Apricus CoolSky Installation Manual

Embed Size (px)

Citation preview

  • 7/31/2019 Apricus CoolSky Installation Manual

    1/68

    CoolSky Ltd 42 Milecross Road, Newtownards BT23 4SRTel: +44 (0)28 9182 9470

    Email: [email protected]

    Company Registration No. NI072166

    VAT No. GB 108838970

    Copyright 2012 CoolSky

  • 7/31/2019 Apricus CoolSky Installation Manual

    2/68

    Apricus Installation Manual

    2

    TABLE OF CONTENTS

    Solar Thermal Introduction 3

    Technical Specification of The Apricus Collector Range 6

    Solar Pumping Station 9Pump Sizing 10

    Solar Expansion Vessels 11

    Sizing and Designing your Solar System 18

    System Sizing 19

    Sizing the Solar Cylinder 21

    Pipe Type and Size 21

    Stagnation & Overheating 22

    Connection of Multiple Collectors 25

    Balancing Flow through Collectors 25

    Wind & Structural Loading 26

    Back-Up Heating Source 29

    Anti-Scald / Tempering Valves 29

    Closed Loop Max Incoming Pressure 29

    Maximum Allowable Pressure 29

    Electrical Supply 30

    Labelling 30

    Building Considerations 31Health & Safety Considerations 32

    Installation Guidelines 34

    Manifold and Bottom Support Track Assembly 35

    Other System Components 37

    Collector Installation 38

    Connection to Plumbing 44

    Insulation 44

    Installation of the Tubes 46

    Commissioning The System 50

    Post Installation 52

    Clean Up 52

    Maintenance & Repair 53

    Maintenance Schedule 55

    Troubleshooting Guide : 56

    Home-Owner Maintenance 60

    Glossary of Terms 63

    Important Information 64

  • 7/31/2019 Apricus CoolSky Installation Manual

    3/68

    Solar Thermal Introduction

    Introduction

    CoolSky Ltd. are distributors in the U.K. and

    Ireland for the Apricus range of Evacuated

    Tube Solar Thermal Collectors. Since theirformation in 2002, Apricus have quickly

    established themselves as a global company

    with offices in USA, France and Australia with

    sales in over 30 countries worldwide.

    Apricus have a modern manufacturing facility

    that includes a 6,500 m2 factory floor,

    administration offices and an R&D Centre.

    Apricus Collectors conform to the European

    Standard EN12975 and carry the European

    SolarKeymark Certification (Licence No. 011-

    7S161R) as a mark of their quality, reliability

    and performance.

    SolarKeymark is considered to be equivalent

    to MCS Product Certification thereby

    qualifying the products for financial

    assistance under various funded schemes

    where available.

    All Apricus collectors, components and

    packaging have been carefully designed so

    that they can be efficiently recycled at end-

    of-life.

    Solar Energy

    Solar Energy is the planets most abundant

    source of energy with the added benefit that

    it is both clean and free.

    (Source : EU Commission Joint Research Centre)

    Whilst the UK and Ireland are considered to

    have mild and temperate climates there are

    parts of the UK that can receive annualradiation levels equivalent to 65% of the

    radiation that is received in places like

    Madrid, Spain, making both the UK and

    Ireland suitable locations for Evacuated Tube

    Solar Thermal Collectors.

    The Apricus Evacuated Tube Solar Collector

    provides an efficient solution for the capture

    of Solar Radiation and is ideal for use in UK

    and Irish climatic conditions. Although the

    peak solar radiation period in the UK and

    Ireland is in the months from May through

    to August, the Apricus Evacuated Tube Solar

    Collectors are highly efficient and able to

    harness the energy of the sun throughout

    the year and to also provide a useful

    contribution to heating during the off-peak

    months.

  • 7/31/2019 Apricus CoolSky Installation Manual

    4/68

    Apricus Installation Manual

    4

    Evacuated Tube Solar Thermal Collectors are

    able to capture the available Solar Energy

    and then transfer it as Thermal Energy to the

    water heating system, thereby raising the

    temperature in the hot water storage

    cylinder, and offsetting the reliance to on

    alternative fuels (such as coal, gas, oil or

    electric) to provide hot water. Up to 70% of

    the domestic hot water requirements can be

    met by the Apricus Solar Collectors.

    Since solar radiation levels depend uponboth the season and the daily weather

    conditions it is always necessary to

    incorporate a back-up water heater (typically

    standard fossil fuel boilers or electric

    immersion heaters) to ensure there is a

    sufficient supply of hot water all year round.

    Key Components of the Solar

    Thermal System

    Solar Energy is collected when the sunlight

    strikes the black selective absorber contained

    inside the evacuated tubes of the Solar

    Collector.

    Each tube contains a copper heat-pipe that

    is in contact with the absorber. The heat-

    pipe contains a small quantity of water

    under a vacuum environment that allows thewater to start boiling at temperatures as low

    as 30C. The water vapour generated when

    boiling rapidly rises to the top of the heat

    pipe where it condenses and transfers its

    thermal energy to the condenser and into

    the copper header pipe within the manifold.

    Fig. 2 Schematic showing the basic layout of a simple solar thermal

    system.

    The condensed fluid then flows back down

    the heat pipe and is re-heated, thereby

    restarting the thermal cycle again.

    A circulating pump moves the heat transfer

    fluid (a propylene-glycol anti-freeze mixture)

    through the copper header pipe within the

    manifold and back to the storage cylinder. A

    solar heat exchanger coil within the storage

    cylinder transfers the thermal energy from

    the heat transfer fluid into the water within

    the storage cylinder. The cooled fluid then

    returns to the collector manifold to be re-

    heated.

    The operation of the solar loop is controlled

    with a temperature differential electronic

    controller. This ensures that solar fluid is

    only circulated in the solar loop when there

    is useful energy to transfer from the

    collector into the storage cylinder.

    Back-up heating using a conventional fossil

    fuel boiler or electrical immersion should

    also be provided for periods when solar

    radiation is unable to meet the total hot

    water demand.

  • 7/31/2019 Apricus CoolSky Installation Manual

    5/68

    5

    Apricus Collectors

    The Apricus Collectors are available in 3

    Standard Models as follows :

    APSE-10 10 Tubes

    APSE-20 20 Tubes

    APSE-30 30 Tubes

    All the Apricus Collectors are certified to the

    European SolarKeymark Scheme thereby

    ensuring the installer and end-user of the

    highest standards and quality in materials

    and manufacturing, which also qualifies the

    collectors for government funded schemes

    requiring MCS Certification.

    The Apricus Solar Tube consists of a circular

    inner absorber tube that is coated with a

    selective absorber layer of Al/N on Al. This

    selective absorber provides each tube with a

    highly selective radiation absorbing surface,

    with typical absorption efficiencies of >92%.

    The absorber tube is encased within a strong

    borosilicate glass enclosure that is then

    placed under ultra-high vacuum conditions

    to ensure the ultimate performance in terms

    of thermal insulation.

    A getter coating at the bottom of the tube is

    used to maintain the ultra-high vacuum level

    within the tube throughout its operational

    lifetime and to ensure maximum collector

    efficiency is achieved.

    Apricus tubes have a round absorber surface

    within the tube, and hence, irradiation from

    the sun always strikes the absorber surface

    in a perpendicular direction. This ensures

    optimum collector performance whatever the

    time of day, morning, mid-day or afternoon.

    This is reflected in the excellent IAM

    (Incident Angle Modifier) figures for the

    Apricus Collectors which makes them the

    ideal choice of collector for the typical UK

    and Irish weather conditions where peak

    solar radiation is not guaranteed to be atmid-day.

  • 7/31/2019 Apricus CoolSky Installation Manual

    6/68

    Apricus Installation Manual

    6

    Technical Specification of The

    Apricus Collector Range

    Model : APRICUS APSE-10Aperture Area : 0.94 m2

    Gross Area : 1.56 m2

    Weight (Dry) : 35kg

    Fluid Capacity : 0.2litres

    Max Pressure : 8 bar

    Stagnation Temp: 219C

    Absorption : 92%

    Emission : 8%

    Width x Length : 796 x 2005 mm

    Height : 156 mm

    Performance Figures :

    0 62.6 %

    a1 1.595

    a2 0.013

    Model : APRICUS APSE-20

    Aperture Area : 1.88 m2

    Gross Area : 2.96 m2

    Weight (Dry) : 64 kg

    Fluid Capacity : 0.52 litres

    Max Pressure : 8 bar

    Stagnation Temp : 219C

    Absorption : 92%

    Emission : 8%

    Width x Length : 1496 x 2005 mm

    Height : 156 mm

    Performance Figures :

    0 62.6 %

    a1 1.595

    a2 0.013

    Model : APRICUS APSE-30Aperture Area : 2.82 m2

    Gross Area : 4.35 m2

    Weight (Dry) : 95 kg

    Fluid Capacity : 0.71 litres

    Max Pressure : 8 bar

    Stagnation Temp : 219C

    Absorption : 92%

    Emission : 8%

    Width x Length : 2196 x 2005 mm

    Height : 156 mm

    Performance Figures :

    0 68.7 %

    a1 1.505

    a2 0.011

    Key Features

    Manifold :

    Material : Anodised Aluminium

    Insulation :

    Material : 50mm Glass Wool

    Conductivity : 0.043 W/mK

    Tubes :

    Glass : 1.8mm Thick Borosilicate

    Absorber : Al-N on Al

    Rubber Components :

    Material : HTV (UV Stable) Silicone

    Max Temp. : 300 C

  • 7/31/2019 Apricus CoolSky Installation Manual

    7/68

    7

    Storage Cylinders

    Both copper and stainless steel storage

    cylinders are available from CoolSky. These

    cylinders are specially designed and

    optimised for Solar Systems, comply with UK

    regulations, and are fully compatible with the

    Apricus Solar Collectors. Options are

    available for both vented and unvented

    systems.

    As an added service we are also able to

    provide cylinders that are designed and

    manufactured to bespoke requirements.

    Vented Solar Cylinders

    The Standard Easy-Fit Vented Copper

    Cylinders are available in either twin coil or

    triple coil configurations and are specifically

    designed to work in conjunction with the

    domestic heating system.

    One or two coils are designed to transfer

    heat from an independent heating source,

    (eg. transferring heat from a central heating

    boiler or solid fuel boiler to the water in the

    solar cylinder) and the solar coil, which is

    manufactured from high efficiency finned

    tubes with a large surface area, to transfer

    heat from the solar panels into the solar hot

    water cylinder with maximum efficiency.

    We are also able to supply custom sizes

    upon request giving you total flexibility in

    the design of your complete system. In

    general, solar cylinders are sized to suit the

    number of occupants and the solar thermal

    panel surface area.

    Nominal Diameters :400 mm Only Twin Coil Available

    450 mm Twin or Triple Coil

    500 mm Twin or Triple Coil

    600 mm Twin or Triple Coil

    Nominal Heights :

    1050 mm, 1200 mm, 1300 mm

    1400 mm & 1800 mm

    Unvented Solar Cylinders

    The Standard Easy-Fit Unvented Stainless

    Steel Cylinders are available in a twin coil

  • 7/31/2019 Apricus CoolSky Installation Manual

    8/68

    Apricus Installation Manual

    8

    configuration and are specifically designed

    to work in conjunction with the domestic

    heating system.

    Manufactured from Duplex Stainless Steel,

    these cylinders provide fast reheat and

    recovery and high value insulation. In

    addition, for installers they are also light and

    easy to handle

    Standard Features:

    Duplex Stainless Steel

    25 Year Guarantee

    Fast Reheat/Recovery

    High Value Insulation

    Nominal Diameter :

    545 mm Only Twin Coil Available

    Nominal Heights :

    1102 mm, 1290 mm, 1478 mm,

    1782 mm, 2041 mm

    Pressure & Temperature Relief

    Valve (PTRV)

    The storage tank must be fitted with a PTRV.

    All tanks should be supplied as standard

    with an approved valve.

    Building Regulations

    The installation of unvented hot water

    cylinder for domestic applications is

    regulated under Building Regulation G3 for

    England and Wales, Technical Standard P3

    for Scotland, Building Regulation P5 for

    Northern Ireland and Technical Guidance

    Document L for the Republic of Ireland. All

    local, relevant and up-to-date regulations

    must be adhered to by the installer. An

    example schematic safety control layout for

    a solar installation to comply with Building

    Regulation G3 (England and Wales) is givenin the CIBSE Solar Heating Design and

    Installation Guide.

    Cool Tip

    Rule of Thumb for sizing storage

    cylinder in domestic installations:

    100 litres per m2

    Aperture Area of Collector

  • 7/31/2019 Apricus CoolSky Installation Manual

    9/68

    9

    Solar Pumping Station

    A Pumping Station is required in the Solar

    Loop for the circulation of propylene glycolheat transfer fluid around the solar loop.

    The Pumping Stations are provided with the

    following key features :

    1. Flowmeter, flow rate regulation and

    graduated scale regulation gauge 2-12

    litre/min.

    2. Isolation valves for filling/flushing of the

    unit. Connections "M with safety chain

    and tap.

    3. Circulating Pump - WILO solar STAR

    ST15-6ECO, connections 1"BSP - 130mm

    class. TF110, VDE, CE.

    4. Return side isolation valve DN20, with

    integrated bracket. Connection "M

    always open on one side.

    5. Integrated high temperature check

    valves. Closure at 90 and opening at

    45. Check valve opening 2kPa (200mm

    c.a.)

    6. Pressure gauge with integrated safety

    relief valve (typ. 6Bar) with discharge

    connection point for isolation valve and

    expansion vessel.

    7. Air stop device with manual integrated

    vent.

    Model Variations :

    The CoolSky range of Pumping Stations areavailable with either Flat Face Male

    Gasket Fittings or 22mm Female

    Compression Fittings.

    A High Head (8m) Pump Version is also

    available for larger installations.

    2

    1

    3

    4

    5

    6

    7

  • 7/31/2019 Apricus CoolSky Installation Manual

    10/68

    Apricus Installation Manual

    10

    Pump Sizing

    Sizing of the Solar Pump

    The standard CoolSky Twin Line Pumping

    station is supplied with a 3-Speed WILO ST

    15/6 Eco Pump (6m head) as standard. This

    is suitable for most domestic installations

    with the pump speed selected to suit the

    pressure drop of the piping. Speed 1 is

    generally suitable for a short pipe run, such

    as on a single-storey house. Speed 3 can

    normally service a 3-storey, 90 collector

    pressurized system.

    If the pipe run is very long or there are more

    than 90 tubes in the collector array, a larger

    pump may be needed. For these installations

    CoolSky supply a Twin Line Pumping station

    with a 3-Speed WILO ST 15/8 High Head

    Pump (8m head).

    If multiple banks of collectors are installed in

    parallel, the head loss should be calculated

    based on the longest pipe run through a

    single bank of collectors and, then, the

    pump can be sized to meet the total flow

    rate requirements.

    Please Note that Drain-back Systems will

    typically require a larger rated pump.

    Flow Meter

    The CoolSky Pumping Staions include a flow

    meter as standard to ensure that flow rates

    are at suitable levels and can be monitored.

    The flow meter includes a restrictor valve

    allowing the flow to be adjusted accordingly.

    Flow Rate

    A suitable flow rate range for each 30 tube

    collector is in the range of 1.5 to 3.0 litres

    per minute.

    Cool Tip

    Set the Flow Rate through the

    collector array to :

    0.1 litre / minute / tube

    That is :

    1 litre / minute for 10-tubes

    2 litres / minute for 20-tubes

    3 litres / minute for 30-tubes

  • 7/31/2019 Apricus CoolSky Installation Manual

    11/68

    11

    Solar Expansion Vessels

    CoolSky offer a range of different sizes of

    Zilmet Solar Expansion vessels. These shouldbe sized according to match the

    requirements of the system to which they

    are connected.

    (note : solar expansion vessels should be installed with

    the hydraulic connection to the top as this will reduce

    heat transfer into the vessel, as shown above)

    The Solar Expansion Vessels include 12, 18

    and 24 litre versions which have been

    specially designed for solar. Other sizes are

    available upon request.

    The Membrane

    Inside the expansion vessel there is a special

    Zilan E solar membrane structured as a bag

    membrane that separates the gas from the

    solar liquid. The development of the

    membrane is a result from long term Zilmet

    field experience in the installation of vessels

    in thermal solar systems.

    The membrane is stable with the Pre-Mixed

    Propylene-Glycol within the solar loop up to

    50% mixtures and has a max. working

    temperature of 110 C. The vessel can

    accommodate short peaks of 130C glycol

    temperature.

    The Zilan E solar membrane is also less likely

    to trap air and consequently, there is a lower

    likelihood of corrosion damage to the steel

    vessel.

    Expansion Vessels are manufactured in

    accordance with the PED 97/23/CE and

    EN13831 directives, which mean that they

    are fit for use in closed solar energy heating

    systems according to DIN 4757 and

    EN12977.

    Expansion Vessel Technical

    SpecificationMax. Operating Pressure: 6bar

    Membrane Temperature: 10 - +100C

    System Temperature: -10 - +100C

    Factory pre-charge: 2.5 bar 20%

    Nominal volume: 12, 18 & 24 L

    Colour: White

    Cool Tip

    The Cold-Fill Pressure of the Solar

    System should be :

    1.3 + (0.1 x Static Height)

    Where the Static Height is in

    Meters.

    Expansion Vessel Pressure should

    be re-set to 0.3 Bar less than the

    Cold Fill Pressure.

  • 7/31/2019 Apricus CoolSky Installation Manual

    12/68

    Apricus Installation Manual

    12

    Expansion Vessel Connection Kit

    CoolSky also provide an expansion vessel

    connection kit to connect the expansion

    vessel to the safety group on the pumping

    station. Each kit includes a wall fixing

    bracket and a self-closing system isolation

    valve (so that the vessel can be removed for

    maintenance without draining the fluid from

    the system and to facilitate periodic gas

    charge checks).

    A pre-formed stainless steel flexible hose is

    also provided to connect the vessel to the

    system at the connection point provided on

    the CoolSky Solar Pumping Station.

    It is recommended that the Pumping Station

    and Expansion Vessel are located as far

    hydraulically away in the Solar Loop from the

    Solar Collector as is practically possible. This

    is to protect the Pumping Station and

    Expansion Vessel from the very high

    temperatures (i.e. >200 C) that can be

    generated by a Vacuum Tube Collector

    under stagnation conditions.

    Mounting the Expansion Vessel

    Always mount solar vessels in a vertical

    position and recognised best practice is to

    connect to the provided connection port on

    the pump station. Where possible, mount

    below the pump station to negate heat

    transfer.

    Avoid mounting in close proximity to the

    solar collector where temperatures can

    exceed 130C. In cases where this cannot be

    avoided, it is highly recommended that the

    expansion vessel be installed in conjunction

    with a heat protecting intermediate vessel.

    Intermediate Vessels

    Intermediate vessels are also available and

    are recommended on solar thermal systems

    where it is likely that temperatures within the

    system will exceed the maximum allowable

    working temperature of the expansion vessel

    Cool Tip

    Always check the internal pressure

    of the Expansion Vessel before

    fitting and reset to 0.3 bar lower

    than the intended cold-fill pressure

    of the Solar Loop.

  • 7/31/2019 Apricus CoolSky Installation Manual

    13/68

    13

    or where the expansion vessel is in close

    proximity to the solar collector.

    It is particularly important that an

    intermediate vessel is installed on systems

    where the volume of the collectors exceeds

    the volume within the flow and return

    pipework. This is because during stagnation

    periods, the very hot solar fluid in the

    collectors can reach vaporisation point. If this

    occurs, the very hot solar fluid is forced out

    by the vapour, into the expansion vessel.

    Intermediate vessels have inlet/outlet

    connections and are installed just before the

    main expansion vessel (as shown above). The

    heat sink that the intermediate vessel

    provides, reduces the working temperature

    at the diaphragm, and hence considerablyextends the working life of the expansion

    vessel.

  • 7/31/2019 Apricus CoolSky Installation Manual

    14/68

    Apricus Installation Manual

    14

    Sizing the Expansion Vessel

    To size an Expansion Vessel for a Solar

    Application the following equation can be

    used :

    ( ) ( )

    Where

    VEV = Nominal Expansion Vessel Size [L]

    VSYS = Total Volume of System [L]

    VSS = Volume of Safety Water Seal [L]

    = 0.005 x VSYS

    or= 3 Litres

    (whichever of above is greater)

    = Solar Fluid Expansion Coefficient

    = 0.13 for CoolSky Fluid

    VCOL = Volume of Collector

    = 0.3 Litres for AP-10

    = 0.5 Litres for AP-20

    = 0.7 Litres for AP-30

    n = Number of Collectors

    PSV = Pressure Relief Valve Setting

    = 6 Bar as CoolSky Standard

    PMAX = Allowable Max Pressure in Bar

    = PSV (0.1 x PSV)

    = 5.4 Bar (for a 6 Bar PRV)

    HST = Static Height of System

    = Height of Collector from Pump

    PEV = Gas Pressure of Expansion Vessel

    = 1 + (0.1 x HST)

    CoolSky recommend that an additional

    safety factor of 1.5 is applied to the VEV

    value to account for the possibility of steam

    in the solar loop.

    Examples of typical domestic Expansion Tank

    Capacities are given in the table below.

    Apricus AP-30 Collector

    Aperture

    Area

    [m2]

    System

    Volume

    [Litres]

    Static

    Head

    [m]

    Expansion

    Tank

    [Litres]

    3 6.9 5 18

    10 18

    6 7.6 5 18

    10 18

    9 8.3 5 18

    10 18

    12 9.0 5 18

    10 24

    The above are based upon a system using

    the Apricus AP-30 Collector with 20 meters

    of DN16 Flexible S/S Pipework and a Heat

    Exchanger with 2 litre capacity.

    The CoolSky Technical Design Team can

    provide assistance and support for the sizing

    of Solar Expansion Vessels for your

    installation if required.

  • 7/31/2019 Apricus CoolSky Installation Manual

    15/68

    15

    Solar Thermal Anti-Freeze

    CoolSky recommend that a Solar Thermal

    Anti-Freeze Fluid is always used in Solar

    Collector Installations. CoolSky supply a pre-

    mixed (40% propylene glycol, 60% water)

    thermal transfer fluid with additional

    corrosion inhibitors for use with the Apricus

    Solar Collectors. The fluid is supplied in 20

    litre drums.

    Only Thermal Fluids that are formulated for

    use with High Performance Evacuated Tube

    Solar Collectors should be used, as these

    have special liquid corrosion inhibitors that

    are able to vaporise and condense effectively

    during normal collector operation.

    The fluid is specially developed for

    Evacuated Tube Solar Thermal collectors and

    provides frost protection to -28C.

    Protective goggles and rubber gloves should

    be used when handling the thermal fluid.

    A full Material Safety Data Sheet (MSDS) is

    available from CoolSky Ltd. upon request.

    Disposal of the fluid should be in accordance

    with local regulations.

    Although some Solar Controllers are

    provided with a Frost Protect Function it

    must be highlighted that this only functions

    when there is electrical power provided to

    the controller and pumps. In the UK and

    Ireland it is not unusual for extremely cold

    weather conditions to be accompanied by

    power outages due to falling power lines,

    thereby rendering the Frost Protection

    Function ineffective. Only the use of a

    suitable anti-freeze fluid will protect the

    solar collector from freezing in the combined

    conditions of extreme cold and power

    outage.

    Apricus Evacuated tubes are not susceptible

    to damage in cold weather, and Apricus heat

    pipes are protected against damage that

    could result from the freezing of the water

    inside by the addition of a special frost-

    protection additive.

    Within the manifold and pipework of the

    solar loop a suitable Solar Anti-Freeze fluid

    must be used. Contact CoolSky for details of

    suitable Anti-Freeze Fluids.

    Freeze related damage is not eligible for

    warranty claims.

    WARNING:

    Failure to implement effective (and

    fail-safe) freeze protection may result

    in rupture of piping and substantial

    property damage.

  • 7/31/2019 Apricus CoolSky Installation Manual

    16/68

    Apricus Installation Manual

    16

    Solar Heat Dissipater

    The Apricus HD-25 is an air to water radiator

    designed to dissipate the energy produced

    by one AP-30 collector.

    Heat dissipation may be necessary when

    solar thermal systems are designed for spaceheating applications which may produce

    more energy than is needed during warmer

    seasons, or for systems where there is an

    irregular or low summer demand, for

    example, schools, holiday homes and sports

    clubs.

    The Apricus HD-25 is an ideal solution to

    protect from excessive overheating and can

    prevent premature ageing of the heat-

    transfer fluids used in the solar loop.

    Materials of Construction

    Piping: Copper (Ag-Zn-Cu brazed)

    Fins: 3A21 Grade Aluminium

    Case: 3A21 Grade Aluminium

    Dimensions

    Height: 500mm

    Depth: 172mm

    Width: 375mm

    Heat Transfer Area: 2.8 m2

    Gross Weight: 6.6 kg

    Inlet/Outlet Pipe: 15 mm x 1.0mm

    Heat Loss Performance

    When T . 40C, heat dissipation 1.3kW

    For optimal performance ensure good

    natural air circulation.

    Installation Guidelines

    Max Flow Rage: 15L/min

    Ideal Location: Good natural air flow

    Transfer Liquid: Propylene Glycol (50%)

  • 7/31/2019 Apricus CoolSky Installation Manual

    17/68

    17

    Safety Valve Discharge Container

    A high temperature discharge container has

    specially designed to capture any propylene

    glycol fluid that is discharged from the

    Pressure Relief Vessel on the Solar Pumping

    Station and to allow its recovery during

    regular maintenance - neatly avoiding the

    issues of potential damage to those areas

    surrounding the valve.

    The unit is manufactured from high

    temperature grade plastic material that is

    suitable for solar systems and up to 160C

    short bursts of glycol/steam. The captured

    fluid is visible through the opaque tank

    which is supplied complete with a drain

    valve.

    Technical Specification

    Capacity 9.6 litre

    Drain valve integral

    Size 300 x 270 x 130mm

    Clearance required 440mm high

    Construction Plastic PE

    Ambient temp -5 - +50C

    Storage -10 - +60C

    Short term discharge 160C

  • 7/31/2019 Apricus CoolSky Installation Manual

    18/68

    Apricus Installation Manual

    18

    Sizing and Designing your Solar

    System

    When starting to design your solar system,

    the first issues to consider are regarding theinstallation site and the practicalities of

    installing the solar collectors.

    This section will provide you with detailed

    guidelines about assessing the suitability of

    any given site for the installation of the Solar

    Collector.

    Standard System Designs

    CoolSky have developed a standard set of

    system designs, which represent the most

    commonly installed configurations in the UK

    and Ireland. We recommend adhering to

    these system designs. Any modifications to

    the design should be checked by a qualified

    engineer.

    When using these designs it is important

    prior to installation, to confirm that the

    designs meet any local regulations.

    All systems must be installed by authorised

    persons. Upon completion of the

    installation, the system may also need to be

    checked by a plumbing inspector prior to

    commissioning, depending upon local

    regulations.

    Free Bespoke Design Service

    The CoolSky Technical Design Team can also

    offer our customers a full bespoke design

    service. System designs and configurations

    for both small and large systems can be

    tailored to our customers particular

    requirements. Contact CoolSky for more

    details on our Free Design Service.

    Collector Direction

    Ideally the collector should face as close to

    due South as possible. A deviation of up to

    15o to the East or West is acceptable and

    will have minimal effect on collector

    performance.

    If installed due east or west, the solar

    collector output will be considerably

    reduced, with predominately morning output

    or afternoon output for each direction

    respectively. However, a dual collector

    option exists with one collector facing east

    and the second collector facing west. This is

    commonly referred to as an East-West

    System.

    NOTE: Installations at or near due East or

    West will mitigate the passive tracking effect

    of the round absorbers within the Apricus

    evacuative tubes. Collectors should not beinstalled facing a northerly direction.

    Collector Orientation

    The collector manifold is normally installed

    on the flat horizontal plane with the tubes

    pointing downwards from the manifold. The

    collector must not be installed up-side-down

    (tubes pointing upwards) or with tubes lying

  • 7/31/2019 Apricus CoolSky Installation Manual

    19/68

    19

    horizontally, as the heat pipes will not

    function.

    Drain Back Systems

    In a drain-back configuration the collector

    must be positioned with 2cm of drop per

    meter.

    Installation Angle

    The solar collector must be installed at an

    angle of between 20-80o from horizontal to

    ensure optimal heat pipe operation. For

    optimum summer performance for Domestic

    Hot Water applications, as a rule of thumb

    the installation angle is typically set as :

    Install Angle = 0.7 x Location Latitude

    In areas prone to hail, a minimum angle of

    45o is advisable. Similarly, in areas prone to

    high snow loads, 45o or higher is advisable

    to encourage the snow to fall off the

    collector surface.

    Avoid Shade

    Collectors should be located so that shadingdoes not occur between 9am - 3pm which

    are the peak sun hours.

    Partial shading due to small objects such as

    antennas and small flues is not a problem.

    If installing multiple rows of collectors

    consider the shading of collectors on the

    row behind (especially in the winter).

    Location of Collector

    The collector should be positioned as close

    as possible to the storage tank to avoid long

    pipe runs.

    System Sizing

    Domestic System Sizing

    For residential domestic water heating

    applications basic rules of thumb exist that

    allow system sizes to be calculated using the

    methodology outlined below.

    For space heating or commercial water

    heating system the sizing calculations are

    more complicated. The CoolSky Technical

    Design Team can assist our customers with a

    free design service for these systems. Using

    special state-of-the-art Solar Thermal design

    packages we can assist in the design and

    optimisation of all Solar Thermal systems no

    matter what the size.

    How much hot water is needed?

    Ideally the exact daily hot water demand

    should be provided through metering.

    However, as this is not always available, the

    daily demand can be estimated using the

    following guidelines :

    Cool Tip

    Rule of Thumb for Optimum

    Installation Angle

    0.7 x Location Latitude

  • 7/31/2019 Apricus CoolSky Installation Manual

    20/68

    Apricus Installation Manual

    20

    Consumption

    Demand

    Liters of Hot Water

    at 60C per person

    LOW 15

    MEDIUM 30

    HIGH 60

    Guidelines for Domestic Hot Water Useage

    A general Rule of Thumb for UK / Ireland is

    to assume a requirement of 50 litres of Hot

    Water per person per day.

    The graphic below shows typical sizing

    guidelines for collectors when used for

    Domestic Hot Water production in the UK

    and Ireland.

    Guidelines for Collectors Sizing to Match User

    Demand for Domestic Hot Water

    Commercial Collector Sizing

    Sizing a commercial system usually requires

    the use of professional modelling software.CoolSky can offer a free design service to

    our customers for these jobs.

    The table below gives guidelines to typical

    Hot Water Demands in commercial

    applications.

    Type of Building Max. Liters of Hot Water at

    60C per person

    Restaurant 6

    Factory 15

    Offices 14

    Hotel 5* 136

    Hotel (Avg) 114

    Sports Facility 40

    Hospital 128

    Holiday Home 50

    Camp Site 40

    Typical Hot Water Demands in Commercial Type

    Properties.

    Cool Tip

    Rule of Thumb to Estimate Hot

    Water Demand at 60 C in UK andIreland :

    50 litres per person per day

  • 7/31/2019 Apricus CoolSky Installation Manual

    21/68

    21

    Sizing the Solar Cylinder

    Domestic Sizing

    The storage cylinder sizes for domestic solar

    thermal installations should be sized

    according to the following minimum

    guidelines :

    20 Tubes = 200 Liter cylinder

    30 Tubes = 300 Liter cylinder

    40 Tubes = 400 Liter cylinder

    60 Tubes = 600 Liter cylinder

    The storage capacity can be a single tank or

    multiple tanks plumbed in parallel.

    Using a smaller capacity tank will lead to the

    system reaching maximum temperature

    sooner, which will often result in wasted

    and/or uncollected energy.

    If the installed collector area exceeds the

    storage capacity of the cylinder there will be

    wasted energy and excess heat in sunny

    weather. Letting the collector stagnate is an

    acceptable means of preventing excessive

    tank temperatures during summer, but

    stagnation periods should be minimised in

    frequency and duration for the sake of

    overall system efficiency. Otherwise, the

    longevity of the evacuated tubes may be

    compromised by more rapidly reducing the

    vacuum level.

    Commercial Cylinder Sizing

    Sizing storage for commercial applications is

    more complex than residential sizing and

    requires a detailed evaluation of hot water

    usage patterns.

    Commercial applications are too varied in

    demand, peak demand, required outputtemp, etc. for set, rules to apply. Hot water

    usage patterns and the total hot water

    demand should both be considered. Use of

    modeling software is strongly advised when

    designing Commercial Systems and this is an

    area where CoolSky can provide system

    designs expertise to our customers.

    Pipe Type and Size

    Pipe Material

    The solar collector loop can get very hot (i.e.

    200C under stagnation conditions) and

    therefore the only recommended material

    choices are copper (hard or soft coiled) or

    corrugated flexible stainless steel pipe.

    Cool Tip

    Rule of Thumb to Size the

    Storage Cylinder :

    10 litres per Solar Tube

  • 7/31/2019 Apricus CoolSky Installation Manual

    22/68

    Apricus Installation Manual

    22

    Plastic Pipe (PEX) or Galvanised Pipe should

    NEVER be used in any part of the Solar

    Loop within a Solar Thermal Collector

    System.

    Pipe Size

    When selecting the size of the pipe for the

    solar loop there are two main issues to be

    taken into account: flow rate and pressure

    drop

    These two factors are closely related; a

    higher pressure drop will reduce the flow

    rate.

    Pressure drop is increased with a smaller

    diameter pipe, as well as the presence of

    bends, elbows and other components that

    will restrict the flow of the water such as

    corrugated stainless steel piping.

    A relatively direct, unobstructed flow path is

    highly desirable.

    If there is the possibility that additional

    collectors will be added to the system in the

    future then it is recommended that a lager

    pipe diameter is used to accommodate the

    future system expansion / upgrade.

    Number of

    Tubes

    Pipe Size

    Cu / SS

    10-40 15mm / DN16

    50-90 22mm / DN20

    90-240 25mm / DN25

    Guidelines showing pipe sizing for typical domestic

    installations

    Securing Pipes

    Pipes must be secured in place with suitable

    brackets, straps, etc. according to plumbing

    code requirements for material and pipe

    diameter and to prevent vibration and

    placing stress on system components.

    Internal Piping

    Extra care must be taken to avoid any piping

    leaks inside the building. Avoid joints in

    attic or overhead spaces that could cause

    significant property damage if they were to

    leak. The CoolSky Standard Systems have

    been designed to minimize the number of

    hydraulic connections and we recommend

    the use of Flat Face gasket seals for the

    hydraulic connections where possible.

    External Piping

    Long external pipe runs should be avoided

    where possible. Pre-insulated pipes should

    have a sheath to protect the insulation from

    UV degradation.

    Stagnation & Overheating

    What is Stagnation?

    Stagnation refers to the condition that

    occurs whenever the pump stops running.

    This could be due to pump failure, power

    outage or most commonly, as the result of a

    max tank temperature protection feature

    setting on the controller.

  • 7/31/2019 Apricus CoolSky Installation Manual

    23/68

    23

    During stagnation, the collector, unable to

    actively dump heat, will continue to rise in

    temperature until the heat loss from the

    collector and piping equals the heat being

    absorbed. In strong sunlight with high

    ambient temperatures, the collector can

    reach peak stagnation temperatures from

    160-220C. Hence, components that may be

    exposed to these high temperatures such as

    valves, plumbing or insulation should be

    suitably rated.

    Pressure Loss with Height

    Even though a system might be a closed

    loop and pressurized, there is always some

    pressure loss caused by height. This is

    extremely important to understand when

    deciding the system pressure. The loss of

    pressure is about 0.1 bar per vertical meter.

    A low system pressure at the collector can

    result in bubbles (vapour) forming within the

    heat transfer fluid due to a lowered fluid

    boiling temperature. These bubbles can

    collect in high points in the solar loop

    piping, especially within the collector itself,

    and cause air locks in the system that will

    result in stagnation, because the pump does

    not have the power to push fluid throughvapour pressure.

    Size System to Avoid Overheating

    The system should be sized so that

    overheating of the tank is difficult to achieve

    in a single day, even during hot, sunny

    periods.

    For properly sized open and closed loop

    systems with suitable heat transfer fluid, it is

    acceptable for the system design to allow

    the solar collector to stagnate (i.e. stop the

    pump) from time-to-time to prevent

    overheating of the storage tank above the

    maximum cylinder set temperature. An

    expansion tank must be properly sized and

    installed to accept the increase in fluid

    volume due to thermal expansion and

    potential steam formation, in order to

    minimise or prevent release of fluid from thepressure relief valve.

    If the system is over-sized, so that stagnation

    occurs often during summer months, the

    system must be able to stagnate repeatedly

    without damage or heat transfer fluid

    degradation. Using stagnation as a daily

    means of dealing with an oversized system is

    NOT recommended.

    Gradual loss of vacuum in evacuated

    tubes over time during normal use is not

    eligible for warranty claims.

    Heat Dissipation

    For systems designed for space heating that

    produce excessive summer heat output a

    heat dissipation loop should be installed.

    CoolSky offer an Apricus kit specially

    designed for this purpose, the HD-25 Heat

    Dissipater. This unit can be installed above

    the pump station on the Flow Line from the

  • 7/31/2019 Apricus CoolSky Installation Manual

    24/68

    Apricus Installation Manual

    24

    collector.

    The unit is a finned fluid to air style radiator

    that can be used to dissipate heat from the

    system once the tank has reached the

    maximum temperature. The heat transfer

    fluid circulates through the copper pipe

    transferring heat to a set of large aluminum

    fins, which in turn dissipate heat to the

    surrounding air. Each HD-25 unit can

    dissipate up to 1.5kW or greater with active

    air flow and is suitable to dissipate theexcess energy from one (1) Apricus 30-Tube

    Collector.

    Note: The HD-25 is for external installation

    only.

    Alternative Thermal Dumps

    During the summer, heat can also be

    dumped into a hot-tub, jacuzzi, pool, towel

    radiator, large storage tank or underground

    thermal store.

    Increased Angle Reduces Summer

    Output

    Apart from installing a smaller collector, a

    good method of reducing summer heat

    output is to angle the collector for optimal

    winter absorption. This is achieved by

    installing the collector at an angle 15-20

    above the latitude angle (so long as the

    collector remains within the recommended

    angles of 20 to 80). This angle corresponds

    closely to the angle of the sun in the sky

    during the winter, thus maximizing winter

    output. Conversely, during the summer

    when the sun is high in the sky, the relative

    surface area of the collector exposed to

    sunlight is reduced, lowering overall heatproduction by about 20-25%. This option is

    ideal for installations that use solar thermal

    for space heating. However, this depends

    upon the overall size of the collector array

    and a heat dissipation unit (or units) may still

    be required for larger arrays.

  • 7/31/2019 Apricus CoolSky Installation Manual

    25/68

    25

    Connection of Multiple Collectors

    It is only recommended to connect up to

    150 tubes in series (i.e. 5 x AP-30 Collectors

    with a maximum flow rate of 15 l/min

    through any Apricus Collector.

    Damage to collectors due to heat

    expansion and copper header distortion is

    not eligible for warranty claims.

    Balancing Flow through Collectors

    When connecting multiple banks of

    collectors (a bank being 1-5 x 30 tube

    collectors in series) in parallel, the flow rate

    through each bank MUST be equal.

    Otherwise, some collectors will run cold, due

    to higher flow rate while others will run hot,

    due to lack of flow. This is not an issue for a

    single bank of up to 150 tubes connected in

    series.

    Reverse Return plumbing, or first in - last

    out, is an effective piping configuration that

    helps to ensure balanced flow. However,

    there are affordable, high quality flow setters

    or circuit setters available and they are often

    a better choice, as they minimize pipe run

    length, costs and heat loss. Below is a

    diagram of reverse return piping.

  • 7/31/2019 Apricus CoolSky Installation Manual

    26/68

    Apricus Installation Manual

    26

    Wind & Structural Loading

    Components must be able to withstand

    environmental forces such as wind loading,

    snow loading, rain and hail. They must also

    be securely and positively fastened to the

    structure.

    Collector wind loading must be considered

    and the resulting stress on attachment

    points thoroughly examined.

    The standard Apricus Frame and Frame Kits

    are all designed to withstand wind speeds of

    up to 130 mph (208 km/h) without damage,

    which corresponds to the mid-range of

    Category 2 cyclones (US Saffir-Simpson

    scale).

    Table A provides peak vertical pull forces and

    horizontal (pushing) forces for an AP-30

    collector. These values represent both rear

    and frontal winds. The highest force of 180

    kg on the middle, front foot at a 60

    collector angle is actually from a frontal, and

    not rear, wind as it is trying to tip the

    collector backward.

    Based on the figures provided in Table A, the

    weight of individual concrete blocks or the

    strength of fixation points requirements can

    be determined.

    NOTE :

    A safety factor of at least 1.2 should be

    used, or as specified by local building

    regulations, whichever is higher.

    30o Angle 45o Angle 60o Angle 30o Angle 45o Angle 60o Angle

    Front Middle 22 8 40 59 100 180

    Front Left/Right 15 13 43 32 74 100

    Rear Middle 38 85 122 18 31 66

    Rear Left/Right 32 78 114 17 24 58

    Combined Load 156 275 488 127 327 808

    Round FootPeak Vertical Pull Load [kg] Peak Forward-Backward Load [kg]

    Table A Showing the Peak Loads on the Collector Feet when subjected to wind

    speeds of 130 mph (208 km/h)

  • 7/31/2019 Apricus CoolSky Installation Manual

    27/68

    27

    If using concrete blocks under the feet,

    connecting the blocks together, particularly

    front and rear, is advisable as it can help

    spread the load. This applies particularly to

    the middle legs which are exposed to the

    peak loads. Before ballasting the system with

    concrete or other weights, be aware of the

    total weight live and dead load capacity of

    the roof structure and determine if the roof

    can safely handle this attachment method.

    Other mounting methods in high wind

    regions may require inspection and approval

    by a licensed engineer or the local building

    authority.

    NOTE :

    It is the responsibility of the installer to

    ensure that the frame mounting is of

    suitable strength.

    Wind related frame and collector damage

    is not eligible for warranty claims.

    Snow Load

    The UK and Ireland as a whole are not

    generally considered to be areas prone to

    heavy snow falls. However, in areas prone to

    heavy or regular snow falls, or where the

    accumulation of snow on the collector is of

    concern, the solar collectors can be installed

    at an angle of 50o or greater to promote

    snow sliding off the tubes. In addition, it is

    advisable to raise the front of the collector

    frame 15 to 20cm off the roof surface as this

    allows the collector to sit above moderate

    snow falls and allow snow to blow away

    from under the collector. A front track

    extension available from CoolSky can be

    used for this purpose.

    Each tube is strong enough to withstand

    >50kg loading, but roof attachment points

    may need to be reinforced. Please refer to

    local regulations regarding snow loadingprecautions.

    Snow loading damage to the collector is

    not eligible for warranty claims.

    Hail Resistance

    The UK and Ireland are not considered to beareas subject to extreme hail conditions.

    The Apricus tubes are manufactured from

    robust borosilicate glass and are able to

    handle significant impact stresses. Testing

    and impact stress modelling shows that the

    tubes are able to withstand impact from hail

    up to 25 mm in diameter, and even larger

    when installed at angle of 45 or greater.

    In areas prone to hail over 20 mm in

    diameter, or where hail impact is of concern,

    it is recommended that the solar collector be

    installed at an angle of 45 or greater to

    provide optimum impact resistance.

  • 7/31/2019 Apricus CoolSky Installation Manual

    28/68

    Apricus Installation Manual

    28

    In the unlikely case that a tube breaks, it can

    easily be replaced. The solar collector can

    still function properly with one or more

    broken tubes, however, a reduction in heat

    output will result (depending upon how

    many tubes are broken). A broken tube

    should be replaced by authorised persons

    only.

    Hail related damage to the collector is not

    eligible for warranty claims.

    Lightning Protection

    It is advisable to earth-ground the copper

    circulation loop of the collector to avoid

    lightning related damage, or electrical safety

    issues. It may also help to prevent galvanic

    corrosion of the copper pipe which can

    result in blue staining of basins/baths etc.

    Ultraviolet (UV) degradation

    Any components installed outside must be

    able to withstand UV radiation without

    significant degradation. Colour fading is

    common, but cracking, peeling and other

    severe degradation should not occur during

    the design-life of any component in the

    system.

    Coastal Regions

    Apricus collectors are manufactured using

    439, 301 and 304 grade stainless steels for

    the solar collector frames, clips and

    fasteners. These grades of Stainless Steel are

    corrosion resistant to salt water, and

    therefore, installation of the collectors in

    costal regions is not normally an issue.

    In some coastal regions, the combination of

    salt spray and living sea microbes can resultin rapid corrosion of the stainless steel. In

    such cases please contact CoolSky for further

    advice.

    Corrosion related damage is not eligible

    for warranty claims.

  • 7/31/2019 Apricus CoolSky Installation Manual

    29/68

    29

    Back-Up Heating Source

    Solar Thermal Collector Systems normally

    require a back-up heating system. Typically

    this is the existing gas or oil boiler that is

    used to boost the Domestic Hot Water

    (DHW) supply on days when there is

    insufficient solar radiation.

    The existing boiler is used to boost the

    storage cylinder either using the top coil of a

    twin coil cylinder or the bottom coil of a

    secondary hot water storage cylinder that isfed by the solar pre-heat cylinder.

    High Temperature Limits

    Any components in close proximity to the

    collector can be exposed to brief periods of

    up to 160C temperatures, when the pump

    turns ON after stagnation. Therefore, the

    high temperature limits of all components in

    the system must be known and cannot be

    exceeded. It is also advisable to ensure that

    components (e.g. pumping station,

    expansion vessel, etc) are located

    hydraulically as far from the collector in the

    solar loop as is possible. Typically this will be

    hydraulically close to the storage cylinder.

    Temperature Control

    The solar controller should have a max tank

    temp function to protect the tank from

    being overheated. Hot water storage

    cylinders should comply with the local

    building regulations and be fitted with the

    appropriate safety features for over-

    temperature and over-pressure protection.

    Anti-Scald / Tempering Valves

    Anit-scald mechanisms are required in order

    to comply with the MCS MIS3001 Section

    4.3.3 Requirement : Incorporate a means to

    limit the water at all points of use to no

    more than 60C or lower depending upon

    scald risk factors.

    This requirement can be met by using

    Thermostatic Mixing Valves (TMVs) within

    2000mm of all points of use to limit the

    temperature to no more than 46C (or lessdepending upon the use). Alternatively a

    TMV at the outlet from the hot water

    cylinder limiting the output temperatures to

    55C to 60C can be used or also by

    providing a thermostatic device to limit the

    solar input to the hot water cylinder. A

    combination of the above may also be

    acceptable.

    Closed Loop Max Incoming

    Pressure

    For closed loop systems, the solar loop must

    operate at no greater than 3.5 Bar and have

    an expansion tank installed to accept fluid

    expansion.

    If a single wall heat exchanger is used, the

    solar loop operating pressure must be below

    the water main pressure.

    Maximum Allowable Pressure

    The maximum allowable operating pressure

    for the solar collector in any system

  • 7/31/2019 Apricus CoolSky Installation Manual

    30/68

    Apricus Installation Manual

    30

    configuration (domestic or commercial) is 8

    bar with pressure relief valve discharge rating

    at no more than 8.5 Bar or lower as specified

    by local building regulations.

    The Pumping Station supplied by CoolSky

    comes with a 6 Bar Pressure Relief Valve

    (PRV) therefore when using these pump

    stations the maximum allowable pressure is

    5.5 Bar (or lower as specified by local

    building regulations).

    When using other components, check the

    maximum pressure ratings for all

    components of the system and only use

    products that can handle the operational

    temperatures and pressures of the system

    design.

    System pressures that exceed those

    requirements outlined above will void the

    warranty.

    Electrical Supply

    Any electrical work must be completed by a

    licensed electrician and/or in accordance

    with relevant electrical codes and building

    regulations.

    Power supply to the controller must be

    protected again water ingress.

    Power supply to the controller must be

    disconnected when the cover is removed

    and/or work with the pump or other slave

    devices is conducted.

    Labelling

    All piping and components should be

    labelled with descriptive stickers/tags to

    allow easy identification during future

    troubleshooting, maintenance or upgrading.

    Labels must be durable enough to last for

    years and withstand normal handling, wetequipment rooms and high temperatures.

  • 7/31/2019 Apricus CoolSky Installation Manual

    31/68

    31

    Building Considerations

    Penetration Through Fire-Rated

    Assemblies

    Any piping that needs to penetrate fire-rated

    assemblies needs to be prepared/finished in

    line with any relevant regulations.

    Roof Penetration

    Depending on the location and local codes,

    there may be various acceptable means of

    penetrating the roof. Flashing are often used

    to ensure a neat and water-tight penetration.

    Regardless of the method used, insulation of

    the solar lines and water-tightness must be

    ensured. Roof penetrations may not impair

    the function of the enclosure. All roof

    penetrations must be sealed to prevent

    water, vermin or any other intrusion.

    Structural Supports

    Any points of attachment for the solar

    collector or other system components must

    be of suitable structural strength to support

    the weight of the components plus any

    loads that may be encountered, such as wind

    or snow loading.

    Any damage to structural supports caused

    by screws, drilled holes or other fastening

    methods must not undermine the structural

    integrity. Seek professional advice as

    required.

    Applicable Codes

    All roof penetrations must meet applicable

    codes, practices and building regulations. All

    members penetrated by solar system

    components must meet relevant codes.

    Adjacent Materials

    Materials adjacent to the solar system

    components should not be exposed to

    elevated temperatures.

  • 7/31/2019 Apricus CoolSky Installation Manual

    32/68

    Apricus Installation Manual

    32

    Health & Safety Considerations

    Anyone undertaking solar heating

    installations should obtain an up-to-date

    copy of the relevant UK HSE (Health &

    Safety Executive) Regulations and / or the

    Irish HSA (Health & Safety Authority)

    regulations and carefully review the contents

    Working at Height

    A Full Risk Analysis should be undertaken

    before any work is started with particular

    attention to work at height, how you plan to

    organize your work, accounting for the

    installation site, prevailing weather conditions

    and the experience and competence of

    others who will also be working at height.

    Reference should be made to the Full

    Current Regulations and Guidelines before

    any work commences which state that a Risk

    Assessment must be undertaken for any

    work undertaken at height and to ensure

    that arrangements are in place to :

    - Eliminate or minimise the risks from

    working at height

    - Safe systems and methods of work are

    in place for the organisation andperformance of work at height

    - Safe systems and methods are in place

    for selecting equipment that is suitable

    to undertake the work

    - Safe systems and methods are in place

    for protecting people from the

    consequences of working at height

    The Regulations set out a basic hierarchy for

    managing and selecting equipment for work

    at height, as follows :

    - Avoid working at height where possible

    - Use work equipment or other suitable

    measures to prevent falls when work

    at height cannot be avoided

    - Where the risk of a fall cannot be

    completely eliminated, then use

    equipment of other measures to

    minimise the distance and

    consequences should a fall occur

    Under the regulations you are required to

    ensure :

    - All work at height is properly planned

    and organized

    - All work at height takes account of

    weather conditions that could endanger

    health and safety

    - Those involved in work at height are

    trained and competent

    - The place where work at height is done

    is safe

    - Equipment for work at height is

    appropriately inspected

    - The risks from fragile surfaces are

    properly controlled

    - The risks from falling objects are

    properly controlled

  • 7/31/2019 Apricus CoolSky Installation Manual

    33/68

    33

    General Safety Information

    This section includes general Health and

    Safety Information. However, reference

    should be made to the current HSE / HSA

    regulations which take precedence.

    Appropriate safety equipment must be used

    when installing the solar collector. The

    installer should consider the use of the

    following items in order to comply with the

    Health & Safety Regulations :

    - Safety glasses, gloves and other required

    personal protective equipment.

    - Well-maintained, properly-fitted safety

    harness, lanyard, rope and appropriate

    anchor for working on the roof.

    - A harness attachment plan that ensures

    you aware of the safe working area with

    your particular harness setup.

    - A first aid kit and the necessary training

    in First Aid.

    - Consider on-site risks such as slippery

    roofs, exposed nails, hot plumbing,

    sunburn, high winds, etc.

    - Safety on the roof is always an importantconsideration. Avoid roof work if it is

    raining and ensure that the inside of the

    manifold does not get wet. Do not let

    rain enter the evacuated tubes.

    - Keep the evacuated tubes out of the sun

    until 2-3 minutes prior to installation. If

    you install the solar collector in direct

    sunlight, the heat pipes will become hot

    very quickly. Try to install the collector

    earlier or later in the day. DO NOT install

    the collector at night.

    A minimum of 2 people are required to

    complete an installation. Do not attempt to

    complete an installation without a qualified

    and experienced installation team.

    Roof work should not be performed without

    a second installer on-site. Each person

    performing work on the roof needs to have

    their own harness, rope, lanyard and anchor,

    in accordance with HSE (UK) or HSA (ROI)

    regulations.

  • 7/31/2019 Apricus CoolSky Installation Manual

    34/68

    Apricus Installation Manual

    34

    Installation Guidelines

    This section contains guidelines for the

    unpacking, inspection, assembly and

    installation of the Apricus Solar Collectors.Several of the more common types of

    Installation are covered in detail. For other

    installations or where further clarification is

    required please contact CoolSky.

    Tube Unpack & Inspect

    Check to make sure the evacuated tubes are

    all intact and the getter at the bottom ofeach tube is still silver coloured by removing

    the rubber caps. The rubber cap should be

    immediately replaced after inspection to

    protect the bottom tip of the glass tube.

    If a tube has a white or clear bottom, it is

    damaged and should be replaced. Any

    damage or breakages should be reported

    immediately upon delivery to CoolSky.

    Damage to collectors and other

    components incurred during transport is not

    eligible for warranty claims.

    Shield Tubes from Sunlight

    Do not expose the tubes to sunlight until

    ready to install, otherwise the heat pipe tip

    will become very hot and can cause serious

    skin burns. The outer glass surface should

    not become hot.

    Frame/Manifold Unpack & Inspect

    Unpack the standard frame that is provided

    together with the manifold. Apricus solar

    collectors are come with a standard frame,

    which is suitable for flush mounting on roofs

    that have a suitable pitch.

    For installation on low-pitched roofs, flat

    roofs or for wall mounts, an additional,

    adjustable frame kit is available. This

    additional adjustable frame will be packed

    separately from the manifold and standard

    frame kit.

    Depending on the roofing material, the

    standard frame may be attached to the roof

    with flashed bracketing solutions (corrugated

    steel, asphalt), roof attachment straps (tiled,

    slated), stand-off bracket (tiled, slated) or

    round feet (asphalt, concrete).

    WARNING:

    Wear safety glasses and leather

    gloves at all times when handling

    evacuated tubes and heat pipes.

    Never touch the inside of evacuated

    tubes or the heat pipe tip after

    exposure to sunlight.

  • 7/31/2019 Apricus CoolSky Installation Manual

    35/68

    35

    An adjustable frame kit designed and

    provided by Apricus is capable of turning the

    standard frame into a rack, in order to

    position the manifold and tubes at the ideal

    azimuth and tilt for almost any location.

    Frame Material

    All frame components are made of 439

    grade stainless steel making the frame both

    strong and corrosion resistant. It is

    important that frame attachment points and

    externally supplied fasteners are also of

    suitable structural strength and corrosion

    resistance.

    Galvanic Reactions

    Zinc galvanized steel roofing or Uni-strut

    must NOT directly contact stainless steel as

    galvanic reaction between the two metals

    can cause premature oxidation of the zinc

    coating and the metal underneath. Apricus

    offers rubber pads which are perfect for

    separating the metals (see image below).

    Fasteners

    It is recommended that stainless steel

    fasteners are used. If using galvanized steel

    bolts, separate dissimilar metals using a

    nylon or high density EPDM/Silicone rubber

    washer.

    Manifold and Bottom Support TrackAssembly

    The Manifold and Bottom Track are secured

    to the standard frame channels using special

    securing plates. These plates are attached to

    the frame channels before they leave the

    factory.

    They only need to be LOOSENED in order to

    allow enough movement to fit the Manifold

    and Bottom Support Track in place. The

    plates are designed so that while somewhat

    loose, they enable the Manifold and Bottom

    Support Track to slide left and right for

    positioning and allow the standard frame

    channels to be easily adjusted side to side to

    suit the roof framing layout.

    Manifold Attachment

    Bottom Support Rail

  • 7/31/2019 Apricus CoolSky Installation Manual

    36/68

    Apricus Installation Manual

    36

    Tightening Nuts

    Once correctly located, the nuts should be

    hand tightened ONLY using the supplied

    wrench, locking the Manifold and Bottom

    Support Track in place. DO NOT use a

    power tool or longer hand tool to tighten

    the nuts as stainless steel is prone to galling

    (cold welding, i.e.), if excessive friction or

    over-torqueing occurs (i.e. the nuts can lock

    to the shaft before they are completely

    seated, if they are over-tightened). The use

    of a lubricant on the threads, such as WD-

    40, will also help to prevent issues.

    Split washers are supplied to ensure the

    stainless steel bolts do not loosen over time.

    Inverted Bolts

    NOTE: Some bolts are inverted with the nut

    on top. This so you can see the threads and

    helps prevent you from loosening the boltso much that the nut drops off. The bolt

    head is prevented from rotating by use of

    nut locks (i.e. rectangular washers), removing

    the need to use a second wrench

    underneath the frame and aiding a quick

    and easy assembly process.

    Customizing the Frame

    The standard frame, together with the

    adjustable angle frame kit components can

    be adapted to a wide range of different

    installation surfaces and situations. Any

    modifications to the frame design must be

    approved by a licensed engineer and done

    with structural integrity in mind, particularly

    in high wind areas.

    Cool Tip

    When drilling the Stainless Steel

    always use a good quality drill bit.

    Take caution when using power

    tools and never do any drilling of

    the frame whilst on the roof.

    Cool Tip

    Any modifications to the mounting

    frame must be approved for

    strength and safety by a licensed

    engineer before installation.

  • 7/31/2019 Apricus CoolSky Installation Manual

    37/68

    37

    Other System Components

    For a typical domestic installation, in

    addition to the solar collector, storage tank,

    and pump station, some or all of the

    following components are also required :

    Solar Expansion Tank

    Copper pipe (straight and/or soft rolled)

    with additional insulation or Flexible Pre-

    Insulated Stainless Steel Pipe.

    An automatic or manual air vent

    Anti-Freeze based Heat transfer fluid

    Flush & Fill Pumping Cart

    Anti-scald valve

    Various plumbing fittings, valves, drainvalves, etc.

    Scissor lift, cherry picker and/or ladders

    and harness equipment for roof work

    Labels and permanent marker to label

    system components and flow paths.

    Cool Tip

    All system components should

    be installed in a manner that

    allows access for maintenance

    and repairs.

    Su ort Rail

    Side Rails

    Tube Cli s

    Attachment Plates

    Roof Attachment

    Strap

    Schematic showing the Apricus Standard Roof Frame (this is supplied with the Apricus

    Manifold in the same box)

  • 7/31/2019 Apricus CoolSky Installation Manual

    38/68

    Apricus Installation Manual

    38

    Collector Installation

    Flush Mounting on

    Pitched Roof

    Installation Planning

    Carefully plan the location of the collector

    frame and plumbing pipes in order to align

    with the roof framing members and develop

    the shortest pipe run possible to the storage

    tank. Any penetrations in the roof or

    building shell must be water-tight and sealed

    with standard roofing materials and/or

    appropriate sealants to avoid leaks and

    comply with local building regulations or

    requirements.

    Securing to Roof

    The manifold and bottom support rail can

    slide left and right in relation to the frame

    side rails, so there is some flexibility when

    selecting the location. The frame side rails

    should be located so that they lay flat, are

    parallel with one another and, if possible,

    aligned with the roof rafters. If the frame

    side rails cannot be aligned with the roof

    rafters, a noggin may need to be attached

    between 2 rafters to provide an attachmentpoint. Ensure that any additions or

    modifications to the roof structure meet

    structural requirement and local building

    regulations.

    A Horizontal Brace is provided with the

    standard frame kit. This gives a useful

    indication of the typical spacing between

    frame side rails. Additional holes may be

    drilled in the horizontal brace to meet

    different roofing rafter locations.

    The Horizontal Brace component is NOT

    structural and is simply to help with

    alignment, so it can be removed if it is

    incorrectly sized for the roof rafters or it is

    not convenient.

    Drain-Back System

    If installing a drain-back system, the frame

    must be rotated slightly to achieve a 2cm

    drop per meter to ensure that the manifold

    is sloped towards whichever header port will

    be the collector outlet (hot), to promote

    complete drainage.

    Tiled and Slate Roof Installations

    Roof Attachment Straps

    Roof attachment straps are used for flush

    mounting on tiled/slated roofs 2 per

    standard side rail. One end of each strap

    should be secured to the underside of the

    Cool Tip

    Ensure that the Assembled Frame is

    square so that the tubes align with

    the manifold header and the

    bottom support track.

    http://edit%2816841%29/
  • 7/31/2019 Apricus CoolSky Installation Manual

    39/68

    39

    standard frame side rails using the supplied

    M8x20 bolts and nut lock assemblies, the

    other end to the roof rafter using two

    stainless steel coach screws. Once the upper

    straps are attached and tightened, adjust the

    bottom straps to ensure that they too are

    providing support to the frame.

    Fragile Slates / High Wind Area

    In areas of high wind or where the roof

    slates are fragile then the roof attachment

    straps should NOT be used.

    A rigid solar stand-off bracket (similar to

    those shown below) and flashing is

    recommended. Care should be taken when

    cutting tiles/slates to avoid breakage, as new

    tiles/slates may not be readily available. It is

    recommended that in such cases a

    professional roofer is used.

    Manifold and Bottom Track

    Attachment

    Once the standard frame channels are

    secured in place on the roof, the manifold

    and bottom track may be attached, taking

    care to ensure they are correctly aligned. The

    manifold and bottom track will lock into the

    frame, secured from above and below with

    the attachment plates that are already in

    place. Make sure that the Manifold andBottom Support Rail are square with the

    frame side rails.

    To ensure proper tube engagement, each

    tube in the Manifold should line up with the

    corresponding cradle on the Bottom

    Support Rail. Each Tube is installed with the

    Heat Pipe snugly engaged within the Header

    with the opening of the glass tube inside the

    Manifold header. The bottom of the tube,

    protected by the Rubber Cap, locates in the

    cradle between each set of prongs on theBottom Support Rail, where it is held in

    place by the Bottom Support Rail Clip.

    Mounting on Low

    Pitched Roof

    If the roof pitch is insufficient, an adjustableangle roof frame kit (as shown below) can

    be used to increase the angle by 27to 57.

    Adjustable frame kits combine with the

    standard frame components to form a

    complete frame assembly.

    It is recommended that the adjustable frame

    kits are completely assembled on the ground

    before taking onto the roof see next

    section.

  • 7/31/2019 Apricus CoolSky Installation Manual

    40/68

    Apricus Installation Manual

    40

    Metal Roof

    Installations

    For installation on a corrugated or ridged

    steel roof, either a Basic Metal Roof Kit or a

    Stand-Off Metal Roof Kit can be used to

    secure the collector to the roof.

    The Basic Metal Roof Kit

    This kit consists of Rubber Sealing Pads that

    are used to separate the frame from the roof

    and also to seal the hole. Addition of some

    silicone sealant or similar roof sealant

    beneath the pad and inside the hole is

    required thereby allowing the rubber pad to

    form a tight seal against the roof, preventing

    any water ingress. Three (3) attachments per

    track are required.

    The Stand-Off Metal Roof Kit

    For installations where longer bolts may be

    required to account for the height of the

    ridges such that the required depth of

    penetration into the rafter is achieved, or

    there is a desire to hold the collector frame

    away from the roof structure, the Stand-Off

    Metal Roof Kit is suitable.

    Each kit consists of 4 or 6 large hanger bolts

    M10 x 250mm with integral rubber seals,

    attachment plates, rubber pads and the

    required nuts, bolts and washers for

    attaching to the collector frame side rails.

    Addition of some silicone sealant or similar

    roof sealant beneath the pad and inside the

    hole is required thereby allowing the rubber

    pad to form a tight seal against the roof,

    preventing any water ingress. Two (2)

    attachments per track are required, thereby

    needing 4 for a 20-tube collector or 6 for a30-tube collector.

  • 7/31/2019 Apricus CoolSky Installation Manual

    41/68

    41

    Flat Roof

    Installation

    The high angle frame is adjustable and

    appropriate for installations on flat surfaces

    and provides adjustment from 27-57. The

    high angle frame kit combines with the

    standard frame components to form the

    complete frame assembly.

    The high angle frame is supplied with Round

    Feet thatare also suitable for attachment toconcrete ballast on a flat roof.

    For additional strength and support a rear X-

    Brace is supplied. The X-Brace has a series of

    elongated holes to allow adjustment of the

    location of the legs. If further adjustment is

    needed, additional 9 mm holes may be

    drilled using a good quality drill bit.

    Assembly of the Support Frame

    When undertaking an installation that

    requires an adjustable angle roof frame kit

    (such as on a flat roof or a low pitched roof)

    it is recommended that the frame is

    completely assembled on the ground on a

    clear flat area. The collector frames are

    relatively light and can easily be carried onto

    the roof once assembled. Assembling on the

    roof is both dangerous and makes it easy to

    lose bolts and nuts that may roll away.

    Frame Feet Anchoring

    Frame feet should be bolted to the

    installation surface using 8 mm diameter

    stainless steel bolts or a similarly sturdy

    fastening method. (Galvanized bolts should

    be NOT be used as these can result galvanic

    corrosion).

    The surface or concrete block must be

    strong/heavy enough to withstand load

    during high winds. Consult a professional

    structural engineer for design requirements.

    Adjusting Frame Angle

    The rear legs of the high angle frame

    comprise two interlocking pieces (top and

    bottom leg), which allow the length of the

    rear leg to be adjusted, thus changing the

    collector angle from between 27o and 57o.

    The rear legs must never be positioned

    greater than a 90o angle (perpendicular) with

    the roof surface, meaning the legs must be

    behind the position of the manifold, not in

    front. See diagram to below.

  • 7/31/2019 Apricus CoolSky Installation Manual

    42/68

    Apricus Installation Manual

    42

    Rear Legs

    Each rear leg has two pieces, a top and a

    bottom, which allows them to be adjusted.

    The two pieces must always be joined

    together by 2 bolts through two sets ofholes each in each leg for structural support.

    Lower Angles

    If an angle less than 27o is required the low

    angle frame kit should be used which

    provides an installation angle of 12o.

    Higher Angles

    If an angle greater than 57o is required, the

    mounting points of the rear feet may be

    raised. Raising the angle greatly increases

    the horizontal force during high winds andmay require additional structural and/or

    hardware upgrades. Consult a building

    engineer for design requirements.

    Standard Frame

    Support Rail

    Standard Frame

    Side Rail

    Dia onal Brace

    Top Rear

    Leg

    Bottom Rear Leg

    When fitting place the large metal washers

    between the inner wall of the side rail and

    the outer face of the diagonal brace to

    ensure a tight fit

    Adjust location of diagonal

    brace to chosen angle

    (from 27 to 52 )

    Apricus A-Frame

    Supplied with

    Round Fixing Feet

    as Standard

    Optional Rubber Pad for

    attaching to metal roofs

    to eliminate galvaniccorrosion risks

  • 7/31/2019 Apricus CoolSky Installation Manual

    43/68

    43

    Wall / Faade

    Installations

    The high angle frame kit may be used for

    Wall / Faade Installations. The legs are

    reversed so that they attach to the bottom

    of the standard frame side rails rather than

    the top. The legs should be position

    perpendicular to the wall and are adjusted

    and secured in the same manner as the Flat

    Roof Installation detailed in the previous

    section.

    Surface Attachment

    The method used for attachment to the wall

    will depend on the wall material.

    - The round feet can be secured with

    stainless steel expansion bolts for

    attachment to brick or concrete surfaces

    - Stainless steel coach screws of at least

    8mm diameter or greater with high

    sheer strength that can penetrate into

    the wall framework can be used with

    wood or synthetic boarding surfaces.

    Wall Strength

    Always consider the weight of the collector

    and the structural integrity of the wall. If the

    wall construction is not suitable for the load,

    it will be necessary to reinforce the wall

    frame accordingly. Consult a building

    engineer for design requirements.

    Recommended Angle

    Ideally, do not install the collector beyond an

    angle of 80o (close to vertical) otherwise

    heat pipe operation will be impaired by 10%

    or greater. Installing vertically is permitted

    and will not void the warranty, but

    performance will be reduced.

    Safety Considerations

    If installing the collector on a wall above a

    walkway, keep in mind the danger of broken

    glass that could fall on pedestrians, if the

    tubes were ever damaged. (E.g. during an

    extreme storm due to flying debris or tree

    branch falling on the collector). It may be

    necessary for a barrier of to be installed

    below the collector to catch any falling

    materials, such as a clear roofing material.

    WARNING:

    For collectors installed above a pedestrian

    area, take appropriate measures to

    minimise injury risk in case a broken tube

    or glass fell onto the ground or people

    below.

  • 7/31/2019 Apricus CoolSky Installation Manual

    44/68

    Apricus Installation Manual

    44

    Connection to Plumbing

    Plumbing Connection

    Once the frame has been mounted and the

    manifold attached, the manifold header may

    be connected to the system plumbing.

    Delayed Commissioning

    If the collector is to be installed (including

    evacuated tubes) prior to plumbing

    connection (e.g. on new house), high

    temperature resistant covers (aluminum foil)should be placed over the header inlet and

    outlet to prevent any contaminants (bugs,

    spiders, leaves, dust) entering the header.

    The solar collector will not be damaged by a

    period of dry stagnation that lasts less than

    14 days.

    If the collector is to be left for any significant

    period of time before being commissioned it

    is recommended that the collector is covered

    with an appropriate tarpaulin. Ensure that

    the tarpaulin is secured to the roof fixings

    DO NOT secure any cover or tarpaulin to the

    glass tubes as this can result in damage /

    breakage of the glass under high wind

    conditions.

    Damage to collectors and other

    components incurred by extended dry or

    wet stagnation is not eligible for warranty

    claims.

    Pipework

    Suitable Pipe Materials

    Only the following materials are

    recommended for use with HighPerformance Evacuated Tube Solar Collector

    Systems, as follows :

    - Flexible Stainless Steel Pipe

    - Copper Tube (hard or soft coiled)

    Plastic Pipes (PEX) and Galvanised Pipes

    should NEVER be used in a solar thermalsystem

    All pipework in the solar loop should be

    suitable insulated in compliance with local

    building regulations.

    Insulation

    Insulate Piping

    Ensure all piping running to and from the

    manifold is appropriately insulated with a

    high quality insulation that complies with

    local building regulations in terms of its

    thermal conductivity and thickness required.

    Heat loss from the piping can be significant

    so particular attention should be taken to

    insulate any possible points of heat loss,

    particularly on outdoor piping.

  • 7/31/2019 Apricus CoolSky Installation Manual

    45/68

    45

    Seal the Insulation and Sensor

    Port

    Ensure the insulation is tight against the

    manifold casing, preventing loss of heat from

    the inlet and outlet. In order to prevent

    water from entering the temperature probe

    port and/or in between the piping and

    insulation foam, a high quality silicone

    sealant should be used to form a water-tight

    seal. This is also important to avoid water

    running down under the insulation along the

    copper / stainless steel pipe into the roofspace.

    Protect Insulation

    EPDM (foam) insulation that is exposed to

    direct sunlight should be protected against

    UV related degradation. CoolSky supply

    Stainless Steel Flexible Pipework that is pre-

    insulated with high-grade EPDM Insulation

    with UV Protective sheath.

  • 7/31/2019 Apricus CoolSky Installation Manual

    46/68

    Apricus Installation Manual

    46

    Installation of the Tubes

    The Apricus solar collector is a simple plug

    in system. The heat pipe and evacuated

    tube assembly just needs to be inserted intothe manifold. The contact between the heat

    pipe condenser/tip and heat pipe port in the

    header needs to be tight in order to ensure

    good heat transfer. Under normal use, once

    the heat pipes are installed they should

    never have to be removed.

    Heat Pipe Preparation

    Do not remove the tubes from the box

    and/or expose the tubes to sunlight until

    ready to install, otherwise the heat pipe tip

    will become hot enough to cause serious

    skin burns. The outer glass surface should

    not become hot.

    Heat Pipe Frost Protection

    Apricus Heat Pipes contain a small amount

    of copper powder, which aids in heat transfer

    and provides freeze protection within the

    heat pipe itself. To ensure that the powder

    is at the bottom of the heat pipes, where is

    needs to be, before installing the tube and

    heat pipe, they should inverted (condenser

    end down), returned upright (condenser at

    top) and then shaken up and down a few

    times to ensure the powder has all returned

    to the bottom. This should be done at

    ground level.

    Damaged Tube

    If an evacuated tube is damaged for any

    reason (E.g. knocked heavily or dropped), it

    will need to be replaced.

    Never throw heat pipes away, as they arevery sturdy and will not be damaged even if

    the glass tube has been broken. They can

    be kept as spares, or inserted into plain

    spare evacuated tubes to provide a new fully

    functional tube.

    WARNING: