ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION 1811 WEST COMMERCIAL - P.O. BOX 47 TELEPHONE (479) 667-2176 OZARK, ARKANSAS 72949 DRAWN BY: J.CALLOWAY DATE: 06.19.2017 REVISION#: 0 General Approved materials will be used as backfill for the first 12” (1 foot) of ditch to protect our facilities from damage. Arkansas Valley Requests that 12” (1 foot) of back fill is over conduit and Arkansas Valley also requires red warning ribbon (provided by Arkansas Valley) to be installed in ditch before the rest of ditch is backfilled. Please call Arkansas Valley one working day in advance of backfilling ditch, for installation of red warning ribbon. If red warning ribbon is not installed before ditch is fully backfilled, AVECC may require you to re-dig ditch to 12” (1 foot) above conduit so red warning ribbon can be installed. All ditches must be excavated all the way to pole, exposing the pole to bottom of ditch. Primary Underground Ditch Specifications Underground primary line should be back filled before it is energized. Width: Single Phase 12” (1 foot) Minimum 3 Phase 24” (2 foot) Minimum Depth: From Existing Ground Line 3 Phase & Single Phase - 48” (4 foot) Exception 1: If a 48” (4 foot) deep ditch cannot be obtained, a minimum of 36” (3 foot) ditch is requested. (This exemption is only valid under certain situations and permission must be granted by Arkansas Valley) Exception 2: If 36” cannot be obtained, a ditch 30” (2.5 feet) deep is acceptable if 4” of concrete is poured above top of conduit in areas that are within that depth. If concrete is used, Arkansas Valley must inspect concrete areas before ditch is back filled. The ditch cannot be less than 30” (2.5 feet). Secondary Underground Ditch Specifications Width: 12” (1 foot) Minimum Depth: 24” (2 foot) Exception: If 24” (2 foot) cannot be obtained, 18” (1.5 feet) deep is allowable if 4” of concrete is poured above top of conduit. The ditch cannot be less than 18” (1.5 feet) DOC#: DOCS-0000001

ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

DRAWN BY: J.CALLOWAY DATE: 06.19.2017 REVISION#: 0

GeneralApproved materials will be used as backfill for the first 12” (1 foot) of ditch to protect our facilities fromdamage. Arkansas Valley Requests that 12” (1 foot) of back fill is over conduit and Arkansas Valley also

requires red warning ribbon (provided by Arkansas Valley) to be installed in ditch before the rest of ditch isbackfilled. Please call Arkansas Valley one working day in advance of backfilling ditch, for installation of

red warning ribbon. If red warning ribbon is not installed before ditch is fully backfilled, AVECC mayrequire you to re-dig ditch to 12” (1 foot) above conduit so red warning ribbon can be installed. All ditches

must be excavated all the way to pole, exposing the pole to bottom of ditch.

Primary Underground Ditch SpecificationsUnderground primary line should be back filled before it is energized.

Width:Single Phase 12” (1 foot) Minimum

3 Phase 24” (2 foot) Minimum

Depth: From Existing Ground Line3 Phase & Single Phase - 48” (4 foot)

Exception 1: If a 48” (4 foot) deep ditch cannot be obtained, a minimum of 36” (3 foot) ditch is requested.(This exemption is only valid under certain situations and permission must be granted by Arkansas Valley)

Exception 2: If 36” cannot be obtained, a ditch 30” (2.5 feet) deep is acceptable if 4” of concrete is pouredabove top of conduit in areas that are within that depth. If concrete is used, Arkansas Valley must inspectconcrete areas before ditch is back filled. The ditch cannot be less than 30” (2.5 feet).

Secondary Underground Ditch SpecificationsWidth:

12” (1 foot) Minimum

Depth:24” (2 foot)

Exception: If 24” (2 foot) cannot be obtained, 18” (1.5 feet) deep is allowable if 4” of concrete is pouredabove top of conduit. The ditch cannot be less than 18” (1.5 feet)

DOC#: DOCS-0000001

Page 2: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 3: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

NOTES1. MEMBER PROVIDES AND INSTALLS: SERVICE ENTRANCE CONDUCTORS, CONDUITS, WEATHER-HEAD, SERVICE DISCONNECT SWITCH, GROUND

ROD IF NECESSARY, WIRE, AND ALL RELATED MATERIALS. ALL WORK SHALL COMPLY WITH COOPERATIVE STANDARDS, THE NATIONAL ELECTRICCODE, AND AUTHORITIES HAVING JURISDICTION.

2. COOPERATIVE PROVIDES AND INSTALLS METER AND SERVICE DROP CONDUCTORS, AND MAKES CONNECTIONS AT THE WEATHER-HEAD.3. THIS SERVICE SHALL BE INSTALLED ON THE BUILDING AT A LOCATION MUTUALLY AGREED UPON BY THE MEMBER AND THE COOPERATIVE.4. ALL CONDUITS SHALL BE ELECTRICAL GRADE PVC,EMC,IMC, OR RMC. ALL CONDUIT CONNECTIONS SHALL BE RAIN-TIGHT. WEATHER-HEAD

MATERIAL SHOULD BE OF THE SAME MATERIAL AS CONDUIT.5. A MINIMUM OF 2'-0" OF EACH CONDUCTOR SHALL EXTEND FROM THE WEATHER-HEAD. THE NEUTRAL SHALL BE MARKED WITH WHITE TAPE ON

BOTH ENDS. SEE TABLE BELOW.6. THE SERVICE ENTRANCE DISCONNECT MEANS SHALL BE INSTALLED AT A READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A BUILDING OR

STRUCTURE, OR INSIDE NEAREST THE POINT OF SERVICE CONDUCTOR ENTRANCE(NOT ALLOWED IN CLOSETS OR BATHROOMS). SERVICEENTRANCE DISCONNECTS SHALL BE EITHER FUSED OR BREAKER TYPE, RATED FOR SERVICE ENTRANCE.

7. ATTACHMENT POINT BY COOPERATIVE.8. A SERVICE MAST MAY BE REQUIRED TO MEET MINIMUM CLEARANCES.9. MINIMUM OF 3 FEET OF CLEARANCE BETWEEN ELECTRIC METER AND GAS METER.10. GROUND WIRE MUST BE ATTACHED TO WALL.11. ANY SERVICE GREATER THAN 320 AMPS, CONSULT THE COOPERATIVE.12. POINT OF ATTACHMENT SHALL BE EITHER ACCESSIBLE TO COOPERATIVE'S BUCKET TRUCK OR HAVE ENOUGH SURFACE (SUCH AS WALL OR

BUILDING STRUCTURE) AND SUFFICIENT GROUND SPACE ON SAME MEMBER'S PROPERTY TO SAFELY SUPPORT A LADDER.13. THE SERVICE ENTRANCE PANEL/DISCONNECT SHALL BE GROUNDED PER THE NATIONAL ELECTRIC CODE BEFORE COOPERATIVE WILL INSTALL

SERVICE AND METER. IF VISUALLY MEANS ARE AVAILABLE FOR THE COOPERATIVE TO IDENTIFY THE MEMBER'S GROUNDING METHOD WHICHCOMPLIES WITH NEC ARTICLE 250, A GROUND ROD MAY NOT BE NECESSARY. OTHERWISE A GROUNDING ROD WILL BE REQUIRED AND THEMEMBER OR MEMBER'S ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL 5/8" X 8' COPPER-CLAD GROUND ROD AND GROUND CLAMP.

5' MIN.-6' MAX.

3' MAX DISTANCE

TO DISCONNECT

SERVICE ENTRANCE MIN. CLEARANCES12'16'

ABOVE GROUNDABOVE RESIDENTIAL DRIVEWAYS

18' ABOVE PUBLIC DRIVEWAYS, ALLEYS, ROADS, AND OTHERAREAS SUBJECT TO TRUCK ANDCONSTRUCTION TRAFFIC

GROUND ROD IF NECESSARY

SHALL BE INSTALLED FLUSH

OR BELOW GRADE. SEE TABLE

BELOW.

POINT OF ATTACHEMENT - BY COOPERATIVE

RISER CONDUIT WITH STRAPS

SPACED EVERY 5'. SEE NOTE 4.

METER SOCKET.

RAIN TIGHT

HUB REQUIRED.

NOTICETHIS DRAWING ILLUSTRATES AVECC REQUIREMENTS

ONLY, AND IS NOT INTENDED TO BE ACOMPREHENSIVE GUIDE FOR THE INSTALLATION OF

AN ELECTRICAL SERVICE. TO INSURE A SAFE,QUALITY INSTALLATION THAT COMPLIES WITH THENATIONAL ELECTRICAL CODE, AND LOCAL CODE

REQUIREMENTS; THE COOPERATIVE RECOMMENDSTHAT ALL WORK BE DONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

MEMBER INSTALLATION MINIMUM WIRE AND CONDUIT SIZESERVICERATING

CONDUITSIZE

ALUMINUMPER NEC

COPPERPER NEC

NEUTRAL GROUNDWIRE SIZE

RESIDENTIAL ONLY

100A200A320A

1-1/2"2"3"

#24/0

500 kcmil

#42/0

350 kcmil

SAME AS PHASE #6 CU#4 CU#2 CU

SAME AS PHASESEE NEC

DISCONNECT

SWITCH

REQUIRED.

SEE NOTE 6.

REFER TO DRAWING SPEC-0000004

FOR METER BASE CONDUCTOR

CONNECTION DETAILS.

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

OVERHEAD METER ON HOUSEATTACHMENT TO WALL OR FASCIA

SINGLE PHASE 240V SERVICE UP TO 320ASPEC-0000001 05.08.17 NTS

JDC 0 N/A

Page 4: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 5: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

NOTES1. MEMBER PROVIDES AND INSTALLS: SERVICE ENTRANCE CONDUCTORS, CONDUITS, WEATHER-HEAD, SERVICE DISCONNECT SWITCH, GROUND

ROD IF NECESSARY, WIRE, AND ALL RELATED MATERIALS. ALL WORK SHALL COMPLY WITH COOPERATIVE STANDARDS, THE NATIONAL ELECTRICCODE, AND AUTHORITIES HAVING JURISDICTION.

2. COOPERATIVE PROVIDES AND INSTALLS METER AND SERVICE DROP CONDUCTORS, AND MAKES CONNECTIONS AT THE WEATHER-HEAD.3. THIS SERVICE SHALL BE INSTALLED ON THE BUILDING AT A LOCATION MUTUALLY AGREED UPON BY THE MEMBER AND THE COOPERATIVE.4. ALL CONDUITS SHALL BE ELECTRICAL GRADE PVC,EMC,IMC, OR RMC. ONLY RIGID METAL CONDUIT SHALL BE USED THROUGH THE ATTIC AND

ABOVE THE ROOF. ALL CONDUIT CONNECTIONS SHALL BE RAIN-TIGHT. WEATHER-HEAD MATERIAL SHOULD BE OF THE SAME MATERIAL ASCONDUIT.

5. A MINIMUM OF 2'-0" OF EACH CONDUCTOR SHALL EXTEND FROM THE WEATHER-HEAD. THE NEUTRAL SHALL BE MARKED WITH WHITE TAPE ONBOTH ENDS. SEE TABLE BELOW.

6. THE SERVICE ENTRANCE DISCONNECT MEANS SHALL BE INSTALLED AT A READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A BUILDING ORSTRUCTURE, OR INSIDE NEAREST THE POINT OF SERVICE CONDUCTOR ENTRANCE(NOT ALLOWED IN CLOSETS OR BATHROOMS). SERVICEENTRANCE DISCONNECTS SHALL BE EITHER FUSED OR BREAKER TYPE, SERVICE ENTRANCE RATED.

7. ATTACHMENT POINT BY COOPERATIVE.8. A SERVICE MAST MAY BE REQUIRED TO MEET MINIMUM CLEARANCES.9. MINIMUM OF 3 FEET OF CLEARANCE BETWEEN ELECTRIC METER AND GAS METER.10. GROUND WIRE MUST BE ATTACHED TO WALL.11. ANY SERVICE GREATER THAN 320 AMPS, CONSULT THE COOPERATIVE.12. POINT OF ATTACHMENT SHALL BE EITHER ACCESSIBLE TO COOPERATIVE'S BUCKET TRUCK OR HAVE ENOUGH SURFACE (SUCH AS WALL OR

BUILDING STRUCTURE) AND SUFFICIENT GROUND SPACE ON SAME MEMBER'S PROPERTY TO SAFELY SUPPORT A LADDER.13. THE SERVICE ENTRANCE PANEL/DISCONNECT SHALL BE GROUNDED PER THE NATIONAL ELECTRIC CODE BEFORE COOPERATIVE WILL INSTALL

SERVICE AND METER. IF VISUALLY MEANS ARE AVAILABLE FOR THE COOPERATIVE TO IDENTIFY THE MEMBER'S GROUNDING METHOD WHICHCOMPLIES WITH NEC ARTICLE 250, A GROUND ROD MAY NOT BE NECESSARY. OTHERWISE A GROUNDING ROD WILL BE REQUIRED AND THEMEMBER OR MEMBER'S ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL 5/8" X 8' COPPER-CLAD GROUND ROD AND GROUND CLAMP.

MEMBER INSTALLATION MINIMUM WIRE AND CONDUIT SIZESERVICERATING

CONDUITSIZE

ALUMINUMPER NEC

COPPERPER NEC

NEUTRAL GROUNDWIRE SIZE

RESIDENTIAL ONLY

100A200A320A

1-1/2"2"3"

#24/0

500 kcmil

#42/0

350 kcmil

SAME AS PHASE #6 CU#4 CU#2 CU

SAME AS PHASESEE NEC

GROUND ROD IF NECESSARY

SHALL BE INSTALLED FLUSH

OR BELOW GRADE. SEE TABLE

BELOW.

SERVICE ENTRANCE MIN. CLEARANCES12'16'

ABOVE GROUNDABOVE RESIDENTIAL DRIVEWAYS

18' ABOVE PUBLIC DRIVEWAYS, ALLEYS, ROADS, AND OTHERAREAS SUBJECT TO TRUCK ANDCONSTRUCTION TRAFFIC

CONDUIT COUPLING NOT

ALLOWED ABOVE THIS POINT

MAST LENGTH:

36" MIN.

40" MAX.

SERVICE DROP AND

CONNECTORS BY AVECC

NOTICETHIS DRAWING ILLUSTRATES AVECC REQUIREMENTS

ONLY, AND IS NOT INTENDED TO BE ACOMPREHENSIVE GUIDE FOR THE INSTALLATION OF

AN ELECTRICAL SERVICE. TO INSURE A SAFE,QUALITY INSTALLATION THAT COMPLIES WITH THENATIONAL ELECTRICAL CODE, AND LOCAL CODE

REQUIREMENTS; THE COOPERATIVE RECOMMENDSTHAT ALL WORK BE DONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

METER ENCLOSURE RAIN TIGHT

HUB REQUIRED

SERVICE ENTRANCE

DISCONNECT MEANS

SEE NOTE 6

3' MAX DISTANCE

FROM METER BASE TO

SERVICE ENTRANCE

DISCONNECT, 2" OR

LARGER NIPPLE

BETWEEN THE METER

BASE & SERVICE

ENTRANCE DISCONNECT

5' MIN.-6' MAX.

4'-0" MAX.

NOTE: REFER TO DRAWING

SPEC-0000004 FOR METER BASE

CONDUCTOR CONNECTION

DETAILS.

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

OVERHEAD METER ON HOUSESERVICE MAST ATTACHMENT

SINGLE PHASE 240V SERVICE UP TO 320ASPEC-0000002 06.06.17 NTS

JDC N/A

Page 6: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 7: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

MEMBER INSTALLATION MINIMUM WIRE AND CONDUIT SIZESERVICERATING

CONDUITSIZE

ALUMINUMPER NEC

COPPERPER NEC

NEUTRAL GROUNDWIRE SIZE

RESIDENTIAL ONLY

100A200A320A

3"3"3"

#24/0

500 kcmil

#42/0

350 kcmil

SAME AS PHASE #6 CU#4 CU#2 CU

SAME AS PHASESEE NEC

5' MIN.-6' MAX.

METER BASE (FURNISHED

BY AVECC & INSTALLED BY

MEMBER/ELECTRICIAN)

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECC REQUIREMENTS

ONLY, AND IS NOT INTENDED TO BE ACOMPREHENSIVE GUIDE FOR THE INSTALLATION OF

AN ELECTRICAL SERVICE. TO INSURE A SAFE,QUALITY INSTALLATION THAT COMPLIES WITH THENATIONAL ELECTRICAL CODE, AND LOCAL CODE

REQUIREMENTS; THE COOPERATIVE RECOMMENDSTHAT ALL WORK BE DONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

MALE ADAPTER &

LOCK RING

GROUND LINE

GROUND ROD IF NECESSARY

SHALL BE INSTALLED FLUSH

OR BELOW GRADE. SEE TABLE

BELOW.

SERVICE ENTRANCE

DISCONNECT MEANS

SEE NOTE 5

3' MAX DISTANCE

FROM METER BASE TO

SERVICE ENTRANCE

DISCONNECT, 2" OR

LARGER NIPPLE

BETWEEN THE METER

BASE & SERVICE

ENTRANCE DISCONNECT

ELECTRICAL PVC SCHEDULE 80 MATERIAL LISTFURNISHED AND INSTALLED BY MEMBER

1 - JOINT OF 3" PVC PIPE 10' LONG2 - SWEEP ELBOW3 - MALE ADAPTER & LOCK RING4 - COUPLING

2'-0" MIN.

2'-0" MAX

2'-0" MIN.*

NOTE(*): EXTEND CONDUIT A MINIMUM OF 2'-0"BEYOND ASPHALT/CEMENT DRIVEWAYS ANDSIDEWALKS.

LONG SWEEP ELBOW

SEE DETAIL 1&2

FOR OPTIONS

SWEEPING 90

DEGREE ELBOW

SWEEPING 45

DEGREE ELBOW

NOTE: THIS ASSEMBLY MAY BESUBSTITUTED TO CLEARFOOTING OF STRUCTURE.

NOTES1. MEMBER PROVIDES AND INSTALLS: SERVICE ENTRANCE CONDUCTORS, CONDUITS, SERVICE DISCONNECT SWITCH, GROUND ROD IF

NECESSARY, WIRE, AND ALL RELATED MATERIALS. ALL WORK SHALL COMPLY WITH COOPERATIVE STANDARDS, THE NATIONAL ELECTRICCODE, AND AUTHORITIES HAVING JURISDICTION.

2. COOPERATIVE PROVIDES AND INSTALLS METER AND CONNECTS COOPERATIVE SIDE OF METER BASE. SEE DRAWING SPEC-0000004.3. THIS SERVICE SHALL BE INSTALLED ON THE BUILDING AT A LOCATION MUTUALLY AGREED UPON BY THE MEMBER AND THE COOPERATIVE.4. ALL CONDUITS SHALL BE ELECTRICAL GRADE PVC,EMC,IMC, OR RMC.. ALL CONDUIT CONNECTIONS SHALL BE RAIN-TIGHT.5. THE SERVICE ENTRANCE DISCONNECT MEANS SHALL BE INSTALLED AT A READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A BUILDING

OR STRUCTURE, OR INSIDE NEAREST THE POINT OF SERVICE CONDUCTOR ENTRANCE(NOT ALLOWED IN CLOSETS OR BATHROOMS).SERVICE ENTRANCE DISCONNECTS SHALL BE EITHER FUSED OR BREAKER TYPE, SERVICE ENTRANCE RATED.

6. MINIMUM OF 3 FEET OF CLEARANCE BETWEEN ELECTRIC METER AND GAS METER.7. GROUND WIRE MUST BE ATTACHED TO WALL.8. ANY SERVICE GREATER THAN 320 AMPS, CONSULT THE COOPERATIVE.9. THE SERVICE ENTRANCE PANEL/DISCONNECT SHALL BE GROUNDED

PER THE NATIONAL ELECTRIC CODE BEFORE COOPERATIVE WILLINSTALL SERVICE AND METER. IF VISUALLY MEANS ARE AVAILABLEFOR THE COOPERATIVE TO IDENTIFY THE MEMBER'S GROUNDINGMETHOD WHICH COMPLIES WITH NEC ARTICLE 250, A GROUND RODMAY NOT BE NECESSARY. OTHERWISE A GROUNDING ROD WILL BEREQUIRED AND THE MEMBER OR MEMBER'S ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL 5 8" X 8' COPPER-CLAD GROUND ROD AND GROUND CLAMP.

10. DITCH MINIMUM IS 2'-0" DEEP BY 1'-0" WIDE.11. DOWN RISER ELBOW CONFIGURATION CAN NOT EXCEED 90 DEGREES.

DETAIL 2DETAIL 1

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

UNDERGROUND METER ON HOUSESINGLE PHASE 240V SERVICE UP TO 320A

RESIDENTIAL ONLYSPEC-0000003 06.06.17 NTS

JDC 0 N/A

Page 8: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 9: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

240 V

NEUTRAL

120V

120V

MEMBER'S LOAD

TOP LUGS ARE RESERVED

FOR AVECC CONDUCTOR

CONNECTION POINT,

MEMBERS'S CONDUCTORS

SHALL NOT BE LANDED ON

TOP LUGS

TOP LUGS ARE RESERVED

FOR AVECC CONDUCTOR

CONNECTION POINT,

MEMBERS'S CONDUCTORS

SHALL NOT BE LANDED ON

TOP LUGS

BOTTOM LUGS ARE RESERVED

FOR MEMBER'S CONDUCTOR

CONNECTIONS

BOTTOM LUGS ARE RESERVED

FOR MEMBER'S CONDUCTOR

CONNECTIONS.

LINE

NOTE: METER BASE IS FOR SERVICE WIRE ONLY,

NOT TO BE USED AS A FEED THROUGH BOX.

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

3 WIRE 120/240 VOLT SINGLE PHASE4 TERMINAL METER SOCKET CONDUCTOR

TERMINATION DETAIL UP TO 320ASPEC-0000004 06.06.17 NTS

JDC 0 N/A

Page 10: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 11: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

NEUTRAL

MEMBER'S LOAD

TOP LUGS ARE RESERVED

FOR AVECC CONDUCTOR

CONNECTION POINT,

MEMBERS'S CONDUCTORS

SHALL NOT BE LANDED ON

TOP LUGS

BOTTOM LUGS ARE RESERVED

FOR MEMBER'S CONDUCTOR

CONNECTIONS

208V

208V

208V

120V

120V

120V

LINE

NOTE: METER BASE IS FOR SERVICE WIRE ONLY,

NOT TO BE USED AS A FEED THROUGH BOX.

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

4 WIRE 120/208 VOLT THREE PHASE4 TERMINAL METER SOCKET CONDUCTOR

TERMINATION DETAIL UP TO 320ASPEC-0000005 06.06.17 NTS

JDC 0 N/A

Page 12: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 13: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECC REQUIREMENTS

ONLY, AND IS NOT INTENDED TO BE ACOMPREHENSIVE GUIDE FOR THE INSTALLATION OF

AN ELECTRICAL SERVICE. TO INSURE A SAFE,QUALITY INSTALLATION THAT COMPLIES WITH THENATIONAL ELECTRICAL CODE, AND LOCAL CODE

REQUIREMENTS; THE COOPERATIVE RECOMMENDSTHAT ALL WORK BE DONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

PRESSURE TREATED - PENTA POLE:1. ROUND ( 5" MINIMUM DIAMETER

AT TOP) OR SQUARE (5"X5"MINIMUM)

2. 16'-0" LENGTH MINIMUM, SET4'-0" IN GROUND

3-WIRES IN CONDUIT MUST BE:

#4 STRANDED COPPER OR

#2 STRANDED ALUMINUM

WITH THW COATING

TOP OF WEATHERHEAD MAST

MUST BE FLUSH WITH

TOP OF POLE

1-1/2" WEATHERHEAD

1-1/2" CONDUIT &

STRAPS

METER BASE FURNISHED

BY COOPERATIVE,

INSTALLED BY

MEMBER/ELECTRIAN

DISCONNECT:

BREAKER SIZE 100 AMPS

WITH RAINTIGHT BOX

ADDITIONAL SUPPORT MAY BE

REQUIRED, IT IS THE MEMBER'S

RESPONSIBILITY TO SECURE POLE

AS WELL AS THE ELECTRICAL

ENCLOSURES

1-1/2" X 4" CONDUIT NIPPLE

#6 BARE GROUND WIRE

5/8" X 8'-0" COPPER CLAD

GROUND ROD & GROUND CLAMP

SHALL BE INSTALLED FLUSH OR

JUST BELOW GRADE.

4'-0" MINIMUM

5'-0" MINIMUM

6'-0" MAXIMUM

NOTES1. MEMBER PROVIDES AND INSTALLS: SERVICE ENTRANCE CONDUCTORS, CONDUITS,

WEATHER-HEAD, SERVICE DISCONNECT SWITCH, GROUND ROD, WIRE, AND ALL RELATEDMATERIALS. ALL WORK SHALL COMPLY WITH COOPERATIVE STANDARDS, THE NATIONALELECTRIC CODE, AND AUTHORITIES HAVING JURISDICTION.

2. COOPERATIVE PROVIDES AND INSTALLS METER AND SERVICE DROP CONDUCTORS, ANDMAKES CONNECTIONS AT THE WEATHER-HEAD.

3. THIS SERVICE SHALL BE INSTALLED AT A LOCATION MUTUALLY AGREED UPON BY THEMEMBER AND THE COOPERATIVE.

4. ALL CONDUITS SHALL BE ELECTRICAL GRADE PVC,EMC,IMC, OR RMC. ALL CONDUITCONNECTIONS SHALL BE RAIN-TIGHT. WEATHER-HEAD MATERIAL SHOULD BE OF THESAME MATERIAL AS CONDUIT.

5. A MINIMUM OF 2'-0" OF EACH CONDUCTOR SHALL EXTEND FROM THE WEATHER-HEAD.THE NEUTRAL SHALL BE MARKED WITH WHITE TAPE ON BOTH ENDS. SEE TABLE BELOW.

6. MINIMUM OF 3 FEET OF CLEARANCE BETWEEN ELECTRIC METER AND GAS METER.7. POINT OF ATTACHMENT SHALL BE ACCESSIBLE TO COOPERATIVE'S BUCKET TRUCK.8. THE SERVICE ENTRANCE PANEL/DISCONNECT SHALL BE GROUNDED PER THE NATIONAL

ELECTRIC CODE BEFORE COOPERATIVE WILL INSTALL SERVICE AND METER.9. SERVICE ENTRANCE DISCONNECTS SHALL BE EITHER FUSED OR BREAKER TYPE, RATED

FOR SERVICE ENTRANCE.10. POWER SUPPLY FROM THE MAIN DISCONNECT SHALL MEET THE REQUIREMENTS OF

SECTION 550 OF THE NATIONAL ELECTRIC CODE(NEC)11. OVERHEAD LINE CAN NOT CROSS RESIDENTIAL DRIVEWAYS, PUBLIC DRIVEWAYS,

ALLEYS, ROADS, OR OTHER AREAS SUBJECT TO TRUCK & CONSTRUCTION TRAFFIC.

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

100 AMPERE METER POLEINSTALLATION

SPEC-0000006 06.06.17 NTSJDC 0 N/A

Page 14: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 15: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECC REQUIREMENTS

ONLY, AND IS NOT INTENDED TO BE ACOMPREHENSIVE GUIDE FOR THE INSTALLATION OF

AN ELECTRICAL SERVICE. TO INSURE A SAFE,QUALITY INSTALLATION THAT COMPLIES WITH THENATIONAL ELECTRICAL CODE, AND LOCAL CODE

REQUIREMENTS; THE COOPERATIVE RECOMMENDSTHAT ALL WORK BE DONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

PRESSURE TREATED - PENTA POLE:1. ROUND ( 5" MINIMUM DIAMETER

AT TOP) OR SQUARE (5"X5"MINIMUM)

2. 16'-0" LENGTH MINIMUM, SET4'-0" IN GROUND

3-WIRES IN CONDUIT MUST BE:

#2/0 STRANDED COPPER OR

#4/0 STRANDED ALUMINUM

WITH THW COATING

TOP OF WEATHERHEAD MAST

MUST BE FLUSH WITH

TOP OF POLE

2" WEATHERHEAD

2" CONDUIT &

STRAPS

METER BASE FURNISHED

BY COOPERATIVE,

INSTALLED BY

MEMBER/ELECTRIAN

DISCONNECT:

BREAKER SIZE 200 AMPS

WITH RAINTIGHT BOX

ADDITIONAL SUPPORT MAY BE

REQUIRED, IT IS THE MEMBER'S

RESPONSIBILITY TO SECURE POLE

AS WELL AS THE ELECTRICAL

ENCLOSURES

2" X 4" CONDUIT NIPPLE

#4 BARE GROUND WIRE

5/8" X 8'-0" COPPER CLAD

GROUND ROD & GROUND CLAMP

SHALL BE INSTALLED FLUSH OR

JUST BELOW GRADE.

4'-0" MINIMUM

5'-0" MINIMUM

6'-0" MAXIMUM

NOTES1. MEMBER PROVIDES AND INSTALLS: SERVICE ENTRANCE CONDUCTORS, CONDUITS,

WEATHER-HEAD, SERVICE DISCONNECT SWITCH, GROUND ROD, WIRE, AND ALL RELATEDMATERIALS. ALL WORK SHALL COMPLY WITH COOPERATIVE STANDARDS, THE NATIONALELECTRIC CODE, AND AUTHORITIES HAVING JURISDICTION.

2. COOPERATIVE PROVIDES AND INSTALLS METER AND SERVICE DROP CONDUCTORS, ANDMAKES CONNECTIONS AT THE WEATHER-HEAD.

3. THIS SERVICE SHALL BE INSTALLED AT A LOCATION MUTUALLY AGREED UPON BY THEMEMBER AND THE COOPERATIVE.

4. ALL CONDUITS SHALL BE ELECTRICAL GRADE PVC,EMC,IMC, OR RMC. ALL CONDUITCONNECTIONS SHALL BE RAIN-TIGHT. WEATHER-HEAD MATERIAL SHOULD BE OF THESAME MATERIAL AS CONDUIT.

5. A MINIMUM OF 2'-0" OF EACH CONDUCTOR SHALL EXTEND FROM THE WEATHER-HEAD. THENEUTRAL SHALL BE MARKED WITH WHITE TAPE ON BOTH ENDS. SEE TABLE BELOW.

6. MINIMUM OF 3 FEET OF CLEARANCE BETWEEN ELECTRIC METER AND GAS METER.7. POINT OF ATTACHMENT SHALL BE ACCESSIBLE TO COOPERATIVE'S BUCKET TRUCK.8. THE SERVICE ENTRANCE PANEL/DISCONNECT SHALL BE GROUNDED PER THE NATIONAL

ELECTRIC CODE BEFORE COOPERATIVE WILL INSTALL SERVICE AND METER.9. SERVICE ENTRANCE DISCONNECTS SHALL BE EITHER FUSED OR BREAKER TYPE, RATED

FOR SERVICE ENTRANCE.10. POWER SUPPLY FROM THE MAIN DISCONNECT SHALL MEET THE REQUIREMENTS OF

SECTION 550 OF THE NATIONAL ELECTRIC CODE(NEC).11. OVERHEAD LINE CAN NOT CROSS RESIDENTIAL DRIVEWAYS, PUBLIC DRIVEWAYS, ALLEYS,

ROADS, OR OTHER AREAS SUBJECT TO TRUCK & CONSTRUCTION TRAFFIC.TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

200 AMPERE METER POLEINSTALLATION

SPEC-0000007 06.06.17 NTSJDC 0 N/A

Page 16: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 17: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

MEMBER INSTALLATION MINIMUM WIRE AND CONDUIT SIZESERVICERATING

CONDUITSIZE

ALUMINUMPER NEC

COPPERPER NEC

NEUTRAL GROUNDWIRE SIZE

100A200A

1-1/2"2"

#24/0

#42/0

SAME AS PHASE #6 CU#4 CUSAME AS PHASE

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECC REQUIREMENTS

ONLY, AND IS NOT INTENDED TO BE ACOMPREHENSIVE GUIDE FOR THE INSTALLATION OF

AN ELECTRICAL SERVICE. TO INSURE A SAFE,QUALITY INSTALLATION THAT COMPLIES WITH THENATIONAL ELECTRICAL CODE, AND LOCAL CODE

REQUIREMENTS; THE COOPERATIVE RECOMMENDSTHAT ALL WORK BE DONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

PRESSURE TREATED - PENTA POLE:1. ROUND ( 5" MINIMUM DIAMETER

AT TOP) OR SQUARE (5"X5"MINIMUM)

2. 16'-0" LENGTH MINIMUM, SET4'-0" IN GROUND

TOP OF WEATHERHEAD MAST

MUST BE FLUSH WITH

TOP OF POLE

WEATHERHEAD, REFER TO

TABLE THIS SHEET FOR SIZE

CONDUIT & STRAPS, REFER

TO TABLE THIS SHEET FOR

CONDUIT & STRAP SIZE

METER BASE FURNISHED

BY COOPERATIVE,

INSTALLED BY

MEMBER/ELECTRIAN

DISCONNECT: BREAKER

TYPE WITH RAINTIGHT BOX.

BREAKER SIZE DEPENDANT

UPON MEMBER, REFER TO

TABLE THIS SHEET FOR

OPTIONS

ADDITIONAL SUPPORT MAY BE REQUIRED, IT IS THE

MEMBER'S RESPONSIBILITY TO SECURE POLE

AS WELL AS THE ELECTRICAL ENCLOSURES

4" LENGTH CONDUIT NIPPLE, REFER TO TABLE THIS

SHEET FOR CONDUIT DIAMETER

BARE GROUND WIRE, REFER TO TABLE THIS

SHEET FOR SIZE

5/8" X 8'-0" COPPER CLAD

GROUND ROD & GROUND CLAMP

SHALL BE INSTALLED FLUSH OR

JUST BELOW GRADE.

4'-0" MINIMUM

5'-0" MINIMUM

6'-0" MAXIMUM

NOTES1. MEMBER PROVIDES AND INSTALLS: SERVICE ENTRANCE CONDUCTORS, CONDUITS,

WEATHER-HEAD, SERVICE DISCONNECT SWITCH, GROUND ROD, WIRE, AND ALL RELATEDMATERIALS. ALL WORK SHALL COMPLY WITH COOPERATIVE STANDARDS, THE NATIONALELECTRIC CODE, AND AUTHORITIES HAVING JURISDICTION.

2. COOPERATIVE PROVIDES AND INSTALLS METER AND SERVICE DROP CONDUCTORS, ANDMAKES CONNECTIONS AT THE WEATHER-HEAD.

3. THIS SERVICE SHALL BE INSTALLED AT A LOCATION MUTUALLY AGREED UPON BY THEMEMBER AND THE COOPERATIVE.

4. ALL CONDUITS SHALL BE ELECTRICAL GRADE PVC,EMC,IMC, OR RMC. ALL CONDUITCONNECTIONS SHALL BE RAIN-TIGHT. WEATHER-HEAD MATERIAL SHOULD BE OF THESAME MATERIAL AS CONDUIT.

5. A MINIMUM OF 2'-0" OF EACH CONDUCTOR SHALL EXTEND FROM THE WEATHER-HEAD.THE NEUTRAL SHALL BE MARKED WITH WHITE TAPE ON BOTH ENDS. SEE TABLE BELOW.

6. MINIMUM OF 3 FEET OF CLEARANCE BETWEEN ELECTRIC METER AND GAS METER.7. POINT OF ATTACHMENT SHALL BE ACCESSIBLE TO COOPERATIVE'S BUCKET TRUCK.8. THE SERVICE ENTRANCE PANEL/DISCONNECT SHALL BE GROUNDED PER THE NATIONAL

ELECTRIC CODE BEFORE COOPERATIVE WILL INSTALL SERVICE AND METER.9. SERVICE ENTRANCE DISCONNECTS SHALL BE EITHER FUSED OR BREAKER TYPE, RATED

FOR SERVICE ENTRANCE.10. POWER SUPPLY FROM THE MAIN DISCONNECT SHALL MEET THE REQUIREMENTS OF

SECTION 550 OF THE NATIONAL ELECTRIC CODE(NEC).11. OVERHEAD LINE CAN NOT CROSS RESIDENTIAL DRIVEWAYS, PUBLIC DRIVEWAYS,

ALLEYS, ROADS, OR OTHER AREAS SUBJECT TO TRUCK & CONSTRUCTION TRAFFIC.

60A 1" #8 #6 SAME AS PHASE #6 CU

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

SMALL LOAD OR TEMPORARYMETER POLE INSTALLATION

SPEC-0000008 06.06.17 NTSJDC 0 N/A

Page 18: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 19: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

5/8" X 8'-0" COPPER CLAD

GROUND ROD & GROUND CLAMP

SHALL BE INSTALLED FLUSH OR

JUST BELOW GRADE.

2'-0"

FRONT OFTRANSFORMER

PRIMARY SECONDARY

2'-0" MAX.

1'-0" MIN.

#6 BARE GROUND WIRE

LEAVE 5' TAIL

#4 COPPER OR

#2 ALUMINUM

COATED

AVECC WILL TERMINATE

IN TRANSFORMER

1-1/2" SCHEDULE 80 PVC

OUT TO DISCONNECT,

SEE DETAIL A THIS SHEET

ADDITIONAL SUPPORT MAY BE

REQUIRED, IT IS THE MEMBER'S

RESPONSIBILITY TO SECURE POLE

AS WELL AS THE ELECTRICAL

ENCLOSURES

ROUND OR SQUARE TREATED POLE

7'-0" LONG, 2'-0" IN THE GROUND

MOUNT TOP OF METER

BASE WITHIN 6" TO TOP

OF POLE

4" SQUARE

OR 4" ROUND

MINIMUM

100 AMP SERVICE RATED

DISCONNECT, RAIN

TIGHT ENCLOSURE

GFCI PROTECTED

RECEPTACLES OR

BREAKER(S) REQUIRED

METER

BASE

REQUIRES

NEUTRAL

BOND

TO METER

BASE

CLOSE

NIPPLE

DETAIL A

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECC REQUIREMENTS

ONLY, AND IS NOT INTENDED TO BE ACOMPREHENSIVE GUIDE FOR THE INSTALLATION OF

AN ELECTRICAL SERVICE. TO INSURE A SAFE,QUALITY INSTALLATION THAT COMPLIES WITH THENATIONAL ELECTRICAL CODE, AND LOCAL CODE

REQUIREMENTS; THE COOPERATIVE RECOMMENDSTHAT ALL WORK BE DONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

NOTES1. MEMBER PROVIDES AND INSTALLS: CONDUIT, SUPPORT BEAM, DISCONNECT SWITCH,

GROUND ROD AND WIRE, AND ALL RELATED MATERIALS. METER BASE IS SUPPLIED BYAVECC AND INSTALLED BY THE MEMBER/ELECTRICIAN. ALL WORK SHALL COMPLY WITHCOOPERATIVE STANDARDS, THE CURRENT VERSION OF THE NATIONAL ELECTRIC CODE,AND AUTHORITIES HAVING JURISDICTION.

2. COOPERATIVE PROVIDES AND INSTALLS METER , TRANSFORMER, PRIMARYCONDUCTORS TO THE TRANSFORMER, AND TERMINATES BOTH PRIMARY ANDSECONDARY CONDUCTORS WITHIN THE TRANSFORMER.

3. THIS SERVICE SHALL BE INSTALLED AT A LOCATION MUTUALLY AGREED UPON BY THEMEMBER AND THE COOPERATIVE.

4. ALL CONDUITS SHALL BE ELECTRICAL GRADE PVC,EMC,IMC, OR RMC. ALL CONDUITCONNECTIONS SHALL BE RAIN-TIGHT.

5. MINIMUM OF 3 FEET OF CLEARANCE BETWEEN ELECTRIC METER AND GAS METER.6. THE SERVICE ENTRANCE PANEL/DISCONNECT SHALL BE GROUNDED PER THE NATIONAL

ELECTRIC CODE BEFORE COOPERATIVE WILL INSTALL SERVICE AND METER.7. SERVICE ENTRANCE DISCONNECTS SHALL BE EITHER FUSED OR BREAKER TYPE, RATED

FOR SERVICE ENTRANCE.8. POWER SUPPLY FROM THE MAIN DISCONNECT SHALL MEET THE REQUIREMENTS OF

SECTION 550 OF THE NATIONAL ELECTRIC CODE(NEC).

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

UNDERGROUND TEMPORARYPOLE INSTALLATION

SPEC-0000009 06.06.17 NTSJDC 0 N/A

Page 20: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 21: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

4'-0" MIN.

6'-0" MAX.

18" MIN.

SEE NEC 300.50

36" MIN.

24" MIN. TO TOP OF CONDUIT

12" MIN. DITCH WIDTH

MEMBER INSTALLED GROUND WIRE

STAPLED TO POST, 5/8" X8'-0" COPPER-

CLAD GROUND ROD INSTALLED FLUSH

OR SLIGHTLY BELOW GRADE, AND CLAMP

REQUIRED. SEE TABLE BELOW

DISCONNECT SWITCH REQUIRED. SEE

NEC 550.32 FOR MOBILE HOMES SERVICE.

PEDESTAL MINIMUM 6" X 6" TREATED

WOOD POST OR EQUIVALENT REQUIRED.

METER BASE PROVIDED BY

AVECC, INSTALLED

BY MEMBER/ELECTRICIAN

MOUNT TOP OF METER

BASE WITHIN 6" TO TOP

OF POLE

NOTE: ALL MATERIALS, EQUIPMENT,AND CONDUIT CONNECTIONS SHALL BERAINTIGHT. ANY RECEPTACLES MUSTBE WEATHERPROOF AND GFCIPROTECTED.

TO MEMBER'S LOAD

NOTE: MEMBER'S CONDUCTORSSHALL BE IN CONDUIT FROM THEDISCONNECT BOX TO 24" BELOWGRADE.

SWEEPING ELBOW,

SCHEDULE 80 PVC

TO COOPERATIVE'SSOURCE

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998

IT SHALL BE A MEMBER'SRESPONSIBILITY TO STAY CLEAR

OF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECC REQUIREMENTS

ONLY, AND IS NOT INTENDED TO BE ACOMPREHENSIVE GUIDE FOR THE INSTALLATION OF

AN ELECTRICAL SERVICE. TO INSURE A SAFE,QUALITY INSTALLATION THAT COMPLIES WITH THENATIONAL ELECTRICAL CODE, AND LOCAL CODE

REQUIREMENTS; THE COOPERATIVE RECOMMENDSTHAT ALL WORK BE DONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

NOTES1. MEMBER PROVIDES AND INSTALLS: CONDUIT, PEDESTAL, DISCONNECT SWITCH, GROUND ROD AND WIRE, AND ALL RELATED MATERIALS.

METER BASE IS SUPPLIED BY AVECC AND INSTALLED BY THE MEMBER/ELECTRICIAN. ALL WORK SHALL COMPLY WITH COOPERATIVESTANDARDS, THE CURRENT VERSION OF THE NATIONAL ELECTRIC CODE, AND AUTHORITIES HAVING JURISDICTION.

2. COOPERATIVE PROVIDES AND INSTALLS METER AND SERVICE LATERAL CONDUCTORS FROM AVECC TRANSFORMER OR SECONDARYPEDESTAL TO THE METER SOCKET.

3. THIS SERVICE SHALL BE INSTALLED AT A LOCATION MUTUALLY AGREED UPON BY THE MEMBER AND THE COOPERATIVE.4. MEMBER SHALL INSTALL SCHEDULE 80 PVC RISER AND SWEEPING ELBOW, OPEN, AND CLOSE DITCH. DITCH MINIMUM IS 24" DEEP BY 12"

WIDE.5. ABOVE GROUND CONDUITS SHALL BE ELECTRICAL GRADE EMT, IMC, RMC, OR SCHEDULE 80 PVC. METER RISER SHALL BE SCHEDULE 80

PVC.6. UNDERGROUND CONDUIT SHALL BE ELECTRICAL GRADE SCHEDULE 40 OR SCHEDULE 80 PVC. ALL ELBOWS SHALL BE SCHEDULE 80 PVC.

SEE TABLE BELOW FOR CONDUIT SIZE.7. CONSULT THE COOPERATIVE FOR SERVICE RATED OVER 320AMPS. 240 VOLT MAX SYSTEM VOLTAGE WITH THIS SERVICE TYPE.

MEMBER INSTALLATION MINIMUM WIRE AND CONDUIT SIZESERVICERATING

CONDUIT SIZE ALUMINUMPER NEC

COPPERPER NEC

NEUTRAL GROUNDWIRE SIZE

100A200A320A

3"3"

SEE NEC

#24/0

#42/0

SAME AS PHASE #6 CU#4 CU#2 CU

SAME AS PHASESEE NEC

1 PHASE 3 PHASE3"3"

SEE NEC SEE NEC SEE NEC

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

METER PEDESTALSINGLE OR THREE PHASE SERVICE UP TO 320A

SPEC-0000010 06.06.17 NTSJDC 0 N/A

Page 22: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 23: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

EQUIPMENT MOUNTING RACK,

SEE NOTE 8.

CONTROL EQUIPMENT - IF THIS EQUIPMENT

INCLUDES A SERVICE DISCONNECT,

A SEPARATE SERVICE DISCONNECT IS

NOT REQUIRED.

MEMBER INSTALLED

GROUND WIRE

STAPLED TO POST,

5/8" X8'-0" COPPER-

CLAD GROUND ROD

INSTALLED FLUSH

OR SLIGHTLY BELOW

GRADE, AND CLAMP

REQUIRED. SEE

TABLE BELOW

5'-0" MIN.

6'-0" MAX.

SERVICE

DISCONNECT

REQUIRED. SERVICE

ENTRANCE RATED

SEE NOTE 9

6" SPACE BETWEEN BOXES

REQUIRED. SEE NOTE 9.

36" MIN.

24" MIN.

SCHEDULE 80 PVC RISER ELBOW AND

CONDUIT REQUIRED. SEE NOTE 7.

TO AVECCSOURCE

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECC

REQUIREMENTS ONLY, AND IS NOT INTENDEDTO BE A COMPREHENSIVE GUIDE FOR THE

INSTALLATION OF AN ELECTRICAL SERVICE. TOINSURE A SAFE, QUALITY INSTALLATION THATCOMPLIES WITH THE NATIONAL ELECTRICAL

CODE, AND LOCAL CODE REQUIREMENTS; THECOOPERATIVE RECOMMENDS THAT ALL WORK

BE DONE BY A QUALIFIED, LICENSEDELECTRICAL CONTRACTOR.

NOTE: ALL MATERIALS, EQUIPMENT, AND CONDUITCONNECTIONS SHALL BE RAINTIGHT. ANY RECEPTACLESMUST BE WEATHERPROOF AND GFCI PROTECTED.

NOTES1. MEMBER PROVIDES AND INSTALLS THE MOUNTING RACK, RISER CONDUIT, METER SOCKET, SERVICE DISCONNECT SWITCH, GROUND ROD AND

WIRE, AND ALL RELATED MATERIALS. ALL WORK SHALL COMPLY WITH COOPERATIVE STANDARDS, THE LATEST EDITION OF THE NATIONALELECTRIC CODE, AND ANY AUTHORITIES HAVING JURISDICTION.

2. COOPERATIVE PROVIDES AND INSTALLS THE METER AND THE SERVICE LATERAL CONDUCTORS FROM THE COOPERATIVE'S SOURCE TO THEMETER.

3. THIS SERVICE SHALL BE INSTALLED AT A LOCATION MUTUALLY AGREED UPON BY THE MEMBER AND THE COOPERATIVE. THE LOCATION SHOULDBE IMMEDIATELY ADJACENT TO A ROADWAY OR DRIVE WHICH IS EASILY ACCESSIBLE AT ALL TIMES BY COOPERATIVE VEHICLES WITHOUTHAVING TO CROSS YARDS, FIELDS, DITCHES, OR AREAS SUBJECT TO FLOOD OR IRRIGATION.

4. MEMBER PROVIDES TRENCH AND ANY REQUIRED CONDUIT FROM THE SERVICE TO THE COOPERATIVE'S SOURCE.5. ALL ABOVE GROUND CONDUITS SHALL BE ELECTRICAL GRADE SCHEDULE 40 PVC, EMT, IMC, OR RMC. ALL CONDUITS SHALL BE RAINTIGHT.6. ALL MATERIAL AND WORKMANSHIP SHALL COMPLY WITH LATEST EDITION OF THE NATIONAL ELECTRIC CODE.7. MEMBER PROVIDES A 24" DEEP BY 12" WIDE TRENCH AND SCHEDULE 80 PVC 36" SWEEP ELBOW WITH END-BELL AND SCHEDULE 80 PVC RISER

CONDUIT TO THE METER. IF SERVICE IS REQUIRED TO BE INSTALLED IN CONDUIT TO THE COOPERATIVE'S SOURCE, SEE TABLE BELOW FORCONDUIT SIZE.

8. MOUNTING RACK VERTICAL POSTS MUST BE A MINIMUM OF 3" SCHEDULE 40 RIGID WEATHERPROOF PIPE, 6" ROUND TREATED POSTS, OR 4"X4"TREATED POSTS. POSTS MUST BE SET 36" DEEP. STEEL POSTS SHOULD BE SET IN CONCRETE. POSTS MUST BE SPACED TO PROVIDE STABLEMOUNTING FOR THE EQUIPMENT. MOUNTING RACK CROSS-MEMBERS MUST BE WEATHERPROOF STEEL OR TREATED WOOD OF SUFFICIENTNUMBER, SIZE, STRENGTH, AND SPACING TO PROVIDE STABLE MOUNTING OF THEELECTRICAL ENCLOSURES. ALTERNATE RACK MATERIAL MAY BE ACCEPTABLEWITH PRIOR APPROVAL FROM AVECC.

9. MAINTAIN 3'-0" WORKING CLEARANCE AROUND METER RACK.10. MEMBER SHALL PROVIDE PROTECTIVE METAL PIPE BARRIER IF METER

RACK IS SUBJECT TO VEHICULAR TRAFFIC.11. SERVICE DISCONNECT SWITCH BOXES MUST NOT BE USED AS A FEED

THROUGH BOX. EACH DISCONNECT MUST HAVE A SEPARATE CONDUITTO METER.

MEMBER

CONDUCTOR'S

SHALL BE IN

CONDUIT

FROM THE BOX TO

24" BELOW GRADE

MEMBER INSTALLATION MINIMUM WIRE AND CONDUIT SIZESERVICERATING

CONDUITSIZE

ALUMINUMPER NEC

COPPERPER NEC

NEUTRAL GROUNDWIRE SIZE

RESIDENTIAL ONLY

100A200A320A

3"3"3"

#24/0

500 kcmil

#42/0

350 kcmil

SAME AS PHASE #6 CU#4 CU#2 CU

SAME AS PHASESEE NEC

NOTE: (2) DISCONNECTS MAY BE SERVED FROM ONE METER SO LONG AS

COMBINED DISCONNECT AMPERE RATING DOES NOT EXCEED THE RATING

OF THE METER. COORDINATE WITH AVECC PRIOR TO RACK CONSTRUCTION.

RACK LENGTH MUST ACCOMMODATE THE METER, DISCONNECTS, AND

CONTROL CABINET IF MOUNTED ON RACK.

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

UNDERGROUND METER ANDEQUIPMENT RACKUP TO 320 AMPS

SPEC-0000011 06.06.17 NTSJDC 0 N/A

Page 24: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 25: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

EQUIPMENT MOUNTING RACK,

SEE NOTE 8.

CONTROL EQUIPMENT - IF THIS EQUIPMENT

INCLUDES A SERVICE DISCONNECT,

A SEPARATE SERVICE DISCONNECT IS

NOT REQUIRED.

MEMBER INSTALLED GROUND WIRE

STAPLED TO POST, 5/8" X8'-0" COPPER-

CLAD GROUND ROD INSTALLED FLUSH

OR SLIGHTLY BELOW GRADE, AND CLAMP

REQUIRED. SEE TABLE DRAWING SPEC-000014.

5'-0" MIN.

6'-0" MAX.

6" SPACE BETWEEN

BOXES REQUIRED.

36" MIN.

24" MIN.

TO AVECCPOLE, 40'-0" MAX.

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECCREQUIREMENTS ONLY, AND IS NOT

INTENDED TO BE A COMPREHENSIVEGUIDE FOR THE INSTALLATION OF ANELECTRICAL SERVICE. TO INSURE ASAFE, QUALITY INSTALLATION THAT

COMPLIES WITH THE NATIONALELECTRICAL CODE, AND LOCAL CODEREQUIREMENTS; THE COOPERATIVERECOMMENDS THAT ALL WORK BEDONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

NOTE: ALL MATERIALS, EQUIPMENT, AND CONDUITCONNECTIONS SHALL BE RAINTIGHT. ANY RECEPTACLESMUST BE WEATHERPROOF AND GFCI PROTECTED.

MEMBER

CONDUCTOR'S

SHALL BE IN

CONDUIT

FROM THE BOX TO

24" BELOW GRADE

48" MIN.

SERVICE DROP AND

CONNECTORS BY AVECC

POLE AND SERVICE DROP ATTACHMENT

INSTALLED BY MEMBER/ELECTRICIAN

SEE NOTES 7 & 8

SEE

NOTE 9

SERVICE

DISCONNECT

REQUIRED.

SERVICE

ENTRANCE RATED

SERVICE ENTRANCE

CONDUCTORS SEE

NOTE 6

CTCABINET

METERBASE

RISER

CONDUIT &

STRAPS

SPACED

EVERY

5'-0". SEE

NOTE 5

12' M

IN. T

O DR

IP LO

OP. 1

6' RE

QUIR

ED IN

AREA

S SU

BJEC

T TO

TRU

CK T

RAFF

IC

13' 6

" MIN

. ATT

ACHM

ENT

HEIG

HT. 1

7' 6"

REQ

UIRE

DIN

ARE

AS S

UBJE

CT T

O TR

UCK

TRAF

FIC

14' M

IN. W

EATH

ERHE

AD H

EIGH

T. 18

' REQ

UIRE

DIN

ARE

AS S

UBJE

CT T

O TR

UCK

TRAF

FIC

NOTES1. MEMBER PROVIDES AND INSTALLS THE POLE, MOUNTING RACK, SERVICE ENTRANCE CONDUCTORS, CONDUITS, WEATHERHEAD, SERVICE

DISCONNECT SWITCH, GROUND ROD AND WIRE, AND ALL RELATED MATERIALS. ALL WORK SHALL COMPLY WITH COOPERATIVE STANDARDS, THELATEST EDITION OF THE NATIONAL ELECTRIC CODE, AND ANY AUTHORITIES HAVING JURISDICTION. MEMBER/ELECTRICAIN INSTALLS CT CABINETAND METER BASE PROVIDED BY AVECC.

2. COOPERATIVE PROVIDES AND INSTALLS THE METER , THE SERVICE DROP CONDUCTORS, AND TERMINATES AT THE WEATHERHEAD.3. THIS SERVICE SHALL BE INSTALLED AT A LOCATION MUTUALLY AGREED UPON BY THE MEMBER AND THE COOPERATIVE. THE LOCATION SHOULD

BE IMMEDIATELY ADJACENT TO A ROADWAY OR DRIVE WHICH IS EASILY ACCESSIBLE AT ALL TIMES BY COOPERATIVE VEHICLES WITHOUT HAVINGTO CROSS YARDS, FIELDS, DITCHES, OR AREAS SUBJECT TO FLOOD OR IRRIGATION.

4. ALL CONDUITS SHALL BE ELECTRICAL GRADE SCHEDULE 40 MINIMUM PVC, EMT, IMC, OR RIGID. ALL CONDUIT CONNECTIONS SHALL BE RAINTIGHT.5. RISER CONDUIT SHALL BE AT LEAST 8' IN LENGTH WITH 2 CONDUIT STRAPS REQUIRED. STRAPS MUST BE PLACED WITHIN 12" OF THE TOP AND AT

THE MIDPOINT OF THE CONDUIT.6. A MINIMUM OF 24" OF CONDUCTOR SHALL EXTEND FROM WEATHERHEAD. NEUTRAL CONDUCTOR SHALL BE MARKED WITH WHITE TAPE AT BOTH

ENDS.7. MEMBER INSTALLED 1/2" GALVANIZED STEEL EYE BOLT WITH 2" X 2" SQUARE WASHER REQUIRED.8. POLE FOR SERVICE DROP ATTACHMENT MUST BE MINIMUM 6" TREATED WOOD OR 6" SCHEDULE 40 WEATHERPROOF STEEL SET IN CONCRETE.

POLE LENGTH SHALL BE MINIMUM 18' OR 22' DEPENDING ON WEATHERHEAD HEIGHT. VERTICAL POST MUST BE MINIMUM 4" ROUND OR 4" X 4"TREATED POSTS, OR 2" SCHEDULE 40 WEATHERPROOF STEEL SET IN CONCRETE. POSTS MUST BE SPACED TO PROVIDE STABLE MOUNTING FOREQUIPMENT. RACK CROSS-MEMBERS MUST BE WEATHERPROOF STEEL OR TREATED WOOD OF SUFFICIENT NUMBER, SIZE, STRENGTH, ANDSPACING TO PROVIDE STABLE MOUNTING OF THE ELECTRICAL ENCLOSURES.

9. MEMBER INSTALLS METER BASE ON DOOR OF CT CABINET WITH 1" NIPPLE THROUGH THE DOOR. REFER TO DRAWING SPEC-0000014 FOR DETAIL.LEAVE 3 FOOT TAIL ON SERVICE WIRES. WIRES SHALL BE COLOR CODED PER NEC STANDARDS.

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

OVERHEAD CT METER ANDEQUIPMENT RACK ( IRRIGATION SERVICE)

3 PHASE SERVICE & 480V SINGLE PHASESPEC-0000012 06.08.17 NTS

JDC 0 N/A

Page 26: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 27: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECC

REQUIREMENTS ONLY, AND IS NOT INTENDEDTO BE A COMPREHENSIVE GUIDE FOR THE

INSTALLATION OF AN ELECTRICAL SERVICE. TOINSURE A SAFE, QUALITY INSTALLATION THATCOMPLIES WITH THE NATIONAL ELECTRICAL

CODE, AND LOCAL CODE REQUIREMENTS; THECOOPERATIVE RECOMMENDS THAT ALL WORK

BE DONE BY A QUALIFIED, LICENSEDELECTRICAL CONTRACTOR.

6" MAX.

36" MIN.

SCHEDULE 40 PVC, 1"

CONDUIT TO AVECC

TRANSFORMER. 20'0" MAX.

PULL STRING

5'-0" MIN.

6'-0" MAX.

NOTE: ALL MATERIALS, EQUIPMENT, ANDCONDUIT CONNECTIONS SHALL BE RAINTIGHT.

METERBASE

EQUIPMENT MOUNTING RACK,

SEE NOTE 6

NOTES1. ALL WORK SHALL COMPLY WITH COOPERATIVE STANDARDS, THE CURRENT EDITION OF THE NATIONAL ELECTRIC CODE, AND AUTHORITIES

HAVING JURISDICTION.2. MEMBER/ELECTRICIAN PROVIDES AND INSTALLS THE MOUNTING RACK, 1" CONDUIT WITH A PULL STRING, AND ALL RELATED MATERIALS.

METER BASE IS PROVIDED BY AVECC AND INSTALLED BY THE MEMBER/ELECTRICIAN.3. COOPERATIVE PROVIDES AND INSTALLS THE METER AND THE METERING CONDUCTORS FROM THE COOPERATIVE'S SOURCE TO THE METER.4. THIS METER RACK SHALL BE INSTALLED AT A LOCATION MUTUALLY AGREED UPON BY THE MEMBER AND THE COOPERATIVE.5. MEMBER IS RESPONSIBLE FOR OPENING AND CLOSING THE TRENCH FROM THE COOPERATIVE'S SOURCE TO THE METER RACK.6. MOUNTING RACK VERTICAL POSTS MUST BE A MINIMUM OF 2" SCHEDULE 40 WEATHERPROOF PIPE, 4" ROUND TREATED POSTS, OR 4" X 4"

TREATED POSTS. POST MUST BE SET 36" DEEP. STEEL POST MUST BE SET IN CONCRETE. POSTS MUST BE SPACED TO PROVIDE STABLEMOUNTING FOR THE EQUIPMENT. MOUNTING RACK CROSS-MEMBERS MUST BE WEATHERPROOF STEEL OR TREATED WOOD OF SUFFICIENTNUMBER, SIZE, STRENGTH, AND SPACING TO PROVIDE STABLE MOUNTING OF THE ELECTRICAL ENCLOSURES. ALTERNATE RACK MATERIALMAY BE ACCEPTABLE WITH PRIOR APPROVAL FROM AVECC.

7. ALL ABOVE GROUND CONDUITS SHALL BE ELECTRICAL GRADE SCHEDULE 40 PVC, EMT, IMC, OR RMC. ALL CONDUIT CONNECTIONS SHALL BERAINTIGHT.

8. MEMBER SHALL PROVIDE PROTECTIVE METAL PIPE BARRIER IF METERRACK IS SUBJECT TO VEHICULAR TRAFFIC. 3'-0" CLEARANCE TO BE MAINTAINED IN FRONT OF ELECTRICAL ENCLOSURES.

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

CT METER ANDEQUIPMENT RACK

SPEC-0000013 06.19.17 NTSJDC 0 N/A

Page 28: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 29: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

1" NIPPLE WITH

BUSHINGS

CT CABINET

CT CABINET

METERBASE

METERBASE

FRONT VIEW SIDE VIEW

NOTES1. MOUNT METER BASE TO DOOR OF CT CABINET, SEAL MOUNTING SCREW/BOLT HOLES TO WEATHERPROOF.2. LEAVE MINIMUM OF 3 FOOT TAIL OF SERVICE WIRE IN CT CAN FOR ROUTING AND TERMINATION.

MEMBER INSTALLATION MINIMUM WIRE AND CONDUIT SIZESERVICERATING

CONDUIT SIZE ALUMINUMPER NEC

COPPERPER NEC

NEUTRAL GROUNDWIRE SIZE

100A200A320A

3"3"

SEE NEC

#24/0

#42/0

SAME AS PHASE #6 CU#4 CU#2 CU

SAME AS PHASESEE NEC

1 PHASE 3 PHASE3"3"

SEE NEC SEE NEC SEE NECLARGER SEE NEC SEE NEC SEE NECSEE NEC SEE NEC SEE NEC

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

DETAIL FOR METER BASEMOUNTED ON CT CABINET

3 PHASE SERVICE & 480V SINGLE PHASESPEC-0000014 06.08.17 NTS

JDC 0 N/A

Page 30: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 31: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

SERVICE

DISCONNECT

REQUIRED. SERVICE

ENTRANCE RATED

SEE NOTE 6

MINIMUM 3'-0" TAIL LENGTH

ON SERVICE WIRE, COLOR

CODED PER NEC

METERBASE

CTCABINET

TO AVECCSOURCE

MEMBER INSTALLED GROUND WIRE, 5/8" X8'-0"

COPPER-CLAD GROUND ROD INSTALLED FLUSH

OR SLIGHTLY BELOW GRADE, AND CLAMP

REQUIRED. SIZE PER NEC

2' MIN.-6' MAX.

TO CENTERLINE

OF CABINET

6" MIN.

BOND TO ENCLOSURE

SEE NOTE 8

HIGH LEG FOR

DELTA SERVICE

PHASE "C"

6" MIN. - 20' MAX.

MINIMUM 1"

CONDUIT

NO EQUIPMENT SHALL

BE MOUNTED UNDER

METER LOCATION

5' MIN - 6' MAX

MEMBER/ELECTRICIAN

PROVIDES & INSTALLS

PVC SCHEDULE 80 RISER

AND SWEEPING ELBOW

SIZED PER COOPERATIVE

AND SERVICE SIZE

24" MIN.

TO TOP OF CONDUIT

TRENCH 12" WIDE

DITCHWITCH NOT ALLOWED

SCHEDULE 80 PVC

ELBOW REQUIRED

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998

IT SHALL BE A MEMBER'SRESPONSIBILITY TO STAY CLEAR

OF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECC REQUIREMENTS

ONLY, AND IS NOT INTENDED TO BE ACOMPREHENSIVE GUIDE FOR THE INSTALLATION OF

AN ELECTRICAL SERVICE. TO INSURE A SAFE,QUALITY INSTALLATION THAT COMPLIES WITH THENATIONAL ELECTRICAL CODE, AND LOCAL CODE

REQUIREMENTS; THE COOPERATIVE RECOMMENDSTHAT ALL WORK BE DONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

NOTES1. ALL WORK SHALL COMPLY WITH COOPERATIVE STANDARDS, THE CURRENT EDITION OF THE NATIONAL ELECTRIC CODE, AND AUTHORITIES

HAVING JURISDICTION.2. THIS SERVICE SHALL BE INSTALLED AT A LOCATION MUTUALLY AGREED UPON BY THE MEMBER AND THE COOPERATIVE. THE LOCATION

SHALL BE READILY ACCESSIBLY AT ALL TIMES TO THE COOPERATIVE.3. ALL MATERIAL, EXCEPT INSTRUMENT TRANSFORMERS, METER, METER SOCKET, AND METERING CONDUCTORS; ARE TO BE FURNISHED,

INSTALLED, AND MAINTAINED BY THE MEMBER.4. INSTRUMENT TRANSFORMERS, CT CABINET, AND METER SOCKET ARE FURNISHED BY THE COOPERATIVE AND INSTALLED BY THE

MEMBER/ELECTRICIAN.5. THE CT CABINET, METER SOCKET, AND ALL ASSOCIATED CONDUITS AND EQUIPMENT SHALL BE SECURELY MOUNTED TO THE BUILDING

WALL USING LAG BOLTS, MASONRY ANCHORS, OR SIMILAR HARDWARE(PLASTICANCHORS ARE NOT ACCEPTABLE).

6. THE COOPERATIVE RECOMMENDS THAT THE DISCONNECT SWITCH BE MOUNTEDOUTSIDE WITHIN 36" OF THE CT CABINET. CONTACT THE LOCAL AUTHORITIES HAVINGJURISDICTION FOR ACTUAL REQUIREMENTS.

7. ALL ABOVE GROUND CONDUITS SHALL BE ELECTRICAL GRADE SCHEDULE 40 PVC,EMT, IMC, OR RMC. ALL CONDUIT CONNECTIONS SHALL BE RAINTIGHT. ALLUNDERGROUND ELBOWS AND RISER SHALL BE SCHEDULE 80 PVC.

8. ALL ENCLOSURES SHALL BE GROUNDED AND BONDED PER NEC REQUIREMENTS.9. CONTACT COOPERATIVE TO DETERMINE PLACEMENT OF CONDUIT SYSTEM TO THE

COOPERATIVE'S FACILITIES. MEMBER IS REQUIRED TO OPEN AND CLOSE SERVICETRENCH, MINIMUM OF 12" WIDE. NO DITCHWITCH ALLOWED.

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

BUILDING MOUNTED CT CABINET FORUNDERGROUND SERVICE

RATED ABOVE 320ASPEC-0000015 06.19.17 NTS

JDC 0 N/A

Page 32: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 33: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

SERVICE

DISCONNECT

REQUIRED. SERVICE

ENTRANCE RATED

SEE NOTE 7

MINIMUM 3'-0" TAIL LENGTH ON SERVICE

WIRE, COLOR CODED PER NEC

METERBASE

CTCABINET

TO AVECCSOURCE

MEMBER INSTALLED GROUND WIRE, 5/8" X8'-0" COPPER-

CLAD GROUND ROD INSTALLED FLUSH OR SLIGHTLY

BELOW GRADE, AND CLAMP REQUIRED. SIZE PER NEC

2' MIN.-6' MAX.

TO CENTERLINE

OF CABINET

6" MIN.

BOND TO

ENCLOSURE

SEE NOTE 9

HIGH LEG FOR

DELTA SERVICE

PHASE "C"

6" MIN. - 20' MAX.

MINIMUM 1"

CONDUIT

NO

EQUIPMENT

SHALL

BE

MOUNTED

UNDER

METER

LOCATION

5' MIN - 6' MAX

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998

IT SHALL BE A MEMBER'SRESPONSIBILITY TO STAY CLEAR

OF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECC REQUIREMENTS

ONLY, AND IS NOT INTENDED TO BE ACOMPREHENSIVE GUIDE FOR THE INSTALLATION OF

AN ELECTRICAL SERVICE. TO INSURE A SAFE,QUALITY INSTALLATION THAT COMPLIES WITH THENATIONAL ELECTRICAL CODE, AND LOCAL CODE

REQUIREMENTS; THE COOPERATIVE RECOMMENDSTHAT ALL WORK BE DONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

NOTES1. ALL WORK SHALL COMPLY WITH COOPERATIVE STANDARDS, THE CURRENT EDITION OF THE NATIONAL ELECTRIC CODE, AND AUTHORITIES

HAVING JURISDICTION.2. THIS SERVICE SHALL BE INSTALLED AT A LOCATION MUTUALLY AGREED UPON BY THE MEMBER AND THE COOPERATIVE. THE LOCATION

SHALL BE READILY ACCESSIBLY AT ALL TIMES TO THE COOPERATIVE.3. CT CABINET AND METER BASE ARE PROVIDED BY AVECC, INSTALLED AND MAINTAINED BY THE MEMBER.4. CT TRANSFORMERS AND METER ARE PROVIDED AND INSTALLED BY AVECC.5. SERVICE ENTRANCE CONDUCTOR TAILS SHALL EXTEND A MINIMUM OF 36 INCHES INSIDE CT CABINET. TERMINATIONS ARE BY AVECC.6. THE CT CABINET, METER SOCKET, AND ALL ASSOCIATED CONDUITS AND EQUIPMENT SHALL BE SECURELY MOUNTED TO THE BUILDING WALL

USING LAG BOLTS, MASONRY ANCHORS, OR SIMILAR HARDWARE(PLASTIC ANCHORS ARE NOT ACCEPTABLE).7. THE COOPERATIVE RECOMMENDS THAT THE DISCONNECT SWITCH BE MOUNTED

OUTSIDE WITHIN 36" OF THE CT CABINET. CONTACT THE LOCAL AUTHORITIES HAVINGJURISDICTION FOR ACTUAL REQUIREMENTS.

8. ALL CONDUITS SHALL BE ELECTRICAL GRADE SCHEDULE 40 PVC,EMT, IMC, OR RMC. MAST(S) THROUGH ATTIC AND ABOVE ROOF LINE SHALL BE RMC;ADDITIONAL BRACING MAY BE REQUIRED TO SUPPORT THE WEIGHT OF THESERVICE DROP CONDUCTORS.ALL CONDUIT CONNECTIONS SHALL BE RAINTIGHT.

9. ALL ENCLOSURES SHALL BE GROUNDED AND BONDED PER NEC REQUIREMENTS.10. CONTACT COOPERATIVE TO DETERMINE PLACEMENT OF CONDUIT/CONDUCTOR

SYSTEM TO THE COOPERATIVE'S FACILITIES.11. BUILDING ATTACHMENT POINT MUST BE A MINIMUM 1/2" GRADE 5 GALVANIZED STEEL

EYEBOLT SECURELY FASTENED TO BUILDING BY THE MEMBER. A MAST MAY BEREQUIRED TO PROVIDE ADEQUATE ATTACHMENT HEIGHT.

SEE NOTE 5

BUILDING ATTACHMENT POINT( AND

MAST IF REQUIRED) INSTALLED BY

MEMBER/ELECTRICIAN. SEE NOTE 9

SERVICE ENTRANCE MIN. CLEARANCES12'16'

ABOVE GROUNDABOVE RESIDENTIAL DRIVEWAYS

18' ABOVE PUBLIC DRIVEWAYS, ALLEYS, ROADS, AND OTHERAREAS SUBJECT TO TRUCK ANDCONSTRUCTION TRAFFIC

COOPERATIVE PROVIDES ANDINSTALLS SERVICE DROP ANDCONNECTORS

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

BUILDING MOUNTED CT CABINET FOROVERHEAD SERVICE

RATED ABOVE 320ASPEC-0000016 06.19.17 NTS

JDC 0 N/A

Page 34: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 35: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

SERVICE DISCONNECT

REQUIRED, SERVICE

ENTRANCE RATED.

SHALL BE INSTALLED

AT A READILY

ACCESSIBLE LOCATION

OUTSIDE OR

NEAREST POINT

OF ENTRY OF

SERVICE CONDUCTORS.

INSTALLATION SHALL

COMPLY WITH

LATEST EDITION

OF NEC.

MEMBER INSTALLED

GROUND WIRE, 5/8" X 8'-0"

COPPER-CLAD GROUND ROD

INSTALLED FLUSH

OR SLIGHTLY BELOW GRADE,

AND CLAMP REQUIRED. SIZE

PER NEC

MEMBER'S BUILDING

INSTRUMENT RATED METER

BASE SUPPLIED BY AVECC &

INSTALLED BY MEMBER/

ELECTRICIAN.

5'0" MIN.

6'0" MAX.

20 FT. MAX. OR USE

DIAGRAM BELOW

PAD MOUNTED TRANSFORMER

SUPPLIED BY AVECC

PAD PROVIDED BY

AVECC FOR SINGLE

PHASE UP TO 167kVA,

SINGLE PHASE

ABOVE 167kVA & ALL

3 PHASE PADS BY

MEMBER PER AVECC

SPECIFICATIONS

1" SCHEDULE 40 PVC OR RMC

CONDUIT, WITH PULL STRING.

PROVIDED & INSTALLED BY

MEMBER/ELECTRICIAN.MEMEBER OWNED AND INSTALLED SERVICE

CONDUCTORS, LEAVE 48" TAIL IN TRANSFORMER FOR

AVECC TO TERMINATE.(LABEL PHASES AND NEUTRAL)

METERING CABLE

PROVIDED & INSTALLED

BY AVECC

5'0" MIN.

6'0" MAX.

ABOVE FINAL

GRADE LEVEL

20FT. MAXIMUM

HORIZONTAL DISTANCE

MAX (2) 90 DEGREE BENDS

MEMBER PROVIDES

AND INSTALLS METER

PEDESTAL OR RACK

REFER TO DRAWING

4.10-2, LOCATE IN AN

AREA NOT SUBJECT

TO VEHICLE TRAFFIC

OR PROTECT WITH A

BARRIER

24" MIN. DEPTH

MEMBER OWNED & INSTALLED SERVICE

CONDCUTORS AND CONDUIT, LEAVE 48"

TAIL IN TRANSFORMER FOR AVECC TO

TERMINATE. (LABEL PHASES AND

NEUTRAL)

1" SCHEDULE 40 PVC OR RMC

CONDUIT, WITH PULL STRING.

PROVIDED & INSTALLED BY

MEMBER/ELECTRICIAN.

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

PADMOUNT CT IN TRANSFORMERSINGLE OR THREE PHASE SERVICE

SPEC-0000017 06.19.17 NTSJDC 0 N/A

Page 36: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 37: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

PAD 3-PHASETRANSFORMER kVA

DIMENSIONS IN INCHES

#1

#2

75, 112-1/2, 150, 225,300, 500

750, 1000, 2500

A B C D E

76 62 10 42 6

104 100 10 54 8

REINFORCING BARSMK1 MK2 MK3 MK4 MK57 #470"

4 #410"

6 #457"

6 #428"

4 #426"

12 #498"

6 #419"

6 #494"

7 #466"

4 #429"

TOOL OR CHAMFER EDGES

MK1

MK2

MK4MK3

3"

3"

3"

18"

PRIMARY

SECONDARY

13"

D

2"

C

A

B

3"

E

NOTES1. CONCRETE TESTING, 4000 POUNDS PER SQUARE INCH; 4% TO 6% ENTRAINED AIR, 3/4" MAXIMUM SIZE AGGREGATE.2. REINFORCING STEEL, ATSM-A615 GRADE 60, PLACE APPROXIMATELY 6" ON CENTER EACH WAY AND SECURELY TIED TOGETHER.3. MINIMUM CONCRETE COVER OVER REINFORCING STEEL IS 2 INCHES UNLESS NOTED OTHERWISE.4. WOOD FLOAT FINISH, LEAVING NO DEPRESSIONS.

1

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

THREE PHASE TRANSFORMERCONCRETE PAD DETAIL

SPEC-0000018 07.03.17 NTSJDC 0 N/A

Page 38: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 39: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

CANOPY OVERDOOR WAY

BUILDING

WALL

BUILDING

WALL

1-3 STORY

BUILDING

WALL

SEE NOTES BELOW

WALKWAY & BALCONY

STAIRS

STAIRS

OVERHANG

NOTES1. IF THE BUILDING HAS AN OVERHANG AND IS 3 OR LESS FLOORS IN HEIGHT ABOVE THE GROUND, THE "A" CLEARANCE IS MEASURED FROM A

POINT BELOW THE EDGE OF THE OVERHANG.2. IF THE BUILDING HAS AN OVERHANG AND IS 4 OR MORE FLOORS IN HEIGHT ABOVE THE GROUND, THE "A" CLEARANCE MAY BE MEASURED

FROM THE BUILDING WALL.3. FIRE ESCAPES, OUTSIDE STAIRS, AND COVERED WALKWAYS ATTACHED TO OR BETWEEN BUILDINGS, SHALL BE CONSIDERED AS PART OF

THE BUILDING.4. IF CLEARANCE LISTED ABOVE CAN NOT OBTAINED SEE DRAWING SPEC-0000020.

TRANSFORMERkVA RATING

DIMENSIONS IN FEET

0-75A B10 14

76-333334-LARGER

20 2030 30

NOTE: TRANSFORMER PADSSHALL NOT BE LOCATED INSHADED AREA.

PREFERREDBUILDING SIDE

THIS SIDE SHALLBE OPEN ANDACCESSIBLE

CONCRETE

PAD

10'

10'

10'

"A"

"A"

"A"

"A"

"A"

"B"

"B"

"B" "B"

"A"

"A"

"A"

"A"

"A"

"B"

"A"

"A"

"A"

"A"

"A"

"A"

"A"

"B" "B"

"A"

"A"

"A"

"A" "A"

"A"

"A"

"A"

"A"

"A"

"A"

"A"

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

LOCATION OF PADMOUNTTRANSFORMERS FROM BUILDINGS

SPEC-0000019 07.03.17 NTSJDC 0 N/A

Page 40: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 41: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

BUILDING

BARRIER

TRANSFORMER

& PAD

BUILDING

BARRIER

TRANSFORMER

& PAD

1' MINIMUM

LESS THAN

"A"

2' MINIMUM

2' MINIMUM

NOT LESS THAN DIMENSION "A"

NOT LESS THAN DIMENSION "A"

NOT LESS THAN DIMENSION "A"

NOTES1. IF DIMENSION "A" IS LESS THAN SHOWN ABOVE, A FIRE BARRIER MAY BE INSTALLED BETWEEN THE TRANSFORMER AND THE BUILDING.2. THE BARRIER SHALL BE CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, SUCH AS REINFORCED CONCRETE, CONCRETE BLOCK, OR

SHEET STEEL.3. REFER TO THE FOLLOWING REFERENCES FOR ADDITIONAL INFORMATION: NEC NFPA 70 450.27

NESC SECTION 15, 152 A2

TRANSFORMERkVA RATING

DIMENSIONS IN FEET

0-75A10

76-333334-LARGER

2030

CLEARANCE FROM BUILDING WALLS & EAVES

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

LOCATION OF PADMOUNTTRANSFORMERS WITH REDUCED

CLEARANCE FROM BUILDINGSSPEC-0000020 07.03.17 NTS

JDC 0 N/A

Page 42: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 43: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

MEMBER INSTALLED GROUND WIRE,

SECURED TO MOUNTING STRUCTURE,

5/8" X8'-0" COPPER-CLAD GROUND ROD

INSTALLED FLUSH OR SLIGHTLY BELOW

GRADE, AND CLAMP REQUIRED. SEE

TABLE DRAWING SPEC-0000010.

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECCREQUIREMENTS ONLY, AND IS NOT

INTENDED TO BE A COMPREHENSIVEGUIDE FOR THE INSTALLATION OF ANELECTRICAL SERVICE. TO INSURE ASAFE, QUALITY INSTALLATION THAT

COMPLIES WITH THE NATIONALELECTRICAL CODE, AND LOCAL CODEREQUIREMENTS; THE COOPERATIVERECOMMENDS THAT ALL WORK BEDONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

METERBASE

NOTES1. AVECC RECOMMENDS THAT A LICENSED ELECTRICIAN INSTALLS TRANSFER SWITCH AND GENERATOR PER NEC CODE AND LOCAL ORDINANCES.2. MANUAL TRANSFER SWITCH SHALL BE CONSTRUCTED IN A MANNER THAT DOES NOT ALLOW UTILITY POWER AND GENERATOR POWER TO BE TIED

TOGETHER AT ANY GIVEN TIME.3. MULTIPLE CIRCUIT BREAKERS/FUSED DISCONNECTS CAN BE CONNECTED AFTER THE TRANSFER SWITCH, SO LONG AS THE SUM OF THE BREAKER

INTERRUPTING CURRENT OF EACH BREAKER/FUSED DISCONNECT DOES NOT EXCEED THE MANUAL TRANSFER SWITCH RATING OR THE ELECTRICSERVICE SIZE.

4. REFER TO DRAWINGS SPEC-000001 THROUGH SPEC-0000017 FOR INCOMING SERVICE REQUIREMENTS, AVECC SUPPLIED EQUIPMENT & SERVICES,MEMBER REQUIRED EQUIPMENT & SERVICES, DITCH REQUIREMENTS, ETC.

5. WHERE PANELS AND EQUIPMENT ARE NOT MOUNTED ON BUILDING STRUCTURE, REFER TO DRAWINGS SPEC-0000011 & SPEC-0000012 FOR RACKMATERIAL AND INSTALLATION REQUIREMENTS. ALLOW ADEQUATE ROOM ON RACK FOR ALL EQUIPMENT/PANELS NECESSARY.

6. ALL EXTERIOR PANELS ARE TO BE RATED NO LESS THAN NEMA 3R.7. WHERE MANUAL TRANSFER SWITCH CLEARLY STATES ON A MANUFACTURER'S LABEL ATTACHED TO TRANSFER SWITCH ENCLOSURE THAT THE

SWITCH HAS BOTH OVER CURRENT PROTECTION RATED FOR THE FULL LOAD ELECTRICAL SERVICE AND IS SERVICE ENTRANCE RATED, THENSERVICE ENTRANCE RATED BREAKER/FUSED DISCONNECT AHEAD OF TRANSFER SWITCH SHOWN ABOVE IS NOT REQUIRED. OTHERWISE,SERVICE ENTRANCE BREAKER/FUSED DISCONNECT MUST BE INSTALLED PRIOR TO AVECC CONNECTING ELECTRICAL SERVICE TO METER.

8. PROTECTIVE BUSHINGS REQUIRED ON ALL CONDUITS.9. NO WIRING GUTTERS OR TROUGHS WILL BE ALLOWED ON THE OUTSIDE OF THE BUILDING.

200AMANUAL

TRANSFERSWITCH

CB

5'-0" MIN.

6'-0" MAX.

6" SPACE BETWEEN BOXES

REQUIRED.

CONDUIT & WIRE TO PORTABLEGENERATOR CONNECTION POINT

OR PERMANENT GENERATOR.INSTALL PER NEC CODE AND

MANUFACTURER'SRECOMMENDATIONS/MANUALS.

NOTE: NEUTRAL IS ISOLATEDFROM THE GROUND AT THE

GENERATOR.

200ACB

SERVICE ENTRANCE RATED CIRCUIT BREAKER

OR FUSED DISCONNECT WITH OVER CURRENT

PROTECTION SIZED APPROPRIATELY FOR FULL

SERVICE LOAD. SEE NOTE 7

SEE NOTE 3

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

200A STANDBY GENERATOR,COMPLETE SERVICE

MANUAL TRANSFER SWITCHSPEC-0000021 12.08.2017 NTS

JDC 0 N/A

Page 44: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 45: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

MEMBER INSTALLED GROUND WIRE,

SECURED TO MOUNTING STRUCTURE,

5/8" X8'-0" COPPER-CLAD GROUND ROD

INSTALLED FLUSH OR SLIGHTLY BELOW

GRADE, AND CLAMP REQUIRED. SEE

TABLE DRAWING SPEC-0000010.

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECCREQUIREMENTS ONLY, AND IS NOT

INTENDED TO BE A COMPREHENSIVEGUIDE FOR THE INSTALLATION OF ANELECTRICAL SERVICE. TO INSURE ASAFE, QUALITY INSTALLATION THAT

COMPLIES WITH THE NATIONALELECTRICAL CODE, AND LOCAL CODEREQUIREMENTS; THE COOPERATIVERECOMMENDS THAT ALL WORK BEDONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

METERBASE

NOTES1. AVECC RECOMMENDS THAT A LICENSED ELECTRICIAN INSTALLS TRANSFER SWITCH AND GENERATOR PER NEC CODE AND LOCAL ORDINANCES.2. MANUAL TRANSFER SWITCH SHALL BE CONSTRUCTED IN A MANNER THAT DOES NOT ALLOW UTILITY POWER AND GENERATOR POWER TO BE TIED

TOGETHER AT ANY GIVEN TIME.3. MULTIPLE CIRCUIT BREAKERS/FUSED DISCONNECTS CAN BE CONNECTED AFTER THE TRANSFER SWITCH, SO LONG AS THE SUM OF THE BREAKER

INTERRUPTING CURRENT OF EACH BREAKER/FUSED DISCONNECT DOES NOT EXCEED THE MANUAL TRANSFER SWITCH CURRENT RATING.4. REFER TO DRAWINGS SPEC-000001 THROUGH SPEC-0000017 FOR INCOMING SERVICE REQUIREMENTS, AVECC SUPPLIED EQUIPMENT & SERVICES,

MEMBER REQUIRED EQUIPMENT & SERVICES, DITCH REQUIREMENTS, ETC.5. WHERE PANELS AND EQUIPMENT ARE NOT MOUNTED ON BUILDING STRUCTURE, REFER TO DRAWINGS SPEC-0000011 & SPEC-0000012 FOR RACK

MATERIAL AND INSTALLATION REQUIREMENTS. ALLOW ADEQUATE ROOM ON RACK FOR ALL EQUIPMENT/PANELS NECESSARY.6. ALL EXTERIOR PANELS ARE TO BE RATED NO LESS THAN NEMA 3R.7. PROTECTIVE BUSHINGS REQUIRED ON ALL CONDUITS.8. NO WIRING GUTTERS OR TROUGHS WILL BE ALLOWED ON THE OUTSIDE OF THE BUILDING.

200AMANUAL

TRANSFERSWITCH

CB

5'-0" MIN.

6'-0" MAX.

6" SPACE BETWEEN BOXES

REQUIRED.

CONDUIT & WIRE TO PORTABLEGENERATOR CONNECTION POINT

OR PERMANENT GENERATOR.INSTALL PER NEC CODE AND

MANUFACTURER'SRECOMMENDATIONS/MANUALS.

NOTE: NEUTRAL IS ISOLATEDFROM THE GROUND AT THE

GENERATOR.

400ACB

SERVICE ENTRANCE RATED CIRCUIT BREAKER

OR FUSED DISCONNECT WITH OVER CURRENT

PROTECTION SIZED APPROPRIATELY FOR FULL

SERVICE LOAD.

200ACB

SEE NOTE 3

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

400A STANDBY GENERATOR,PARTIAL SERVICE

MANUAL TRANSFER SWITCHSPEC-0000022 12.08.2017 NTS

JDC 0 N/A

Page 46: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 47: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

MEMBER INSTALLED GROUND WIRE,

SECURED TO MOUNTING STRUCTURE,

5/8" X8'-0" COPPER-CLAD GROUND ROD

INSTALLED FLUSH OR SLIGHTLY BELOW

GRADE, AND CLAMP REQUIRED. SEE

TABLE DRAWING SPEC-0000010.

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECCREQUIREMENTS ONLY, AND IS NOT

INTENDED TO BE A COMPREHENSIVEGUIDE FOR THE INSTALLATION OF ANELECTRICAL SERVICE. TO INSURE ASAFE, QUALITY INSTALLATION THAT

COMPLIES WITH THE NATIONALELECTRICAL CODE, AND LOCAL CODEREQUIREMENTS; THE COOPERATIVERECOMMENDS THAT ALL WORK BEDONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

METERBASE

NOTES1. AVECC RECOMMENDS THAT A LICENSED ELECTRICIAN INSTALLS TRANSFER SWITCH AND GENERATOR PER NEC CODE AND LOCAL ORDINANCES.2. MANUAL TRANSFER SWITCH SHALL BE CONSTRUCTED IN A MANNER THAT DOES NOT ALLOW UTILITY POWER AND GENERATOR POWER TO BE TIED

TOGETHER AT ANY GIVEN TIME.3. MULTIPLE CIRCUIT BREAKERS/FUSED DISCONNECTS CAN BE CONNECTED AFTER THE TRANSFER SWITCH, SO LONG AS THE SUM OF THE BREAKER

INTERRUPTING CURRENT OF EACH BREAKER/FUSED DISCONNECT DOES NOT EXCEED THE MANUAL TRANSFER SWITCH RATING OR THE ELECTRICSERVICE SIZE.

4. REFER TO DRAWINGS SPEC-000001 THROUGH SPEC-0000017 FOR INCOMING SERVICE REQUIREMENTS, AVECC SUPPLIED EQUIPMENT & SERVICES,MEMBER REQUIRED EQUIPMENT & SERVICES, DITCH REQUIREMENTS, ETC.

5. WHERE PANELS AND EQUIPMENT ARE NOT MOUNTED ON BUILDING STRUCTURE, REFER TO DRAWINGS SPEC-0000011 & SPEC-0000012 FOR RACKMATERIAL AND INSTALLATION REQUIREMENTS. ALLOW ADEQUATE ROOM ON RACK FOR ALL EQUIPMENT/PANELS NECESSARY.

6. ALL EXTERIOR PANELS ARE TO BE RATED NO LESS THAN NEMA 3R.7. WHERE MANUAL TRANSFER SWITCH CLEARLY STATES ON A MANUFACTURER'S LABEL ATTACHED TO TRANSFER SWITCH ENCLOSURE THAT THE

SWITCH HAS BOTH OVER CURRENT PROTECTION RATED FOR THE FULL LOAD ELECTRICAL SERVICE AND IS SERVICE ENTRANCE RATED, THENSERVICE ENTRANCE RATED BREAKER/FUSED DISCONNECT AHEAD OF TRANSFER SWITCH SHOWN ABOVE IS NOT REQUIRED. OTHERWISE,SERVICE ENTRANCE BREAKER/FUSED DISCONNECT MUST BE INSTALLED PRIOR TO AVECC CONNECTING ELECTRICAL SERVICE TO METER.

8. PROTECTIVE BUSHINGS REQUIRED ON ALL CONDUITS.9. NO WIRING GUTTERS OR TROUGHS WILL BE ALLOWED ON THE OUTSIDE OF THE BUILDING.

400AMANUAL

TRANSFERSWITCH

CB

5'-0" MIN.

6'-0" MAX.

6" SPACE BETWEEN BOXES

REQUIRED.

CONDUIT & WIRE TO PORTABLEGENERATOR CONNECTION POINT

OR PERMANENT GENERATOR.INSTALL PER NEC CODE AND

MANUFACTURER'SRECOMMENDATIONS/MANUALS.

NOTE: NEUTRAL IS ISOLATEDFROM THE GROUND AT THE

GENERATOR.

400ACB

SERVICE ENTRANCE RATED CIRCUIT BREAKER

OR FUSED DISCONNECT WITH OVER CURRENT

PROTECTION SIZED APPROPRIATELY FOR FULL

SERVICE LOAD. SEE NOTE 7

SEE NOTE 3

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

400A STANDBY GENERATOR,COMPLETE SERVICE

MANUAL TRANSFER SWITCHSPEC-0000023 12.08.2017 NTS

JDC 0 N/A

Page 48: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 49: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

MEMBER INSTALLED GROUND WIRE,

SECURED TO MOUNTING STRUCTURE,

5/8" X8'-0" COPPER-CLAD GROUND ROD

INSTALLED FLUSH OR SLIGHTLY BELOW

GRADE, AND CLAMP REQUIRED. SEE

TABLE DRAWING SPEC-0000010.

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECCREQUIREMENTS ONLY, AND IS NOT

INTENDED TO BE A COMPREHENSIVEGUIDE FOR THE INSTALLATION OF ANELECTRICAL SERVICE. TO INSURE ASAFE, QUALITY INSTALLATION THAT

COMPLIES WITH THE NATIONALELECTRICAL CODE, AND LOCAL CODEREQUIREMENTS; THE COOPERATIVERECOMMENDS THAT ALL WORK BEDONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

METERBASE

NOTES1. AVECC RECOMMENDS THAT A LICENSED ELECTRICIAN INSTALLS TRANSFER SWITCH AND GENERATOR PER NEC CODE AND LOCAL ORDINANCES.2. MULTIPLE CIRCUIT BREAKERS/FUSED DISCONNECTS CAN BE CONNECTED AFTER THE TRANSFER SWITCH, SO LONG AS THE SUM OF THE BREAKER

INTERRUPTING CURRENT OF EACH BREAKER/FUSED DISCONNECT DOES NOT EXCEED THE AUTOMATIC TRANSFER SWITCH RATING OR THEELECTRIC SERVICE SIZE.

3. REFER TO DRAWINGS SPEC-000001 THROUGH SPEC-0000017 FOR INCOMING SERVICE REQUIREMENTS, AVECC SUPPLIED EQUIPMENT & SERVICES,MEMBER REQUIRED EQUIPMENT & SERVICES, DITCH REQUIREMENTS, ETC.

4. WHERE PANELS AND EQUIPMENT ARE NOT MOUNTED ON BUILDING STRUCTURE, REFER TO DRAWINGS SPEC-0000011 & SPEC-0000012 FOR RACKMATERIAL AND INSTALLATION REQUIREMENTS. ALLOW ADEQUATE ROOM ON RACK FOR ALL EQUIPMENT/PANELS NECESSARY.

5. ALL EXTERIOR PANELS ARE TO BE RATED NO LESS THAN NEMA 3R.6. WHERE AUTOMATIC TRANSFER SWITCH CLEARLY STATES ON A MANUFACTURER'S LABEL ATTACHED TO TRANSFER SWITCH ENCLOSURE THAT

THE SWITCH HAS BOTH OVER CURRENT PROTECTION RATED FOR THE FULL LOAD ELECTRICAL SERVICE AND IS SERVICE ENTRANCE RATED, THENSERVICE ENTRANCE RATED BREAKER/FUSED DISCONNECT AHEAD OF TRANSFER SWITCH SHOWN ABOVE IS NOT REQUIRED. OTHERWISE,SERVICE ENTRANCE BREAKER/FUSED DISCONNECT MUST BE INSTALLED PRIOR TO AVECC CONNECTING ELECTRICAL SERVICE TO METER.

7. PROTECTIVE BUSHINGS REQUIRED ON ALL CONDUITS.8. NO WIRING GUTTERS OR TROUGHS WILL BE ALLOWED ON THE OUTSIDE OF THE BUILDING.

200AAUTOMATICTRANSFER

SWITCH

CB

5'-0" MIN.

6'-0" MAX.

6" SPACE BETWEEN BOXES

REQUIRED.

CONDUIT & WIRE TO PERMANENTGENERATOR. INSTALL PER NECCODE AND MANUFACTURER'S

RECOMMENDATIONS/MANUALS.NOTE: NEUTRAL IS ISOLATEDFROM THE GROUND AT THE

GENERATOR.

200ACB

SERVICE ENTRANCE RATED CIRCUIT BREAKER

OR FUSED DISCONNECT WITH OVER CURRENT

PROTECTION SIZED APPROPRIATELY FOR FULL

SERVICE LOAD. SEE NOTE 6

SEE NOTE 2

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

200A STANDBY GENERATOR,COMPLETE SERVICE

AUTOMATIC TRANSFER SWITCHSPEC-0000024 12.08.2017 NTS

JDC 0 N/A

Page 50: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 51: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

MEMBER INSTALLED GROUND WIRE,

SECURED TO MOUNTING STRUCTURE,

5/8" X8'-0" COPPER-CLAD GROUND ROD

INSTALLED FLUSH OR SLIGHTLY BELOW

GRADE, AND CLAMP REQUIRED. SEE

TABLE DRAWING SPEC-0000010.

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECCREQUIREMENTS ONLY, AND IS NOT

INTENDED TO BE A COMPREHENSIVEGUIDE FOR THE INSTALLATION OF ANELECTRICAL SERVICE. TO INSURE ASAFE, QUALITY INSTALLATION THAT

COMPLIES WITH THE NATIONALELECTRICAL CODE, AND LOCAL CODEREQUIREMENTS; THE COOPERATIVERECOMMENDS THAT ALL WORK BEDONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

METERBASE

200AAUTOMATICTRANSFER

SWITCH

CB

5'-0" MIN.

6'-0" MAX.

6" SPACE BETWEEN BOXES

REQUIRED.

400ACB

SERVICE ENTRANCE RATED CIRCUIT BREAKER

OR FUSED DISCONNECT WITH OVER CURRENT

PROTECTION SIZED APPROPRIATELY FOR FULL

SERVICE LOAD.

200ACB

SEE NOTE 2

NOTES1. AVECC RECOMMENDS THAT A LICENSED ELECTRICIAN INSTALLS TRANSFER SWITCH AND GENERATOR PER NEC CODE AND LOCAL ORDINANCES.2. MULTIPLE CIRCUIT BREAKERS/FUSED DISCONNECTS CAN BE CONNECTED AFTER THE TRANSFER SWITCH, SO LONG AS THE SUM OF THE BREAKER

INTERRUPTING CURRENT OF EACH BREAKER/FUSED DISCONNECT DOES NOT EXCEED THE AUTOMATIC TRANSFER SWITCH CURRENT RATING.3. REFER TO DRAWINGS SPEC-000001 THROUGH SPEC-0000017 FOR INCOMING SERVICE REQUIREMENTS, AVECC SUPPLIED EQUIPMENT & SERVICES,

MEMBER REQUIRED EQUIPMENT & SERVICES, DITCH REQUIREMENTS, ETC.4. WHERE PANELS AND EQUIPMENT ARE NOT MOUNTED ON BUILDING STRUCTURE, REFER TO DRAWINGS SPEC-0000011 & SPEC-0000012 FOR RACK

MATERIAL AND INSTALLATION REQUIREMENTS. ALLOW ADEQUATE ROOM ON RACK FOR ALL EQUIPMENT/PANELS NECESSARY.5. ALL EXTERIOR PANELS ARE TO BE RATED NO LESS THAN NEMA 3R.6. PROTECTIVE BUSHINGS REQUIRED ON ALL CONDUITS.7. NO WIRING GUTTERS OR TROUGHS WILL BE ALLOWED ON THE OUTSIDE OF THE BUILDING.

CONDUIT & WIRE TO PERMANENTGENERATOR. INSTALL PER NECCODE AND MANUFACTURER'S

RECOMMENDATIONS/MANUALS.NOTE: NEUTRAL IS ISOLATEDFROM THE GROUND AT THE

GENERATOR.

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

400A STANDBY GENERATOR,PARTIAL SERVICE

AUTOMATIC TRANSFER SWITCHSPEC-0000025 12.08.2017 NTS

JDC 0 N/A

Page 52: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 53: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

MEMBER INSTALLED GROUND WIRE,

SECURED TO MOUNTING STRUCTURE,

5/8" X8'-0" COPPER-CLAD GROUND ROD

INSTALLED FLUSH OR SLIGHTLY BELOW

GRADE, AND CLAMP REQUIRED. SEE

TABLE DRAWING SPEC-0000010.

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECCREQUIREMENTS ONLY, AND IS NOT

INTENDED TO BE A COMPREHENSIVEGUIDE FOR THE INSTALLATION OF ANELECTRICAL SERVICE. TO INSURE ASAFE, QUALITY INSTALLATION THAT

COMPLIES WITH THE NATIONALELECTRICAL CODE, AND LOCAL CODEREQUIREMENTS; THE COOPERATIVERECOMMENDS THAT ALL WORK BEDONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

METERBASE

400AAUTOMATICTRANSFER

SWITCH

CB

5'-0" MIN.

6'-0" MAX.

6" SPACE BETWEEN BOXES

REQUIRED.

400ACB

SERVICE ENTRANCE RATED CIRCUIT BREAKER

OR FUSED DISCONNECT WITH OVER CURRENT

PROTECTION SIZED APPROPRIATELY FOR FULL

SERVICE LOAD. SEE NOTE 6

SEE NOTE 2

NOTES1. AVECC RECOMMENDS THAT A LICENSED ELECTRICIAN INSTALLS TRANSFER SWITCH AND GENERATOR PER NEC CODE AND LOCAL ORDINANCES.2. MULTIPLE CIRCUIT BREAKERS/FUSED DISCONNECTS CAN BE CONNECTED AFTER THE TRANSFER SWITCH, SO LONG AS THE SUM OF THE BREAKER

INTERRUPTING CURRENT OF EACH BREAKER/FUSED DISCONNECT DOES NOT EXCEED THE AUTOMATIC TRANSFER SWITCH RATING OR THEELECTRIC SERVICE SIZE.

3. REFER TO DRAWINGS SPEC-000001 THROUGH SPEC-0000017 FOR INCOMING SERVICE REQUIREMENTS, AVECC SUPPLIED EQUIPMENT & SERVICES,MEMBER REQUIRED EQUIPMENT & SERVICES, DITCH REQUIREMENTS, ETC.

4. WHERE PANELS AND EQUIPMENT ARE NOT MOUNTED ON BUILDING STRUCTURE, REFER TO DRAWINGS SPEC-0000011 & SPEC-0000012 FOR RACKMATERIAL AND INSTALLATION REQUIREMENTS. ALLOW ADEQUATE ROOM ON RACK FOR ALL EQUIPMENT/PANELS NECESSARY.

5. ALL EXTERIOR PANELS ARE TO BE RATED NO LESS THAN NEMA 3R.6. WHERE AUTOMATIC TRANSFER SWITCH CLEARLY STATES ON A MANUFACTURER'S LABEL ATTACHED TO TRANSFER SWITCH ENCLOSURE THAT

THE SWITCH HAS BOTH OVER CURRENT PROTECTION RATED FOR THE FULL LOAD ELECTRICAL SERVICE AND IS SERVICE ENTRANCE RATED, THENSERVICE ENTRANCE RATED BREAKER/FUSED DISCONNECT AHEAD OF TRANSFER SWITCH SHOWN ABOVE IS NOT REQUIRED. OTHERWISE,SERVICE ENTRANCE BREAKER/FUSED DISCONNECT MUST BE INSTALLED PRIOR TO AVECC CONNECTING ELECTRICAL SERVICE TO METER.

7. PROTECTIVE BUSHINGS REQUIRED ON ALL CONDUITS.8. NO WIRING GUTTERS OR TROUGHS WILL BE ALLOWED ON THE OUTSIDE OF THE BUILDING.

CONDUIT & WIRE TO PERMANENTGENERATOR. INSTALL PER NECCODE AND MANUFACTURER'S

RECOMMENDATIONS/MANUALS.NOTE: NEUTRAL IS ISOLATEDFROM THE GROUND AT THE

GENERATOR.

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

400A STANDBY GENERATOR,COMPLETE SERVICE

AUTOMATIC TRANSFER SWITCHSPEC-0000026 12.08.2017 NTS

JDC 0 N/A

Page 54: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 55: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

MEMBER INSTALLED GROUND WIRE,

SECURED TO MOUNTING STRUCTURE,

5/8" X8'-0" COPPER-CLAD GROUND ROD

INSTALLED FLUSH OR SLIGHTLY BELOW

GRADE, AND CLAMP REQUIRED. REFER

TO GROUND WIRE SIZE.

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECCREQUIREMENTS ONLY, AND IS NOT

INTENDED TO BE A COMPREHENSIVEGUIDE FOR THE INSTALLATION OF ANELECTRICAL SERVICE. TO INSURE ASAFE, QUALITY INSTALLATION THAT

COMPLIES WITH THE NATIONALELECTRICAL CODE, AND LOCAL CODEREQUIREMENTS; THE COOPERATIVERECOMMENDS THAT ALL WORK BEDONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

METERBASE

600A OR LARGER

AUTOMATICTRANSFER

SWITCH

CB

5'-0" MIN.

6'-0" MAX.

6" SPACE BETWEEN BOXES

REQUIRED.

600ACBOR

LARGER

SERVICE ENTRANCE RATED CIRCUIT BREAKER

OR FUSED DISCONNECT WITH OVER CURRENT

PROTECTION SIZED APPROPRIATELY FOR FULL

SERVICE LOAD. SEE NOTE 6

SEE NOTE 2

CONDUIT & WIRE TO PERMANENTGENERATOR. INSTALL PER NECCODE AND MANUFACTURER'S

RECOMMENDATIONS/MANUALS.NOTE: NEUTRAL IS ISOLATEDFROM THE GROUND AT THE

GENERATOR.

NOTES1. AVECC RECOMMENDS THAT A LICENSED ELECTRICIAN INSTALLS TRANSFER SWITCH AND GENERATOR PER NEC CODE AND LOCAL ORDINANCES.2. MULTIPLE CIRCUIT BREAKERS/FUSED DISCONNECTS CAN BE CONNECTED AFTER THE TRANSFER SWITCH, SO LONG AS THE SUM OF THE BREAKER

INTERRUPTING CURRENT OF EACH BREAKER/FUSED DISCONNECT DOES NOT EXCEED THE AUTOMATIC TRANSFER SWITCH RATING OR THEELECTRIC SERVICE SIZE.

3. REFER TO DRAWINGS SPEC-000001 THROUGH SPEC-0000017 FOR INCOMING SERVICE REQUIREMENTS, AVECC SUPPLIED EQUIPMENT & SERVICES,MEMBER REQUIRED EQUIPMENT & SERVICES, DITCH REQUIREMENTS, ETC.

4. WHERE PANELS AND EQUIPMENT ARE NOT MOUNTED ON BUILDING STRUCTURE, REFER TO DRAWINGS SPEC-0000011 & SPEC-0000012 FOR RACKMATERIAL AND INSTALLATION REQUIREMENTS. ALLOW ADEQUATE ROOM ON RACK FOR ALL EQUIPMENT/PANELS NECESSARY.

5. ALL EXTERIOR PANELS ARE TO BE RATED NO LESS THAN NEMA 3R.6. WHERE MANUAL TRANSFER SWITCH CLEARLY STATES ON A MANUFACTURER'S LABEL ATTACHED TO TRANSFER SWITCH ENCLOSURE THAT THE

SWITCH HAS BOTH OVER CURRENT PROTECTION RATED FOR THE FULL LOAD ELECTRICAL SERVICE AND IS SERVICE ENTRANCE RATED, THENSERVICE ENTRANCE RATED BREAKER/FUSED DISCONNECT AHEAD OF TRANSFER SWITCH SHOWN ABOVE IS NOT REQUIRED. OTHERWISE,SERVICE ENTRANCE BREAKER/FUSED DISCONNECT MUST BE INSTALLED PRIOR TO AVECC CONNECTING ELECTRICAL SERVICE TO METER.

7. PROTECTIVE BUSHINGS REQUIRED ON ALL CONDUITS.8. NO WIRING GUTTERS OR TROUGHS WILL BE ALLOWED ON THE OUTSIDE OF THE BUILDING.9. REFER TO DRAWING SPEC-0000017 FOR PAD MOUNT TRANSFORMER/CT INSTALLATION REQUIREMENTS.10. THE SERVICE ENTRANCE BREAKER/FUSED DISCONNECT CURRENT RATING MUST MATCH TRANSFER SWITCH CURRENT RATINGS IF SERVICE

ENTRANCE RATED BREAKER/FUSED DISCONNECT IS REQUIRED.11. REFER TO DRAWING SPEC-0000017 FOR INCOMING SERVICE REQUIREMENTS FROM PAD MOUNT TRANSFORMER.

SCHEDULE 40 PVC, 1"

CONDUIT TO AVECC

TRANSFORMER. 20'0"

MAX. SEE NOTE 9.

SEE NOTE 11

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

UG 600A OR LARGER STANDBYGENERATOR, COMPLETE SERVICE

AUTOMATIC TRANSFER SWITCHSPEC-0000027 12.08.2017 NTS

JDC 0 N/A

Page 56: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 57: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

MEMBER INSTALLED GROUND WIRE,

SECURED TO MOUNTING STRUCTURE,

5/8" X8'-0" COPPER-CLAD GROUND ROD

INSTALLED FLUSH OR SLIGHTLY BELOW

GRADE, AND CLAMP REQUIRED. REFER

TO NEC FOR GROUND WIRE SIZE.

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECCREQUIREMENTS ONLY, AND IS NOT

INTENDED TO BE A COMPREHENSIVEGUIDE FOR THE INSTALLATION OF ANELECTRICAL SERVICE. TO INSURE ASAFE, QUALITY INSTALLATION THAT

COMPLIES WITH THE NATIONALELECTRICAL CODE, AND LOCAL CODEREQUIREMENTS; THE COOPERATIVERECOMMENDS THAT ALL WORK BEDONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

METERBASE

600AAUTOMATICTRANSFER

SWITCH

CB

5'-0" MIN.

6'-0" MAX.

6" SPACE BETWEEN BOXES

REQUIRED.

600ACB

SERVICE ENTRANCE RATED CIRCUIT BREAKER

OR FUSED DISCONNECT WITH OVER CURRENT

PROTECTION SIZED APPROPRIATELY FOR FULL

SERVICE LOAD. SEE NOTE 6

SEE NOTE 2

CONDUIT & WIRE TO PERMANENTGENERATOR. INSTALL PER NECCODE AND MANUFACTURER'S

RECOMMENDATIONS/MANUALS.NOTE: NEUTRAL IS ISOLATEDFROM THE GROUND AT THE

GENERATOR.

NOTES1. AVECC RECOMMENDS THAT A LICENSED ELECTRICIAN INSTALLS TRANSFER SWITCH AND GENERATOR PER NEC CODE AND LOCAL ORDINANCES.2. MULTIPLE CIRCUIT BREAKERS/FUSED DISCONNECTS CAN BE CONNECTED AFTER THE TRANSFER SWITCH, SO LONG AS THE SUM OF THE BREAKER

INTERRUPTING CURRENT OF EACH BREAKER/FUSED DISCONNECT DOES NOT EXCEED THE AUTOMATIC TRANSFER SWITCH RATING OR THEELECTRIC SERVICE SIZE.

3. REFER TO DRAWINGS SPEC-000001 THROUGH SPEC-0000017 FOR INCOMING SERVICE REQUIREMENTS, AVECC SUPPLIED EQUIPMENT & SERVICES,MEMBER REQUIRED EQUIPMENT & SERVICES, DITCH REQUIREMENTS, ETC.

4. WHERE PANELS AND EQUIPMENT ARE NOT MOUNTED ON BUILDING STRUCTURE, REFER TO DRAWINGS SPEC-0000011 & SPEC-0000012 FOR RACKMATERIAL AND INSTALLATION REQUIREMENTS. ALLOW ADEQUATE ROOM ON RACK FOR ALL EQUIPMENT/PANELS NECESSARY.

5. ALL EXTERIOR PANELS ARE TO BE RATED NO LESS THAN NEMA 3R.6. WHERE MANUAL TRANSFER SWITCH CLEARLY STATES ON A MANUFACTURER'S LABEL ATTACHED TO TRANSFER SWITCH ENCLOSURE THAT THE

SWITCH HAS BOTH OVER CURRENT PROTECTION RATED FOR THE FULL LOAD ELECTRICAL SERVICE AND IS SERVICE ENTRANCE RATED, THENSERVICE ENTRANCE RATED BREAKER/FUSED DISCONNECT AHEAD OF TRANSFER SWITCH SHOWN ABOVE IS NOT REQUIRED. OTHERWISE,SERVICE ENTRANCE BREAKER/FUSED DISCONNECT MUST BE INSTALLED PRIOR TO AVECC CONNECTING ELECTRICAL SERVICE TO METER.

7. PROTECTIVE BUSHINGS REQUIRED ON ALL CONDUITS.8. NO WIRING GUTTERS OR TROUGHS WILL BE ALLOWED ON THE OUTSIDE OF THE BUILDING.9. REFER TO DRAWING SPEC-0000012 FOR OVERHEAD CT INSTALLATION REQUIREMENTS.10. THE SERVICE ENTRANCE BREAKER/FUSED DISCONNECT CURRENT RATING MUST MATCH TRANSFER SWITCH CURRENT RATINGS IF SERVICE

ENTRANCE RATED BREAKER/FUSED DISCONNECT IS REQUIRED.

OVERHEAD SERVICE, SEE NOTE 9

CT CAN

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

OH 600A STANDBYGENERATOR, COMPLETE SERVICE

AUTOMATIC TRANSFER SWITCHSPEC-0000028 12.08.2017 NTS

JDC 0 N/A

Page 58: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 59: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

MEMBER INSTALLED GROUND WIRE,

SECURED TO MOUNTING STRUCTURE,

5/8" X8'-0" COPPER-CLAD GROUND ROD

INSTALLED FLUSH OR SLIGHTLY BELOW

GRADE, AND CLAMP REQUIRED. REFER

TO NEC FOR GROUND WIRE SIZE.

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECCREQUIREMENTS ONLY, AND IS NOT

INTENDED TO BE A COMPREHENSIVEGUIDE FOR THE INSTALLATION OF ANELECTRICAL SERVICE. TO INSURE ASAFE, QUALITY INSTALLATION THAT

COMPLIES WITH THE NATIONALELECTRICAL CODE, AND LOCAL CODEREQUIREMENTS; THE COOPERATIVERECOMMENDS THAT ALL WORK BEDONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

METERBASE

5'-0" MIN.

6'-0" MAX.

SCHEDULE 40 PVC, 1"

CONDUIT TO AVECC

TRANSFORMER. 20'0" MAX.

SEE NOTE 8.

NOTES1. AVECC RECOMMENDS THAT A LICENSED ELECTRICIAN INSTALLS TRANSFER SWITCH AND GENERATOR PER NEC CODE AND LOCAL ORDINANCES.2. MULTIPLE CIRCUIT BREAKERS/FUSED DISCONNECTS CAN BE CONNECTED AFTER THE TRANSFER SWITCH, SO LONG AS THE SUM OF THE BREAKER

INTERRUPTING CURRENT OF EACH BREAKER/FUSED DISCONNECT DOES NOT EXCEED THE AUTOMATIC TRANSFER SWITCH RATING OR THEELECTRIC SERVICE SIZE.

3. REFER TO DRAWINGS SPEC-000001 THROUGH SPEC-0000017 FOR INCOMING SERVICE REQUIREMENTS, AVECC SUPPLIED EQUIPMENT & SERVICES,MEMBER REQUIRED EQUIPMENT & SERVICES, DITCH REQUIREMENTS, ETC.

4. WHERE PANELS AND EQUIPMENT ARE NOT MOUNTED ON BUILDING STRUCTURE, REFER TO DRAWINGS SPEC-0000011 & SPEC-0000012 FOR RACKMATERIAL AND INSTALLATION REQUIREMENTS. ALLOW ADEQUATE ROOM ON RACK FOR ALL EQUIPMENT/PANELS NECESSARY.

5. ALL EXTERIOR PANELS ARE TO BE RATED NO LESS THAN NEMA 3R.6. PROTECTIVE BUSHINGS REQUIRED ON ALL CONDUITS.7. NO WIRING GUTTERS OR TROUGHS WILL BE ALLOWED ON THE OUTSIDE OF THE BUILDING.8. REFER TO DRAWING SPEC-0000017 FOR PAD MOUNT TRANSFORMER/CT INSTALLATION REQUIREMENTS.9. REFER TO DRAWING SPEC-0000017 FOR INCOMING SERVICE REQUIREMENTS FROM PAD MOUNT TRANSFORMER.

AUTOMATICTRANSFER

SWITCH

CB

6" SPACE BETWEEN BOXES

REQUIRED.

SERVICE ENTRANCE RATED CIRCUIT BREAKER

OR FUSED DISCONNECT WITH OVER CURRENT

PROTECTION SIZED APPROPRIATELY FOR FULL

SERVICE LOAD.

CB

SEE NOTE 2

CONDUIT & WIRE TO PERMANENTGENERATOR. INSTALL PER NECCODE AND MANUFACTURER'S

RECOMMENDATIONS/MANUALS.NOTE: NEUTRAL IS ISOLATEDFROM THE GROUND AT THE

GENERATOR.

600ACBOR

LARGER

SEE NOTE 9

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

UG 600A & LARGER STANDBYGENERATOR, PARTIAL SERVICE

AUTOMATIC TRANSFER SWITCHSPEC-0000029 12.08.2017 NTS

JDC 0 N/A

Page 60: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.

Page 61: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

MEMBER INSTALLED GROUND WIRE,

SECURED TO MOUNTING STRUCTURE,

5/8" X8'-0" COPPER-CLAD GROUND ROD

INSTALLED FLUSH OR SLIGHTLY BELOW

GRADE, AND CLAMP REQUIRED. REFER

TO NEC FOR GROUND WIRE SIZE.

MAKE AN ARKANSAS ONE CALL48 HOURS BEFORE YOU DIG

DIAL 1-800-482-8998IT SHALL BE A MEMBER'S

RESPONSIBILITY TO STAY CLEAROF ALL UNDERGROUND FACILITIES

NOTICETHIS DRAWING ILLUSTRATES AVECCREQUIREMENTS ONLY, AND IS NOT

INTENDED TO BE A COMPREHENSIVEGUIDE FOR THE INSTALLATION OF ANELECTRICAL SERVICE. TO INSURE ASAFE, QUALITY INSTALLATION THAT

COMPLIES WITH THE NATIONALELECTRICAL CODE, AND LOCAL CODEREQUIREMENTS; THE COOPERATIVERECOMMENDS THAT ALL WORK BEDONE BY A QUALIFIED, LICENSED

ELECTRICAL CONTRACTOR.

METERBASE

5'-0" MIN.

6'-0" MAX.

NOTES1. AVECC RECOMMENDS THAT A LICENSED ELECTRICIAN INSTALLS TRANSFER SWITCH AND GENERATOR PER NEC CODE AND LOCAL ORDINANCES.2. MULTIPLE CIRCUIT BREAKERS/FUSED DISCONNECTS CAN BE CONNECTED AFTER THE TRANSFER SWITCH, SO LONG AS THE SUM OF THE BREAKER

INTERRUPTING CURRENT OF EACH BREAKER/FUSED DISCONNECT DOES NOT EXCEED THE AUTOMATIC TRANSFER SWITCH RATING OR THEELECTRIC SERVICE SIZE.

3. REFER TO DRAWINGS SPEC-000001 THROUGH SPEC-0000017 FOR INCOMING SERVICE REQUIREMENTS, AVECC SUPPLIED EQUIPMENT & SERVICES,MEMBER REQUIRED EQUIPMENT & SERVICES, DITCH REQUIREMENTS, ETC.

4. WHERE PANELS AND EQUIPMENT ARE NOT MOUNTED ON BUILDING STRUCTURE, REFER TO DRAWINGS SPEC-0000011 & SPEC-0000012 FOR RACKMATERIAL AND INSTALLATION REQUIREMENTS. ALLOW ADEQUATE ROOM ON RACK FOR ALL EQUIPMENT/PANELS NECESSARY.

5. ALL EXTERIOR PANELS ARE TO BE RATED NO LESS THAN NEMA 3R.6. PROTECTIVE BUSHINGS REQUIRED ON ALL CONDUITS.7. NO WIRING GUTTERS OR TROUGHS WILL BE ALLOWED ON THE OUTSIDE OF THE BUILDING.8. REFER TO DRAWING SPEC-0000012 FOR OVERHEAD CT INSTALLATION REQUIREMENTS.

OVERHEAD SERVICE, SEE NOTE 9

CT CAN

AUTOMATICTRANSFER

SWITCH

CB

6" SPACE BETWEEN BOXES

REQUIRED.

CB

SEE NOTE 2

CONDUIT & WIRE TO PERMANENTGENERATOR. INSTALL PER NECCODE AND MANUFACTURER'S

RECOMMENDATIONS/MANUALS.NOTE: NEUTRAL IS ISOLATEDFROM THE GROUND AT THE

GENERATOR.

600ACB

SERVICE ENTRANCE RATED CIRCUIT BREAKER

OR FUSED DISCONNECT WITH OVER CURRENT

PROTECTION SIZED APPROPRIATELY FOR FULL

SERVICE LOAD.

TITLE

ARKANSAS VALLEY ELECTRICCOOPERATIVE COOPERATION

DRAWN BY: REV. DATE:REV:DWG#: SCALE:DATE:

OZARK 1-800-468-2176 : WALDRON 1-800-468-2152 : POCOLA 1-800-468-2419 : VAN BUREN 1-800-486-9910

OH 600A STANDBYGENERATOR, PARTIAL SERVICE

AUTOMATIC TRANSFER SWITCHSPEC-0000030 12.08.2017 NTS

JDC 0 N/A

Page 62: ARKANSAS VALLEY ELECTRIC COOPERATIVE CORPORATION

ARKANSAS VALLEY ELECTRICCOOPERATIVE CORPORATION1811 WEST COMMERCIAL - P.O. BOX 47

TELEPHONE (479) 667-2176OZARK, ARKANSAS 72949

CONSTRUCTION COSTS FOR TYPICAL JOBS1. SINGLE PHASE OVERHEAD LINE EXTENSION: FOR QUALIFYING STRUCTURE

A. FIRST 1,320 WITHOUT CHARGE.B. $5.84 PER FOOT BEYOND 1,320 FEET.

A. EXAMPLE: LINE EXTENSIONS, ETC.B. SINGLE PHASE OVERHEAD, FIRST 1320 FEET IS INCLUDED IN LINE EXTENSION.C. THREE PHASE OVERHEAD, COST IS NOT INCLUDED IN THE LINE EXTENSION. MEMBER

RESPONSIBLE FOR THREE PHASE RIGHT-OF-WAY COST.

2. RIGHT-OF-WAY BASED ON $8.40 PER FOOT: FOR QUALIFYING STRUCTURES

A. $9.14 PER FOOT FOR BOTH CONVERSION AND NEW LINE EXTENSIONS.3. THREE PHASE OVERHEAD LINE EXTENSION

A. $7.46 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.4. SINGLE PHASE PRIMARY UNDERGROUND EXTENSION

A. $17.40 PER FOOT; MEMBER REQUIRED TO OPEN & CLOSE DITCH.5. THREE PHASE PRIMARY UNDERGROUND EXTENSION

CONTACT ARKANSAS VALLEY ELECTRIC COOPERATIVE COOPERATION FOR PRICING.8. LIGHT POLES:

A. BASED ON PER WORK ORDER BASIS (POOLS, MEMBER REQUEST , ETC.)B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

6. UNDERGROUND SERVICE LINE RELOCATES:

A. $7.40 PER FOOT; FIRST 100 FEET FREE FOR QUALIFYING STRUCTURES.B. MEMBER REQUIRED TO OPEN & CLOSE DITCH.

7. SINGLE PHASE UNDERGROUND SERVICE (OVER 100 FEET):

PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE.

DRAWN BY: J.CALLOWAY REVISION#: 1DATE: 02.22.2018 DOC#: DOCS-0000002

NOTE: QUALIFYING STRUCTURE IS A PERMANENT LIVING QUARTERS THAT IS AT LEAST 400 SQUARE FOOTIN SIZE WITH PRESSURIZED RUNNING WATER AND A SEPTIC SYSTEM.