2
ATs Series Automatic Transfer Switch 19 ATs-1000E ~ 30/40A, 7.2/9.6kVA, 230vac Key ATs features Enables redundant UPS, backup generators or other ac power sources to be used for a single load. Less than a 20ms transfer time from source A to source B. User selectable transfer times of 20ms, 40ms or 1 second. Built-in circuit breakers Designed to handle out-of-phase and/or asynchronous ac sources Rack-mountable LED status indicators DB9 communications interface Audible alarms with enable/disable switch TSi Power’s ATs Series user customizable automatic transfer switches (ATS) are for enabling the use of redundant power sources, such as small uninterruptible power systems feeding industrial controls, PLC cabinets, internet servers, telecom systems, etc. Typical ATs applications Designed for situations where reliability and predictability matter to the enterprise. Examples: telecommunications equipment, rectifiers, cell sites, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment. Key ATs benefits If the ATs DIP Switch is set to “Fast transfer” (20ms typical transfer time) mode, then when redundant power sources are present, it can replace an expensive UPS system and battery banks for most computers, telecommunication, and industrial equipment (since switchmode power supplies used in most new electronics equipment provide a minimum of 20ms in capacitor hold-up time under full load conditions). If a ‘positive power break’ is needed during the transfer, then the ATs may be set to “Slow transfer” (1 second) mode to ensure a full 1 second ac power outage during transfer. Also, the two ac sources do not have to be synchronized since the ATs is designed to switch between two asynchronous ac sources without damage to itself or to equipment powered by switchmode power supplies. How the ATs works The ATs is fed by two ac power sources. When the primary power source detector circuit senses a loss of power on that circuit, it immediately switches the load over to the backup power source feed in less than 20ms. Upon restoration of primary power, the ATs will switch back in less than 20ms. This is fast enough to be invisible to computer switch-mode power supplies. Model ATs-1000E 30 amps 7200 VA 7200 watts 230 volts ATs-1000E-40A 40 amps 7200 VA 7200 watts 230 volts Two ac inputs ~ one ac output Automatic transfer switch Compact Automatic Transfer Switch ATs ATs backup feed UPS #1 or other power source automatic transfer switch primary feed UPS #2 or other power source system telecom mission critical server or TSi Power Corporation Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) [email protected] www.carebase.com Copyright © 2006 TSi

Automatic Transfer Switch 230vac 30A 40A Ac Redundant Power System ATs 1000E

Embed Size (px)

DESCRIPTION

ats230

Citation preview

  • ATs SeriesAutomatic Transfer Switch

    19

    ATs-1000E ~ 30/40A, 7.2/9.6kVA, 230vac

    Key ATs features Enables redundant UPS, backup

    generators or other ac powersources to be used for a single load.

    Less than a 20ms transfer time from source A to source B.

    User selectable transfer times of 20ms, 40ms or 1 second.

    Built-in circuit breakers Designed to handle out-of-phase

    and/or asynchronous ac sources Rack-mountable LED status indicators DB9 communications interface Audible alarms with

    enable/disable switch

    TSi Powers ATs Series user customizable automatic transfer switches (ATS) are for enabling the use of redundant power sources, such as small uninterruptible power systems feeding industrial controls, PLC cabinets, internet servers, telecom systems, etc.

    Typical ATs applications Designed for situations where reliability and predictability matter to the enterprise. Examples: telecommunications equipment, rectifiers, cell sites, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.

    Key ATs benefitsIf the ATs DIP Switch is set to Fast transfer (20ms typical transfer time) mode, then when redundant power sources are present, it can replace an expensive UPS system and battery banks for most computers, telecommunication, and industrial equipment (since switchmode power supplies used in most new electronics equipment provide a minimum of 20ms in capacitor hold-up time under full load conditions). If a positive power break is needed during the transfer, then the ATs may be set to Slow transfer (1 second) mode to ensure a full 1 second ac power outage during transfer.Also, the two ac sources do not have to be synchronized since the ATs is designed to switch between two asynchronous ac sources without damage to itself or to equipment powered by switchmode power supplies.

    How the ATs worksThe ATs is fed by two ac power sources. When the primary power source detector circuit senses a loss of power on that circuit, it immediately switches the load over to the backup power source feed in less than 20ms. Upon restoration of primary power, the ATs will switch back in less than 20ms. This is fast enough to be invisible to computer switch-mode power supplies.

    ModelATs-1000E

    30 amps7200 VA7200 watts230 volts

    ATs-1000E-40A40 amps7200 VA7200 watts230 volts

    Two ac inputs ~ one ac output Automatic transfer switch Compact

    Automatic Transfer Switch

    ATs ATs

    backup feed

    UPS #1 orother power source

    automatic transferswitch

    primary feed

    UPS #2 orother power source

    system

    telecom

    mission

    critical

    serveror

    TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] 2006 TSi

  • 20 ATs SeriesATs-1000E-30A/40A

    TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] 2006 TSi

    solid-staterelay #1

    hardwire L2

    L1

    ac output

    backup ac input

    Ground

    solid-staterelay # 2

    ground

    Hardwire230vacpower supply

    alarm

    logic xxmsDelay

    DB9 alarm signalsground

    L2

    L1

    L2

    L1primary ac input

    230vac primary ac Detection

    backup ac Detection

    230vaccircuit breaker

    30 or 40A

    circuit breaker30 or 40A

    ATs-1000E-230V-2006-07-07.pdf

    Specification ATs-1000E (30A) ATs-1000E-40A Electrical

    Capacity in VA (watts) 7200VA (7200W) maximum 9600VA (9600W) maximum Switching technology Solid-state relays (SSRs)

    Input Nominal voltage 230 volts ac single phase

    Primary ac voltage 200 to 270 volts acBackup ac voltage 190 to 270 volts acFrequency range 47 to 63 HzOver-current protection User resettable circuit breakerCircuit breaker ratings 30 amps 40 ampsTypical transfer time 20ms, 40ms or 1000ms (user selectable)Transfer time selection Via a four position DIP switch ~ factory set at 20ms

    Input /output wire size 10mm2 (AWG8) Ac input Hardwire terminals (plugs and receptacles optional - please call)

    OutputNominal voltage 230 volts ac, single phase Load regulation Better than 2% from no load to full loadPower efficiency 98% or higher Ac distribution Hardwire terminals (plugs and receptacles optional).

    Hardwired units must be installed by a qualified electrician.Indicators Green LED for primary ac presence, yellow LED for backup ac

    presence, flashing red LED for loss of primary or backup ac. Audible alarms Buzzer beeps when loss of primary or backup ac occurs. Audible alarm switch Audible alarm (buzzer) and enable/disable switch. Alarm contacts A rear-mounted DB-9 connector sends loss of primary ac and

    loss of backup ac signal for external power status monitoring. Physical

    Dimensions 406mm (16) wide x 83mm (3.25)high x 305mm(12)deep Weight 7kg (15 lbs) Rack mount options Front mount kits: For a 19 Rack: use # MK-5019A

    For a 23 Rack: use # MK-5023A For a 24 Rack: use # MK-5024ACenter mount kits: For a 19 Rack: use # MK-5019F For a 23 Rack: use # MK-5023F For a 24 Rack: use # MK-5024F

    Wall or Floor mount kits: use # MK-5000CEnvironmental

    Ambient temperature 0o to 40oC (32 to 104F). 10 to 90% Relative Humidity(non-condensing). Warranty Warranty Two year limited warranty, parts and labor.

    ATs system architecture

    TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trade-marks of their respective companies.

    Specifications

    ATs ATs

    Automatic transferswitch

    Knockout covers and cable glands for line cords shown

    ATs rear view withknockout covers off ready to hardwire

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile () /PDFXOutputCondition () /PDFXRegistryName (http://www.color.org) /PDFXTrapped /Unknown

    /Description >>> setdistillerparams> setpagedevice