Upload
mvbi
View
213
Download
0
Embed Size (px)
Citation preview
8/13/2019 Baracu- Theoretical Evaluations of the Natural Infiltration of the Air in Buildings, 2013, CIEM_S2_3
1/8
CIEM 2013
THEORETICAL EVALUATIONS OF THE NATURAL
INFILTRATION OF THE AIR IN BUILDINGS
TudorBARACU1, CatalinTEODOSIU2,
Marius-Victor BIRSAN3, AdrianBADEA4
Heat loss throughairinfiltrationcan reach50% of totalin a buildingfrom the
interactionwith the external environment. Tolimitor
controlairinfiltrationinbuildingsrequires acorrect estimate of them based onseveral
models. From thetechnicalliteratureare foundvariousevaluation algorithmsstartingfromtheusual"rule of practice" to rigorous analyticalalgorithms. This studyaims
atpresentingvariousexistingmodelsfor estimatingair leakage, and also it is builta new
algorithmto evaluate thenatural infiltrationof the air through the envelope, taking inconsideration the cyclicvariation of theatmospheric pressure.
Keywords: Natural Infiltration of the Air, Air Leakage, Air Infiltration
1. Introduction
Naturalairinfiltrationproblemappearedafterthe
buildingenergyconcernsbecame moreintenseas a result ofthe 1973 oilcrisis. In
order to evaluatescientificallythe aeraulicbehaviorof a building, it was inventedin1977 initially in Sweden the Blower Window as a research tool, then in USA
was found that using the equipment"Blower Door" is more practical for
meteringair exchangeinterms ofa given pressure difference.
In 1977 Esbensen and Korsgaard concluded that buildings were not so
tight as they were assumed, finding that the number of air changes per hour after
measurements was 5 times higher [1].
In the same year, GautamDutt make calculations for estimating heat loss in
buildings from New Jersey, and in 1979 published in the "New York Times" that
at measurements on some buildings the heat loss is 3 ... 7 times more than
estimation calculations [2].
The problem of estimating air leakage in natural conditions based oninformation obtained from pressure tests resulted in an interest to researchers, but
so far are mainly empirical formulas due to nonlinearity of the phenomenon and
the diversity of ways and surfaces of interacting between the and outdoor. There
1PhDc, University POLITEHNICA of Bucharest, Romania, e-mail: [email protected]
2Prof. Dr., Technical University of Civil Engineering, e-mail: [email protected]
3PhD., National Meteorological Administration, Romania, e-mail:[email protected]
4Prof. Dr., University POLITEHNICA of Bucharest, Romania, e-mail: [email protected]
8/13/2019 Baracu- Theoretical Evaluations of the Natural Infiltration of the Air in Buildings, 2013, CIEM_S2_3
2/8
Tudor Baracu, CatalinTeodosiu, Marius-Victor Birsan, Adrian Badea
are also analytical approaches having as example the evaluations of Mattson
(2007) considering the simplified case of initial pressure difference that is
equilibratedin time by interaction building- environment [3].
Lee et al. (2001) [4] prepared an installation to study airtightness
measurement with transient methods and succeeded to obtained also the
differential equation of the process, finally obtaining close results in comparisons.
This study aims to present theoretical approaches that describe the air
change between building and exterior. It prepares the ground of more detailed
analysis that will follow after the issues of some special defined pressure tests at
the Passive House POLITEHNICA from Bucharest. At that location are already
done measurements [5] according to standard EN13829 [6] and it is also in the
view a new approach that will consider also the time between successive pressurepoints in the process of free equilibration of the pressure difference house-
environment.In [7] was published also pressure tests for a building with detailed
information of empirical procedures.
2.Estimations of the natural infiltration of the air
In this section it is underlined the state of the researches involving the
evaluation of natural air leakage and later is described a new algorithm that is
using to the power law of the air leakage in buildings.
Sherman (1987) [8] considers a relation ofthe natural infiltration of the airas air changes per hour
(1)
where is a correlation factor for which Sherman [8] formula:
(2)
where is an climatic factor function of temperature and wind,
factor of height (given in tables) and is a factor
of shading to the wind. In this way can be obtained the range of the values that
can be taken by correlation factor.
(3)
From various measurements data was found that the most frequent value
of is centered around 20.
8/13/2019 Baracu- Theoretical Evaluations of the Natural Infiltration of the Air in Buildings, 2013, CIEM_S2_3
3/8
Theoretical evaluations of the natural infiltration of the air in buildings
Those empirical formulas have to be taken in consideration only as a
simple reference because it is not published explicitly the methods that drived to
them.
An ASHRAE Addendum [9] present also a method of determination of the
air leakage normalized for a year.
(4)
where NL is normalized leakage, a factor of weather and shielding and
floors area. It is also interesting that the addendum offer a balanced approach,
such that the necessary ventilation rate takes in consideration the average
infiltration:
(5)
Awbi (2003) [9] indicates formula
(6)
Also it is cited the result of Building Research Establishment [10] obtained
by gas tracing test and statistical processing of data available for non-domestic
buildings
(7)
Another approach is to estimate the natural air leakage based on climatic
data containing atmospheric pressure. In [11] is described a method that
considered power law of the air leakage and atmospheric pressure having a simple
sinusoidal cyclic variation. There was obtained finally that
(8)
where is a coefficient that can be calibrated according to the measurements.
That algorithm is more complete if it is considered a normalized value by
RMS method
(9)
8/13/2019 Baracu- Theoretical Evaluations of the Natural Infiltration of the Air in Buildings, 2013, CIEM_S2_3
4/8
Tudor Baracu, CatalinTeodosiu, Marius-Victor Birsan, Adrian Badea
where is the daily amplitude of pressure along of a day with
.
In this way is obtained a slightly different expression
(10)
wherefmis also a coefficient that have to be calibrated by measurements.
It can be considered a RMS normalization where mechanical power is
analogical to the electric power in alternating current along of a period of
variation.
(11)
(12)
a) b)Fig. 1 Atmospheric pressure along of the year 2012:a) natural variation (Source: National
Meteorological Administration, Romania); b) parametric variation
If it is analyzed the atmospheric pressure along of a year (fig. 1a) it is
found that can be used a parametric form (fig. 2b) that approximate and reproduce
it with a good accuracy. This parametric form is more suitable for mathematical
8/13/2019 Baracu- Theoretical Evaluations of the Natural Infiltration of the Air in Buildings, 2013, CIEM_S2_3
5/8
Theoretical evaluations of the natural infiltration of the air in buildings
analysis and also gives in a simplistic manner the trends of atmospheric pressure
variation. Fig. 2b is the representation of the equation:
(13)
In this way, the variation of the pressure along of a year has mainly 3
cyclic components with their initial phases , , and periods , and
. However, in the equations solved in this study it is used an simplified
parametric form
(14)
The most quantifiable situations of air leakage are: pressure difference
between two faces of a building (example: one face being upwind and the other
downwind) such that in steady regime the flow rate that goes in is equal to the
flow rate that goes out; an initial pressure difference indoor-outdoor that
diminishes progressively after the building is put in interaction with the
environment; pressure difference due created by the cyclic outdoor pressure
variation.
Mattson (2007) [3] proposed a differential equation of the air leakageconsidering an initial known pressure difference outdoor-indoor.
(15)
or, in a simple form
(16)
Resolving the equation he found the solution
(17)
In this study is proposed a generalization of Mattsons approach
considering not only a pressure equilibration after an initial disequilibrium but an
active and cyclic action (in simplified sinusoidal form) of the daily outdoor
pressure.
8/13/2019 Baracu- Theoretical Evaluations of the Natural Infiltration of the Air in Buildings, 2013, CIEM_S2_3
6/8
Tudor Baracu, CatalinTeodosiu, Marius-Victor Birsan, Adrian Badea
Equation (13) had shown earlier three main cyclic components of
atmosphere pressure along of the year, and in order to simplify the problem will
be considered only the daily variation. Because of the slow variation along of the
day with relatively small amplitude (about 500 Pa) the regime of air flow in the
infiltration process it is laminar.
The equation will have the general form
(18)
Exponent aof the power law of air leakage has values in the range of
0.5-1.0 and the value a=2/3 is the most common. The problem is that for non-
integer values of a, like 1/2 or 2/3, the differential equation is non-resolvable byquadrature methods. The only way to find a parametric solution for the equation
(18) is to consider value a=1, the upper limit of the exponent.
(19)
where it is considered that initially the indoor and outdoor pressure are the same
(pi=pe=pm), so
(20)
Firstly it is solved the linear differential equation
(21)
obtainingthe integrating factor
(22)
is obtained the general solution
(23)
and applying initial condition gives
8/13/2019 Baracu- Theoretical Evaluations of the Natural Infiltration of the Air in Buildings, 2013, CIEM_S2_3
7/8
Theoretical evaluations of the natural infiltration of the air in buildings
(24)
For a given exponent a, the pressure difference will be considered as the
pressure difference for a=1 corrected by a factor fa that can be calibrated by
experimental measurements.
(25)
This article, by its approaches prepares the theoretical background of the
practical tests that will be issued later. It is aimed in the end to be done
comparative analysis, calibrations of the theoretical results from the
measurements.
6. Conclusions
In this study was presented empirical formula that evaluate the air leakage
of the buildings normalized for long periods (usually one year) published by
several authors. Additionally, it is remarked an analytic approach of Mattson for
simplified physical conditions of air leakage.
The empirical data of atmospheric pressure was parameterized in order toobtain a sinusoidal expression of it and to be able to use it in the differential
equation of air leakage.
Atmospheric pressure have relatively slow variation along of the time of a
day and this fact conducted to the assumption that the regime of air leakage
through envelope of the building is laminar, a thing that is different from the
standard Pa, pressure tests where the regime is turbulent especially for pressure
differences like 50 Pa, 75 Pa.
In this paper was adapted and completed the approach of Mattson for more
realistic outdoor conditions like the cyclic variation of the atmospheric pressure. It
was assumed a value a=1 of the exponent of power low in order to obtain a
solvable differential equation. The solution of the differential equation will becorrected by a factor that will take in consideration empirical measurements.
There are prepared the analytical instruments of evaluation of the air
leakage of a building and additionally are planned some pressure tests to the
Passive House POLITEHNICA where will be added new algorithms of
measurements. It will be consideredexplicitly the time in the transient process of
air exchange building-environment while are passed through different pressure
points by the indoor air in the process of free equalization with the outdoor
conditions.
8/13/2019 Baracu- Theoretical Evaluations of the Natural Infiltration of the Air in Buildings, 2013, CIEM_S2_3
8/8
Tudor Baracu, CatalinTeodosiu, Marius-Victor Birsan, Adrian Badea
R E F E R E N C E S
[1]. T. V. Esbensen, V. Korsgaard, Performance of Zero Energy House in Denmark, 1st GermanSolar Energy Forum 26.-28. September 1977, Hamburg, 1977
[2]. http://www.greenbuildingadvisor.com/blogs/dept/musings/blower-door-basics[3]. B. Mattsson, J. A. Claesson, Transient Pressurisation Method for Air Infiltration
Measurements of Building Envelope Components, Journal of Building Physics July 200731: 35-53, 2007
[4]. M. J. Lee, Air tightness measurement with transient methods using sudden, 2011[5]. C. Teodosiu, Determination of air permeability, Report of UTCB, 2010[6]. EN13829:2002, Thermal Performance of Buildings - Determination of air permeability of
buildings - Fan pressurisation method, Brussels, 2002
[7]. A. Damian, V. Iordache, V. Nastase, System of measurement of the permeability of thebuildings, The 15th Conference of Comfort, Efficiency, Energy Conservation and
Protection of environment, 26-28 November, Bucharest, 2008.
[8]. The Energy Conservatory, Minneapolis Blower Door- Operation Manual for Model 3 andModel 4 Systems, 2010
[9]. ASHRAE Addendum 62.2 2010, Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings, Atlanta, 2012
[10]. H. B. Awbi, Ventilation of buildings, 2 Ed., Spon Press, Taylor & Francis, London, 2003[11]. T.Baracu, V.Tanasiev, T.Mamut, C.Streche, A.Badea, A transient thermal analysis by
thermal networks of the Passive House POLITEHNICA from Bucharest, International
Journal of Sustainable Building Technology and Urban Development, Taylor & Francis,
London - Seoul, 2013.