AUTOMATIC TRANSFER SWITCH
CATALOGUE
https://btb-electric.com
AUTOMATIC TRANSFER SWITCH
2
ATbS
(3P ; 4P)
OPERATION ENVIRONMENTATbS automatic changing-over isolation switch can work
reliably under the following conditions:
- Height above sea level does not exceed 2,000m;
- Ambient temperature is not higher than 40OC and not lower than -5OC.
- Relative humidity is not larger than 95%;
- No expiosive dangerous medium environment;
- No rain and snow attack environment;
Note: if the load isolation switch is expected to be used in the condition that the ambient temperature is higher than +40OC or is lower than -5OC ~ -45OC, customers should inform to the manufactory
MODEL & MEANING
PRODUCT OUTLINEATbS automatic changing-over switch integrates switch and logic control. Thus it is not necessary to provide external cont roller.
This truly electrome mechanical intergrated automatic change-over switch has the following functions such as voltage detection, frequency detection, communication interface, electrical and mechanical inter interlocking etc., So, automatic control, electrical remote control and emergency manual control can be performed.
The operation is carried out through the logic control board, which gives various commands to control the motor and gearbox. The motor drives the accelerator which can take swich spring power accumulating and instantaneous release, swiftly turns making and breaking the circuit or makes circuit switching. The visible operation status can help you to perform safe separation, increasing extremely the various electrical and mechanical performance.
The shell of switch ATbS is made of metal. Being small and compack, while the shell of switch ATbS is made of different materials: it is control section made of metal, but the switching section is made of glassfibre unsaturated polyester resin, having stronger dielectric property and protective capa-bility as well as safe operation performance.
This kind of switch is suitable for the automatic change-over of the main power source and the secondary power source of the power supply system or the automatic change-over and safe separation of the 2 sets of load-equipment.
This kind of switch has a beautiful, novel and simple structure, a small volume but complete functions, being the best choice among congeneric of products.
CONFORM STANDARDATbS series Automatic change-over switch complies With The Following Standards:
International Standard:
IEC60947-1(1998) ( Low-voltage switchgear and controlgear,part one: General Rules)
IEC 6094-3(1999)( Low-voltage switchgear and controlgear, switches, disconnectors, switch-disconnectors and fuse-con-bination units)
IEC60947-6(1999) (Low-voltage switch equipment and control equipment multi-function-switch automatic change-over switch electrical device)
PRODUCT USAGEATbS series Automatic change-over switch mainly suitable for distribution or electromotor network, which under AC 50Hz, rated voltage 380V, rated voltage DC220V, rated current 125-3200A, main power and standby power or mutual standby power change over system or city power and generator group overload switch-over. At the same time, it can operated under un-frequency On and Off circuit act as disconnector.
https://btb-electric.com
AUTOMATIC TRANSFER SWITCH
3
Conventional thermal current Ith A 125A 200A 400A 630A 800A 1000A 1250A 1600A 2000A 2500A 3200A
Rated impulse withstand voltage Ui(V) 660 660 660 800 800
Rated surge- resistant voltage Uimp KV 6 6 6 8 8
Rated Working voltage Ui(V) AC440V AC440V AC440V AC440V AC440V
Rated working current le(A)
AC-31 125 200 400 630 800 1000 1250 1600 2000 2500 3200
AC-33 125 200 340 536 800 1000 1000 1000 1250 1250 1250
AC-35 125 200 400 630 800 1000 1000 1250 2000 2000 2500
Rated making capability 10Ie 10Ie 10Ie 10Ie 10Ie
Rated breaking capability 8Ie 8Ie 8Ie 8Ie 8Ie
Rated limit short circuit current KA 13kA 35kA 35kA 50kA 75kA
Change-over time I-O-II or II-O I 1.2s 1.2s 1.2s 1.2S 2.4S
Power supply voltage control
AC220V
AC220V AC220V AC220V AC220V
Start 40W 40W 325W 325W 355W 355W 400W 400W 600W
Normal 18W 18W 62W 62W 90W 90W 98W 98W 120W
Weight (kg) 3poles 6.8 9 17.6 18.3 40.4 40.4 42 44 95 100 105
4poles 7 9.3 18.3 19.1 46.2 46.2 49.9 51.7 102.4 112.3 122.6
Such products are widely used at the field of important power supply site which transport, distribution power supply system and automatization. System for Fire Protection. Hospital, Bank, Building etc., Which does not allowed off.
PERFORMANCE AND CHARACTERISTIC- It adopted double complex contact, horizontal and vertical type frame work, Micro motor pre-saving and Micro electronic control technical, basically, it have come to ‘zezo’ are (No Arc Chute);
- It adopt reliable machine interlock and electric interlock, the excutive union parts adopt independency overload disconnect switch, it makes more reliable and safety;
- Adopt ‘zezo’ technique, it can force to set ‘zezo’ under emergency situation (break off two way power supply at the same time), meet the requirement of fire protection linkage;
- Operate overload disconect switch change over adopt singleness electromotor drive switch over smooth and reliable, no noise, little wallop;
- Operate machine drive motor use only under the executive overload disconnect switch change over instances current across, outstanding energy saying;
- Perform overload disconnect switch with mechanism interlock device, it ensure the common use, standby power working reliable and not interference;
- Distinct On and Off position indecator, padlock function etc., safe realize the disconnect between electric power and overload;
- High security, high automatization, high reliable, use life more than 8000 times;
- Machine & Electricity perfect design, On-Off change-over nicety, agility, smooth, adopt international advanced logical control technique high anti-interference and no interference outside;
- It include main power ciose, standby power separate, main power separate, standby power close, main, standby power all break off and steady working (I - 0 - II)
- Easy installation, control loop adopt terminal connection and insert.
- Four kind of operation function: emergency manual operation, electromotion remote control operation, automatic control stage emergency off operation, automatic control operation.
MAIN TECHNICAL PARAMETERS
https://btb-electric.com
AUTOMATIC TRANSFER SWITCH
4
ATbS 125A - 1600A EXTERNAL DIMENSION AND INSTALLATION DIMENSION
In A A1 B B1 C E G J K L N P R S T U W OX Y Y1
125A/3 376 283.5 135 134 261 208 166 262.5 78/108 7 87 36 20 25 3.5 134 155 9 56 141
125A/4 406 316 135 134 261 208 166 295 78/108 7 87 36 20 25 3.5 134 155 9 56 141
160A/3 376 283.5 135 134 261 208 166 262.5 78/108 7 87 36 20 25 3.5 134 155 9 56 141
160A/4 406 316 135 134 261 208 166 295 78/108 7 87 36 20 25 3.5 134 155 9 56 141
200A/3 416 323.5 170 134 261 208 166 302.5 78/108 7 87 50 25 30 3.5 134 164 11 60 145
200A/4 466 373.5 170 134 261 208 166 353 78/108 7 87 50 25 30 3.5 134 164 11 60 145
250A/3 416 323.5 170 134 261 208 166 302.5 78/108 7 87 50 25 30 3.5 134 164 11 60 145
250A/4 466 373.5 170 134 261 208 166 353 78/108 7 87 50 25 30 3.5 134 164 11 60 145
400A/3 455 378.5 240 208 333 270 166 358.5 176 11 103.5 65 30 40 5 208 197 12 83 193
400A/4 515 438.5 240 208 333 270 166 418.5 176 11 103.5 65 30 40 5 208 197 12 83 193
630A/3 455 378.5 260 208 333 270 160 358.5 176 11 103.5 65 40 50 6 208 197 12 83 194
630A/4 515 438.5 260 208 333 270 160 418.5 176 11 103.5 65 40 50 6 208 197 12 84 194
800A/3 871.5 524 340 250 387 319.5 448 499 212 11 88 120 60 69 8 250 198.5 12.5 84 252
800A/4 975.5 637.5 340 250 387 319.5 448 612.5 212 13 88 120 60 69 8 250 207 12.5 107 252
1000A/3 871.5 524 340 250 387 319.5 448 499 212 13 88 120 60 69 8 250 198.5 12.5 107 252
1000A/4 975.5 637.5 340 250 387 319.5 448 612.5 212 13 88 120 60 69 8 250 207 12.5 107 252
1250A/3 871.5 524 369 250 387 319.5 448 499 212 13 88 120 80 69 8 250 198.5 13 107 252
1250A/4 975.5 637.5 369 250 387 319.5 448 612.5 212 13 88 120 80 69 8 250 207 13 107 252
1600A/3 871.5 524 376 250 387 319.5 448 499 212 13 88 120 80 69 10 250 198.5 13 109 253.5
1600A/4 975.5 637.5 376 250 387 319.5 448 612.5 212 13 88 120 80 69 10 250 207 13 109 253.5
OUTLINE AND INSTALLATION DIMENSION
https://btb-electric.com
AUTOMATIC TRANSFER SWITCH
5
ATbS 2000A – 3200A EXTERNAL DIMENSION AND INSTALLATION DIMENSION
INPUT AND OUTPUT COPPER BAR DIMENSION CHART
https://btb-electric.com
AUTOMATIC TRANSFER SWITCH
6
TERMINAL LOCATION DRAWING
TERMINAL FUNCTIONS INTRODUCTION
Terminal Serial No. Access point serial No. Function
Terminal No. 1
101, 106 Power supply neutral wire and live wire output for feedback
102, 103 Power 1 supply live wire and neutral wire input
104, 105 Power 2 supply live wire and neutral wire input
Terminal No. 2
201, 206 Passive control when disconnected and active control when closed
202 Common terminal of external passive control signal input
203 When closed with 202, Line I is switched on
204 When closed with 202, Line 0 is switched on
205 When closed with 202, Line II is switched on
Terminal No. 3
301, 306 Not used
302 Common terminal of passive position feedback signal output
303 Closed with 302 when Line I is switched on.
304 Closed with 302 when Line 0 is switched on.
305 Closed with 302 when Line II is switched on.
https://btb-electric.com
AUTOMATIC TRANSFER SWITCH
7
CIRCUIT DIAGRAM
WIRING DIAGRAM
TYPICAL WIRING DIAGRAM
https://btb-electric.com
AUTOMATIC TRANSFER SWITCH CONTROLLER
8
Items Contents
Operating Voltage AC170V-277V during AC power LI N1/L2N2 supply.
Power Consumption <3W (Standby mode: <1W) AC Voltage Input AC170V~AC277V(ph-N)
Rated Frequency 50/60HZ
1# Close Relay Output 5A AC250V Volts free output
2# Close Relay Output 5A AC250V Volts free output
Open Relay Output 5A AC250V Volts free output
AUX.OUTPUT 1 16A AC250V Volts free output
AUX.OUTPUT 2 16A AC250V Volts free output
Gen Start Relay 7A AC250V Volts free output
1# Close Input COM2 connect is active.
2# Close Input COM2 connect is active.
Forced Breaking Input COM2 connect is active.
Communication LINK interface, MODBUS Protocol
Case Dimensions 139mmx120mmx50mm
Panel Cutout 130mmx111mm
Working Conditions Temperature: (-25~+70)°C;
Storage Condition Temperature: (-25~+70)°C
Protection Level IP55 Gasket
Insulation Strength Apply AC2.2kV voltage between high voltage terminal and low voltage terminal;
Weight 0.51kg
TECHNICAL PARAMETER
ATS CONTROLLER ATbS C53
The powerful Microprocessor contained within the ATbS C53 controller allows for precision voltage (2-way 3-phase/single phase) measuring and make accurate judgment on abnormal voltage (power lost, over/under voltage, over/under frequency, loss of phase, phase sequence wrong) and control ATS to transfer after the delay has expired. This controller is suitable for NO Breaking ATS and ONE Breaking ATS. When #1 power is abnormal, the controller will send signal to start genset after the “#1 abnormal delay” has expired. “Three remote” (remote control, remote measurement and remote communication) Function can be implemented with the help of LINK communi-cation port.
I IIOClose CloseOpen
AutoMan
AUTO
AUTO
Source 1
Load
Source 2
ATbS C53
https://btb-electric.com
AUTOMATIC TRANSFER SWITCH CONTROLLER
9
ATbS C56 - ATS CONTROLLER
TYPICAL WIRING DIAGRAM ATbS C53
ATbS C56 series ATS controller is intelligent dual-supply module with configurable function, automatic measurement, LCD display, and digital communication. It combines digital, intelligence and networking. Automatic measurement and control can reduce incorrect operation. It is an ideal option for ATS.
The powerful Microprocessor contained within the unit allows for precision voltage (2-way-3-phase/single phase) measuring and make accurate judgment; in addition, the corresponding digital output port will active when there is over/under voltage, over/under frequency, loss of phase and other abnormal
I IIOClose Close
Set
Open
AUTO
Auto/Man
AUTO
ATbS C56
!
condition occurs. This controller has full consideration in various application of ATS (automatic transfer system) and can be directly used for specialized ATS, Contactor ATS, Air break ATS etc. It has compact structure, advanced circuits, simple wiring and high reliability, and can be widely used in electrical devices, automatic control and testing system of electric power, telecommunications, petroleum, coal, metallurgy, railways, municipal administration, intelligent building, etc.
https://btb-electric.com
AUTOMATIC TRANSFER SWITCH CONTROLLER
10
Items Contents
Operating Voltage 1. DC 8.0V~35.0V continuous 2. AC170V~277V, AC power L1N1/L2N2 supply
Power Consumption <3W (Standby mode: ≤2W)
AC Voltage Input
AC system ATbS C56
3P4W (ph-N) AC30V~AC270V
1P2W (ph-N) AC30V~AC270V
2P3W (ph-N) AC30V~AC270V
Rated Frequency 50/60Hz
Close Relay Output 16A AC250V Volts free output
Auxiliary Relay Output 1 7A AC250V Volts free output
Auxiliary Relay Output 2 7A AC250V Volts free output
Auxiliary Relay Output 3 16A AC250V Volts free output
Auxiliary Relay Output 4 16A AC250V Volts free output
Digital Input GND connected is active.
Communication LINK interface, MODBUS Protocol
Case Dimensions 139mmx120mmx48mm
Panel Cutout 130mmx111mm
Working ConditionsTemperature: (-25~+70)°C;
Humidity: (20~93)%RH
Storage Condition Temperature: (-25~+70)°C
Protection Level IP55 Gasket: when there is waterproof gasket installed between controller and the control panel;
Insulation StrengthApply AC2.2kV voltage between high voltage terminal and low voltage terminal and the leakage current is not more than 3mA within 1min.
Weight 0.62kg
TECHNICAL PARAMETER
https://btb-electric.com
AUTOMATIC TRANSFER SWITCH CONTROLLER
11
INSTALLATION ATbS C53, C56
TYPICAL WIRING DIAGRAM ATbS C56
Add: OrhangaziMah. Mimsan San. Sit. 200 sok.
No:5 Esenyurt / İstanbul / Turkey
E-mail: [email protected]