Upload
irfan-ullah
View
221
Download
0
Embed Size (px)
Citation preview
7/27/2019 Annunciation System
1/3
Annunciation System
Guidelines and consideration in planning and designing annunciation system for
grid stations
1. Audio and visual signalsEvery power system should be provided with an annunciation system both
audio and visual signals in the event of trouble or abnormal conditions.
a. Audio signals. Horns and intermittent gongs are used for audible signalsdevises. An intermittent gongs is provided in the grid control rooms.
Howler horn are used in the unit area and areas where back ground
noise is high or area remote from yards.
b.
Visual signals. These are provided lighted lettered window panels ofannunciatar. In larger grid stations annuciator panels indication is
augmented by unit trouble lamps located in a readily visible position
close to the unit. The event recorder is normally located in the control
rooms. Separate annunciators (when provided ) for station service
system and switchyards should be located on associated control panels
of the station service switchgear or on the switchyard control panels.
2. Annunciatorsa. General. The annunciators system should be designed for operation on
ungrounded 110VDC or 220VDC.All remote contacts used for trouble
annunciation should be electrically independent of contacts used for
other purpose so annuciator circuits are separated from DC circuits .
Auxiliary relays should be provided where independent contacts
otherwise be obtained. The annunciator equipment should use solid
state logic units, lighted window or LED type, designed and tested for
surge with standing capacity in accordance with IEC.
b. The switchboard annunciator operational sequence should be manual orautomatic.
Automatic reset should be employed when there is either an SER or
SCADA system backup. When system is controlled and dispatched by
7/27/2019 Annunciation System
2/3
through the SCADA system , the reset features of the annuciators
should be coordinated to ensure proper operation.
Switchboard Annuciator operational sequence
Field
contact
Control pushbutton
or switch
Alarm
light
Horn Aux or repeater
contact
Normal Off Off Off
Abnormal Flashing On On
Abnormal Acknowledge or
silence
On Off On
Normal Reset Off Off Off
Normal test On Off Off
Certain alarm points have several trouble contacts in parallel byequipment group .generally, these are transformer bucholz and
pressure relief valve operation.
A control console window-indicating light annuciator is common to all
units. One unit at time can be selected by use of the appropriate unit
trouble status lighted pushbutton. Visual indication is provided when
the unit switchboard annuciator is activated . The console window
indicating lights are generally grouped by switch board annuciator
points and provide essential trouble status to the operator. Unit trouble
are normally categorized by shutdown, differential, over current,
cooling. The window indicating light annuciator provides back up for a
sequential event recorder. Unit switchboard annuciator remote control
switches to silence and reset the switch-board annuciator should be
provided on control console.
Signal Description Signal Description
87t Transformer diff 21 Line distance
74 T/F over heat 50G T/F neutral o/c50/51T T/F o/c 49 T/F over heat
86 BF lock out 42 Cooling failure
71Q T/F low oil 63Q T/F sudden pressure
94L1 Line lock out 63 Loss of CB energy for
trip and close
7/27/2019 Annunciation System
3/3