9360 Sunset Drive STE 220 | Miami, FL 33173 | T: 305.264.8100 | F: 305.262.6978 | www.afceng.com | [email protected]
April 19, 2018 Product Approval Administrator Building Codes & Standards Section Department of Business & Professional Regulations 1940 North Monroe Street, Suite 90 Tallahassee, FL 32399-2100 Ref: Schuco USA LLLP
Series “AWS 65/70/75/90” Tilt & Turn/Fixed Window System - (L.M.I.) Certificate of Independence
Dear Sirs,
As the design engineer retained by Schuco USA LLLP on the product referenced above, I do hereby declare that I do not have and will not have any financial interest in any company manufacturing or distributing the above referenced product, nor do I have or will have any financial interest with any other entity involved in the approval process of the product.
Sincerely,
Javad Ahmad, P.E. Director of Engineering
Sealed 4/19/18
FL 26978
Detailed Product Description: Date: 04/17/18
Manufacturer: SCHUCO USA , LLLP
Manufacturer Address: 240 PANE ROAD NEWINGTON, CT 06111
Model Name: SERIES “AWS 65/70.HI/75.SI+/90.SI+” TILT TURN & FIXED WINDOW SYSTEM
Maximum Frame Width: 96"
Maximum Frame Height: 72”
Maximum Load: +70PSF, -70 PSF (Large Missile Impact)
Installation Drawings # W18-42
Test Description Test Location Test Report Date Test Report # Test Sealed By
4/17/2018 H9301.01-250-18 Vinu Abraham, P.E.
4/17/2018 H9301.01-250-18 Vinu Abraham, P.E.
4/17/2018 H9301.01-250-18 Vinu Abraham, P.E.
4/17/2018 H9301.01-250-18 Vinu Abraham, P.E.
Test Description Test Location Test Report Date Test Report# Test Sealed By
FBC 1626.2
(TAS 201 & 203)
Large Missile
Impact & CyclicIntertek 4/17/2018 H9301.01-250-18 Vinu Abraham, P.E.
Evaluation Report Engineer:
PE # 70592
EB # 3538
PRODUCT APPROVAL EVALUATION
RULE CHAPTER #61G20-3 • METHOD 1 OPTION D
This product complies with the High Velocity Hurricane Zone (HVHZ) testing requirements.
Comparative analysis used _X Yes No
Mandatory Tests (Tested in accordance with AAMA 101/I.S.2/NAFS/TAS-202)
The above maximum parameters do not occur simultaneously.
See charts on installation drawings for combinations of span vs. load.
ASTM E283Air Infiltration
LeakageIntertek
ASTM E331 OR
ASTM 547 & TAS
202
Water
PenetrationIntertek
ASTM E330 & TAS
202Uniform Static Air
Press.Intertek
ASTM F588 Forced Entry Test Intertek
Supplemental Tests (Tested in accordance with TAS-201 and TAS-203)
Under the limitations of the attached installation drawings, to the best of my knowledge and ability, the above product
conforms to the requirements of the 2017 Florida Building Code.
Javad Ahmad
Al-Farooq Corporation
9360 Sunset Drive STE 220 | Miami, FL 33173 | T: 305.264.8100 | F: 305.262.6978 | www.afceng.com | [email protected]
Sealed 4/20/18
Sealed 5/2/18
Sealed 5/2/18
Sealed 5/2/18
Sealed 5/2/18
Sealed 5/2/18
Sealed 5/2/18
Sealed 5/2/18
Sealed 5/2/18