—RELION® 615 SERIES

Motor Protection and ControlREM615Application Manual

Page 2: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and
Page 3: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Document ID: 1MRS756885Issued: 2018-12-20

Revision: MProduct version: 5.0 FP1

© Copyright 2018 ABB. All rights reserved

Page 4: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Copyright

This document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imparted to a third party,nor used for any unauthorized purpose.

The software or hardware described in this document is furnished under a license andmay be used, copied, or disclosed only in accordance with the terms of such license.

TrademarksABB and Relion are registered trademarks of the ABB Group. All other brand orproduct names mentioned in this document may be trademarks or registeredtrademarks of their respective holders.

WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.

www.abb.com/relion

Page 5: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Disclaimer

The data, examples and diagrams in this manual are included solely for the concept orproduct description and are not to be deemed as a statement of guaranteed properties.All persons responsible for applying the equipment addressed in this manual mustsatisfy themselves that each intended application is suitable and acceptable, includingthat any applicable safety or other operational requirements are complied with. Inparticular, any risks in applications where a system failure and/or product failurewould create a risk for harm to property or persons (including but not limited topersonal injuries or death) shall be the sole responsibility of the person or entityapplying the equipment, and those so responsible are hereby requested to ensure thatall measures are taken to exclude or mitigate such risks.

This product has been designed to be connected and communicate data andinformation via a network interface which should be connected to a secure network.It is the sole responsibility of the person or entity responsible for networkadministration to ensure a secure connection to the network and to take the necessarymeasures (such as, but not limited to, installation of firewalls, application ofauthentication measures, encryption of data, installation of anti virus programs, etc.)to protect the product and the network, its system and interface included, against anykind of security breaches, unauthorized access, interference, intrusion, leakage and/ortheft of data or information. ABB is not liable for any such damages and/or losses.

This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requested tonotify the manufacturer. Other than under explicit contractual commitments, in noevent shall ABB be responsible or liable for any loss or damage resulting from the useof this manual or the application of the equipment.

Page 6: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Conformity

This product complies with the directive of the Council of the European Communitieson the approximation of the laws of the Member States relating to electromagneticcompatibility (EMC Directive 2004/108/EC) and concerning electrical equipment foruse within specified voltage limits (Low-voltage directive 2006/95/EC). Thisconformity is the result of tests conducted by ABB in accordance with the productstandard EN 60255-26 for the EMC directive, and with the product standards EN60255-1 and EN 60255-27 for the low voltage directive. The product is designed inaccordance with the international standards of the IEC 60255 series.

Page 7: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Table of contents

Section 1 Introduction.......................................................................5This manual........................................................................................ 5Intended audience.............................................................................. 5Product documentation.......................................................................6

Product documentation set............................................................6Document revision history............................................................. 6Related documentation..................................................................7

Symbols and conventions...................................................................7Symbols.........................................................................................7Document conventions..................................................................8Functions, codes and symbols...................................................... 8

Section 2 REM615 overview.......................................................... 13Overview...........................................................................................13

Product version history................................................................13PCM600 and relay connectivity package version........................14

Operation functionality......................................................................15Optional functions........................................................................15

Physical hardware............................................................................ 15Local HMI......................................................................................... 18

Display.........................................................................................18LEDs............................................................................................19Keypad........................................................................................ 19

Web HMI...........................................................................................20Authorization.....................................................................................21

Audit trail......................................................................................22Communication.................................................................................24

Self-healing Ethernet ring............................................................25Ethernet redundancy................................................................... 26Process bus.................................................................................28Secure communication................................................................30

Section 3 REM615 standard configurations...................................31Standard configuration..................................................................... 31

Addition of control functions for primary devices and the useof binary inputs and outputs........................................................ 33

Connection diagrams........................................................................34Standard configuration A.................................................................. 39

Applications................................................................................. 39Functions.....................................................................................40

Table of contents

REM615 1Application Manual

Page 8: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Default I/O connections.......................................................... 41Default disturbance recorder settings.....................................42

Functional diagrams.................................................................... 43Functional diagrams for protection ........................................ 44Functional diagrams for disturbance recorder........................52Functional diagrams for condition monitoring.........................52Functional diagrams for control and interlocking....................54Functional diagrams for measurement functions .................. 56Functional diagrams for I/O and alarm LEDs......................... 57Functional diagrams for other timer logics............................. 60Other functions....................................................................... 60

Standard configuration B.................................................................. 60Applications................................................................................. 60Functions.....................................................................................61

Default I/O connections.......................................................... 61Default disturbance recorder settings.....................................63

Functional diagrams.................................................................... 65Functional diagrams for protection ........................................ 65Functional diagrams for disturbance recorder........................76Functional diagrams for condition monitoring.........................77Functional diagrams for control and interlocking....................79Functional diagrams for measurements functions .................81Functional diagrams for I/O and alarm LEDs ........................ 83Functional diagrams for other timer logics............................. 87Other functions ...................................................................... 88

Standard configuration C..................................................................88Applications................................................................................. 88Functions.....................................................................................89

Default I/O connections.......................................................... 89Default disturbance recorder settings.....................................91

Functional diagrams.................................................................... 93Functional diagrams for protection ........................................ 93Functional diagrams for disturbance recorder......................102Functional diagrams for condition monitoring.......................103Functional diagrams for control and interlocking..................105Functional diagrams for measurement functions ................ 108Functional diagrams for I/O and alarms LEDs .................... 110Functional diagrams for other timer logics........................... 114Other functions .................................................................... 116

Standard configuration D................................................................116Applications............................................................................... 116Functions...................................................................................117

Default I/O connections........................................................ 117

Table of contents

2 REM615Application Manual

Page 9: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Default disturbance recorder settings...................................119Functional diagrams.................................................................. 120

Functional diagrams for protection ...................................... 121Functional diagrams for disturbance recorder......................131Functional diagrams for condition monitoring.......................132Functional diagrams for control and interlocking..................134Functional diagrams for measurement functions ................ 137Functional diagrams for I/O and alarm LEDs ...................... 140Functional diagrams for other timer logics........................... 143Other functions..................................................................... 144

Section 4 Requirements for measurement transformers..............145Current transformers...................................................................... 145

Current transformer requirements for overcurrent protection.... 145Current transformer accuracy class and accuracy limitfactor.................................................................................... 145Non-directional overcurrent protection................................. 146Example for non-directional overcurrent protection..............147

Section 5 Protection relay's physical connections........................149Inputs..............................................................................................149

Energizing inputs.......................................................................149Phase currents..................................................................... 149Residual current................................................................... 149Phase voltages.....................................................................149Residual voltage...................................................................150Sensor inputs....................................................................... 150

Auxiliary supply voltage input.................................................... 150Binary inputs..............................................................................150Optional light sensor inputs....................................................... 153RTD/mA inputs.......................................................................... 153

Outputs........................................................................................... 154Outputs for tripping and controlling............................................154Outputs for signalling.................................................................154IRF.............................................................................................156

Section 6 Glossary....................................................................... 157

Table of contents

REM615 3Application Manual

Page 10: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

4

Page 11: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Section 1 Introduction

1.1 This manual

The application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purpose atypical protection function can be used. The manual can also be used when calculatingsettings.

1.2 Intended audience

This manual addresses the protection and control engineer responsible for planning,pre-engineering and engineering.

The protection and control engineer must be experienced in electrical powerengineering and have knowledge of related technology, such as protection schemesand principles.

1MRS756885 M Section 1Introduction

REM615 5Application Manual

Page 12: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

1.3 Product documentation

1.3.1 Product documentation set

Pla

nnin

g &

pu

rcha

se

Eng

inee

ring

Inst

alla

tion

Com

mis

sion

ing

Ope

ratio

n

Mai

nten

ance

Dec

omm

issi

onin

g,

dein

stal

latio

n &

dis

posa

l

Quick start guideQuick installation guideBrochureProduct guideOperation manualInstallation manualConnection diagramEngineering manualTechnical manualApplication manualCommunication protocol manualIEC 61850 engineering guidePoint list manualCyber security deployment guideline

GUID-12DC16B2-2DC1-48DF-8734-0C8B7116124C V2 EN

Figure 1: The intended use of documents during the product life cycle

Product series- and product-specific manuals can be downloadedfrom the ABB Web site http://www.abb.com/relion.

1.3.2 Document revision historyDocument revision/date Product version HistoryA/2009-07-03 2.0 First release

B/2010-06-11 3.0 Content updated to correspond to theproduct version

C/2010-06-29 3.0 Terminology updated

D/2010-09-24 3.0 Content updated

E/2012-05-11 4.0 Content updated to correspond to theproduct version

F/2013-02-21 4.0 FP1 Content updated to correspond to theproduct version

G/2013-12-20 5.0 Content updated to correspond to theproduct version

Table continues on next page

Section 1 1MRS756885 MIntroduction

6 REM615Application Manual

Page 13: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Document revision/date Product version HistoryH/2014-01-24 5.0 Content updated

K/2015-10-30 5.0 FP1 Content updated to correspond to theproduct version

L/2016-05-20 5.0 FP1 Content updated

M/2018-12-20 5.0 FP1 Content updated

Download the latest documents from the ABB Web sitehttp://www.abb.com/relion.

1.3.3 Related documentationName of the document Document IDModbus Communication Protocol Manual 1MRS756468

DNP3 Communication Protocol Manual 1MRS756709

IEC 60870-5-103 Communication Protocol Manual 1MRS756710

IEC 61850 Engineering Guide 1MRS756475

Engineering Manual 1MRS757121

Installation Manual 1MRS756375

Operation Manual 1MRS756708

Technical Manual 1MRS756887

Cyber Security Deployment Guideline 1MRS758280

1.4 Symbols and conventions

1.4.1 Symbols

The electrical warning icon indicates the presence of a hazard whichcould result in electrical shock.

The warning icon indicates the presence of a hazard which couldresult in personal injury.

The caution icon indicates important information or warning relatedto the concept discussed in the text. It might indicate the presence ofa hazard which could result in corruption of software or damage toequipment or property.

1MRS756885 M Section 1Introduction

REM615 7Application Manual

Page 14: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

The information icon alerts the reader of important facts andconditions.

The tip icon indicates advice on, for example, how to design yourproject or how to use a certain function.

Although warning hazards are related to personal injury, it is necessary to understandthat under certain operational conditions, operation of damaged equipment may resultin degraded process performance leading to personal injury or death. Therefore,comply fully with all warning and caution notices.

1.4.2 Document conventions

A particular convention may not be used in this manual.

• Abbreviations and acronyms are spelled out in the glossary. The glossary alsocontains definitions of important terms.

• Push button navigation in the LHMI menu structure is presented by using thepush button icons.To navigate between the options, use and .

• Menu paths are presented in bold.Select Main menu/Settings.

• LHMI messages are shown in Courier font.To save the changes in nonvolatile memory, select Yes and press .

• Parameter names are shown in italics.The function can be enabled and disabled with the Operation setting.

• Parameter values are indicated with quotation marks.The corresponding parameter values are "On" and "Off".

• Input/output messages and monitored data names are shown in Courier font.When the function starts, the START output is set to TRUE.

• This document assumes that the parameter setting visibility is "Advanced".

1.4.3 Functions, codes and symbolsTable 1: Functions included in the relay

Function IEC 61850 IEC 60617 IEC-ANSIProtection

Three-phase non-directionalovercurrent protection, low stage

PHLPTOC1 3I> (1) 51P-1 (1)

Three-phase non-directionalovercurrent protection, high stage

PHHPTOC1 3I>> (1) 51P-2 (1)

Three-phase non-directionalovercurrent protection,instantaneous stage

PHIPTOC1 3I>>> (1) 50P/51P (1)

Table continues on next page

Section 1 1MRS756885 MIntroduction

8 REM615Application Manual

Page 15: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Function IEC 61850 IEC 60617 IEC-ANSINon-directional earth-faultprotection, low stage

EFLPTOC1 Io> (1) 51N-1 (1)

Non-directional earth-faultprotection, high stage

EFHPTOC1 Io>> (1) 51N-2 (1)

Directional earth-fault protection,low stage

DEFLPDEF1 Io> -> (1) 67N-1 (1)

Three-phase undervoltageprotection

PHPTUV1 3U< (1) 27 (1)

Positive-sequence undervoltageprotection

PSPTUV1 U1< (1) 47U+ (1)

Negative-sequence overvoltageprotection

NSPTOV1 U2> (1) 47O- (1)

Frequency protection FRPFRQ1 f>/f<,df/dt (1) 81 (1)

FRPFRQ2 f>/f<,df/dt (2) 81 (2)

Negative-sequence overcurrentprotection for machines

MNSPTOC1 I2>M (1) 46M (1)

MNSPTOC2 I2>M (2) 46M (2)

Loss of load supervision LOFLPTUC1 3I< (1) 37 (1)

Motor load jam protection JAMPTOC1 Ist> (1) 51LR (1)

Motor start-up supervision STTPMSU1 Is2t n< (1) 49,66,48,51LR (1)

Phase reversal protection PREVPTOC1 I2>> (1) 46R (1)

Thermal overload protection formotors

MPTTR1 3Ith>M (1) 49M (1)

Circuit breaker failure protection CCBRBRF1 3I>/Io>BF (1) 51BF/51NBF (1)

Master trip TRPPTRC1 Master Trip (1) 94/86 (1)

TRPPTRC2 Master Trip (2) 94/86 (2)

TRPPTRC3 Master Trip (3) 94/86 (3)

TRPPTRC4 Master Trip (4) 94/86 (4)

TRPPTRC5 Master Trip (5) 94/86 (5)

Arc protection ARCSARC1 ARC (1) 50L/50NL (1)

ARCSARC2 ARC (2) 50L/50NL (2)

ARCSARC3 ARC (3) 50L/50NL (3)

Table continues on next page

1MRS756885 M Section 1Introduction

REM615 9Application Manual

Page 16: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Function IEC 61850 IEC 60617 IEC-ANSIMultipurpose protection MAPGAPC1 MAP (1) MAP (1)

MAPGAPC2 MAP (2) MAP (2)

MAPGAPC3 MAP (3) MAP (3)

MAPGAPC4 MAP (4) MAP (4)

MAPGAPC5 MAP (5) MAP (5)

MAPGAPC6 MAP (6) MAP (6)

MAPGAPC7 MAP (7) MAP (7)

MAPGAPC8 MAP (8) MAP (8)

MAPGAPC9 MAP (9) MAP (9)

MAPGAPC10 MAP (10) MAP (10)

MAPGAPC11 MAP (11) MAP (11)

MAPGAPC12 MAP (12) MAP (12)

MAPGAPC13 MAP (13) MAP (13)

MAPGAPC14 MAP (14) MAP (14)

MAPGAPC15 MAP (15) MAP (15)

MAPGAPC16 MAP (16) MAP (16)

MAPGAPC17 MAP (17) MAP (17)

MAPGAPC18 MAP (18) MAP (18)

Control

Circuit-breaker control CBXCBR1 I <-> O CB (1) I <-> O CB (1)

Disconnector control DCXSWI1 I <-> O DCC (1) I <-> O DCC (1)

DCXSWI2 I <-> O DCC (2) I <-> O DCC (2)

Earthing switch control ESXSWI1 I <-> O ESC (1) I <-> O ESC (1)

Disconnector position indication DCSXSWI1 I <-> O DC (1) I <-> O DC (1)

DCSXSWI2 I <-> O DC (2) I <-> O DC (2)

DCSXSWI3 I <-> O DC (3) I <-> O DC (3)

Earthing switch indication ESSXSWI1 I <-> O ES (1) I <-> O ES (1)

ESSXSWI2 I <-> O ES (2) I <-> O ES (2)

Emergency start-up ESMGAPC1 ESTART (1) ESTART (1)

Condition monitoring and supervision

Circuit-breaker conditionmonitoring

SSCBR1 CBCM (1) CBCM (1)

Trip circuit supervision TCSSCBR1 TCS (1) TCM (1)

TCSSCBR2 TCS (2) TCM (2)

Current circuit supervision CCSPVC1 MCS 3I (1) MCS 3I (1)

Fuse failure supervision SEQSPVC1 FUSEF (1) 60 (1)

Runtime counter for machines anddevices

MDSOPT1 OPTS (1) OPTM (1)

Measurement

Disturbance recorder RDRE1 DR (1) DFR (1)

Table continues on next page

Section 1 1MRS756885 MIntroduction

10 REM615Application Manual

Page 17: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Function IEC 61850 IEC 60617 IEC-ANSILoad profile record LDPRLRC1 LOADPROF (1) LOADPROF (1)

Fault record FLTRFRC1 FAULTREC (1) FAULTREC (1)

Three-phase current measurement CMMXU1 3I (1) 3I (1)

Sequence current measurement CSMSQI1 I1, I2, I0 (1) I1, I2, I0 (1)

Residual current measurement RESCMMXU1 Io (1) In (1)

Three-phase voltage measurement VMMXU1 3U (1) 3V (1)

Residual voltage measurement RESVMMXU1 Uo (1) Vn (1)

Sequence voltage measurement VSMSQI1 U1, U2, U0 (1) V1, V2, V0 (1)

Three-phase power and energymeasurement

PEMMXU1 P, E (1) P, E (1)

RTD/mA measurement XRGGIO130 X130 (RTD) (1) X130 (RTD) (1)

Frequency measurement FMMXU1 f (1) f (1)

IEC 61850-9-2 LE sampled valuesending

SMVSENDER SMVSENDER SMVSENDER

IEC 61850-9-2 LE sampled valuereceiving (voltage sharing)

SMVRCV SMVRCV SMVRCV

Other

Minimum pulse timer (2 pcs) TPGAPC1 TP (1) TP (1)

TPGAPC2 TP (2) TP (2)

TPGAPC3 TP (3) TP (3)

TPGAPC4 TP (4) TP (4)

Minimum pulse timer (2 pcs,second resolution)

TPSGAPC1 TPS (1) TPS (1)

Minimum pulse timer (2 pcs, minuteresolution)

TPMGAPC1 TPM (1) TPM (1)

Pulse timer (8 pcs) PTGAPC1 PT (1) PT (1)

PTGAPC2 PT (2) PT (2)

Time delay off (8 pcs) TOFGAPC1 TOF (1) TOF (1)

TOFGAPC2 TOF (2) TOF (2)

TOFGAPC3 TOF (3) TOF (3)

TOFGAPC4 TOF (4) TOF (4)

Time delay on (8 pcs) TONGAPC1 TON (1) TON (1)

TONGAPC2 TON (2) TON (2)

TONGAPC3 TON (3) TON (3)

TONGAPC4 TON (4) TON (4)

Set-reset (8 pcs) SRGAPC1 SR (1) SR (1)

SRGAPC2 SR (2) SR (2)

SRGAPC3 SR (3) SR (3)

SRGAPC4 SR (4) SR (4)

Move (8 pcs) MVGAPC1 MV (1) MV (1)

MVGAPC2 MV (2) MV (2)

Table continues on next page

1MRS756885 M Section 1Introduction

REM615 11Application Manual

Page 18: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Function IEC 61850 IEC 60617 IEC-ANSIGeneric control point (16 pcs) SPCGAPC1 SPC (1) SPC (1)

SPCGAPC2 SPC (2) SPC (2)

Analog value scaling SCA4GAPC1 SCA4 (1) SCA4 (1)

SCA4GAPC2 SCA4 (2) SCA4 (2)

SCA4GAPC3 SCA4 (3) SCA4 (3)

SCA4GAPC4 SCA4 (4) SCA4 (4)

Integer value move MVI4GAPC1 MVI4 (1) MVI4 (1)

Section 1 1MRS756885 MIntroduction

12 REM615Application Manual

Page 19: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Section 2 REM615 overview

2.1 Overview

REM615 is a dedicated motor protection and control relay designed for the protection,control, measurement and supervision of asynchronous motors in manufacturing andprocess industry. REM615 is a member of ABB’s Relion® product family and part ofits 615 protection and control product series. The 615 series relays are characterizedby their compactness and withdrawable-unit design.

Re-engineered from the ground up, the 615 series has been designed to unleash the fullpotential of the IEC 61850 standard for communication and interoperability betweensubstation automation devices. Once the standard configuration relay has been giventhe application-specific settings, it can directly be put into service.

The 615 series relays support a range of communication protocols including IEC61850 with Edition 2 support, process bus according to IEC 61850-9-2 LE, IEC60870-5-103, Modbus® and DNP3. Profibus DPV1 communication protocol issupported by using the protocol converter SPA-ZC 302.

2.1.1 Product version historyProduct version Product history2.0 Product released

3.0 • New configurations A and B• Additions to configuration C• Application configurability support• Analog GOOSE support• Large display with single line diagram• Enhanced mechanical design• Increased maximum amount of events and fault records• Frequency measurement and protection• RTD/mA measurement and protection• Multi-port Ethernet option

4.0 • Additions/changes for configurations A-C• Dual fiber optic Ethernet communication option (COM0032)• Generic control point (SPCGGIO) function blocks• Additional logic blocks• Button object for SLD• Controllable disconnector and earth switch objects for SLD• Additional multi-purpose protection instances• Increased maximum amount of events and fault records

Table continues on next page

1MRS756885 M Section 2REM615 overview

REM615 13Application Manual

Page 20: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Product version Product history4.0 FP1 • High-availability seamless redundancy (HSR) protocol

• Parallel redundancy protocol (PRP-1)• Parallel use of IEC 61850 and DNP3 protocols• Parallel use of IEC 61850 and IEC 60870-5-103 protocols• Two selectable indication colors for LEDs (red or green)• Online binary signal monitoring with PCM600

5.0 • New configuration D• New layout in Application Configuration tool for all configurations• Support for IEC 61850-9-2 LE• IEEE 1588 v2 time synchronization• Load profile recorder• High-speed binary outputs• Profibus adapter support• Support for multiple SLD pages• Import/export of settings via WHMI• Setting usability improvements• HMI event filtering tool

5.0 FP1 • IEC 61850 Edition 2• Currents sending support with IEC 61850-9-2 LE• Support for configuration migration (starting from Ver.3.0 to Ver.5.0 FP1)• Software closable Ethernet ports• Chinese language support• Report summary via WHMI• Additional timer, set-reset and analog value scaling functions

2.1.2 PCM600 and relay connectivity package version

• Protection and Control IED Manager PCM600 2.6 (Rollup 20150626) or later• REM615 Connectivity Package Ver.5.1 or later

• Parameter Setting• Signal Monitoring• Event Viewer• Disturbance Handling• Application Configuration• Signal Matrix• Graphical Display Editor• Communication Management• IED User Management• IED Compare• Firmware Update• Fault Record tool• Load Record Profile• Lifecycle Traceability• Configuration Wizard• AR Sequence Visualizer• Label Printing• IEC 61850 Configuration• IED Configuration Migration

Section 2 1MRS756885 MREM615 overview

14 REM615Application Manual

Page 21: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Download connectivity packages from the ABB Web sitehttp://www.abb.com/substationautomation or directly with UpdateManager in PCM600.

2.2 Operation functionality

2.2.1 Optional functions

• Arc protection• Modbus TCP/IP or RTU/ASCII• IEC 60870-5-103• DNP3 TCP/IP or serial• RTD/mA measurements and multipurpose protection (configurations A and B

only)• IEC 61850-9-2 LE (configurations B, C and D only)• IEEE 1588 v2 time synchronization

2.3 Physical hardware

The protection relay consists of two main parts: plug-in unit and case. The contentdepends on the ordered functionality.

1MRS756885 M Section 2REM615 overview

REM615 15Application Manual

Page 22: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Table 2: Plug-in unit and case

Main unit Slot ID Content optionsPlug-inunit

- HMI Small (5 lines, 20 characters)Large (10 lines, 20 characters) with SLD

Small Chinese (3 lines, 8 or more characters)Large Chinese (7 lines, 8 or more characters) withSLD

X100 Auxiliary power/BOmodule

48...250 V DC/100...240 V AC; or 24...60 V DC2 normally-open PO contacts1 change-over SO contact1 normally-open SO contact2 double-pole PO contacts with TCS1 dedicated internal fault output contact

X110 1) BIO module 8 binary inputs4 signal output contacts

BIO module 8 binary inputs3 HSO contacts

X120 AI/BI module Only with configurations A and C:3 phase current inputs (1/5 A)1 residual current input (1/5 A or 0.2/1 A)2)

4 binary inputs

AI/BI module Only with configuration B:3 phase current inputs (1/5 A)1 residual current input (1/5 A or 0.2/1 A)2)

3 phase voltage inputs (60...210 V)

Case X130 AI/BI module Only with configuration C:3 phase voltage inputs (60...210 V)1 residual voltage input (60...210 V)4 binary inputs

Optional RTD/mA module Optional for configurations A and B:2 generic mA inputs6 RTD sensor inputs

Optional BIO module Optional for configuration B:6 binary inputs3 signal output contacts

Sensor input module Only with standard configuration D:3 combi sensor inputs (three-phase current andvoltage)1 residual current input (0.2/1 A)1)

X000 Optional communicationmodule

See the technical manual for details about differenttypes of communication modules.

1) BIO module (X110) is optional for configuration A.2) The 0.2/1 A input is normally used in applications requiring sensitive earth-fault protection and featuring

core-balance current transformers.

Rated values of the current and voltage inputs are basic setting parameters of theprotection relay. The binary input thresholds are selectable within the range 16…176V DC by adjusting the binary input setting parameters.

The connection diagrams of different hardware modules are presented in this manual.

Section 2 1MRS756885 MREM615 overview

16 REM615Application Manual

Page 23: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

See the installation manual for more information about the case andthe plug-in unit.

Table 3: Input/output overview

Std.conf.

Order code digit Analog channels Binary channels 5-6 7-8 CT VT Combi

sensorBI BO RTD mA

AAC / AD

AB 4 - - 4 4 PO+ 2 SO

- -

AD 4 - - 12 4 PO+ 6 SO

- -

FE

4 - - 12 4 PO+ 2 SO+ 3HSO

- -

AG / AH AB 4 - - 4 4 PO+ 2 SO

6 2

B

CA / CB

AH 4 3 - 8 4 PO+ 6 SO

- -

AJ 4 3 - 14 4 PO+ 9 SO

- -

FD

4 3 - 8 4 PO+ 2 SO+ 3HSO

- -

FF

4 3 - 14 4 PO+ 5 SO+ 3HSO

- -

CC /CD

AH 4 3 - 8 4 PO+ 6 SO

6 2

FD

4 3 - 8 4 PO+ 2 SO+ 3HSO

6 2

C AE / AF

AG 4 5 - 16 4 PO+ 6 SO

- -

FC

4 5 - 16 4 PO+ 2 SO+ 3HSO

- -

D DA

AH 1 - 3 8 4 PO+ 6 SO

- -

FD

1 - 3 8 4 PO+ 2 SO+ 3HSO

- -

1MRS756885 M Section 2REM615 overview

REM615 17Application Manual

Page 24: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

2.4 Local HMI

The LHMI is used for setting, monitoring and controlling the protection relay. TheLHMI comprises the display, buttons, LED indicators and communication port.

REF615

Overcurrent

Dir. earth-fault

Voltage protection

Phase unbalance

Thermal overload

Breaker failure

Disturb. rec. Triggered

CB condition monitoring

Supervision

Arc detected

Autoreclose shot in progr.

A070704 V4 EN

Figure 2: Example of the LHMI

2.4.1 Display

The LHMI includes a graphical display that supports two character sizes. Thecharacter size depends on the selected language. The amount of characters and rowsfitting the view depends on the character size.

Table 4: Small display

Character size1) Rows in the view Characters per row

Small, mono-spaced (6 × 12 pixels) 5 20

Large, variable width (13 × 14 pixels) 3 8 or more

1) Depending on the selected language

Section 2 1MRS756885 MREM615 overview

18 REM615Application Manual

Page 25: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Table 5: Large display

Character size1) Rows in the view Characters per row

Small, mono-spaced (6 × 12 pixels) 10 20

Large, variable width (13 × 14 pixels) 7 8 or more

1) Depending on the selected language

The display view is divided into four basic areas.

1 2

3 4A070705 V3 EN

Figure 3: Display layout

1 Header

2 Icon

3 Content

4 Scroll bar (displayed when needed)

2.4.2 LEDs

The LHMI includes three protection indicators above the display: Ready, Start andTrip.

There are 11 matrix programmable LEDs on front of the LHMI. The LEDs can beconfigured with PCM600 and the operation mode can be selected with the LHMI,WHMI or PCM600.

2.4.3 Keypad

The LHMI keypad contains push buttons which are used to navigate in different viewsor menus. With the push buttons you can give open or close commands to objects inthe primary circuit, for example, a circuit breaker, a contactor or a disconnector. The

1MRS756885 M Section 2REM615 overview

REM615 19Application Manual

Page 26: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

push buttons are also used to acknowledge alarms, reset indications, provide help andswitch between local and remote control mode.

A071176 V1 EN

Figure 4: LHMI keypad with object control, navigation and command pushbuttons and RJ-45 communication port

2.5 Web HMI

The WHMI allows secure access to the protection relay via a Web browser. When theSecure Communication parameter in the protection relay is activated, the Web serveris forced to take a secured (HTTPS) connection to WHMI using TLS encryption.TheWHMI is verified with Internet Explorer 8.0, 9.0, 10.0 and 11.0.

WHMI is disabled by default.

WHMI offers several functions.

• Programmable LEDs and event lists• System supervision• Parameter settings• Measurement display• Disturbance records• Fault records• Load profile record• Phasor diagram• Single-line diagram• Importing/Exporting parameters• Report summary

The menu tree structure on the WHMI is almost identical to the one on the LHMI.

Section 2 1MRS756885 MREM615 overview

20 REM615Application Manual

Page 27: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

A070754 V6 EN

Figure 5: Example view of the WHMI

The WHMI can be accessed locally and remotely.

• Locally by connecting the laptop to the protection relay via the frontcommunication port.

• Remotely over LAN/WAN.

2.6 Authorization

Four user categories have been predefined for the LHMI and the WHMI, each withdifferent rights and default passwords.

The default passwords in the protection relay delivered from the factory can bechanged with Administrator user rights.

User authorization is disabled by default for LHMI but WHMI alwaysuses authorization.

1MRS756885 M Section 2REM615 overview

REM615 21Application Manual

Page 28: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Table 6: Predefined user categories

Username User rightsVIEWER Read only access

OPERATOR • Selecting remote or local state with (only locally)• Changing setting groups• Controlling• Clearing indications

ENGINEER • Changing settings• Clearing event list• Clearing disturbance records• Changing system settings such as IP address, serial baud rate or

disturbance recorder settings• Setting the protection relay to test mode• Selecting language

ADMINISTRATOR • All listed above• Changing password• Factory default activation

For user authorization for PCM600, see PCM600 documentation.

2.6.1 Audit trail

The protection relay offers a large set of event-logging functions. Critical system andprotection relay security-related events are logged to a separate nonvolatile audit trailfor the administrator.

Audit trail is a chronological record of system activities that allows the reconstructionand examination of the sequence of system and security-related events and changes inthe protection relay. Both audit trail events and process related events can beexamined and analyzed in a consistent method with the help of Event List in LHMIand WHMI and Event Viewer in PCM600.

The protection relay stores 2048 audit trail events to the nonvolatile audit trail.Additionally, 1024 process events are stored in a nonvolatile event list. Both the audittrail and event list work according to the FIFO principle. Nonvolatile memory is basedon a memory type which does not need battery backup nor regular component changeto maintain the memory storage.

Audit trail events related to user authorization (login, logout, violation remote andviolation local) are defined according to the selected set of requirements from IEEE1686. The logging is based on predefined user names or user categories. The user audittrail events are accessible with IEC 61850-8-1, PCM600, LHMI and WHMI.

Section 2 1MRS756885 MREM615 overview

22 REM615Application Manual

Page 29: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Table 7: Audit trail events

Audit trail event DescriptionConfiguration change Configuration files changed

Firmware change Firmware changed

Firmware change fail Firmware change failed

Attached to retrofit test case Unit has been attached to retrofit case

Removed from retrofit test case Removed from retrofit test case

Setting group remote User changed setting group remotely

Setting group local User changed setting group locally

Control remote DPC object control remote

Control local DPC object control local

Test on Test mode on

Test off Test mode off

Reset trips Reset latched trips (TRPPTRC*)

Setting commit Settings have been changed

Time change Time changed directly by the user. Note that this is not usedwhen the protection relay is synchronised properly by theappropriate protocol (SNTP, IRIG-B, IEEE 1588 v2).

View audit log Administrator accessed audit trail

Login Successful login from IEC 61850-8-1 (MMS), WHMI, FTP orLHMI.

Logout Successful logout from IEC 61850-8-1 (MMS), WHMI, FTP orLHMI.

Password change Password changed

Firmware reset Reset issued by user or tool

Audit overflow Too many audit events in the time period

Violation remote Unsuccessful login attempt from IEC 61850-8-1 (MMS),WHMI, FTP or LHMI.

Violation local Unsuccessful login attempt from IEC 61850-8-1 (MMS),WHMI, FTP or LHMI.

PCM600 Event Viewer can be used to view the audit trail events and process relatedevents. Audit trail events are visible through dedicated Security events view. Sinceonly the administrator has the right to read audit trail, authorization must be used inPCM600. The audit trail cannot be reset, but PCM600 Event Viewer can filter data.Audit trail events can be configured to be visible also in LHMI/WHMI Event listtogether with process related events.

To expose the audit trail events through Event list, define theAuthority logging level parameter via Configuration/Authorization/Security. This exposes audit trail events to all users.

1MRS756885 M Section 2REM615 overview

REM615 23Application Manual

Page 30: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Table 8: Comparison of authority logging levels

Audit trail event Authority logging level

NoneConfiguration change

Settinggroup

Settinggroup,control

Settingsedit

All

Configuration change ● ● ● ● ●

Firmware change ● ● ● ● ●

Firmware change fail ● ● ● ● ●

Attached to retrofit testcase

● ● ● ● ●

Removed from retrofittest case

● ● ● ● ●

Setting group remote ● ● ● ●

Setting group local ● ● ● ●

Control remote ● ● ●

Control local ● ● ●

Test on ● ● ●

Test off ● ● ●

Reset trips ● ● ●

Setting commit ● ●

Time change ●

View audit log ●

Login ●

Logout ●

Password change ●

Firmware reset ●

Violation local ●

Violation remote ●

2.7 Communication

The protection relay supports a range of communication protocols including IEC61850, IEC 61850-9-2 LE, IEC 60870-5-103, Modbus® and DNP3. Profibus DPV1communication protocol is supported by using the protocol converter SPA-ZC 302.Operational information and controls are available through these protocols. However,some communication functionality, for example, horizontal communication betweenthe protection relays, is only enabled by the IEC 61850 communication protocol.

The IEC 61850 communication implementation supports all monitoring and controlfunctions. Additionally, parameter settings, disturbance recordings and fault recordscan be accessed using the IEC 61850 protocol. Disturbance recordings are availableto any Ethernet-based application in the IEC 60255-24 standard COMTRADE fileformat. The protection relay can send and receive binary signals from other devices

Section 2 1MRS756885 MREM615 overview

24 REM615Application Manual

Page 31: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

(so-called horizontal communication) using the IEC 61850-8-1 GOOSE profile,where the highest performance class with a total transmission time of 3 ms issupported. Furthermore, the protection relay supports sending and receiving of analogvalues using GOOSE messaging. The protection relay meets the GOOSEperformance requirements for tripping applications in distribution substations, asdefined by the IEC 61850 standard.

The protection relay can support five simultaneous clients. If PCM600 reserves oneclient connection, only four client connections are left, for example, for IEC 61850and Modbus.

All communication connectors, except for the front port connector, are placed onintegrated optional communication modules. The protection relay can be connected toEthernet-based communication systems via the RJ-45 connector (100Base-TX) or thefiber-optic LC connector (100Base-FX).

2.7.1 Self-healing Ethernet ring

For the correct operation of self-healing loop topology, it is essential that the externalswitches in the network support the RSTP protocol and that it is enabled in theswitches. Otherwise, connecting the loop topology can cause problems to thenetwork. The protection relay itself does not support link-down detection or RSTP.The ring recovery process is based on the aging of the MAC addresses, and the link-up/link-down events can cause temporary breaks in communication. For a betterperformance of the self-healing loop, it is recommended that the external switchfurthest from the protection relay loop is assigned as the root switch (bridge priority= 0) and the bridge priority increases towards the protection relay loop. The end linksof the protection relay loop can be attached to the same external switch or to twoadjacent external switches. A self-healing Ethernet ring requires a communicationmodule with at least two Ethernet interfaces for all protection relays.

1MRS756885 M Section 2REM615 overview

REM615 25Application Manual

Page 32: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Managed Ethernet switchwith RSTP support

Managed Ethernet switchwith RSTP support

Client BClient A

Network ANetwork B

GUID-283597AF-9F38-4FC7-B87A-73BFDA272D0F V3 EN

Figure 6: Self-healing Ethernet ring solution

The Ethernet ring solution supports the connection of up to 30protection relays. If more than 30 protection relays are to beconnected, it is recommended that the network is split into severalrings with no more than 30 protection relays per ring. Each protectionrelay has a 50-μs store-and-forward delay, and to fulfil theperformance requirements for fast horizontal communication, thering size is limited to 30 protection relays.

2.7.2 Ethernet redundancy

IEC 61850 specifies a network redundancy scheme that improves the systemavailability for substation communication. It is based on two complementaryprotocols defined in the IEC 62439-3:2012 standard: parallel redundancy protocolPRP and high-availability seamless redundancy HSR protocol. Both protocols rely onthe duplication of all transmitted information via two Ethernet ports for one logicalnetwork connection. Therefore, both are able to overcome the failure of a link orswitch with a zero-switchover time, thus fulfilling the stringent real-timerequirements for the substation automation horizontal communication and timesynchronization.

PRP specifies that each device is connected in parallel to two local area networks.HSR applies the PRP principle to rings and to the rings of rings to achieve cost-effective redundancy. Thus, each device incorporates a switch element that forwardsframes from port to port. The HSR/PRP option is available for all 615 series protectionrelays. However, RED615 supports this option only over fiber optics.

Section 2 1MRS756885 MREM615 overview

26 REM615Application Manual

Page 33: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

IEC 62439-3:2012 cancels and replaces the first edition published in2010. These standard versions are also referred to as IEC 62439-3Edition 1 and IEC 62439-3 Edition 2. The protection relay supportsIEC 62439-3:2012 and it is not compatible with IEC 62439-3:2010.

PRPEach PRP node, called a double attached node with PRP (DAN), is attached to twoindependent LANs operated in parallel. These parallel networks in PRP are calledLAN A and LAN B. The networks are completely separated to ensure failureindependence, and they can have different topologies. Both networks operate inparallel, thus providing zero-time recovery and continuous checking of redundancy toavoid communication failures. Non-PRP nodes, called single attached nodes (SANs),are either attached to one network only (and can therefore communicate only withDANs and SANs attached to the same network), or are attached through a redundancybox, a device that behaves like a DAN.

Ethernet switchIEC 61850 PRPEthernet switch

SCADACOM600

GUID-334D26B1-C3BD-47B6-BD9D-2301190A5E9D V2 EN

Figure 7: PRP solution

In case a laptop or a PC workstation is connected as a non-PRP node to one of the PRPnetworks, LAN A or LAN B, it is recommended to use a redundancy box device or anEthernet switch with similar functionality between the PRP network and SAN toremove additional PRP information from the Ethernet frames. In some cases, defaultPC workstation adapters are not able to handle the maximum-length Ethernet frameswith the PRP trailer.

There are different alternative ways to connect a laptop or a workstation as SAN to aPRP network.

1MRS756885 M Section 2REM615 overview

REM615 27Application Manual

Page 34: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

• Via an external redundancy box (RedBox) or a switch capable of connecting toPRP and normal networks

• By connecting the node directly to LAN A or LAN B as SAN• By connecting the node to the protection relay's interlink port

HSRHSR applies the PRP principle of parallel operation to a single ring, treating the twodirections as two virtual LANs. For each frame sent, a node, DAN, sends two frames,one over each port. Both frames circulate in opposite directions over the ring and eachnode forwards the frames it receives, from one port to the other. When the originatingnode receives a frame sent to itself, it discards that to avoid loops; therefore, no ringprotocol is needed. Individually attached nodes, SANs, such as laptops and printers,must be attached through a “redundancy box” that acts as a ring element. For example,a 615 or 620 series protection relay with HSR support can be used as a redundancybox.

GUID-207430A7-3AEC-42B2-BC4D-3083B3225990 V2 EN

Figure 8: HSR solution

2.7.3 Process bus

Process bus IEC 61850-9-2 defines the transmission of Sampled Measured Valueswithin the substation automation system. International Users Group created aguideline IEC 61850-9-2 LE that defines an application profile of IEC 61850-9-2 tofacilitate implementation and enable interoperability. Process bus is used fordistributing process data from the primary circuit to all process bus compatibledevices in the local network in a real-time manner. The data can then be processed byany protection relay to perform different protection, automation and control functions.

Section 2 1MRS756885 MREM615 overview

28 REM615Application Manual

Page 35: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

UniGear Digital switchgear concept relies on the process bus together with currentand voltage sensors. The process bus enables several advantages for the UniGearDigital like simplicity with reduced wiring, flexibility with data availability to alldevices, improved diagnostics and longer maintenance cycles.

With process bus the galvanic interpanel wiring for sharing busbar voltage value canbe replaced with Ethernet communication. Transmitting measurement samples overprocess bus brings also higher error detection because the signal transmission isautomatically supervised. Additional contribution to the higher availability is thepossibility to use redundant Ethernet network for transmitting SMV signals.

Common EthernetStation bus (IEC 61850-8-1), process bus (IEC 61850-9-2 LE) and IEEE 1588 v2 time synchronization

GO

OS

E

SM

V

GO

OS

E

SM

V

SM

V

GO

OS

E

GO

OS

E

SM

V

GO

OS

E

SM

V

SM

V

GO

OS

E

SM

V

GO

OS

E

GUID-2371EFA7-4369-4F1A-A23F-CF0CE2D474D3 V5 EN

Figure 9: Process bus application of voltage sharing and synchrocheck

The 615 series supports IEC 61850 process bus with sampled values of analogcurrents and voltages. The measured values are transferred as sampled values usingthe IEC 61850-9-2 LE protocol which uses the same physical Ethernet network as theIEC 61850-8-1 station bus. The intended application for sampled values is sharing themeasured voltages from one 615 series protection relay to other devices with phasevoltage based functions and 9-2 support.

The 615 series protection relays with process bus based applications use IEEE 1588 v2Precision Time Protocol (PTP) according to IEEE C37.238-2011 Power Profile forhigh accuracy time synchronization. With IEEE 1588 v2, the cabling infrastructurerequirement is reduced by allowing time synchronization information to betransported over the same Ethernet network as the data communications.

1MRS756885 M Section 2REM615 overview

REM615 29Application Manual

Page 36: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

IEC 61850

HSR

SMV

tra

ffic

Backup 1588

master clock

Managed HSR

Ethernet

switch

Primary

IEEE 1588 v2

master clock

Secondary

IEEE 1588 v2

master clock

(optional)

Managed HSR

Ethernet

switch

GUID-7C56BC1F-F1B2-4E74-AB8E-05001A88D53D V5 EN

Figure 10: Example network topology with process bus, redundancy and IEEE1588 v2 time synchronization

The process bus option is available for all 615 series protection relays equipped withphase voltage inputs. Another requirement is a communication card with IEEE 1588v2 support (COM0031...COM0037). However, RED615 supports this option onlywith the communication card variant having fiber optic station bus ports. See the IEC61850 engineering guide for detailed system requirements and configuration details.

2.7.4 Secure communication

The protection relay supports secure communication for WHMI and file transferprotocol. If the Secure Communication parameter is activated, protocols require TLSbased encryption method support from the clients. In this case WHMI must beconnected from a Web browser using the HTTPS protocol and in case of file transferthe client must use FTPS.

Section 2 1MRS756885 MREM615 overview

30 REM615Application Manual

Page 37: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Section 3 REM615 standard configurations

3.1 Standard configuration

REM615 is available with four alternative standard configurations. The standardsignal configuration can be altered by means of the graphical signal matrix or thegraphical application functionality of the Protection and Control IED ManagerPCM600. Further, the application configuration functionality of the relay supports thecreation of multi-layer logic functions using various logical elements including timersand flip-flops. By combining protection functions with logic function blocks, the relayconfiguration can be adapted to user-specific application requirements.

The relay is delivered from the factory with default connections described in thefunctional diagrams for binary inputs, binary outputs, function-to-functionconnections and alarm LEDs. Some of the supported functions in REM615 must beadded with the Application Configuration tool to be available in the Signal Matrix tooland in the relay. The positive measuring direction of directional protection functionsis towards the outgoing feeder.

Table 9: Standard configuration

Description Std.conf.Basic motor protection (RTD option) A

Motor protection with voltage and frequency based protection and measurements (RTDoption) B

Motor protection with voltage and frequency based protection and measurements C

Motor protection with voltage and frequency based protection and measurements(sensor inputs) D

Table 10: Supported functions

Function IEC 61850 A B C DProtectionThree-phase non-directional overcurrent protection, lowstage

PHLPTOC 1 1 1 1

Three-phase non-directional overcurrent protection, highstage

PHHPTOC 1 1 1 1

Three-phase non-directional overcurrent protection,instantaneous stage

PHIPTOC 1 1 1 1

Non-directional earth-fault protection, low stage EFLPTOC 1 Non-directional earth-fault protection, high stage EFHPTOC 1 1 1 1Directional earth-fault protection, low stage DEFLPDEF 11) 1 11)

Three-phase undervoltage protection PHPTUV 1 1 1Positive-sequence undervoltage protection PSPTUV 1 1 1Negative-sequence overvoltage protection NSPTOV 1 1 1Frequency protection FRPFRQ 2 2 2

Table continues on next page

1MRS756885 M Section 3REM615 standard configurations

REM615 31Application Manual

Page 38: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Function IEC 61850 A B C DNegative-sequence overcurrent protection for machines MNSPTOC 2 2 2 2Loss of load supervision LOFLPTUC 1 1 1 1Motor load jam protection JAMPTOC 1 1 1 1Motor start-up supervision STTPMSU 1 1 1 1Phase reversal protection PREVPTOC 1 1 1 1Thermal overload protection for motors MPTTR 1 1 1 1Circuit breaker failure protection CCBRBRF 1 1 1 1Master trip TRPPTRC 2

(3) 2)2(3) 2)

2(3) 2)

2(3) 2)

Arc protection ARCSARC (3) (3) (3) (3)Multipurpose protection MAPGAPC 18 18 18 18ControlCircuit-breaker control CBXCBR 1 1 1 1Disconnector control DCXSWI 2 2 2 2Earthing switch control ESXSWI 1 1 1 1Disconnector position indication DCSXSWI 3 3 3 3Earthing switch indication ESSXSWI 2 2 2 2Emergency start-up ESMGAPC 1 1 1 1Condition monitoring and supervisionCircuit-breaker condition monitoring SSCBR 1 1 1 1Trip circuit supervision TCSSCBR 2 2 2 2Current circuit supervision CCSPVC 1 1 1 1Fuse failure supervision SEQSPVC 1 1 1Runtime counter for machines and devices MDSOPT 1 1 1 1MeasurementDisturbance recorder RDRE 1 1 1 1Load profile record LDPRLRC 1 1 1 1Fault record FLTRFRC 1 1 1 1Three-phase current measurement CMMXU 1 1 1 1Sequence current measurement CSMSQI 1 1 1 1Residual current measurement RESCMMXU 1 1 1 1Three-phase voltage measurement VMMXU 1 1 1Residual voltage measurement RESVMMXU 1 Sequence voltage measurement VSMSQI 1 1 1Three-phase power and energy measurement PEMMXU 1 1 1RTD/mA measurement XRGGIO130 (1) (1) Frequency measurement FMMXU1 1 1 1

IEC 61850-9-2 LE sampled value sending 3)4) SMVSENDER (1) (1) (1)

IEC 61850-9-2 LE sampled value receiving (voltage sharing)3)4)

SMVRCV (1) (1) (1)

OtherMinimum pulse timer (2 pcs) TPGAPC 4 4 4 4Minimum pulse timer (2 pcs, second resolution) TPSGAPC 1 1 1 1Minimum pulse timer (2 pcs, minute resolution) TPMGAPC 1 1 1 1Pulse timer (8 pcs) PTGAPC 2 2 2 2Time delay off (8 pcs) TOFGAPC 4 4 4 4Time delay on (8 pcs) TONGAPC 4 4 4 4Set-reset (8 pcs) SRGAPC 4 4 4 4Move (8 pcs) MVGAPC 2 2 2 2Generic control point (16 pcs) SPCGAPC 2 2 2 2

Table continues on next page

Section 3 1MRS756885 MREM615 standard configurations

32 REM615Application Manual

Page 39: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Function IEC 61850 A B C DAnalog value scaling (4 pcs) SCA4GAPC 4 4 4 4Integer value move (4 pcs) MVI4GAPC 1 1 1 11, 2, ... = Number of included instances. The instances of a protection function represent the number of identical protection function blocks available in thestandard configuration.() = optional

1) "Uo calculated" is always used.2) Master trip is included and connected to the corresponding HSO in the configuration only when the BIO0007 module is used. If additionally

the ARC option is selected, ARCSARC is connected in the configuration to the corresponding master trip input.3) Available only with IEC 61850-9-24) Available only with COM0031-0037

3.1.1 Addition of control functions for primary devices and the useof binary inputs and outputs

If extra control functions intended for controllable primary devices are added to theconfiguration, additional binary inputs and/or outputs are needed to complement thestandard configuration.

If the number of inputs and/or outputs in a standard configuration is not sufficient, itis possible either to modify the chosen standard configuration in order to release somebinary inputs or binary outputs which have originally been configured for otherpurposes, or to integrate an external input/output module, for example RIO600, to theprotection relay.

The external I/O module’s binary inputs and outputs can be used for the less time-critical binary signals of the application. The integration enables releasing someinitially reserved binary inputs and outputs of the protection relay’s standardconfiguration.

The suitability of the protection relay’s binary outputs which have been selected forprimary device control should be carefully verified, for example make and carry andbreaking capacity. If the requirements for the primary device control circuit are notmet, using external auxiliary relays should be considered.

1MRS756885 M Section 3REM615 standard configurations

REM615 33Application Manual

Page 40: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

3.2 Connection diagrams

GUID-3B376A84-ACD8-4641-965F-1E83998849DC V1 EN

Figure 11: Connection diagram for the A configuration

Section 3 1MRS756885 MREM615 standard configurations

34 REM615Application Manual

Page 41: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

GUID-1596C4FB-2B52-431E-8CF8-F0D4E8797542 V1 EN

Figure 12: Connection diagram for the B configuration

1MRS756885 M Section 3REM615 standard configurations

REM615 35Application Manual

Page 42: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

GUID-2A2AFE30-749F-4491-A5C1-1A3FB5DB73E1 V1 EN

Figure 13: Connection diagram for the B configuration (motor protection withphase-to-earth voltage measurement)

Section 3 1MRS756885 MREM615 standard configurations

36 REM615Application Manual

Page 43: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

GUID-E79DC16A-BFCE-4340-88A2-1BAE7035E82F V2 EN

Figure 14: Connection diagram for the C configuration

1MRS756885 M Section 3REM615 standard configurations

REM615 37Application Manual

Page 44: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

GUID-F1C23E9E-B743-4CB1-A744-13281CD5E7DF V1 EN

Figure 15: Connection diagram for the C configuration (motor protection withphase-to-earth voltage measurement)

Section 3 1MRS756885 MREM615 standard configurations

38 REM615Application Manual

Page 45: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

REM615

X13Light sensor input 1 1)

X14Light sensor input 2 1)

X15Light sensor input 3 1)

16

17

1918

X100

67

89

10

111213

15

14

2

1

3

45

22

212324

SO2

TCS2

PO4

SO1

TCS1

PO3

PO2

PO1

IRF

+

-Uaux

20

L1L2L3

P2

P1 S1

S2

X110

34

56

7

89

10BI 6

BI 5

BI 4

BI 3

BI 2

BI 8

BI 712

13

11

BI 112

X110

16

14

15

19

17

18

22

20

21

SO3

SO2

SO1

23SO4

24

PositiveCurrentDirection

1) Optional2) BIO0005 module (8BI+4BO) Alternative module BIO0007 (8BI+3HSO)

M3~

X130

12

X131

45

IL1

78

U1

X132

45

IL2

78

U2

X133

45

IL3

78

U3

Io0,2/1A

N

2) 2)

GUID-A1563EFF-39EC-419A-BED7-BAC7A6FE0713 V1 EN

Figure 16: Connection diagram for the D configuration

3.3 Standard configuration A

3.3.1 Applications

The standard configuration is intended for comprehensive protection and controlfunctionality of circuit breaker controlled asynchronous motors. With minor

1MRS756885 M Section 3REM615 standard configurations

REM615 39Application Manual

Page 46: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

modifications, the standard configuration can also be applied for contactor controlledmotors. There is also an option for mA/RTD measurement and protection.

The protection relay with a standard configuration is delivered from the factory withdefault settings and parameters. The end user flexibility for incoming, outgoing andinternal signal designation within the protection relay enables this configuration to befurther adapted to different primary circuit layouts and the related functionality needsby modifying the internal functionality using PCM600.

3.3.2 Functions

Io

ALSO AVAILABLE

- Disturbance and fault recorders- Event log and recorded data- High-Speed Output module (optional)- Local/Remote push button on LHMI- Self-supervision- Time synchronization: IEEE 1588 v2,

SNTP, IRIG-B- User management- Web HMI

ORAND

REMARKS

Optionalfunction

No. ofinstances

Alternative function to be defined when ordering

OR

Io/Uo

Calculatedvalue

CONTROL AND INDICATION 1) MEASUREMENT

MOTOR PROTECTION AND CONTROL RELAY

PROTECTION LOCAL HMI

Analog interface types 1)

Current transformer

Voltage transformer

1) Conventional transformer inputs

ESTARTESTART

Object Ctrl 2) Ind 3)

CB 1 -

DC 2 3

ES 1 21) Check availability of binary inputs/outputs

from technical documentation2) Control and indication function for

primary object3) Status indication function for primary object

STANDARD CONFIGURATION

RL

ClearESCI

O

Configuration ASystemHMITimeAuthorization

RL

ClearESCI

O

U12 0. 0 kVP 0.00 kWQ 0.00 kVAr

IL2 0 A

A

18×MAPMAP

REM615

- I, Io- Limit value supervision- Load profile record- RTD/mA measurement (optional)- Symmetrical components

4

-

A

6xRTD2xmA

MCS 3IMCS 3I

3×ARC

50L/50NL

Master TripLockout relay

94/86

3I<37

2×I2>M46M

I2>>46R

3Ith>M49M

Is2t n<49, 66, 48, 51LR

3I>>>50P/51P

3I>/Io>BF51BF/51NBF

Ist>51LR

3I>51P-1

Io>>51N-2

Io>51N-1

2×TCSTCM

CBCMCBCM

OPTSOPTM

Io

Io

3I

3×CONDITION MONITORING AND SUPERVISION

COMMUNICATION

Protocols: IEC 61850-8-1 Modbus®

IEC 60870-5-103 DNP3Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232Redundant protocols: HSR PRP RSTP

3I>>51P-2

Master TripLockout relay

94/86

3×2×

GUID-4A93E0BB-46C2-4A06-BC4F-50C42B51366F V2 EN

Figure 17: Functionality overview for standard configuration A

Section 3 1MRS756885 MREM615 standard configurations

40 REM615Application Manual

Page 47: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

3.3.2.1 Default I/O connections

Connector pins for each input and output are presented in the IED physicalconnections section.

Table 11: Default connections for binary inputs

Binary input DescriptionX120-BI1 Emergency start

X120-BI2 Circuit breaker closed

X120-BI3 Circuit breaker open

X120-BI4 External restart inhibit

Table 12: Default connections for mA/RTD inputs

RTD/mA input DescriptionX130-AI1 -

X130-AI2 -

X130-AI3 Motor winding U temperature

X130-AI4 Motor winding V temperature

X130-AI5 Motor winding W temperature

X130-AI6 Motor cooling air temperature

X130-AI7 Motor bearing temperature

X130-AI8 Motor ambient temperature

Table 13: Default connections for binary outputs

Binary output DescriptionX100-PO1 Restart enable

X100-PO2 Breaker failure backup trip to upstream breaker

X100-SO1 Open command (for contractor application)

X100-SO2 Start indication

X100-PO3 Open circuit breaker/trip

X100-PO4 Close circuit breaker

X110-HSO1 Arc protection instance 1 operate activated

X110-HSO2 Arc protection instance 2 operate activated

X110-HSO3 Arc protection instance 3 operate activated

Table 14: Default connections for LEDs

LED Description1 Short-circuit protection operate

2 Earth-fault protection operate

3 Thermal overload protection operate

Table continues on next page

1MRS756885 M Section 3REM615 standard configurations

REM615 41Application Manual

Page 48: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

LED Description4 Combined operate indication of the other protection functions

5 Motor restart inhibit

6 Breaker failure protection operate

7 Disturbance recorder triggered

8 Circuit breaker condition monitoring alarm

9 TCS, motor runtime counter or measuring circuit fault alarm

10 Arc protection operate

11 Emergency start enabled

3.3.2.2 Default disturbance recorder settings

Table 15: Default disturbance recorder analog channels

Channel Description1 IL1

2 IL2

3 IL3

4 Io

5 -

6 -

7 -

8 -

9 -

10 -

11 -

12 -

Table 16: Default disturbance recorder binary channels

Channel ID text Level trigger mode1 PHLPTOC1 - start Positive or Rising

2 PHIPTOC2 - start Positive or Rising

3 EFLPTOC1 - start Positive or Rising

4 EFHPTOC1 - start Positive or Rising

5 MPTTR1 - alarm Level trigger off

6 MPTTR1 - blk restart Level trigger off

7 ESMGAPC1 - st emerg ena Level trigger off

8 STTPMSU1 - mot startup Positive or Rising

9 STTPMSU1 - lock start Level trigger off

10 MNSPTOC1 - start Positive or Rising

11 MNSPTOC1 - blk restart Level trigger off

Table continues on next page

Section 3 1MRS756885 MREM615 standard configurations

42 REM615Application Manual

Page 49: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Channel ID text Level trigger mode12 MNSPTOC2 - start Positive or Rising

13 MNSPTOC2 - blk restart Level trigger off

14 PREVPTOC1 - start Positive or Rising

15 MAPGAPC1 - start Positive or Rising

16 MAPGAPC2 - start Positive or Rising

17 MAPGAPC3 - start Positive or Rising

18 CCBRBRF1 - trret Level trigger off

19 CCBRBRF1 - trbu Level trigger off

20 PHLPTOC1 - operate Level trigger off

21 PHIPTOC2 - operate Level trigger off

22 JAMPTOC1 - operate Level trigger off

23 EFLPTOC1 - operate Level trigger off

EFHPTOC2 - operate

24 MNSPTOC1 - operate Level trigger off

MNSPTOC2 - operate

25 PREVPTOC1 - operate Level trigger off

26 LOFLPTUC1 - operate Level trigger off

27 MPTTR1 - operate Level trigger off

28 MAPGAPC1 - operate Level trigger off

29 MAPGAPC2 - operate Level trigger off

30 MAPGAPC3 - operate Level trigger off

31 X120BI1 - Emerg start ena Level trigger off

32 X120BI2 - CB closed Level trigger off

33 X120BI3 - CB opened Level trigger off

34 X120BI4 - Ext restart inhibit Level trigger off

35 STTPMSU1 - opr iit Positive or Rising

36 CCSPVC1 - fail Level trigger off

37 ARCSARC1 - ARC flt det Level trigger off

ARCSARC2 - ARC flt det

ARCSARC3 - ARC flt det

38 ARCSARC1 - operate Positive or Rising

39 ARCSARC2 - operate Positive or Rising

40 ARCSARC3 - operate Positive or Rising

3.3.3 Functional diagrams

The functional diagrams describe the default input, output, alarm LED and function-to-function connections. The default connections can be viewed and changed withPCM600 according to the application requirements.

1MRS756885 M Section 3REM615 standard configurations

REM615 43Application Manual

Page 50: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

The analog channels have fixed connections to the different function blocks inside theprotection relay’s standard configuration. However, the 12 analog channels availablefor the disturbance recorder function are freely selectable as a part of the disturbancerecorder’s parameter settings.

The phase currents to the protection relay are fed from a current transformer. Theresidual current to the protection relay is fed from either residually connected CTs, anexternal core balance CT, neutral CT or calculated internally.

The protection relay offers six different setting groups which can be set based onindividual needs. Each group can be activated or deactivated using the setting groupsettings available in the protection relay.

Depending on the communication protocol the required function block needs to beinstantiated in the configuration.

3.3.3.1 Functional diagrams for protection

The functional diagrams describe the IEDs protection functionality in detail andaccording to the factory set default connections.

Two overcurrent stages are offered for overcurrent and short-circuit protection. Thenon-directional low stage PHLPTOC1 can be used for overcurrent protection whereasinstantaneous stage PHIPTOC1 can be used for short-circuit protection. Theoperation of PHIPTOC1 is not blocked as default by any functionality and it should beset over the motor start current level to avoid unnecessary operation. The Motor loadjam protection function JAMPTOC1 is blocked by the motor start-up protectionfunction.

PHIPTOC1BLOCKENA_MULT

OPERATESTART

PHLPTOC1BLOCKENA_MULT

OPERATESTART

PHLPTOC1_OPERATE

PHIPTOC1_OPERATEPHIPTOC1_START

PHLPTOC1_START

JAMPTOC1BLOCK OPERATE JAMPTOC1_OPERATESTTPMSU1_MOT_STARTUP

GUID-6418DDC4-68C0-486E-B8C0-11C1F3A9ADE8 V1 EN

Figure 18: Overcurrent protection functions

Two negative-sequence overcurrent protection stages MNSPTOC1 and MNSPTOC2are provided for phase unbalance protection. These functions are used to protect themotor against phase unbalance. Unbalance in the network feeder of the motor causesoverheating of the motor.

Section 3 1MRS756885 MREM615 standard configurations

44 REM615Application Manual

Page 51: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

MNSPTOC1BLOCK OPERATE

STARTBLK_RESTART

MNSPTOC2BLOCK OPERATE

STARTBLK_RESTART

ORB1B2

O

MNSPTOC1_BLK_RESTART

MNSPTOC2_BLK_RESTART

MNSPTOC1_OPERATE

MNSPTOC1_OPERATE

MNSPTOC2_OPERATE

MNSPTOC2_OPERATE

MNSPTOC1_START

MNSPTOC2_START

CCSPVC1_FAIL

CCSPVC1_FAIL

MNSPTOC_OPERATE

GUID-E6A3B420-A91C-41D8-9015-D3DF46E8EFDD V2 EN

Figure 19: Negative-sequence overcurrent protection function

The phase reversal protection PREVPTOC1 is based on the calculated negativephase-sequence current. It detects high negative sequence current values during motorstart-up, caused by incorrectly connected phases, which in turn causes the motor torotate in the opposite direction.

The negative-sequence and phase reversal protection are blocked if the current circuitsupervision detects failure in the current measurement circuit.

PREVPTOC1BLOCK OPERATE

STARTPREVPTOC1_OPERATEPREVPTOC1_START

CCSPVC1_FAIL

GUID-D3963D96-A662-4F2F-BD5F-AA22ADDA7487 V2 EN

Figure 20: Phase reversal protection function

Two stages are provided for non-directional earth-fault protection to detect phase-to-earth faults that may be the result of, for example, insulation ageing.

1MRS756885 M Section 3REM615 standard configurations

REM615 45Application Manual

Page 52: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

EFHPTOC1BLOCKENA_MULT

OPERATESTART

EFLPTOC1BLOCKENA_MULT

OPERATESTART

ANDB1B2

O

EFHPTOC1_OPERATE

EFHPTOC1_OPERATE

EFLPTOC1_OPERATE

EFLPTOC1_OPERATE

PHIPTOC1_START

PHIPTOC1_START

EFHPTOC1_START

EFLPTOC1_START

EFxPTOC_OPERATE

GUID-3EAB80E2-7348-4463-8C97-93FF0A1211C4 V1 EN

Figure 21: Earth-fault protection functions

The emergency start function ESMGAPC1 allows motor start-ups although thecalculated thermal level or cumulative start-up time counter is blocking the restart.The emergency start is enabled for ten minutes after the selected binary inputX120:BI1 is energized.

On the rising edge of the emergency start signal, various events occur.

• The calculated thermal level in MPTTR1 is set slightly below the restart inhibitlevel to allow at least one motor start-up.

• The value of the cumulative start-up time counter STTPMSU1 is set slightlybelow the set restart inhibit value to allow at least one motor start-up.

• The set start value of the MAPGAPC1 function is increased (or decreased)depending on the Start value Add setting (only if the optional RTD/mA moduleis included).

• Alarm LED 11 is activated.

A new emergency start cannot be made until the emergency start signal has been resetand the emergency start time has expired.

ESMGAPC1BLOCKST_EMERG_RQ

ST_EMERG_ENAX120_BI1_EMERG_START_ENA

ESMGAPC1_ST_EMERG_ENA

GUID-7532106A-2E0A-4864-B9CE-5EDC4E15FDE6 V1 EN

Figure 22: Motor emergency start-up function

The thermal overload protection for motors MPTTR1 detects short and long termoverloads under varying load conditions. When the emergency start request is issuedfor the emergency start function, it activates the corresponding input of the thermaloverload function. Restart blocking, issued by the thermal overload function, preventsthe closing of the breaker in machine overload situation. The emergency start requestremoves the blocking and enables the restarting of the motor.

Section 3 1MRS756885 MREM615 standard configurations

46 REM615Application Manual

Page 53: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

If the IED is ordered with RTD/mA card, the motor ambient temperature can bemeasured with input RTD X130:AI8 and it is connected to the thermal overloadprotection function MPTTR1.

MPTTR1BLOCKSTART_EMERGTEMP_AMB

OPERATEALARM

BLK_RESTART MPTTR1_BLK_RESTART

MPTTR1_OPERATEESMGAPC1_ST_EMERG_ENA

X130_AI8_MOTOR_AMBIENT_TEMPMPTTR1_ALARM

GUID-A48D50ED-BA78-4159-9913-8E73F26B4D84 V1 EN

Figure 23: Thermal overcurrent protection function

The restart inhibit is activated for a set period when a circuit breaker is opened. Thisis called remanence voltage protection where the motor has damping remanencevoltage after the circuit breaker opening. Re-closing after a too short period of timecan lead to stress for the machine and other apparatus. The remanence voltageprotection waiting time can be set by a timer function TPSGAPC1.

The restart inhibit is also activated under various conditions.

• An active trip command• Motor start-up supervision has issued lockout• Motor unbalance function has issued restart blocking• An external restart inhibit is activated by a binary input X120:BI4

With the motor start-up supervision function STTPMSU1, the starting of the motor issupervised by monitoring three-phase currents or the status of the energizing circuitbreaker of the motor. When the emergency start request is activated by ESMGAPC1and STTPMSU1 is in lockout state, which inhibits motor starting, the lockout isdeactivated and emergency starting is available.

STTPMSU1BLOCKBLK_LK_STCB_CLOSEDSTALL_INDST_EMERG_ENA

OPR_IITOPR_STALLMOT_START

LOCK_STARTX120_BI2_CB_CLOSED

STTPMSU1_LOCK_START

STTPMSU1_OPR_IIT

STTPMSU1_MOT_STARTUP

ESMGAPC1_ST_EMERG_ENA

GUID-AE31431D-358F-42EA-B2EB-7E4CC2BD7B92 V1 EN

Figure 24: Motor start-up supervision function

The runtime counter for machines and devices MDSOPT1 provides history data sincethe last commissioning. The counter counts the total number of motor running hoursand is incremented when the energizing circuit breaker is closed.

MDSOPT1BLOCKPOS_ACTIVERESET

ALARMWARNINGX120_BI2_CB_CLOSED

MDSOPT1_ALARM

GUID-2714A54C-C7E2-4A62-A9F1-44764D8A92CB V1 EN

Figure 25: Motor runtime counter

The loss of load situation is detected by LOFLPTUC1. The loss of load situationoccurs, for example, if there is a damaged pump or a broken conveyor.

1MRS756885 M Section 3REM615 standard configurations

REM615 47Application Manual

Page 54: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

LOFLPTUC1BLOCK OPERATE

STARTLOFLPTUC1_OPERATE

GUID-460792B9-EFF6-4678-9A43-97DF301F48EE V1 EN

Figure 26: Loss of load protection function

The RTD/mA monitoring (optional) functionality provides several temperaturemeasurements for motor protection. Temperature of the motor windings U, V and Wis measured with inputs RTD X130:AI3, RTD X130:AI4, and RTD X130:AI5. Themeasured values are connected from function X130 (RTD) to function MAX3. Themaximum temperature value is connected to the multipurpose analog protection blockMAPGAPC1.

The motor cooling air temperature and motor bearing temperature can be measuredwith inputs RTD X130:AI6 and RTD X130:AI7. The protection functionality fromthese temperatures is provided by MAPGAPC2 and MAPGAPC3 functions.

MAPGAPC1AI_VALUEBLOCKENA_ADD

OPERATESTART

MAPGAPC2AI_VALUEBLOCKENA_ADD

OPERATESTART

MAPGAPC3AI_VALUEBLOCKENA_ADD

OPERATESTART

MAX3IN1IN2IN3

OUT MAPGAPC1_OPERATE

MAPGAPC2_OPERATE

MAPGAPC3_OPERATE

MAPGAPC1_START

MAPGAPC2_START

MAPGAPC3_START

ESMGAPC1_ST_EMERG_ENA

X130_AI3_MOTOR_WDG_U_TEMPX130_AI4_MOTOR_WDG_V_TEMPX130_AI5_MOTOR_WDG_W_TEMP

X130_AI6_MOTOR_COOLING_AIR_TEMP

X130_AI7_MOTOR_BEARING_TEMP

OR6B1B2B3B4B5B6

OMAPGAPC1_OPERATEMAPGAPC2_OPERATEMAPGAPC3_OPERATE

MAPGAPC_OPERATE

GUID-7BC533E6-EB4E-488F-A11C-9E86943509B1 V1 EN

Figure 27: Multipurpose mA/RTD monitoring

The circuit breaker failure protection CCBRBRF1 is initiated via the START input bynumber of different protection functions available in the IED. The breaker failureprotection function offers different operating modes associated with the circuitbreaker position and the measured phase and residual currents.

Section 3 1MRS756885 MREM615 standard configurations

48 REM615Application Manual

Page 55: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

The circuit breaker failure protection function has two operating outputs: TRRET andTRBU. The TRRET operate output is used for retripping its own breaker throughTRPPTRC2_TRIP. The TRBU output is used to give a backup trip to the breakerfeeding upstream. For this purpose, the TRBU operate output signal is connected to thebinary output X100:PO2.

CCBRBRF1BLOCKSTARTPOSCLOSECB_FAULT

CB_FAULT_ALTRBU

TRRET

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O CCBRBRF1_TRBU

X120_BI2_CB_CLOSED

PHLPTOC1_OPERATEPHIPTOC1_OPERATEJAMPTOC1_OPERATE

EFHPTOC1_OPERATEMNSPTOC1_OPERATE

MNSPTOC2_OPERATESTTPMSU1_OPR_IIT

ARCSARC1_OPERATEARCSARC2_OPERATEARCSARC3_OPERATE

CCBRBRF1_TRRET

EFLPTOC1_OPERATE

GUID-D7C7B065-6A72-4E5E-8E4A-FB3EDD8699F5 V1 EN

Figure 28: Circuit breaker failure protection function

Three arc protection stages ARCSARC1...3 are included as an optional function. Thearc protection offers individual function blocks for three arc sensors that can beconnected to the IED. Each arc protection function block has two different operationmodes, that is, with or without the phase and residual current check.

The operate signals from ARCSARC1...3 are connected to both trip logic TRPPTRC1and TRPPTRC2. If the IED is ordered with high speed binary outputs, the individualoperate signals from ARCSARC1...3 are connected to dedicated trip logicTRPPTRC3...5. The outputs of TRPPTRC3...5 are available at high speed outputsX110:HSO1, X110:HSO2 and X110:HSO3.

1MRS756885 M Section 3REM615 standard configurations

REM615 49Application Manual

Page 56: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

OR6B1B2B3B4B5B6

O

ARCSARC1BLOCKREM_FLT_ARCOPR_MODE

OPERATEARC_FLT_DET

ARCSARC2BLOCKREM_FLT_ARCOPR_MODE

OPERATEARC_FLT_DET

ARCSARC3BLOCKREM_FLT_ARCOPR_MODE

OPERATEARC_FLT_DET

ARCSARC1_OPERATE

ARCSARC1_OPERATE

ARCSARC2_OPERATE

ARCSARC2_OPERATE

ARCSARC3_OPERATE

ARCSARC3_OPERATE

ARCSARC1_ARC_FLT_DET

ARCSARC2_ARC_FLT_DET

ARCSARC3_ARC_FLT_DET

ARC_OPERATE

GUID-41BDA7A8-9364-447E-9334-AC8C986A4596 V1 EN

TRPPTRC3BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

TRPPTRC4BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

TRPPTRC5BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

TRPPTRC3_TRIP

TRPPTRC4_TRIP

TRPPTRC5_TRIP

ARCSARC1_OPERATE

ARCSARC2_OPERATE

ARCSARC3_OPERATE

GUID-6C3DC16F-44CE-431F-ACB1-EE82D5AB5540 V1 EN

Figure 29: Arc protection with dedicated HSO

General start and operate signals from all the functions are connected to pulse timerTPGAPC1 for setting the minimum pulse length for the outputs. The output fromTPGAPC1 is connected to binary outputs.

Section 3 1MRS756885 MREM615 standard configurations

50 REM615Application Manual

Page 57: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

TPGAPC1IN1IN2

OUT1OUT2

GENERAL_START_PULSE

STTPMSU1_LOCK_STARTSTTPMSU1_MOT_STARTUP

PHIPTOC1_STARTPHLPTOC1_START

EFHPTOC1_START

MNSPTOC1_STARTMNSPTOC2_STARTPREVPTOC1_START

EFLPTOC1_START

MAPGAPC1_STARTMAPGAPC2_STARTMAPGAPC3_START

GUID-D36EAFFF-2A57-4C37-B400-AD9E5F234C53 V1 EN

Figure 30: General start and operate signals

The operate signals from the protection functions are connected to trip logicsTRPPTRC1. The output of these trip logic functions is available at binary outputsX100:PO3 and X100:SO1. The trip logic functions are provided with a lockout andlatching function, event generation and the trip signal duration setting. If the lockoutoperation mode is selected, the binary input can be assigned to RST_LKOUT input ofthe trip logic to enable external reset with a push button.

Three other trip logics TRPPTRC3...4 are also available if the IED is ordered withhigh speed binary outputs options.

TRPPTRC1BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

TRPPTRC1_TRIPPHLPTOC1_OPERATEPHIPTOC1_OPERATEJAMPTOC1_OPERATE

EFHPTOC1_OPERATEMNSPTOC1_OPERATE

MNSPTOC2_OPERATE

STTPMSU1_OPR_IIT

ARCSARC1_OPERATEARCSARC2_OPERATEARCSARC3_OPERATE

MAPGAPC1_OPERATEMAPGAPC2_OPERATEMAPGAPC3_OPERATE

PREVPTOC1_OPERATELOFLPTUC1_OPERATE

MPTTR1_OPERATE

CCBRBRF1_TRRET

EFLPTOC1_OPERATE

GUID-C3F9216B-BD31-467B-A966-E363A2A815F2 V1 EN

Figure 31: Trip logic TRPPTRC1

1MRS756885 M Section 3REM615 standard configurations

REM615 51Application Manual

Page 58: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

3.3.3.2 Functional diagrams for disturbance recorder

The START and the OPERATE outputs from the protection stages are routed to triggerthe disturbance recorder or, alternatively, only to be recorded by the disturbancerecorder depending on the parameter settings. Additionally, the selected signals fromdifferent functions and the few binary inputs are also connected to the disturbancerecorder.

RDRE1C1C2C3C4C5C6C7C8C9C10C11C12C13C14C15C16C17C18C19C20C21C22C23C24C25C26C27C28C29C30C31C32C33C34C35C36C37C38C39C40C41C42C43C44C45C46C47C48C49C50C51C52C53C54C55C56C57C58C59C60C61C62C63C64

TRIGGERED

OR6B1B2B3B4B5B6

O

ORB1B2

O

ORB1B2

O

CCBRBRF1_TRBU

X120_BI3_CB_OPENEDX120_BI2_CB_CLOSED

STTPMSU1_LOCK_START

MPTTR1_BLK_RESTART

MNSPTOC1_BLK_RESTART

MNSPTOC2_BLK_RESTART

X120_BI4_EXT_RESTART_INHIBIT

PHLPTOC1_OPERATEPHIPTOC1_OPERATEJAMPTOC1_OPERATE

EFHPTOC1_OPERATE

MNSPTOC1_OPERATEMNSPTOC2_OPERATE

STTPMSU1_OPR_IIT

ARCSARC1_OPERATEARCSARC2_OPERATEARCSARC3_OPERATE

MAPGAPC1_OPERATEMAPGAPC2_OPERATEMAPGAPC3_OPERATE

PREVPTOC1_OPERATELOFLPTUC1_OPERATE

MPTTR1_OPERATE

CCBRBRF1_TRRET

EFLPTOC1_OPERATE

STTPMSU1_MOT_STARTUP

PHIPTOC1_STARTPHLPTOC1_START

EFHPTOC1_START

MNSPTOC1_START

MNSPTOC2_START

PREVPTOC1_START

EFLPTOC1_START

MAPGAPC1_STARTMAPGAPC2_STARTMAPGAPC3_START

CCSPVC1_FAIL

X120_BI1_EMERG_START_ENA

ESMGAPC1_ST_EMERG_ENA

MPTTR1_ALARM

ARCSARC1_ARC_FLT_DETARCSARC2_ARC_FLT_DETARCSARC3_ARC_FLT_DET

DISTURB_RECORD_TRIGGERED

GUID-4767F54E-444D-4CFC-ACD7-6A7179446678 V2 EN

Figure 32: Disturbance recorder

3.3.3.3 Functional diagrams for condition monitoring

CCSPVC1 detects failures in the current measuring circuits. When a failure isdetected, it can be used to block the current protection functions that measure thecalculated sequence component currents to avoid unnecessary operation. However,the BLOCK input signal is not connected in the configuration.

Section 3 1MRS756885 MREM615 standard configurations

52 REM615Application Manual

Page 59: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

CCSPVC1BLOCK FAIL

ALARMCCSPVC1_FAILCCSPVC1_ALARM

GUID-6BC73CDF-8A4C-4619-AD3B-A2A90F1D7CC6 V2 EN

Figure 33: Current circuit supervision function

The circuit-breaker condition monitoring function SSCBR1 supervises the switchstatus based on the connected binary input information and the measured currentlevels. SSCBR1 introduces various supervision methods.

SSCBR1BLOCKPOSOPENPOSCLOSEOPEN_CB_EXECLOSE_CB_EXEPRES_ALM_INPRES_LO_INSPR_CHR_STSPR_CHRRST_IPOWRST_CB_WEARRST_TRV_TRST_SPR_T

TRV_T_OP_ALMTRV_T_CL_ALMSPR_CHR_ALM

OPR_ALMOPR_LO

IPOW_ALMIPOW_LO

CB_LIFE_ALMMON_ALM

PRES_ALMPRES_LO

OPENPOSINVALIDPOSCLOSEPOS

CB_OPEN_COMMANDCB_CLOSE_COMMAND

X120_BI3_CB_OPENEDX120_BI2_CB_CLOSED

SSCBR1_TRV_T_OP_ALMSSCBR1_TRV_T_CL_ALMSSCBR1_SPR_CHR_ALMSSCBR1_OPR_ALMSSCBR1_OPR_LOSSCBR1_IPOW_ALMSSCBR1_IPOW_LOSSCBR1_CB_LIFE_ALMSSCBR1_MON_ALMSSCBR1_PRES_ALMSSCBR1_PRES_LO

GUID-FC1FB871-CEB4-4474-AD33-BDDAE69AE66B V1 EN

Figure 34: Circuit-breaker condition monitoring function

ORB1B2

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

SSCBR1_TRV_T_OP_ALMSSCBR1_TRV_T_CL_ALMSSCBR1_SPR_CHR_ALM

SSCBR1_OPR_ALMSSCBR1_OPR_LO

SSCBR1_IPOW_ALM

SSCBR1_IPOW_LOSSCBR1_CB_LIFE_ALM

SSCBR1_MON_ALMSSCBR1_PRES_ALM

SSCBR1_PRES_LO

SSCBR1_ALARMS

GUID-D1CCF380-E15F-4D4A-A2B2-E91C289A900A V1 EN

Figure 35: Logic for circuit breaker monitoring alarm

Two separate trip circuit supervision functions are included: TCSSCBR1 for poweroutput X100:PO3 for master trip and TCSSCBR2 for power output X100:PO4 forcircuit breaker closing. The trip circuit supervision TCSSCRB1 is blocked by themaster trip TRPPTRC1 and the circuit breaker open signal. The trip circuitsupervision function TCSSCBR2 is blocked by the circuit breaker close signal.

It is assumed that there is no external resistor in the circuit breakertripping coil circuit connected in parallel with the circuit breakernormally open auxiliary contact.

1MRS756885 M Section 3REM615 standard configurations

REM615 53Application Manual

Page 60: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

TCSSCBR1BLOCK ALARM

TCSSCBR2BLOCK ALARM

ORB1B2

OTRPPTRC1_TRIP

X120_BI3_CB_OPENED

X120_BI2_CB_CLOSED

TCSSCBR1_ALARM

TCSSCBR2_ALARM

ORB1B2

OTCSSCBR1_ALARMTCSSCBR2_ALARM

TCSSCBR_ALARM

GUID-4303B14D-B03D-4E5B-A072-30FCFD2F4D7A V1 EN

Figure 36: Trip circuit supervision function

3.3.3.4 Functional diagrams for control and interlocking

The circuit breaker closing is enabled when the ENA_CLOSE input is activated. Theinput can be activated by the configuration logic, which is a combination of thedisconnector or breaker truck and earth-switch position status, status of the trip logics,gas pressure alarm and circuit breaker spring charging status. In the configuration,only trip logic activates the close-enable signal to the circuit-breaker control functionblock. The open operation for circuit breaker is always enabled.

Connect the additional signals required by the application for closingand opening of the circuit breaker.

CBXCBR1POSOPENPOSCLOSEENA_OPENENA_CLOSEBLK_OPENBLK_CLOSEAU_OPENAU_CLOSETRIPSYNC_OKSYNC_ITL_BYP

SELECTEDEXE_OPEXE_CL

OP_REQCL_REQ

OPENPOSCLOSEPOS

OKPOSOPEN_ENAD

CLOSE_ENAD

TRUE

CBXCBR_CLOSE_ENAD

RESTART_INHIBIT

X120_BI3_CB_OPENEDX120_BI2_CB_CLOSED

CBXCBR1_ENA_CLOSE

CBXCBR1_EXE_OPCBXCBR1_EXE_CL

FALSE

CBXBCR1_AU_OPENCBXBCR1_AU_CLOSE

GUID-AF13D032-2E0C-42EE-9047-992D53777E20 V2 EN

Figure 37: Circuit breaker 1 control logic

ORB1B2

O CB_CLOSE_COMMANDCBXCBR1_EXE_CL

GUID-37D6FF45-A028-45E1-9030-B19466A67253 V1 EN

Figure 38: Signals for closing coil of circuit breaker 1

Section 3 1MRS756885 MREM615 standard configurations

54 REM615Application Manual

Page 61: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

ORB1B2

OTRPPTRC1_TRIP CB_OPEN_COMMANDCBXCBR1_EXE_OP

GUID-0D529A3A-6F2A-43DF-931D-743A14C45946 V1 EN

Figure 39: Signals for opening coil of circuit breaker 1

NOTIN OUTTRPPTRC1_TRIP CBXCBR1_ENA_CLOSE

GUID-4ECE441D-D55F-4DEA-AF7A-EEE210EA19BE V1 EN

Figure 40: Circuit breaker 1 close enable logic

Connect higher-priority conditions before enabling the closing ofcircuit breaker. These conditions cannot be bypassed with bypassfeature of the function.

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

TRPPTRC1_TRIP

RESTART_INHIBIT

STTPMSU1_LOCK_START

MPTTR1_BLK_RESTART

MNSPTOC1_BLK_RESTARTMNSPTOC2_BLK_RESTART

END_OF_REMANENCE_TIME

X120_BI4_EXT_RESTART_INHIBIT

GUID-4D9EA332-C1C1-4307-BC8B-AF0025FA3ED8 V1 EN

Figure 41: Circuit breaker 1 close blocking logic

When the motor restart is inhibited, the BLK_CLOSE input is activated and the circuitbreaker is not closed. When all conditions of the circuit breaker closing are met, theCLOSE_ENAD output of the CBXCBR1 is activated and the X100:PO1 output isclosed.

The configuration also includes restart inhibit. Restart inhibit is activated undervarious conditions.

• An active trip command• Motor start-up supervision has issued lockout• Motor unbalance function has issued restart blocking• Thermal protection has issued blocked restart• An external restart inhibit is activated by a binary input X120:BI4• Time during which remanence voltage is present

The configuration includes logic for generating circuit breaker external closing andopening command with the IED in local or remote mode.

Check the logic for the external circuit breaker closing command andmodify it according to the application.

1MRS756885 M Section 3REM615 standard configurations

REM615 55Application Manual

Page 62: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Connect the additional signals for closing and opening of circuitbreaker in local or remote mode, if applicable for the configuration.

ANDB1B2

O

ANDB1B2

O

ORB1B2

O CBXCBR1_AU_CLOSE

CONTROL_LOCAL

CONTROL_REMOTE

FALSE

FALSE

GUID-5E40E51B-253D-4CEA-AEBC-376288BD0824 V1 EN

Figure 42: External closing command for circuit breaker 1

ANDB1B2

O

ORB1B2

O

ANDB1B2

O

CBXBCR1_AU_OPEN

CONTROL_LOCAL

CONTROL_REMOTE

FALSE

FALSE

GUID-68245F45-CB10-416F-8096-2C3EDADEBF36 V1 EN

Figure 43: External opening command for circuit breaker 1

3.3.3.5 Functional diagrams for measurement functions

The phase current inputs to the IED are measured by the three-phase currentmeasurement function CMMXU1. The current input is connected to the X120 card inthe back panel. The sequence current measurement CSMSQI1 measures the sequencecurrent and the residual current measurement RESCMMXU1 measures the residualcurrent.

The measurements can be seen in the LHMI and they are available under themeasurement option in the menu selection. Based on the settings, function blocks cangenerate low alarm or warning and high alarm or warning signals for the measuredcurrent values.

The load profile record LDPRLRC1 is included in the measurements sheet.LDPRLRC1 offers the ability to observe the loading history of the correspondingfeeder.

CMMXU1BLOCK HIGH_ALARM

HIGH_WARNLOW_WARN

LOW_ALARM

GUID-B514CC03-FA19-4BED-9DAF-175C11DFD8E8 V1 EN

Figure 44: Current measurement: Three-phase current measurement

Section 3 1MRS756885 MREM615 standard configurations

56 REM615Application Manual

Page 63: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

CSMSQI1

GUID-CBE90941-AFD2-463F-9F9C-4D04917A21EC V1 EN

Figure 45: Current measurement: Sequence current measurement

RESCMMXU1BLOCK HIGH_ALARM

HIGH_WARN

GUID-E2233F77-F025-467F-AD28-135BDC53C125 V1 EN

Figure 46: Current measurement: Residual current measurement

FLTRFRC1BLOCKCB_CLRD

GUID-7241F46A-5CB0-41F1-AEEB-30A501A90244 V2 EN

Figure 47: Other measurement: Data monitoring

LDPRLRC1RSTMEM MEM_WARN

MEM_ALARM

GUID-5DFC88FD-420E-43ED-AAEA-6425B3314F90 V2 EN

Figure 48: Other measurement: Load profile record

3.3.3.6 Functional diagrams for I/O and alarm LEDs

X120_BI3_CB_OPENED

X120_BI2_CB_CLOSED

X120_BI4_EXT_RESTART_INHIBIT

X120_BI1_EMERG_START_ENA

X120 (AIM).X120-Input 1

X120 (AIM).X120-Input 2

X120 (AIM).X120-Input 3

X120 (AIM).X120-Input 4GUID-F7FCB288-172A-4EB8-AEF5-C74570C2579F V1 EN

Figure 49: Default binary inputs - X120

1MRS756885 M Section 3REM615 standard configurations

REM615 57Application Manual

Page 64: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

GENERAL_START_PULSE

CBXCBR_CLOSE_ENAD

CCBRBRF1_TRBU

TRPPTRC1_TRIP

CB_OPEN_COMMAND

CB_CLOSE_COMMAND

X100 (PSM).X100-PO1

X100 (PSM).X100-PO2

X100 (PSM).X100-SO1

X100 (PSM).X100-SO2

X100 (PSM).X100-PO3

X100 (PSM).X100-PO4GUID-1835C57B-317C-40A1-AFB1-97766B5CE903 V1 EN

Figure 50: Default binary outputs - X100

TRPPTRC3_TRIP

TRPPTRC4_TRIP

TRPPTRC5_TRIP

X110 (BIO-H).X110-HSO1

X110 (BIO-H).X110-HSO2

X110 (BIO-H).X110-HSO3GUID-8DF2F2CA-FEBE-45C7-ABE2-E0A28E3C99B7 V1 EN

Figure 51: Default binary outputs - X110

X130_AI8_MOTOR_AMBIENT_TEMP

X130_AI3_MOTOR_WDG_U_TEMP

X130_AI4_MOTOR_WDG_V_TEMP

X130_AI5_MOTOR_WDG_W_TEMP

X130_AI6_MOTOR_COOLING_AIR_TEMP

X130_AI7_MOTOR_BEARING_TEMP

X130 (RTD).AI_VAL3

X130 (RTD).AI_VAL4

X130 (RTD).AI_VAL5

X130 (RTD).AI_VAL6

X130 (RTD).AI_VAL7

X130 (RTD).AI_VAL8GUID-6E527557-2DBA-4402-94D1-3B088F23A684 V1 EN

Figure 52: Default mA/RTD inputs - X130

Section 3 1MRS756885 MREM615 standard configurations

58 REM615Application Manual

Page 65: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

OR6B1B2B3B4B5B6

O

LED1OKALARMRESET

LED2OKALARMRESET

LED3OKALARMRESET

LED4OKALARMRESET

LED5OKALARMRESET

ORB1B2

O

RESTART_INHIBIT

PHLPTOC1_OPERATE

PHIPTOC1_OPERATE

JAMPTOC1_OPERATE

STTPMSU1_OPR_IIT

PREVPTOC1_OPERATELOFLPTUC1_OPERATE

MPTTR1_OPERATE

EFxPTOC_OPERATE

MNSPTOC_OPERATE

MAPGAPC_OPERATE

GUID-3A6579B1-1F7C-446A-ABAD-839B08B8697C V2 EN

LED6OKALARMRESET

LED7OKALARMRESET

LED8OKALARMRESET

LED9OKALARMRESET

LED10OKALARMRESET

LED11OKALARMRESET

OR6B1B2B3B4B5B6

O

CCBRBRF1_TRBU

ESMGAPC1_ST_EMERG_ENA

DISTURB_RECORD_TRIGGERED

ARC_OPERATE

TCSSCBR_ALARMMDSOPT1_ALARMCCRDIF1_ALARM

SSCBR1_ALARMS

GUID-F6D597B3-832D-49BD-86D6-8136874F00DD V2 EN

Figure 53: Default LED connections

1MRS756885 M Section 3REM615 standard configurations

REM615 59Application Manual

Page 66: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

3.3.3.7 Functional diagrams for other timer logics

The configuration also includes logic for remanence voltage. The restart inhibit isactivated for a set period when a circuit breaker is in open state. This is calledremanence voltage protection where the motor has damping remanence voltage afterthe opening of a circuit breaker. Reclosing after a short period of time can lead to stressfor the machine and other apparatus. The remanence voltage protection waiting timecan be set by a timer function TPSGAPC1.

TPSGAPC1IN1IN2

OUT1OUT2

CB_OPEN_COMMAND END_OF_REMANENCE_TIME

GUID-8DD72101-BF5E-4FE5-9A08-A4CB851D8049 V1 EN

Figure 54: Timer logic for remanence voltage to disappear

3.3.3.8 Other functions

The configuration includes few instances of multipurpose protection functionMAPGAPC and different types of timers and control functions. These functions arenot included in application configuration but they can be added based on the systemrequirements.

3.4 Standard configuration B

3.4.1 Applications

The standard configuration is intended for comprehensive protection and controlfunctionality of the circuit breaker controlled asynchronous motors. With minormodifications, the standard configuration can also be applied for contactor controlledmotors. There is also an option for mA/RTD measurement and protection.

The protection relay with a standard configuration is delivered from the factory withdefault settings and parameters. The end user flexibility for incoming, outgoing andinternal signal designation within the protection relay enables this configuration to befurther adapted to different primary circuit layouts and the related functionality needsby modifying the internal functionality using PCM600.

Section 3 1MRS756885 MREM615 standard configurations

60 REM615Application Manual

Page 67: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

3.4.2 Functions

CONDITION MONITORING AND SUPERVISION

ALSO AVAILABLE

- Disturbance and fault recorders- Event log and recorded data- High-Speed Output module (optional)- Local/Remote push button on LHMI- Self-supervision- Time synchronization: IEEE 1588 v2,

SNTP, IRIG-B- User management- Web HMI

ORAND

REMARKS

Optionalfunction

No. ofinstances

Alternative function to be defined when ordering

OR

Io/Uo

Calculatedvalue

CONTROL AND INDICATION 1) MEASUREMENT

MOTOR PROTECTION AND CONTROL RELAY

PROTECTION LOCAL HMI

Analog interface types 1)

Current transformer

Voltage transformer

1) Conventional transformer inputs

ESTARTESTART

Object Ctrl 2) Ind 3)

CB 1 -

DC 2 3

ES 1 21) Check availability of binary inputs/outputs

from technical documentation2) Control and indication function for

primary object3) Status indication function for primary object

STANDARD CONFIGURATION

RL

ClearESCI

O

Configuration ASystemHMITimeAuthorization

RL

ClearESCI

O

U12 0. 0 kVP 0.00 kWQ 0.00 kVAr

IL2 0 A

A

18×MAPMAP

REM615

- I, U, Io, P, Q, E, pf, f- Limit value supervision- Load profile record- RTD/mA measurement (optional)- Symmetrical components

4

3

COMMUNICATION

Protocols: IEC 61850-8-1/-9-2LE Modbus®

IEC 60870-5-103 DNP3Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232Redundant protocols: HSR PRP RSTP

Master TripLockout relay

94/86

Io>>51N-2

Io>→67N-1

3×ARC

50L/50NL

3I<37

2×I2>M46M

I2>>46R

3Ith>M49M

Is2t n<49, 66, 48, 51LR

3I>>>50P/51P

3I>/Io>BF51BF/51NBF

Ist>51LR

3I>51P-1

CBCMCBCM

FUSEF60

MCS 3IMCS 3I

2×TCSTCM

OPTSOPTM

3U<27

U2>47O-

U1<47U+

2×f>/f<,df/dt81

3I>>51P-2

3I

Io

Io

B

Io

Uo

3I Io

UL1UL2UL3 UL1

UL2

UL3

6xRTD2xmA

UL1

UL2

UL3

Master TripLockout relay

94/86

3×2×

GUID-521A1FAA-FF73-4988-BA61-33AA451F33E0 V2 EN

Figure 55: Functionality overview for standard configuration B

3.4.2.1 Default I/O connections

Connector pins for each input and output are presented in the IED physicalconnections section.

1MRS756885 M Section 3REM615 standard configurations

REM615 61Application Manual

Page 68: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Table 17: Default connections for binary inputs

Binary input DescriptionX110-BI1 Emergency restart inhibit

X110-BI2 External trip

X110-BI3 Circuit breaker closed

X110-BI4 Circuit breaker open

X110-BI5 Voltage transformer secondary MCB open

X110-BI6 Emergency start

X110-BI7 Lockout reset

X110-BI8 Setting group change

Table 18: Default connections for mA/RTD inputs

RTD/mA input DescriptionX130-AI1 -

X130-AI2 -

X130-AI3 Motor winding U temperature

X130-AI4 Motor winding V temperature

X130-AI5 Motor winding W temperature

X130-AI6 Motor cooling air temperature

X130-AI7 Motor bearing temperature

X130-AI8 Motor ambient temperature

Table 19: Default connections for binary outputs

Binary output DescriptionX100-PO1 Restart enable

X100-PO2 Breaker failure backup trip to upstream breaker

X100-SO1 Open command (for contractor application)

X100-SO2 Start indication

X100-PO3 Open circuit breaker/trip

X100-PO4 Close circuit breaker

X110-SO1 Motor startup indication

X110-SO2 Thermal overload alarm

X110-SO3 Voltage protection alarm

X110-SO4 Start indication

X110-HSO1 Arc protection instance 1 operate activated

X110-HSO2 Arc protection instance 2 operate activated

X110-HSO3 Arc protection instance 3 operate activated

Section 3 1MRS756885 MREM615 standard configurations

62 REM615Application Manual

Page 69: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Table 20: Default connections for LEDs

LED Description1 Short-circuit protection operate

2 Earth-fault protection operate

3 Thermal overload protection operate

4 Combined operate indication of the other protection functions

5 Motor restart inhibit

6 Breaker failure protection operate

7 Disturbance recorder triggered

8 Circuit breaker condition monitoring alarm

9 TCS, motor runtime counter or measuring circuit fault alarm

10 Arc protection operate

11 Emergency start enabled

3.4.2.2 Default disturbance recorder settings

Table 21: Default disturbance recorder analog channels

Channel Description1 IL1

2 IL2

3 IL3

4 Io

5 U1

6 U2

7 U3

8 -

9 -

10 -

11 -

12 -

Table 22: Default disturbance recorder binary channels

Channel ID text Level trigger mode1 PHLPTOC1 - start Positive or Rising

2 PHIPTOC2 - start Positive or Rising

3 DEFLPDEF1 - start Positive or Rising

4 EFHPTOC1 - start Positive or Rising

5 MPTTR1 - alarm Level trigger off

6 MPTTR1 - blk restart Level trigger off

7 ESMGAPC1 - st emerg ena Level trigger off

Table continues on next page

1MRS756885 M Section 3REM615 standard configurations

REM615 63Application Manual

Page 70: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Channel ID text Level trigger mode8 STTPMSU1 - mot startup Positive or Rising

9 STTPMSU1 - lock start Level trigger off

10 MNSPTOC1 - start Positive or Rising

11 MNSPTOC1 - blk restart Level trigger off

12 MNSPTOC2 - start Positive or Rising

13 MNSPTOC2 - blk restart Level trigger off

14 PREVPTOC1 - start Positive or Rising

15 PHPTUV1 - start Positive or Rising

16 PSPTUV1 - start Positive or Rising

17 NSPTOV1 - start Positive or Rising

18 FRPFRQ1 - start Positive or Rising

19 FRPFRQ2 - start Positive or Rising

20 MAPGAPC1 - start Positive or Rising

21 MAPGAPC2 - start Positive or Rising

22 MAPGAPC3 - start Positive or Rising

23 CCBRBRF1 - trret Level trigger off

24 CCBRBRF1 - trbu Level trigger off

25 PHLPTOC1 - operate Level trigger off

26 PHIPTOC2 - operate Level trigger off

27 JAMPTOC1 - operate Level trigger off

28 DEFLPDEF1 - operate Level trigger off

EFHPTOC2 - operate

29 MNSPTOC1 - operate Level trigger off

MNSPTOC2 - operate

30 PREVPTOC1 - operate Level trigger off

31 LOFLPTUC1 - operate Level trigger off

32 MPTTR1 - operate Level trigger off

33 PHPTUV1 - operate Level trigger off

34 PSPTUV1 - operate Level trigger off

35 NSPTOV1 - operate Level trigger off

36 FRPFRQ1 - operate Level trigger off

37 FRPFRQ2 - operate Level trigger off

38 MAPGAPC1 - operate Level trigger off

39 MAPGAPC2 - operate Level trigger off

40 MAPGAPC3 - operate Level trigger off

41 X110BI1 - Ext restart inhibit Positive or Rising

42 X110BI2 - Ext trip Level trigger off

43 X110BI6 - Emerg start ena Level trigger off

44 X110BI3 - CB closed Level trigger off

Table continues on next page

Section 3 1MRS756885 MREM615 standard configurations

64 REM615Application Manual

Page 71: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Channel ID text Level trigger mode45 X110BI4 - CB opened Level trigger off

46 X110BI7 - rst lockout Level trigger off

47 X110BI5 - MCB opened Level trigger off

48 X110BI8 - SG changed Level trigger off

49 STTPMSU1 - opr iit Positive or Rising

50 SEQSPVC1 - fusef 3ph Level trigger off

51 SEQSPVC1 - fusef u Level trigger off

52 CCSPVC1 - fail Level trigger off

53 ARCSARC1 - ARC flt det Level trigger off

ARCSARC2 - ARC flt det

ARCSARC3 - ARC flt det

54 ARCSARC1 - operate Positive or Rising

55 ARCSARC2 - operate Positive or Rising

56 ARCSARC3 - operate Positive or Rising

3.4.3 Functional diagrams

The functional diagrams describe the default input, output, alarm LED and function-to-function connections. The default connections can be viewed and changed withPCM600 according to the application requirements.

The analog channels have fixed connections to the different function blocks inside theprotection relay’s standard configuration. However, the 12 analog channels availablefor the disturbance recorder function are freely selectable as a part of the disturbancerecorder’s parameter settings.

The phase currents to the protection relay are fed from a current transformer. Theresidual current to the protection relay is fed from either residually connected CTs, anexternal core balance CT, neutral CT or calculated internally.

The phase voltages to the protection relay are fed from a voltage transformer.

The protection relay offers six different setting groups which can be set based onindividual needs. Each group can be activated or deactivated using the setting groupsettings available in the protection relay.

Depending on the communication protocol the required function block needs to beinstantiated in the configuration.

3.4.3.1 Functional diagrams for protection

The functional diagrams describe the IEDs protection functionality in detail andaccording to the factory set default connections.

1MRS756885 M Section 3REM615 standard configurations

REM615 65Application Manual

Page 72: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Two overcurrent stages are offered for overcurrent and short-circuit protection. Thenon-directional low stage PHLPTOC1 can be used for overcurrent protection whereasinstantaneous stage PHIPTOC1 can be used for short-circuit protection. Theoperation of PHIPTOC1 is not blocked as default by any functionality and it should beset over the motor start current level to avoid unnecessary operation.

The motor load jam protection function JAMPTOC1 is blocked by the motor start-upprotection function.

PHIPTOC1BLOCKENA_MULT

OPERATESTART

PHLPTOC1BLOCKENA_MULT

OPERATESTART

PHLPTOC1_OPERATE

PHIPTOC1_OPERATEPHIPTOC1_START

PHLPTOC1_START

JAMPTOC1BLOCK OPERATE JAMPTOC1_OPERATESTTPMSU1_MOT_STARTUP

GUID-FAF481A6-E226-4328-8991-0D7633BB9552 V1 EN

Figure 56: Overcurrent protection functions

Two negative-sequence overcurrent protection stages MNSPTOC1 and MNSPTOC2are provided for phase unbalance protection. These functions are used to protect themotor against phase unbalance. Unbalance in the network feeder of the motor causesoverheating of the motor.

MNSPTOC1BLOCK OPERATE

STARTBLK_RESTART

MNSPTOC2BLOCK OPERATE

STARTBLK_RESTART

ORB1B2

O

MNSPTOC1_BLK_RESTART

MNSPTOC2_BLK_RESTART

MNSPTOC1_OPERATE

MNSPTOC1_OPERATE

MNSPTOC2_OPERATE

MNSPTOC2_OPERATE

MNSPTOC1_START

MNSPTOC2_START

CCSPVC1_FAIL

CCSPVC1_FAIL

MNSPTOC_OPERATE

GUID-0937403C-E21D-4AE5-8185-700ADDA35BEC V2 EN

Figure 57: Negative-sequence overcurrent protection function

Section 3 1MRS756885 MREM615 standard configurations

66 REM615Application Manual

Page 73: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

The phase reversal protection PREVPTOC1 is based on the calculated negativephase-sequence current. It detects high negative sequence current values during motorstart-up, caused by incorrectly connected phases, which in turn causes the motor torotate in the opposite direction.

The negative-sequence and phase reversal protection are blocked if the current circuitsupervision detects failure in the current measurement circuit.

PREVPTOC1BLOCK OPERATE

STARTPREVPTOC1_OPERATEPREVPTOC1_START

CCSPVC1_FAIL

GUID-DC00B6A6-16DB-4C0C-B7FC-5ACF5386A3C3 V2 EN

Figure 58: Phase reversal protection function

One stage is provided for non-directional earth-fault protection EFHPTOC1 to detectphase-to-earth faults that may be result of, for example, insulation ageing. In addition,there is a directional protection stage DEFLPDEF1 which can also be used as a lowstage non-directional earth-fault protection without residual voltage requirement.However, the residual voltage can help to detect earth faults at a low fault current levelselectively and to discriminate the apparent residual current caused, for example, bypartial current transformer saturation at motor start-up.

Both the directional and non-directional earth-fault are blocked by the activation ofinstantaneous stage of overcurrent protection.

DEFLPDEF1BLOCKENA_MULTRCA_CTL

OPERATESTART

DEFLPDEF1_OPERATEPHIPTOC1_STARTDEFLPDEF1_START

EFHPTOC1BLOCKENA_MULT

OPERATESTART

EFHPTOC1_OPERATEPHIPTOC1_STARTEFHPTOC1_START

GUID-C8EAF55D-77EB-4DF7-AAE6-4FA425177EEB V1 EN

Figure 59: Earth-fault protection functions

The emergency start function ESMGAPC1 allows motor start-ups although thecalculated thermal level or cumulative start-up time counter is blocking the restart.The emergency start is enabled for ten minutes after the selected binary inputX110:BI6 is energized.

On the rising edge of the emergency start signal, various events occur.

1MRS756885 M Section 3REM615 standard configurations

REM615 67Application Manual

Page 74: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

• The calculated thermal level in MPTTR1 is set slightly below the restart inhibitlevel to allow at least one motor start-up.

• The value of the cumulative start-up time counter STTPMSU1 is set slightlybelow the set restart inhibit value to allow at least one motor start-up.

• The set start value of the MAPGAPC1 function is increased (or decreased)depending on the Start value Add setting (only if the optional RTD/mA moduleis included).

• Alarm LED 11 is activated.

A new emergency start cannot be made until the emergency start signal has been resetand the emergency start time has expired.

ESMGAPC1BLOCKST_EMERG_RQ

ST_EMERG_ENAX110_BI6_EMERG_START_ENA

ESMGAPC1_ST_EMERG_ENA

GUID-C2126238-0890-4C29-8D21-EEC005C0D18B V1 EN

Figure 60: Motor emergency start-up function

The thermal overload protection for motors MPTTR1 detects short and long termoverloads under varying load conditions. When the emergency start request is issuedfor the emergency start function, it activates the corresponding input of the thermaloverload function. Restart blocking, issued by the thermal overload function, preventsthe closing of the breaker in machine overload situation. The emergency start requestremoves the blocking and enables the restarting of the motor.

If IED is ordered with RTD/mA card, the motor ambient temperature can be measuredwith input RTD X130:AI8 and it is connected to the thermal overload protectionfunction MPTTR1.

MPTTR1BLOCKSTART_EMERGTEMP_AMB

OPERATEALARM

BLK_RESTART MPTTR1_BLK_RESTART

MPTTR1_OPERATEESMGAPC1_ST_EMERG_ENA

X130_AI8_MOTOR_AMBIENT_TEMPMPTTR1_ALARM

GUID-A12B6BCE-4B5E-4B1E-A883-F4293FE3223F V1 EN

Figure 61: Thermal overcurrent protection function

The restart inhibit is activated for a set period when a circuit breaker is opened. Thisis called remanence voltage protection where the motor has damping remanencevoltage after the circuit breaker opening. Reclosing after a too short period of time canlead to stress for the machine and other apparatus. The remanence voltage protectionwaiting time can be set by a timer function TPSGAPC1.

The restart inhibit is also activated under various conditions.

• An active trip command• Motor start-up supervision has issued lockout• Motor unbalance function has issued restart blocking• An external restart inhibit is activated by a binary input X120:BI4

Section 3 1MRS756885 MREM615 standard configurations

68 REM615Application Manual

Page 75: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

With the motor start-up supervision function STTPMSU1, the starting of the motor issupervised by monitoring three-phase currents or the status of the energizing circuitbreaker of the motor. When the emergency start request is activated by ESMGAPC1and STTPMSU1 is in lockout state, which inhibits motor starting, the lockout isdeactivated and emergency starting is available.

The upstream blocking from the motor start-up is connected to the binary outputX110:SO1. The output is used for sending a blocking signal to the relevantovercurrent protection stage of the IED at the infeeding bay.

STTPMSU1BLOCKBLK_LK_STCB_CLOSEDSTALL_INDST_EMERG_ENA

OPR_IITOPR_STALLMOT_START

LOCK_STARTX110_BI3_CB_CLOSED

STTPMSU1_LOCK_START

STTPMSU1_OPR_IIT

STTPMSU1_MOT_STARTUP

ESMGAPC1_ST_EMERG_ENA

GUID-3C9059F5-9F2D-4C18-878D-0673AC41C70F V

Figure 62: Motor start-up supervision function

The runtime counter for machines and devices MDSOPT1 provides history data sincethe last commissioning. The counter counts the total number of motor running hoursand is incremented when the energizing circuit breaker is closed.

MDSOPT1BLOCKPOS_ACTIVERESET

ALARMWARNINGX110_BI3_CB_CLOSED

MDSOPT1_ALARM

GUID-95BB595F-CD69-49FB-8100-E0C61ACF80A7 V1 EN

Figure 63: Motor runtime counter

The loss of load situation is detected by LOFLPTUC1. The loss of load situationoccurs, for example, if there is a damaged pump or a broken conveyor.

LOFLPTUC1BLOCK OPERATE

STARTLOFLPTUC1_OPERATE

GUID-3F2DA54F-8EE3-4270-83A1-35AAE360CED7 V1 EN

Figure 64: Loss of load protection function

The RTD/mA monitoring (optional) functionality provides several temperaturemeasurements for motor protection. Temperature of the motor windings U, V and Wis measured with inputs RTD X130:AI3, RTD X130:AI4, and RTD X130:AI5. Themeasured values are connected from function X130 (RTD) to function MAX3. Themaximum temperature value is connected to the analog multipurpose protectionMAPGAPC1.

The motor cooling air temperature and motor bearing temperature can be measuredwith inputs RTD X130:AI6 and RTD X130:AI7. The protection functionality fromthese temperatures is provided by MAPGAPC2 and MAPGAPC3 functions.

1MRS756885 M Section 3REM615 standard configurations

REM615 69Application Manual

Page 76: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

MAPGAPC1AI_VALUEBLOCKENA_ADD

OPERATESTART

MAPGAPC2AI_VALUEBLOCKENA_ADD

OPERATESTART

MAPGAPC3AI_VALUEBLOCKENA_ADD

OPERATESTART

MAX3IN1IN2IN3

OUT MAPGAPC1_OPERATE

MAPGAPC2_OPERATE

MAPGAPC3_OPERATE

MAPGAPC1_START

MAPGAPC2_START

MAPGAPC3_START

ESMGAPC1_ST_EMERG_ENA

X130_AI3_MOTOR_WDG_U_TEMPX130_AI4_MOTOR_WDG_V_TEMPX130_AI5_MOTOR_WDG_W_TEMP

X130_AI6_MOTOR_COOLING_AIR_TEMP

X130_AI7_MOTOR_BEARING_TEMP

OR6B1B2B3B4B5B6

OMAPGAPC1_OPERATEMAPGAPC2_OPERATEMAPGAPC3_OPERATE

MAPGAPC_OPERATE

GUID-1DF158C9-B026-481C-BAE9-3FC674F02F0C V1 EN

Figure 65: Multipurpose mA/RTD monitoring

The three-phase undervoltage protection PHPTUV1 offers protection againstabnormal phase voltage conditions. The positive-sequence undervoltage protectionPSPTUV1 and negative-sequence overvoltage protection NSPTOV1 functions areincluded to protect the machine against single-phasing, excessive unbalance betweenphases and abnormal phase order.

A failure in the voltage measuring circuit is detected by the fuse failure function. Theactivation is connected to block undervoltage protection functions and voltage basedunbalance protection functions to avoid faulty tripping. The three-phase undervoltageprotection PHPTUV1 in addition is also blocked during motor start-up to preventunwanted operation in case of a short voltage drop.

Section 3 1MRS756885 MREM615 standard configurations

70 REM615Application Manual

Page 77: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

PHPTUV1BLOCK OPERATE

STARTPHPTUV1_OPERATEPHPTUV1_START

BLOCK_PHPTUV

OR6B1B2B3B4B5B6

OPHPTUV1_OPERATEPSPTUV1_OPERATENSPTOV1_OPERATE

VOLTAGE_PROT_OPERATE

PSPTUV1BLOCK OPERATE

STARTPSPTUV1_OPERATEPSPTUV1_START

SEQSPVC1_FUSEF_U

NSPTOV1BLOCK OPERATE

STARTNSPTOV1_OPERATENSPTOV1_START

SEQSPVC1_FUSEF_U

GUID-E6F20A5B-02C9-4856-900E-F94940807A6A V2 EN

Figure 66: Voltage protection function

Two frequency protection stages FRPFRQ1 and FRPFRQ2 are offered. Thesefunctions are used to protect the motor against abnormal power system frequency.

1MRS756885 M Section 3REM615 standard configurations

REM615 71Application Manual

Page 78: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

FRPFRQ1BLOCK OPERATE

OPR_OFRQOPR_UFRQ

OPR_FRGSTART

ST_OFRQST_UFRQ

ST_FRG

FRPFRQ2BLOCK OPERATE

OPR_OFRQOPR_UFRQ

OPR_FRGSTART

ST_OFRQST_UFRQ

ST_FRG

ORB1B2

O

FRPFRQ1_OPERATE

FRPFRQ1_OPERATE

FRPFRQ2_OPERATE

FRPFRQ2_OPERATE

FRPFRQ1_START

FRPFRQ2_START

FREQUENCY_OPERATE

GUID-8F3373F6-1FE5-4492-B941-2DC0A6CBDD29 V1 EN

Figure 67: Frequency protection function

The circuit breaker failure protection CCBRBRF1 is initiated via the START input bynumber of different protection functions available in the IED. The circuit breakerfailure protection function offers different operating modes associated with the circuitbreaker position and the measured phase and residual currents.

The circuit breaker failure protection function has two operating outputs: TRRET andTRBU. The TRRET operate output is used for retripping its own breaker throughTRPPTRC2_TRIP. The TRBU output is used to give a backup trip to the breakerfeeding upstream. For this purpose, the TRBU operate output signal is connected to thebinary output X100:PO2.

CCBRBRF1BLOCKSTARTPOSCLOSECB_FAULT

CB_FAULT_ALTRBU

TRRET

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O CCBRBRF1_TRBU

X110_BI3_CB_CLOSED

PHLPTOC1_OPERATEPHIPTOC1_OPERATEJAMPTOC1_OPERATE

DEFLPDEF1_OPERATEEFHPTOC1_OPERATEMNSPTOC1_OPERATE

MNSPTOC2_OPERATESTTPMSU1_OPR_IIT

ARCSARC1_OPERATEARCSARC2_OPERATEARCSARC3_OPERATE

CCBRBRF1_TRRET

GUID-61192BCD-46A7-444A-B09E-A85AAA307DF6 V1 EN

Figure 68: Circuit breaker failure protection function

Section 3 1MRS756885 MREM615 standard configurations

72 REM615Application Manual

Page 79: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Three arc protection stages ARCSARC1...3 are included as an optional function. Thearc protection offers individual function blocks for three arc sensors that can beconnected to the IED. Each arc protection function block has two different operationmodes, that is, with or without the phase and residual current check.

The operate signals from ARCSARC1...3 are connected to both trip logic TRPPTRC1and TRPPTRC2. If the IED is ordered with high speed binary outputs, the individualoperate signals from ARCSARC1...3 are connected to dedicated trip logicTRPPTRC3...5. The outputs of TRPPTRC3...5 are available at high speed outputsX110:HSO1, X110:HSO2 and X110:HSO3.

1MRS756885 M Section 3REM615 standard configurations

REM615 73Application Manual

Page 80: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

OR6B1B2B3B4B5B6

O

ARCSARC1BLOCKREM_FLT_ARCOPR_MODE

OPERATEARC_FLT_DET

ARCSARC2BLOCKREM_FLT_ARCOPR_MODE

OPERATEARC_FLT_DET

ARCSARC3BLOCKREM_FLT_ARCOPR_MODE

OPERATEARC_FLT_DET

ARCSARC1_OPERATE

ARCSARC1_OPERATE

ARCSARC2_OPERATE

ARCSARC2_OPERATE

ARCSARC3_OPERATE

ARCSARC3_OPERATE

ARCSARC1_ARC_FLT_DET

ARCSARC2_ARC_FLT_DET

ARCSARC3_ARC_FLT_DET

ARC_OPERATE

GUID-AD2CD1B8-DEF5-4BEF-98EA-E1B9A9C04925 V1 EN

TRPPTRC3BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

TRPPTRC4BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

TRPPTRC5BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

TRPPTRC3_TRIP

TRPPTRC4_TRIP

TRPPTRC5_TRIP

ARCSARC1_OPERATE

ARCSARC2_OPERATE

ARCSARC3_OPERATE

X110_BI7_RST_LOCKOUT

X110_BI7_RST_LOCKOUT

X110_BI7_RST_LOCKOUT

GUID-6D80CE3D-2199-4449-A794-50D2FD8FA498 V1 EN

Figure 69: Arc protection with dedicated HSO

General start and operate from all the functions are connected to minimum pulse timerTPGAPC for setting the minimum pulse length for the outputs. The output fromTPGAPC is connected to binary outputs.

Section 3 1MRS756885 MREM615 standard configurations

74 REM615Application Manual

Page 81: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

TPGAPC1IN1IN2

OUT1OUT2 GENERAL_OPERATE_PULSE

GENERAL_START_PULSE

STTPMSU1_LOCK_START

PHPTUV1_OPERATEPSPTUV1_OPERATENSPTOV1_OPERATE

PHLPTOC1_OPERATEPHIPTOC1_OPERATEJAMPTOC1_OPERATE

DEFLPDEF1_OPERATEEFHPTOC1_OPERATEMNSPTOC1_OPERATE

MNSPTOC2_OPERATE

STTPMSU1_OPR_IIT

ARCSARC1_OPERATEARCSARC2_OPERATEARCSARC3_OPERATE

MAPGAPC1_OPERATEMAPGAPC2_OPERATEMAPGAPC3_OPERATE

PREVPTOC1_OPERATELOFLPTUC1_OPERATE

MPTTR1_OPERATE

FRPFRQ1_OPERATEFRPFRQ2_OPERATE

STTPMSU1_MOT_STARTUP

PHIPTOC1_START

MAPGAPC1_STARTMAPGAPC2_STARTMAPGAPC3_START

PHLPTOC1_START

DEFLPDEF1_STARTEFHPTOC1_START

MNSPTOC1_STARTMNSPTOC2_STARTPREVPTOC1_START

PHPTUV1_STARTPSPTUV1_STARTNSPTOV1_START

FRPFRQ1_STARTFRPFRQ2_START

GUID-81B01018-22D5-475E-B6FE-55830D5B7D80 V1 EN

Figure 70: General start and operate signals

The operate signals from the protection functions are connected to trip logicsTRPPTRC1. The output of these trip logic functions is available at binary outputX100:PO3 and also at X100:SO1. The trip logic functions are provided with a lockoutand latching function, event generation and the trip signal duration setting. If thelockout operation mode is selected, binary input X110:BI7 can be assigned toRST_LKOUT input of the trip logic to enable external reset with a push button.

Three other trip logics TRPPTRC3...4 are also available if the IED is ordered withhigh speed binary outputs options.

1MRS756885 M Section 3REM615 standard configurations

REM615 75Application Manual

Page 82: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

TRPPTRC1BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

TRPPTRC1_TRIP

PHPTUV1_OPERATEPSPTUV1_OPERATENSPTOV1_OPERATE

PHLPTOC1_OPERATEPHIPTOC1_OPERATEJAMPTOC1_OPERATE

DEFLPDEF1_OPERATEEFHPTOC1_OPERATEMNSPTOC1_OPERATE

MNSPTOC2_OPERATE

STTPMSU1_OPR_IIT

ARCSARC1_OPERATEARCSARC2_OPERATEARCSARC3_OPERATE

MAPGAPC1_OPERATEMAPGAPC2_OPERATEMAPGAPC3_OPERATE

PREVPTOC1_OPERATELOFLPTUC1_OPERATE

MPTTR1_OPERATE

CCBRBRF1_TRRET

X110_BI2_EXT_TRIPFRPFRQ1_OPERATEFRPFRQ2_OPERATE

X110_BI7_RST_LOCKOUTGUID-096B82A8-C0C6-4079-A225-108F9BDCE59B V1 EN

Figure 71: Trip logic TRPPTRC1

3.4.3.2 Functional diagrams for disturbance recorder

The START and the OPERATE outputs from the protection stages are routed to triggerthe disturbance recorder or, alternatively, only to be recorded by the disturbancerecorder depending on the parameter settings. Additionally, the selected signals fromdifferent functions and the few binary inputs are also connected to the disturbancerecorder.

Section 3 1MRS756885 MREM615 standard configurations

76 REM615Application Manual

Page 83: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

RDRE1C1C2C3C4C5C6C7C8C9C10C11C12C13C14C15C16C17C18C19C20C21C22C23C24C25C26C27C28C29C30C31C32C33C34C35C36C37C38C39C40C41C42C43C44C45C46C47C48C49C50C51C52C53C54C55C56C57C58C59C60C61C62C63C64

TRIGGERED

OR6B1B2B3B4B5B6

O

ORB1B2

O

ORB1B2

O

X110_BI8_SG_CHANGE

CCBRBRF1_TRBU

X110_BI4_CB_OPENEDX110_BI3_CB_CLOSED

STTPMSU1_LOCK_START

MPTTR1_BLK_RESTART

MNSPTOC1_BLK_RESTART

MNSPTOC2_BLK_RESTART

X110_BI1_EXT_RESTART_INHIBIT

PHPTUV1_OPERATEPSPTUV1_OPERATENSPTOV1_OPERATE

PHLPTOC1_OPERATEPHIPTOC1_OPERATEJAMPTOC1_OPERATE

DEFLPDEF1_OPERATEEFHPTOC1_OPERATE

MNSPTOC1_OPERATEMNSPTOC2_OPERATE

STTPMSU1_OPR_IIT

ARCSARC1_OPERATEARCSARC2_OPERATEARCSARC3_OPERATE

MAPGAPC1_OPERATEMAPGAPC2_OPERATEMAPGAPC3_OPERATE

PREVPTOC1_OPERATELOFLPTUC1_OPERATE

MPTTR1_OPERATE

CCBRBRF1_TRRET

X110_BI2_EXT_TRIP

FRPFRQ1_OPERATEFRPFRQ2_OPERATE

X110_BI7_RST_LOCKOUT

STTPMSU1_MOT_STARTUP

PHIPTOC1_START

MAPGAPC1_STARTMAPGAPC2_STARTMAPGAPC3_START

PHLPTOC1_START

DEFLPDEF1_STARTEFHPTOC1_START

MNSPTOC1_START

MNSPTOC2_START

PREVPTOC1_STARTPHPTUV1_STARTPSPTUV1_STARTNSPTOV1_STARTFRPFRQ1_STARTFRPFRQ2_START

CCSPVC1_FAIL

X110_BI6_EMERG_START_ENA

ESMGAPC1_ST_EMERG_ENA

SEQSPVC1_FUSEF_U

X110_BI5_MCB_OPENED

MPTTR1_ALARM

ARCSARC1_ARC_FLT_DETARCSARC2_ARC_FLT_DETARCSARC3_ARC_FLT_DET

SEQSPVC1_FUSEF_3PH

DISTURB_RECORD_TRIGGERED

GUID-8F9EE49B-4A88-4990-9F5A-B1B934E45EE3 V2 EN

Figure 72: Disturbance recorder

3.4.3.3 Functional diagrams for condition monitoring

CCSPVC1 detects failures in the current measuring circuits. When a failure isdetected, it can be used to block the current protection functions that measure thecalculated sequence component currents to avoid unnecessary operation. However,the BLOCK input signal is not connected in the configuration.

CCSPVC1BLOCK FAIL

ALARMCCSPVC1_FAILCCSPVC1_ALARM

GUID-89FEC503-CAB6-4068-9F76-A51950A66D43 V2 EN

Figure 73: Current circuit supervision function

The fuse failure supervision SEQSPVC1 detects failures in the voltage measurementcircuits. Failures, such as an open MCB, raise an alarm.

1MRS756885 M Section 3REM615 standard configurations

REM615 77Application Manual

Page 84: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

SEQSPVC1BLOCKCB_CLOSEDDISCON_OPENMINCB_OPEN

FUSEF_3PHFUSEF_UX110_BI3_CB_CLOSED SEQSPVC1_FUSEF_U

X110_BI5_MCB_OPENED

SEQSPVC1_FUSEF_3PH

GUID-F8A7FA9C-4EE8-4943-B087-23C4BCF8A8D7 V2 EN

Figure 74: Fuse failure supervision function

The circuit-breaker condition monitoring function SSCBR1 supervises the switchstatus based on the connected binary input information and the measured currentlevels. SSCBR1 introduces various supervision methods.

SSCBR1BLOCKPOSOPENPOSCLOSEOPEN_CB_EXECLOSE_CB_EXEPRES_ALM_INPRES_LO_INSPR_CHR_STSPR_CHRRST_IPOWRST_CB_WEARRST_TRV_TRST_SPR_T

TRV_T_OP_ALMTRV_T_CL_ALMSPR_CHR_ALM

OPR_ALMOPR_LO

IPOW_ALMIPOW_LO

CB_LIFE_ALMMON_ALM

PRES_ALMPRES_LO

OPENPOSINVALIDPOSCLOSEPOS

CB_OPEN_COMMANDCB_CLOSE_COMMAND

X110_BI4_CB_OPENEDX110_BI3_CB_CLOSED

SSCBR1_TRV_T_OP_ALMSSCBR1_TRV_T_CL_ALMSSCBR1_SPR_CHR_ALMSSCBR1_OPR_ALMSSCBR1_OPR_LOSSCBR1_IPOW_ALMSSCBR1_IPOW_LOSSCBR1_CB_LIFE_ALMSSCBR1_MON_ALMSSCBR1_PRES_ALMSSCBR1_PRES_LO

GUID-D1AA4644-EE6F-4686-9FB8-3FDD20EE292F V1 EN

Figure 75: Circuit-breaker condition monitoring function

ORB1B2

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

SSCBR1_TRV_T_OP_ALMSSCBR1_TRV_T_CL_ALMSSCBR1_SPR_CHR_ALM

SSCBR1_OPR_ALMSSCBR1_OPR_LO

SSCBR1_IPOW_ALM

SSCBR1_IPOW_LOSSCBR1_CB_LIFE_ALM

SSCBR1_MON_ALMSSCBR1_PRES_ALM

SSCBR1_PRES_LO

SSCBR1_ALARMS

GUID-30631446-3C4E-490A-A94C-70DC48E76E05 V1 EN

Figure 76: Logic for circuit breaker monitoring alarm

Two separate trip circuit supervision functions are included: TCSSCBR1 for poweroutput X100:PO3 for master trip and TCSSCBR2 for power output X100:PO4 forcircuit breaker closing. The trip circuit supervision TCSSCRB1 is blocked by themaster trip TRPPTRC1 and the circuit breaker open signal. The trip circuitsupervision TCSSCBR2 is blocked by the circuit breaker close signal.

It is assumed that there is no external resistor in the circuit breakertripping coil circuit connected in parallel with the circuit breakernormally open auxiliary contact.

Section 3 1MRS756885 MREM615 standard configurations

78 REM615Application Manual

Page 85: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

TCSSCBR1BLOCK ALARM

TCSSCBR2BLOCK ALARM

ORB1B2

O

ORB1B2

OTRPPTRC1_TRIP

X110_BI4_CB_OPENED

X110_BI3_CB_CLOSED

TCSSCBR1_ALARM

TCSSCBR1_ALARM

TCSSCBR2_ALARM

TCSSCBR2_ALARMTCSSCBR_ALARM

GUID-DC6189A6-9C93-4DCF-BF50-4C649C270858 V1 EN

Figure 77: Trip circuit supervision function

3.4.3.4 Functional diagrams for control and interlocking

The circuit breaker closing is enabled when the ENA_CLOSE input is activated. Theinput can be activated by the configuration logic, which is a combination of thedisconnector or breaker truck and earth-switch position status, status of the trip logics,gas pressure alarm and circuit-breaker spring charging status. In the configuration,only trip logic activates the close-enable signal to the circuit-breaker control functionblock. The open operation for circuit breaker is always enabled.

Connect the additional signals required by the application for closingand opening of the circuit breaker.

CBXCBR1POSOPENPOSCLOSEENA_OPENENA_CLOSEBLK_OPENBLK_CLOSEAU_OPENAU_CLOSETRIPSYNC_OKSYNC_ITL_BYP

SELECTEDEXE_OPEXE_CL

OP_REQCL_REQ

OPENPOSCLOSEPOS

OKPOSOPEN_ENAD

CLOSE_ENAD

TRUE

CBXCBR1_CLOSE_ENAD

RESTART_INHIBIT

X110_BI4_CB_OPENEDX110_BI3_CB_CLOSED

CBXCBR1_ENA_CLOSE

CBXCBR1_EXE_OPCBXCBR1_EXE_CL

FALSE

CBXCBR1_AU_OPENCBXCBR1_AU_CLOSE

GUID-A15641C5-367C-4102-A450-D224AE38552E V2 EN

Figure 78: Circuit breaker 1 control logic

ORB1B2

O CB_CLOSE_COMMANDCBXCBR1_EXE_CL

GUID-D943DA22-76B9-4B6C-BA53-B08A75D4FA72 V1 EN

Figure 79: Signals for closing coil of circuit breaker 1

1MRS756885 M Section 3REM615 standard configurations

REM615 79Application Manual

Page 86: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

ORB1B2

OTRPPTRC1_TRIP CB_OPEN_COMMANDCBXCBR1_EXE_OP

GUID-0ED63062-F19D-46CF-9061-93275B1AE89D V1 EN

Figure 80: Signals for opening coil of circuit breaker 1

NOTIN OUTTRPPTRC1_TRIP CBXCBR1_ENA_CLOSE

GUID-4BB7CA45-A584-4EE8-B2C0-E02D5B1CC8A1 V1 EN

Figure 81: Circuit breaker 1 close enable logic

Connect higher-priority conditions before enabling the circuitbreaker. These conditions cannot be bypassed with bypass feature ofthe function.

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

TRPPTRC1_TRIP

RESTART_INHIBIT

STTPMSU1_LOCK_START

MPTTR1_BLK_RESTART

MNSPTOC1_BLK_RESTARTMNSPTOC2_BLK_RESTART

END_OF_REMANENCE_TIME

X110_BI1_EXT_RESTART_INHIBIT

GUID-9523F9AB-A25C-461B-AB86-87A886DB6864 V1 EN

Figure 82: Circuit breaker 1 close blocking logic

When the motor restart is inhibited, the BLK_CLOSE input is activated and the circuitbreaker is not closed. When all conditions of the circuit breaker closing are met, theCLOSE_ENAD output of the CBXCBR1 is activated and the X100:PO1 output isclosed.

The configuration also includes restart inhibit. Restart inhibit is activated undervarious conditions.

• An active trip command• Motor start-up supervision has issued lockout• Motor unbalance function has issued restart blocking• Thermal protection has issued blocked restart• An external restart inhibit is activated by a binary input X120:BI4• Time during which remanence voltage is present

The configuration includes logic for generating circuit breaker external closing andopening command with the IED in local or remote mode.

Check the logic for the external circuit breaker closing command andmodify it according to the application.

Section 3 1MRS756885 MREM615 standard configurations

80 REM615Application Manual

Page 87: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Connect the additional signals for closing and opening of the circuitbreaker in local or remote mode, if applicable for the application.

ANDB1B2

O

ANDB1B2

O

ORB1B2

O CBXCBR1_AU_CLOSE

CONTROL_LOCAL

CONTROL_REMOTE

FALSE

FALSE

GUID-8C7FDA1C-5D7C-4A66-930F-A8BE8AE53D0A V1 EN

Figure 83: External closing command for circuit breaker 1

ANDB1B2

O

ORB1B2

O

ANDB1B2

O

CBXBCR1_AU_OPEN

CONTROL_LOCAL

CONTROL_REMOTE

FALSE

FALSE

GUID-8BC54BB0-CEE7-4890-B3DE-4B6957EBFD13 V1 EN

Figure 84: External opening command for circuit breaker 1

3.4.3.5 Functional diagrams for measurements functions

The phase current inputs to the IED are measured by the three-phase currentmeasurement function CMMXU1. The current input is connected to the X120 card inthe back panel. The sequence current measurement CSMSQI1 measures the sequencecurrent and the residual current measurement RESCMMXU1 measures the residualcurrent.

The three-phase voltage inputs to the IED are measured by the three-phase voltagemeasurement function VMMXU1 respectively. The voltage input is connected to theX130 card in the back panel. The sequence voltage measurement VSMSQI1 measuresthe sequence voltage.

The measurements can be seen in the LHMI and they are available under themeasurement option in the menu selection. Based on the settings, function blocks cangenerate low alarm or warning and high alarm or warning signals for the measuredcurrent values.

The frequency measurement FMMXU1 of the power system and the three-phasepower and energy measurement PEMMXU1 are available. The load profile recordLDPRLRC1 is included in the measurements sheet. LDPRLRC1 offers the ability toobserve the loading history of the corresponding feeder.

1MRS756885 M Section 3REM615 standard configurations

REM615 81Application Manual

Page 88: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

CMMXU1BLOCK HIGH_ALARM

HIGH_WARNLOW_WARN

LOW_ALARM

GUID-C54F36DB-09E4-46E9-BF50-E2FDF16A25A9 V1 EN

Figure 85: Current measurement: Three-phase current measurement

CSMSQI1

GUID-942BB8E4-7E19-47BD-8B29-6362EEE0E29B V1 EN

Figure 86: Current measurement: Sequence current measurement

RESCMMXU1BLOCK HIGH_ALARM

HIGH_WARN

GUID-C9A8998D-3F0B-48A7-90AF-72C55FDF5A88 V1 EN

Figure 87: Current measurement: Residual current measurement

VMMXU1BLOCK HIGH_ALARM

HIGH_WARNLOW_WARN

LOW_ALARM

GUID-34CA9A90-7D2D-4949-91AB-CD24FC1758A8 V1 EN

Figure 88: Voltage measurement: Three-phase voltage measurement

VSMSQI1

GUID-151BF252-6601-46FB-9438-41761F0DA39A V1 EN

Figure 89: Voltage measurement: Sequence voltage measurement

FMMXU1

GUID-3BECF359-6024-4ACB-8EB8-C3CF5F416744 V1 EN

Figure 90: Other measurement: Frequency measurement

PEMMXU1RSTACM

GUID-C453546A-9E42-4658-912A-B56187EA93D1 V1 EN

Figure 91: Other measurement: Three-phase power and energy measurement

FLTRFRC1BLOCKCB_CLRD

GUID-FE57CC4D-7B3C-4B3F-B412-D85686F59060 V2 EN

Figure 92: Other measurement: Data monitoring

Section 3 1MRS756885 MREM615 standard configurations

82 REM615Application Manual

Page 89: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

LDPRLRC1RSTMEM MEM_WARN

MEM_ALARM

GUID-DDA2CCF4-88C1-4AB7-9C80-13F7CD7F12FA V2 EN

Figure 93: Other measurement: Load profile record

3.4.3.6 Functional diagrams for I/O and alarm LEDs

ORB1B2

O

ORB1B2

O

ORB1B2

O

ORB1B2

O

ORB1B2

O

ORB1B2

O

ORB1B2

O

ORB1B2

O X110_BI8_SG_CHANGE

X110_BI4_CB_OPENED

X110_BI3_CB_CLOSED

X110_BI1_EXT_RESTART_INHIBIT

X110_BI2_EXT_TRIP

X110_BI7_RST_LOCKOUT

X110_BI6_EMERG_START_ENA

X110_BI5_MCB_OPENED

X110 (BIO).X110-Input 8

X110 (BIO-H).X110-Input 7

X110 (BIO).X110-Input 6

X110 (BIO-H).X110-Input 4

X110 (BIO).X110-Input 2

X110 (BIO-H).X110-Input 8

X110 (BIO-H).X110-Input 6

X110 (BIO-H).X110-Input 2

X110 (BIO).X110-Input 5

X110 (BIO-H).X110-Input 3

X110 (BIO).X110-Input 4

X110 (BIO-H).X110-Input 5

X110 (BIO).X110-Input 1

X110 (BIO).X110-Input 7

X110 (BIO).X110-Input 3

X110 (BIO-H).X110-Input 1

GUID-A7AD9820-AE94-4ADB-B4FD-60FAB8EF4AA7 V1 EN

Figure 94: Default binary inputs - X110

1MRS756885 M Section 3REM615 standard configurations

REM615 83Application Manual

Page 90: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

MOTOR_STARTUP_PULSE

THERMAL_ALARM_PULSE

VOLTAGE_PROT_OPERATE_PULSE

GENERAL_OPERATE_PULSE

TRPPTRC3_TRIP

TRPPTRC4_TRIP

TRPPTRC5_TRIP

X110 (BIO).X110-SO1

X110 (BIO).X110-SO2

X110 (BIO).X110-SO4

X110 (BIO).X110-SO3

X110 (BIO-H).X110-HSO1

X110 (BIO-H).X110-HSO2

X110 (BIO-H).X110-HSO3

GUID-BB5646F5-9DBF-443C-B139-79A1FE45871A V1 EN

Figure 95: Default binary outputs - X110

GENERAL_START_PULSE

CBXCBR1_CLOSE_ENAD

CCBRBRF1_TRBU

TRPPTRC1_TRIP

CB_OPEN_COMMAND

CB_CLOSE_COMMAND

X100 (PSM).X100-PO1

X100 (PSM).X100-PO2

X100 (PSM).X100-SO1

X100 (PSM).X100-SO2

X100 (PSM).X100-PO3

X100 (PSM).X100-PO4GUID-F65EAF03-936D-4A46-AD94-D47FA8F66AF2 V1 EN

Figure 96: Default binary outputs - X100

Section 3 1MRS756885 MREM615 standard configurations

84 REM615Application Manual

Page 91: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

X130_AI8_MOTOR_AMBIENT_TEMP

X130_AI3_MOTOR_WDG_U_TEMP

X130_AI4_MOTOR_WDG_V_TEMP

X130_AI5_MOTOR_WDG_W_TEMP

X130_AI6_MOTOR_COOLING_AIR_TEMP

X130_AI7_MOTOR_BEARING_TEMP

X130 (RTD).AI_VAL3

X130 (RTD).AI_VAL4

X130 (RTD).AI_VAL5

X130 (RTD).AI_VAL6

X130 (RTD).AI_VAL7

X130 (RTD).AI_VAL8GUID-D47D1857-2F58-4456-9880-EBBE90CE9388 V1 EN

Figure 97: Default mA/RTD inputs X130

1MRS756885 M Section 3REM615 standard configurations

REM615 85Application Manual

Page 92: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

ORB1B2

O

LED1OKALARMRESET

LED2OKALARMRESET

LED3OKALARMRESET

LED4OKALARMRESET

LED5OKALARMRESET

RESTART_INHIBIT

PHLPTOC1_OPERATE

PHIPTOC1_OPERATE

JAMPTOC1_OPERATE

DEFLPDEF1_OPERATEEFHPTOC1_OPERATE

STTPMSU1_OPR_IIT

PREVPTOC1_OPERATELOFLPTUC1_OPERATE

MPTTR1_OPERATE

VOLTAGE_PROT_OPERATEMNSPTOC_OPERATE

FREQUENCY_OPERATEMAPGAPC_OPERATE

GUID-7289A685-B44D-4FB0-879E-855252CD8DC3 V2 EN

Section 3 1MRS756885 MREM615 standard configurations

86 REM615Application Manual

Page 93: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

LED6OKALARMRESET

LED7OKALARMRESET

LED8OKALARMRESET

LED9OKALARMRESET

LED10OKALARMRESET

LED11OKALARMRESET

OR6B1B2B3B4B5B6

O

CCBRBRF1_TRBU

ESMGAPC1_ST_EMERG_ENA

SEQSPVC1_FUSEF_USEQSPVC1_FUSEF_3PH

DISTURB_RECORD_TRIGGERED

ARC_OPERATE

TCSSCBR_ALARM

MDSOPT1_ALARMCCSPVC1_ALARM

SSCBR1_ALARMS

GUID-F9A2A99B-C952-4D47-9E75-E9E047991114 V2 EN

Figure 98: Default LED connections

3.4.3.7 Functional diagrams for other timer logics

The configuration also includes voltage operate, motor startup and thermal alarm,blocking logic for phase under voltage protection and logic for remanence voltage.The restart inhibit is activated for a set period when a circuit breaker is in open state.This is called remanence voltage protection where the motor has damping remanencevoltage after the opening of a circuit breaker. Reclosing after a short period of time canlead to stress for the machine and other apparatus. The remanence voltage protectionwaiting time can be set by a timer function TPSGAPC1.

TPGAPC3IN1IN2

OUT1OUT2

VOLTAGE_PROT_OPERATE_PULSEVOLTAGE_PROT_OPERATE

GUID-079D5685-0D3D-4F5F-8120-7A7BB7B4184B V1 EN

Figure 99: Timer logic for voltage protection operate alarm

1MRS756885 M Section 3REM615 standard configurations

REM615 87Application Manual

Page 94: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

TPGAPC2IN1IN2

OUT1OUT2

MOTOR_STARTUP_PULSETHERMAL_ALARM_PULSE

STTPMSU1_MOT_STARTUPMPTTR1_ALARM

GUID-93AD6A7A-ABE6-4B6D-82D8-EDA0B5E1C9BB V1 EN

Figure 100: Timer logic for motor startup and thermal alarm

Add signals for blocking phase undervoltage protection.

OR6B1B2B3B4B5B6

OSTTPMSU1_MOT_STARTUPSEQSPVC1_FUSEF_U

BLOCK_PHPTUV

GUID-341CECED-357B-445F-A1E7-C89863ADAE53 V2 EN

Figure 101: Blocking logic for phase undervoltage protection

TPSGAPC1IN1IN2

OUT1OUT2

CB_OPEN_COMMAND END_OF_REMANENCE_TIME

GUID-921A62B2-1032-4600-B26C-4A8F1BE93EBC V1 EN

Figure 102: Timer logic for remanence voltage to disappear

3.4.3.8 Other functions

The configuration includes few instances of multipurpose protection functionMAPGAPC and different types of timers and control functions. These functions arenot included in application configuration but they can be added based on the systemrequirements.

3.5 Standard configuration C

3.5.1 Applications

The standard configuration for motor protection with current and voltage basedprotection and measurements functions is intended for comprehensive protection andcontrol functionality of the circuit breaker controlled asynchronous motors. Withminor modifications, the standard configuration can also be applied for contactorcontrolled motors.

The protection relay with a standard configuration is delivered from the factory withdefault settings and parameters. The end user flexibility for incoming, outgoing and

Section 3 1MRS756885 MREM615 standard configurations

88 REM615Application Manual

Page 95: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

internal signal designation within the protection relay enables this configuration to befurther adapted to different primary circuit layouts and the related functionality needsby modifying the internal functionality using PCM600.

3.5.2 Functions

Io

CONDITION MONITORING AND SUPERVISION

ALSO AVAILABLE

- Disturbance and fault recorders- Event log and recorded data- High-Speed Output module (optional)- Local/Remote push button on LHMI- Self-supervision- Time synchronization: IEEE 1588 v2,

SNTP, IRIG-B- User management- Web HMI

REMARKS

Optionalfunction

No. ofinstances

Alternative function to be defined when ordering

OR

Io/Uo

Calculatedvalue

CONTROL AND INDICATION 1) MEASUREMENT

MOTOR PROTECTION AND CONTROL RELAY

PROTECTION LOCAL HMI

Analog interface types 1)

Current transformer

Voltage transformer

1) Conventional transformer inputs

ESTARTESTART

Object Ctrl 2) Ind 3)

CB 1 -

DC 2 3

ES 1 21) Check availability of binary inputs/outputs

from technical documentation2) Control and indication function for

primary object3) Status indication function for primary object

STANDARD CONFIGURATION

RL

ClearESCI

O

Configuration ASystemHMITimeAuthorization

RL

ClearESCI

O

U12 0. 0 kVP 0.00 kWQ 0.00 kVAr

IL2 0 A

A

18×MAPMAP

REM615

- I, U, Io, Uo, P, Q, E, pf, f- Limit value supervision- Load profile record- Symmetrical components

4

5

C

COMMUNICATION

Protocols: IEC 61850-8-1/-9-2LE Modbus®

IEC 60870-5-103 DNP3Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232Redundant protocols: HSR PRP RSTP

2) One of the five inputs is reserved for future applications

2)

Master TripLockout relay

94/86

CBCMCBCM

FUSEF60

Io>→67N-1

3U<27

U2>47O-

U1<47U+

2×f>/f<,df/dt81

MCS 3IMCS 3I

2×TCSTCM

OPTSOPTM

3×ARC

50L/50NL

3I<37

2×I2>M46M

I2>>46R

3Ith>M49M

Is2t n<49, 66, 48, 51LR

3I>>>50P/51P

3I>/Io>BF51BF/51NBF

Ist>51LR

3I>51P-1

Io>>51N-2

3I>>51P-2

Uo

Io

3I Io

3I

Io

UL1UL2UL3

UL1

UL2

UL3

UL1

UL2

UL3

Uo

ORAND

Master TripLockout relay

94/86

3×2×

GUID-C6EEADA8-8AB0-4BE0-8D58-97351C7B0D07 V2 EN

Figure 103: Functionality overview for standard configuration C

3.5.2.1 Default I/O connections

Connector pins for each input and output are presented in the IED physicalconnections section.

1MRS756885 M Section 3REM615 standard configurations

REM615 89Application Manual

Page 96: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Table 23: Default connections for binary inputs

Binary input DescriptionX110-BI1 MCB open

X110-BI2 Setting group change

X110-BI3 Rotation direction

X110-BI4 Speed switch (motor running)

X110-BI5 Disconnector close/circuit breaker truck in

X110-BI6 Disconnector close/circuit breaker truck out

X110-BI7 Earth-switch close

X110-BI8 Earth-switch open

X120-BI1 Emergency start enable

X120-BI2 Circuit breaker closed

X120-BI3 Circuit breaker open

X120-BI4 Lock-out reset

X130-BI1 External restart inhibit

X130-BI2 External trip

X130-BI3 Gas pressure alarm

X130-BI4 Circuit breaker spring charged

Table 24: Default connections for binary outputs

Binary output DescriptionX100-PO1 Restart enable

X100-PO2 Breaker failure backup trip to upstream breaker

X100-SO1 Open command (for contractor application)

X100-SO2 Operate indication

X100-PO3 Open circuit breaker/trip

X100-PO4 Close circuit breaker

X110-SO1 Motor startup indication

X110-SO2 Thermal overload alarm

X110-SO3 Protection start alarm

X110-HSO1 Arc protection instance 1 operate activated

X110-HSO2 Arc protection instance 2 operate activated

X110-HSO3 Arc protection instance 3 operate activated

Table 25: Default connections for LEDs

LED Description1 Short-circuit protection operate

2 Earth-fault protection operate

3 Thermal overload protection operate

Table continues on next page

Section 3 1MRS756885 MREM615 standard configurations

90 REM615Application Manual

Page 97: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

LED Description4 Combined operate indication of the other protection functions

5 Motor restart inhibit

6 Breaker failure protection operate

7 Disturbance recorder triggered

8 Circuit breaker condition monitoring alarm

9 TCS, motor runtime counter or measuring circuit fault alarm

10 Arc protection operate

11 Emergency start enabled

3.5.2.2 Default disturbance recorder settings

Table 26: Default disturbance recorder analog channels

Channel Description1 IL1

2 IL2

3 IL3

4 Io

5 Uo

6 U1

7 U2

8 U3

9 -

10 -

11 -

12 -

Table 27: Default disturbance recorder binary channels

Channel ID text Level trigger mode1 PHLPTOC1 - start Positive or Rising

2 PHIPTOC2 - start Positive or Rising

3 DEFLPDEF1 - start Positive or Rising

4 EFHPTOC1 - start Positive or Rising

5 MPTTR1 - alarm Level trigger off

6 MPTTR1 - blk restart Level trigger off

7 ESMGAPC1 - st emerg ena Level trigger off

8 STTPMSU1 - mot startup Positive or Rising

9 STTPMSU1 - lock start Level trigger off

10 MNSPTOC1 - start Positive or Rising

Table continues on next page

1MRS756885 M Section 3REM615 standard configurations

REM615 91Application Manual

Page 98: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Channel ID text Level trigger mode11 MNSPTOC1 - blk restart Level trigger off

12 MNSPTOC2 - start Positive or Rising

13 MNSPTOC2 - blk restart Level trigger off

14 PREVPTOC1 - start Positive or Rising

15 PHPTUV1 - start Positive or Rising

16 PSPTUV1 - start Positive or Rising

17 NSPTOV1 - start Positive or Rising

18 FRPFRQ1 - start Positive or Rising

19 FRPFRQ2 - start Positive or Rising

20 CCBRBRF1 - trret Level trigger off

21 CCBRBRF1 - trbu Level trigger off

22 PHLPTOC1 - operate Level trigger off

23 PHIPTOC2 - operate Level trigger off

24 JAMPTOC1 - operate Level trigger off

25 DEFLPDEF1 - operate Level trigger off

EFHPTOC2 - operate

26 MNSPTOC1 - operate Level trigger off

MNSPTOC2 - operate

27 PREVPTOC1 - operate Level trigger off

28 LOFLPTUC1 - operate Level trigger off

29 MPTTR1 - operate Level trigger off

30 PHPTUV1 - operate Level trigger off

31 PSPTUV1 - operate Level trigger off

32 NSPTOV1 - operate Level trigger off

33 FRPFRQ1 - operate Level trigger off

34 FRPFRQ2 - operate Level trigger off

35 X120BI1 - emerg start ena Level trigger off

36 X120BI2 - CB closed Level trigger off

37 X120BI3 - CB opened Level trigger off

38 X130BI1 - ext restart inhibit Level trigger off

39 X130BI2 - ext trip Positive or Rising

40 X130BI3 - gas pressure alarm Level trigger off

41 X130BI4 - CB spring charged Level trigger off

42 X110BI1 - MCB opened Level trigger off

43 X110BI2 - SG changed Level trigger off

44 X110BI3 - rotate direction Level trigger off

45 X110BI4 - speed switch Level trigger off

46 STTPMSU1 - opr iit Positive or Rising

47 STTPMSU1 - opr stall Positive or Rising

Table continues on next page

Section 3 1MRS756885 MREM615 standard configurations

92 REM615Application Manual

Page 99: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Channel ID text Level trigger mode48 SEQSPVC1 - fusef 3ph Level trigger off

49 SEQSPVC1 - fusef u Level trigger off

50 CCSPVC1 - fail Level trigger off

51 ARCSARC1 - ARC flt det Level trigger off

ARCSARC2 - ARC flt det

ARCSARC3 - ARC flt det

52 ARCSARC1 - operate Positive or Rising

53 ARCSARC2 - operate Positive or Rising

54 ARCSARC3 - operate Positive or Rising

3.5.3 Functional diagrams

The functional diagrams describe the default input, output, alarm LED and function-to-function connections. The default connections can be viewed and changed withPCM600 according to the application requirements.

The analog channels have fixed connections to the different function blocks inside theprotection relay’s standard configuration. However, the 12 analog channels availablefor the disturbance recorder function are freely selectable as a part of the disturbancerecorder’s parameter settings.

The phase currents to the protection relay are fed from a current transformer. Theresidual current to the protection relay is fed from either residually connected CTs, anexternal core balance CT, neutral CT or calculated internally.

The phase voltages to the protection relay are fed from a voltage transformer. Theresidual voltage to the protection relay is fed from either residually connected VTs, anopen delta connected VT or calculated internally.

The protection relay offers six different setting groups which can be set based onindividual needs. Each group can be activated or deactivated using the setting groupsettings available in the protection relay.

Depending on the communication protocol the required function block needs to beinstantiated in the configuration.

3.5.3.1 Functional diagrams for protection

The functional diagrams describe the IEDs protection functionality in detail andaccording to the factory set default connections.

Two overcurrent stages are offered for overcurrent and short-circuit protection. Thenon-directional low stage PHLPTOC1 can be used for overcurrent protection whereasinstantaneous stage PHIPTOC1 can be used for short-circuit protection. Theoperation of PHIPTOC1 is not blocked as default by any functionality and it should beset over the motor start current level to avoid unnecessary operation. The motor load

1MRS756885 M Section 3REM615 standard configurations

REM615 93Application Manual

Page 100: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

jam protection function JAMPTOC1 is blocked by the motor start-up protectionfunction.

PHIPTOC1BLOCKENA_MULT

OPERATESTART

PHLPTOC1BLOCKENA_MULT

OPERATESTART

PHLPTOC1_OPERATE

PHIPTOC1_OPERATEPHIPTOC1_START

PHLPTOC1_START

JAMPTOC1BLOCK OPERATE JAMPTOC1_OPERATESTTPMSU1_MOT_STARTUP

GUID-DBE4CD75-F49A-40D0-B0F5-A7D40C59A2E8 V1 EN

Figure 104: Overcurrent protection functions

Two negative-sequence overcurrent protection stages MNSPTOC1 and MNSPTOC2are provided for phase unbalance protection. These functions are used to protect themotor against phase unbalance. Unbalance in the network feeder of the motor causesoverheating of the motor.

MNSPTOC1BLOCK OPERATE

STARTBLK_RESTART

MNSPTOC2BLOCK OPERATE

STARTBLK_RESTART

ORB1B2

O

MNSPTOC1_BLK_RESTART

MNSPTOC2_BLK_RESTART

MNSPTOC1_OPERATE

MNSPTOC1_OPERATE

MNSPTOC2_OPERATE

MNSPTOC2_OPERATE

MNSPTOC1_START

MNSPTOC2_START

BLOCK_MNSPTOC_AND_PREVPTOC

BLOCK_MNSPTOC_AND_PREVPTOC

MNSPTOC_OPERATE

GUID-0A652CF6-EF49-459D-8B3A-B92B84E4E064 V1 EN

Figure 105: Negative-sequence overcurrent protection function

The phase reversal protection PREVPTOC1 is based on the calculated negative phasesequence current. It detects high negative sequence current values during motor start-up, caused by incorrectly connected phases, which in turn causes the motor to rotatein the opposite direction.

The negative-sequence and phase reversal protection are blocked if the current circuitsupervision detects failure in the current measurement circuit or when the networkrotation direction changes.

Section 3 1MRS756885 MREM615 standard configurations

94 REM615Application Manual

Page 101: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

PREVPTOC1BLOCK OPERATE

STARTPREVPTOC1_OPERATEPREVPTOC1_START

BLOCK_MNSPTOC_AND_PREVPTOC

GUID-52C8EF5A-C63F-43C4-905C-91DE8D949887 V1 EN

Figure 106: Phase reversal protection function

One stage is provided for non-directional earth-fault protection EFHPTOC1 to detectphase-to-earth faults that may be the result of, for example, insulation ageing. Adirectional protection stage DEFLPDEF1 can also be used as a low stage non-directional earth-fault protection without residual voltage requirement. However, theresidual voltage can help to detect earth faults at a low fault current level selectivelyand to discriminate the apparent residual current caused, for example, by partialcurrent transformer saturation at motor start-up.

Both the directional and non-directional earth-fault are blocked by the activation ofinstantaneous stage of overcurrent protection.

DEFLPDEF1BLOCKENA_MULTRCA_CTL

OPERATESTART

DEFLPDEF1_OPERATEPHIPTOC1_STARTDEFLPDEF1_START

EFHPTOC1BLOCKENA_MULT

OPERATESTART

EFHPTOC1_OPERATEPHIPTOC1_STARTEFHPTOC1_START

GUID-6D556CB9-FB2D-4FBE-93F4-DC87E9C53FE2 V1 EN

Figure 107: Earth-fault protection functions

The emergency start function ESMGAPC1 allows motor start-ups although thecalculated thermal level or cumulative start-up time counter is blocking the restart.The emergency start is enabled for ten minutes after the selected binary inputX120:BI1 is energized.

On the rising edge of the emergency start signal, various events occur.

• The calculated thermal level in MPTTR1 is set slightly below the restart inhibitlevel to allow at least one motor start-up.

• The value of the cumulative start-up time counter STTPMSU1 is set slightlybelow the set restart inhibit value to allow at least one motor start-up.

• Alarm LED 11 is activated.

A new emergency start cannot be made until the emergency start signal has been resetand the emergency start time has expired.

1MRS756885 M Section 3REM615 standard configurations

REM615 95Application Manual

Page 102: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

ESMGAPC1BLOCKST_EMERG_RQ

ST_EMERG_ENAX110_BI6_EMERG_START_ENA

ESMGAPC1_ST_EMERG_ENA

GUID-C5195DB3-DC48-4C06-B748-E70A51C1A7BD V1 EN

Figure 108: Motor emergency start-up function

The thermal overload protection for motors MPTTR1 detects short and long termoverloads under varying load conditions. When the emergency start request is issuedfor the emergency start function, it activates the corresponding input of the thermaloverload function. Restart blocking, issued by the thermal overload function, preventsthe closing of the breaker in machine overload situation. The emergency start requestremoves the blocking and enables the restarting of the motor.

MPTTR1BLOCKSTART_EMERGTEMP_AMB

OPERATEALARM

BLK_RESTART MPTTR1_BLK_RESTART

MPTTR1_OPERATEESMGAPC1_ST_EMERG_ENA MPTTR1_ALARM

GUID-3B8C3BFA-9273-4BE4-A600-8F2AA5FBF99F V1 EN

Figure 109: Thermal overcurrent protection function

The restart inhibit is activated for a set period when a circuit breaker is opened. Thisis called remanence voltage protection where the motor has damping remanencevoltage after the circuit breaker opening. Re-closing after a too short period of timecan lead to stress for the machine and other apparatus. The remanence voltageprotection waiting time can be set by a timer function TPSGAPC1.

The restart inhibit is also activated under various conditions.

• An active trip command• Motor start-up supervision has issued lockout• Motor unbalance function has issued restart blocking• An external restart inhibit is activated by a binary input X130:BI1

With the motor start-up supervision function STTPMSU1, the starting of the motor issupervised by monitoring three-phase currents or the status of the energizing circuitbreaker of the motor. When the emergency start request is activated by ESMGAPC1and STTPMSU1 is in lockout state, which inhibits motor starting, the lockout isdeactivated and emergency starting is available.

The upstream blocking from the motor start-up is connected to the binary outputX110:SO1. The output is used for sending a blocking signal to the relevantovercurrent protection stage of the IED at the infeeding bay.

STTPMSU1BLOCKBLK_LK_STCB_CLOSEDSTALL_INDST_EMERG_ENA

OPR_IITOPR_STALLMOT_START

LOCK_START

NOTIN OUT

X120_BI2_CB_CLOSEDSTTPMSU1_LOCK_START

STTPMSU1_OPR_IITSTTPMSU1_OPR_STALLSTTPMSU1_MOT_STARTUP

ESMGAPC1_ST_EMERG_ENA

X110_BI4_SPEED_SWITCH

GUID-5928D9C4-DFE7-4DE8-AEB6-E5FC037BC56F V1 EN

Figure 110: Motor start-up supervision function

Section 3 1MRS756885 MREM615 standard configurations

96 REM615Application Manual

Page 103: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

The runtime counter for machines and devices MDSOPT1 provides history data sincethe last commissioning. The counter counts the total number of motor running hoursand is incremented when the energizing circuit breaker is closed.

MDSOPT1BLOCKPOS_ACTIVERESET

ALARMWARNINGX120_BI2_CB_CLOSED

MDSOPT1_ALARM

GUID-F729AF12-C821-4741-808E-37A9CCF939A0 V1 EN

Figure 111: Motor runtime counter

The loss of load situation is detected by LOFLPTUC1. The loss of load situationoccurs, for example, if there is a damaged pump or a broken conveyor.

LOFLPTUC1BLOCK OPERATE

STARTLOFLPTUC1_OPERATE

GUID-7611604A-150E-4017-BE05-CD19A060224D V1 EN

Figure 112: Loss of load

The three-phase undervoltage protection PHPTUV1 offers protection againstabnormal phase voltage conditions. Positive-sequence undervoltage protectionPSPTUV and negative-sequence overvoltage protection NSPTOV functions areincluded to protect the machine against single-phasing, excessive unbalance betweenphases and abnormal phase order.

A failure in the voltage measuring circuit is detected by the fuse failure function. Theactivation is connected to block undervoltage protection functions and voltage basedunbalance protection functions to avoid faulty tripping. The three-phase undervoltageprotection PHPTUV1 in addition is also blocked during motor start-up to preventunwanted operation in case of short voltage drop, whereas positive and negativesequence protection is blocked when the network rotation direction changes.

1MRS756885 M Section 3REM615 standard configurations

REM615 97Application Manual

Page 104: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

PHPTUV1BLOCK OPERATE

STARTPHPTUV1_OPERATEPHPTUV1_START

BLOCK_PHPTUV

PSPTUV1BLOCK OPERATE

STARTPSPTUV1_OPERATEPSPTUV1_START

BLOCK_PSPTUV_AND_NSPTOV

NSPTOV1BLOCK OPERATE

STARTNSPTOV1_OPERATENSPTOV1_START

BLOCK_PSPTUV_AND_NSPTOV

OR6B1B2B3B4B5B6

OPHPTUV1_OPERATEPSPTUV1_OPERATENSPTOV1_OPERATE

VOLTAGE_PROT_OPERATE

GUID-9A71649C-FA63-42E9-A2E6-9888DCDFB526 V1 EN

Figure 113: Undervoltage and sequence voltage protection function

Two frequency protection stages FRPFRQ1 and FRPFRQ2 are offered. Thesefunctions are used to protect the motor against an abnormal power system frequency.

FRPFRQ1BLOCK OPERATE

OPR_OFRQOPR_UFRQ

OPR_FRGSTART

ST_OFRQST_UFRQ

ST_FRG

FRPFRQ2BLOCK OPERATE

OPR_OFRQOPR_UFRQ

OPR_FRGSTART

ST_OFRQST_UFRQ

ST_FRG

ORB1B2

O

FRPFRQ1_OPERATE

FRPFRQ1_OPERATE

FRPFRQ2_OPERATE

FRPFRQ2_OPERATE

FRPFRQ1_START

FRPFRQ2_START

FREQUENCY_OPERATE

GUID-ED2CB6D1-1C49-4BAA-9EF4-4BDDDADB3C7F V1 EN

Figure 114: Frequency protection function

Section 3 1MRS756885 MREM615 standard configurations

98 REM615Application Manual

Page 105: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

The circuit breaker failure protection CCBRBRF1 is initiated via the START input bynumber of different protection functions available in the IED. The circuit breakerfailure protection function offers different operating modes associated with the circuitbreaker position and the measured phase and residual currents.

The circuit breaker failure protection function has two operating outputs: TRRET andTRBU. The TRRET operate output is used for retripping its own breaker throughTRPPTRC2_TRIP. The TRBU output is used to give a backup trip to the breakerfeeding upstream. For this purpose, the TRBU operate output signal is connected to thebinary output X100:PO2.

CCBRBRF1BLOCKSTARTPOSCLOSECB_FAULT

CB_FAULT_ALTRBU

TRRET

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O CCBRBRF1_TRBU

X120_BI2_CB_CLOSED

PHLPTOC1_OPERATEPHIPTOC1_OPERATEJAMPTOC1_OPERATE

DEFLPDEF1_OPERATEEFHPTOC1_OPERATEMNSPTOC1_OPERATE

MNSPTOC2_OPERATESTTPMSU1_OPR_IIT

ARCSARC1_OPERATEARCSARC2_OPERATEARCSARC3_OPERATE

CCBRBRF1_TRRET

STTPMSU1_OPR_STALL

GUID-C4DF665A-7BC4-4350-A327-5376EB242488 V1 EN

Figure 115: Circuit breaker failure protection function

Three arc protection stages ARCSARC1...3 are included as an optional function. Thearc protection offers individual function blocks for three arc sensors that can beconnected to the IED. Each arc protection function block has two different operationmodes with or without the phase and residual current check.

The operate signals from ARCSARC1...3 are connected to both trip logic TRPPTRC1and TRPPTRC2. If the IED has been ordered with high speed binary outputs,individual operate signals from ARCSARC1...3 are connected to dedicated trip logicTRPPTRC3...5. The outputs of TRPPTRC3...5 are available at high speed outputsX110:HSO1, X110:HSO2 and X110:HSO3.

1MRS756885 M Section 3REM615 standard configurations

REM615 99Application Manual

Page 106: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

OR6B1B2B3B4B5B6

O

ARCSARC1BLOCKREM_FLT_ARCOPR_MODE

OPERATEARC_FLT_DET

ARCSARC2BLOCKREM_FLT_ARCOPR_MODE

OPERATEARC_FLT_DET

ARCSARC3BLOCKREM_FLT_ARCOPR_MODE

OPERATEARC_FLT_DET

ARCSARC1_OPERATE

ARCSARC1_OPERATE

ARCSARC2_OPERATE

ARCSARC2_OPERATE

ARCSARC3_OPERATE

ARCSARC3_OPERATE

ARCSARC1_ARC_FLT_DET

ARCSARC2_ARC_FLT_DET

ARCSARC3_ARC_FLT_DET

ARC_OPERATE

GUID-89F56A09-D132-43B3-81F6-C5A0B9136946 V1 EN

TRPPTRC3BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

TRPPTRC4BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

TRPPTRC5BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

TRPPTRC3_TRIP

TRPPTRC4_TRIP

TRPPTRC5_TRIP

ARCSARC1_OPERATE

ARCSARC2_OPERATE

ARCSARC3_OPERATE

X120_BI4_RST_LOCKOUT

X120_BI4_RST_LOCKOUT

X120_BI4_RST_LOCKOUT

GUID-D3C03537-D501-437A-B871-6FB1F43BE698 V1 EN

Figure 116: Arc protection with dedicated HSO

General start and operate from all the functions are connected to minimum pulse timerTPGAPC for setting the minimum pulse length for the outputs. The output fromTPGAPC is connected to binary outputs.

Section 3 1MRS756885 MREM615 standard configurations

100 REM615Application Manual

Page 107: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

TPGAPC1IN1IN2

OUT1OUT2

GENERAL_START_PULSEGENERAL_OPERATE_PULSE

STTPMSU1_LOCK_START

PHPTUV1_OPERATEPSPTUV1_OPERATENSPTOV1_OPERATE

PHLPTOC1_OPERATEPHIPTOC1_OPERATEJAMPTOC1_OPERATE

DEFLPDEF1_OPERATEEFHPTOC1_OPERATEMNSPTOC1_OPERATE

MNSPTOC2_OPERATE

STTPMSU1_OPR_IIT

ARCSARC1_OPERATEARCSARC2_OPERATEARCSARC3_OPERATE

PREVPTOC1_OPERATELOFLPTUC1_OPERATE

MPTTR1_OPERATE

FRPFRQ1_OPERATEFRPFRQ2_OPERATE

STTPMSU1_MOT_STARTUP

PHIPTOC1_STARTPHLPTOC1_START

DEFLPDEF1_STARTEFHPTOC1_START

MNSPTOC1_STARTMNSPTOC2_STARTPREVPTOC1_START

PHPTUV1_STARTPSPTUV1_STARTNSPTOV1_START

FRPFRQ1_STARTFRPFRQ2_START

GUID-4D208014-27C2-4646-AE6E-8A5F8F5A58A8 V1 EN

Figure 117: General start and operate signals

The operate signals from the protections are connected to trip logics TRPPTRC1. Theoutput of these trip logic functions is available at binary output X100:PO3 and also atX100:SO1. The trip logic functions are provided with a lockout and latching function,event generation and the trip signal duration setting. If the lockout operation mode isselected, binary input X120:BI4 can be assigned to RST_LKOUT input of the trip logicto enable external reset with a push button.

Three other trip logics TRPPTRC3...4 are also available if the IED is ordered withhigh speed binary outputs options.

1MRS756885 M Section 3REM615 standard configurations

REM615 101Application Manual

Page 108: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

TRPPTRC1BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

OTRPPTRC1_TRIP

PHPTUV1_OPERATEPSPTUV1_OPERATENSPTOV1_OPERATE

PHLPTOC1_OPERATEPHIPTOC1_OPERATEJAMPTOC1_OPERATE

DEFLPDEF1_OPERATEEFHPTOC1_OPERATEMNSPTOC1_OPERATE

MNSPTOC2_OPERATE

STTPMSU1_OPR_IIT

ARCSARC1_OPERATEARCSARC2_OPERATEARCSARC3_OPERATE

PREVPTOC1_OPERATELOFLPTUC1_OPERATE

MPTTR1_OPERATE

CCBRBRF1_TRRET

X130_BI2_EXT_TRIPFRPFRQ1_OPERATEFRPFRQ2_OPERATE

X120_BI4_RST_LOCKOUT

STTPMSU1_OPR_STALL

GUID-391D553C-A9B7-4AA5-8ADE-E239675E333A V1 EN

Figure 118: Trip logic TRPPTRC1

3.5.3.2 Functional diagrams for disturbance recorder

The START and the OPERATE outputs from the protection stages are routed to triggerthe disturbance recorder or, alternatively, only to be recorded by the disturbancerecorder depending on the parameter settings. Additionally, the selected signals fromdifferent functions and the few binary inputs are also connected to the disturbancerecorder.

Section 3 1MRS756885 MREM615 standard configurations

102 REM615Application Manual

Page 109: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

RDRE1C1C2C3C4C5C6C7C8C9C10C11C12C13C14C15C16C17C18C19C20C21C22C23C24C25C26C27C28C29C30C31C32C33C34C35C36C37C38C39C40C41C42C43C44C45C46C47C48C49C50C51C52C53C54C55C56C57C58C59C60C61C62C63C64

TRIGGERED

OR6B1B2B3B4B5B6

O

ORB1B2

O

ORB1B2

O

X110_BI2_SG_CHANGE

CCBRBRF1_TRBU

X120_BI3_CB_OPENEDX120_BI2_CB_CLOSED

X130_BI3_GAS_PRESSURE_ALAMX130_BI4_CB_SPRING_CHARGED

STTPMSU1_LOCK_START

MPTTR1_BLK_RESTART

MNSPTOC1_BLK_RESTART

MNSPTOC2_BLK_RESTART

X130_BI1_EXT_RESTART_INHIBIT

PHPTUV1_OPERATEPSPTUV1_OPERATENSPTOV1_OPERATE

PHLPTOC1_OPERATEPHIPTOC1_OPERATEJAMPTOC1_OPERATE

DEFLPDEF1_OPERATEEFHPTOC1_OPERATE

MNSPTOC1_OPERATEMNSPTOC2_OPERATE

STTPMSU1_OPR_IIT

ARCSARC1_OPERATEARCSARC2_OPERATEARCSARC3_OPERATE

PREVPTOC1_OPERATELOFLPTUC1_OPERATE

MPTTR1_OPERATE

CCBRBRF1_TRRET

X130_BI2_EXT_TRIP

FRPFRQ1_OPERATEFRPFRQ2_OPERATE

STTPMSU1_OPR_STALL

STTPMSU1_MOT_STARTUP

PHIPTOC1_STARTPHLPTOC1_START

DEFLPDEF1_STARTEFHPTOC1_START

MNSPTOC1_START

MNSPTOC2_START

PREVPTOC1_STARTPHPTUV1_STARTPSPTUV1_STARTNSPTOV1_STARTFRPFRQ1_STARTFRPFRQ2_START

X120_BI1_EMERG_START_ENA

ESMGAPC1_ST_EMERG_ENA

X110_BI4_SPEED_SWITCH

X110_BI1_MCB_OPENED

CCSPVC1_FAIL

X110_BI3_ROTATE_DIRECTION

SEQSPVC1_FUSEF_U

MPTTR1_ALARM

ARCSARC1_ARC_FLT_DETARCSARC2_ARC_FLT_DETARCSARC3_ARC_FLT_DET

SEQSPVC1_FUSEF_3PH

DISTURB_RECORD_TRIGGERED

GUID-E81E7D4C-A682-4D99-8669-5A44436573BB V2 EN

Figure 119: Disturbance recorder

3.5.3.3 Functional diagrams for condition monitoring

CCSPVC1 detects failures in the current measurement circuits. When a failure isdetected, it can be used to block the current protection functions that measure thecalculated sequence component currents to avoid unnecessary operation. However,the BLOCK input signal is not connected in the configuration.

CCSPVC1BLOCK FAIL

ALARMCCSPVC1_FAILCCSPVC1_ALARM

GUID-DFF512BF-5351-4160-8D95-70A630E71F8A V2 EN

Figure 120: Current circuit supervision function

The fuse failure supervision SEQSPVC1 detects failures in the voltage measurementcircuits. Failures, such as an open MCB, raise an alarm.

1MRS756885 M Section 3REM615 standard configurations

REM615 103Application Manual

Page 110: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

SEQSPVC1BLOCKCB_CLOSEDDISCON_OPENMINCB_OPEN

FUSEF_3PHFUSEF_UX120_BI2_CB_CLOSED

X110_BI1_MCB_OPENED

SEQSPVC1_FUSEF_USEQSPVC1_FUSEF_3PH

GUID-B19A22BC-BBA6-4DE4-8CFB-FADF7219C0C8 V2 EN

Figure 121: Fuse failure supervision function

The circuit-breaker condition monitoring function SSCBR1 supervises the switchstatus based on the connected binary input information and the measured currentlevels. SSCBR1 introduces various supervision methods.

Set the parameters for SSCBR1 properly.

SSCBR1BLOCKPOSOPENPOSCLOSEOPEN_CB_EXECLOSE_CB_EXEPRES_ALM_INPRES_LO_INSPR_CHR_STSPR_CHRRST_IPOWRST_CB_WEARRST_TRV_TRST_SPR_T

TRV_T_OP_ALMTRV_T_CL_ALMSPR_CHR_ALM

OPR_ALMOPR_LO

IPOW_ALMIPOW_LO

CB_LIFE_ALMMON_ALM

PRES_ALMPRES_LO

OPENPOSINVALIDPOSCLOSEPOS

CB_OPEN_COMMANDCB_CLOSE_COMMAND

X120_BI3_CB_OPENEDX120_BI2_CB_CLOSED

X130_BI3_GAS_PRESSURE_ALAM

X130_BI4_CB_SPRING_CHARGEDCB_SPRING_DISCHARGED

SSCBR1_TRV_T_OP_ALMSSCBR1_TRV_T_CL_ALMSSCBR1_SPR_CHR_ALMSSCBR1_OPR_ALMSSCBR1_OPR_LOSSCBR1_IPOW_ALMSSCBR1_IPOW_LOSSCBR1_CB_LIFE_ALMSSCBR1_MON_ALMSSCBR1_PRES_ALMSSCBR1_PRES_LO

GUID-3D179275-E6D3-49B4-9516-7EFD66B48AF6 V1 EN

Figure 122: Circuit-breaker condition monitoring function

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

ORB1B2

O

SSCBR1_TRV_T_OP_ALMSSCBR1_TRV_T_CL_ALMSSCBR1_SPR_CHR_ALM

SSCBR1_OPR_ALMSSCBR1_OPR_LO

SSCBR1_IPOW_ALM

SSCBR1_IPOW_LOSSCBR1_CB_LIFE_ALM

SSCBR1_MON_ALMSSCBR1_PRES_ALM

SSCBR1_PRES_LO

SSCBR1_ALARMS

GUID-187AC72A-0AC2-4A55-AF55-CCD8020EC2F7 V1 EN

Figure 123: Logic for circuit breaker monitoring alarm

NOTIN OUTX130_BI4_CB_SPRING_CHARGED CB_SPRING_DISCHARGED

GUID-8A18E075-3D1A-4FEB-8142-29F13BC831F7 V1 EN

Figure 124: Logic for start of circuit breaker spring charging

Two separate trip circuit supervision functions are included: TCSSCBR1 for poweroutput X100:PO3 for master trip and TCSSCBR2 for power output X100:PO4 forcircuit breaker closing. The trip circuit supervision TCSSCRB1 is blocked by the

Section 3 1MRS756885 MREM615 standard configurations

104 REM615Application Manual

Page 111: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

master trip TRPPTRC1 and the circuit breaker open signal. The trip circuitsupervision TCSSCBR2 is blocked by the circuit breaker close signal.

It is assumed that there is no external resistor in the circuit breakertripping coil circuit connected in parallel with the circuit breakernormally open auxiliary contact.

Set the parameters for TCSSCBR1 properly.

TCSSCBR1BLOCK ALARM

ORB1B2

OTRPPTRC1_TRIP

X120_BI3_CB_OPENED TCSSCBR1_ALARM

ORB1B2

OTCSSCBR1_ALARMTCSSCBR2_ALARM

TCSSCBR_ALARM

TCSSCBR2BLOCK ALARMX120_BI2_CB_CLOSED TCSSCBR2_ALARM

GUID-71E9B5C3-D648-4C9C-938C-E7F999BC3D9C V1 EN

Figure 125: Trip circuit supervision function

3.5.3.4 Functional diagrams for control and interlocking

Two types of disconnector and earthing switch function blocks are available.DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 andESXSWI1 are controllable type. By default, the status only blocks are connected instandard configuration. The disconnector (CB truck) and line side earthing switchstatus information is connected to DCSXSWI1 and ESSXSI1 respectively.

DCSXSWI1POSOPENPOSCLOSE

OPENPOSCLOSEPOS

OKPOS DCSXSWI1_OKPOS

X110_BI6_CB_TRUCK_IN_TESTX110_BI5_CB_TRUCK_IN_SERVICE

ESSXSWI1POSOPENPOSCLOSE

OPENPOSCLOSEPOS

OKPOS

ESSXSWI1_OPENPOSX110_BI8_ES1_OPENEDX110_BI7_ES1_CLOSED

GUID-18E4B885-F5BF-43A9-A50D-50DBDB81034E V1 EN

Figure 126: Disconnector and earth-switch control logic

The circuit breaker closing is enabled when the ENA_CLOSE input is activated. Theinput can be activated by the configuration logic, which is a combination of the

1MRS756885 M Section 3REM615 standard configurations

REM615 105Application Manual

Page 112: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

disconnector or breaker truck and earth-switch position status, status of the trip logics,gas pressure alarm and circuit-breaker spring charging status.

The OKPOS output from DCSXSWI defines if the disconnector or breaker truck iseither open (in test position) or close (in service position). This output, together withthe open earth-switch and non-active trip signals, activates the close-enable signal tothe circuit-breaker control function block. The open operation for circuit breaker isalways enabled.

CBXCBR1POSOPENPOSCLOSEENA_OPENENA_CLOSEBLK_OPENBLK_CLOSEAU_OPENAU_CLOSETRIPSYNC_OKSYNC_ITL_BYP

SELECTEDEXE_OPEXE_CL

OP_REQCL_REQ

OPENPOSCLOSEPOS

OKPOSOPEN_ENAD

CLOSE_ENAD

TRUE

CBXCBR1_CLOSE_ENAD

X120_BI3_CB_OPENEDX120_BI2_CB_CLOSED

CBXCBR1_ENA_CLOSE

CBXCBR1_EXE_OPCBXCBR1_EXE_CL

FALSERESTART_INHIBIT

CBXCBR1_AU_OPENCBXCBR1_AU_CLOSE

GUID-CF0F5F14-E048-423C-9A89-FCD9E8E97D24 V2 EN

Figure 127: Circuit breaker control logic: Circuit breaker 1

Any additional signals required by the application can be connectedfor opening and closing of circuit breaker.

ORB1B2

O CB_CLOSE_COMMANDCBXCBR1_EXE_CL

GUID-CE55535E-E1DD-4CEA-9F81-A8FDBCF25EE6 V1 EN

Figure 128: Circuit breaker control logic: Signals for closing coil of circuit breaker1

ORB1B2

OTRPPTRC1_TRIP CB_OPEN_COMMANDCBXCBR1_EXE_OP

GUID-70CC022C-C5BF-4A4B-AD7B-7E44DFFA01E5 V1 EN

Figure 129: Circuit breaker control logic: Signals for opening coil of circuit breaker1

NOTIN OUT

AND6B1B2B3B4B5B6

O

NOTIN OUT

TRPPTRC1_TRIP CBXCBR1_ENA_CLOSE

X130_BI3_GAS_PRESSURE_ALAM

DCSXSWI1_OKPOSESSXSWI1_OPENPOS

X130_BI4_CB_SPRING_CHARGED

GUID-EFAE5126-C871-4821-8D29-75F9FE82966E V1 EN

Figure 130: Circuit breaker close enable logic

Section 3 1MRS756885 MREM615 standard configurations

106 REM615Application Manual

Page 113: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Connect higher-priority conditions before enabling the circuitbreaker. These conditions cannot be bypassed with bypass feature ofthe function.

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

TRPPTRC1_TRIP

RESTART_INHIBIT

STTPMSU1_LOCK_START

MPTTR1_BLK_RESTART

MNSPTOC1_BLK_RESTARTMNSPTOC2_BLK_RESTART

END_OF_REMANENCE_TIME

X130_BI1_EXT_RESTART_INHIBIT

GUID-6DB4F1C4-F44B-4E53-B400-4FC2FD7AEC8E V1 EN

Figure 131: Circuit breaker close blocking logic

When the motor restart is inhibited, the BLK_CLOSE input is activated and the circuitbreaker is not closed. When all conditions of the circuit breaker closing are met, theCLOSE_ENAD output of the CBXCBR1 is activated and the X100:PO1 output isclosed.

The configuration also includes restart inhibit. The restart inhibit is activated undervarious conditions.

• An active trip command• Motor start-up supervision has issued lockout• Motor unbalance function has issued restart blocking• An external restart inhibit is activated by a binary input X130:BI1• Thermal protection has issued blocked restart• Time during which remanence voltage is present

The configuration includes logic for generating circuit breaker external closing andopening command with the IED in local or remote mode.

Check the logic for the external circuit breaker closing command andmodify it according to the application.

Connect the additional signals for closing and opening of the circuitbreaker in local or remote mode, if applicable for the application.

ANDB1B2

O

ANDB1B2

O

ORB1B2

O CBXCBR1_AU_CLOSE

CONTROL_LOCAL

CONTROL_REMOTE

FALSE

FALSE

GUID-A4C4D1D0-69BE-44D9-B8F1-07945960BB13 V1 EN

Figure 132: External closing command for circuit breaker

1MRS756885 M Section 3REM615 standard configurations

REM615 107Application Manual

Page 114: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

ANDB1B2

O

ORB1B2

O

ANDB1B2

O

CBXBCR1_AU_OPEN

CONTROL_LOCAL

CONTROL_REMOTE

FALSE

FALSE

GUID-6A1D7D54-3399-49FB-99BA-51E8CA693883 V1 EN

Figure 133: External opening command for circuit breaker

3.5.3.5 Functional diagrams for measurement functions

The phase current inputs to the IED are measured by the three-phase currentmeasurement function CMMXU1. The current input is connected to the X120 card inthe back panel. The sequence current measurement CSMSQI1 measures the sequencecurrent and the residual current measurement RESCMMXU1 measures the residualcurrent.

The three-phase voltage inputs to the IED are measured by the three-phase voltagemeasurement function VMMXU1. The voltage input is connected to the X130 card inthe back panel. The sequence voltage measurement VSMSQI1 measures the sequencevoltage and the residual voltage measurement RESVMMXU1 measures the residualvoltage.

The measurements can be seen in the LHMI and they are available under themeasurement option in the menu selection. Based on the settings, function blocks cangenerate low alarm or warning and high alarm or warning signals for the measuredcurrent values.

The frequency measurement FMMXU1 of the power system and the three-phasepower and energy measurement PEMMXU1 are available. The load profile recordLDPRLRC1 is included in the measurements sheet. LDPRLRC1 offers the ability toobserve the loading history of the corresponding feeder.

CMMXU1BLOCK HIGH_ALARM

HIGH_WARNLOW_WARN

LOW_ALARM

GUID-60F932B2-7975-4964-9C3B-94A5D84C2539 V

Figure 134: Current measurement: Three-phase current measurement

CSMSQI1

GUID-0D06A0D8-1D1A-4E95-9EA6-2337AB91EBC7 V1 EN

Figure 135: Current measurement: Residual current measurement

Section 3 1MRS756885 MREM615 standard configurations

108 REM615Application Manual

Page 115: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

RESCMMXU1BLOCK HIGH_ALARM

HIGH_WARN

GUID-4B6816A9-24FE-4C58-AE91-CD6117616677 V1 EN

Figure 136: Current measurement: Sequence current measurement

VMMXU1BLOCK HIGH_ALARM

HIGH_WARNLOW_WARN

LOW_ALARM

GUID-700E0762-868B-45BC-B3A9-D509A877A5E6 V1 EN

Figure 137: Voltage measurement: Three-phase voltage measurements

VSMSQI1

GUID-3D0D4E5E-5D51-4411-823D-C5742805A40D V1 EN

Figure 138: Voltage measurement: Residual voltage measurements

RESVMMXU1BLOCK HIGH_ALARM

HIGH_WARN

GUID-87C1DC72-26D9-4ECB-AB77-1FE3584FA9B6 V1 EN

Figure 139: Voltage measurement: Sequence voltage measurements

FMMXU1

GUID-D9FE76AA-48DA-4AF5-AB39-87E5B2546D4E V1 EN

Figure 140: Other measurements: Frequency measurement

PEMMXU1RSTACM

GUID-FA4D4D5C-4E1F-4295-A534-72F2EF214AA9 V1 EN

Figure 141: Other measurements: Three-phase power and energy measurement

FLTRFRC1BLOCKCB_CLRD

GUID-985AF6BA-E07A-4AAC-8873-DBE6640AD3EC V2 EN

Figure 142: Other measurements: Data monitoring

LDPRLRC1RSTMEM MEM_WARN

MEM_ALARM

GUID-D9953584-EEFB-4A3A-A3B0-34F3FBD89C78 V2 EN

Figure 143: Other measurements: Load profile record

1MRS756885 M Section 3REM615 standard configurations

REM615 109Application Manual

Page 116: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

3.5.3.6 Functional diagrams for I/O and alarms LEDs

ORB1B2

O

ORB1B2

O

ORB1B2

O

ORB1B2

O

ORB1B2

O

ORB1B2

O

ORB1B2

O

ORB1B2

O

X110_BI2_SG_CHANGE

X110_BI6_CB_TRUCK_IN_TEST

X110_BI5_CB_TRUCK_IN_SERVICE

X110_BI8_ES1_OPENED

X110_BI7_ES1_CLOSED

X110_BI4_SPEED_SWITCH

X110_BI1_MCB_OPENED

X110_BI3_ROTATE_DIRECTION

X110 (BIO-H).X110-Input 8

X110 (BIO).X110-Input 4

X110 (BIO-H).X110-Input 6

X110 (BIO).X110-Input 6

X110 (BIO).X110-Input 2

X110 (BIO).X110-Input 5

X110 (BIO-H).X110-Input 7

X110 (BIO).X110-Input 7

X110 (BIO-H).X110-Input 3

X110 (BIO-H).X110-Input 2

X110 (BIO).X110-Input 1

X110 (BIO-H).X110-Input 1

X110 (BIO-H).X110-Input 4

X110 (BIO).X110-Input 3

X110 (BIO-H).X110-Input 5

X110 (BIO).X110-Input 8

GUID-F080A3BD-DBF7-4D37-B904-45CA9644FFD5 V1 EN

Figure 144: Default binary inputs - X110

Section 3 1MRS756885 MREM615 standard configurations

110 REM615Application Manual

Page 117: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

X120_BI3_CB_OPENED

X120_BI2_CB_CLOSED

X120_BI4_RST_LOCKOUT

X120_BI1_EMERG_START_ENA

X120 (AIM).X120-Input 1

X120 (AIM).X120-Input 2

X120 (AIM).X120-Input 3

X120 (AIM).X120-Input 4GUID-615D994B-EEE6-40B0-8D70-716BAA088F8B V1 EN

Figure 145: Default binary inputs - X120

X130_BI3_GAS_PRESSURE_ALAM

X130_BI4_CB_SPRING_CHARGED

X130_BI1_EXT_RESTART_INHIBIT

X130_BI2_EXT_TRIP

X130 (AIM).X130-Input 1

X130 (AIM).X130-Input 2

X130 (AIM).X130-Input 3

X130 (AIM).X130-Input 4GUID-D592BF34-737A-4C28-9EEF-148E1E6E234A V1 EN

Figure 146: Default binary inputs - X130

CBXCBR1_CLOSE_ENAD

CCBRBRF1_TRBU

TRPPTRC1_TRIP

CB_OPEN_COMMAND

CB_CLOSE_COMMAND

GENERAL_OPERATE_PULSE

X100 (PSM).X100-PO1

X100 (PSM).X100-PO2

X100 (PSM).X100-SO1

X100 (PSM).X100-SO2

X100 (PSM).X100-PO3

X100 (PSM).X100-PO4GUID-982C6892-7B94-478B-9AC3-7BC72D2D04EC V1 EN

Figure 147: Default binary outputs - X100

1MRS756885 M Section 3REM615 standard configurations

REM615 111Application Manual

Page 118: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

GENERAL_START_PULSE

MOTOR_STARTUP_PULSE

THERMAL_ALARM_PULSE

VOLTAGE_PROT_OPERATE_PULSE

TRPPTRC3_TRIP

TRPPTRC4_TRIP

TRPPTRC5_TRIP

X110 (BIO).X110-SO1

X110 (BIO).X110-SO2

X110 (BIO).X110-SO4

X110 (BIO).X110-SO3

X110 (BIO-H).X110-HSO1

X110 (BIO-H).X110-HSO2

X110 (BIO-H).X110-HSO3

GUID-12DACD1B-0269-4FB3-84E5-A75CE34B0C40 V1 EN

Figure 148: Default binary outputs - X110

Section 3 1MRS756885 MREM615 standard configurations

112 REM615Application Manual

Page 119: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

ORB1B2

O

LED1OKALARMRESET

LED2OKALARMRESET

LED3OKALARMRESET

LED5OKALARMRESET

RESTART_INHIBIT

PHIPTOC1_OPERATE

DEFLPDEF1_OPERATEEFHPTOC1_OPERATE

MPTTR1_OPERATE

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

LED4OKALARMRESET

ORB1B2

OPHLPTOC1_OPERATEJAMPTOC1_OPERATE

STTPMSU1_OPR_IIT

PREVPTOC1_OPERATELOFLPTUC1_OPERATE

STTPMSU1_OPR_STALL

VOLTAGE_PROT_OPERATEMNSPTOC_OPERATE

FREQUENCY_OPERATE

GUID-ECDA1413-F459-435E-83FA-392B44D4884E V2 EN

1MRS756885 M Section 3REM615 standard configurations

REM615 113Application Manual

Page 120: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

LED6OKALARMRESET

LED7OKALARMRESET

LED8OKALARMRESET

LED9OKALARMRESET

LED10OKALARMRESET

LED11OKALARMRESET

OR6B1B2B3B4B5B6

O

CCBRBRF1_TRBU

ESMGAPC1_ST_EMERG_ENA

SEQSPVC1_FUSEF_USEQSPVC1_FUSEF_3PH

DISTURB_RECORD_TRIGGERED

ARC_OPERATE

MDSOPT1_ALARM

SSCBR1_ALARMS

TCSSCBR_ALARM

CCSPVC1_ALARM

GUID-C757EB63-14BD-43C8-B4FA-40A051BD13E3 V2 EN

Figure 149: Default LED connection

3.5.3.7 Functional diagrams for other timer logics

The configuration also includes voltage operate, motor start-up and thermal alarm,blocking logic for phase under voltage protection, blocking logic for sequence voltageprotection, blocking logic for phase reversal and negative-sequence overcurrentprotection and logic for remanence voltage. The restart inhibit is activated for a setperiod when a circuit breaker is in open state. This is called remanence voltageprotection where the motor has damping remanence voltage after the opening of acircuit breaker. Re-closing after a short period of time can lead to stress for themachine and other apparatus. The remanence voltage protection waiting time can beset by a timer function TPSGAPC1.

TPGAPC3IN1IN2

OUT1OUT2

VOLTAGE_PROT_OPERATE_PULSEVOLTAGE_PROT_OPERATE

GUID-77C67806-A62A-469F-AC93-D564C1E37A7F V1 EN

Figure 150: Timer logic for voltage protection operate alarm

Section 3 1MRS756885 MREM615 standard configurations

114 REM615Application Manual

Page 121: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

TPGAPC2IN1IN2

OUT1OUT2

MOTOR_STARTUP_PULSETHERMAL_ALARM_PULSE

STTPMSU1_MOT_STARTUPMPTTR1_ALARM

GUID-1BBE2FE9-BADD-4EA1-939C-76924C4D4F27 V1 EN

Figure 151: Timer logic for motor start-up and thermal alarm

Add the signals for blocking positive-sequence undervoltageprotection and negative-sequence overvoltage protection.

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

STTPMSU1_MOT_STARTUP

BLOCK_PSPTUV_AND_NSPTOV

BLOCK_PHPTUV

X110_BI3_ROTATE_DIRECTION

SEQSPVC1_FUSEF_U

SEQSPVC1_FUSEF_U

GUID-7A820161-695B-4852-B7BF-F4BC8DAC755A V2 EN

Figure 152: Blocking logic for phase undervoltage and sequence voltageprotection

Add the signals for blocking phase reversal and negative-sequenceovercurrent protection.

OR6B1B2B3B4B5B6

O BLOCK_MNSPTOC_AND_PREVPTOCCCSPVC1_FAILX110_BI3_ROTATE_DIRECTION

GUID-26A300D5-A26A-4654-98D4-72AE6EC45860 V2 EN

Figure 153: Blocking logic for phase reversal and negative-sequence overcurrentprotection

TPSGAPC1IN1IN2

OUT1OUT2

CB_OPEN_COMMAND END_OF_REMANENCE_TIME

GUID-126BB792-D9EA-4E9D-BC3C-F4E3901F0F63 V1 EN

Figure 154: Timer logic for remanence voltage to disappear

1MRS756885 M Section 3REM615 standard configurations

REM615 115Application Manual

Page 122: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

3.5.3.8 Other functions

The configuration includes few instances of multipurpose protection functionMAPGAPC and different types of timers and control functions. These functions arenot included in application configuration but they can be added based on the systemrequirements.

3.6 Standard configuration D

3.6.1 Applications

The standard configuration for motor protection with current and voltage basedprotection and measurements functions is mainly intended for comprehensiveprotection and control functionality of circuit breaker controlled asynchronousmotors. With minor modifications this standard configuration can be applied also forcontactor controlled motors.

The protection relay with a standard configuration is delivered from the factory withdefault settings and parameters. The end user flexibility for incoming, outgoing andinternal signal designation within the protection relay enables this configuration to befurther adapted to different primary circuit layouts and the related functionality needsby modifying the internal functionality using PCM600.

Section 3 1MRS756885 MREM615 standard configurations

116 REM615Application Manual

Page 123: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

3.6.2 Functions

ALSO AVAILABLE

- Disturbance and fault recorders- Event log and recorded data- High-Speed Output module (optional)- Local/Remote push button on LHMI- Self-supervision- Time synchronization: IEEE 1588 v2,

SNTP, IRIG-B- User management- Web HMI

REMARKS

Optionalfunction

No. ofinstances

Alternative function to be defined when ordering

OR

Io/Uo

Calculatedvalue

CONTROL AND INDICATION 1) MEASUREMENT

MOTOR PROTECTION AND CONTROL RELAY

PROTECTION LOCAL HMI

ESTARTESTART

Object Ctrl 2) Ind 3)

CB 1 -

DC 2 3

ES 1 21) Check availability of binary inputs/outputs

from technical documentation2) Control and indication function for

primary object3) Status indication function for primary object

STANDARD CONFIGURATION

RL

ClearESCI

O

Configuration ASystemHMITimeAuthorization

RL

ClearESCI

O

U12 0. 0 kVP 0.00 kWQ 0.00 kVAr

IL2 0 A

A

18×MAPMAP

REM615

Io - I, U, Io, P, Q, E, pf, f- Limit value supervision- Load profile record- Symmetrical components

D

Analog interface types 1)

Current sensor

Voltage sensor

Voltage transformer1) Combi sensor inputs with conventional

Io input

3

3

1

Master TripLockout relay

94/86

Io>→67N-1

3U<27

U2>47O-

U1<47U+

2×f>/f<,df/dt81

3×ARC

50L/50NL

3I<37

2×I2>M46M

I2>>46R

3Ith>M49M

Is2t n<49, 66, 48, 51LR

3I>>>50P/51P

3I>/Io>BF51BF/51NBF

Ist>51LR

3I>51P-1

CBCMCBCM

FUSEF60

MCS 3IMCS 3I

2×TCSTCM

OPTSOPTM

Io>>51N-2

3I>>51P-2

3I

Io

Uo

Io

Io3I

UL1

UL2

UL3

UL1

UL2

UL3

CONDITION MONITORING AND SUPERVISION

COMMUNICATION

Protocols: IEC 61850-8-1/-9-2LE Modbus®

IEC 60870-5-103 DNP3Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232Redundant protocols: HSR PRP RSTP

ORAND

Master TripLockout relay

94/86

3×2×

GUID-13051FBE-3F18-43EF-9309-7DE749EDA262 V2 EN

Figure 155: Functionality overview for standard configuration D

3.6.2.1 Default I/O connections

Connector pins for each input and output are presented in the IED physicalconnections section.

1MRS756885 M Section 3REM615 standard configurations

REM615 117Application Manual

Page 124: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Table 28: Default connections for binary inputs

Binary input DescriptionX110-BI1 Circuit breaker plug not inserted

X110-BI2 Circuit breaker spring discharged

X110-BI3 Circuit breaker in opened position

X110-BI4 Circuit breaker in closed position

X110-BI5 Circuit breaker truck in test

X110-BI6 Circuit breaker truck in service

X110-BI7 Earthing switch in opened position

X110-BI8 Earthing switch in closed position

Table 29: Default connections for binary outputs

Binary input DescriptionX100-PO1 Release for circuit breaker closing

X100-PO2 Circuit breaker close command

X100-SO1 Release for circuit breaker truck

X100-SO2 Release for earthing switch

X100-PO3 Circuit breaker open command

X100-PO4 Circuit breaker failed signal - Retrip

X110-HSO1 Arc protection instance 1 operate activated

X110-HSO2 Arc protection instance 2 operate activated

X110-HSO3 Arc protection instance 3 operate activated

Table 30: Default connections for LEDs

LED Description1 Circuit breaker close enabled

2 Short-circuit protection operated

3 Earth-fault protection operated

4 Loss of load protection operated

5 Other protection function operated

6 -

7 Thermal overload protection operated

8 Undervoltage or frequency protection operated

9 Supervision alarm

10 Circuit breaker condition monitoring alarm

11 -

Section 3 1MRS756885 MREM615 standard configurations

118 REM615Application Manual

Page 125: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

3.6.2.2 Default disturbance recorder settings

Table 31: Default disturbance recorder analog channels

Channel Description1 IL1

2 IL2

3 IL3

4 Io

5 U1

6 U2

7 U3

8 -

9 -

10 -

11 -

12 -

Table 32: Default disturbance recorder binary channels

Channel ID text Level trigger mode1 PHLPTOC1 - start Positive or Rising

2 PHIPTOC2 - start Positive or Rising

3 DEFLPDEF1 - start Positive or Rising

4 EFHPTOC1 - start Positive or Rising

5 MPTTR1 - alarm Level trigger off

6 MPTTR1 - blk restart Level trigger off

7 ESMGAPC1 - st emerg ena Level trigger off

8 STTPMSU1 - mot startup Positive or Rising

9 STTPMSU1 - lock start Level trigger off

10 MNSPTOC1 - start Positive or Rising

11 MNSPTOC1 - blk restart Level trigger off

12 MNSPTOC2 - start Positive or Rising

13 MNSPTOC2 - blk restart Level trigger off

14 PREVPTOC1 - start Positive or Rising

15 PHPTUV1 - start Positive or Rising

16 PSPTUV1 - start Positive or Rising

17 NSPTOV1 - start Positive or Rising

18 FRPFRQ1 - start Positive or Rising

19 FRPFRQ2 - start Positive or Rising

20 CCBRBRF1 - trret Level trigger off

21 CCBRBRF1 - trbu Level trigger off

Table continues on next page

1MRS756885 M Section 3REM615 standard configurations

REM615 119Application Manual

Page 126: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Channel ID text Level trigger mode22 PHLPTOC1 - operate Level trigger off

23 PHIPTOC2 - operate Level trigger off

24 JAMPTOC1 - operate Level trigger off

25 DEFLPDEF1 - operate Level trigger off

EFHPTOC2 - operate

26 MNSPTOC1 - operate Level trigger off

MNSPTOC2 - operate

27 PREVPTOC1 - operate Level trigger off

28 LOFLPTUC1 - operate Level trigger off

29 MPTTR1 - operate Level trigger off

30 PHPTUV1 - operate Level trigger off

31 PSPTUV1 - operate Level trigger off

32 NSPTOV1 - operate Level trigger off

33 FRPFRQ1 - operate Level trigger off

34 FRPFRQ2 - operate Level trigger off

35 X110BI1 - plug out Level trigger off

36 X110BI2 - spring dischraged Level trigger off

37 X110BI4 - CB closed Level trigger off

38 X110BI3 - CB opened Level trigger off

39 STTPMSU1 - opr iit Positive or Rising

40 STTPMSU1 - opr stall Positive or Rising

41 CCSPVC1 - fail Level trigger off

42 ARCSARC1 - ARC flt det Level trigger off

ARCSARC2 - ARC flt det

ARCSARC3 - ARC flt det

43 ARCSARC1 - operate Positive or Rising

44 ARCSARC2 - operate Positive or Rising

45 ARCSARC3 - operate Positive or Rising

3.6.3 Functional diagrams

The functional diagrams describe the default input, output, alarm LED and function-to-function connections. The default connections can be viewed and changed withPCM600 according to the application requirements.

The analog channels have fixed connections to the different function blocks inside theprotection relay’s standard configuration. However, the 12 analog channels availablefor the disturbance recorder function are freely selectable as a part of the disturbancerecorder’s parameter settings.

Section 3 1MRS756885 MREM615 standard configurations

120 REM615Application Manual

Page 127: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

The phase currents to the protection relay are fed from Rogowski or Combi sensors.The residual current to the protection relay is fed from either residually connectedCTs, an external core balance CT, neutral CT or calculated internally.

The phase voltages to the protection relay are fed from Combi sensors. The residualvoltage is calculated internally.

The protection relay offers six different setting groups which can be set based onindividual needs. Each group can be activated or deactivated using the setting groupsettings available in the protection relay.

Depending on the communication protocol the required function block needs to beinstantiated in the configuration.

3.6.3.1 Functional diagrams for protection

The functional diagrams describe the IEDs protection functionality in detail andaccording to the factory set default connections.

Two overcurrent stages are offered for overcurrent and short-circuit protection. Thenon-directional low stage PHLPTOC1 can be used for overcurrent protection whereasinstantaneous stage PHIPTOC1 can be used for short-circuit protection. Theoperation of PHIPTOC1 is not blocked as default by any functionality and it should beset over the motor start current level to avoid unnecessary operation.

The motor load jam protection function JAMPTOC1 is blocked by the motor start-upprotection function.

JAMPTOC1BLOCK OPERATE JAMPTOC1_OPERATESTTPMSU1_MOT_STARTUP

OR6B1B2B3B4B5B6

OPHLPTOC1_OPERATEPHIPTOC1_OPERATE PHxPTOC_OPERATE

PHIPTOC1BLOCKENA_MULT

OPERATESTART

PHLPTOC1BLOCKENA_MULT

OPERATESTART

PHLPTOC1_OPERATE

PHIPTOC1_OPERATEPHIPTOC1_START

PHLPTOC1_START

GUID-CD01E423-8CA3-423B-B9A5-FA38BE771DB7 V1 EN

Figure 156: Overcurrent protection functions

1MRS756885 M Section 3REM615 standard configurations

REM615 121Application Manual

Page 128: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Two negative-sequence overcurrent protection stages MNSPTOC1 and MNSPTOC2are provided for phase unbalance protection. These functions are used to protect themotor against phase unbalance. Unbalance in the network feeder of the motor causesoverheating of the motor.

MNSPTOC1BLOCK OPERATE

STARTBLK_RESTART

MNSPTOC2BLOCK OPERATE

STARTBLK_RESTART

MNSPTOC1_BLK_RESTART

MNSPTOC2_BLK_RESTART

MNSPTOC1_OPERATE

MNSPTOC2_OPERATE

MNSPTOC1_START

MNSPTOC2_START

BLOCK_MNSPTOC_AND_PREVPTOC

BLOCK_MNSPTOC_AND_PREVPTOC

GUID-9CB13EDF-867B-4226-9F15-762A26B5ED01 V1 EN

Figure 157: Negative-sequence overcurrent protection function

The phase reversal protection PREVPTOC1 is based on the calculated negative phasesequence current. It detects high negative sequence current values during motor start-up, caused by incorrectly connected phases, which in turn causes the motor to rotatein the opposite direction.

The negative-sequence and phase reversal protection are blocked if the current circuitsupervision detects failure in the current measurement circuit.

PREVPTOC1BLOCK OPERATE

STARTPREVPTOC1_OPERATEPREVPTOC1_START

BLOCK_MNSPTOC_AND_PREVPTOC

GUID-28285504-349B-4F65-ABF6-4C654FA683C9 V1 EN

Figure 158: Phase reversal protection function

One stage is provided for non-directional earth-fault protection EFHPTOC1 to detectphase-to-earth faults that may be result of, for example, insulation ageing. In addition,there is a directional protection stage DEFLPDEF1 which can also be used as a lowstage non-directional earth-fault protection without residual voltage requirement.However, the residual voltage can help to detect earth faults at a low fault current levelselectively and to discriminate the apparent residual current caused, for example, bypartial current transformer saturation at motor start-up.

Both the directional and non-directional earth-fault are blocked by the activation ofinstantaneous stage of overcurrent protection.

Section 3 1MRS756885 MREM615 standard configurations

122 REM615Application Manual

Page 129: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

DEFLPDEF1BLOCKENA_MULTRCA_CTL

OPERATESTART

DEFLPDEF1_OPERATEPHIPTOC1_STARTDEFLPDEF1_START

EFHPTOC1BLOCKENA_MULT

OPERATESTART

EFHPTOC1_OPERATEPHIPTOC1_STARTEFHPTOC1_START

GUID-4A5CC52E-07E8-4155-9B5D-533B7269E444 V1 EN

Figure 159: Earth-fault protection functions

The emergency start function ESMGAPC1 allows motor start-ups although thecalculated thermal level or cumulative start-up time counter is blocking the restart.The emergency start is enabled for ten minutes after the selected binary input isenergized. However it should be noted that by default no binary inputs are provided toperform emergency start operation.

On the rising edge of the emergency start signal, various events occur.

• The calculated thermal level in MPTTR1 is set slightly below the restart inhibitlevel to allow at least one motor start-up.

• The value of the cumulative start-up time counter STTPMSU1 is set slightlybelow the set restart inhibit value to allow at least one motor start-up.

A new emergency start cannot be made until the emergency start signal has been resetand the emergency start time has expired.

ESMGAPC1BLOCKST_EMERG_RQ

ST_EMERG_ENA ESMGAPC1_ST_EMERG_ENA

GUID-F8A07949-5C21-4395-B9EC-FE17FEB83543 V1 EN

Figure 160: Motor emergency start-up function

The thermal overload protection for motors MPTTR1 detects short and long termoverloads under varying load conditions. When the emergency start request is issuedfor the emergency start function, it activates the corresponding input of the thermaloverload function. Restart blocking, issued by the thermal overload function, preventsthe closing of the breaker in machine overload situation. The emergency start requestremoves the blocking and enables the restarting of the motor.

MPTTR1BLOCKSTART_EMERGTEMP_AMB

OPERATEALARM

BLK_RESTART MPTTR1_BLK_RESTART

MPTTR1_OPERATEESMGAPC1_ST_EMERG_ENA MPTTR1_ALARM

GUID-3A6761EB-8D8A-4B68-B782-CC328BCD0DE7 V1 EN

Figure 161: Thermal overcurrent protection function

The restart inhibit is activated for a set period when a circuit breaker is opened. Thisis called remanence voltage protection where the motor has damping remanence

1MRS756885 M Section 3REM615 standard configurations

REM615 123Application Manual

Page 130: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

voltage after the circuit breaker opening. Re-closing after a too short period of timecan lead to stress for the machine and other apparatus. The remanence voltageprotection waiting time can be set by a timer function TPSGAPC1.

The restart inhibit is also activated under various conditions.

• An active trip command• Motor start-up supervision has issued lockout• Motor unbalance function has issued restart blocking• Thermal protection has issued restart blocking

With the motor start-up supervision function STTPMSU1 the starting of the motor issupervised by monitoring three-phase currents or the status of the energizing circuitbreaker of the motor. When the emergency start request is activated by ESMGAPC1and STTPMSU1 is in lockout state, which inhibits motor starting, the lockout isdeactivated and emergency starting is available.

STTPMSU1BLOCKBLK_LK_STCB_CLOSEDSTALL_INDST_EMERG_ENA

OPR_IITOPR_STALLMOT_START

LOCK_STARTX110_BI4_CB_CLOSED

STTPMSU1_LOCK_START

STTPMSU1_OPR_IITSTTPMSU1_OPR_STALLSTTPMSU1_MOT_STARTUP

ESMGAPC1_ST_EMERG_ENA

GUID-2D71D072-551D-477B-A422-01FD94082049 V1 EN

Figure 162: Motor start-up supervision function

The runtime counter for machines and devices MDSOPT1 provides history data sincethe last commissioning. The counter counts the total number of motor running hoursand is incremented when the energizing circuit breaker is closed.

MDSOPT1BLOCKPOS_ACTIVERESET

ALARMWARNING

ANDB1B2

OX110_BI4_CB_CLOSED

X110_BI6_CB_TRUCK_IN_SERVICEMDSOPT1_ALARM

GUID-33783965-D14C-4002-BED5-91E06B7FAF14 V1 EN

Figure 163: Motor runtime counter

The loss of load situation is detected by LOFLPTUC1. The loss of load situationoccurs, for example, if there is a damaged pump or a broken conveyor.

LOFLPTUC1BLOCK OPERATE

STARTLOFLPTUC1_OPERATE

GUID-5ACF2032-B800-40B0-BDA4-1760CE55086B V1 EN

Figure 164: Loss of load

The three-phase undervoltage protection PHPTUV1 offers protection againstabnormal phase voltage conditions. Positive-sequence undervoltage protectionPSPTUV1 and negative-sequence overvoltage protection NSPTOV1 functions areincluded to protect the machine against single-phasing, excessive unbalance betweenphases and abnormal phase order.

Section 3 1MRS756885 MREM615 standard configurations

124 REM615Application Manual

Page 131: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

The three-phase undervoltage protection PHPTUV1 is blocked during motor start-upto prevent unwanted operation. A failure in the voltage measuring circuit can bedetected by the fuse failure function. The activation can be used to block undervoltageprotection functions as well as voltage based unbalance protection functions to avoidfaulty tripping however that is not included in configuration by default.

NSPTOV1BLOCK OPERATE

STARTNSPTOV1_OPERATENSPTOV1_START

BLOCK_PSPTUV_AND_NSPTOV

PSPTUV1BLOCK OPERATE

STARTPSPTUV1_OPERATEPSPTUV1_START

BLOCK_PSPTUV_AND_NSPTOV

OR6B1B2B3B4B5B6

OPHPTUV1_OPERATEPSPTUV1_OPERATENSPTOV1_OPERATE

VOLTAGE_PROT_OPERATE

PHPTUV1BLOCK OPERATE

STARTPHPTUV1_OPERATEPHPTUV1_START

BLOCK_PHPTUV

GUID-4B207048-28E6-409B-8818-889C1E932446 V1 EN

Figure 165: Undervoltage and sequence voltage protection function

Two frequency protection stages FRPFRQ1 and FRPFRQ2 are offered. Thesefunctions are used to protect the motor against an abnormal power system frequency.

1MRS756885 M Section 3REM615 standard configurations

REM615 125Application Manual

Page 132: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

FRPFRQ1BLOCK OPERATE

OPR_OFRQOPR_UFRQ

OPR_FRGSTART

ST_OFRQST_UFRQ

ST_FRG

FRPFRQ2BLOCK OPERATE

OPR_OFRQOPR_UFRQ

OPR_FRGSTART

ST_OFRQST_UFRQ

ST_FRG

ORB1B2

O

FRPFRQ1_OPERATE

FRPFRQ1_OPERATE

FRPFRQ2_OPERATE

FRPFRQ2_OPERATE

FRPFRQ1_START

FRPFRQ2_START

FREQUENCY_OPERATE

GUID-E143951F-9E4F-40D7-9361-05047152FDCB V1 EN

Figure 166: Frequency protection function

The circuit breaker failure protection CCBRBRF1 is initiated via the START input bynumber of different protection functions available in the IED. The circuit breakerfailure protection function offers different operating modes associated with the circuitbreaker position and the measured phase and residual currents.

The circuit breaker failure protection function has two operating outputs: TRRET andTRBU. The TRRET operate output is used for retripping its own breaker throughTRPPTRC2_TRIP. The same TRRET output is also connected to the binary outputX100:PO4.

CCBRBRF1BLOCKSTARTPOSCLOSECB_FAULT

CB_FAULT_ALTRBU

TRRET

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

OCCBRBRF1_TRRET

X110_BI4_CB_CLOSED

PHLPTOC1_OPERATEPHIPTOC1_OPERATEJAMPTOC1_OPERATE

DEFLPDEF1_OPERATEEFHPTOC1_OPERATEMNSPTOC1_OPERATE

MNSPTOC2_OPERATESTTPMSU1_OPR_IIT

ARCSARC1_OPERATEARCSARC2_OPERATEARCSARC3_OPERATE

STTPMSU1_OPR_STALL

CCBRBRF1_TRBU

GUID-DC77A295-DE9F-41D0-9AC6-73DD29DEE09E V1 EN

Figure 167: Circuit breaker failure protection function

Section 3 1MRS756885 MREM615 standard configurations

126 REM615Application Manual

Page 133: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Three arc protection stages ARCSARC1...3 are included as an optional function. Thearc protection offers individual function blocks for three arc sensors that can beconnected to the IED. Each arc protection function block has two different operationmodes, with or without the phase and residual current check.

Operate signal from ARCSARC1...3 are connected to both trip logic TRPPTRC1 andTRPPTRC2. If the IED has been ordered with high speed binary outputs, theindividual operate signals from ARCSARC1...3, are connected to dedicated trip logicTRPPTRC3...5, The outputs of TRPPTRC3...5 are available at high speed outputsX110:HSO1, X110:HSO2 and X110:HSO3.

1MRS756885 M Section 3REM615 standard configurations

REM615 127Application Manual

Page 134: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

OR6B1B2B3B4B5B6

O

ARCSARC1BLOCKREM_FLT_ARCOPR_MODE

OPERATEARC_FLT_DET

ARCSARC2BLOCKREM_FLT_ARCOPR_MODE

OPERATEARC_FLT_DET

ARCSARC3BLOCKREM_FLT_ARCOPR_MODE

OPERATEARC_FLT_DET

ARCSARC1_OPERATE

ARCSARC1_OPERATE

ARCSARC2_OPERATE

ARCSARC2_OPERATE

ARCSARC3_OPERATE

ARCSARC3_OPERATE

ARCSARC1_ARC_FLT_DET

ARCSARC2_ARC_FLT_DET

ARCSARC3_ARC_FLT_DET

ARC_OPERATE

GUID-74D7504C-90BF-4D7B-B59F-A2D9A4B75FD1 V1 EN

TRPPTRC3BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

TRPPTRC4BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

TRPPTRC5BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

TRPPTRC3_TRIP

TRPPTRC4_TRIP

TRPPTRC5_TRIP

ARCSARC1_OPERATE

ARCSARC2_OPERATE

ARCSARC3_OPERATE

GUID-BB1144E4-6139-4795-AB29-42065417D5D3 V1 EN

Figure 168: Arc protection with dedicated HSO

General start and operate from all the functions are connected to minimum pulse timerTPGAPC for setting the minimum pulse length for the outputs.

Section 3 1MRS756885 MREM615 standard configurations

128 REM615Application Manual

Page 135: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

TPGAPC1IN1IN2

OUT1OUT2

STTPMSU1_LOCK_START

PHPTUV1_OPERATEPSPTUV1_OPERATENSPTOV1_OPERATE

PHLPTOC1_OPERATEPHIPTOC1_OPERATEJAMPTOC1_OPERATE

DEFLPDEF1_OPERATEEFHPTOC1_OPERATEMNSPTOC1_OPERATE

MNSPTOC2_OPERATE

STTPMSU1_OPR_IIT

ARCSARC1_OPERATEARCSARC2_OPERATEARCSARC3_OPERATE

PREVPTOC1_OPERATELOFLPTUC1_OPERATE

MPTTR1_OPERATE

FRPFRQ1_OPERATEFRPFRQ2_OPERATE

STTPMSU1_MOT_STARTUP

PHIPTOC1_STARTPHLPTOC1_START

DEFLPDEF1_STARTEFHPTOC1_START

MNSPTOC1_STARTMNSPTOC2_STARTPREVPTOC1_START

PHPTUV1_STARTPSPTUV1_STARTNSPTOV1_START

FRPFRQ1_STARTFRPFRQ2_START

GUID-8BF8F839-6838-42BB-8BDA-C9DAD887E3A6 V1 EN

Figure 169: General start and operate signals

The operate signals from the protection functions are connected to the two trip logicsTRPPTRC1 and TRPPTRC2. The output from TRPPTRC1 trip logic functions isavailable at binary output X100:PO3. The trip logic functions are provided with alockout and latching function, event generation and the trip signal duration setting. If

1MRS756885 M Section 3REM615 standard configurations

REM615 129Application Manual

Page 136: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

the lockout operation mode is required, binary input can be assigned to RST_LKOUTinput of the trip logic to enable external reset with a push button.

Three other trip logics TRPPTRC3...4 are also available if the IED is ordered withhigh speed binary outputs options.

TRPPTRC1BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

CCBRBRF1_TRRET

TRPPTRC1_TRIP

PHPTUV1_OPERATEPSPTUV1_OPERATENSPTOV1_OPERATE

PHLPTOC1_OPERATEPHIPTOC1_OPERATEJAMPTOC1_OPERATE

DEFLPDEF1_OPERATEEFHPTOC1_OPERATEMNSPTOC1_OPERATE

MNSPTOC2_OPERATE

STTPMSU1_OPR_IIT

ARCSARC1_OPERATEARCSARC2_OPERATEARCSARC3_OPERATE

PREVPTOC1_OPERATELOFLPTUC1_OPERATE

MPTTR1_OPERATE

STTPMSU1_OPR_STALL

FRPFRQ1_OPERATEFRPFRQ2_OPERATE

GUID-A8968FB2-C4B5-4551-AC56-4A3000C11956 V1 EN

Figure 170: Trip logic TRPPTRC1

Section 3 1MRS756885 MREM615 standard configurations

130 REM615Application Manual

Page 137: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

TRPPTRC2BLOCKOPERATERST_LKOUT

TRIPCL_LKOUT

CCBRBRF1_TRRET

TRPPTRC2_TRIP

PHPTUV1_OPERATEPSPTUV1_OPERATENSPTOV1_OPERATE

PHLPTOC1_OPERATEPHIPTOC1_OPERATEJAMPTOC1_OPERATE

DEFLPDEF1_OPERATEEFHPTOC1_OPERATEMNSPTOC1_OPERATE

MNSPTOC2_OPERATE

STTPMSU1_OPR_IIT

PREVPTOC1_OPERATELOFLPTUC1_OPERATE

MPTTR1_OPERATE

STTPMSU1_OPR_STALL

FRPFRQ1_OPERATEFRPFRQ2_OPERATE

ARCSARC1_OPERATEARCSARC2_OPERATEARCSARC3_OPERATE

GUID-F40DC1A8-E388-4C3B-8690-AB26B00C94D9 V1 EN

Figure 171: Trip logic TRPPTRC1

3.6.3.2 Functional diagrams for disturbance recorder

The START and the OPERATE outputs from the protection stages are routed to triggerthe disturbance recorder or, alternatively, only to be recorded by the disturbancerecorder depending on the parameter settings. Additionally, the selected signals fromdifferent functions and few binary inputs are also connected to the disturbancerecorder.

1MRS756885 M Section 3REM615 standard configurations

REM615 131Application Manual

Page 138: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

RDRE1C1C2C3C4C5C6C7C8C9C10C11C12C13C14C15C16C17C18C19C20C21C22C23C24C25C26C27C28C29C30C31C32C33C34C35C36C37C38C39C40C41C42C43C44C45C46C47C48C49C50C51C52C53C54C55C56C57C58C59C60C61C62C63C64

TRIGGERED

OR6B1B2B3B4B5B6

O

ORB1B2

O

ORB1B2

O

CCBRBRF1_TRRET

X110_BI4_CB_CLOSEDX110_BI3_CB_OPENED

STTPMSU1_LOCK_START

MPTTR1_BLK_RESTART

MNSPTOC1_BLK_RESTART

MNSPTOC2_BLK_RESTART

X110_BI2_SPRING_DISCHARGEDX110_BI1_PLUG_OUT

PHPTUV1_OPERATEPSPTUV1_OPERATENSPTOV1_OPERATE

PHLPTOC1_OPERATEPHIPTOC1_OPERATEJAMPTOC1_OPERATE

DEFLPDEF1_OPERATEEFHPTOC1_OPERATE

MNSPTOC1_OPERATEMNSPTOC2_OPERATE

STTPMSU1_OPR_IIT

PREVPTOC1_OPERATELOFLPTUC1_OPERATE

MPTTR1_OPERATE

STTPMSU1_OPR_STALL

FRPFRQ1_OPERATEFRPFRQ2_OPERATE

ARCSARC1_OPERATEARCSARC2_OPERATEARCSARC3_OPERATE

STTPMSU1_MOT_STARTUP

PHIPTOC1_STARTPHLPTOC1_START

DEFLPDEF1_STARTEFHPTOC1_START

MNSPTOC1_START

MNSPTOC2_START

PREVPTOC1_STARTPHPTUV1_STARTPSPTUV1_STARTNSPTOV1_STARTFRPFRQ1_STARTFRPFRQ2_START

ESMGAPC1_ST_EMERG_ENA

CCSPVC1_FAIL

MPTTR1_ALARM

CCBRBRF1_TRBU

ARCSARC1_ARC_FLT_DETARCSARC2_ARC_FLT_DETARCSARC3_ARC_FLT_DET

GUID-879FC5EA-4355-4D43-810B-FE93224E9543 V2 EN

Figure 172: Disturbance recorder

3.6.3.3 Functional diagrams for condition monitoring

CCSPVC detects failures in the current measuring circuits. When a failure is detected,it can be used to block the current protection functions that measures the calculatedsequence component currents to avoid unnecessary operation. However, the BLOCKinput signal is not connected in the configuration.

Section 3 1MRS756885 MREM615 standard configurations

132 REM615Application Manual

Page 139: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

CCSPVC1BLOCK FAIL

ALARMCCSPVC1_FAILCCSPVC1_ALARM

GUID-9DE44742-C3E8-4991-A4E5-DBAACADC6F5F V2 EN

Figure 173: Current circuit supervision function

The circuit-breaker condition monitoring function SSCBR1 supervises the switchstatus based on the connected binary input information and the measured currentlevels. SSCBR1 introduces various supervision methods.

Set the parameters for SSCBR1 properly.

SSCBR1BLOCKPOSOPENPOSCLOSEOPEN_CB_EXECLOSE_CB_EXEPRES_ALM_INPRES_LO_INSPR_CHR_STSPR_CHRRST_IPOWRST_CB_WEARRST_TRV_TRST_SPR_T

TRV_T_OP_ALMTRV_T_CL_ALMSPR_CHR_ALM

OPR_ALMOPR_LO

IPOW_ALMIPOW_LO

CB_LIFE_ALMMON_ALM

PRES_ALMPRES_LO

OPENPOSINVALIDPOSCLOSEPOS

CB_OPEN_COMMANDCB_CLOSE_COMMAND

X110_BI4_CB_CLOSEDX110_BI3_CB_OPENED

X110_BI2_SPRING_DISCHARGED

SSCBR1_TRV_T_OP_ALMSSCBR1_TRV_T_CL_ALMSSCBR1_SPR_CHR_ALMSSCBR1_OPR_ALMSSCBR1_OPR_LOSSCBR1_IPOW_ALMSSCBR1_IPOW_LOSSCBR1_CB_LIFE_ALMSSCBR1_MON_ALMSSCBR1_PRES_ALMSSCBR1_PRES_LO

CB_SPRING_CHARGED

GUID-7BDBBD2B-C3E7-4ADD-BFFC-A54306576638 V1 EN

Figure 174: Circuit-breaker condition monitoring function

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

ORB1B2

O

SSCBR1_TRV_T_OP_ALMSSCBR1_TRV_T_CL_ALMSSCBR1_SPR_CHR_ALM

SSCBR1_OPR_ALMSSCBR1_OPR_LO

SSCBR1_IPOW_ALM

SSCBR1_IPOW_LOSSCBR1_CB_LIFE_ALM

SSCBR1_MON_ALMSSCBR1_PRES_ALM

SSCBR1_PRES_LO

SSCBR1_ALARMS

GUID-AEDC3866-D18C-4021-880A-79B9FD1FBD7E V1 EN

Figure 175: Logic for circuit breaker monitoring alarm

NOTIN OUTX110_BI2_SPRING_DISCHARGED CB_SPRING_CHARGED

GUID-B4FCFACE-B1B4-45A7-9747-2F6568D998CC V1 EN

Figure 176: Logic for start of circuit breaker spring charging

Two separate trip circuit supervision functions are included: TCSSCBR1 for poweroutput X100:PO3 for master trip and TCSSCBR2 for power output X100:PO4 forcircuit breaker closing. The trip circuit supervision TCSSCRB1 is blocked by both themaster trips TRPPTRC1 and TRPPTRC2 and the binary input X110:BI1 indicating

1MRS756885 M Section 3REM615 standard configurations

REM615 133Application Manual

Page 140: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

IED plug out. The trip circuit supervision TCSSCBR2 is blocked by the circuitbreaker closing signal or by the binary input X110:BI1 indicating IED plug out.

It is assumed that there is external resistor in the circuit breakertripping coil circuit connected in parallel with the circuit breakernormally open auxiliary contact.

Set the parameters for TCSSCBR1 properly.

ORB1B2

O TCSSCBR_ALARMTCSSCBR1_ALARMTCSSCBR2_ALARM

TCSSCBR2BLOCK ALARM

ORB1B2

OX110_BI4_CB_CLOSEDX110_BI1_PLUG_OUT

TCSSCBR2_ALARM

TCSSCBR1BLOCK ALARM

OR6B1B2B3B4B5B6

OTRPPTRC1_TRIPTRPPTRC2_TRIP

X110_BI1_PLUG_OUT TCSSCBR1_ALARM

GUID-14A1145B-D426-4D05-8DE7-1BA4F3AEA97B V1 EN

Figure 177: Trip circuit supervision function

3.6.3.4 Functional diagrams for control and interlocking

Two types of disconnector and earthing switch function blocks are available.DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 andESXSWI1 are controllable type. By default, the status only blocks are connected instandard configuration. The disconnector (CB truck) and line side earthing switchstatus information is connected to DCSXSWI1 and ESSXSI1.

The configuration also includes closed enable interlocking logic for disconnector andearthing switch. These signals are available for binary outputs X100:SO1 andX100:SO2.

Any additional signals required by the application can be connectedfor enable operation with earthing switch.

Section 3 1MRS756885 MREM615 standard configurations

134 REM615Application Manual

Page 141: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

DCSXSWI1POSOPENPOSCLOSE

OPENPOSCLOSEPOS

OKPOS DCSXSWI1_OKPOS

X110_BI5_CB_TRUCK_IN_TESTX110_BI6_CB_TRUCK_IN_SERVICE

AND6B1B2B3B4B5B6

O DC1_CLOSE_ENABLEESSXSWI1_OPENPOSCBXCBR1_OPENPOS

ESSXSWI1POSOPENPOSCLOSE

OPENPOSCLOSEPOS

OKPOS

ESSXSWI1_OPENPOSX110_BI7_ES1_OPENEDX110_BI8_ES1_CLOSED

OR6B1B2B3B4B5B6

O ES1_CLOSE_ENABLEX110_BI5_CB_TRUCK_IN_TEST

X110_BI1_PLUG_OUT

GUID-5159BE3C-2B41-4E80-BF89-6CC0B48DEBCB V1 EN

Figure 178: Disconnector and earth-switch control logic

The circuit breaker closing is enabled when the ENA_CLOSE input is activated. Theinput can be activated by the configuration logic, which is a combination of thedisconnector or breaker truck and earth-switch position status, status of the trip logics,gas pressure alarm and circuit-breaker spring charging status.

The OKPOS output from DCSXSWI defines if the disconnector or breaker truck iseither open (in test position) or close (in service position). This output, together withthe open earth-switch and non-active trip signals, spring charged status and non-activetrip circuit supervision alarm, activates the close-enable signal to the circuit-breakercontrol function block. The open operation for circuit breaker is always enabled.

CBXCBR1POSOPENPOSCLOSEENA_OPENENA_CLOSEBLK_OPENBLK_CLOSEAU_OPENAU_CLOSETRIPSYNC_OKSYNC_ITL_BYP

SELECTEDEXE_OPEXE_CL

OP_REQCL_REQ

OPENPOSCLOSEPOS

OKPOSOPEN_ENAD

CLOSE_ENAD

TRUECBXCBR1_ENA_CLOSE

CBXCBR1_EXE_CLX110_BI4_CB_CLOSEDX110_BI3_CB_OPENED

FALSERESTART_INHIBIT

CBXCBR1_EXE_OP

CBXCBR1_AU_OPENCBXCBR1_AU_CLOSE

CBXCBR1_OPENPOS

GUID-112B8BEF-3DE2-4620-91D4-98CFD95C59FF V2 EN

Figure 179: Circuit breaker control logic: Circuit breaker 1

Any additional signals required by the application can be connectedfor opening and closing of circuit breaker.

1MRS756885 M Section 3REM615 standard configurations

REM615 135Application Manual

Page 142: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

ORB1B2

O CB_CLOSE_COMMANDCBXCBR1_EXE_CL

GUID-A57F7ECC-A14F-4F14-9AD7-80245D4233DE V1 EN

Figure 180: Circuit breaker control logic: Signal for closing of circuit breaker 1

OR6B1B2B3B4B5B6

O CB_OPEN_COMMANDTRPPTRC1_TRIPTRPPTRC2_TRIP

CBXCBR1_EXE_OP

GUID-FABEBF90-0AD3-4B47-968D-29E718BECB64 V1 EN

Figure 181: Circuit breaker control logic: Signal for opening of circuit breaker 1

NOTIN OUT

AND6B1B2B3B4B5B6

O

NOTIN OUT

NOTIN OUT

CBXCBR1_ENA_CLOSETRPPTRC1_TRIP

TRPPTRC2_TRIP

DCSXSWI1_OKPOSESSXSWI1_OPENPOS

TCSSCBR_ALARM

X110_BI2_SPRING_DISCHARGED

GUID-235A0C52-F1E8-49B0-8A01-A984A1CFDC85 V1 EN

Figure 182: Circuit breaker close enable logic

Connect the higher-priority conditions before ending the closing ofcircuit breaker. This condition cannot be bypassed with bypass featureof the function.

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

RESTART_INHIBIT

TRPPTRC1_TRIPTRPPTRC2_TRIP

STTPMSU1_LOCK_START

MPTTR1_BLK_RESTART

MNSPTOC1_BLK_RESTARTMNSPTOC2_BLK_RESTART

END_OF_REMANENCE_TIME

GUID-D509B766-516A-4743-AC43-0FFB47BED5B5 V1 EN

Figure 183: Circuit breaker close blocking logic

When the motor restart is inhibited, the BLK_CLOSE input is activated and the circuitbreaker is not closed. When all conditions of the circuit breaker closing are met, theCLOSE_ENAD output of the CBXCBR1 is activated and the X100:PO1 output isclosed.

The configuration also includes restart inhibit. The restart inhibit is activated undervarious conditions.

Section 3 1MRS756885 MREM615 standard configurations

136 REM615Application Manual

Page 143: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

• An active trip command• Motor start-up supervision has issued lockout• Motor unbalance function has issued restart blocking• Thermal protection has issued blocked restart• Time during which remanence voltage is present

The configuration includes logic for generating circuit breaker external closing andopening command with the IED in local or remote mode.

Check the logic for the external circuit breaker closing command andmodify it according to the application.

Connect any additional signal applicable for the configuration forclosing and opening of circuit breaker in local or remote mode.

ANDB1B2

O

ANDB1B2

O

ORB1B2

O CBXCBR1_AU_CLOSE

CONTROL_LOCAL

CONTROL_REMOTE

FALSE

FALSE

GUID-EC0971B6-4978-4C57-9FDE-FCCE23F09E45 V1 EN

Figure 184: External closing command for circuit breaker

ANDB1B2

O

ORB1B2

O

ANDB1B2

O

CBXBCR1_AU_OPEN

CONTROL_LOCAL

CONTROL_REMOTE

FALSE

FALSE

GUID-623D1BE0-E501-4C89-A5C3-9DD1F44C8516 V1 EN

Figure 185: External opening command for circuit breaker

3.6.3.5 Functional diagrams for measurement functions

The phase current inputs to the IED are measured by the three-phase currentmeasurement function CMMXU1. The three-phase current input is connected to theX131, X132 and X133 card in the back panel for the three-phases. The sequencecurrent measurement CSMSQI1 measures the sequence current and the residualcurrent measurement RESCMMXU1 measures the residual current. The residualcurrent input is connected to the X130 card in the back panel.

The three-phase bus side phase voltage inputs to the IED are measured by the three-phase voltage measurement function VMMXU1 respectively. The three-phasecurrent input is connected to the X131, X132 and X133 card in the back panel for the

1MRS756885 M Section 3REM615 standard configurations

REM615 137Application Manual

Page 144: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

three-phases. The sequence voltage measurement VSMSQI1 measures the sequencevoltage.

The measurements can be seen in the LHMI and they are available under themeasurement option in the menu selection. Based on the settings, the function blockscan generate low alarm or warning and high alarm or warning signals for the measuredcurrent values.

The frequency measurement FMMXU1 of the power system and the three-phasepower and energy measurement PEMMXU1 are available. The load profile recordLDPRLRC1 is included in the measurements sheet. LDPRLRC1 offers the ability toobserve the loading history of the corresponding feeder.

CMMXU1BLOCK HIGH_ALARM

HIGH_WARNLOW_WARN

LOW_ALARM

GUID-D7982B6C-1154-407A-9D00-AB805A41251F V1 EN

Figure 186: Current measurement: Three-phase current measurement

CSMSQI1

GUID-F200ED57-7F7C-4A3F-8683-16069D3FED0A V1 EN

Figure 187: Current measurement: Sequence current measurements

RESCMMXU1BLOCK HIGH_ALARM

HIGH_WARN

GUID-8033A0A3-4337-4658-8C4F-C9BB43C71386 V1 EN

Figure 188: Current measurement: Residual current measurements

VMMXU1BLOCK HIGH_ALARM

HIGH_WARNLOW_WARN

LOW_ALARM

GUID-17FD1816-A1A0-4942-8601-41B9E820A8DE V1 EN

Figure 189: Voltage measurement: Three-phase voltage measurement

VSMSQI1

GUID-A9EFD885-8A1A-4C2D-B6E7-61CE8355C9DC V1 EN

Figure 190: Voltage measurement: Sequence voltage measurement

FMMXU1

GUID-DDFBF72C-8C1C-4B01-A2A0-1B74C90BC3D1 V1 EN

Figure 191: Other measurement: Frequency measurement

Section 3 1MRS756885 MREM615 standard configurations

138 REM615Application Manual

Page 145: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

PEMMXU1RSTACM

GUID-ED19EC38-ECB8-4ACD-9246-4E7A5AA4A90C V1 EN

Figure 192: Other measurement: Three-phase power and energy measurement

FLTRFRC1BLOCKCB_CLRD

GUID-642C92D1-8B08-4148-BEA9-7BD2B8B8B36D V2 EN

Figure 193: Other measurement: Data monitoring

LDPRLRC1RSTMEM MEM_WARN

MEM_ALARM

GUID-580EA1D1-4F0F-4D4D-8788-D404ECFA40D8 V2 EN

Figure 194: Other measurement: Load profile record

1MRS756885 M Section 3REM615 standard configurations

REM615 139Application Manual

Page 146: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

3.6.3.6 Functional diagrams for I/O and alarm LEDs

ORB1B2

O

ORB1B2

O

ORB1B2

O

ORB1B2

O

ORB1B2

O

ORB1B2

O

ORB1B2

O

ORB1B2

O

X110_BI4_CB_CLOSED

X110_BI3_CB_OPENED

X110_BI2_SPRING_DISCHARGED

X110_BI5_CB_TRUCK_IN_TEST

X110_BI6_CB_TRUCK_IN_SERVICE

X110_BI7_ES1_OPENED

X110_BI8_ES1_CLOSED

X110_BI1_PLUG_OUT

X110 (BIO-H).X110-Input 2

X110 (BIO-H).X110-Input 3

X110 (BIO-H).X110-Input 5

X110 (BIO).X110-Input 2

X110 (BIO).X110-Input 6

X110 (BIO).X110-Input 4

X110 (BIO).X110-Input 7

X110 (BIO-H).X110-Input 6

X110 (BIO-H).X110-Input 1

X110 (BIO-H).X110-Input 8

X110 (BIO-H).X110-Input 7

X110 (BIO).X110-Input 3

X110 (BIO).X110-Input 5

X110 (BIO).X110-Input 1

X110 (BIO).X110-Input 8

X110 (BIO-H).X110-Input 4

GUID-F7E38B7C-25FA-414E-A8D1-E3589B09D8B5 V1 EN

Figure 195: Binary inputs - X110 terminal block

Section 3 1MRS756885 MREM615 standard configurations

140 REM615Application Manual

Page 147: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

CB_OPEN_COMMAND

CB_CLOSE_COMMAND

ES1_CLOSE_ENABLE

DC1_CLOSE_ENABLE

CBXCBR1_ENA_CLOSE

CCBRBRF1_TRRET

X100 (PSM).X100-PO1

X100 (PSM).X100-PO2

X100 (PSM).X100-SO1

X100 (PSM).X100-SO2

X100 (PSM).X100-PO3

X100 (PSM).X100-PO4GUID-C087FF9C-A233-42B9-AAEB-7FFFDD0AAC53 V1 EN

Figure 196: Binary outputs - X100 terminal block

TRPPTRC3_TRIP

TRPPTRC4_TRIP

TRPPTRC5_TRIP

X110 (BIO-H).X110-HSO1

X110 (BIO-H).X110-HSO2

X110 (BIO-H).X110-HSO3GUID-2978537E-53FA-4CF8-9CFE-20E11C2E0C11 V1 EN

Figure 197: Binary outputs - X110 terminal block

1MRS756885 M Section 3REM615 standard configurations

REM615 141Application Manual

Page 148: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

OR6B1B2B3B4B5B6

O

LED1OKALARMRESET

LED2OKALARMRESET

LED3OKALARMRESET

LED4OKALARMRESET

LED5OKALARMRESET

ORB1B2

O

CBXCBR1_ENA_CLOSE

PHPTUV1_OPERATEPSPTUV1_OPERATE

NSPTOV1_OPERATE

PHLPTOC1_OPERATEJAMPTOC1_OPERATE

DEFLPDEF1_OPERATEEFHPTOC1_OPERATE

MNSPTOC1_OPERATEMNSPTOC2_OPERATE

STTPMSU1_OPR_IIT

PREVPTOC1_OPERATELOFLPTUC1_OPERATE

LOFLPTUC1_OPERATE

STTPMSU1_OPR_STALL

PHxPTOC_OPERATE

FRPFRQ_OPERATE

LED6OKALARMRESET

LED7OKALARMRESET

MPTTR1_OPERATE

GUID-1435607E-79DC-4F93-958D-B77FA21A15DA V2 EN

Section 3 1MRS756885 MREM615 standard configurations

142 REM615Application Manual

Page 149: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

LED8OKALARMRESET

LED9OKALARMRESET

LED10OKALARMRESET

LED11OKALARMRESET

OR6B1B2B3B4B5B6

O

ORB1B2

O

TCSSCBR_ALARM

VOLTAGE_PROT_OPERATE

MDSOPT1_ALARMCCSPVC1_ALARM

FRPFRQ_OPERATE

SSCBR1_ALARMS

GUID-FDAD7121-C008-489C-83AB-A14FDF29EB11 V2 EN

Figure 198: Default LED connections

3.6.3.7 Functional diagrams for other timer logics

The configuration also includes voltage operate, motor start-up and thermal alarm,blocking logic for phase under voltage protection, blocking logic for phase revesal andnegative-sequence overcurrent protection and logic for remanence voltage. Therestart inhibit is activated for a set period when a circuit breaker is in open state. Thisis called remanence voltage protection where the motor has damping remanencevoltage after the opening of a circuit breaker. Re-closing after a short period of timecan lead to stress for the machine and other apparatus. The remanence voltageprotection waiting time can be set by a timer function TPSGAPC1.

TPGAPC2IN1IN2

OUT1OUT2

MOTOR_STARTUP_PULSETHERMAL_ALARM_PULSE

STTPMSU1_MOT_STARTUPMPTTR1_ALARM

GUID-3F7FED3B-5D49-49DA-9430-30B325807B95 V1 EN

Figure 199: Timer logic for motor start-up and thermal alarm

TPGAPC3IN1IN2

OUT1OUT2

VOLTAGE_PROT_OPERATE_PULSEVOLTAGE_PROT_OPERATE

GUID-4C128D34-EB88-474A-AB5B-C478756072C5 V1 EN

Figure 200: Timer logic for voltage protection operate alarm

1MRS756885 M Section 3REM615 standard configurations

REM615 143Application Manual

Page 150: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Add the signals for blocking phase undervoltage protection.

OR6B1B2B3B4B5B6

OSTTPMSU1_MOT_STARTUP BLOCK_PHPTUV

GUID-C7AC0C98-9430-4D3F-8FC7-FB469B8981AE V1 EN

Figure 201: Blocking logic for phase undervoltage and sequence voltageprotection

Add the signals for blocking phase reversal and negative-sequenceovercurrent protection.

OR6B1B2B3B4B5B6

O BLOCK_MNSPTOC_AND_PREVPTOCCCSPVC1_FAIL

GUID-CE75CC23-EF1C-42D2-991A-A09E0AC32FE0 V2 EN

Figure 202: Blocking logic for phase reversal and negative-sequence overcurrentprotection

TPSGAPC1IN1IN2

OUT1OUT2

CB_OPEN_COMMAND END_OF_REMANENCE_TIME

GUID-4FDEAF07-18C7-4235-886F-2867748D6F78 V1 EN

Figure 203: Timer logic for remanence voltage to disappear

3.6.3.8 Other functions

The configuration includes few instances of multipurpose protection functionMAPGAPC and different types of timers and control functions. These functions arenot included in application configuration but they can be added based on the systemrequirements.

Section 3 1MRS756885 MREM615 standard configurations

144 REM615Application Manual

Page 151: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Section 4 Requirements for measurementtransformers

4.1 Current transformers

4.1.1 Current transformer requirements for overcurrent protection

For reliable and correct operation of the overcurrent protection, the CT has to bechosen carefully. The distortion of the secondary current of a saturated CT mayendanger the operation, selectivity, and co-ordination of protection. However, whenthe CT is correctly selected, a fast and reliable short circuit protection can be enabled.

The selection of a CT depends not only on the CT specifications but also on thenetwork fault current magnitude, desired protection objectives, and the actual CTburden. The protection settings of the protection relay should be defined in accordancewith the CT performance as well as other factors.

4.1.1.1 Current transformer accuracy class and accuracy limit factor

The rated accuracy limit factor (Fn) is the ratio of the rated accuracy limit primarycurrent to the rated primary current. For example, a protective current transformer oftype 5P10 has the accuracy class 5P and the accuracy limit factor 10. For protectivecurrent transformers, the accuracy class is designed by the highest permissiblepercentage composite error at the rated accuracy limit primary current prescribed forthe accuracy class concerned, followed by the letter "P" (meaning protection).

Table 33: Limits of errors according to IEC 60044-1 for protective current transformers

Accuracy class Current error atrated primarycurrent (%)

Phase displacement at rated primarycurrent

Composite error atrated accuracy limitprimary current (%)minutes centiradians

5P ±1 ±60 ±1.8 5

10P ±3 - - 10

The accuracy classes 5P and 10P are both suitable for non-directional overcurrentprotection. The 5P class provides a better accuracy. This should be noted also if thereare accuracy requirements for the metering functions (current metering, powermetering, and so on) of the protection relay.

The CT accuracy primary limit current describes the highest fault current magnitudeat which the CT fulfils the specified accuracy. Beyond this level, the secondary current

1MRS756885 M Section 4Requirements for measurement transformers

REM615 145Application Manual

Page 152: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

of the CT is distorted and it might have severe effects on the performance of theprotection relay.

In practise, the actual accuracy limit factor (Fa) differs from the rated accuracy limitfactor (Fn) and is proportional to the ratio of the rated CT burden and the actual CTburden.

The actual accuracy limit factor is calculated using the formula:

F FS S

S Sa n

in n

in

≈ ×

+

+

A071141 V1 EN

Fn the accuracy limit factor with the nominal external burden Sn

Sin the internal secondary burden of the CT

S the actual external burden

4.1.1.2 Non-directional overcurrent protection

The current transformer selectionNon-directional overcurrent protection does not set high requirements on the accuracyclass or on the actual accuracy limit factor (Fa) of the CTs. It is, however,recommended to select a CT with Fa of at least 20.

The nominal primary current I1n should be chosen in such a way that the thermal anddynamic strength of the current measuring input of the protection relay is notexceeded. This is always fulfilled when

I1n > Ikmax / 100,

Ikmax is the highest fault current.

The saturation of the CT protects the measuring circuit and the current input of theprotection relay. For that reason, in practice, even a few times smaller nominalprimary current can be used than given by the formula.

Recommended start current settingsIf Ikmin is the lowest primary current at which the highest set overcurrent stage is tooperate, the start current should be set using the formula:

Current start value < 0.7 × (Ikmin / I1n)

I1n is the nominal primary current of the CT.

The factor 0.7 takes into account the protection relay inaccuracy, current transformererrors, and imperfections of the short circuit calculations.

Section 4 1MRS756885 MRequirements for measurement transformers

146 REM615Application Manual

Page 153: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

The adequate performance of the CT should be checked when the setting of the highset stage overcurrent protection is defined. The operate time delay caused by the CTsaturation is typically small enough when the overcurrent setting is noticeably lowerthan Fa.

When defining the setting values for the low set stages, the saturation of the CT doesnot need to be taken into account and the start current setting is simply according to theformula.

Delay in operation caused by saturation of current transformersThe saturation of CT may cause a delayed protection relay operation. To ensure thetime selectivity, the delay must be taken into account when setting the operate timesof successive protection relays.

With definite time mode of operation, the saturation of CT may cause a delay that isas long as the time constant of the DC component of the fault current, when the currentis only slightly higher than the starting current. This depends on the accuracy limitfactor of the CT, on the remanence flux of the core of the CT, and on the operate timesetting.

With inverse time mode of operation, the delay should always be considered as beingas long as the time constant of the DC component.

With inverse time mode of operation and when the high-set stages are not used, the ACcomponent of the fault current should not saturate the CT less than 20 times thestarting current. Otherwise, the inverse operation time can be further prolonged.Therefore, the accuracy limit factor Fa should be chosen using the formula:

Fa > 20 × Current start value / I1n

The Current start value is the primary start current setting of the protection relay.

4.1.1.3 Example for non-directional overcurrent protection

The following figure describes a typical medium voltage feeder. The protection isimplemented as three-stage definite time non-directional overcurrent protection.

1MRS756885 M Section 4Requirements for measurement transformers

REM615 147Application Manual

Page 154: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

A071142 V1 EN

Figure 204: Example of three-stage overcurrent protection

The maximum three-phase fault current is 41.7 kA and the minimum three-phase shortcircuit current is 22.8 kA. The actual accuracy limit factor of the CT is calculated tobe 59.

The start current setting for low-set stage (3I>) is selected to be about twice thenominal current of the cable. The operate time is selected so that it is selective with thenext protection relay (not visible in Figure 204). The settings for the high-set stage andinstantaneous stage are defined also so that grading is ensured with the downstreamprotection. In addition, the start current settings have to be defined so that theprotection relay operates with the minimum fault current and it does not operate withthe maximum load current. The settings for all three stages are as in Figure 204.

For the application point of view, the suitable setting for instantaneous stage (I>>>) inthis example is 3 500 A (5.83 × I2n). I2n is the 1.2 multiple with nominal primarycurrent of the CT. For the CT characteristics point of view, the criteria given by thecurrent transformer selection formula is fulfilled and also the protection relay settingis considerably below the Fa. In this application, the CT rated burden could have beenselected much lower than 10 VA for economical reasons.

Section 4 1MRS756885 MRequirements for measurement transformers

148 REM615Application Manual

Page 155: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Section 5 Protection relay's physical connections

5.1 Inputs

5.1.1 Energizing inputs

5.1.1.1 Phase currents

The protection relay can also be used in single or two-phaseapplications by leaving one or two energizing inputs unoccupied.However, at least terminals X120:7-8 must be connected.

Table 34: Phase current inputs included in configurations A, B and C

Terminal DescriptionX120:7-8 IL1

X120:9-10 IL2

X120:11-12 IL3

5.1.1.2 Residual current

Table 35: Residual current input included in configurations A, B and C

Terminal DescriptionX120:13-14 Io

Table 36: Residual current input included in configuration D

Terminal DescriptionX130:1-2 Io

5.1.1.3 Phase voltages

Table 37: Phase voltage inputs included in configuration B

Terminal DescriptionX120:1-2 U1

X120:3-4 U2

X120:5-6 U3

1MRS756885 M Section 5Protection relay's physical connections

REM615 149Application Manual

Page 156: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Table 38: Phase voltage inputs included in configuration C

Terminal DescriptionX130:11-12 U1

X130:13-14 U2

X130:15-16 U3

5.1.1.4 Residual voltage

Table 39: Residual voltage input included in configuration C

Terminal DescriptionX130:17-18 Uo

5.1.1.5 Sensor inputs

Table 40: Combi sensor inputs included in configuration D

Terminal DescriptionX131 IL1

U1

X132 IL2U2

X133 IL3U3

5.1.2 Auxiliary supply voltage input

The auxiliary voltage of the protection relay is connected to terminals X100:1-2. AtDC supply, the positive lead is connected to terminal X100:1. The permitted auxiliaryvoltage range (AC/DC or DC) is marked on the top of the LHMI of the protectionrelay.

Table 41: Auxiliary voltage supply

Terminal DescriptionX100:1 + Input

X100:2 - Input

5.1.3 Binary inputs

The binary inputs can be used, for example, to generate a blocking signal, to unlatchoutput contacts, to trigger the disturbance recorder or for remote control of protectionrelay's settings.

Binary inputs of slot X110 are available with configurations B, C and D and optionalfor A.

Section 5 1MRS756885 MProtection relay's physical connections

150 REM615Application Manual

Page 157: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Table 42: Binary input terminals X110:1-13 with BIO0005 module

Terminal DescriptionX110:1 BI1, +

X110:2 BI1, -

X110:3 BI2, +

X110:4 BI2, -

X110:5 BI3, +

X110:6 BI3, -

X110:6 BI4, -

X110:7 BI4, +

X110:8 BI5, +

X110:9 BI5, -

X110:9 BI6, -

X110:10 BI6, +

X110:11 BI7, +

X110:12 BI7, -

X110:12 BI8, -

X110:13 BI8, +

Table 43: Binary input terminals X110:1-10 with BIO0007 module

Terminal DescriptionX110:1 BI1, +

X110:5 BI1, -

X110:2 BI2, +

X110:5 BI2, -

X110:3 BI3, +

X110:5 BI3, -

X110:4 BI4, +

X110:5 BI4, -

X110:6 BI5, +

X110:10 BI5, -

X110:7 BI6, +

X110:10 BI6, -

X110:8 BI7, +

X110:10 BI7, -

X110:9 BI8, +

X110:10 BI8, -

Binary inputs of slot X120 are available with configurations A and C.

1MRS756885 M Section 5Protection relay's physical connections

REM615 151Application Manual

Page 158: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Table 44: Binary input terminals X120-1...6

Terminal DescriptionX120:1 BI1, +

X120:2 BI1, -

X120:3 BI2, +

X120:2 BI2, -

X120:4 BI3, +

X120:2 BI3, -

X120:5 BI4, +

X120:6 BI4, -

Binary inputs of slot X130 are optional for configuration B.

Table 45: Binary input terminals X130:1-9

Terminal DescriptionX130:1 BI1, +

X130:2 BI1, -

X130:2 BI2, -

X130:3 BI2, +

X130:4 BI3, +

X130:5 BI3, -

X130:5 BI4, -

X130:6 BI4, +

X130:7 BI5, +

X130:8 BI5, -

X130:8 BI6, -

X130:9 BI6, +

Binary inputs of slot X130 are available with configuration C.

Table 46: Binary input terminals X130:1-8 with AIM0006 module

Terminal DescriptionX130:1 BI1, +

X130:2 BI1, -

X130:3 BI2, +

X130:4 BI2, -

X130:5 BI3, +

X130:6 BI3, -

X130:7 BI4, +

X130:8 BI4, -

Section 5 1MRS756885 MProtection relay's physical connections

152 REM615Application Manual

Page 159: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

5.1.4 Optional light sensor inputs

If the protection relay is provided with the optional communication module with lightsensor inputs, the pre-manufactured lens-sensor fibers are connected to inputs X13,X14 and X15. See the connection diagrams.For further information, see arcprotection.

The protection relay is provided with connection sockets X13, X14and X15 only if the optional communication module with light sensorinputs has been installed. If the arc protection option is selected whenordering a protection relay, the light sensor inputs are included in thecommunication module.

Table 47: Light sensor input connectors

Terminal DescriptionX13 Input Light sensor 1

X14 Input Light sensor 2

X15 Input Light sensor 3

5.1.5 RTD/mA inputs

RTD/mA inputs are optional for configurations A and B.

Table 48: RTD/mA inputs

Terminal DescriptionX130:1 mA1 (AI1), +

X130:2 mA1 (AI1), -

X130:3 mA2 (AI2), +

X130:4 mA2 (AI2), -

X130:5 RTD1 (AI3), +

X130:6 RTD1 (AI3), -

X130:7 RTD2 (AI4), +

X130:8 RTD2 (AI4), -

X130:9 RTD3 (AI5), +

X130:10 RTD3 (AI5), -

X130:11 Common1)

X130:12 Common2)

X130:13 RTD4 (AI6), +

X130:14 RTD4 (AI6), -

X130:15 RTD5 (AI7), +

Table continues on next page

1MRS756885 M Section 5Protection relay's physical connections

REM615 153Application Manual

Page 160: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Terminal DescriptionX130:16 RTD5 (AI7), -

X130:17 RTD6 (AI8), +

X130:18 RTD6 (AI8), -

1) Common ground for RTD channels 1-32) Common ground for RTD channels 4-6

5.2 Outputs

5.2.1 Outputs for tripping and controlling

Output contacts PO1, PO2, PO3 and PO4 are heavy-duty trip contacts capable ofcontrolling most circuit breakers. In the factory default configuration, the trip signalsfrom all the protection stages are routed to PO3 and PO4.

Table 49: Output contacts

Terminal DescriptionX100:6 PO1, NO

X100:7 PO1, NO

X100:8 PO2, NO

X100:9 PO2, NO

X100:15 PO3, NO (TCS resistor)

X100:16 PO3, NO

X100:17 PO3, NO

X100:18 PO3 (TCS1 input), NO

X100:19 PO3 (TCS1 input), NO

X100:20 PO4, NO (TCS resistor)

X100:21 PO4, NO

X100:22 PO4, NO

X100:23 PO4 (TCS2 input), NO

X100:24 PO4 (TCS2 input), NO

5.2.2 Outputs for signalling

SO output contacts can be used for signalling on start and tripping of the protectionrelay. On delivery from the factory, the start and alarm signals from all the protectionstages are routed to signalling outputs.

Section 5 1MRS756885 MProtection relay's physical connections

154 REM615Application Manual

Page 161: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Table 50: Output contacts X100:10-14

Terminal DescriptionX100:10 SO1, common

X100:11 SO1, NC

X100:12 SO1, NO

X100:13 SO2, NO

X100:14 SO2, NO

Output contacts of slot X110 are optional for configuration A.

Table 51: Output contacts X110:14-24 with BIO0005

Terminal DescriptionX110:14 SO1, common

X110:15 SO1, NO

X110:16 SO1, NC

X110:17 SO2, common

X110:18 SO2, NO

X110:19 SO2, NC

X110:20 SO3, common

X110:21 SO3, NO

X110:22 SO3, NC

X110:23 SO4, common

X110:24 SO4, NO

Table 52: Optional high-speed output contacts X110:15-24 with BIO0007

Terminal DescriptionX110:15 HSO1, NO

X110:16 HSO1, NO

X110:19 HSO2, NO

X110:20 HSO2, NO

X110:23 HSO3, NO

X110:24 HSO3, NO

Output contacts of slot X130 are available in the optional BIO module (BIOB02A).

Table 53: Output contacts X130:10-18

Terminal DescriptionX130:10 SO1, common

X130:11 SO1, NO

X130:12 SO1, NC

Table continues on next page

1MRS756885 M Section 5Protection relay's physical connections

REM615 155Application Manual

Page 162: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Terminal DescriptionX130:13 SO2, common

X130:14 SO2, NO

X130:15 SO2, NC

X130:16 SO3, common

X130:17 SO3, NO

X130:18 SO3, NC

5.2.3 IRF

The IRF contact functions as an output contact for the self-supervision system of theprotection relay. Under normal operating conditions, the protection relay is energizedand the contact is closed (X100:3-5). When a fault is detected by the self-supervisionsystem or the auxiliary voltage is disconnected, the contact X100:3-5 drops off and thecontact X100:3-4 closes.

Table 54: IRF contact

Terminal DescriptionX100:3 IRF, common

X100:4 Closed; IRF, or Uaux disconnected

X100:5 Closed; no IRF, and Uaux connected

Section 5 1MRS756885 MProtection relay's physical connections

156 REM615Application Manual

Page 163: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Section 6 Glossary

100BASE-FX A physical medium defined in the IEEE 802.3 Ethernetstandard for local area networks (LANs) that uses fiberoptic cabling

100BASE-TX A physical medium defined in the IEEE 802.3 Ethernetstandard for local area networks (LANs) that usestwisted-pair cabling category 5 or higher with RJ-45connectors

615 series Series of numerical protection and control relays forprotection and supervision applications of utilitysubstations, and industrial switchgear and equipment

AI Analog inputASCII American Standard Code for Information InterchangeBI Binary inputBIO Binary input and outputBO Binary outputCB Circuit breakerCT Current transformerDAN Doubly attached nodeDC 1. Direct current

2. Disconnector3. Double command

DNP3 A distributed network protocol originally developed byWestronic. The DNP3 Users Group has the ownershipof the protocol and assumes responsibility for itsevolution.

DPC Double-point controlEMC Electromagnetic compatibilityEthernet A standard for connecting a family of frame-based

computer networking technologies into a LANFIFO First in, first outFTP File transfer protocolFTPS FTP SecureGOOSE Generic Object-Oriented Substation EventHMI Human-machine interface

1MRS756885 M Section 6Glossary

REM615 157Application Manual

Page 164: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

HSO High-speed outputHSR High-availability seamless redundancyHTTPS Hypertext Transfer Protocol SecureI/O Input/outputIEC International Electrotechnical CommissionIEC 60870-5-103 1. Communication standard for protective equipment

2. A serial master/slave protocol for point-to-pointcommunication

IEC 61850 International standard for substation communicationand modeling

IEC 61850-8-1 A communication protocol based on the IEC 61850standard series

IEC 61850-9-2 A communication protocol based on the IEC 61850standard series

IEC 61850-9-2 LE Lite Edition of IEC 61850-9-2 offering process businterface

IED Intelligent electronic deviceIEEE 1686 Standard for Substation Intelligent Electronic Devices'

(IEDs') Cyber Security CapabilitiesIP address A set of four numbers between 0 and 255, separated by

periods. Each server connected to the Internet isassigned a unique IP address that specifies the locationfor the TCP/IP protocol.

IRIG-B Inter-Range Instrumentation Group's time code formatB

LAN Local area networkLC Connector type for glass fiber cable, IEC 61754-20LCD Liquid crystal displayLE Light EditionLED Light-emitting diodeLHMI Local human-machine interfaceMAC Media access controlMCB Miniature circuit breakerMMS 1. Manufacturing message specification

2. Metering management systemModbus A serial communication protocol developed by the

Modicon company in 1979. Originally used forcommunication in PLCs and RTU devices.

Section 6 1MRS756885 MGlossary

158 REM615Application Manual

Page 165: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

Modbus TCP/IP Modbus RTU protocol which uses TCP/IP and Ethernetto carry data between devices

NC Normally closedNO Normally openPCM600 Protection and Control IED ManagerPO Power outputPRP Parallel redundancy protocolPTP Precision Time ProtocolREM615 Motor protection and control relayRIO600 Remote I/O unitRJ-45 Galvanic connector typeRSTP Rapid spanning tree protocolRTD Resistance temperature detectorRTU Remote terminal unitSAN Single attached nodeSingle-line diagram Simplified notation for representing a three-phase

power system. Instead of representing each of threephases with a separate line or terminal, only oneconductor is represented.

SLD Single-line diagramSMV Sampled measured valuesSNTP Simple Network Time ProtocolSO Signal outputTCS Trip-circuit supervisionVT Voltage transformerWAN Wide area networkWHMI Web human-machine interface

1MRS756885 M Section 6Glossary

REM615 159Application Manual

Page 166: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

160

Page 167: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

161

Page 168: Application Manual REM615 Motor Protection and Control · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and

ABB Distribution SolutionsDistribution AutomationP.O. Box 699FI-65101 VAASA, FinlandPhone +358 10 22 11

ABB Distribution AutomationManeja WorksVadodara-390013, IndiaPhone +91 265 2604386Fax +91 265 2638922

www.abb.com/mediumvoltagewww.abb.com/relionwww.abb.com/substationautomation