Advantech AE Technical Share Document
Date
2015 / 04 / 07
SR#
Category
□ FAQ■ SOP
Related OS
Win7/ WinXP
Abstract
Connection Guide of Panel Express for S7-1500 Ethernet
Keyword
WOP/ WebOP/ Siemens/ S7-1500/ Panel Express
Related Product
Panel Express/ WOP-2000V Series/ WOP-2000T Series
· Problem Description:
This connection guide introduces how to connect Siemens S7-1500 with WebOP HMI. User can set the communication setup in TCP/IP and it can connect Siemens S7-1500 with WebOP HMI.
Note: this document could also be adapted with WOP-2000V/WOP-2000T Series.
System Architecture:
Hardware:
HMI
Manufacturing Company
Order number
Description
Advantech
PE-TPC1251-01NA01K
COMPUTER SYSTEM, TPC-1251T w/PE 1500 Tag, CFast 32Gb, WES7Pro
Advantech
PE-TPC1551-01NA01K
COMPUTER SYSTEM, TPC-1551T w/PE 1500 Tag, CFast 32Gb, WES7Pro
PLC
Manufacturing Company
Order number
SIEMENS
S7-1500 CPU 1516-3 PN/DP
· Brief Solution - Step by Step:
S7-1500 PLC setting
1. Create a new project:
2. Add a new device: SIMATC S7-1500 CPU 1516-3 PN/DP
3. In PLC_1 [CPU1516-3 PN/DP], choose properties.
Please confirm 2 points setting:
4. Create a new data block:
a. chooses “Add new block”
b. choose “Data block”:
c. Set the “Name”: DBW0, and set “Data type”: Array [0..10] of Int.
d-1. Choose Data_block_1 [DB1] properties:
d-2. Choose “Attributes”(optimized block access cancel
5. Extended download to device(Load
Continue without synchronization
“No action” change to “Re-initialize”.
Program is load to CPU
6. Hardware setting: setting(Date & Time(General
(General remember change date data)
WebOP Designer General setting:
Link Type: Direct Link (Ethernet)
Device/Server: Siemens AG/ SIMATIC S7 (Ethernet)
Setting Parameter: IP Address(192.168.1.1(same the S7-1500 X2 port)
Setting Numeric Entry: DB1.DBW0~DB1.DBW9
Monitor Data_block_1 data & started Panel Express runtime: