Click here to load reader
Upload
laercio-marques
View
210
Download
70
Tags:
Embed Size (px)
DESCRIPTION
BACnet Network Set Up and Troubleshooting
Citation preview
125-5103 Siemens Industry, Inc. 2013-11-14 Restricted
BACnet
Network Setup and
Troubleshooting Manual
3
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Table of contents
About this Manual .............................................................................................................. 5
Chapter 1 - BACnet Basics ............................................................................................... 6
BACnet Internetwork ............................................................................................................ 6
BACnet Network Numbers ................................................................................................... 6
BACnet Device Instance ...................................................................................................... 7
BACnet Data Link Layer ...................................................................................................... 7
BBMD - BACnet/IP Broadcast Management Device ........................................................... 8
Foreign Devices ................................................................................................................... 8
BACnet Objects and Properties ........................................................................................... 8
Chapter 2 - BACnet Firmware/Hardware ....................................................................... 10
Firmware Compatibility Chart ............................................................................................ 10
Hardware Overview ........................................................................................................... 11
Maximum Number of MS/TP Devices per network ........................................................... 12
Chapter 3 - BACnet IP ALN ............................................................................................. 13
Overview ............................................................................................................................ 13
Standard BACnet/IP Networks .......................................................................................... 13
BBMDs ............................................................................................................................ 13
Foreign Device ................................................................................................................... 16
Setting or Modifying the Field Panel IP Configuration ....................................................... 17
Chapter 4 - BACnet MS/TP ALN ..................................................................................... 21
Overview ............................................................................................................................ 21
Rules for BACnet MS/TP ALN ........................................................................................... 22
Adding a BACnet Field Panel as a MS/TP ALN Node ...................................................... 22
Configuring BACnet MS/TP Network Type ........................................................ 22
Modifying BACnet Device Settings .................................................................... 22
Modifying MS/TP ALN Settings .......................................................................... 24
Chapter 5 - BACnet MS/TP FLN ...................................................................................... 26
Overview ............................................................................................................................ 26
MS/TP FLN versus MS/TP ALN ........................................................................................ 27
Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network ........... 28
Configuring BACnet MS/TP Network Type ........................................................ 28
Configuring a Field Panel as a MS/TP Device ................................................... 28
Adding a BACnet TEC or a Third-party MS/TP Device to a BACnet Field Panel30
Cimetrics MS/TP Router Set Up for Communication with BACnet TECs .......... 36
Chapter 6 - Troubleshooting BACnet Network Using WireShark ............................... 45
Overview ............................................................................................................................ 45
Setting Up Wireshark Capture Software ............................................................................ 45
Starting Wireshark ............................................................................................................. 47
4
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Saving Wireshark Capture ................................................................................................. 51
Wireshark Display Filters ................................................................................................... 52
Building Wireshark Display Filters ..................................................................................... 54
Displaying Wireshark Statistics .......................................................................................... 57
Wireshark Examples .......................................................................................................... 72
Chapter 7 - Wiring Guideline for MS/TP Network ......................................................... 74
Overview ............................................................................................................................ 74
MS/TP 3-Wire Specification* ............................................................................................. 74
3-Wire Network Terminator (550-975P100, Pkg. of 100) .................................................. 75
3-Wire Network RS-485 Reference Terminator (550-974P10 Pkg. of 10) ........................ 76
Network Repeater for 3-Wire Networks ............................................................................. 76
MS/TP 2-Wire Specification ............................................................................................... 78
About this Manual
5
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
About this Manual This manual is intended to help you understand, commission, and troubleshoot the
Building Automation and Control networks (BACnet) standard data communication
protocol in the APOGEE Building Automation System. The networks that are not
configured properly may results in a variety of BACnet communication issues.
Here is a list of useful documents to help with understanding/configuring BACnet at the
beginning of the manual.
BACnet Application Guide (125-1984)
APOGEE Wiring Guidelines for Field Panels and Equipment Controllers (125-3002)
PXC Modular Series for BACnet Networks Technical Specification Sheet (149-487)
PXC Compact Series for BACnet Networks Technical Specification Sheet (149-206)
PXC-24 Unitary Equipment Controller Technical Specification Sheet (149-837)
Siemens MS/TP Point Pick-up Module Technical Specification Sheet (149-220)
PXM10T and PXM10S Operator Display for Siemens Compact and Modular Controllers Technical Specification Sheet (149-210)
Chapter 1 - BACnet Basics BACnet Internetwork
6
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Chapter 1 - BACnet Basics
BACnet Internetwork A BACnet internetwork is two or more BACnet networks setup to communicate to each
other. The BACnet networks are connected to each other by BACnet routers. There
must only be one path between the two BACnet devices on a BACnet internetwork.
BACnet Network Numbers Each BACnet network number in a BACnet internetwork must be unique. The range for
BACnet network numbers is 1 through 65534.
If the jobsite does not have a predefined scheme, use the following BACnet network
numbering scheme which is based on Building Field Panel.
NOTE:
Use BACnet Network #1 for the BACnet/IP backbone.
For MSTP FLNs, break the BACnet network range (1 through 65534) into two sections
BBBFF where
BBB is the building number (001 through 418)
FF is the Field Panel number (01 through 99)
Example
Building 65, Field Panel 43 with a MSTP FLN.
The BACnet/IP network number for Building 65 Panel 43 is 1.
The MS/TP network number for Building 65 Panel 43 is 6543.
Example BACnet Network.
Chapter 1 - BACnet Basics BACnet Device Instance
7
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
BACnet Device Instance Each BACnet device must have a unique Device Instance in a BACnet internetwork.
The range for Device Instance numbers is 0 4194302.
If the jobsite does not have a predefined scheme, use the following Device Instance
numbering scheme which is based on Building Field Panel MSTP Device.
Break the BACnet Device Instance range (0 through 4194302) into three sections
BBBFFMM where
BBB is the building number (001 through 418)
FF is the Field Panel number (01 through 99)
MM is the MSTP/FLN Device number (01 through 99)
Example
Building 65, Field Panel 43 with a MSTP TEC 21.
The Field Panel would be Device Instance 654300.
MSTP TEC 21 would be Device Instance 654321.
BACnet Data Link Layer BACnet can communicate over various datalinks. The datalinks that BACnet supports
are BACnet/IP, Ethernet, ARCNET, PTP, MS/TP, ZigBee, and LonTalk.
Some of the common protocols are:
IP
Uses the IP protocol
Controller to controller
Controller to HMI
Some field devices
Ethernet 802.3
Raw Ethernet Packets
MS/TP
Field Devices
NOTE:
Native BACnet means that a device supports that functionality/protocol without the
addition of a gateway or other module.
Chapter 1 - BACnet Basics BBMD - BACnet/IP Broadcast Management Device
8
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
BBMD - BACnet/IP Broadcast Management Device A BBMD is a network application that resides inside of a BACnet/IP device. Its purpose
is to distribute BACnet broadcasts between IP subnets that would typically be blocked
by IP routers. The IP address of the BBMD device must be static.
There are two methods a BBMD may use to distribute messages, which are called 1-
Hop distribution and 2-Hop distribution.
A BBMD configured for 1-Hop distribution sends a packet with a destination
address that causes the IP Router to broadcast the message on another subnet.
The IP router needs to be configured for direct-broadcast which is not typical.
A BBMD configured for 2-Hop distribution sends a packet to another BBMD that
rebroadcasts the packet on its subnet.
NOTE:
Siemens Industry, Inc. recommends to always use 2-Hop forwarding.
Foreign Devices A foreign device is a BACnet/IP device that registers with a BBMD device to receive
BACnet broadcast messages for a set period of time. It resides on a subnet that does
not have a BBMD in it. It is typically used for BACnet/IP devices that are not permanent
on the network, like a laptop.
BACnet Objects and Properties Data inside a BACnet device is organized as a series of objects. Each object has a
type and a set of properties. There is always at least one object in a device it is used
to represent the device itself. The other objects represent the devices data.
Commonly used properties - Almost all objects you encounter will have these (and
more) properties.
Object Type:
Popular Object Types: Analog Input, Analog Output, Binary Input, Binary Output.
Instance Number:
A number that must be not be repeated for any other object of the same type. The
instance number and the object type must be unique for every object in a device.
Name:
Name of device.
Present Value:
The current value of the object. BACnet has ways of telling you if the present value is
valid it uses a property called Reliability.
Chapter 1 - BACnet Basics BACnet Objects and Properties
9
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
BACnet Services
Services are like messages and allow devices to do something.
AddListElement Service. Rarely supported
RemoveListElement Service. Rarely supported
CreateObject Service. Rarely supported
DeleteObject Service. Rarely supported
ReadProperty Service. Always Supported
ReadPropertyConditional Service. Rarely supported - Returns a list of
objects/properties that meet the specified selection criteria. For example, all Analog
Inputs.
ReadPropertyMultiple Service. Often supported
ReadRange Service. Rarely supported
WriteProperty Service. Almost always supported
WritePropertyMultiple Service. Less often supported than ReadPropertyMultiple
Chapter 2 - BACnet Firmware/Hardware Firmware Compatibility Chart
10
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Chapter 2 - BACnet Firmware/Hardware
Firmware Compatibility Chart The following table provides a quick reference to the compatible features offered for
each revision. The left column represents the various features of the firmware, and the
top row represents the different firmware revisions. For example, Firmware Revision
3.1 supports MS/TP Routing, Remote Trending, P1BIM, DB Restore from Flash, USB,
Adapt and Wireless FLN.
Compatible Functionalities Each Firmware Revision Supports.
Firmware Rev. 3.2.5 3.2.4 3.2.3 a)
3.2.2 a) 3.2 3.1 3.0.1 3.0
UEC 16
Desigo CC support
Remote Notification
SNMP
Facility To Go
Web Server
PXM 10T/S
File System/Auto-Save
Event Enrollment
Hand-Off-Auto (HOA) b)
MS/TP Routing
Remote Trending
P1BIM
DB Restore from Flash
USB Support
Adapt
Wireless FLN
a) Firmware is designed for PXC Series controllers, the features attached to this firmware are for these
specific controllers only.
b) For PXC Compact Series controllers only.
Chapter 2 - BACnet Firmware/Hardware Hardware Overview
11
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Hardware Overview The following table provides a quick reference for hardware supported by BACnet
Firmware and the ALN and FLN options supported by each type of hardware.
Field Panel ALN FLN
PXC Compact 24
PXC Compact 16
BACnet/IP Optional depending on model requires FLN license
P1 or BACnet MS/TP (Configurable FLN: controller supports either one P1 FLN or one BACnet MS/TP FLN).
Supports up to 32 BACnet or P1 TECs on single FLN network.
BACnet MS/TP BACnet MS/TP FLN or P1 FLN not supported in combination with BACnet MS/TP ALN on PXC Compact.
UEC 16/24 BACnet MS/TP P1 or BACnet MS/TP (Configurable FLN: controller supports either one P1 FLN or one BACnet MS/TP FLN).
PXC Compact 36 BACnet/IP Optional FLN requires license for PXC 36 BASE, or included with PXC 36 with FLN and TX I/O support.
P1 or BACnet MS/TP (Configurable FLN: controller supports either two P1 FLNs or one BACnet MS/TP FLN).
Supports up to 96 BACnet TECs on single FLN network, or up to 96 P1 TECs among two FLN networks (that is, up to 48 on each of two FLN networks). Always match electrical and performance requirements to number of devices on FLN.
When FLN is configured for BACnet MS/TP, then it also supports BACnet MS/TP ALN.
BACnet MS/TP Optional FLN requires license for PXC 36 BASE, or included with PXC 36 with FLN and TX I/O support.
P1 or BACnet MS/TP (Configurable FLN: controller supports one P1 FLN or one BACnet MS/TP FLN).
PXC Modular BACnet/IP and/or BACnet MS/TP
Three P1 FLNs or one BACnet MS/TP FLN (Configurable).
Power Open Processor BACnet/IP Three P1 FLNs or one BACnet MS/TP FLN (Configurable)
Power MEC BACnet/IP Optional depending on model: Three P1 FLNs or one BACnet MS/TP FLN (Configurable)
BACnet/IP Lon-Talk
Chapter 2 - BACnet Firmware/Hardware Maximum Number of MS/TP Devices per network
12
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
The PXC Compact 36 includes (2) RS-485 connections which are marked B and A.
ALN Connection
B A
BACnet/IP MSTP ALN MSTP FLN
BACnet/IP P1 FLN (FLN2)
P1 FLN (FLN1)
BACnet MS/TP
ALN FLN
HMI prompt? S, H, F, C, A, M, M (System, Hardware, Fieldpanels, Config, Aln, Mstp, Modify)
Some of the BACnet controllers can reside on BACnet IP ALN, BACnet MS/TP ALN or
BACnet MS/TP FLN.
PXC-24 Unitary Equipment Controller
PXC-16 Unitary Equipment Controller
PXC Compact 16
PXC Compact 24
Maximum Number of MS/TP Devices per network
Field Panel Number of MSTP FLN
Ports
Max Number of MS/TP device
per FLN
Number of MSTP ALN
ports
Max Number of MS/TP ALN Devices per
ALN
PXC Modular 1 96 1 10
PXC Compact 36 1 96 1 10
PXC Compact 16/24 1 32
Power MBC/Power MEC
1 96
Chapter 3 - BACnet IP ALN Overview
13
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Chapter 3 - BACnet IP ALN
Overview BACnet/IP networks are a collection of one or more IP sub networks (IP domains) to
which a single, unique BACnet network number is assigned. You can set up the
software to function as one of the following:
A Standard BACnet/IP or MS/TP device
A BACnet Broadcast Management Device (BBMD)
A Foreign Device
Use the following guidelines to determine the appropriate setup for your installation.
UDP/IP on port 47808 (0xBAC0)
MAC address is IP Address, Port Number
Unicast, Broadcast
BACnet/IP and BACnet Ethernet Share Wire
Standard BACnet/IP Networks Set up a workstation to function as a Standard BACnet/IP device if the BACnet/IP
network does not span IP routers. A Standard BACnet/IP network consists of BACnet
devices on a single IP subnet.
BBMDs Many IP routers prevent broadcast messages from being transmitted across a Wide
Area Network (WAN). The BACnet protocol uses broadcast messages called Who-Is
and I-Am to interrogate the network and determine what other BACnet devices exist on
the BACnet Internetwork. For these broadcast messages to be transmitted across IP
routers that block such messages, one device on each IP subnet must be set up as a
BBMD.
Each BBMD has a table called a Broadcast Distribution Table (BDT) which is the same
in every BBMD in a given BACnet/IP network. If the BBMD has also been designated
to register foreign devices as described below, it will also have a Foreign Device Table
(FDT).
Chapter 3 - BACnet IP ALN BBMDs
14
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Guidelines/Recommendations
Set up only one BBMD for each IP subnet, and set up the Broadcast Distribution Table
with the IP addresses of all other BBMDs that you want the workstation to work with.
The Broadcast Distribution Tables must match the list of BACnet devices. If this is
already an operational BACnet network, BBMDs may have been set up by the Network
Administrator/Coordinator. Always consult with your Network Administrator/Coordinator
when setting up BBMDs. There must be only one BBMD per IP subnet. This BBMD
may be a workstation, Siemens field panel or a third-party panel.
BBMDs can only be configured on BACnet/IP networks.
Each workstation that acts as a BBMD for a subnet requires a fixed IP address.
All Broadcast Distribution Tables on all BBMDs on a particular BACnet/IP network
must be identical.
There are two ways that a BBMD may distribute broadcast messages to remote IP
subnets.
Sending directed broadcasts to an IP subnet (also called "one-hop" distribution).
This involves sending the message using a BACnet/IP address in which the
network portion of the address contains the subnet of the destination IP subnet and
the host portion of the address contains all 1's. While this method of distribution is
efficient, it requires that the IP router serving the destination subnet be configured
to support the passage of such directed broadcasts.
Sending directed unicasts to another BBMD (also called "two-hop" distribution).
It transmits the message using the BACnet/IP broadcast address. Since the use of
one-hop distribution requires an IP router configured to pass directed broadcasts
and the two-hop method is always available. Two-hop distribution is strongly
recommended.
Chapter 3 - BACnet IP ALN BBMDs
15
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Example
1. A field panel in IP Subnet 1 (10.0.0.x) initiates a broadcast message (such as
WHO-IS) that is received by the other BACnet device and the BBMD on the same
subnet.
2. The BBMD on IP Subnet 1 sees the broadcast and sends a directed unicast
message through the IP routers to the BBMD on IP Subnet 2 (20.0.0.x) and IP
Subnet 3 (30.0.0.x)
3. The BBMDs of IP Subnet 2 and 3 then re-broadcast the message on its respective
network.
If a new BBMD joins the network, the Insight workstation must be rebooted if its
defined as BBMD.
Chapter 3 - BACnet IP ALN Foreign Device
16
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
BBMD Configurations
BBMD on Computer
No Embedded Panels on Subnet (that is, DataCenter)
Pro:
A computer is more powerful and can handle more communications.
Cons:
Broadcast communications goes down temporarily upon reboot of a computer
Broadcast communications goes down temporarily upon modification of the
BACstac.
BBMD on Field Panel
No computer on Subnet
Pro:
No restart required for BBMD changes.
Con:
Not as powerful as a computer; might slow down control on field panel.
Foreign Device BACnet devices can be configured as a foreign device if you do not allow the Siemens
field panel to be a BBMD on their network or if a third party device is on a different
subnet and does not support the BBMD function.
May or may not support the BBMD service.
Every foreign device must be subscribed to a single BBMD on another subnet.
Communicate broadcasted message ONLY with the BBMD to which they are
individually subscribed.
Do not re-broadcast message received from their subscribed BBMD to their local
network.
Chapter 3 - BACnet IP ALN Setting or Modifying the Field Panel IP Configuration
17
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Setting or Modifying the Field Panel IP Configuration
NOTE:
The field panel coldstarts during this procedure.
HMI S, H, E, S, M (System, Hardware, Ethernet, ipSettings, Modify)
Prompt / Field Option/Entry Description
Node name Alphanumeric field Object name of the panel - must be unique on the entire system.
Site name Alpha-numeric field BACnet panels and Insight software on same IP subnet should have the same site name. The site name affects which discovery and replication times are used.
BLN name Alpha-numeric field This must be identical to the System Name of the BACnet ALN in System Profile.
DNS suffix ENTER = continue without entering data BACnet field panels do not use naming resolution.
DHCP Y DHCP is enabled DHCP server is to assign the field panels IP addresses.
N DHCP is disabled If using fixed IP addresses.
IP address Numeric field If DHCP = N, you are prompted for an IP setting. Enter the IP setting. If DHCP = Y, you are not prompted for the IP setting.
Netmask Numeric field
Gateway address IP address for the assigned gateway If there is no IP gateway, enter 0.0.0.0.
DNS 1 Enter the address of the DNS server.
This can be obtained from the sites IT department. If you do not need to specify DNS addresses, enter 0.0.0.0 for each of these.
DNS 2
DNS 3
DNS 4
Chapter 3 - BACnet IP ALN Setting or Modifying the Field Panel IP Configuration
18
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Telnet Enabled Y Telnet is enabled To allow remote HMI sessions via Telnet and to enable FTP
N Telnet is disabled Remote HMI and FTP are blocked.
Configure BACnet Y BACnet configuration options are displayed.
N Exit configuration and save or discard changes.
Configure BACnet device Y Configure BACnet Device.
Device Instance Number Numeric field. Valid values are 0 through 4,194, 302 - must be unique on the entire BACnet site. Recommended values: 7000 though 7999 for Siemens panels.
Device Location Alpha-numeric field Specify a descriptive location so the customer or other Siemens employee can locate the device.
Device Description ENTER = accept existing value Enter a device description.
Device Reserved Instance Base ENTER = accept the default of 10,000 Enter the instance number where the field panel starts creating BACnet points for FLN devices; this must be at least 10000.
COV Resubscribe Period (min) ENTER = accepts default of 30 Enter a number that identifies how often the field panel and the system will re-register for COVs.
COV Poll Rate (sec) ENTER = accepts default of 60 Enter a number, in seconds (10 to 3600) that identifies how often the field panel and the system will poll devices that do not support the Subscribe COV BACnet service.
N ENTER = default value (10000)
Enable BACnet IP ALN Y Configure the IP ALN
BACnet IP Network Number Specify a network, valid values are 1 through 65534. This network must be unique for the entire BACnet site. No other BACnet MS/TP ALN or BACnet MS/TP FLN or third-party network number may be the same.
UDP Port Accept the default BACnet UDP port, 47808. Other port may be used if required.
N No IP ALN.
Act as a Foreign Device Y A foreign device is a BACnet device (workstation or field panel) that has
Chapter 3 - BACnet IP ALN Setting or Modifying the Field Panel IP Configuration
19
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
an IP connection but does not have a BBMD or multicast router on its subnet to allow it access to BACnet broadcast messages. A foreign device enables itself to send and receive both directed and broadcast messages.
Foreign devices are only used when a BACnet device is joining a network that spans multiple IP subnets and it is only going to be on that network for a short time.
N If the BACnet network does not span multiple Networks, enter N.
Enable MSTP ALN Y If MS/TP ALN is used, enter Y and configure the next 3 parameters.
MSTP ALN Baud Rate Enter the desired baud rate. 38400 is recommended.
MSTP ALN Network Number Specify a network. Valid values are 1 through 65534. This network must be unique for the entire BACnet site. No other BACnet/IP ALN, BACnet MS/TP ALN or BACnet MS/TP FLN or third-party network number may be the same.
MSTP ALN Node Address Enter a MAC address. Valid values are 0 through 127. Address 0 is recommended .
This address is the MAC address of the BACnet/IP to BACnet MS/TP ALN router. No other device on the BACnet MS/TP ALN may have the same MAC address. Other MS/TP FLNs or MS/TP ALNs may use this address.
N Enter N unless MS/TP ALN is being used.
P1, Mstp P Select P for p1.
FLN1 Baud Rate A typical baud rate is 4800 for TECs and VFDs. If you are using P1 BIM, PXC on P1, PXMs, you can specify another baud rate.
On a PXC Modular, you will be prompted for the baud rates of all three FLNs.
FLN2 Baud Rate
FLN3 Baud Rate
Wireless Enabled (Y/N) If the FLN will be Wireless, specify Y. Otherwise, specify N.
M Select M for MS/TP FLN.
Enable MSTP FLN (Y/N) Select Y to enable the MS/TP FLN.
MSTP FLN Baud Rate Enter the desired baud rate. 38.4k is recommended
Chapter 3 - BACnet IP ALN Setting or Modifying the Field Panel IP Configuration
20
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
MSTP FLN Network Number Specify a network. Valid values are 1 through 65534. This network must be unique for the entire BACnet site.
No other BACnet/IP ALN, BACnet MS/TP ALN or BACnet MS/TP FLN or third party network number may be the same.
MSTP FLN Node Address Enter a BACnet Media Access Control (MAC) address. Valid values are 0 through 127. Address 0 is recommended. This address with be the MAC address of the BACnet/IP to BACnet MS/TP FLN router. No other device on the BACnet MS/TP FLN may have the same MAC address. Other MS/TP FLNs or MS/TP ALNs may use this address.
MSTP Keep Alive Poll Rate Enter desired time between live node scans (10 to 300 seconds) if different than the default setting.
Accept the default of 60.
MSTP FLN Discovery Poll Rate Enter the desired time between dead node scans (10 to 300 seconds) if different than default setting. Accept the default of 60.
OK to coldstart (Y/N) Y Coldstart the field panel and save the configuration.
N Do not coldstart - discard any changes.
Chapter 4 - BACnet MS/TP ALN Overview
21
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Chapter 4 - BACnet MS/TP ALN
Overview Firmware Revision 3.1 and later supports BACnet MS/TP ALN. The BACnet MS/TP
ALN configuration is supported exclusively through the PXC Modular and select PXC
Compact hardware (see PXC Modular Configuration & Sizing Guidelines (145-045)
and PXC Compact Configuration & Sizing Guidelines (145-171)). The PXC Modular
and PXC Compact 36 are the only APOGEE field panels that have simultaneous
support for BACnet/IP ALN and BACnet MS/TP ALN. Therefore, they act as a router
between BACnet/IP and BACnet MS/TP devices, objects, and properties, as specified
by the BACnet standard.
The BACnet MS/TP ALN has the following performance considerations:
In general, faster baud rates will increase performance on the network, so that 76.8
Kbps will perform faster than 19.2 Kbps, for example. However faster baud rates
do increase sensitivity to outside interference on RS-485 wiring. Every device on
the network must support and be configured for the same baud rate.
Since Siemens devices that reside on a BACnet MS/TP ALN are treated as field
panels to be backed up and monitored by the Insight workstation, network traffic
between these devices and the Insight workstation is extensive. This limits the
number of devices that may productively reside on a single BACnet MS/TP ALN
network to approximately 10 devices, depending on point counts and network
activity. Network performance may drop significantly if more than 10 Siemens field
panels are added to the MS/TP ALN.
Additional BACnet MS/TP ALN networks, with different ALN Name, may be added
without compromising network performance through an additional PXC
Modular/PXC Compact 36.
Third-party BACnet MS/TP devices may be added to a BACnet MS/TP ALN without
the consequence of excess traffic.
Each additional device on a BACnet MS/TP network that is set up as a master
(ALN devices must be MS/TP masters) creates another device to pass the token,
which takes time and decreases overall response times. Consider every additional
node on the MS/TP network as adding 1 second to the token pass response time.
Token pass times may exceed 1 second per node depending on the support of
COV and the number of points monitored.
Chapter 4 - BACnet MS/TP ALN Rules for BACnet MS/TP ALN
22
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Rules for BACnet MS/TP ALN Only PXC Modular with Firmware Revision 3.1 and later and the PXC Compact 36
BACnet field panel support the BACnet/IP ALN to BACnet MS/TP ALN router
functions.
Integration drivers are not supported as BACnet ALN routers.
Only one BACnet/IP to BACnet MS/TP router is allowed per ALN.
All BACnet MS/TP ALN devices on an ALN must be on the same physical MS/TP
segment.
A maximum of 10 Siemens field panels, including the Router, can be wired on a
single BACnet MS/TP ALN.
For example, you have two PXC Modular and two PXC Compact 36 field panels on a
BACnet IP network. Each of those supervisory controllers has nine PXC Compact
16/24 connected to the MS/TP ALN port . In this case, you must define four separate
ALNs in System Profile.
Adding a BACnet Field Panel as a MS/TP ALN Node
Configuring BACnet MS/TP Network Type
HMI S, H, F, C, E, M (System, Hardware, Fieldpanels, Config, nEttype, Modify)
Prompt / Field Option / Entry Description
Alnnode, Flnnode A Type A for Alnnode and then press ENTER
F Type F for Flnnode and then press ENTER
Ok to coldstart (Y/N) Y Type Y to coldstart the device and save the configuration changes
N Type N to cancel, all configuration changes will be lost.
Modifying BACnet Device Settings
CAUTION
If the Device Instance Number or Device Reserved Instance Base are changed, the
field panel coldstarts at the end of this procedure.
NOTE:
To accept the existing value and advance to the next entry field at any step of BACnet
configuration, press ENTER.
Chapter 4 - BACnet MS/TP ALN Adding a BACnet Field Panel as a MS/TP ALN Node
23
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
To modify BACnet device settings, type the following letters in sequence and proceed
with the steps:
HMI S, H, F, C, V, M (System, Hardware, Fieldpanels, Config, deVice, Modify)
Prompt / Field Option / Entry Description
Device Instance Number Enter the device instance number (0 through 4,194,302)
Recommended values are 7000 through
7999; must be unique throughout the
BACnet network.
Device Location Enter the device location
Device Description Enter the device description
Device Reserved Instance Base Enter the starting reserved instance
number
For more information on this parameter, see
Device Reserved Instance Base in this
section
COV Resubscribe Period (min) Enter the COV resubscribe period in
minutes
COV Poll Rate (sec) enter the COV poll rate in seconds
OK to coldstart (Y/N) This prompt only displays if you change the
Instance Number or Device Reserved
Instance Base.
Y Coldstart the device and save your
configuration changes
N Cancel the configuration
Example
>Point, Application, Time, Message, Cancel, System, passWord,
Bye? s
>Diagnostics, Users, dSt, Bacnet, Error_msgs, Hardware, Text,
Quit? h
>Fieldpanels, Ethernet, nodeNametable, Disks, Reportprinter,
Licensemanager, Quit? f
>Log, Display, Add, dElete, Modify, Config, Quit? c
>Hmi, Aln, deVice, db_fiLe, Fln, Names, Defaultlanguage, Quit? v
>Display, Modify, Quit? m
>Device Instance Number : 13933--
>Device Location : BIERMAN SUB BASEMENT---------
>Device Description : ABSORPTION CHILLER-----------
>Device Reserved Instance Base : 10000--
>COV Resubscribe Period (min) : 30--
>COV Poll Rate (sec) : 60--
Command successful
>Display, Modify, Quit? -
Chapter 4 - BACnet MS/TP ALN Adding a BACnet Field Panel as a MS/TP ALN Node
24
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Modifying MS/TP ALN Settings
NOTE:
The field panel coldstarts during this procedure.
For more information on ALN port configuration, see PXC Modular Port Configuration
and PXC Compact Port Configuration.
To modify MS/TP ALN settings, complete the following steps:
HMI S, H, F, C, A, M, M (System, Hardware, Field Panel, Config, Aln, Mstp, Modify)
NOTE:
If the MS/TP ALN is already enabled, and the BACnet/IP ALN port is either disabled
or not present on this device, the following prompt is not displayed. Under these
conditions, continue this procedure with the following step (MS/TP ALN Baud Rate
prompt).
Prompt / Field Option / Entry Description
Enable MSTP ALN (Y/N) Y Enables the MS/TP ALN port
N Disables the MS/TP ALN port
MSTP ALN Baud Rate Enter the Baud rate for this port
MSTP ALN Network Number Enter the network number for this port, or press ENTER to accept the current value, if other than 65535
The network number must be changed from the system default of 65535
MSTP ALN Node Address Enter the node address for this port
If you made any changes from existing values during this procedure, OK to coldstart (Y/N) is displayed. Do one of the following:
Y Coldstarts the device and saves your configuration changes
N Cancels the configuration
Example
>MSTP ALN Network Number : 55---
>MSTP ALN Node Address : 127
>MSTP ALN Baud Rate : 9600----
>OK to coldstart (Y/N) : y
Chapter 4 - BACnet MS/TP ALN Adding a BACnet Field Panel as a MS/TP ALN Node
25
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Devices Instance #7001 is BACnet/IP device and #7002 is BACnet MS/TP ALN device.
Both appear on same level of ALN in System Profile.
Chapter 5 - BACnet MS/TP FLN Overview
26
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Chapter 5 - BACnet MS/TP FLN
Overview Firmware Revision 3.1 or later supports BACnet MS/TP FLN configuration (not
including the BACnet MS/TP Intennjjhg vgration Driver discussed above). The BACnet
MS/TP FLN configuration is supported through the PXC Modular with the FLN
expansion module, PXC Compact with FLN port and FLN license, Power MEC with
FLN, and Power Open Processor. With Firmware Revision 3.1 or later, the FLN may
be configured in the field panel as either a BACnet MS/TP FLN or P1 FLN. When
configured for BACnet MS/TP FLN, physical FLN 1 port is used for communication and
all other FLN ports are deactivated.
The BACnet MS/TP FLN has the following performance considerations:
In general, faster baud rates will increase performance on the BACnet MS/TP
network, so that 76.8 Kbps will perform faster than 19.2 Kbps, for example.
However faster baud rates do increase sensitivity to RS-485 wiring guidelines. Also
a number of microprocessor UARTS of MS/TP device cannot accurately produce
76800 baud signals. Devices using these microprocessors might list 76800 as
supported but you may have network issue. 38.4K Kbps is strongly recommended
for MS/TP network communication.
BACnet MS/TP devices resident on a BACnet MS/TP FLN are treated as FLN
devices with point teams automatically created in the field panel. Point teams are
intended to optimize communication with application specific devices, such as
Siemens BACnet TECs.
Siemens BACnet TECs are supported by the field panel and Insight workstation
with initial values support, and drag and drop reports.
NOTE:
All Programmable TEC and BACnet TEC (Rev Bx20 series) are 1/8 load.
Each additional device on a BACnet MS/TP network that is set up as a master
creates another device to pass the token, which takes time and decreases overall
network response times. Consider every additional node on the MS/TP network as
adding 1 second to the token pass response time. Token pass times may exceed 1
second per node depending on the support of COV and the number of points
monitored. Loading a FLN with the maximum of 96 devices, response times due to
token pass may be approximately 90 seconds.
Each additional device on a BACnet MS/TP network that is set up as a slave
creates another device to poll, which takes time and decreases overall network
response times. Consider every additional node on the MS/TP network as adding 1
second to the poll time which impacts overall response time. Response times may
exceed 1 second per node depending on the number of points monitored. Loading
a FLN with the maximum of 96 devices, response times due to polling may be
approximately 90 seconds. Generally, with Siemens-only devices and low
monitoring requirements, all devices configured as slaves on the MS/TP network
perform faster than all devices configured as masters.
Chapter 5 - BACnet MS/TP FLN MS/TP FLN versus MS/TP ALN
27
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
In general, expect that BACnet MS/TP FLNs will perform slower than P1 FLNs due
to the following: increased communication requirements for BACnet MS/TP
compared to P1, lack of COV support in many BACnet MS/TP devices (including
BACnet TECs), token passing when MS/TP devices configured as masters require
additional communication time, and high volume of devices on single physical
network which adds to communication time. So despite the significant increased
speed of the BACnet MS/TP baud rate over the P1 baud rate, the actual
communication response is slower due to the factors cited above.
Based on field experience with MS/TP devices connected to a BACnet router, data
transfer speed is decreased as the number of MS/TP devices is increased. When
the number of devices exceeds 50, the data transfer speed becomes unacceptably
slow for most customers. The system may experience slow updates of points
(COVs, Alarms, etc.), and/or frequent device failures and return from failures.
Therefore, it is recommended not to connect more than 50 BACnet MS/TP devices
on a single BACnet network.
MS/TP FLN versus MS/TP ALN
Advantages
You can have more than 10 Siemens field panels reside on a MS/TP FLN whereas
you are limited to only10 Siemens field panels on a MS/TP ALN.
You want to replace a third-party controller that is on the FLN with a Siemens
BACnet field panel and use the same wiring.
With a MS/TP Driver you can add a Siemens BACnet field panel on that FLN.
Disadvantages
You cannot edit the field panels database from the Insight workstation.
The field panel cannot be restored from the workstation if it coldstarts. However, it
can restore its own database using the flash memory Autorestore feature.
If the System Name for points in the child field panel is longer than 12 characters,
then the parent panel will use the ObjectName_InstanceNumber as the name.
Chapter 5 - BACnet MS/TP FLN Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network
28
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Adding a BACnet MS/TP PXC Compact 16/24 or UEC
to a MS/TP FLN Network
NOTE:
BACnet MS/TP PXC-16/24 controller is configured as an ALN node out of factory,
opposed to UEC is configured as a FLN node out of factory.
Configuring BACnet MS/TP Network Type
HMI S, H, F, C, E, M (System, Hardware, Fieldpanels, Config, nEttype, Modify)
Prompt / Field Option / Entry Description
Alnnode, Flnnode A Type A for Alnnode and then press ENTER
F Type F for Flnnode and then press ENTER
Ok to coldstart (Y/N) Y Type Y to coldstart the device and save the configuration changes
N Type N to cancel, all configuration changes will be lost.
Configuring a Field Panel as a MS/TP Device
NOTE:
Although the UEC has a functional Ethernet port, it does not support BACnet IP ALN.
The IP connection can be used for Telnet, FTP, etc. but must be configured only if
these options are used. (See Steps 3 through 6.)
HMI S, H, E, S, M (System, Hardware, Ethernet, ipSettings, Modify)
Prompt / Field Option / Entry Description
Node name Alpha-numeric field Object name of the panel, must be unique on the entire system.
Site name Alpha-numeric field BACnet panels and Insight software on same IP subnet should have the same site name. The site name affects which discovery and replication times are used.
BLN name Alpha-numeric field This must be identical to the System Name of the BACnet ALN in System Profile.
Chapter 5 - BACnet MS/TP FLN Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network
29
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
DNS suffix ENTER = continue without entering data BACnet field panels do not use naming resolution.
DHCP Y DHCP is enabled DHCP server is to assign the field panels IP addresses.
N DHCP is disabled If using fixed IP addresses.
IP address Numeric field If DHCP = N, you are prompted for an IP setting. Enter the IP setting. If DHCP = Y, you are not prompted for the IP setting.
Telnet Enabled Y Telnet is enabled To allow remote HMI sessions via Telnet and to enable FTP
N Telnet is disabled Remote HMI and FTP are blocked.
Configure BACnet Y BACnet configuration options are displayed.
N Exit configuration and save or discard changes.
Configure BACnet device Y Configure BACnet Device.
Device Instance Number Numeric field Valid values are 0 through 4,194, 302 - must be unique on the entire BACnet site. Recommended values: 7000 through 7999 for Siemens panels.
Device Location Alpha-numeric field Specify a descriptive location so the customer or other Siemens employee can locate the device.
Device Description ENTER = accept existing value Enter a device description.
Device Reserved Instance Base ENTER = accept the default of 10,000 Enter the instance number where the field panel starts creating BACnet points for FLN devices; this must be at least 10000.
COV Resubscribe Period (min) ENTER = accepts default of 30 Enter a number that identifies how often the field panel and the system will re-register for COVs.
COV Poll Rate (sec) ENTER = accepts the default of 60 Enter a number, in seconds (10 to 3600) that identifies how often the field panel and the system will poll devices that do not support the Subscribe COV BACnet service.
N ENTER = default value (10000)
Chapter 5 - BACnet MS/TP FLN Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network
30
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Enable MSTP ALN Y If MS/TP ALN is used, enter Y and configure the next 3 parameters.
MSTP ALN Baud Rate Enter the desired baud rate. 38400 is recommended.
MSTP ALN Network Number Specify a network. Valid values are 1 through 65534. This network must be unique for the entire BACnet site. No other BACnet/IP ALN, BACnet MS/TP ALN or BACnet MS/TP FLN or third-party network number may be the same.
MSTP ALN Node Address Enter a MAC address. Valid values are 0 through 127. Address 0 is recommended.
This address with be the MAC address of the BACnet/IP to BACnet MS/TP ALN router. No other device on the BACnet MS/TP ALN may have the same MAC address. Other MS/TP FLNs or MS/TP ALNs may use this address.
N Enter N unless MS/TP ALN is being used.
OK to coldstart (Y/N) Y Coldstarts the field panel and saves the configuration.
N Do not coldstart - discard any changes.
It is strongly recommended that you enable the Auto-Save and Auto-Restore features
since the field panel is now configured as a MS/TP FLN device and can no longer
perform a database transfer with the Insight workstation.
Adding a BACnet TEC or a Third-party MS/TP Device to a
BACnet Field Panel The following procedure explains how to add a BACnet MS/TP device on the FLN of a
BACnet/IP field panel with Firmware Revision 3.1 and later. It can be performed from
the Insight workstation or from the field panels HMI prompt.
Gathering Information from the BACnet MS/TP Device
The following information is required from each BACnet MS/TP device:
MAC Address
For BACnet TECs (BTECs), the MAC address is also the value of CTLR
ADDRESS (Point 1).
MS/TP Device Instance Number
See the ID field in the BACnet Properties dialog box in WCIS.
Baud Rate
See the Baud Rate drop-down list in the BACnet Properties dialog box in WCIS.
MS/TP Node Type (slave or master)
See the MSTP Slave check box in the BACnet Properties dialog box in WCIS.
Chapter 5 - BACnet MS/TP FLN Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network
31
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
The following Figure is an example of the BTEC information displayed in the WCIS
BACnet Properties dialog box:
MAC Address = 50 (from the value of CTLR ADDRESS (Point 1))
MSTP Device Instance Number = 250205 (from the ID field)
Baud Rate = 38400 bps
MS/TP Node Type = Slave (MSTP Slave option is checked)
BACnet Properties Dialog Box
Chapter 5 - BACnet MS/TP FLN Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network
32
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Configuring the FLN for MS/TP
From the Insight Workstation
1. In System Profile, double-click BACnet/IP field panel.
2. Go to the FLN Configuration section. From the Type menu, select MS/TP.
3. Click the FLN Settings button.
The MS/TP FLN Settings dialog box displays.
4. Check Enable MS/TP FLN Port.
5. In the Baud Rate drop-down list, select the rate that matches the baud rate of the
BACnet MS/TP device. For more information, see the section Gathering Information from the BACnet MS/TP Device.
6. In the Network Number field, specify a unique number.
Valid values are 0 through 65534. This number should not be the same as the BACnet/IP Network Number or any
other network number on the site, including third-party network numbers.
The Virtual BACnet network in the Cimetrics properties has a default network number of 2. The network number cannot match any network number used for
the MS/TP FLN.
7. Leave the rest of the fields as default in the MS/TP FLN Settings dialog box and
click OK.
8. When the BACnet Field Panel Definition dialog box displays, click OK.
9. Click Yes when prompted with the following message:
The changes made to the panel definition will cause the field
panel to coldstart. Do you wish to proceed?
Chapter 5 - BACnet MS/TP FLN Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network
33
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
FLN Settings Dialog Box
From the Field Panels HMI Port
Point, Application, Time, Message, Cancel, System, passWord, Bye? s
Diagnostics, Users, dSt, Bacnet, Error_msgs, Hardware, Text, Quit? h
Fieldpanels, Ethernet, nodeNametable, Disks, Reportprinter, Licensemanager, Quit? f
Log, Display, Add, dElete, Modify, Config, Quit? c
Hmi, Aln, deVice, db_fiLe, Fln, mBus, Names, Defaultlanguage, Quit? f
fln1, fln2, fln3, Wireless, Mstp, flnType, Quit? m
Enable MSTP FLN (Y/N) : Y
Enter baud rate : 38400--- NOTE: Must be identical to the MS/TP device baud rate. See the Baud Rate drop-down list in the BACnet Properties dialog box in WCIS.
Network Number : 21--- NOTE: Must be a unique number. Valid values are 1 through 65534. This number cannot be the same as the BACnet/IP Network Number or any other Network Number on the site, including third-party network numbers.
MSTP Device Mac Address : 127 NOTE: Field panel's MAC address. Leave it as 127, unless another device on the network has a MAC address of 127.
Keep Alive Poll Rate : 60--- NOTE: Leave it as the default.
Discovery Poll Rate : 60--- NOTE: Leave it as the default.
Command successful
Chapter 5 - BACnet MS/TP FLN Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network
34
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Adding the MS/TP Device
From the Insight Workstation:
1. In System Profile, drag and drop a BACnet TEC icon to FLN 1 of the BACnet/IP
field panel.
2. Enter the parameters for the following:
- System Name and Name: Enter a descriptive name without any special
characters. It does not have to match the Name defined in Device Properties in
WCIS.
- Descriptor: (Optional) Enter a description without any special characters.
- Graphic Name: (Optional)
- Application: Select 65535 for a BTEC; otherwise, enter a number from 10000
through 11999.
- Device Instance: MS/TP Device Instance Number. For BTECs this is the value
from the ID field in WCIS.
- Network Number: Enter the MSTP Device Network Number. This number must
be identical to the Network Number defined in the MS/TP FLN Settings dialog
box in the procedure Configuring the FLN for MS/TP. Valid values are 1 through 65534. This number must not be same as the BACnet/IP Network
Number.
- BACnet MAC Address: Enter the value for the Controller Address point
obtained from WCIS in the procedure Gathering Information from the BACnet MS/TP Device. Enter the value as a decimal value.
- MS/TP Node Type: Select the same MS/TP node type as you obtained from
WCIS in the procedure Gathering Information from the BACnet MS/TP Device.
- Initial Value Priority: Select 16 Available 16.
- Save Relinquish Defaults: Select this check box for a BTEC. Clear this check
box for third-party devices.
- Password: Enter HIGH
Chapter 5 - BACnet MS/TP FLN Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network
35
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
FLN Device Definition Dialog Box
From the Field Panels HMI Port
Point, Application, Time, Message, Cancel, System, passWord, Bye? a
Ppcl, flNdevice, Quit? n
Mstp, Tec, Uc, Quit? m
Log, Display, Edit, Initvalues, Quit? e
Add, Modify, Copy, Delete, Look, Quit? a
Field Value
---------------------------------------------------------------------------
MSTP Device system name : ASB54A
MSTP Device name : ASB54A
MSTP Device Instance Number : 70011 NOTE: This is the number from the ID field in the BACnet Properties dialog box in WCIS.
Application number : XXXXX NOTE: Leave this field blank for BACnet TECs (BTECs). For third-party devices, valid values are 10000 through 11999
Descriptor : NOTE: You can enter any type of descriptor.
Access group(s) :
Field panel name : 70011 NOTE: Device Instance Number of the field panel.
Master, Slave : Slave NOTE: Can be either Slave or Master.
MSTP Device Network Number : 11 NOTE: Enter a unique number. Valid values are 1 through 65534. It cannot be the same as the BACnet/IP Network Number or any other Network Number on the site, including third-party network numbers.
Chapter 5 - BACnet MS/TP FLN Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network
36
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
MSTP Device Mac Address : 1 NOTE: For BTECs, the MAC address is also the value of CTLR ADDRESS (Point 1).
Initial Value Priority : 16 NOTE: For third-party devices, leave this field at 16.
Save Relinquish Defaults : YES NOTE: For BTECs, set this field to YES. For third-party devices, set this field to NO.
Device Init Password : HIGH
NOTE:
The field panel must be made ready for communications to occur.
Cimetrics MS/TP Router Set Up for Communication with
BACnet TECs The Cimetrics B6000 Router allows the BACnet MS/TP TEC and third-party MS/TP
devices to communicate with an Insight BACnet Client by converting BACnet/IP to
BACnet MS/TP. This following procedure covers the entire setup procedure for the
Cimetrics B6000 Router, the BACnet TEC configuration, and the Insight workstation
configuration. The MS/TP Router specifically refers to the Cimetrics B6000 BACnet MS/TP router, whereas router refers to generic BACnet routers.
The following procedures are for configuring the MS/TP Router:
Gathering Necessary Information
Wiring and Network Electrical Considerations
Setting the MS/TP Router Terminations
Connecting to the MS/TP Router with a Computer for Configuring
Configuring the MS/TP Router BACnet/IP Settings
Configuring the MS/TP Router MS/TP Settings
Confirming the MS/TP Router Settings
Configuring the BACnet TECs
Establishing Communication with the Insight workstation
The Configuring the BACnet TECs procedure may be performed before Setting the MS/TP Router Terminations through Configuring the MS/TP Router Settings (in the case that the BACnet TECs are available before the MS/TP Router).
Gathering Necessary Information
Physical Network (DNET) Setting Numbers, UDP Port Number, BTEC Object Names
and Object IDs.
Before going to the job site, be sure to obtain the BACnet TEC startup document(s) for
your application(s). Those documents are available at:
http://iknow.us.abatos.com/customsolutions/HVAC_main.asp
Beacon: https://inet.sbt.siemens.com/customsolutions/HVAC_main.asp
Chapter 5 - BACnet MS/TP FLN Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network
37
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
To configure the MS/TP Router, it is necessary to assign it two physical network
numbers, one for each of the following:
The BACnet/IP network
The MS/TP network
Cimetrics refers to the physical network numbers as DNET numbers. These DNET
numbers must be configured properly or communication cannot be established.
In addition, it is also necessary to know the UDP port number that is being used, since
this must be configured at both the router and at the Insight BACnet workstation. This
process assumes the Cimetrics router will be used in conjunction with an Insight
workstation. If it is used with another third-party system, you must find the physical
network number(s) the third-party system uses.
Physical Network (DNET) Setting Numbers and UDP Port Number
To determine which network numbers and which UDP port number to use, if there are
no third-party BACnet vendors present, do the following at the Insight workstation: This
procedure assumes you have already followed the Setting Up BACnet in the Insight
Online Documentation under Getting Started.
1. Click Start, Settings, Control Panel, and then double-click Network Connections.
2. Right-click the connection that represents the Network Interface Card that is bound
to the BACstac Protocol, and then click Properties.
3. Select Cimetrics BACstac(TM) Routing Edition v4.2 Protocol, and then click
Properties.
4. Make a note of the following:
Physical Network number for the BACnet/IP network to which you intend to
connect the router. This is located in the Network Num column. This number will be
used as the Routers BACnet/IP DNET number.
The UPD Port number. This number will be used in the BACnet/IP configuration of
the B6000 Router. It is usually set to 47808.
The network numbers of any other networks in the Cimetrics BACstac(TM) Routing
Edition v4.2 Protocol. When you configure the MS/TP Routers MS/TP settings,
make sure neither the BACnet/IP DNET number nor the MS/TP DNET number is
the same value as any of the physical network or virtual numbers defined for the
Insight workstation.
To determine which physical network numbers and which UDP port number to use, if
the third-party BACnet vendors are present, then ask the following questions:
Which physical network numbers are being used for the BACnet/IP network?
Use this network number for both of the following:
The Routers BACnet/IP DNET number.
The Insight BACnet workstations BACnet/IP network number.
Which physical network and virtual numbers they are using for other networks?
Do not use these network numbers in the routers configuration or for the Insight
BACnet workstations Cimetrics Setting.
Which UDP port they are using? The UPD port 47808 is the default, but
sometimes, other ports may be used.
Chapter 5 - BACnet MS/TP FLN Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network
38
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
BTEC Object Names and Object IDs
Be sure to consult with the customer or third-party vendor to determine the best
naming convention for the BTEC Object Names and Object IDs on the MS/TP network.
The names are determined in the same way as standard APOGEE Automation System
names. The Object IDs are usually in a range reserved for this type of device. If the job
is small, the Object IDs can be in any range. However, if there are several BACnet
devices on the network, an organizational spreadsheet should be used to keep an ID
from being accidentally reused.
Wiring and Network Electrical Considerations
All BACnet TECs must be daisy chained. No T-Taps are allowed.
The end of every segment must be terminated. The end of a segment is any FLN
connector with only one set of wires connected to it. The following are different
ways to terminate segment ends:
The MS/TP Router is terminated by placing the termination jumpers (see
Setting the Router Termination).
The recommended wiring is our standard ALN/FLN wiring, 24 gauge, Cat 5,
twisted, shielded pair, low capacitance (12.5 pF/ft.), available from Anixter. See
the Field Purchasing Guide for more information.
Terminate the last TEC with an ALN Trunk Terminator (Part Number 538-664).
Terminate all FLN connectors that connect to an HSTIE by setting the Trunk
Termination Switch (inside the HSTIE enclosure) for that FLN connector to an
End of Line (EOL). Do not add an ALN Trunk Terminator. If there are two sets
of wires in one FLN connector, the Trunk Termination Switch should be set to
Normal (NRML).
HSTIEs are required if more than 31 of the older BACnet TECs are used. For
BACnet TECs sold after November 2005, a maximum of 50 TECs can be placed
on a single router without any HSTIE. Additional TECs can actually be used, but
over 50 is not recommended because change of values (COVs) will update slowly.
To determine if the BACnet TECs are the type that allows more than 31 on a segment,
locate the chip labeled U16 on the board, which is about 1-inch above terminations 7
and 8. If the TEC is the newer type, the marking MAX3085 is printed on the chip. The
older types of TECs have a series of numbers printed on them, but not "MAX3085".
The E terminal of the power connector for all BACnet TECs must be connected to
earth ground. If the E terminal is not connected to earth ground, the BACnet TECs
could potentially lock up and stop communicating.
Connect the shield wire to every BACnet TEC and to the MS/TP Router.
Chapter 5 - BACnet MS/TP FLN Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network
39
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Setting the Router Termination
Only perform this procedure if the router is at the end of a segment (which means, the
routers MS/TP connector has only one set of FLN wires connected to it).
1. Unplug all connections to the router, including power.
2. With a small Phillips screwdriver, remove the four screws on the sides of the router.
3. Remove the top cover.
4. Move the three jumpers near the green MS/TP connector on J5 from Spare to
Terminated.
Termination Jumper Placement inside the Cimetrics B6000 Router.
5. Place the cover back and tighten the four screws.
6. Reconnect the power supply. Leave the Ethernet and MS/TP connectors
disconnected.
Chapter 5 - BACnet MS/TP FLN Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network
40
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Connecting to the Router with a Computer for Configuring
1. Obtain an Ethernet Crossover cable or an Ethernet hub and two Ethernet patch
cables.
2. Configure your laptop computer or another computer to have a fixed IP address of
192.168.88.90 with a subnet mask of 255.255.255.0. To do so, perform the
following steps (these steps assume you have Windows XP):
- Click Start, Settings, Control Panel, and then double-click Network
Connections.
- Right-click on the Connection that represents your Network Interface Card, and
then click Properties.
- Select Internet Protocol (TCP/IP), and then click the Properties button.
- Select Use the Following IP Address.
- Type the following:
IP address 192.168.88.90 Subnet Mask 255.255.255.0
- Click OK to the Internet Protocol (TCI/IP) Properties dialog box.
- Click OK to the Local Area Connection Properties dialog box.
- Close the Network Connections window.
3. Disable the ISA Firewall Client by right-clicking on the ISA Firewall Client icon in
the system tray in the lower right corner of the screen and selecting Disable.
ISA Firewall Client Icon.
4. Open Internet Explorer. Type http:// 192.168.88.89 in the Address box and press
ENTER.
5. The MS/TP Router prompts you for a User Name and Password. Type admin for
both the username and password.
Configuring the Router BACnet/IP Settings [Not released]
1. Log on to the B600 Web interface, click on BACnet/IP settings.
2. Enter the desired IP address for the router.
3. Set Network Mask, type the desired subnet mask for the router.
Make a note of the MS/TP Routers IP address and Subnet Mask for your records.
4. Set UDP Port, use 47808, unless you are not using the default BACnet port.
5. Set DNET, type the Physical Network number you obtained from Procedure 1; this
should match the physical network number of the Insight workstations BACstac
properties.
6. Click Save.
Chapter 5 - BACnet MS/TP FLN Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network
41
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Configuring the Router MS/TP Settings
1. Click MS/TP Settings.
2. Configure the baud rate. The recommended baud rate is 38400 bps.
A baud rate of 76800 bps does not work with HSTIEs.
- Set the value of This Station (MAC), to a value from 1 through 127, that is not
equal to any of the ADDRESS (1) subpoints of any BACnet TECs. The MS/TP
Router is actually a node on the MS/TP network, similar to TECs. If the MAC
address of the MS/TP Router were the same as one of the BACnet TECs, the
network would not communicate properly and the BACnet TECs would fail.
- Set Max Info Frames to a value of 1.
- Set Max Master to 127. This sets the highest MAC address the MS/TP Router
can poll. As a general rule, this should be at least the value of the highest TEC
address on the network if it is not, the TECs cannot communicate.
- Set Reply Timeout to 255 mS.
- Set Usage Timeout to 20 mS.
- Set DNET to a unique value. This value must be different from the following:
The DNET parameter on the BACnet/IP settings. The Insight workstation's Cimetrics Network numbers (physical and virtual). The networks for any other router or Insight workstation.
- Click Save.
Confirming the Router Settings
1. Click Activate Configuration.
2. Click Confirm.
The following message displays: Confirmation saved. Now rebooting the device.
3. Close Internet Explorer.
4. Disconnect the Ethernet cable that was used for configuring and connect the cable
that will be used to connect the MS/TP Router to the Insight workstation.
5. From the Insight workstation, click Start, Run, type CMD and then press ENTER.
6. Verify that the Insight workstation has Ethernet connectivity to the MS/TP Router.
Type PING [IP address of MS/TP Router] and then press ENTER.
7. If you need to verify settings from the Insight workstation, open Internet Explorer
and type http://[IP address of MS/TP router]in the address box and then press
ENTER.
The MS/TP Router configuration Web page can still be contacted from a computer
whose IP address is 192.168.88.90 by typing http://192.168.88.89 in the address box
of Internet Explorer. This method works even if the MS/TP router has been configured
with a different IP address. This is useful if the IP address of the MS/TP Router is
unknown.
Chapter 5 - BACnet MS/TP FLN Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network
42
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Configuring BACnet TECs
Perform the following procedure at all BACnet TECs.
1. Connect to the BACnet TEC with WCIS 2.1.4 or later through the TECs HMI port.
- WCIS 2.1.4 is available on the Field Support Web site:
http://iknow.us009.siemens.net/fieldsupport/WindowsCIS.asp
- From Beacon: https://inet.sbt.siemens.com/fieldsupport/WindowsCIS.asp
2. Set the communications baud rate to 1200 bps.
3. Click Device, and then Connect.
4. Set the MAC address of the BACnet TEC by overriding the point ADDRESS (1), to
the desired value.
NOTE: Do not leave more than one BACnet TEC that has not been addressed
connected to the network. The default address of 99 is a valid BACnet address.
Therefore, if you leave more than one BACnet TEC connected with an address of
99, you will have duplicate addresses, and you will be unable to establish
communication.
5. Set APPLICATION (2) to the desired application.
6. Follow the remaining procedures in the Startup Documents with the exception of
Configuring BACnet Parameters section:
- http://iknow.us.abatos.com/customsolutions/HVAC_main.asp
- From Beacon: https://inet.sbt.siemens.com/customsolutions/HVAC_main.asp
7. Save TEC initial values using the backup feature in WCIS 2.1.4. Neither the MS/TP
Router nor the BACnet MS/TP Driver has the ability to back up or restore initial
values.
8. Click the Device drop-down menu. The WCIS software pauses and the mouse
pointer may change to an hour glass.
9. Click on Device Properties. Again, there may be a pause.
10. Set Object Name to a unique name (12-character limit).
11. Set the Object ID to a unique value from 0 to 4194303.
NOTE: Object ID is not the MAC address; it is a higher-level address within the
BACnet MS/TP protocol (device instance number).NOTICE!
12. Type a Description for the controller (60-character limit). (Optional)
13. Type a Location describing the physical location of controller (60-character limit).
(Optional)
14. Set CIS/MMI Command Property to a value 8.
15. If the TEC is connected to an MS/TP Router and metric units are desired, select
the Metric Units check box.
16. Set the baud rate to match Baud Rate of the MS/TP Router. The options for baud
rate are; 9600, 19200, 38400 or 76800. The default is 19200.
NOTE: HSTIEs cannot be configured for 76800 bps. It is recommended to
configure the BACnet TECs to a baud rate of 38400 bps.
Chapter 5 - BACnet MS/TP FLN Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network
43
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
17. Configure the controller for MSTP Master or Slave. To determine which to use,
consider the following:
- Use Master if you will be referencing several of the BACnet TEC points in
PPCL. If you select Master, you can use the BACnet TEC point names in
PPCL, such as [ObjectName]Room Temp.
- Use Slave if you are concerned with performance, specifically the rate at which
the BACnet TECs update. To use the BACnet TEC point names, such as
[ObjectName]Room Temp in PPCL, you must manually type the name in the
BACnet address table from System Profile or the field panel HMI, or use a fully
qualified BACnet object name, such as 70001_AI_4.
- If the customer requests Metric Units, select the Metric Units check box.
- Click the Write button.
- Initialize the TEC, or cycle power to it.
18. Follow the procedures in the BACnet TEC startup document(s) for your application.
Those documents are available at.
http://iknow.us.abatos.com/customsolutions/HVAC_main.asp.
Establishing Communication with an Insight Workstation
1. If the BACnet TECs are configured for MS/TP Slave, change the value of the
registry key PingByReadPropertyFrequency to a value of 4. To do this:
- Click Start, Run, and type regedt32 and press ENTER.
- Navigate to HKEY_LOCAL_MACHINE\SOFTWARE\LANDIS &
GYR\Insight\CurrentVersion\BACnet\Client\.
- Double-click PingByReadPropertyFrequency, and change the value from 0
(default) to 4. Click OK.
- Exit Regedt32.
2. Once all the BACnet TECs have been configured, connect the MS/TP connector to
the MS/TP Router.
3. Open System Profile at the Insight workstation.
4. If there is not already one present, create a BACnet ALN.
5. Do one of the following:
- If the TECs are configured for MS/TP master, click Enable BACnet Discovery in
System Profile, and then click Send Who Is.
- If the TECs are configured for MS/TP Slave or you want to specify the System
Name of the TECs, manually add the BACnet TEC. To do this, drag-and-drop a
field panel on the ALN for each TEC.
6. Set the Device Instance Number equal to the TEC device instance number (Object
ID) in Configuring BACnet TEC, Step 11.
7. Assign a unique System Name and Name.
Chapter 5 - BACnet MS/TP FLN Adding a BACnet MS/TP PXC Compact 16/24 or UEC to a MS/TP FLN Network
44
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
8. If you are not using BACnet Discovery, manually add a TEC. To do this, drag-and-
drop a field panel on the ALN for each TEC.
- Set the Device Instance Number equal to the TEC device instance number
(Object ID) in Configuring BACnet TEC, Step 11.
- Assign a unique System Name and Name.
9. Using Database Transfer, upload each BACnet TEC.
10. Run a Point Log report to verify that all of the BACnet TECs are communicating.
Chapter 6 - Troubleshooting BACnet Network Using WireShark Overview
45
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Chapter 6 - Troubleshooting BACnet Network
Using WireShark
Overview Wireshark is an open source network analyzer. This is a software application that can
be used to capture, view, and save network traffic for the purpose of troubleshooting
network communication problems including BACnet (BACnet/IP, BACnet Ethernet, and
BACnet MS/TP).
Installation
Wireshark can be installed on most Microsoft operating systems running Windows XP,
Windows Server 2003, Windows Vista, Windows 2008, Windows 7, and Windows 2008
R2.
You can download a copy of the latest Wireshark application from
http://www.wireshark.org/.
During the Wireshark installation, two components are installed:
Wireshark Application for configuring the capture filters, setting capture
parameters, displaying frames, decoding frames, producing graphs, tables, and
statistics.
Winpcap Drivers used to capture packets off the NDIS interface.
Setting Up Wireshark Capture Software Install Wireshark on a computer running BACnet software, for example an Insight
workstation.
1. Capture all IP network packets on an Insight workstation.
2. Capture all IP network packets on a specific field panel using an Ethernet hub.
Install Wireshark on laptop computer and connect to the Ethernet network using a true
hub so that the laptop computer will get all packets received and delivered from the
perspective of the field panel. See Figure Switched Media (with Hub).
NOTE: Unlike switches, when routing data, hubs broadcast the data to all of their ports
knowing that the correct recipient will receive it.
Chapter 6 - Troubleshooting BACnet Network Using WireShark Setting Up Wireshark Capture Software
46
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
True hub models that are known to work:
Netgear DS104
Netgear DS108
Netgear GS108NA
Netgear GS105?
Advantage - Cheap and easy to install.
Disadvantage - Reduces link to half duplex and is not practical on servers or switch
uplink.
Capture all IP network packets on a specific field panel using a switch with port
mirror.
Install Wireshark on laptop computer and connect to the Ethernet network using a
switch with port mirroring capabilities. Using the switch management, you can select
both the monitoring port and assign a specific port you wish to monitor. Actual
procedures vary between switch models and you may need to use a terminal emulator,
specialized SNMP client software or (more recently) a Web browser.
Chapter 6 - Troubleshooting BACnet Network Using WireShark Starting Wireshark
47
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Switch model that is known to work:
Netgear GS108E
Advantage - Does not require link to be dropped and great for one-time link monitoring.
Disadvantage - Requires switch access and configuration.
Capture all MS/TP network packets using a Serial to RS-485 adaptor.
Install Wireshark on laptop computer and connect to the RS-485 network using a Serial
to RS-485 adapter.
Starting Wireshark
1. Click Start, Programs, Wireshark.
The main window displays.
2. The two main menus you will use are:
- File. The File menu allows you to open, save, and export capture files.
- Capture. The Capture menu allows you to start and stop a capture, as well as
select a network interface where you want capture data to reside on.
Chapter 6 - Troubleshooting BACnet Network Using WireShark Starting Wireshark
48
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Starting and Stopping Wireshark Capture for an IP Network
1. To start a capture, select Interfaces from the Capture drop-down menu.
The Capture Interfaces dialog box displays.
2. Select the network card you want to capture data from by using the radio buttons
on the left side and then click the Start button.
3. The data packets will display in the main window.
4. Select Stop from the Capture menu, to stop the capture.
Chapter 6 - Troubleshooting BACnet Network Using WireShark Starting Wireshark
49
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Starting and Stopping Wireshark Capture for MSTP network using MSTPCAP
1. From Command Prompt, type the following:
MSTPCAP
- where syntax is COMx where x is port, for example COM2 or COM12. where syntax number equal to baud (19200, 38400, etc) where is \\.\pipe\wireshark
MSTPCAP creates capture files in the following format: Mstp_YYYYMMDDHHMMSS.cap (YearMonthDayHourMinuteSeconds)
NOTE: There is a packet counter that increments every 100 packets. If counter
stays at 0, check ComPort and Baud settings.
2. After running MSTPCAP with a WindowsPipe, start Wireshark.
3. Select Options from the Capture menu.
4. In the Interface field, enter WindowPipe (use from MSTPCAP command line).
5. Click the Start button.
The data packets will display in the main window.
6. Select Stop from the Capture menu to stop capture.
NOTE: After stopping Wireshark capture, you must also stop MSTPCAP by using
CTRL-C in Command Prompt.
7. The data packets will display in the main window.
Chapter 6 - Troubleshooting BACnet Network Using WireShark Starting Wireshark
50
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
8. Select Stop from the Capture menu, to stop the capture.
Chapter 6 - Troubleshooting BACnet Network Using WireShark Saving Wireshark Capture
51
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Saving Wireshark Capture
NOTE:
You can only save a capture that is not actively running.
1. To save the data packets, select Save-As from the File menu.
The Wireshark Save file as dialog box displays.
2. To save all the packets, select the All packets and Captured radio buttons in the
Packet Range section.
3. Navigate to the folder location where you want to save the captures, type in a
filename, and then click Save.
Chapter 6 - Troubleshooting BACnet Network Using WireShark Wireshark Display Filters
52
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Wireshark Display Filters Display Filters are used to view only the packets that you want to see and hide the
packets you dont want to see. You do this by building a filter expression in the filter
toolbar.
To build a filter expression, you will use a combination of Comparison operators,
Logical operators, common keywords, and values. The following tables are the most
commonly used operators, keywords, and values used to build expressions.
Comparison Operators
Description Wireshark syntax English syntax
Equal == eq
Not equal != ne
Greater than > gt
Less than < lt
Greater than or equal to >= ge
Less than or equal to
Chapter 6 - Troubleshooting BACnet Network Using WireShark Wireshark Display Filters
53
Siemens Industry, Inc. Network Setup and Troubleshooting Manual 125-5103
Restricted 2013-11-14
Common keywords BACnet
Description Wireshark syntax
Only BACnet Packets bacnet
BACnet Object Type bacapp.objectType
BACnet Object Instance bacapp.instance_number
BACnet Confirmed Service bacapp.confirmed_service
BACnet Unconfirmed Service bacapp.unconfirmed_service
BACnet Object Type Values
Object Type Value
Analog Input 0
Analog Output 1
Analog Value 2
Binary Input 3
Binary Output 4
Binary Value 5
Calendar 6
Command 7
Device 8
EventEnrollment 9
MultiState Input 13
MultiState Output 14
MultiState Value 19
BACnet Confirmed Service Values (that is, bacapp.confirmed_service == xx)
Object Type Value
confirmedCOVNotification 1
confirmedEventEnro