PRE-FIN. S.M.FASCIA ON CONT.S.M. CLEATS
3/16"x1" PRE-FIN.GALV. BRACKETSAT 3'-0" O.C.
PRE-FIN. S.M. FASCIA
PRE-FIN. S.M. DRIPEDGE ON CONT.S.M. CLEATS
ROOF ASSEMBLY TYPE 'B'
(2) P.T. 2x8 WOOD BLOCKINGCONT. WITH COUNTERSUNK 1/2"ØBOLTS AT 2'-0" O.C.
STL. ANGLE OR BENT PLATE,REFER TO STRUCT. ANCHOR STL.ANGLE TO P.T. WOOD BLOCKINGWITH 1/2"Ø BOLTS AT 2 '-0" O.C.
5"x5" PRE-FIN. S.M.DOWNSPOUT (7"x7" @KITCHEN - REFER TOROOF PLAN).
ROOF MEMBRANE, INSTALL PERROOF MANUFACTURER, EXTENDDOWN OVER WOOD BLOCKING
SLOPE
1"
8" @
KIT
CHEN
& G
YM
5" T
YP.
2"
FILL VOIDS WITH BATT INSULATION
CAVITY VENTS AT 48" O.C.
8" @ KITCHEN & GYM6" TYP.1/2"
T.O. MASONRY132' - 0"
BOND BEAM, REFERTO STRUCT.
ROOF ASSEMBLYTYPE "A"
FULLY ADHERED MEMBRANEWALL FLASHING, EXTEND UPAND OVER F.O. PARAPETBLKG. PROVIDE ANCHORAGEPER ROOF MFR
FACE BRICK
CAVITY VENTS @ 48" O.C.
STL. JOIST, REFER TOSTRUCT.
FIBER CANT, TYP.
4 1/8" 4"
SLOPE.
BOND BEAM, REFERTO STRUCT.REFER TO
PLANS
JOIST BRG VARIES
REFER TO STRUCT
CONT. LADDER TYPE HORIZ.REINF. @ 16" O.C. VERT., 8"O.C. VERT. @ PARAPET
A4.23
P.T. WD. BLKG. CONT. TYP.LOOSE-FILL PERLITEINSULATION @ ALL OPENCELLS, FULL HEIGHT OFPARAPET TO NEARESTCOURSE BELOW ROOF DECK
VARI
ES -
REFE
R TO
STR
UCT.
1"
MIN4"
6"1"
1"5"
1/2" 6"
2 1/8"
10 3/16"
PARAPET WALL THICKNESSREFER TO FLOOR PLANS FOR WALL TYPES
4"
MIN
.1"
MIN
.1"
3 1/
2"
1/2"
LOOSE-FILL PERLITEINSULATION @ ALL OPENCELLS, FULL HEIGHT OFPARAPET TO NEARESTCOURSE BELOW ROOFDECK
A4.23
STEEL ANGLE ANCHORED TOCMU, GROUT CMU SOLID.REFER TO STRUCT.
ROOF ASSEMBLY TYPE 'A'
J-CLOSURE
POP RIVET 12" O.C.
ONE CONT. ROW OFBUTYL TAPE
PRE-FIN. S.M. FLASHING,CONT.
T.O.M.
VARIES - REFER TO
5/8" EXT. MAT-FACED GYP. BD.ON 6" MTL. STUDS @ 16" O.C.CONT. WITH BATT INSUL.
1' - 0
"
2X P.T. WD. BLKG. CONT.TYP.
CONT. LADDER TYPEHORIZ. REINF. @ 16" O.C.VERT., 8" O.C. VERT. @PARAPET
T.O. MASONRYVARIES - REFER TO ROOF PLAN
STEEL ANGLEANCHORED TO CMU.GROUT CMU SOLID.REFER TO STRUCT.
8" OR 12" NOM. CONC. BONDBEAM, REFER TO STRUCT.
ROOF ASSEMBLY TYPE "A"
CONT. LADDER TYPE HORIZ.REINF. @ 16" O.C., VERT., 8"O.C. VERT. @ PARAPET
FULLY ADHERED MEMBRANE WALLFLASHING, EXTEND UP AND OVERF.O. PARAPET BLKG. PROVIDEANCHORAGE PER ROOF MFR
FACE BRICK
CAVITY VENTS @ 48" O.C.
REFER TO DETAIL 5/A4.2FOR TYPICAL NOTES
LOOSE-FILL PERLITEINSULATION @ ALL OPENCELLS, FULL HEIGHT OFPARAPET TO NEARESTCOURSE BELOW ROOFDECK
*REFER TO PLANS
A4.23
2X P.T. WD. BLKG.CONT. TYP.
JOIST BRG.
117' - 4"
CONT. LADDER TYPE HORIZ. REINF. @ 16" O.C.,VERT., 8" O.C. VERT. @ PARAPET
ROOF ASSEMBLYTYPE 'B'
BOND BEAM, CONT.,REFER TO STRUCT.
STL. JOIST, REFER TOSTRUCT.
3/4" EXT. GRADEPLYWOOD ON 1 1/2" RIGIDINSUL. ON 1 1/2" MTL. "Z"FURRING @ 16" O.C.
STEEL ANGLE, REFER TOSTRUCT., GROUT CMU SOLID.PAINT EXPOSED STEEL
FULLY ADHERED MEMBRANE WALL FLASHING,PROVIDE ANCHORAGE PER ROOF MFR
4"4"
S.M. FLASHING W/ 2 PIECE REMOVABLE COUNTERFLASHING - COMPRESSION FIT W/ LOCKING TABS,HEM EDGE, EXTEND UNDER STEEL ANGLE
4" FIBER CANT TYP
SLOPE.
SELF ADHERED THRU-WALL MASONRYFLASHING WITH TERMINATION BAR ANDSEALANT EXTEND 1/2" BEYOND FACE OFBRICK. TRIM OFF EXCESS AS DIRECTEDBY ARCHITECT.
MORTAR NET CONT.
CAVITY VENTS @ 48"O.C. INSTALL ABOVEMORTAR NET AND 8" MIN. ABOVE FLASHING.
COTTON ROPE WEEPS @ 24" O.C.
B
TERMINATION BAR ANDSEALANT, CONT.
B.O. ANGLE119' - 4"
2
8" M
IN.
B
2
ROOF ASSEMBLYTYPE 'C'
12" NOM. BONDBEAM CONT.REFER TOSTRUCT.
LADDER TYPEHORIZ. REINF.@ 16" O.C.
PRE-FIN. VENTED MTL.SOFFIT PANEL
SEAL VOID AIRTIGHT
FILL VOID W/ INSUL.
STEEL OUTRIGGER,REFER TO STRUCT.
MTL. Z-CLOSURE PER MTL.WALL PANEL MFR.
PRE-FIN. S.M. WALL PANEL ON2 1/2" ZEE FURRING @ 4'-0" O.C. CUT CMU AS
REQ'D
D1' - 7 5/8"
ROOF ASSEMBLYTYPE 'C'
12" NOM. BONDBEAM CONT.REFER TOSTRUCT.
LADDER TYPEHORIZ. REINF.@ 16" O.C.
PRE-FIN. VENTED MTL.SOFFIT PANEL
SEAL VOID AIRTIGHT
FILL VOID W/ INSUL.
STEEL OUTRIGGER,REFER TO STRUCT.
MTL. Z-CLOSURE PER MTL.WALL PANEL MFR.
CUT CMU ASREQ'D
D1' - 7 5/8"
12" NOM. CMU BOND BEAM,REFER TO STRUCT.
ROOF ASSEMBLYTYPE "B"
FULLY ADHERED MEMBRANEWALL FLASHING, EXTEND UPAND OVER F.O. PARAPETBLKG. PROVIDE ANCHORAGEPER ROOF MFR
CAVITY VENTS @ 48" O.C.
STL. JOIST, REFER TOSTRUCT.
FIBER CANT TYP
3 7/8" 4"
SLOPE.
12" NOM. CMU BOND BEAM,REFER TO STRUCT.
JOIST BRG.111' - 4"
A4.23
CONT. LADDER TYPE HORIZ.REINF. @ 16" O.C. VERT., 8"O.C. VERT. @ PARAPET
LOOSE-FILL PERLITEINSULATION @ ALL OPENCELLS, FULL HEIGHT OFPARAPET TO NEARESTCOURSE BELOW ROOF DECK
P.T. WD. BLKG. CONT.
PRE-FIN. ALUM.WALKWAY COVER
T.O.M.113' - 8"
CUT CMU AS REQ'D
REFERTO
PLAN
8"
4'-0" UNLESS NOTED OTHERWISE ON ROOF PLAN
UNLE
SS N
OTED
OTHE
RWIS
E ON
ELEV
ATIO
NS
GROUT CMUSOLID
PRE-FIN. S.M.DRIP EDGE ONCONT. S.M.CLEATS. MATCHCOLOR OF MTL.PANEL, TYP.
PRE-FIN. S.M.GUTTER WITHSPACERS AT3'-0" O.C.
3/16"x1" PAINTEDGALV. BRACKETSAT 3'-0" O.C.
5"x5" PRE-FIN. S.M.DOWNSPOUT U.N.O.
1"5"
ROOF ASSEMBLY TYPE 'C'
6"
PRE-FIN. METAL FASCIAWRAP WITH DRIP,MATCH COLOR OFMETAL PANEL, TYP.
P.T. 2x10 WOODBLOCKINGCONT. (CUT ASREQ'D) WITHCOUNTERSUNK1/2"Ø BOLTS AT2'-0" O.C.
CONT. BENT STL.PLATE, REFER TOSTRUCT. DWGS.
P.T. 2x WOODBLOCKING, CONT.
1/2"(2) LAYERS EXT.3/4" PLYWOODSHEATHING,CONT.
PRE-FIN.VENTED MTL.SOFFIT PANEL
SEALANT, CONT.
1"
3 1/
8"
ICE/WATER SHIELDUNDERLAYMENT, EXTENDUP EAVE 3'-0" MIN. ANDEXTEND OVER FACE OFP.T. WOOD BLOCKING
1' - 4
1/2
"
1"
COPYRIGHT © 2015SHERMAN / CARTER /BARNHART, PSC
JOB NO.
DATE
DRAWN
CHECKED
REVISIONS
SHEET
DE
SIG
N D
EV
ELO
PM
EN
T
3/20
/20
15 9
:40
:14
AM
A4.2
NEH, BB, FS
MAR. 2, 2015
1460
KC
BU
ILD
ING
SE
CTI
ON
S A
ND
DE
TAIL
S
HA
ZEL
GR
EE
N E
LEM
EN
TAR
YS
CH
OO
L25
15 K
EN
TU
CK
Y 1
394
EA
ST
BE
RN
ST
AD
T, K
Y 4
0729
1460
HA
ZE
L G
RE
EN
ELE
ME
NT
AR
Y S
CH
OO
L
3" = 1'-0"2 ROOF DETAIL
1 1/2" = 1'-0"6 ROOF DETAIL
3" = 1'-0"1 ROOF DETAIL
3" = 1'-0"3 TYPICAL COPING DETAIL
1 1/2" = 1'-0"7 ROOF DETAIL
1 1/2" = 1'-0"5 ROOF DETAIL
1 1/2" = 1'-0"12 ROOF DETAIL
1 1/2" = 1'-0"13 ROOF DETAIL
1 1/2" = 1'-0"19 ROOF DETAIL
1 1/2" = 1'-0"20 ROOF DETAIL
1 1/2" = 1'-0"21 ROOF DETAIL
1 1/2" = 1'-0"4 TYPICAL CANOPY DETAIL
3" = 1'-0"11 TYPICAL GUTTER DETAIL @ OVERHANG