note: See Damp Location Product Summary on the back page for individual product details.
InstallationDamp location models do not affect normal fixture operation and may be used in either a switched or unswitched fixture. In switched fixtures, an unswitched lead must be connected to the emergency ballast ahead of the wall switch. The emergency ballast may be remotely installed up to one half the distance the AC ballast manufacturer recommends remoting the AC ballast from the lamp or up to 50 feet, whichever is less.
Note: If a damp location ballast is used in an emergency-only fixture, no AC ballast is necessary.
bodine®
bodine®
About The ManufacturerSince 1962, The Bodine Company, Inc., has responded to advancements in lamp/ballast technologies by developing a complete line of tubular and compact fluorescent emergency ballasts for a variety of emergency lighting applications. Products are sold through a nationwide network of manufacturers’ representatives and electrical distributors for field retrofit or directly to lighting fixture manufacturers for factory installation only. The Bodine Company is a member of the Illuminating Engineering Society of North America (IESNA) and the National Electrical Manufacturers Association (NEMA).
All models are 120/277 VAC dual voltage input and suitable for damp locations where the ambient temperature for the emergency ballast is 0°C minimum, +50°C maximum. Damp location models are not recommended for heated air outlets or hazardous location fixtures. For alternate configurations and UL Component Recognized models for hazardous location fixtures, please contact Bodine. For complete technical specifications, please refer to the appropriate dry location counterpart specification sheet.* The BDL500 and BDL600 are UL LISTED for use in sealed and gasketed fixtures.
OperationWhen AC power fails, the damp location emergency ballast automatically switches to emergency mode, keeping either one or two lamps illuminated at a reduced lumen output for a minimum of 90 minutes. If two-lamp operation is selected, lumen output is evenly distributed between the lamps. When AC power is restored, the damp location emergency ballast returns to the charging mode.
Model # Lumen Output # Lamps Operated Type of Lamps Operated Full Warranty
BDL500* (B50) 1100 - 1400 lm 217 W - 215 W (2’-8’) T8, T10 or T12
4-Pin Long Compact5 Years
BDL600* (B60) 600 - 700 lm 217 W - 215 W (2’-8’) T8, T10 or T12
4-Pin Long Compact3 Years
BDL700 (B70A) 600 - 700 lm 117 W - 215 W (2’-8’) T8, T10 or T12
4-Pin Long Compact3 Years
BDL900 (B90) 500 - 600 lm 117 W - 40 W (2’-4’) T8, T10 or T12
4-Pin Long Compact1 Year
BDL94C (B94C) 300 - 750 lm 26 W - 42 W
(4-Pin) Twin, Quad or Triple Twin-Tube2 Years
BDL426 (B426) 450 - 950 lm 2 2 Years
BDL463 (B463) 300 - 650 lm 110 W - 26 W
(2-Pin) Quad or Triple Twin-Tube2 Years
BDL413 (B413) 200 - 625 lm 15 W - 13 W
(2-Pin) Twin or Quad Tube2 Years
10 W - 26 W (2-Pin) Twin, Quad or Triple Twin-Tube
Meeting Global Demands for Superior Technology cBDL Series
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
bodine
®
! IMPORTANT SAFEGUARDS !WHEN USING ELECTRICAL EQUIPMENT, BASICSAFETY PRECAUTIONS SHOULD ALWAYS BEFOLLOWED, INCLUDING THE FOLLOWING:
SAVE THESE INSTRUCTIONS
THIS PRODUCT CONTAINS A RECHARGEABLE NICKEL-CADMIUM BATTERY.THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.
©The Bodine Company, Inc.236 Mt. Pleasant Rd. • Collierville, TN 38017-2752 • Tech Support 888-263-4638 • Fax 901-854-1630 • www.bodine.com
76000201
FLUORESCENT EMERGENCY BALLAST
Installation Instructions
1. To prevent high voltage from being present on red & yellow output leads prior to installation, inverterconnector must be open. Do not join inverter connector until installation is complete and AC power issupplied to the emergency ballast.
2. This product is for use with two 17- 40 W (2' - 4') T8, T10 or T12 fluorescent lamps; one 25 - 215 W (2' - 8')T8, T10 or T12 fluorescent lamp; two 13 - 26 W (4-pin) compact fluorescent lamps without integral starters;or one 18 - 42 W (4-pin) compact fluorescent lamp without integral starter.
3. Make sure all connections are in accordance with the National Electrical Code and any local regulations.4. To reduce the risk of electric shock, disconnect both normal and emergency power supplies and inverter
connector of the emergency ballast before servicing.5. This emergency ballast is for factory or field installation in either the ballast channel or on top of the fixture.6. This product is suitable for damp locations where the ambient temperature is 0°C minimum, +50°C
maximum. Product is also suitable for installation in sealed and gasketed fixtures. Product is not suitable forheated air outlets and wet or hazardous locations.
7. An unswitched AC power source is required (120 through 277 VAC, 50/60 Hz).8. Do not install near gas or electric heaters.9. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field replaceable.
Contact the manufacturer for information on service.10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.11. Do not use this product for other than intended use.12. Servicing should be performed by qualified service personnel.
BDL60U
Ni-Cd
UNIVERSAL INPUT
04/25/05
STEP #1 INSTALLING THE EMERGENCY BALLAST> Disconnect AC power from the fixture. Remove the ballast channel cover and install the emergency
ballast either in the ballast channel or on top of the fixture.
> Depending on the type of fixture in use, install emergency ballast using one of the methods
illustrated below.
* For installation on top of the fixture, wire bundle covers (RMC-60) may be required by state or local codes. These covers are available from themanufacturer as an accessory kit and must be ordered separately. Call your local distributor or the factory for complete information.
Inside Ballast Channel Inside Strip Fixture On Top of Fixture
WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED & YELLOWOUTPUT LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN.DO NOT JOIN INVERTER CONNECTOR UNTIL INSTALLATION IS COMPLETE AND ACPOWER IS SUPPLIED TO THE EMERGENCY BALLAST.
STEP #2 INSTALLING THE TEST SWITCH> Refer to the illustrations above and install the test switch
through the ballast channel cover of a troffer or through the
side of a strip fixture.
> Drill a 1/2" hole and install the switch as shown.
> Refer to the diagrams below and wire the test switch so that it
removes AC power from both the emergency ballast and the AC
ballast at the same time.
INSTALLATION
NOTE: Make sure that the necessary branch circuit wiring is available. An unswitchedsource of power is required. The emergency ballast must be fed from the samebranch circuit as the AC ballast.
*
UNSWITCHED FIXTURE SWITCHED FIXTURE
Fixture
Toggle Switch
Hex Nut
Hex Nut
Test Switch
Leads
Leads
Thro
w to
Tes
t
BLACK
WHITE
BLACK
WHITE
BLACK
RED
BLACK
RED
HOT ACBALLAST
EMERGENCYBALLAST
COM
TEST SWITCH
BLACK
WHITE
BLACK
WHITE
BLACK
RED
BLACK
RED
HOT
COM
TEST SWITCH
WALL SWITCH
ACBALLAST
EMERGENCYBALLAST
NOTE: After installing the charging indicator light and test switch, mark each with the appropriate label.
INSTALLATION
TROFFER STYLE FIXTURE STRIP STYLE FIXTURE
When AC power is applied, the charging indicator light is illuminated, indicating that the battery is being charged. When power
fails, the emergency ballast automatically switches to emergency power (internal battery), operating either one or two lamps at
reduced illumination for a minimum of 90 minutes. This emergency ballast also operates one 32 W T8 fluorescent lamp in
emergency mode for a minimum of 120 minutes.
Although no routine maintenance is required to keep the emergency ballast functional, it should be checked periodically to
ensure that it is working. The following schedule is recommended:
1. Visually inspect the charging indicator light monthly. It should be illuminated.
2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds. Either one or
two lamps should operate at reduced illumination.
3. Conduct a 90-minute discharge test once a year. Either one or two lamps should operate at reduced
illumination for at least 90 minutes.
! REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL !
STEP #3
STEP #4 WIRING THE EMERGENCY BALLAST> Determine the type of AC ballast installed in the fixture.
> Select the appropriate wiring diagram on back to connect the emergency ballast to the AC ballast and lamp(s).
Make sure all connections are in accordance with the National Electrical Code and any local regulations.
> After installation is complete, supply AC power to the emergency ballast and join the inverter connector.
> At this point, power should be connected to both the AC ballast and the emergency ballast and the Charging
Indicator Light should illuminate indicating the battery is charging.
> A short-term discharge test may be conducted after the emergency ballast has been charging for one hour. Charge
for 24 hours before conducting a long-term discharge test. Refer to OPERATION.
> In a readily visible location, attach the label "CAUTION - This Unit Has More Than One Power Connection Point.
To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And Emergency
Power Supplies Before Servicing."
INSTALLING THE CHARGING INDICATOR LIGHT> Install the CHARGING INDICATOR LIGHT as shown in the illustration below so that it will be visible after the
fixture is installed.
OPERATION
MAINTENANCE
EmergencyBallast
Leads to Charging Indicator Light
7/8" Bushing Inserted into Ballast ChannelCover
1/2" White Bushing to Hold ChargingIndicator Light
BallastChannel
Cover
7/8" Punch
Plastic Tubing(please cut to
necessary length)
Charging Indicator Light Fixture Lens
ChargingIndicator
Light
1/2" WhiteBushing
Violet (+)
Brown (–)
Violet (+)
Brown (–)
1/2" WhiteBushing
5/8" BlackBushing
5/8" BlackBushing
1/2" Punch
Fixture Fixture
ChargingIndicator
Light
04/25/0576000201
FIG 15a-UV THREE (3) LAMP RAPID START BALLAST
FIG 3a-UV TWO (2) LAMP RAPID START BALLASTFIG 36a-UV TWO (2) LAMP INSTANT START BALLAST
FIG 7a-UV THREE (3) LAMP INSTANT START BALLAST
FIG 14a-UV FOUR (4) LAMP INSTANT START BALLAST FIG 51a-UV FOUR (4) LAMP RAPID START BALLAST
FIG 1a-UV ONE (1) 17-215 W LAMP WITHOUT AC BALLAST
WIRING DIAGRAMS for EMERGENCY-ONLY fixturesFIG 1b-UV TWO (2) 17-40 W LAMPS WITHOUT AC BALLAST
FIG 36b-UV TWO (2) LAMP INSTANT START BALLAST FIG 3b-UV TWO (2) LAMP RAPID START BALLAST
FIG 7b-UV THREE (3) LAMP INSTANT START BALLAST FIG 14b-UV FOUR (4) LAMP INSTANT START BALLAST
LAMP 1
LAMP 2 (EMERGENCY)
BLACKWHITE
LINE
RED
BLUEBLUE
BLUEBLUE/WHT
YELL/BLKYELLOW
RED
RED WHITE
INVERTERCONNECTOR
BLACKWHITE
VIOLETBROWN
COMEMERGENCYBALLAST
ACBALLAST
CHARGINGINDICATOR
LIGHT
TO UNSWITCHED AC BLACKWHITE
YELLOWYELLOW
LINE
REDRED
BLUEBLUE
BLUEBLUE/WHTYELL/BLKYELLOW
RED
RED WHITE
INVERTERCONNECTOR
BLACKWHITE
VIOLETBROWN
COMEMERGENCYBALLAST
ACBALLAST
CHARGINGINDICATOR
LIGHT
TO UNSWITCHED AC
LAMP 1
LAMP 2 (EMERGENCY)
BLACKWHITE
LINEBLUE
BLUE/WHTYELL/BLKYELLOW
RED
RED WHITE
INVERTERCONNECTOR
BLACKWHITE
VIOLETBROWN
COMEMERGENCYBALLAST
ACBALLAST
CHARGINGINDICATOR
LIGHT
orYELL
RED
BLUEBLUEBLUE
TO UNSWITCHED AC
(EMERGENCY)LAMP 3
LAMP 2
LAMP 1
(EMERGENCY)LAMP 3
LAMP 2
LAMP 1
BLUEBLUE/WHTYELL/BLKYELLOW
RED
RED WHITE
INVERTERCONNECTOR
BLACKWHITE
VIOLETBROWN
COMEMERGENCYBALLAST
BLACKWHITE
YELLOWYELLOW
LINE
REDRED
BLUE/WHTBLUE/WHT
BLUEBLUE
CHARGINGINDICATOR
LIGHT
TO UNSWITCHED AC
ACBALLAST
LAMP 3
LAMP 2
LAMP 1
(EMERGENCY)LAMP 4
BLUEBLUE/WHTYELL/BLKYELLOW
RED
RED WHITE
INVERTERCONNECTOR
BLACKWHITE
VIOLETBROWN
COMEMERGENCYBALLAST
BLACKWHITE
YELLOWYELLOW
LINE
REDRED
BLUEBLUE
CHARGINGINDICATOR
LIGHT
TO UNSWITCHED AC
ACBALLAST
LAMP 1
LAMP 2
LAMP 3
LAMP 4
BLACKWHITE
YELLOWYELLOWBROWNBROWN
LINEREDREDBLUE/WHTBLUE/WHTBLUEBLUE
BLUEBLUE/WHT
YELL/BLKYELLOW
RED
RED WHITE
INVERTERCONNECTOR
EMERGENCYBALLAST
ACBALLAST
BLACKWHITE
VIOLETBROWN
COM
CHARGINGINDICATOR
LIGHT
TO UNSWITCHED AC
BLACKWHITE
LINE
RED
BLUEBLUE
BLUE
BLUE/WHTYELL/BLKYELLOW
RED
RED WHITE
INVERTERCONNECTOR
BLACKWHITE
VIOLETBROWN
COMEMERGENCYBALLAST
ACBALLAST
CHARGINGINDICATOR
LIGHT
TO UNSWITCHED HOT
LAMP 2
LAMP 1 LAMP 2
BLACKWHITE
YELLOWYELLOW
LINE
REDRED
BLUEBLUE
BLUEBLUE/WHT
YELL/BLKYELLOW
RED
RED WHITE
INVERTERCONNECTOR
BLACKWHITE
VIOLETBROWN
COMEMERGENCYBALLAST
ACBALLAST
CHARGINGINDICATOR
LIGHT
TO UNSWITCHED HOT
LAMP 1
LAMP 3 (EMERGENCY)
LAMP 2 (EMERGENCY)
BLACKWHITE
LINEBLUE
BLUE/WHTYELL/BLKYELLOW
RED
RED WHITE
INVERTERCONNECTOR
BLACKWHITE
VIOLETBROWN
COMEMERGENCYBALLAST
ACBALLAST
CHARGINGINDICATOR
LIGHT
orYELL
RED
BLUEBLUEBLUE
TO UNSWITCHED AC
LAMP 1
LAMP 2
LAMP 3
LAMP 4 (EMERGENCY)
(EMERGENCY)
BLACKWHITE
YELLOWYELLOW
LINE
REDRED
BLUE
BLUE/WHTYELL/BLKYELLOW
RED
RED WHITE
INVERTERCONNECTOR
EMERGENCYBALLAST
ACBALLAST
BLUEBLUE
BLACKWHITE
VIOLETBROWN
COM
CHARGINGINDICATOR
LIGHT
TO UNSWITCHED AC
LAMP
BLUEBLUE/WHT
YELL/BLKYELLOW
RED
RED WHITE
INVERTERCONNECTOR
EMERGENCYBALLAST
CAPCAP
BLACKWHITE
VIOLETBROWN
COM
CHARGINGINDICATOR
LIGHT
TO UNSWITCHED AC BLUEBLUE/WHT
YELL/BLKYELLOW
RED
RED WHITE
INVERTERCONNECTOR
EMERGENCYBALLAST
CAPCAP
LAMP
LAMP
BLACKWHITE
VIOLETBROWN
COM
CHARGINGINDICATOR
LIGHT
TO UNSWITCHED AC
EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUITTYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.
WIRING DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION
WIRING DIAGRAMS for 2-LAMP EMERGENCY OPERATION (2 -́ 4 ,́ 17- 40 W lamps only)