15
ATG 2782 - 1/15 ATG Technical Approval with Certification Institut de Sécurité Incendie asbl Rue de Paris, 15 B-4020 Liège Tel. +32 (0)4 340.42.70 Fax +32 (0)4 340.42.79 ANPI - Division Certification Rue d'Arlon 15 B-1050 Brussels Tel. +32 2 234 36 10 Fax +32 2 234 36 17 ATG 2782 Fire-resistant roller shutters roller shutters (FR 1h) for industrial use Roller shutter VR60 Valid from 10/11/2015 until 09/11/2020 Approval holder: FLEMA SPRL Rue Outre 46 7910 Anvaing Tel.: +32 69 67 27 87 Fax: +32 69 67 27 80 E-mail: [email protected] Website: www.flema.be Based on frequency of use tests, these doors can only be used as doors, which close automatically in the event of a fire. For this purpose, they must always be fitted with a system that causes them to close automatically in the event of a fire and a mechanism that keeps then in open position, which is described in this approval document. Except in the event of a fire, they must always be in open position. 1 Scope In compliance with Standard NBN 713.020 - Addendum 1 - "Fire resistance of construction materials" and the unified technical specifications STS 53.1 – Doors (2006 edition), the term "doors" refers to construction materials that consist of one or more panels, their frame and their connections to the main structure, which may include a transom or other fixed devices, together with suspension, closure and manoeuvring fittings. The fire resistance of the doors has been examined, based on the results of tests conducted, according to Standard NBN 713.020 - Fire resistance of construction materials - 1968 edition – and Addendum 1 – 1982 edition. The BENOR mark is granted on the basis of all test reports, including possible interpolations/extrapolations and not only the individual reports. The presence of the BENOR/ATG mark on a door certifies that the components listed in the following description and tested in compliance with NBN 713.020 indicates fire resistance, as shown on the BENOR/ATG label, subject to the following conditions: Compliance with the procedures of the General Regulations and Special Regulations for Use and Monitoring of the BENOR/ATG mark in the Passive Fire Protection sector Compliance with installation guidelines, which are issued with the door and included in paragraph 5 of this approval document. For this purpose, all BENOR/ATG doors supplied must be accompanied by a copy of this approval document, together with the installation guidelines. The durability, suitability and safety of the doors have been examined, based on the results of tests conducted according to the Unified Technical Specifications STS 53.2 “Industrial Doors” (in preparation). The technical approval is issued by UBAtc asbl. Permission to use the BENOR/ATG mark is granted by ANPI-BOSEC, subject to the conduct of continuous checks during manufacturing and regular external checks of factory-made components by a delegate of the inspection body designated by ANPI-BOSEC. In order to obtain a satisfactory guarantee that a fire-resistant door has been correctly installed, it is recommended that a fitter is employed to install the doors, who is certified by an accredited body for this task, such as ISIB. This type of certification is issued on the basis of a training course and practical test, in which understanding and correct application of the installation guidelines are assessed. By adding the ISIB mark, i.e. a transparent label with the certification number of the fitter, based on the following model (diameter: 22 mm), which must be applied to the BENOR/ATG label, and by issuing a certification of installation, the fitter certifies that the door has been fitted according to paragraph 5 of this approval document and assumes responsibility for its installation.

ATG Technical Approval with Certification · The presence of the BENOR/ATG mark on a door certifies that the components listed in the following description and tested in compliance

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: ATG Technical Approval with Certification · The presence of the BENOR/ATG mark on a door certifies that the components listed in the following description and tested in compliance

ATG 2782 - 1/15

ATG Technical Approval with Certification

Institut de Sécurité

Incendie asbl

Rue de Paris, 15

B-4020 Liège

Tel. +32 (0)4 340.42.70

Fax +32 (0)4 340.42.79

ANPI - Division

Certification

Rue d'Arlon 15 B-1050

Brussels

Tel. +32 2 234 36 10

Fax +32 2 234 36 17

ATG 2782

Fire-resistant roller shutters

roller shutters (FR 1h) for

industrial use

Roller shutter VR60

Valid from 10/11/2015

until 09/11/2020

Approval holder:

FLEMA SPRL

Rue Outre 46

7910 Anvaing

Tel.: +32 69 67 27 87

Fax: +32 69 67 27 80

E-mail: [email protected]

Website: www.flema.be

Based on frequency of use tests, these doors can only be used as doors, which close automatically in the event of a

fire. For this purpose, they must always be fitted with a system that causes them to close automatically in the event of a

fire and a mechanism that keeps then in open position, which is described in this approval document. Except in the

event of a fire, they must always be in open position.

1 Scope

In compliance with Standard NBN 713.020 - Addendum 1 - "Fire

resistance of construction materials" and the unified technical

specifications STS 53.1 – Doors (2006 edition), the term "doors" refers

to construction materials that consist of one or more panels, their

frame and their connections to the main structure, which may

include a transom or other fixed devices, together with suspension,

closure and manoeuvring fittings.

The fire resistance of the doors has been examined, based on the

results of tests conducted, according to Standard NBN 713.020 -

Fire resistance of construction materials - 1968 edition – and

Addendum 1 – 1982 edition. The BENOR mark is granted on the

basis of all test reports, including possible

interpolations/extrapolations and not only the individual reports.

The presence of the BENOR/ATG mark on a door certifies that the

components listed in the following description and tested in

compliance with NBN 713.020 indicates fire resistance, as shown

on the BENOR/ATG label, subject to the following conditions:

Compliance with the procedures of the General

Regulations and Special Regulations for Use and

Monitoring of the BENOR/ATG mark in the Passive Fire

Protection sector

Compliance with installation guidelines, which are issued

with the door and included in paragraph 5 of this

approval document. For this purpose, all BENOR/ATG

doors supplied must be accompanied by a copy of this

approval document, together with the installation

guidelines.

The durability, suitability and safety of the doors have been

examined, based on the results of tests conducted according to

the Unified Technical Specifications STS 53.2 “Industrial Doors” (in

preparation).

The technical approval is issued by UBAtc asbl. Permission to use

the BENOR/ATG mark is granted by ANPI-BOSEC, subject to the

conduct of continuous checks during manufacturing and regular

external checks of factory-made components by a delegate of

the inspection body designated by ANPI-BOSEC.

In order to obtain a satisfactory guarantee that a fire-resistant door

has been correctly installed, it is recommended that a fitter is

employed to install the doors, who is certified by an accredited

body for this task, such as ISIB. This type of certification is issued on

the basis of a training course and practical test, in which

understanding and correct application of the installation

guidelines are assessed.

By adding the ISIB mark, i.e. a transparent label with the

certification number of the fitter, based on the following model

(diameter: 22 mm), which must be applied to the BENOR/ATG

label, and by issuing a certification of installation, the fitter certifies

that the door has been fitted according to paragraph 5 of this

approval document and assumes responsibility for its installation.

Page 2: ATG Technical Approval with Certification · The presence of the BENOR/ATG mark on a door certifies that the components listed in the following description and tested in compliance

ATG 2782 - 2/15

By adding this label, the certified fitter agrees to have his work

checked regularly by the certification body.

2 Description

2.1 Field of application

Fire-resistant roller shutters VR 60:

With a fire resistance rating of one hour (FR 1 h), which is

based on the following test reports:

Test report numbers

Université de Liège, Département de mécanique des Materials

et structures, Laboratoire d’essais au feu, Chemin des Chevreuils

1, 4000 Liège

EF/GF/1038

Institut für Brandschutztechnik und Sicherheitsforschung,

Petzoldstrasse 45, Postfach 27, 4017 Linz (Austria)

06082501

For the following types:

Roller shutter

The performance of which, according to STS 53.2 (in

preparation), has been determined, based on the

following reports:

Test report numbers

Centre Technique de l’Industrie du Bois

8277

The shutters are placed in openings created in concrete, brick or

cellular concrete walls with a minimum thickness of 90 mm and

satisfactory mechanical stability. Lightweight partition walls should

not be used.

The various shutters that make up a door are separated by a over-

mantel, which must have at least the same fire resistance and

mechanical stability characteristics as the partition wall, in which

they are installed.

The wall openings must satisfy the conditions described in § 6.1, so

that the shutters can be fitted according to the conditions

described in § 6.

The floor covering in these openings must hard and flat. Tiling,

parquet flooring, concrete or linoleum can be used.

2.2 Marking and checks

These doors are subject to the integrated BENOR/ATG procedure,

which enables the manufacturer to obtain permission to use the

BENOR/ATG mark shown below.

The BENOR/ATG mark of conformity takes the form of a thin

adhesive label (diameter: 22 mm), based on the following model:

These marks are numbered. They are issued to the manufacturer

exclusively by Bosec.

This mark is added in the factory by the manufacturer to the left-

hand guide at a height of 1.5 m.

No marks must be displayed on the frame.

Only by displaying the above-described BENOR/ATG mark on a

component can the manufacturer certify that this component

complies with the relevant description included in this approval

document:

Component According to paragraph

Materials 3

Shutter:

Description 4.1.1

Dimensions 4.1.1.5

Frame 4.1.2

Guide profiles (1) 4.1.3

Accessories (2) -

(1): if applicable (2): if mentioned on the delivery note

2.3 Delivery and on-site checks

Each delivery of BENOR/ATG doors must be accompanied by a

copy of this approval document, so that acceptance tests can be

conducted after installation.

On-site checks include:

1. Checking that the BENOR/ATG mark is present on the

shutter

2. Checking the conformity of the components described

in the following table

3. Checking the conformity of the installation with the

description included in this approval document

In particular, the checks mentioned in Sections 2 and 3 include:

Component According to paragraph

Materials for installation 3

Dimensions 4.1.1.5

Accessories (3) –

Fitting 6

(3): if the latter are not mentioned on the delivery note.

2.4 Comments regarding requirements described in the

specifications

The fire-resistant shutters have special characteristics, which

enable them to complement, when in closed position, the fire

resistance characteristics of the wall, in which they are installed.

In general, this special performance can only be achieved by

means of the specially designed door and depend on the care

taken when the complete door is assembled (see "Delivery and on-

site checks " - paragraph 2.3).

As a result, the door components (panel, frame, metal fittings,

dimensions, accessories, etc.) must be selected according to the

restrictions of this approval document (see "Delivery and on-site

checks " - paragraph 2.3).

Page 3: ATG Technical Approval with Certification · The presence of the BENOR/ATG mark on a door certifies that the components listed in the following description and tested in compliance

ATG 2782 - 3/15

3 Materials (4)

The Bosec-Benor-ATG office is aware of the trade name and

characteristics of each constituent component. They are checked

by means of samples taken by a delegate of the inspection body,

which is designated by BOSEC.

3.1 Panel

3.1.1 Blades

Pine or multiplex wood (minimum density: 450 kg/m3 ;

wood moisture content: 8 at 12 %)

PVC profile

Intumescent product

3.1.2 Bottom joint

Co-extruded PVC profile (36 mm x 30 mm)

3.1.3 Horizontal blade angle

2 mm-thick steel J-profile

Fitted to the upper shutter blade

Used to hold the door in place in the event of fire

3.1.4 Fastener + inox cable

3 mm diameter cable

Used to assemble the shutter

The fastener is secured on the lower blade

The cable is secured on the adjustable cable fastener

(Section 3.1.5).

3.1.5 Adjustable cable fastener

Used to fasten the shutter to the drum

3.1.6 Blade support

Plastic component

Secured on the adjustable cable fastener (Section 3.1.5).

Enables the door to be rolled up correctly.

3.1.7 Cover

Secured on the blade support (Section 3.1.6).

Reinforcement and finishing part

3.1.8 Motor arm

Keeps and guides the motor on the universal bearing (3.1.13).

3.1.9 Seal cap

Secured on the motor arm (3.1.8).

Keeps the roller in position

3.1.10 Roller

Roller for 30 mm diameter axle

Enables the drum and motor to slide along the universal support

(3.1.13).

3 roll / door

3.1.11 Drum flange

30 mm diameter axle

To be soldered onto one side of the 159 mm diameter tube (3.1.14)

in order to create the drum.

3.1.12 Motor flange

30 mm diameter axle with keyway

For connection to the motor

To be soldered onto one side of the drum (3.1.14) in order to create

the drum.

3.1.13 Universal support

Support, on which the drum is positioned, so that the shutter can

be rolled up

3.1.14 Tube

Outer diameter 159 mm

To be used with the drum flange (3.1.11) and motor flange (3.1.12),

in order to create the drum

3.1.15 Rubber sleeve

To be placed around the cable (3.1.4) and fixed onto the drum

Makes it possible to roll up the shutter without damaging it

3.1.16 Bottom plate

To be placed on each side of the lower part of the shutter

Also makes it possible to secure security cells

(4) The following table shows the permissible deviations for

material characteristics when on-site checks are

conducted:

Material characteristic Permissible deviation

Dimensions of PVC profiles 1 mm

The following table shows the permissible deviations for

material characteristics when checks are conducted

during manufacturing:

Material characteristic Permissible deviation

Core thickness

(mm)

0.5 mm

(based on an average of 5

measurements)

Wood moisture content

(%)

2 %

(based on an average of 5

measurements)

PVC profiles

(mm)

0.5 mm

Section of intumescent

product (mm x mm)

0.2 mm

(based on an average of 5

measurements)

Section of frame

(mm x mm)

0.5 mm

Volume mass

(kg/m3)

- 5 %

(based on an average of 5

measurements)

- 10 %

(based on individual

measurements)

Page 4: ATG Technical Approval with Certification · The presence of the BENOR/ATG mark on a door certifies that the components listed in the following description and tested in compliance

ATG 2782 - 4/15

3.2 Frame

3.2.1 Vertical and horizontal bars of door frame

PVC profile

Intumescent product

Pine (minimum density: 450 kg/m3 ; wood humidity

content: 8 at 12 %)

To be placed around the opening

3.2.2 Perlau

Perlau 20 mm/ 2 mm - To be placed in the wall baffle

Perlau 35 mm / 2 mm - To be placed in the bottom joint

3.2.3 Horizontal angle of lintel

2 mm thick galvanised steel profile, placed above the frame

3.3 Guide profiles

3.3.1 Outer upper vertical angle

To be bolted onto the inner guide, in order to form a “U” shape

Acts as a fastener for the guide wheel (3.3.5)

3.3.2 Outer universal vertical angle

To be placed as an extension below the upper angle (3.3.1) in

order to assemble doors measuring up to 6 metres

3.3.3 Inner universal vertical angle

To be secured on the frame, together with the outer guide (3.3.1),

in order to form a “U” shape

Symmetrical on the left or right

3.3.4 Side ‘U” profile

PVC finishing profile covered with an intumescent product on the

surface that comes into contact with the outer and inner angles

(3.3.1 - 3.3.3).

The shutter slides on this part when the door is opened.

3.3.5 Pair of guide rollers

Makes it possible to align the shutter when rolling up and unrolling

the door

To be secured on the upper higher angle (3.3.1).

3.3.6 M8X19 bolts

Enable the angles to be fixed together.

3.4 Motor

3.4.1 Electric motor MFZ

Main three-phase motor (220 V or 380 V)

24 V back-up motor

3.4.2 Plate CS300

The plate built into the control box MFZ makes it possible to operate

the door automatically and ensure that it is safe.

3.4.3 Adapters

Enable the different motors to be connected to the 30 mm

diameter flange.

3.4.4 Safety cells

Mobile photoelectric barrier consisting of:

1 a pair of unit 4 cells

1 connection box

Makes it possible to ensure that the automatic door is safe.

Maximum movement speed 320 mm/s

3.5 Lightweight partition

It is not permitted to fit a door in a lightweight partition.

4 Components

4.1 Roller shutter, solid, without transom

4.1.1 Panel

The panel consists of:

4.1.1.1 A series of blades

PVC blades with standard dimensions: 63 mm high and 36 mm

thick

Length can be adjusted to the opening (clear width+

200 mm),

A profile with PVC finish (section: 36 mm x 30 mm) is

placed under the shutter,

A J-profile (baffle – section: 22 x 57.5 x 65 x 2 mm) is

placed on the top blade

The shutter is formed by stacking blades, which are threaded

through steel cables. The blades are pierced with 4.5 mm diameter

holes at 400 mm intervals in the core, so that the cables can be

threaded through.

The 3 mm diameter steel cables are secured on the drum every

400 mm.

4.1.1.2 Filling

The blades consist of:

A PVC coating with raised spacers on the inside and a

tongue and groove joint on both sides

A core consisting of two horizontal pine battens

An Intumescent product between the two battens and

coating

4.1.1.3 Covering

Paint can be applied

4.1.1.4 Intumescent product

A strip of intumescent product (section: 35 mm x 2 mm) is placed

on:

The upper edge of the top blade between the blade and

J-profile

The upper edge of the lower blade between the blade

and profile finished with PVC.

Page 5: ATG Technical Approval with Certification · The presence of the BENOR/ATG mark on a door certifies that the components listed in the following description and tested in compliance

ATG 2782 - 5/15

4.1.1.5 Dimensions

The dimensions of each blade are shown in the following table.

Dimensions

Height 63 mm

Thickness 36 mm

The dimensions of the shutter must fall within the following limits:

Dimensions Minimum Maximum

Height 1000 mm 6000 mm

Width 1000 mm 6000 mm

Thickness without coating 36 mm

The maximum surface of the shutter is limited to 30 m².

4.1.2 Frame

The frame consists of:

A PVC profile, filled with pine and intumescent product

(width: 124 mm, thickness: 22 mm) on three sides of the

opening (sides and top);

A steel J-profile (baffle – section: 22 x 24 x 50 x 2 mm) is

placed above the PVC profile on the lintel across the

entire width of the opening; a strip of intumescent

product (section: 20 mm x 2 mm) is placed in this steel

profile.

4.1.3 Guide profiles

Z-profile made from galvanised steel (section: 35 x 77 x

124 x 24 x 2 mm)

J-profile made from galvanised steel (section: 21 x 51 x

103 x 2 mm)

The guide profiles are placed on the frame. The 2 parts form a U-

profile, which is necessary in order to guide the shutter, in which

the PVC side U-profile covered with an intumescent product slides

on the surface that comes into contact with the guide profiles. This

side U-profile serves as an airtight and watertight finish profile.

4.1.4 Movement mechanism

These roller shutters must always be fitted with a mechanism that

causes them to close in the event of fire, together with a

mechanism that keeps them in open position.

The roller shutter works by means of a motor (3 phases / 400 V),

which is connected to a worm drive.

In the event of fire, an additional 24 V motor, powered by a low-

voltage back-up device, ensures that the door is fully closed.

The motor and drive controls form a single unit and are always

supplied with the shutter.

The electric motor of the MFZ type consists of a range of 5 motors,

according to the weight of the shutter:

Ref. Maximum shutter weight

4501 (FDF 20-22-12) 226 kg

4502 (FDF 30-42-12) 431 kg

4503 (FDF 50-60-10) 615 kg

4504 (FDF 50-75-10) 769 kg

4505 (FDF 60-100-9) 1000 kg

5 Manufacture

The office is informed of the manufacturing plants where the

shutters and frame are made, which are also listed in the control

agreement with Bosec. They are labelled in the manner described

in paragraph 2.2.

6 Position

The shutters are stored, processed and positioned as normal

internal doors, according to STS 53.1; it is recommended that the

doors are only installed indoors.

6.1 The opening

The dimensions of the opening are determined, in order to position

the door as described in paragraph §6.2.

The perimeter of the opening must be smooth and level across a

minimum width of 15 cm on the door side.

The finish and level surface of the partition walls must always allow

the door to function properly.

The level floor surface must allow the door to function with the

clearance stipulated in paragraph 6.4.

6.2 Position of the frame

6.2.1 PVC frame

The frame complies with the provisions of § 4.1.2.1.

It must be placed in an opening created in concrete, brick or

cellular concrete walls with a minimum thickness of 90 mm.

Lightweight partition walls should not be used.

The different shutters that make up a door must be separated by an

over-mantel, which must have the same characteristics and stability

as the wall, in which they are installed.

The frame must be square and level.

The PVC profiles and Z-shaped guide profiles are fastened to the

wall at 600 mm intervals using screws and the appropriate plugs

(minimum diameter: 8 mm). The Z-shaped guide profiles are

directly fastened to the wall at 600 mm intervals using screws and

the appropriate plugs (minimum diameter: 8 mm).

If the door is fitted in a cellular concrete partition wall, it must be

secured using torpedo plugs at 600 mm intervals.

If the perimeter of the opening is not sufficiently smooth and a

clearance of over 3 mm is created between the profile and the wall,

it will be necessary to place rockwool between the wall and PVC

profile.

The PVC side U-profile covered with an intumescent product slides

into the guide rail created by the J-profile and Z-profile.

6.3 Fitting the panel

The shutter is slipped in to the U-profile.

The BENOR/ATG mark of conformity is displayed in a visible place

on the left guide at a height of 1.5 m.

The fitter is not permitted to score, cut, pierce, trim or shrink, extend

or enlarge the panel.

Any other necessary adjustments must be carried out by the

manufacturer, in compliance with this technical approval.

Page 6: ATG Technical Approval with Certification · The presence of the BENOR/ATG mark on a door certifies that the components listed in the following description and tested in compliance

ATG 2782 - 6/15

6.4 Clearances

The maximum permissible clearances are shown in the following

table.

The maximum permissible clearance between the panel(s) and

floor must be respected throughout the entire thickness of the

panel when the door is in closed position.

For this purpose, the floor under the door must be sufficiently level.

The latter must be prepared by companies, which are responsible

for levelling floors so that the maximum difference between the

lowest and highest point in the finished floor between the door

(zone 1 in Fig. 3) is equivalent to the maximum permissible

clearance between the panel and the floor.

Maximum permissible clearance (mm)

Between the shutter and bottom of the rail 18

Between the panel and the floor (*) 5

(*): The floor covering must be hard and level, such as tiling,

concrete, linoleum or parquet flooring.

The clearances are measured in all places with a 10 mm wide

gauge.

6.5 Commissioning

The (certified) fitter must, after installation, check that the door

functions properly.

The full closure of the door, from any position, must be checked

and recorded in the installation report.

6.6 Maintenance

The proper functioning of the roller shutter must be checked

regularly (according to the manufacturer’s instructions). This

maintenance, which should preferably be carried out by skilled

persons (e.g. the manufacturer, fitter, etc.) is vital when it comes to

guaranteeing that the doors provide a barrier against fires.

Maintenance includes:

Checking that the door closes fully if a fire is detected,

Checking that it moves freely inside the opening,

Checking the anti-jamming device,

Maintaining the moving parts and motor,

Checking for cable wear,

Immediately repair or replacement by the fitter or

customer of all damaged parts in the shutter or

guide/movement mechanism.

6.7 Safety – personal safety recommendations

In order to ensure that all persons are safe, it is recommend that

the European standard NBN EN 13241-1 (Industrial Doors) is

respected, even though it does not apply to this type of door.

General safety requirements

Motorised shutter

1. Maximum closure speed in the final 1.5 m: 0.3 m/s

2. Danger of persons becoming trapped:

Automatic shutdown per detection zone or

Maximum brake power: 400 N

Note: 1 and 2 also apply in the event of an emergency, detection

and power failure.

General fire safety requirements

The shutter, which closes automatically in the event of

fire, must close from any position if a fire occurs.

The closing system must be controlled by a fairly sensitive

detection system, so that the door closes at a fairly low

temperature, in order to ensure that the door functions

effectively.

Roller shutters should not be seen as an emergency exit.

7 Performance

The performance of the above-described doors has been

determined, based on the following standards:

7.1 Fire resistance

NBN 713.020 "Fire resistance of construction materials", 1968 edition

and Addendum 1, 1982 edition: Fire Resistance: 1 hour,

NBN EN 13501-2 2003 edition: EI1 60, provided the immediate

scope of application of Standard NBN EN 1634-1, 2000 edition, is

respected.

7.2 Mechanical resistance

Tests were conducted on a shutter with the clear dimensions of 4 m

x 4 m, according to the STS 53.2 specifications, unless otherwise

mentioned.

7.2.1 Mechanical durability according to NBN EN 12605,

requirements according to NBN EN 12604

Number of cycles: 2000

7.2.2 Safe opening according to NBN EN 12605, requirements

according to NBN EN 12604

The door meets these requirements (for max. 750 kg)

7.2.3 Manoeuvring forces according to NBN EN 12445 or

NBN EN 12978, requirements according to NBN EN 12453

or NBN EN 12978

The door meets these requirements.

7.3 Conclusion

A VR60 roller shutter, with the clear dimensions of 4 m x 4 m, is

classified as follows:

FLEMA VR 60

Performance Class

Fire resistance Fire resistant for 1 hour

EI1 60

Frequency of use 2000 cycles

Safe opening The shutter meets the

requirements

Manoeuvring forces The shutter meets the

requirements

Page 7: ATG Technical Approval with Certification · The presence of the BENOR/ATG mark on a door certifies that the components listed in the following description and tested in compliance

ATG 2782 - 7/15

Description Image Diagram

Panel

Text ref.: 3.1

Blade

Text ref.: 3.1.1

Flema ref.: 3051, 3052, 3053, 3054

Bottom joint

Text ref.: 3.1.2

Flema ref.: 2001, 2002

Horizontal angle of blade

Text ref.: 3.1.3.

Flema ref.: 6251

Fastener + inox cable

Text ref.: 3.1.4

Flema ref.: 1101, 1102, 1103

Adjustable cable fastener

Text ref.: 3.1.5

Flema ref.: 2601

Page 8: ATG Technical Approval with Certification · The presence of the BENOR/ATG mark on a door certifies that the components listed in the following description and tested in compliance

ATG 2782 - 8/15

Blade support

Text ref.: 3.1.6

Flema ref.: 2501

Cover

Text ref.: 3.1.7

Flema ref.: 2701

Motor arm

Text ref.: 3.1.8

Flema ref.: 4003

Seal cap

Text ref.: 3.1.9

Flema ref.: 4001

Roller

Text ref.: 3.1.10

Flema ref.: 1301

Drum flange

Text ref.: 3.1.11

Flema ref.: 4004

Page 9: ATG Technical Approval with Certification · The presence of the BENOR/ATG mark on a door certifies that the components listed in the following description and tested in compliance

ATG 2782 - 9/15

Motor flange

Text ref.: 3.1.12

Flema ref.: 4004

Universal support

Text ref.: 3.1.13

Flema ref.: 1201

Tube

Text ref.: 3.1.14

Flema ref.: 5001, 5002

Rubber sleeve

Text ref.: 3.1.15

Flema ref.: 5030

Bottom plate

Text ref.: 3.1.16

Flema ref.: 5050

Page 10: ATG Technical Approval with Certification · The presence of the BENOR/ATG mark on a door certifies that the components listed in the following description and tested in compliance

ATG 2782 - 10/15

Frame

Text ref.: 3.2

Fire-resistant frame profile

Text ref.: 3.2.1

Flema ref.: 2451, 2452

Perlau

Text ref.: 3.2.2

Flema ref.: 7010, 7012

Horizontal angle of the lintel

Text ref.: 3.2.3

Flema ref.: 6201

Guide profiles

Text ref.: 3.3

Upper outer vertical angle

Text ref.: 3.3.1

Flema ref.: 6001, 6002

Outer universal vertical angle

Text ref.: 3.3.2

Flema ref.: 6051, 6052, 6053

Inner universal vertical angle

Text ref.: 3.3.3

Flema ref.: 6101, 6102, 6103

Page 11: ATG Technical Approval with Certification · The presence of the BENOR/ATG mark on a door certifies that the components listed in the following description and tested in compliance

ATG 2782 - 11/15

Side U-profile

Text ref.: 3.3.4

Flema ref.: 2201, 2202, 2203

Pair of guide rollers

Text ref.: 3.3.5

Flema ref.: 1001

Bolts M8x19

Text ref.: 3.3.6

Flema ref.: 4005

Motor

Text ref.: 3.4

Electric motor MFZ

Text ref.: 3.4.1

Flema ref.: 4501, 4502, 4503, 4504, 4505

Page 12: ATG Technical Approval with Certification · The presence of the BENOR/ATG mark on a door certifies that the components listed in the following description and tested in compliance

ATG 2782 - 12/15

Figure 1

Page 13: ATG Technical Approval with Certification · The presence of the BENOR/ATG mark on a door certifies that the components listed in the following description and tested in compliance

ATG 2782 - 13/15

Figure 2

Page 14: ATG Technical Approval with Certification · The presence of the BENOR/ATG mark on a door certifies that the components listed in the following description and tested in compliance

ATG 2782 - 14/15

Figure 3

8 Conditions

A. This technical approval exclusively covers the product

mentioned on the cover page of the Technical Approval.

B. Only the approval holder and, if applicable, the

distributor may assert rights based on the Technical

Approval.

C. The approval holder and, if applicable, the distributor are

not permitted, in any way, to use the name of the UBAtc,

its logo, the ATG mark, the Technical Approval or the

approval reference for product evaluations that fail to

comply with the Technical Approval or products, kits or

systems, including their properties or characteristics,

which do not form the object of the Technical Approval.

D. Information provided in any way by the approval holder,

distributor or a recognized contractor or by their

representatives to (potential) product users (e.g. for

clients, contractors, architects, consultants, designers,

etc.), which is specified in the Technical Approval may

not be incomplete or contradict the content of the

Technical Approval or information referred to in the

Technical Approval.

E. The approval holder is at all times obliged to provide

UBAtc, the approval operator and the certification

operator with prompt and prior notification of any

adjustments made to raw materials and products,

installation instructions and/or the manufacturing and

installation processes and equipment. Depending on the

information communicated, the UBAtc, the approval

operator and the certification operator will judge

whether it is necessary to adjust the Technical Approval.

F. The Technical Approval is based on the available

technical and scientific knowledge and information,

complemented by information provided by the

applicant and completed by an approval examination,

which takes account of the specific nature of the

product. Nevertheless, users remain responsible for

selecting the product as specified in the Technical

Approval, for specific uses intended by the user.

G. The intellectual property rights associated with the

Technical Approval, including the copyright, belong

exclusively to the UBAtc.

H. Any references to the Technical Approval shall be

accompanied by an ATG reference (ATG 2782) and the

validity period.

I. The UBAtc, the approval body and the certification body

cannot be held responsible for any damage or adverse

consequences suffered by third parties (e.g. the user)

that result from the failure of the approval holder or

distributor to respect the provisions of Article 9.

Page 15: ATG Technical Approval with Certification · The presence of the BENOR/ATG mark on a door certifies that the components listed in the following description and tested in compliance

UBAtc npo is an approval body which is member of the European Union for Technical

Approval in Construction (UEAtc, zie www.ueatc.eu) en dat aangemeld werd door de

FOD Economie in het kader van Verordening (EU) n°305/2011 en lid is of the European

Organisation for Technical Assessments (EOTA, see www.eota.eu). Certification bodies

designated by UBAtc npo operate in compliance with a system that may be accredited

by BELAC (www.belac.be).

This Technical Approval has been published by UBAtc, under the responsibility of the approval operator ANPI, and based on a favourable

opinion by specialist group "PROTECTION PASSIVE CONTRE L'INCENDIE ", expressed on 13 June 2013.

In addition, the certification operator, ANPI, confirmed that the production process meets the conditions for certification and that a

certification agreement has been signed by the ATG holder.

Date of issue: 30 December 1899.

This ATG supersedes ATG 09/2782, valid from 22/01/2009 to 21/01/2012. Changes from previous versions are listed below:

For UBAtc, declaration of the validity of the approval process For the approval and certification operator

Peter Wouters, director Benny De Blaere, director

Alain Verhoyen, general

manager Bart Sette, director

This technical approval shall remain valid, provided that the product, its manufacture and

all related processes:

are maintained, in order to achieve, as a minimum, the examination results

specified in this Technical Approval;

are continuously monitored by the certification operator, which confirms that the

certification continues to be valid;

If these conditions are no longer met, the Technical Approval shall be suspended or

withdrawn and the Technical Approval shall be removed from the UBAtc website. Technical

approvals are regularly updated. It is recommended to always use the version published on

the UBAtc website (www.ubatc.be).

The most recent version of the Technical Approval may be consulted using the adjacent QR

code.