Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
Technical Data 61889
Fluid chilled or hot water, up to 60% glycolFlow characteristic equal percentageControllable flow range 75°Valve Size [mm] 5” [125]Pipe connector pattern to mate with ANSI 125 flangeHousing Cast iron - GG 25Ball stainless steelStem stainless steelStem seal EPDM (lubricated)Seat PTFEO-ring EPDM (lubricated)Characterized disc stainless steelBody Pressure Rating ANSI Class 125, standard class BANSI Class 125Number of Bolt Holes 8Close-off pressure ∆ps 175 psiCv 290 Weight 74.97 lb [34 kg]Fluid Temp Range (water) 0...250°F [-18...120°C]Leakage rate 0% for A – ABServicing maintenance-free
Flow/Mounting Details
ApplicationThis valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow.
Suitable Actuators Non-Spring Electronic fail-safeB6500S-290 GRB(X) GKRB(X)
Dimensions (Inches [mm])
BA
C
D
G
E F
I
GRB, GRX
A B C D E F G I13.3” [338]
10.3” [262]
14.4” [366]
9.4” [239]
5.0” [127] 8.5” [216]
0.9” [22]
Safety NotesWARNING: This product can expose you to lead which is known to the State of California to cause cancer and reproductive harm. For more information go to www.p65warnings.ca.gov
B6500S-290 Technical Data SheetStainless Steel Ball and Stem
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
Date
cre
ated
, 06/
11/2
020
- Sub
ject
to c
hang
e. ©
Bel
imo
Airc
ontro
ls (U
SA),
Inc.
Dimensions (Inches [mm])
D
BA
C
E F
G
I
GKRB, GKRX
A B C D E F G I13.5” [343]
10.3” [262]
14.4” [366]
9.7” [246]
5.0” [127] 8.5” [216]
0.9” [22]
Dimensions (Inches [mm])
DC
BA
G
E F
I
GRX, GKRX
A B C D E F G I17.5” [444]
10.3” [262]
17.0” [433]
13.6” [345]
5.0” [127] 8.5” [216]
0.9” [22]
Dimensions (Inches [mm])
DC
BA
G
E F
I
GRX, GKRX
A B C D E F G I17.5” [444]
10.3” [262]
17.0” [433]
13.6” [345]
5.0” [127] 8.5” [216]
0.9” [22]
B6500S-290 Technical Data SheetStainless Steel Ball and Stem
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
Date
cre
ated
, 06/
11/2
020
- Sub
ject
to c
hang
e. ©
Bel
imo
Airc
ontro
ls (U
SA),
Inc.
Technical Data 146973
Power Supply 24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10%Power consumption in operation 8 WPower consumption in rest position
2.5 W
Transformer sizing 11 VA (class 2 power source)Electrical Connection 18 GA plenum cable with 1/2” conduit
connector, degree of protection NEMA 2 / IP54, 3 ft [1 m] 10 ft [3 m] and 16ft [5 m]
Overload Protection electronic thoughout 0...90° rotationOperating Range 2...10 V (default), 4...20 mA w/ ZG-R01 (500
Ω, 1/4 W resistor), variable (VDC, on/off, floating point)
Operating range Y variable Start point 0.5...30 V End point 2.5...32 V
Input Impedance 600 ΩPosition Feedback 2...10 V, Max. 0.5 mA, VDC variableAngle of rotation 90°, adjustable with mechanical stopDirection of motion motor selectable with switch 0/1Position indication Mechanically, 30...65 mm strokeManual override external push buttonRunning Time (Motor) default 150 s, variable 90...150 sAmbient humidity max. 95% r.H., non-condensingAmbient temperature -22...122°F [-30...50°C]Storage temperature -40...176°F [-40...80°C]Degree of Protection IP54, NEMA 2, UL Enclosure Type 2Agency Listing cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02, CE acc. to 2014/30/EU and 2014/35/EU
Noise level, motor 45 dB(A)Servicing maintenance-freeQuality Standard ISO 9001Weight 2.7 lb [1.2 kg]
†Rated Impulse Voltage 800V, Type of action 1.AA, Control Pollution Degree 3
GRX24-MFT Technical Data SheetModulating, Non-Spring Return, 24 V, Multi-Function Technology®
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
Date
cre
ated
, 06/
04/2
020
- Sub
ject
to c
hang
e. ©
Bel
imo
Airc
ontro
ls (U
SA),
Inc.
Wiring Diagrams
INSTALLATION NOTES
A Actuators with appliance cables are numbered.
Provide overload protection and disconnect as required.
Actuators may also be powered by 24 VDC.
Only connect common to negative (-) leg of control circuits.
A 500 Ω resistor (ZG-R01) converts the 4 to 20 mA control signal to 2 to 10 VDC.
Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line.
For triac sink the Common connection from the actuator must be connected to the Hot connection of the controller. Position feedback cannot be used with a triac sink controller; the actuator internal common reference is not compatible.
IN4004 or IN4007 diode. (IN4007 supplied, Belimo part number 40155).
46Actuators may be controlled in parallel. Current draw and input impedance must be observed.
47Master-Slave wiring required for piggy-back applications. Feedback from Master to control input(s) of Slave(s).
Meets cULus requirements without the need of an electrical ground connection.
! WARNING! LIVE ELECTRICAL COMPONENTS!During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
Blk (1)
Red (2)
Pnk (4)
Wht (3)
Org (5)
LineVolts
24 VAC Transformer
PositionFeedback VDC (+)
(–)
Common
+ Hot
Y2 Input
Y1 Input
U Output
A 1 3 46 47
On/Off
24 VAC Transformer (AC Only)
Blk (1) Common
Red (2) + Hot
Wht (3) Y1 Input
Org (5) U Output
Pnk (4) Y2 Input
LineVolts
(–)(+)
Position Feedback VDC
1 10 46 47
Floating Point
Blk (1) Common
Red (2) + Hot
Pnk (4) Y2 Input
Wht (3) Y1 Input
Org (5) U Output
(–)(+)
LineVolts
24 VAC Transformer
500 1/4 watt
Control Signal
VDC / mA
A 1 3 5 46 47
7
(+) Feedback
VDC/mA Control
Blk (1) Common
Red (2) + Hot
Wht (3) Y1 Input
Pnk (4) Y2 Input
Org (5) U Output
Line
Volts
24 VAC Transformer (AC only)
(–) (+)
PositionFeedback VDC
A 1 8 46 47
PWM Control
GRX24-MFT Technical Data SheetModulating, Non-Spring Return, 24 V, Multi-Function Technology®
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
Date
cre
ated
, 06/
04/2
020
- Sub
ject
to c
hang
e. ©
Bel
imo
Airc
ontro
ls (U
SA),
Inc.
Functions
0%
50%
100%
Control mode acc. to Y1
Min
Mid
Max
Normal
a b c Org (5)
24 VAC Transformer (AC Only)
U Output
1 5
Blk (1) Common
Red (2) + Hot
Pnk (4)
Wht (3) (–)(+)
LineVolts
B
C
A
VDC / mAControl Signal
Y2 Input
Y1 Input
127
Ω
182
Override Control
Blk (1) Common
Red (2) + Hot
Wht (3) Y1 Input
Org (5) U Output
Master24 VAC Transformer
Line Volts
Control Signal (–)
(+)
Blk (1) Common
Red (2) + Hot
Wht (3) Y1 Input
Org (5) U Output
Ω
1 5 46 47
7
Slave 1
Master - Slave
GRX24-MFT Technical Data SheetModulating, Non-Spring Return, 24 V, Multi-Function Technology®
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
Date
cre
ated
, 06/
04/2
020
- Sub
ject
to c
hang
e. ©
Bel
imo
Airc
ontro
ls (U
SA),
Inc.