10
The Assessment of Instrument transformers by Dielectric Response Analysis By Stephanie Raetzke Maik Koch Andreas Schroecker Michael Krueger

Assessment of Instrument Transformers

Embed Size (px)

Citation preview

Page 1: Assessment of Instrument Transformers

The Assessment of Instrument transformers

by Dielectric Response Analysis

By

Stephanie Raetzke

Maik Koch Andreas Schroecker

Michael Krueger

Page 2: Assessment of Instrument Transformers

SECOND PAGE IS LEFT BLANK

Page 3: Assessment of Instrument Transformers

THE ASSESSMENT OF INSTRUMENT TRANSFORMERS BY DIELECTRIC RESPONSE

ANALYSIS

Stephanie Raetzke, Maik Koch, Andreas Schroecker, Michael Krueger Omicron Electronics

Abstract

The dielectric response analysis is typically used to assess the condition of power transformers.

Due to its wide frequency range it is possible to distinguish between different effects and

information about the moisture in the solid insulation, the oil conductivity and the insulation

geometry are obtained. This paper presents and discusses the application of the dielectric

response analysis to other assets like instrument transformers. The method can be used to get

valuable information about the insulation condition, since the insulation is also made of oil and

cellulosic material, even though the geometry is different compared to power transformers.

Typical measurements on instrument transformers are shown. Similar to power transformers, the

curves are influenced by moisture, temperature and ageing. The cause and effect of each factor

will be explained. Extensive measurements on instrument transformers were done and the

results are analyzed. The paper will introduce characteristic parameters like dissipation factor

and capacitance ratios at different frequencies, which indicate the health of instrument

transformers. Threshold values will be discussed and a possible interpretation scheme is

presented, which may be used for asset management.

Introduction

Instrument transformers are important apparatuses used in transmission and distribution networks all over the world. As instrument transformers were not as expensive as eg. Power transformers, they were replaced rather than repaired. However, a defect instrument transformer can explode, what may cause extensive damages of surrounding plant sections. To avoid such kind of failures with expensive secondary damages, several tests can be performed to determine the condition of instrument transformers. The choice of tests and the testing frequency is widely varying from utility to utility. Typical are for example visual inspection, oil analysis and DGA, insulation resistance measurement, high voltage withstand tests, partial discharge measurement or ratio checks [1]. Also the measurement of

dielectric properties, like the dissipation factor (tan) or capacitance at mains frequency (50/60 Hz) is often used to gain information about the condition of the oil-paper insulation. However, e.g. moisture, oil properties and temperature strongly influence the dissipation factor reading at mains frequency, what causes uncertainties in analysis. The measurement over a wide frequency range can help to distinguish between different effects for a more detailed analysis of the insulation condition.

Dielectric response measurement on instrument transformers Dielectric response methods have been developed to deduce moisture in paper and pressboard from dielectric properties like polarization currents and dissipation factor [2]. They are typically used to assess the condition of power transformers, but can also be applied to other oil-paper/pressboard-insulations like bushings, cables or instrument transformers. Due to the wide frequency range of the dielectric response measurement it is possible to distinguish between different effects and gain information about the insulation condition itself, moisture in the solid insulation or oil conductivity [3].

Page 4: Assessment of Instrument Transformers

Ageing and moisture in oil paper insulations Common instrument transformers are oil paper isolated, which is ageing during their life span. The ageing of the insulation is depending on some influencing factors, like e.g. the temperature, present oxygen, water or acids. Especially water in the solid insulation can be critical [4]. Existing water causes hydrolysis, which has water as a chemical product. Therefore the water is an accelerator for ageing of the solid insulation. Typically, new oil-paper-insulations have a very low water content of 0.5% or less in the solid insulation. During service the water content is increasing due to e.g. leakages and hydrolysis. Above 2.2% water content the solid insulation is called moderately wet [3], what is typical for instrument transformers being in service for several years. At the physically end of life, the insulation is often wet having a water content of 3.5% or above. Even though water content in the solid insulation is no direct measure for ageing, it is a strong indicator for the condition of the solid insulation. Dielectric response of instrument transformers

f /Hz0.001 0.01 0.1 1.0 10.0 100

DF

0.005

0.010

0.020

0.050

0.100

0.200

0.500

1.000 1%@20°C

3

2

1

Figure 1 Dielectric response of cellulosic material at 20°C with 1% (2% and 3%) water content

The setup for the dielectric response measurement is the same as for traditional dissipation factor measurement at mains frequencies. The resulting curves are similar to the single response of cellulosic material without any oil (Figure 1) [5], since the insulation itself consists mainly of paper material. Figure 2 shows the dielectric response curves of four CTs of the same type. All of them were manufactured and in service since 1963, having nearly identical slopes, suggesting a similar ageing behavior. Like for the cellulosic material only, the dielectric dissipation factor (DF) is decreasing with increasing frequency, usually having a minimum around 1-100 Hz. Especially at low frequencies, the slope of the curves seems to be linearly. As for other oil-paper-insulations, the temperature as well as the oil conductivity is strongly influencing the dielectric response. Higher temperatures and higher oil conductivities are shifting the curves towards higher frequencies [6].

Page 5: Assessment of Instrument Transformers

frequency in Hz

Figure 2 Dielectric response four CTs of the same type, manufactured in 1963 (110N / 260kV), having a water

content of 1.8 – 1.9% and an oil conductivity of 3 – 6 pS/m

0,001

0,01

0,1

1

10

0,01 0,1 1 10 100 1000

Dis

sip

atio

n F

acto

r

Frequency in Hz

old; 4% water content, 9 pS/m oil conductivity

old; 2% water content, 2 pS/m oil conductivity

new; 1,2% water content, 3 pS/m oil conductivity

new; 0,5% water content, 6 pS/m oil conductivity

Figure 3 Dielectric response of instrument transformers of different age and condition

Comparing instrument transformers of different age and condition (Figure 3), we can find significant differences between the curves. Newly manufactured and very dry instrument transformers have a very flat response. Both, water content and ageing result in a steeper slope at lower frequencies. However, the values for the dissipation factor at mains frequencies are in the same range as for new

Page 6: Assessment of Instrument Transformers

ones. Only for the heavily aged and wet instrument transformer the dissipation factor at mains frequency is significantly enhanced. The slope of this curve clearly differs compared to the others. Having very high dissipation factors at all frequencies the curve shows a hump, which is not apparent for the other curves.

Moisture determination The moisture determination using the dielectric response curves is based on a comparison between the measured curve and a modeled curve (Figure 4). The curve modeling is done with help of a data base including data about the material properties of cellulosic material with different water contents and temperatures. Using the so called XY-model [6], a dielectric response is calculated under consideration of the insulation geometry, temperature, oil and moisture content. A fitting algorithm aligns the dielectric response of the data base to that of the real insulation and automatically delivers the oil conductivity, the water content of the cellulose material as well as the moisture saturation.

Measurement

Temperature

Insulation geometryXY-model

moisture content,

(oil conductivity)

Comparison

(Oil)

Data base

Figure 4 Calculation of the water content based on comparison

of the measured dielectric response to a modeled curve The used XY-model is developed to model the properties of oil-paper insulations, initially for power transformers. The model takes into account the amount of barriers and spacers of the insulation. Instrument transformers consist as well of a cylindrical insulation, similar to power transformers. The main part of the insulation (70% - 90%) is consisting of paper, enwrapping the inner conductor and therefore having similar behavior as barriers. Also oil gaps exist, as between spacers of power transformer insulations. Therefore it is assumed, that the XY-model can be applied to instrument transformers. Investigations on several instrument transformer measurements showed, that this approach is adequate for the dielectric response analysis on instrument transformers. Assessment of insulation condition using dielectric response In this investigation more than 30 instrument transformers of different types and designs were measured and the results are used in the following chapter to identify meaningful parameters to assess the insulation condition. Since there is no direct quantification for ageing, the water content in the solid insulation is used as an indicator for the insulation condition. However, using the dielectric response more measured parameters are gained, which can be used for decision trees in asset management.

Page 7: Assessment of Instrument Transformers

Relationship between moisture and dissipation factor at different frequencies A typical measurement providing information about the insulation condition of high voltage assets is the dissipation factor measurement at mains frequency (Figure 5, left). This value tends to increase for higher moisture contents in the solid insulation. However, the dissipation factor at 50 Hz is having very similar values for dry insulations and insulations with water content up to about 3%. This is reasonable, since the slope of the dissipation factor has the smallest steepness and its minimum around mains frequencies. A high measured dissipation factor of more than 0.01 would therefore indicate high water content, what is usually a sign for bad insulation condition. However, the value seems not to be capable to display the increasing moisture for dry and moderate insulations.

0,001

0,010

0,100

0 1 2 3 4 5

DF

(50 H

z)

water content in %

0,1

1,0

10,0

0 1 2 3 4 5

DF

(10 m

Hz)

water content in %

Figure 5 Dissipation factor at 50 Hz (left) and 10 mHz (right) and water content

for various instrument transformers of different condition

The dielectric response enables to analyze also lower frequencies, e.g. the dissipation factor at 10 mHz (Figure 5, right). This value also tends to increase with increasing water content in the solid insulation. As it can be seen also in Figure 3, moisture as well as ageing is increasing the slope of the dissipation factor curve leading to higher values at 10 mHz. Therefore it is more sensitive to progressive moisture and ageing also in first stages. Influence of oil conductivity The oil conductivity of the measured instrument transformers is widely spread for all frequencies and there is no direct relation between both (Figure 6). Since the oil conductivity strongly influences the slope of the dielectric response, it is very important to differentiate between effect of moisture ingress and oil conductivity. This is not possible with a measurement at mains frequency. Only a wide frequency range enables to differentiate between the effects of moisture and oil conductivity [3].

Page 8: Assessment of Instrument Transformers

0,1

1

10

100

0 1 2 3 4 5

oil

co

nd

ucti

vit

y in

pS

/ m

water content in %

Figure 6 Oil conductivity and water content

for various instrument transformers of different condition

tance An ideal insulation has a stable capacitance for all frequencies. However, the capacitance of a real insulation is slightly increasing towards low frequencies (Figure 7, left). This increase can be visualized in the ratio of the capacitances at 10 mHz and 50 Hz (Figure 7, right). They have a clear tendency to increase with increasing water content. This finding suggests the capacitance ratio as a good value, which can be used for assessment decisions.

100

1.000

0,01 1 100

Cap

acit

an

ce i

n p

F

Frequency in Hz

old; 4% water content, 9 pS/m oil conductivity

old; 2% water content, 2 pS/m oil conductivity

new; 1,2% water content, 3 pS/m oil conductivity

new; 0,5% water content, 6 pS/m oil conductivity

1,0

1,2

1,4

1,6

1,8

0 1 2 3 4 5

C1

0 m

Hz

/ C

50

Hz

water content in %

Figure 7 Frequency dependent capacitances of various instrument transformers depending on frequency (left)

and ratio of capacitance values between 10 mHz and 50 Hz (right)

Interpretation Scheme

For an effective asset management a reliable scheme is needed for funded conclusions on the condition of the single power assets. Here a possible interpretation scheme is suggested, using the discussed values gained by the dielectric response. Besides the dielectric response, other measured values can be

Page 9: Assessment of Instrument Transformers

used. However, this schemes is constricted to the dielectric values, moisture and oil conductivity all with reference to 25°C.

Step 1: regularly testing, e.g. every second year Regularly testing can be done by a dielectric response measurement and condition assessment afterwards. Following requirements should be fulfilled:

DF at 50 Hz < 0.01 Water content < 2,2% Oil conductivity < 10 pS/m

If an instrument transformer fails, the instrument transformers probably have a defect or ageing or moisture ingress is progressive. Further investigations should be done.

Step 2: extraordinary investigations For conspicuous instrument transformers, following requirements can be used for further investigations:

DF at 10 mHz < 1 C10mHz / C50Hz < 1.3

If an instrument transformer passes the test, retesting after e.g. six months should be recommended. For instrument transformers, which fail, a replacement plan should be formulated.

Conclusion

The dielectric response analysis, typically used for power transformer can also be applied to instrument transformers. The measurement of the dielectric properties over a wide frequency range enables to distinguish between main influencing effects like moisture content, oil conductivity and temperature. So the dielectric response analysis of instrument transformer enables a funded condition assessment of the insulation. Besides water content in the solid insulation and oil conductivity, further values like the dissipation factor and capacitances at different frequencies can be used to gain information about the insulation condition. A possible interpretation scheme helps to conclude a further plan of action.

References 1. "State of the Art of Instrument Transformers", CIGRÉ Study Committee A3, Technical Brochure

394, Paris, 2009 2. S. M. Gubanski, et al.: “Dielectric Response Diagnoses for Transformer Windings” CIGRÉ Task

Force D1.1.14, Technical Brochure 414, Paris, 2010 3. M. Koch, M. Krueger: “A Fast and Reliable Dielectric Diagnostic Method to Determine Moisture

in Power Transformers”, International Conference on Condition Monitoring and Diagnosis CMD, Peking, China, 21 - 24 April 2008

4. Sokolov et al.: “Moisture Equilibrium and Moisture Migration within Transformer Insulation

Systems”; Cigré Working Group A2.30, Technical Brochure 359, Paris 2008 5. M. Koch, M. Krueger, M. Puetter: " Advanced Insulation Diagnostic by Dielectric Spectroscopy";

TechCon Asia Pacific, Sydney, Australia, May 2009 6. M. Koch: "Reliable Moisture Determination in Power Transformers”, PhD thesis, Institute of

Energy Transmission and High Voltage Engineering, University of Stuttgart, Sierke Verlag Göttingen, Germany, 2008.

Page 10: Assessment of Instrument Transformers

Biography Stephanie Raetzke is product manager for primary testing solutions of Omicron Energy, Austria. She studied electrical engineering at the Technical University Munich, where she graduated in 2003 with a Dipl.-Ing. Degree. In 2009 she received her PhD in high voltage engineering also from Technical University Munich. Her research focus lies on materials for high voltage insulations and their properties, especially the dielectric response analysis. Maik Koch leads the product management of Omicron electronics, Austria. He graduated as a Doctor of Philosophy at the University of Stuttgart in Germany in 2008. He is specialized in ageing and moisture determination of oil paper insulated power transformers using chemical and electrical analysis methods. He contributes to working groups of Cigrè and IEEE and has published more than 50 scientific papers. His career started with an apprenticeship as an electrician (1988). Thereafter he studied Electrical Engineering at the University of Applied Science “Lausitz” in Germany where he graduated in 1995. For seven years he worked with various companies. Meanwhile he studied electrical engineering and received his Diploma degree at the Technical University of Cottbus in Germany in 2003. From 2003 to 2007 he has been working as a scientific assistant at the University of Stuttgart in Germany before he joined Omicron in 2007. Andreas Schroecker is responsible for technical sales and application for Omicron electronics Asia Ltd., Hong Kong. Starting his professional career in technical and application support, he was responsible for technical sales and applications for different countries, before focusing on South-East Asia. 1996 he graduated from electrical engineering college (HTL) in Bregenz (Austria) and 1999 from commercial college (HAK Kolleg) in Innsbruck (Austria) Michael Krueger is head of the OMICRON Engineering Services, which is a competence center for primary testing. He studied electrical engineering at the University of Aachen (RWTH) and the University of Kaiserslautern (Germany) and graduated in 1976 (Dipl.-Ing.). In 1990 he received the Dr. techn. from the University of Vienna. Michael Krueger has 30 years experience in high voltage engineering and insulation diagnosis. He is member of VDE, Cigré and IEEE.