Annunciation System

Embed Size (px)

Citation preview

  • 7/27/2019 Annunciation System

    1/3

    Annunciation System

    Guidelines and consideration in planning and designing annunciation system for

    grid stations

    1. Audio and visual signalsEvery power system should be provided with an annunciation system both

    audio and visual signals in the event of trouble or abnormal conditions.

    a. Audio signals. Horns and intermittent gongs are used for audible signalsdevises. An intermittent gongs is provided in the grid control rooms.

    Howler horn are used in the unit area and areas where back ground

    noise is high or area remote from yards.

    b.

    Visual signals. These are provided lighted lettered window panels ofannunciatar. In larger grid stations annuciator panels indication is

    augmented by unit trouble lamps located in a readily visible position

    close to the unit. The event recorder is normally located in the control

    rooms. Separate annunciators (when provided ) for station service

    system and switchyards should be located on associated control panels

    of the station service switchgear or on the switchyard control panels.

    2. Annunciatorsa. General. The annunciators system should be designed for operation on

    ungrounded 110VDC or 220VDC.All remote contacts used for trouble

    annunciation should be electrically independent of contacts used for

    other purpose so annuciator circuits are separated from DC circuits .

    Auxiliary relays should be provided where independent contacts

    otherwise be obtained. The annunciator equipment should use solid

    state logic units, lighted window or LED type, designed and tested for

    surge with standing capacity in accordance with IEC.

    b. The switchboard annunciator operational sequence should be manual orautomatic.

    Automatic reset should be employed when there is either an SER or

    SCADA system backup. When system is controlled and dispatched by

  • 7/27/2019 Annunciation System

    2/3

    through the SCADA system , the reset features of the annuciators

    should be coordinated to ensure proper operation.

    Switchboard Annuciator operational sequence

    Field

    contact

    Control pushbutton

    or switch

    Alarm

    light

    Horn Aux or repeater

    contact

    Normal Off Off Off

    Abnormal Flashing On On

    Abnormal Acknowledge or

    silence

    On Off On

    Normal Reset Off Off Off

    Normal test On Off Off

    Certain alarm points have several trouble contacts in parallel byequipment group .generally, these are transformer bucholz and

    pressure relief valve operation.

    A control console window-indicating light annuciator is common to all

    units. One unit at time can be selected by use of the appropriate unit

    trouble status lighted pushbutton. Visual indication is provided when

    the unit switchboard annuciator is activated . The console window

    indicating lights are generally grouped by switch board annuciator

    points and provide essential trouble status to the operator. Unit trouble

    are normally categorized by shutdown, differential, over current,

    cooling. The window indicating light annuciator provides back up for a

    sequential event recorder. Unit switchboard annuciator remote control

    switches to silence and reset the switch-board annuciator should be

    provided on control console.

    Signal Description Signal Description

    87t Transformer diff 21 Line distance

    74 T/F over heat 50G T/F neutral o/c50/51T T/F o/c 49 T/F over heat

    86 BF lock out 42 Cooling failure

    71Q T/F low oil 63Q T/F sudden pressure

    94L1 Line lock out 63 Loss of CB energy for

    trip and close

  • 7/27/2019 Annunciation System

    3/3