Upload
abhishek-narayan
View
218
Download
0
Embed Size (px)
Citation preview
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 1/27
Ventilation for Acceptable
Indoor Air Quality62.1-2004
Dave Kahn, P.E.Dave Kahn, P.E.
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 2/27
The Industries Ventilation Standard
Consensus Standard
Standard of CareUsed in NFPA 5000 BuildingConstruction and Safety Code
LEED Requirement
Adopted by the 97 UniformBuilding Code
Not adopted by 03 or 06 IMC
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 3/27
1973 First Issued office 15 cfm/p
1981 Lower Rates office 5 cfm/p
1989 Higher Rates office 20 cfm/p
1999 Little Change office 20 cfm/p
2001 More Mandatory Language
2004 Key Changes
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 4/27
Area-related and occupancy-related ventilationcomponents (62N 2001)
Minimum Ventilation Rate Table revised to applyonly to nonsmoking spaces
Appendix G Existing buildings
Indoor air humidity (65% max) and pressure
requirements (positive when dehumidifying)Requirement to deliver outdoor air to occupiedspaces
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 5/27
Means to balance the system to achieve minimumairflow.
Design documentation to state ventilation rate andair distribution assumptions.
Controls to enable the fan to operate wheneverthe spaces served are occupied.
VAV systems with fixed OA dampers must complyat minimum supply airflow.
MERV 6 filters upstream of all coils or otherdevices with wetted surfaces.
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 6/27
Ventilation Rate ProcedureMost commonly used method
Lookup table
Need zone air distribution effectiveness
LEED requires this method
Indoor Air Quality ProcedureDesign to maintain specific contaminant levels
Mass Balance Analysis
Methods used in similar buildings
Validation by contaminant monitoring
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 7/27
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 8/27
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 9/27
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 10/27
Single zone 2004
High School classroom 35 x35 30 people
Vbz
= Rp
Pz
+ Ra
Az
10 cfm /person 10 * 30 = 300 cfm
0.12 cfm/ft2 0.12 * 35 * 35 = 147 cfm
300 + 147 = 447 cfm
Zone outdoor airflow Voz =Vbz / Ez
447 /1 = 447 cfm or 14.9 cfm/person
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 11/27
Single zone 2001
High school classroom 35 x 35 30 people
15 cfm /person 15 * 30 = 450 cfm cfm
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 12/27
Single zone IMC
High school classroom 35 x 3530 people
15 cfm/person
50 people/1000 ft2
50/1000 * 35 * 35 = 61.25 people
62 * 15 = 930 cfm
403.3 Ventilation rate. The occupant load utilized
for design of the ventilation system shall not be less
than the number determined from the estimated
maximum occupant load rate indicated in
Table 403.3.Exception: The occupant load is not required to be
determined, based on the estimated maximum occupant
load rate indicated in Table 403.3 where approved
statistical data document the accuracy of an alternate
anticipated occupant density.
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 13/27
Single zone 2004
Hotel auditorium 40 x30 , 170 people
Vbz = RpPz + RaAz
5 cfm /person 5 * 170 = 850 cfm
0.06 cfm/ft2 0.06 * 40 * 30 = 72 cfm
850 + 72 = 922 cfm
Zone outdoor airflow Voz =Vbz / Ez
922 /1 = 922 cfm or 5.4 cfm/person
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 14/27
Single zone 2001
Hotel auditorium 40 x30 , 170 people
15 cfm/person
15 * 170 = 2,550 cfm
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 15/27
Single zone 2003 IMC
Hotel auditorium 40 x30 , 170 people
15 cfm/person
15 * 170 = 2,550 cfm
Estimated maximum occupancy:120 people/1000 ft2 or 144 people
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 16/27
Smoking areas shall have more ventilationand/or air cleaning than comparable
non-smoking areas.
Specific ventilation rate requirements cannotbe determined until cognizant authorities
determine the concentration of smoke thatachieves an acceptable level of risk
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 17/27
Primary outdoor air fraction Zp
Zp = Voz /Vpz
Voz - zone outdoor airflow
Vpz - minimum zone primary airflow(supply air)
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 18/27
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 19/27
Vou = D all zonesRpPz + all zones RaAz
Vou - uncorrected outdoor air intakeD - occupant diversity = Ps / all zones Pz
Ps -total population of area servedby the system
Pz - largest number of peoplein the zone
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 20/27
Vot = Vou /Ev
Vot - design outdoor air intake flow
Vou - uncorrected outdoor air intake
Ev - ventilation efficiency from Table 6-3or Appendix A
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 21/27
0.070.300.070.15Primary outdoor air fraction, Voz/VpzmZp
1200120012001200The minimum value of the primary airflow tozone from air handler. In CAV systems, Vpzm= Vpz. cfm
Vpzm
1200120012001200Primary airflow to zone from air handler. InVAV systems, use the design value. cfm
Vpz
#DIV/0!8935689178Outdoor airflow to the zone corrected for zone
air distribution effectiveness, (Pz*Rp +Az*Ra)/Ez, cfm
Voz
0.90.90.90.9Zone air distribution effectiveness, Table 6.2Ez
0301206060Az*Ra
05020020100Pz*
Rp
0.060.060.120.060.06People outdoor air rate from Table 6.1,cfm/person
Ra
551055Area outdoor air rate from Table 6.1, cfm/ft2Rp
1020420Zone population, largest # of people expectedto occupy zone
Pz
500100010001000Floor area of zone, ft2Az
Office
space
Conference /
meeting
Classrooms (age 9
plus)
Reception
areas
Office
space
Space type (select from pull-down list)
Zone 4Zone 3Zone 2Zone 1Zones served by system
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 22/27
= Vot/Sum of Vpz11%552Minimum outdoor air intake, Vou/Ev, cfmVot
Percent outdoor air intake
0.80System ventilation efficiency, Table 6.3 based on maxZpEv
0.30Max ZpMax Zp
SYSTEM EFFICIENCY
Not used in calculation0.09Mixing ratio at primary air handler of uncorrected outdoor air intaketo system primary flow, = Vou/Vps
Xs
441Uncorrected outdoor air intake, = D* Rp*Pz + Ra*Az, cfmVou
0.46Occupant diversity, ratio of system peak occupancy to sum of spacepeak occupancies, = Ps/ Pz
D
25System population, maximum simultaneious # of occupants of
space served by system
Ps
SYSTEM LEVEL
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 23/27
Reset outdoor air intake flow.Occupancy
Expected occupancy scheduled by time of day.
Occupancy sensors.Estimate occupancy based on CO2.
Air Distribution EfficiencyIf min OA determined in heating mode, OA can be reduced duringcooling due to a higher EzSolve equations in appendix A dynamically based on zone andsystem flows to reset zone minimums and outdoor airflow.
Don t drop below the area outdoor air rate Ra.Economically limited to high-density occupancies.
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 24/27
CO2.
Time averaging to reduce zone population is not
allowedConstant Volume with no air flow measurement
At CO2 max, damper positioned to admit Vot designoccupancy
At ambient CO2 levels set minimum to admit requiredair quantity with no occupants Vat
Linear reset between CO2max and CO2 ambient
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 25/27
CO2 with VAV Systems%CO2 = (CR -400)/(CR-max 400) 400 ppm ambient assumed
VAV Box Primary Air
ResetSystem OA Setpoint Reset
CR zone concentration
Cooling Max
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 26/27
Read the standard
Handbook is available
ASHRAE courses
8/8/2019 ASHRAE62.1-2007ChapterPresentation
http://slidepdf.com/reader/full/ashrae621-2007chapterpresentation 27/27