AM-WRF DEWATERING IMPROVEMENTS PROJECT
-
Upload
others
-
View
1
-
Download
0
Embed Size (px)
Citation preview
W A S H I N G T O N
C A L I F O R N I A
I D A H O COBURG
ALBANY
CW
GS
LW
G-001
1976018.00-G-001.dwg
pw :\\
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
AM-WRF DEWATERING IMPROVEMENTS PROJECT
PROJECT VICINITY
PROJECT NUMBER SS-20-02
GENERAL G-001 TITLE SHEET, REGION AND VICINITY MAPS G-002 SHEET
INDEX, EQUIPMENT PREFIXES AND ABBREVIATIONS G-003 PIPING SCHEDULE
AND GENERAL SYMBOLS G-004 SOLIDS STREAM PROCESS SCHEMATIC AND
DESIGN CRITERIA CIVIL C-001 CIVIL DETAILS C-100 OVERALL SITE PLAN
DEMOLITION D-201 DEWATERING BUILDING DEMOLITION PLAN D-202
DEWATERING BUILDING HVAC AND COMPRESSED AIR DEMOLITION PLAN D-211
CAKE STORAGE BUILDING DEMOLITION PLAN ARCHITECTURAL A-001 CODE
SUMMARY, SCHEDULES AND NOTES A-211 CAKE STORAGE BUILDING ELEVATIONS
STRUCTURAL S-001 STRUCTURAL GENERAL NOTES AND ABBREVIATIONS S-002
SPECIAL INSPECTION AND TESTING SCHEDULE S-003 STANDARD DETAILS
S-201 DEWATERING BUILDING FLOOR PLAN AND PLATFORM PLAN S-202
DEWATERING BUILDING SECTIONS S-203 DEWATERING BUILDING SECTIONS AND
DETAILS S-204 DEWATERING BUILDING DETAILS 1 S-205 DEWATERING
BUILDING DETAILS 2 S-210 CAKE STORAGE BUILDING FLOOR PLAN S-211
CAKE STORAGE BUILDING TOP PLAN S-212 CAKE STORAGE BUILDING SECTIONS
S-213 CAKE STORAGE BUILDING SECTIONS AND DETAILS MECHANICAL M-001
PIPING SYMBOLS AND NOTES M-002 STANDARD DETAILS M-005 HVAC
SCHEDULE, LEGEND AND ABBREVIATIONS M-006 CAKE STORAGE BUILDING AND
DEWATERING BUILDING HVAC SCHEMATICS M-200 DEWATERING BUILDING TOP
PLAN M-201 DEWATERING BUILDING PARTIAL BOTTOM PLAN M-202 DEWATERING
BUILDING SECTIONS 1 M-203 DEWATERING BUILDING SECTIONS 2 M-205
DEWATERING BUILDING HVAC PLAN M-211 CAKE STORAGE BUILDING PLAN
M-212 CAKE STORAGE BUILDING SECTIONS INSTRUMENTATION I-001 LEGEND
I-004 NETWORK BLOCK DIAGRAM I-011 P&ID BIOSOLIDS TRANSFER AND
SLUDGE FEED PUMPS I-012 P&ID POLYMER FEED SYSTEM I-013 P&ID
ROTARY SCREW PRESS 1 I-014 P&ID ROTARY SCREW PRESS 2 I-015
P&ID SCREW PRESS CONVEYORS I-016 P&ID CAKE CONVEYORS I-017
P&ID VENTILATION AND ODOR CONTROL ELECTRICAL E-001 LEGEND AND
ABBREVIATIONS E-002 STANDARD DETAILS 1 E-003 STANDARD DETAILS 2
E-005 MCC 10A / 10B SINGLE LINE DIAGRAM DEMOLITION E-006 EXISTING
SWBD 10A / 10B SINGLE LINE DIAGRAM AND MCC 10A / 10B ELEVATIONS -
DEMOLITION E-007 MCC 10A / 10B SINGLE LINE DIAGRAM E-008 MCC 10A /
10B ELEVATIONS E-009 CONDUIT AND WIRE SCHEDULE 1 E-010 CONDUIT AND
WIRE SCHEDULE 2 E-011 PANELBOARD SCHEDULES E-012 CONDUIT ROUTING
SCHEMATIC 1 E-013 CONDUIT ROUTING SCHEMATIC 2 E-014 CONDUIT ROUTING
SCHEMATIC 3 E-015 CONDUIT ROUTING SCHEMATIC 4 E-020 WIRING DIAGRAMS
FIRE ALARM SYSTEM AND SPARE STARTER E-021 WIRING DIAGRAMS EXHAUST
FANS E-022 WIRING DIAGRAMS SLUDGE FEED PUMP E-023 WIRING DIAGRAMS
SLUDGE FEED PUMP (CONTINUED) E-024 WIRING DIAGRAMS SCREW PRESS AND
CAKE CONVEYOR LCS E-025 WIRING DIAGRAMS SCREW PRESS AND CAKE
CONVEYOR LCS (CONTINUED) E-026 WIRING DIAGRAMS (E) EAST BAY - CAKE
LOADING CONVEYORS E-027 WIRING DIAGRAMS SCREW CONVEYORS AND CAKE
CONVEYORS E-028 WIRING DIAGRAMS CAKE STORAGE BUILDING ODOR CONTROL
UNIT AND GO NOGO STATIONS E-029 WIRING DIAGRAMS (F) COMPOSTING
SUPPLY FAN AND (F) COMPOSTING EXHAUST FAN E-030 WIRING DIAGRAMS
POLYMER AND SCREW PRESS EXHAUST FANS E-101 SITE PLAN E-201
DEWATERING BUILDING POWER, CONTROL AND SIGNAL PLAN E-202 DEWATERING
BUILDING MEZZANINE POWER, CONTROL AND SIGNAL PLAN E-211 CAKE
STORAGE BUILDING POWER, CONTROL AND SIGNAL PLAN
CW
GS
LW
G-002
1976018.00-G-002.dwg
pw :\\
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
AM-WRF DEWATERING IMPROVEMENTS PROJECT
SHEET INDEX: ABBREVIATIONS: & AND L ANGLE @ AT " INCH
SUPERSCRIPT ' FOOT SUPERSCRIPT Ø PHASE, DIAMETER A AIR OR PNEUMATIC
AB ANCHOR BOLT, AGGREGATE BASE AC ASBESTOS CEMENT A/C ASPHALT
CONCRETE ACP ASBESTOS CEMENT PIPE AFF ABOVE FINISHED FLOOR AGG
AGGREGATE ALUM ALUMINUM APPROX APPROXIMATE (-LY) APN ASSESORS
PARCEL NUMBER ARCH ARCHITECT (-URAL) ARV AIR RELEASE VALVE AU
ABOVEGROUND UTILITY AVE AVENUE AVG AVERAGE AVV AIR VACUUM
VALVE
BF BLIND FLANGE BFP BACKFLOW PREVENTER BFV BUTTERFLY VALVE BM BENCH
MARK BFPV BACKFLOW PREVENTER VALVE BLDG BUILDING BO BLOW OFF
CAV COMBINATION AIR VALVE CB CATCH BASIN CI CAST IRON CIP CAST IRON
PIPE CMP CORRUGATED METAL PIPE C CENTERLINE CY CUBIC YARD CL CLASS,
CENTERLINE CLR CLEAR (-ANCE) COL COLUMN CONC CONCRETE CONN CONNECT
(-S, -TION) CONST CONSTRUCT (-TION) CONT CONTINU (-ED, -OUS)
L
(D) DEMOLISH DEF DEFLECT DI DUCTILE IRON DIA DIAMETER DIP DUCTILE
IRON PIPE DIM DIMENSION DR DIMENSION RATIO DWG DRAWING
(E), EXIST EXISTING E EAST EA EACH ECC ECCENTRIC EDAC EDGE OF
ASPHALT EL ELEVATION ELEC ELECTRIC (-AL) ELL ELBOW ENCL ENCLOSURE
ENGR ENGINEER ENV DEPARTMENT OF ENVIRONMENTAL SERVICES,
CITY AND COUNTY OF HONOLULU EP, EOP EDGE OF PAVEMENT EQUIP
EQUIPMENT ETC ET CETERA EXP JT EXPANSION JOINT EXT EXTERIOR
(F) FUTURE FT FEET (FOOT) FC FLEXIBLE COUPLING FCA FLANGED COUPLING
ADAPTER FF FINISHED FLOOR FG FINISH GRADE FH FIRE HYDRANT FL
FLANGED FLEX FLEXIBLE FM FLOW METER, FINISHED GRADE FRP FIBERGLASS
REINFORCED PLASTIC
GB GRADE BREAK GPD GALLONS PER DAY GPM GALLONS PER MINUTE GS
GALVANIZED STEEL GV GATE VALVE GALV GALVANIZE GEN GENERATOR GND
GROUND GP GUARD POST
HB HOSE BIBB HDPE HIGH DENSITY POLYETHYLENE HVAC HEATING,
VENTILATING & AIR CONDITIONING HT HEIGHT HORIZ HORIZONTAL HP
HORSEPOWER HWY HIGHWAY
ICV IRRIGATION CONTROL VALVE ID INSIDE DIAMETER IE INVERT ELEVATION
INV INVERT IRR IRRIGATION
JB JUNCTION BOX
LF LINEAR FEET LT LEFT LTG LIGHTING
MFR MANUFACTURER MGD MILLION GALLONS PER DAY (M) MODIFIED MH
MANHOLE MJ MECHANICAL JOINT MATL, MTL MATERIAL MAX MAXIMUM MECH
MECHANICAL MFR MANUFACTURER MIN MINIMUM MISC MISCELLANEOUS MPT MALE
PIPE THREAD MW MONITORING WELL
(N) NEW N NORTH NC NORMALLY CLOSED NFC NOT FOR CONSTRUCTION NO
NORMALLY OPEN, NUMBER NPSH NET POSITIVE SUCTION HEAD NTS NOT TO
SCALE N/A NOT APPLICABLE NOM NOMINAL
OC ON CENTER OD OUTSIDE DIAMETER OF OVERFLOW OH OVERHEAD
P PIPE PC POINT OF CURVATURE PE PERMANENT EASEMENT PG PRESSURE
GAUGE ASSEMBLY PL PROPERTY LINE PP POWER POLE PROP PROPOSED PSI
POUNDS PER SQUARE INCH PSIG POUNDS PER SQUARE INCH-GAUGE PT POINT
OF TANGENCY PUE PUBLIC UTILITY EASEMENT PVC POLYVINYL
CHLORIDE
R RADIUS (R) RELOCATE RCP REINFORCED CONCRETE PIPE RD ROAD RR
RAILROAD RT RIGHT RS RAW SEWAGE R/W RIGHT-OF-WAY RW RECYCLED WATER
RWL RAINWATER LEADER RWP RECYCLED WATER PIPE RED REDUCE REF
REFERENCE REINF REINFORCING (-MENT) REQ'D REQUIRED
S SOUTH SA SAMPLE SCHED SCHEDULE SCO SANITARY SEWER CLEAN OUT SD
STORM DRAIN SECT SECTION SHT, SH SHEET SIM SIMILAR SL SIGNAL LIGHT
SPEC SPECIFICATION SQ SQUARE IN2 SQUARE INCHES SS SANITARY SEWER,
STAINLESS STEEL SSMH SANITARY SEWER MANHOLE ST STREET STA STATION
STND STANDARD SURF SURFACE SWBD SWITCH BOARD SWPPP STORM WATER
POLLUTION
PREVENTION PLAN
QSD QUALIFIED SWPPP DEVELOPER
t THICKNESS T TYPE TB THRUST BLOCK TBM TEMPORARY BENCH MARK TCE
TEMPORARY CONSTRUCTION EASEMENT TEL TELEPHONE THK THICK TOP TOP OF
PAVEMENT TOS TOP OF SLAB TPM TENTATIVE PARCEL MAP TYP TYPICAL
UG UNDERGROUND UPRR UNION PACIFIC RAILROAD
V VENT VAR VARIES VCP VITRIFIED CLAY PIPE VERT VERTICAL VTR VENT
THROUGH ROOF
W WEST; WIDE; WIDTH WAB WORK AREA BOUNDARY WP WEATHER PROTECTED WS
WELDED STEEL WWF WELDED WIRE FABRIC WWM WELDED WIRE MESH WWTP
WASTEWATER TREATMENT PLANT W/ WITH W/IN WITHIN W/O WITHOUT WSP
WELDED STEEL PIPE
XING CROSSING
AIR DRYER
AUTOMATIC TRANSFER SWITCH
BACKFLOW PREVENTER
BUTTERFLY VALVE
BALL VALVE
COLLECTOR
COMPRESSOR (AIR, GAS, ETC.)CP
MISCELLANEOUS EQUIPMENT
MOTOR OPERATOR
PRESSURE DIFFERENTIAL CONTROL VALVE
DEAERATOR
DIGESTER FLOATING COVER DISTRIBUTOR (ARM TYPE, EDUCTOR, EJECTOR,
DIFFUSER, ETC.)
DAMPER
FAN
PNL
POP
PRV
PSV
PV
PVL
SBD
SC
SCL
SCN
SEP
SWG
SLR
SMP
SRT
T
TBX
TCV
PNEUMATIC OPERATOR PRESSURE CONTROLLED VALVE (NON
SELF-ACTING)
PRESSURE SAFETY VALVE (VACUUM OR PRESSURE RELIEF)
PLUG VALVE PRESSURE VESSEL (AIR RECEIVER, ETC)
SWITCHBOARD (ELECTRICAL)
SPEED CONTROLLER
SEPARATOR (SEDIMENTATION TRAP, DRIP TRAP, CYCLONE, STRAINER,
ETC)
SWITCHGEAR
SILENCER
SAMPLER
TERMINAL BOX, BOARD, OR CABINET (ELECTRICAL, INSTRUMENTATION,
TELEPHONE) TEMPERATURE CONTROL VALVE (SELF-ACTING)
FV
GBV
GBT
GEN
GT
GV
HEX
HH
HOP
HTR
HTT
INJ
KV
LCV
LV
LVR
GLOBE VALVE
GATE VALVE
HEAT TRACE TAPE
LOUVER
TEL
TFR
TSV
TV
UH
US
UVM
VIB
WHR
WSU
YV
UNIT HEATER
UTILITY STATION
DU DRIVE UNIT
BOILERBLR
STP SOUND TRAP
SV SOLENOID VALVE
VERTICAL DATUM: EXISTING ELEVATIONS SHOWN ARE BASED ON OWNER
PROVIDED RECORD DRAWINGS. VERTICAL DATUM IS NGVD (29) 47.
CONTRACTOR TO FIELD VERIFY AS NEEDED.
FLAG NOTE
ELEVATION MARK
ELEVATION MARK
DEMOLITION
INFORMATION SHOWN MAY NOT BE ALL INCLUSIVE. THIS IS A GENERALIZED
LEGEND SHEET. THIS CONTRACT MAY NOT USE ALL INFORMATION
SHOWN.
NOTES:
CUTTING PLANE (SECTION)
BREAK LINE (LONG)
BREAK LINE (SHORT)
DETAIL REFERENCE
DETAIL (NUMERAL) 1
SECTION REFERENCE SECTION DRAWN ON SHEET G-004:
SHEET WHERE SECTION IS REFERENCED
A G-004
A G-006
SECTION (LETTER)
SECTION (LETTER)
(IN PLAN OR SECTION) ASPHALT CONCRETE (EXISTING)
ABBREV SYSTEM SIZE SERVICE FLOW PIPE TYPE MATERIAL LINING VALVE
SYSTEM TEST PRESSURE INSULATION
D DRAIN <4" E/S G V-1 PVC - B 20 NO
D DRAIN ≤4" B/C G N-3 CI - - 6 NO
D DRAIN >4" B/C G N-1 DI CM B 20 NO
D DRAIN ≥4" E/S G N-2 DI CM B 20 NO
NG NATURAL GAS ALL E P X-1 BS - J 30 NO
POL POLYMER ALL B/C P V-1 PVC - C 75 NO
POLS POLYMER SOLUTION ALL B/C P V-1 PVC - C 75 NO
SLF SLUDGE FEED <4" E/S P Y-1 GS - B 100 NO
SLF SLUDGE FEED ≥4" B/C P N-1 DI CM B 100 NO
SLF SLUDGE FEED ≥4" E/S P N-2 DI CM B 100 NO
V VENT <4" E/S G Q-3 ABS - - 6 NO
1W POTABLE WATER <4" B/E P T-1 CU - E 125 NO
1W POTABLE WATER ≥4" B P N-1 DI CM A 125 NO
1W POTABLE WATER ≥4" E P N-2 DI CM A 125 NO
2W NON-POTABLE WATER <4" B/E P V-1 PVC - A 125 NO
2W NON-POTABLE WATER ≥4" B P N-1 DI CM A 125 NO
2W NON-POTABLE WATER ≥4" E P N-2 DI CM A 125 NO
3W PLANT SERVICE WATER <4" B/E P V-1 PVC - A 125 NO
3W PLANT SERVICE WATER ≥4" B P N-1 DI CM A 125 NO
3W PLANT SERVICE WATER ≥4" E P N-2 DI CM A 125 NO
SIZE NOMINAL DIAMETER IN INCHES
SERVICE B = BURIED C = CONCRETE ENCASED E = EXPOSED
MATERIAL FOR REFERENCE ONLY, SEE SPECIFICATION 15050 FOR DETAILED
PIPE MATERIALS. ABS = ACRYLONITRILE BUTADIENE-STYRENE BS = BLACK
STEEL CI = CAST IRON CU = COPPER DI = DUCTILE IRON GS = GALVANIZED
STEEL PVC = POLYVINYL CHLORIDE
VALVE SYSTEM SEE SPECIFICATION 15050 UNLESS NOTED.
TEST PRESSURE PRESSURE IN PSI
PIPING SCHEDULE LEGEND:
EQUIPMENT DESIGNATIONS
SITE CODE
WW1-015FV6001
G-003
1976018.00-G-003.dwg
pw :\\
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
(E) LIVE BOTTOM SCREW AND
INCLINED SCREW CONVEYORS
FEED PUMPS (E) SLUDGE
YEAR 2020, PPD (DRY) YEAR 2040, PPD (DRY)
MAXIMUM MONTH YEAR 2020 PPD (DRY) YEAR 2040 PPD (DRY)
SOLIDS CONCENTRATION, %
TYPE NUMBER CAPACITY, GPM HEAD, FT POWER, HP
SLUDGE FEED PUMPS (EXISTING) TYPE NUMBER CAPACITY, GPM DISCHARGE
PRESSURE, PSI POWER, HP
DEWATERING FLOCCULATION TANKS
ROTARY SCREW PRESSES NUMBER CAPACITY, EACH UNIT
HYDRAULIC, GPM MASS, DRY LB/HR
POWER, HP (EACH UNIT) CAPTURE RATE % CAKE SOLIDS CONCENTRATION, %
POLYMER CONSUMPTION, ACTIVE LB/DT
POLYMER SYSTEM NUMBER POLYMER TYPE CAPACITY RANGE
POLYMER, GPH (EACH UNIT) DILUTION WATER, GPM (EACH UNIT)
STORAGE TYPE CAKE CONVEYANCE
SCREW PRESS CONVEYORS TYPE NUMBER LENGTH, FT POWER, HP (EACH)
CAKE CONVEYORS TYPE NUMBER LENGTH, FT POWER, HP (EACH)
CAKE STORAGE 1 TOTAL AREA, SF TOTAL CAKE VOLUME, CY DAYS OF STORAGE
2
ODOR CONTROL TYPE CAPACITY, CFM POWER, HP
VALUE
15-25
25
NOTES:
1. VALUES ASSUME USE OF THE EAST BAY OF THE EXISTING CAKE STORAGE
BUILDING. TOTAL MATERIAL HEIGHT IS ASSUMED TO BE 8 FEET AND 25
PERCENT OF THE TOTAL SPACE IS ASSUMED TO BE OPEN FOR MOVEMENT OF
MATERIALS HANDLING EQUIPMENT.
2. VALUE CALCULATED AT YEAR 2020 AVERAGE ANNUAL SOLIDS
PRODUCTION.
MH
GS
LW
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
<3"
AC PAVING, OR GROUND COVER, OR CONCRETE SLAB WHERE APPLICABLESLOPE
TRENCH
AS REQUIRED
5" 10"
NOTE:
1. WHERE SHORING IS REQUIRED, "A" IS TO THE BACK OF SHORING.
PIPE ZONE MATERIAL (PER SPEC SECTION 02300) 95% RELATIVE
COMPACTION
SELECT FILL (PER SECTION 02300) 95% RELATIVE COMPACTION. IN PAVED
AREAS USE AGGREGATE BASE (PER SECTION 02300) 95% RELATIVE
COMPACTION
>12", <24" 12" >3", <12"
WARNING TAPE 6" MIN
2BOLLARD DETAIL
8" SCHEDULE 40 STEEL PIPE, FILL WITH CONCRETE
1" GROUT SLOPE AWAY FROM PIPE
95% RELATIVE COMPACTION SELECT FILL ALL AROUND
CONCRETE ENCASEMENT
1. STEEL PIPE SHALL BE SEAMLESS, CONFORMING TO TO ASTM A53, GRADE
A.
2. HOT DIP GALVANIZED PIPE IN ACCORDANCE WITH ASTM A525, G-90
COMMERCIAL.
3. PROVIDE A PROTECTIVE COATING PER SECTION 09960. COLOR SHALL BE
SAFETY YELLOW.
ASPHALT CONCRETE, 5" COMPACTED THICKNESS
SUBGRADE
NOTE:
1. ASPHALT CONCRETE PAVEMENT SHALL CONFORM TO THE REQUIREMENTS OF
SECTION 304 "ASPHALT CONCRETE PAVEMENT" OF THE CITY OF ALBANY
STANDARD CONSTRUCTION SPECIFICATIONS.
2. ASPHALT SHALL BE REPLACED 12" PAST THE DEMOLITION EDGES. THE 12"
SECTIONS OF ASPHALT ON EACH SIDE OF THE DEMOLISHED AREA SHALL BE
SAWCUT AND REMOVED IMMEDIATELY PRIOR TO PLACING NEW ASPHALT.
(E) A/C
(E) A/C
3TYPICAL ASPHALT CONCRETE PAVING CUTBACK DETAIL
AGGREGATE BASE PER SECTION 02300 12" COMPACTED THICKNESS AT 95%
RELATIVE COMPACTION
CW
GS
LW
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
(E) AEROBIC DIGESTERS
(E) BLOWER BUILDING
PROJECT LIMITS
(E) AEROBIC DIGESTER TRANSFER PUMP VALVE VAULT
3W ACCESS, SEE NOTE 6 1
CW
GS
OVERALL SITE PLAN
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
1. PLANT PERIMETER FENCING SHALL REMAIN INTACT AT ALL TIMES.
2. CONTRACTOR TO MAINTAIN ACCESS TO ALL PORTIONS OF THE PLANT FOR
PLANT PERSONNEL AT ALL TIMES. CONTRACTOR SHALL COORDINATE ACCESS
WITH OTHER CONTRACTORS ON SITE.
3. CONTRACTOR SHALL RESTRICT MOVEMENT AROUND THE PLANT TO THE AREAS
AND ROUTES INDICATED ON THIS DRAWING UNLESS APPROVED
OTHERWISE.
4. CONTRACTOR SHALL LIMIT PARKING AND STORAGE OF MATERIALS TO THE
DESIGNATED STAGING AREA FOR THE PROJECT.
5. PROVIDE TEMPORARY BIOSOLIDS DEWATERING FACILITIES AT LOCATION
SHOWN PER REQUIREMENTS OF SPECIFICATION SECTION 01500. PROVIDE
TEMPORARY POWER AND CONNECTION TO OWNER'S CONTROL SYSTEM. FROM
WITHIN THE EXISTING INFLUENT PUMPING STATION. SEE ELECTRICAL SHEET
E-101. PROVIDE WASHWATER BY CONNECTING TO THE EXISTING 1 1/2-INCH
3W LINE LOCATED IN THE BOILER ROOM OF THE EXISTING HEADWORKS
BUILDING. PROVIDE TEMPORARY PIPING TO CONNECT THE AEROBIC DIGESTER
TRANSFER PUMP TO THE TEMPORARY BIOSOLIDS DEWATERING SYSTEM.
CONNECTION TO EXISTING SLUDGE TRANSFER PIPING SYSTEM CAN BE MADE
WITHIN THE EXISTING AEROBIC DIGESTER TRANSFER PUMP VALVE VAULT.
DISCHARGE FILTRATE TO ADJACENT SANITARY SEWER MANHOLE.
6. 3W WATER FOR THE TEMPORARY BIOSOLIDS DEWATERING FACILITY MAY BE
ACCESSED AT THE NORTH END OF THE LOWER LEVEL OF THE EXISTING
HEADWORKS BUILDING VIA AN EXISTING 1 ½ INCH UTILITY WATER STATION
WITH QUICK CONNECT. IF LARGER SIZED SUPPLY IS NEEDED, 2-INCH AND
3-INCH SUPPLY LINES ARE ALSO LOCATED WITHIN THE NORTH END OF THE
LOWER LEVEL OF THE EXISTING HEADWORKS BUILDING BUT WILL REQUIRE
INSERTING A CONNECTION POINT INTO THE EXISTING PIPING. CONTRACTOR
TO RESTORE PIPING SYSTEM TO ORIGINAL OR BETTER CONDITION PRIOR TO
COMPLETION OF THE WORK.
GENERAL NOTES:
SEE SPECIFICATION SECTION 01010 FOR CONSTRUCTION SEQUENCING AND
TEMPORARY SOLIDS DEWATERING FACILITIES THAT MUST BE IN PLACE PRIOR
TO INITIATING DEMOLITION WORK.
REPAIR HOLES AND MINOR SURFACE DAMAGE IN CONCRETE FROM DEMOLITION
PER DETAIL S-3060 .
METAL ANCHORS AND CUT BARS ASSOCIATED WITH DEMOLITION SHALL BE
BURNED BACK 1-INCH BELOW CONCRETE SURFACE. FILL WITH REPAIR MORTAR
TO MATCH FINISH AND SURFACE ELEVATION OF EXISTING ADJACENT
SURFACE.
PULL WIRES BACK FROM EQUIPMENT/DEVICES BEING DEMOLISHED TO SOURCE.
REMOVE EXPOSED CONDUIT, FITTINGS AND ACCESSORIES FROM DEVICE TO
SOURCE. CONDUIT EMBEDDED IN CONCRETE SHALL BE CAPPED AND
SEALED.
DEMOLISH 6-INCH SLF PIPE ABOVE FLOOR FOR CONNECTION OF NEW SLF PIPE
TO FEED NEW ROTARY SCREW PRESSES.
DEMOLISH BELT FILTER PRESSES, BELT PRESS MEZZANINE STRUCTURES,
CONCRETE SUPPORT PIERS, ASSOCIATED EXPOSED PIPING AND SUPPORTS, AND
ASSOCIATED ELECTRICAL AND CONTROL EQUIPMENT. ONE OF TWO BELT FILTER
PRESSES IS SHOWN FOR CLARITY. DEMOLISH BOTH BELT FILTER PRESSES AND
ASSOCIATED ITEMS AS LISTED.
DEMOLISH BELT FILTER SUMP GRATING THAT IS LOCATED BENEATH BOTH BELT
FILTER PRESSES. DEMOLISH GRATING, SUPPORTS, ANCHORS AND ASSOCIATED
ITEMS.
DEMOLISH CAKE PUMPS, EQUIPMENT SUPPORTS, PIPING AND ASSOCIATED
ELECTRICAL/CONTROL EQUIPMENT.
DEMOLISH WASHWATER BOOSTER PUMPS, EQUIPMENT SUPPORTS, PIPING AND
ASSOCIATED ELECTRICAL/CONTROL EQUIPMENT.
CAP AND ABANDON EXISTING 1 1/2-INCH 3W 6 INCHES ABOVE FLOOR
ELEVATION.
DEMOLISH DUPLEX BASKET STRAINER.
DEMOLISH SEAL WATER STATION AND ASSOCIATED PIPING AND SUPPORTS. CAP
2W PIPE THAT PROVIDES WATER TO THE STATION.
CAP AND ABANDON 2W SEAL WATER LINES 6 INCHES ABOVE FLOOR
ELEVATION.
CAP AND ABANDON 3-INCH 3W PIPE 6 INCHES ABOVE FLOOR
ELEVATION.
DEMOLISH 6-INCH AND 8-INCH DWS PIPING IN UTILITY TRENCH. DEMOLISH
TRENCH COVERS AND SUPPORTS. FILL TRENCH WITH CONCRETE, SEE
STRUCTURAL SHEETS.
DEMOLISH 8-INCH DWS PIPE, 1/2-INCH PA PIPE, ASSOCIATED HEAT
TRACING, SUPPORTS AND PRECAST CONCRETE UTILITY TRENCH BETWEEN THE
CAKE STORAGE BUILDING AND DEWATERING BUILDING. BACKFILL AND REPAIR
ROAD SURFACE PER DETAILS 1/C-001 AND 3/C-001.
DEMOLISH POLYMER METERING PUMP, EQUIPMENT SUPPORTS, SUCTION AND
DISCHARGE PIPING AND ASSOCIATED ELECTRICAL/CONTROL EQUIPMENT. CAP
CONNECTION TO UPSTREAM 2-INCH POLS PIPE. DEMOLISH POLYMER DISCHARGE
PIPE BETWEEN PUMP AND CONNECTION POINT TO THE 8-INCH DWS PIPE NEAR
CAKE PUMP 2.
FILL SUMP BENEATH EACH BELT FILTER PRESS WITH CONCRETE. SEE
STRUCTURAL SHEETS.
DEMOLISH WINDOW AND PROVIDE WALL PENETRATION FOR NEW SCREW
CONVEYORS. SEE SHEET S-203.
CORE DRILL FOR NEW 2W LINE. SEE SHEET M-203 FOR ADDITIONAL
DEMOLITION.
RELOCATE PER SHEET D-202.
DEMOLISH FLOOR DRAIN AND SURROUNDING CONCRETE AS NEEDED TO CONNECT
TO EXISTING DRAIN AS SHOWN ON SHEET M-202. SIMILAR FOR EACH BELT
FILTER PRESS.
DEMOLISH POLYMER FEED SYSTEM INCLUDING WETTING UNIT, POLYMER
MIXING/HOLDING TANKS, MIXERS, POLYMER FEED PUMPS, PIPING, CONTROL
PANEL AND ASSOCIATED ELECTRICAL/CONTROL EQUIPMENT.
PROVIDE BLIND FLANGE.
CAP 1/2-INCH PA LINES 6 INCHES ABOVE FLOOR.
CAP AND ABANDON 3-INCH 3W PIPE THAT RUNS BENEATH THE FLOOR SLAB AND
PROVIDES WATER TO WASHWATER BOOSTER PUMP 2. CAP 3W PIPE 6 INCHES
ABOVE FLOOR ELEVATION.
GENERAL NOTES: 1.
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
AM-WRF DEWATERING IMPROVEMENTS PROJECT
DEMOLISH 4-INCH PLUG VALVE FOR CONNECTION TO CLEANOUT SHOWN ON
SHEET M-202. TYPICAL EACH BELT FILTER PRESS.
DEMOLISH COMPRESSED AIR SYSTEM THROUGHOUT THE DEWATERING
BUILDING.
DEMOLISH POLYMER POST DILUTION PANEL. CAP 2W AND 3W SUPPLY 6 INCHES
ABOVE FLOOR. SALVAGE MAGNETIC FLOW METERS AND TURN OVER TO
OWNER.
KEY NOTES CONTINUED:
CONNECTION POINT FOR NEW POLS PIPING.
DEMOLISH MCC 10A AND MCC 10B FOR INSTALLATION OF NEW MCC. SEE MCC
DEMOLITION SHEETS E-005 AND E-006.
DEMOLISH EQUIPMENT PAD.
KEY NOTES CONTINUED:
D-202
1976018.00-D-202.dwg
pw :\\
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
DEWATERING BUILDING HVAC DEMOLITION PLAN
REMOVE FAN AND DUCTING, CAP AND SEAL ROOF OPENING PER DETAIL
20/S-205.
REPLACE UPPER AND LOWER DUCTING, DIFFUSERS, AND EQUIPMENT FOR
WWP-BDB1-AHU-0001. DEMOLISH EXISTING WWP-BDB1-AHU-0001 AND CONCRETE
BASE. GAS SUPPLY TO REMAIN, WITH NEW PIPING TO REPLACEMENT
UNIT.
RELOCATE CONDENSING UNIT AND ASSOCIATED REFRIGERANT PIPING AS SHOWN
ON SHEET M-205.
AT INTERIOR FACE OF LOUVER, PROVIDE BLANK-OFF PANEL ASSEMBLY
CONSISTING OF:
A. 18 GAUGE GALVANNEALED STEEL PLATE (BLACK PAINT FINISH TO
BUILDING EXTERIOR) B. 2-INCH THICK RIGID POLYISOCYANURATE
INSULATION C. 18 GAUGE GALVANNEALED STEEL PLATE (BLACK PAINT FINISH
TO BUILDING INTERIOR.
BLANK-OFF ASSEMBLY SIZE TO MATCH EXISTING LOUVER OPENING, FIELD
VERIFY SIZES. PROVIDE 3" LONG STAINLESS STEEL SELF-TAPPING SCREWS,
ONE AT EACH CORNER, 4" O.C. ELSEWHERE. PROVIDE BACKER ROD AND
SILICONE SEALANT AT PANEL/WALL JOINT AROUND ENTIRE PERIMETER;
SEALANT COLOR TO MATCH ADJACENT CMU.
HOODS AND ASSOCIATED DUCTWORK TO BE REMOVED.
DUCTWORK AND APPURTENANCES TO BE REPLACED.
DEMOLISH AIR COMPRESSOR, AIR DRYER, CONCRETE EQUIPMENT BASES,
COMPRESSED AIR PIPING THROUGHOUT THE DEWATERING BUILDING,
APPURTENANCES AND ASSOCIATED ELECTRICAL EQUIPMENT. SALVAGE AIR
COMPRESSOR AND AIR DRYER AND TURN OVER TO OWNER.
REPLACE EXISTING 36"Wx36"H LOUVER WITH 36"Wx48"H LOUVER.
EXISTING EQUIPMENT TO REMAIN.
REMOVE FAN, ASSOCIATED DUCTWORK AND EQUIPMENT PAD.
REMOVE FAN AND ASSOCIATED DUCTING. ROUTE VENT LINE SHOWN ON M-201
THROUGH EXISTING OPENING AND SEAL PER DETAIL 21/S-205.
KEY NOTES:
1/4"=1'-0"
30 6
3/16"=1'-0"
DEWATERING BUILDING MEZZANINE HVAC DEMOLITION PLAN
1. REPAIR HOLES AND MINOR SURFACE DAMAGE IN CONCRETE FROM
DEMOLITION PER DETAIL S-3060 .
2. METAL ANCHORS AND CUT BARS ASSOCIATED WITH DEMOLITION SHALL BE
BURNED BACK 1-INCH BELOW CONCRETE SURFACE. FILL WITH REPAIR MORTAR
TO MATCH FINISH AND SURFACE ELEVATION OF EXISTING ADJACENT
SURFACE.
3. PULL WIRES BACK FROM EQUIPMENT/DEVICES BEING DEMOLISHED TO
SOURCE. REMOVE EXPOSED CONDUIT, FITTINGS AND ACCESSORIES FROM
DEVICE TO SOURCE UNLESS CONDUIT WILL BE REUSED. CONDUIT EMBEDDED IN
CONCRETE SHALL BE CAPPED AND SEALED.
GENERAL NOTES: 1
D-211
1976018.00-D-211.dwg
pw :\\
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
1/8"=1'-0"
PROVIDE OPENING FOR ACCESS DOOR PER SHEET S-210.
DEMOLISH 8-INCH DWS PIPE AND ASSOCIATED VALVES, HEAT TRACING, PIPE
SUPPORTS AND ANCHORS.
DEMOLISH 8-INCH DWS PIPE, 1/2-INCH PA PIPE, ASSOCIATED HEAT
TRACING, SUPPORTS AND PRECAST CONCRETE UTILITY TRENCH BETWEEN THE
CAKE STORAGE BUILDING AND DEWATERING BUILDING. BACKFILL AND REPAIR
ROAD SURFACE PER DETAILS 1/C-001 AND 3/C-001.
DEMOLISH 4-INCH DWS AND 2-INCH D TO A MINIMUM 1-INCH BELOW THE
CONCRETE SURFACE OF THE INSIDE FACE OF THE CONVEYOR SUMP. FILL PIPE
PENETRATION WITH NON-SHRINK GROUT.
DEMOLISH MONORAIL AND ASSOCIATED BEAM, COLUMN SUPPORTS, AND
ANCHORS.
REMOVE EXISTING PAVING AS NEEDED FOR NEW EQUIPMENT AND ASSOCIATED
CONCRETE SLABS. SEE STRUCTURAL AND MECHANICAL SHEETS.
CORE DRILL FOR NEW 4" D, SEE SHEET M-211. LOCATE TO ACHIEVE NEEDED
DRAIN SLOPE.
DEMOLISH AN APPROXIMATELY 4 FEET HIGH BY 40 FEET LONG BAND OF T-111
SIDING WITH ASSOCIATED WOOD SUPPORT FRAMING AT THE TOP OF THE
EXISTING CONCRETE WALL OF THE EAST BAY OF THE CAKE STORAGE
BUILDING. COORDINATE WITH NEW WORK SHOWN ON SOUTH ELEVATION ON
DRAWING A-211.
KEY NOTES: 1
SEE SPECIFICATION SECTION 01010 FOR CONSTRUCTION SEQUENCING AND
TEMPORARY SOLIDS DEWATERING FACILITIES THAT MUST BE IN PLACE PRIOR
TO INITIATING DEMOLITION WORK.
REPAIR HOLES AND MINOR SURFACE DAMAGE IN CONCRETE FROM DEMOLITION
PER DETAIL S-3060 .
METAL ANCHORS AND CUT BARS ASSOCIATED WITH DEMOLITION SHALL BE
BURNED BACK 1-INCH BELOW CONCRETE SURFACE. FILL WITH REPAIR MORTAR
TO MATCH FINISH AND SURFACE ELEVATION OF EXISTING ADJACENT
SURFACE.
PULL WIRES BACK FROM EQUIPMENT/DEVICES BEING DEMOLISHED TO SOURCE.
REMOVE EXPOSED CONDUIT, FITTINGS AND ACCESSORIES FROM DEVICE TO
SOURCE. CONDUIT EMBEDDED IN CONCRETE SHALL BE CAPPED AND
SEALED.
GENERAL NOTES: 1.
B DOOR
A DOOR
APPLICABLE CODES:
2019 OREGON STRUCTURAL SPECIALTY CODE (OSSC) 2019 OREGON FIRE CODE
(OFC) 2019 OREGON MECHANICAL SPECIALTY CODE (OMSC) 2019 OREGON ZERO
ENERGY READY COMMERCIAL CODE (OZERCC) 2017 OREGON ELECTRICAL
SPECIALTY CODE (OESC) - BASED ON 2017 NFPA 70, NATIONAL ELECTRICAL
CODE 2019 OREGON OSHA REGULATIONS NFPA 820 - STANDARD FOR FIRE
PROTECTION IN
WASTEWATER AND COLLECTION FACILITIES TITLE (18) BUILDING PROVISIONS
OF THE ALBANY CODE
GENERAL NOTES:
1. EXITS: REQUIRED EXIT DOORS SHALL BE 36 INCHES WIDE BY 80-INCHES
HIGH AT A MINIMUM. BASED ON THE OCCUPANCY LOAD, ALL BUILDINGS
REQUIRE A MINIMUM OF ONE EXIT DOOR.
2. INSULATION: PROVIDED IN HEATED AND COOLED AREAS 3. EXIT
ILLUMINATION IS REQUIRED AT ONE-FOOT CANDLE 4. PORTABLE FIRE
EXTINGUISHERS SHALL BE INSTALLED AND MAINTAINED
IN ACCORDANCE WITH OREGON FIRE CODE.
ZONING: HI - HEAVY INDUSTRIAL DISTRICT
BUILDING BUILDING INFORMATION TYPE V B, PER OSSC 602.5,CONSTRUCTION
TYPE
DEWATERING BUILDING
BUILDING: F-1 MODERATE HAZARD FACTORY INDUSTRIAL PER OSSC
306.2
ACTUAL HEIGHT / STORY
HVAC CONDITIONED
OCCUPANCY SEPARATIONS
ACCESSIBILITY NOT REQUIRED PER OSSC SECTIONS 1103.2.9
FIRE PROTECTION REQUIREMENTS (NFPA 820) HYDRANT PROTECTION WITHIN
225' OF STRUCTURE PER TABLE C102.1,
FIRE FLOW (NFPA 820) 2,250 GPM FOR 2 HOURS PER TABLE
B105.1(2)
NONE REQUIRED PER OSSC TABLE 508.4
SINGLE STORY BUILDING, SLAB-ON-GRADE FLOOR, LOAD BEARING CMU WALLS,
METAL ROOF OVER WOOD ROOF FRAMING.
BUILDING ELEMENT FIRE RESISTANCE 0-HOUR RATING AS PER OSSC TABLE
601 FOR TYPE V B CONSTRUCTION
EXTERIOR WALL FIRE RESISTANCE (BASED ON SEPARATION DISTANCE)
0-HOUR RATING AS PER OSSC TABLE 602 FOR TYPE V B CONSTRUCTION
SPRINKLER SYSTEM NOT REQUIRED PER OSSC SECTIONS 903.2.4,
903.3.1.1.1.1 AND 903.3.1.1.1.2
SMOKE DETECTION NOT REQUIRED PER OSSC SECTION 907
SMOKE AND HEAT VENTS NOT REQUIRED PER OSSC SECTION 910.2.1
OCCUPANT LOAD 63 PER OSSC TABLE 1004.5 POLYMER PUMP ROOM (1,400
S.F.) 14 OCCUPANTS (1 EXIT REQUIRED / 1 ACTUAL PER OSSC TABLE
1015.1)
SOLIDS LABORATORY (208 S.F.) 3 OCCUPANTS (1 EXIT REQUIRED / 2
ACTUAL PER OSSC TABLE 1015.1) CONTROL ROOM (224 S.F.) 3 OCCUPANTS
(1 EXIT REQUIRED / 1 ACTUAL PER OSSC TABLE 1015.1)
FIRE ALARM REQUIRED PER NFPA 820
MAXIMUM PATH OF EGRESS TRAVEL 75 FEET PER OSSC TABLE 1006.2.1
VENTILATION REQUIRED PER OSSC SECTION 1202.1
ENERGY CODE (OEESC) INSULATION - ROOF NO CHANGE REQUIRED AT
EXISTING ENVELOPE INSULATION PER OZERCC INSULATION - WALL GLAZING -
U-VALUE
STANDBY POWER (NFPA 820) REQUIRED
NFPA 820 ELECTRICAL CLASSIFICATION
POLYMER STORAGE UNCLASSIFIED MEZZANINE (a) UNCLASSIFIED SCREW PRESS
ROOM (a) UNCLASSIFIED
(a) ROOM TO BE CONTINUOUSLY VENTILATED AT SIX (6) AIR CHANGES/HOUR.
(NOTE: SIX (6) AIR CHANGES/HOUR MINIMUM REQUIRED PER NFPA
820)
CODE SUMMARY
POLYMER STORAGE ROOM (364 S.F.) 4 OCCUPANTS (1 EXIT REQUIRED / 1
ACTUAL PER OSSC TABLE 1015.1)
POLYMER PUMP ROOM (a) UNCLASSIFIED
STORAGE ROOM (80 S.F.) 1 OCCUPANT (1 EXIT REQUIRED / 1 ACTUAL PER
OSSC TABLE 1015.1)
ELECTRICAL ROOM (192 S.F.) 2 OCCUPANTS (1 EXIT REQUIRED / 2 ACTUAL
PER OSSC TABLE 1015.1) SCREW PRESS ROOM (2,762 S.F.) 28 OCCUPANTS
(1 EXIT REQUIRED / 4 ACTUAL PER OSSC TABLE 1015.1)
RESTROOM (80 S.F.) 1 OCCUPANT (1 EXIT REQUIRED / 1 ACTUAL PER OSSC
TABLE 1015.1)
MEZZANINE (896 S.F.) 9 OCCUPANTS (1 EXIT REQUIRED / 1 ACTUAL PER
OSSC TABLE 1015.1)
NO CHANGE REQUIRED AT EXISTING ENVELOPE INSULATION PER OZERCC NO
CHANGE REQUIRED AT EXISTING ENVELOPE INSULATION PER OZERCC
BUILDING BUILDING INFORMATION TYPE V B, PER OSSC 602.5,CONSTRUCTION
TYPE
CAKE STORAGE BUILDING
BUILDING: S-1 MODERATE HAZARD STORAGE PER OSSC 311.2
ACTUAL HEIGHT / STORY
HVAC NOT CONDITIONED
ACCESSIBILITY NOT REQUIRED PER OSSC SECTIONS 1103.2.9
FIRE PROTECTION REQUIREMENTS (NFPA 820)
FIRE FLOW (NFPA 820)
NONE REQUIRED PER OSSC TABLE 508.4
SINGLE STORY BUILDING, SLAB-ON-GRADE FLOOR, LOAD BEARING CMU WALLS,
METAL ROOF OVER WOOD ROOF FRAMING.
BUILDING ELEMENT FIRE RESISTANCE 0-HOUR RATING AS PER OSSC TABLE
601 FOR TYPE V B CONSTRUCTION
EXTERIOR WALL FIRE RESISTANCE (BASED ON SEPARATION DISTANCE)
0-HOUR RATING AS PER OSSC TABLE 602 FOR TYPE V B CONSTRUCTION
SPRINKLER SYSTEM NOT REQUIRED PER OSSC SECTIONS 903.2.4,
903.3.1.1.1.1 AND 903.3.1.1.1.2
SMOKE DETECTION NOT REQUIRED PER OSSC SECTION 907
SMOKE AND HEAT VENTS NOT REQUIRED PER OSSC SECTION 910.2.1
OCCUPANT LOAD 23 PER OSSC TABLE 1004.5 EAST BAY (3,200 S.F.) 11
OCCUPANTS (1 EXIT REQUIRED / 1 ACTUAL PER OSSC TABLE 1015.1)
FIRE ALARM REQUIRED PER NFPA 820
MAXIMUM PATH OF EGRESS TRAVEL 100 FEET PER OSSC TABLE
1006.2.1
VENTILATION REQUIRED PER OSSC SECTION 1202.1
ENERGY CODE (OEESC) INSULATION - ROOF NO CHANGE REQUIRED AT
EXISTING ENVELOPE INSULATION PER OZERCC INSULATION - WALL GLAZING -
U-VALUE
STANDBY POWER (NFPA 820) REQUIRED
NFPA 820 ELECTRICAL CLASSIFICATION CAKE STORAGE UNCLASSIFIED
NO CHANGE REQUIRED AT EXISTING ENVELOPE INSULATION PER OZERCC NO
CHANGE REQUIRED AT EXISTING ENVELOPE INSULATION PER OZERCC
WEST BAY (3,200 S.F.) 11 OCCUPANTS (1 EXIT REQUIRED / 1 ACTUAL PER
OSSC TABLE 1015.1)
HYDRANT PROTECTION WITHIN 225' OF STRUCTURE PER TABLE C102.1,
2,250 GPM FOR 2 HOURS PER TABLE B105.1(2)
4
3
2
1
0
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
Federal Way, WA
A-001
1976018.00-A-001.dwg
pw :\\
AND FIRE EXTINGUISHERSAND FIRE EXTINGUISHERS
(a) ALL ROOMS TO BE CONTINUOUSLY VENTILATED AT 6 AIR CHANGES/HOUR
MINIMUM PER NFPA 820
DOOR SCHEDULE
NO. WIDTH X HEIGHT TYPE MATERIAL MATERIAL HDWRE GROUP
FIRE RATINGHEAD JAMB SILLTHERMAL
2O.H. 12'-0" x 16'-0"
ARI-11692
FFFFFFeFeFeFeFFeFeFFFeFeFeFFFFFFFeFeFFeFeFeFeFFFFeFeFeFFFFFeFFFeFFFeFFFFFFFFFF
ddddddddddddddddddddddddddddeddddddededddeedederarararaaaaaarararararraaaaararraaaaaaaarrraaaaaaaaaraaaaaarraaaaaaaaallllllllllllllllllllllllllllllllll
WaWWaWaWWWWaWWaWaWaWaWaWWaWWaWWaWaWaWaWWWaaWaWaWaWaWWWWaWaWaWWWWaWWaWaWWWWaWaWaWaWWWWWWaaaaaaWaWWWWWWaaaaWaWWaWaWaWWaWWaWaWWaWWWWWWWWWWWW
yyyyyyyyyyyyyyyyyyy,
WWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
17 '-6
TYPICAL NEW LOUVER; SEE ALSO EQUIPMENT SCHEDULES SHEET M-005
NEW KALWALL INSTALLATION - SEE STRUCTURAL FOR DIMENSIONS
SHEET METAL CLOSURE PANEL AT DUCT PENETRATION. SEE ALSO
MECHANICAL
CLOSURE PANEL AT CONVEYOR BELT PENETRATION. SEE ALSO DETAIL
1/S-213
4
3
2
1
0
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
Federal Way, WA
PRPRPRPRPRRRRPRPRRPRPRRRRRRRRPRRRRRRRPRPRPRPRRRRRRRRRRRRPRRPRPRPRRPRPRRPRPRRRRRRPRRRRRPRRRRRRPRRRRRRPRRRPRRRRRRPRRRRRRPRRRRPR
SSESESESESESESSSSSEESESESESSSSSSSSSSESESSSESSSSSSSESESESESESESSSSSSSESESESESSSSSESESSSSESSSSSSSSESESESSSSSESSSSSEESSSSSEESSSEESSESESSESSSESSSEEEESSSSSEESSSSTTTTOTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTT
N
MAMAMAMAMAMAMAMMAMAMAMMAMAMAMAMAAMAMAMAMAAAAAMAMAMAMAMAAMAAAAMAMAMAMAMMAMAMAMAAMAMAAAAMAMMAMAMAMMMAMAMAMAMAMAMMMMAAMAMMMMAAAMAMAMMAMAMMMMAAAMAMMAMAAAMAMAAAMAMAAAAMMMMMAMAAMAAMAAARRRRKRRRRRKRRRRRRRRRRRRRKKRKKKRKRKRKRRRRKKKKKRKRKRKRKRRRRKKKKKRKRKRRRRRRKKKKRKRRRRRRRRRKKRKRKRRRRRRRRRRKRKRKRRRRRRRKRRRRRRRRKRRRRRRRRRRRRRRRRRR
SOIL AND FOUNDATIONS 1. GEOTECHNICAL INVESTIGATIONS FOR DESIGN
PURPOSES FOR THIS PROJECT WERE
MADE BY FOUNDATION ENGINEERING, INC. IN A REPORT DATED MARCH 16,
2020. 2. IN ACCORDANCE WITH THE IBC CHAPTER 18 THE SOILS AT THE
ALBANY-MILLERSBURG
WATER RECLAMATION FACILITY ARE GENERALLY CLASSIFIED AS MEDIUM DENSE
TO VERY DENSE GRAVELLY SILT WITH SAND (ML).
3. THE DESIGN BEARING CAPACITY OF THE SOILS IS 1,500 PSF FOR
FOOTINGS. BEARING CAPACITY OF SOILS ARE FOR DEAD AND LIVE LOADS FOR
FOUNDATIONS. BEARING VALUES MAY BE INCREASED BY ONE-THIRD WHEN
TRANSIENT LOADS SUCH AS WIND OR SEISMIC LOADS ARE INCLUDED.
4. SOILS SHALL BE EXCAVATED TO THE ELEVATIONS INDICATED ON THE
DRAWINGS FOR FOUNDATIONS. THE SUBGRADE SHALL BE PREPARED AS
INDICATED ON THE DRAWINGS AND SPECIFICATIONS AND APPROVED BY THE
GEOTECHNICAL ENGINEER. EXCAVATED MATERIAL SHALL BE REPLACED WITH
STRUCTURAL FILL AS SHOWN ON THE DRAWINGS. FOUNDATIONS SHALL BE
CONSTRUCTED AGAINST UNDISTURBED NATIVE COMPETENT MATERIAL OR
COMPACTED STRUCTURAL FILL.
GENERAL 1. DESIGN AND CONSTRUCTION SHALL CONFORM TO THE 2018
INTERNATIONAL BUILDING
CODE, THE 2019 OREGON STRUCTURAL SPECIALTY CODE, AND THE REFERENCED
BUILDING CODE STANDARDS.
2. THESE NOTES AS WELL AS THE TYPICAL DETAILS APPLY TO ALL PARTS OF
THE PROJECT, UNLESS NOTED OTHERWISE.
3. SHOP DRAWINGS FOR THIS CONTRACT SHALL BE COORDINATED WITH
FAVORABLY REVIEWED EQUIPMENT MANUFACTURER'S DRAWINGS.
4. DIMENSIONS NOTED WITH AN ASTERISK, " * ", ARE TO BE COORDINATED
WITH FAVORABLY REVIEWED SUBMITTAL BY THE EQUIPMENT
MANUFACTURER.
5. STRUCTURAL DETAIL CALLOUTS DENOTED AS S-XXXX SHALL REFER TO THE
STRUCTURAL STANDARD DETAILS.
PERMITS AND INSPECTIONS 1. THE CONTRACTOR IS RESPONSIBLE FOR
OBTAINING ALL PERMITS AND INSPECTIONS
REQUIRED BY THE LOCAL BUILDING INSPECTOR AND AS DESCRIBED IN THE
SPECIFICATIONS.
2. THE CONTRACTOR SHALL SELECT, INSTALL AND MAINTAIN SHORING,
SHEETING, BRACING AND SLOPING AS NECESSARY TO MAINTAIN SAFE
EXCAVATIONS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING FULL
COMPLIANCE WITH 29 CFR PART 1926 OSHA SUBPART P EXCAVATIONS AND
TRENCHES REQUIREMENTS. ALL EARTHWORK SHALL BE PERFORMED IN STRICT
ACCORDANCE WITH APPLICABLE LAW, INCLUDING LOCAL ORDINANCES, AND
APPLICABLE OSHA REQUIREMENTS.
SPECIAL INSPECTIONS AND STRUCTURAL OBSERVATIONS 1. THE CONTRACTOR
SHALL NOTIFY THE ENGINEER 48-HOURS BEFORE PLACEMENT OF
REINFORCING STEEL AND CONCRETE SO THAT THE SUBGRADE OF EXCAVATIONS
MAY BE INSPECTED BY THE GEOTECHNICAL ENGINEER.
2. THE GEOTECHNICAL ENGINEER SHALL VERIFY BACKFILL MATERIAL AND
BACKFILLING PROCEDURES AND PROVIDE SOIL COMPACTION TESTS.
3. STRUCTURAL OBSERVATION SHALL BE PROVIDED BY THE DESIGN
ENGINEER(S) OF RECORD OR THEIR AUTHORIZED REPRESENTATIVES IN
ACCORDANCE WITH IBC 2018, SECTION 1704. STRUCTURAL OBSERVATION
SHALL CONSIST OF SITE VISITS AT INTERVALS APPROPRIATE TO THE STAGE
OF CONSTRUCTION TO OBSERVE CONSTRUCTION IN PROGRESS AND REVIEW OF
TESTING AND INSPECTION REPORTS FOR GENERAL COMPLIANCE WITH THE
CONSTRUCTION DOCUMENTS RELATING TO THE STRUCTURAL WORK AND THE
NONSTRUCTURAL COMPONENTS AND EQUIPMENT ANCHORAGE.
4. SPECIAL INSPECTION IN ACCORDANCE WITH IBC 2018, SECTION 1704,
SHALL BE REQUIRED AS INDICATED IN THE SPECIAL INSPECTION AND
TESTING SCHEDULE ON NEXT SHEET.
2. CONCRETE CONSTRUCTION SHALL CONFORM TO ACI 318-14 INCLUDING BAR
BENDS AND HOOKS, UNLESS DETAILED OTHERWISE.
3. SUBMIT CONCRETE AND MASONRY LIFT DRAWINGS SHOWING THE LOCATION
OF CONSTRUCTION JOINTS, WATERSTOPS AND OTHER TYPES OF JOINTS OTHER
THAN SPECIFIED OR SHOWN ON THE DRAWINGS FOR FAVORABLE REVIEW BY THE
ENGINEER BEFORE START OF WORK ON FORMS, REINFORCING STEEL OR
PLACING CONCRETE. ANY ADDITIONAL VERTICAL OR HORIZONTAL
CONSTRUCTION JOINTS SHALL HAVE A STANDARD KEYWAY AND SHALL BE
FAVORABLY REVIEWED BY THE ENGINEER. REFER TO SPECIFICATIONS AND
TYPICAL DETAILS FOR ADDITIONAL INFORMATION. CONSTRUCTION JOINTS
SHALL BE ROUGHENED TO 1/4-INCH AMPLITUDE.
4. OPENINGS, PIPE SLEEVES, CONDUITS, INSERTS AND OTHER EMBEDDED
ITEMS SHALL BE IN PLACE BEFORE CONCRETE IS PLACED. IT IS THE
CONTRACTOR'S RESPONSIBILITY TO COORDINATE ARCHITECTURAL, CIVIL,
MECHANICAL, ELECTRICAL, LANDSCAPING, HVAC, PLUMBING,
INSTRUMENTATION AND OTHER PLANS FOR ITEMS REQUIRING SLEEVES AND
EMBEDMENTS IN CONCRETE WHICH ARE NOT INDICATED OR SHOWN ON
STRUCTURAL DRAWINGS. NO PIPES OR SLEEVES SHALL PASS THROUGH
STRUCTURAL MEMBERS (UNLESS SHOWN ON STRUCTURAL DRAWINGS).
COORDINATE WITH EQUIPMENT MANUFACTURERS DRAWINGS FOR ANCHORING
DEVICES.
5. UNLESS OTHERWISE NOTED, ALL EXPOSED EDGES AND CORNERS SHALL BE
CHAMFERED 3/4-INCH. INTERIOR FLOOR SLABS AND EXTERIOR SIDEWALKS
SHALL HAVE TOOLED 3/8-INCH RADIUS CONSTRUCTION JOINT.
6. EACH FACE CONCRETE SHALL BE REINFORCED A MINIMUM OF NO. 5 BARS
AT 12-INCHES EACH WAY.
7. CONCRETE ENCASE ALL PIPES AND CONDUITS UNDER CONCRETE SLABS AND
FOOTINGS
REINFORCING STEEL 1. REINFORCING BARS SHALL BE ASTM A615-GRADE 60.
2. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185. 3. ARRANGEMENT
AND DETAILING OF REINFORCING STEEL, INCLUDING BAR SUPPORTS
AND
SPACERS, SHALL BE IN ACCORDANCE WITH THE LATEST ACI 315 DETAILING
MANUAL. 4. REINFORCING SHALL LAP IN ACCORDANCE WITH THE CONCRETE
REINFORCEMENT SPLICE
TABLE, UNLESS OTHERWISE SHOWN. WHEN BARS OF DIFFERENT SIZE LAP TO
EACH OTHER, SPLICE LENGTH FOR THE SMALLER BAR CAN BE USED. DOWELS
SHALL HAVE THE SAME SIZE AND SPACING AS THAT OF THE REINFORCING
STEEL THEY ARE SPLICED AND SHALL HAVE A MINIMUM LAP AS NOTED ABOVE.
BAR SPLICES SHALL BE STAGGERED.
5. HOOK REINFORCING BARS INTERUPTED BY OPENINGS. 6. NO WELDING OF
REINFORCING BARS SHALL BE PERMITTED, UNLESS APPROVAL IN
WRITING IS OBTAINED FROM THE ENGINEER PRIOR TO CONSTRUCTION. 7.
DIMENSIONS TO REINFORCING ARE TO BAR CENTERLINES, UNLESS NOTED
OTHERWISE
BAR COVER IS CLEAR DISTANCE BETWEEN THE BAR AND THE CONCRETE
SURFACE. UNLESS NOTED OR SHOWN OTHERWISE BAR COVER FOR REINFORCING
STEEL SHALL BE AS FOLLOWS:
FOOTINGS AND BASE SLABS: FORMED SURFACES AND BOTTOMS ON CONCRETE
WORK MAT 2-INCH TOP SURFACES EXPOSED TO EARTH, WATER, OR WEATHER
2-INCH BOTTOMS AND SIDES IN CONTACT WITH EARTH 3-INCH
SUSPENDED SLABS: FORMED SURFACES EXPOSED TO EARTH, WATER, OR
WEATHER 2-INCH TOP AND BOTTOM BARS DRY CONDITION 1-INCH
BEAMS AND COLUMNS: DRY CONDITIONS:
STIRRUPS, SPIRALS, AND TIES 1 1/2-INCH PRINCIPAL REINFORCEMENT
2-INCH
EXPOSED TO EARTH, WATER, OR WEATHER: STIRRUPS, SPIRALS, AND TIES
2-INCH PRINCIPAL REINFORCEMENT 2 1/2-INCH
WALLS: LESS THAN 12-INCHES THICK 1 1/2-INCH 12 TO 16-INCHES THICK
2-INCH OVER 16 INCHES THICK 2 1/2-INCH
CONCRETE: 1. CEMENT SHALL BE ASTM C150 TYPE II FOR ALL STRUCTURES.
CONCRETE
SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH (PSI) AS NOTED IN
THE TABLE BELOW AND AS FURTHER DEFINED IN THE SPECIFICATIONS:
STRUCTURAL STEEL: 1. UNLESS OTHERWISE NOTED, STRUCTURAL STEEL SHALL
CONFORM TO ASTM
A36. W- AND WT- SHAPES SHALL CONFORM TO ASTM A992. PLATES
CONNECTING TO W- AND WT- SHAPES SHALL CONFORM TO ASTM A572 GRADE
50. HOLLOW STRUCTURAL SECTIONS (HSS) SHALL CONFORM TO ASTM A500
GRADE B. STEEL PIPE SHALL CONFORM TO ASTM A53 TYPE E OR S.
2. ALL STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED BY AN AISC
CERTIFIED FABRICATOR IN CONFORMANCE WITH THE LATEST AISC
SPECIFICATION PARTS 1 THRU 4 AND THE "SPECIFICATION FOR STRUCTURAL
STEEL BUILDINGS".
3. CONNECTIONS AND BOLTS SHALL CONFORM TO THE AISC ALLOWABLE STRESS
DESIGN SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490
BOLTS. CONNECTIONS SHALL USE ASTM A325-X BOLTS UNLESS NOTED
OTHERWISE. PROVIDE WASHERS AT ALL CONNECTIONS WITH OVERSIZE OR
SHORT SLOTTED HOLES.
4. WELD ELECTRODES SHALL CONFORM TO AWS A5.1 OR A5.5 E70XX
ELECTRODES. WELDING SHALL BE DONE BY CERTIFIED WELDERS. WELDING
SHALL USE ONLY APPROVED ELECTRODES. WELDING SHALL CONFORM TO THE
PROVISIONS OF THE LATEST STRUCTURAL WELDING CODE (AWS D1.1).
5. UNLESS NOTED OTHERWISE, STRUCTURAL STEEL COMPONENTS AND
CONNECTIONS SHALL BE PAINTED OR PROTECTIVE COATED IN ACCORDANCE
WITH THE SPECIFICATIONS.
6. SHOP PRIME FOLLOWING FABRICATION PER SPECIFICATION 09900. FIELD
PAINT STRUCTURAL STEEL FOLLOWING FIELD INSTALLATION PER
SPECIFICATION 09900.
LOADING CRITERIA 1. MINIMUM LOADING REQUIREMENTS PER CHAPTER 16 OF
THE 2019 OSSC. 2. DEAD LOAD: AS CALCULATED 3. LIVE LOADS:
FIXED STAIRWAYS & EXIT-WAYS 100 PSF UNIFORM, 300 LBS PER TREAD
HANDRAILS, GUARDRAILS AND GRAB BARS 50 PLF AT TOP RAIL, 200 LBS
POINT GRATING, CHECKERED PLATE, ACCESS HATCHES EQUAL TO FLOOR LIVE
LOAD, H20 RATED AT
VEHICULAR ACCESS LOCATIONS 4. WIND LOAD:
BASIC WIND SPEED, V 104 MPH BASIC WIND SPEED, VASD 80 MPH EXPOSURE
C
5. SNOW LOAD: IMPORTANCE FACTOR, I 1.10 BASIC GROUND SNOW LOAD, Pg
10 PSF MINIMUM BALANCED ROOF SNOW LOAD, Pm 22 PSF
6. SEISMIC LOAD: RISK CATEGORY III SEISMIC IMPORTANCE FACTOR, Ie
1.25 SEISMIC IMPORTANCE FACTOR, Ip 1.50 SITE CLASS D SITE
COEFFICIENT SS 0.80 g SITE COEFFICIENT S1 0.42 g SEISMIC DESIGN
RESPONSE PARAMETER SDS 0.63 g SEISMIC DESIGN RESPONSE PARAMETER SD1
0.44 g SEISMIC DESIGN CATEGORY D SITE COEFFICIENT Fa 1.18 SITE
COEFFICIENT Fv 1.58 LONG PERIOD TRANSITION PERIOD, TL 16 S
CAKE STORAGE FACILITY SEISMIC DESIGN: EQUIVALENT LATERAL FORCE
PROCEDURE PER ASCE 7-10 CH. 12.8
RETROFIT LATERAL FORCE-RESISTING SYSTEM: LIGHT-FRAME WOOD SHEAR
WALLS AT CENTER WALL IN NORTH-SOUTH DIRECTION
DEFLECTION AMPLIFICATION FACTOR, Cd 4.5 RESPONSE MODIFICATION
COEFFICIENT, R 7.0 OVERSTRENGTH FACTOR, 2.5 SEISMIC RESPONSE
COEFFICIENT, Cs 0.11 SEISMIC BASE SHEAR, V 7.0 KIPS (LRFD)
EXISTING LATERAL FORCE RESISTING SYSTEM : ORDINARY CONCENTRIC
BRACED FRAME ACTING AT OUTER WALLS IN BOTH DIRECTIONS
DEFLECTION AMPLIFICATION FACTOR, Cd 3.25 RESPONSE MODIFICATION
COEFFICIENT, R 3.25 OVERSTRENGTH FACTOR, 2.0 SEISMIC RESPONSE
COEFFICIENT, Cs 0.25 SEISMIC BASE SHEAR, V 31 KIPS (EAST-WEST),
15.5 KIPS
(NORTH-SOUTH) (LRFD)
OF STATE HIGHWAY TRANSPORTATION OFFICIAL
AB AGGREGATE BASE, ANCHOR BOLT ACI AMERICAN CONCRETE
INSTITUTE ADDIT ADDITIONAL ADJ ADJACENT AISC AMERICAN INSTITUTE
OF
STEEL CONSTRUCTION AISI AMERICAN IRON AND
STEEL INSTITUTE AITC AMERICAN INSTITUTE OF
TIMBER CONSTRUCTION ALUM ALUMINUM ALT ALTERNATE ANSI AMERICAN
NATIONAL STANDARDS
INSTITUTE APA AMERICAN PLYWOOD
TESTING AND MATERIALS ASME AMERICAN SOCIETY OF
MECHANICAL ENGINEERS AWS AMERICAN WELDING SOCIETY AWWA AMERICAN
WATER WORKS
ASSOCIATION
B/ BOTTOM OF BB(S) BEARING BAR(S) BLKG BLOCKING BLDG BUILDING BM
BEAM BM-1 BEAM MEMBER 1 BN BOUNDARY NAILING BOT BOTTOM BP BASE
PLATE BS BOTH SIDES BTWN BETWEEN
C CHANNEL CALC'S CALCULATIONS CC,C/C CENTER-TO-CENTER CIP CAST IN
PLACE CJ CONSTRUCTION JOINT CJP COMPLETE JOINT PENETRATION
CENTERLINE CLSM CONTROLLED LOW STRENGTH
MATERIAL CLR CLEAR CNJ CONTROL JOINT COL COLUMN CONC CONCRETE CONN
CONNECTION CONST CONSTRUCTION CONT CONTINUOUS
DBL DOUBLE DIA DIAMETER DIAG DIAGONAL DIM DIMENSION DL DEAD LOAD DN
DOWN DWG(S) DRAWINGS
(E) EXISTING EA EACH EF EACH FACE EL ELEVATION ELEC ELECTRICAL
EMBED EMBEDMENT EN EDGE NAILING EQ EQUAL EQUIP EQUIPMENT ES EACH
SIDE EW EACH WAY EXP EXPANSION EXT EXTERIOR
(F) FUTURE FD FLOOR DRAIN FF FINISH FLOOR FIN FINISH FLR FLOOR FN
FIELD NAILING FNDN FOUNDATION FRP FIBERGLASS REINFORCED
PLASTIC FS FAR SIDE FT FOOT/FEET FTG FOOTING
GA GAGE/GAUGE GALV GALVANIZED GLB GLULAM BEAM
HDG HOT DIP GALVANIZE(D) H.M. HOLLOW METAL HORIZ HORIZONTAL HSS
HOLLOW STRUCTURAL SECTION HT HEIGHT HWL HIGH WATER LEVEL
IBC INTERNATIONAL BUILDING CODE ICC INTERNATIONAL CODE COUNCIL IN
INCH INT INTERIOR
JT JOINT
KIP 1,000 POUNDS KSI KIPS PER SQUARE INCH
L,∠ ANGLE LB(S) POUNDS LB/SF POUND(S) PER SQUARE FOOT LL LIVE LOAD
LLH LONG LEG HORIZONTAL LLV LONG LEG VERTICAL LLBB LONG LEG
BACK-TO-BACK LONGIT LONGITUDINAL LT LIGHT LW LIGHT WEIGHT
MATL MATERIAL MAX MAXIMUM MB MACHINE BOLT MC MOISTURE CONTENT MC
MISCELLANEOUS CHANNEL MECH MECHANICAL MIN MINIMUM MISC
MISCELLANEOUS MSE MECHANICALLY STABILIZED
EARTH
N/A NOT APPLICABLE (N) NEW NDT NON-DESTRUCTIVE TEST(ING) NFPA
NATIONAL FIRE PROTECTION
ASSOCIATION NIC NOT IN CONTACT
NO. NUMBER NOM NOMINAL NS NEAR SIDE NSG NON-SHRINK GROUT NTS NOT TO
SCALE
OC ON CENTERS OD OUTSIDE DIAMETER OH OPPOSITE HAND, OVERHEAD
OPNG(S) OPENING(S) OPP OPPOSITE OSHA OCCUPATIONAL SAFETY AND
HEALTH ASSOCIATION
PER PERIODIC PEMB PRE-ENGINEERED METAL
BUILDING PL PLATE PLF POUND PER LINEAL FOOT PP PARTIAL PENETRATION
PSF POUND PER SQUARE FOOT PSI POUND PER SQUARE INCH PT(S) POINT(S)
PT PRESSURE TREATED
R, RAD RADIUS RECT RECTANGLE, RECTANGULAR REINF REINFORCING, -MENT
REQ'D REQUIRED
SCH SCHEDULE SF SQUARE FOOT SHT SHEET SIM SIMILAR SLBB SHORT LEGS
BACK-TO-BACK SLH SHORT LEG HORIZONTAL SLV SHORT LEG VERTICAL SMS
SHEET METAL SCREW SPEC(S) SPECIFICATION(S) SQ SQUARE SS STAINLESS
STEEL SSD SATURATED SURFACE DRY STAG STAGGER STD STANDARD STIFF
STIFFENER STL STEEL STRUC STRUCTURE SUSP SUSPENDED SYM
SYMMETRICAL
T/ TOP OF T&B TOP AND BOTTOM TS STRUCTURAL TUBING TYP
TYPICAL
UON UNLESS OTHERWISE NOTED UT ULTRASONIC TESTING
VERT VERTICAL VIF VERIFY IN FIELD
W/ WITH W/O WITHOUT W, WF WIDE FLANGE WCLIB WEST COAST LUMBER
INSPECTION BUREAU WP WORK POINT WSTP WATERSTOP WT WEIGHT,
STRUCTURAL TEE WALL THICKNESS WWF WELDED WIRE FABRIC
YD YARD
DEFERRED SUBMITTALS IN ACCORDANCE WITH IBC SECTION 107.3.4.1
SUBMITTAL DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED
TO THE ARCHITECT OR ENGINEER OF RECORD WHO SHALL REVIEW THEM AND
FORWARD THEM TO THE BUILDING OFFICIAL WITH A NOTATION INDICATING
THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND THAT
THEY HAVE BEEN FOUND TO BE IN GENERAL CONFORMANCE WITH THE DESIGN.
THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL DESIGN
AND SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
OFFICIAL. THE FOLLOWING ITEMS WILL BE DEFINED AS DEFERRED SUBMITTAL
ITEMS:
1. SEISMIC ANCHORAGE FOR ALL MECHANICAL EQUIPMENT AND ARCHITECTURAL
COMPONENTS WHERE ANCHORAGE NOT SHOWN ON CONTRACT DRAWINGS. SEE
SECTION 01190.
2. SUPPORTS AND ANCHORAGE FOR PIPING AND CONDUIT LESS THAN 6 INCHES
IN DIAMETER.
3. CONVEYOR SUPPORTS AND ANCHORAGE. 4. SCREW PRESS AND FLOCCULATION
TANK SUPPORTS AND ANCHORAGE.
STRUCTURAL GENERAL NOTES STRUCTURAL ABBREVIATIONS
GOVERNING CODES
E 2,500 MISC SITE WORK
JDS
JDS
DEC
S-001
1976018.00-S-001.dwg
pw :\\
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
SPECIAL INSPECTIONS 1. GENERAL: PROVIDE STRUCTURAL TESTS AND
SPECIAL INSPECTIONS IN ACCORDANCE WITH CHAPTER 17
OF THE 2018 INTERNATIONAL BUILDING CODE AND 2019 OREGON STRUCTURAL
SPECIALTY CODE. STRUCTURAL TESTS AND SPECIAL INSPECTIONS SHALL
GOVERN THE QUALITY, WORKMANSHIP AND REQUIREMENTS FOR MATERIALS
COVERED. MATERIALS OF CONSTRUCTION AND TESTS SHALL CONFORM TO THE
APPLICABLE STANDARDS LISTED IN THE REFERENCED BUILDING CODE.
2. APPROVED AGENCIES: THE OWNER (OR THE REGISTERED DESIGN
PROFESSIONAL IN RESPONSIBLE CHARGE ACTING AS THE OWNER'S AGENT)
SHALL EMPLOY ONE OR MORE APPROVED AGENCIES TO PERFORM SPECIAL
INSPECTIONS DURING CONSTRUCTION ON THE TYPES OF WORK LISTED. WHERE
THE TERMS APPROVED AGENCY ARE NOTED THE ENGINEERS OF RECORD
INVOLVED IN THE DESIGN OF THE PROJECT MAY ACT AS THE APPROVED
AGENCY.
3. ACCESS: MAINTAIN ACCESS AND EXPOSURE TO WORK FOR WHICH SPECIAL
INSPECTION IS REQUIRED UNTIL COMPLETION OF THE REQUIRED SPECIAL
INSPECTIONS.
4. REPORTING REQUIREMENTS: SPECIAL INSPECTORS SHALL KEEP RECORDS OF
INSPECTIONS. DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE
ATTENTION OF THE CONTRACTOR FOR CORRECTION. IF THEY ARE NOT
CORRECTED, THE DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF
THE BUILDING OFFICIAL AND TO THE REGISTERED DESIGN PROFESSIONAL IN
RESPONSIBLE CHARGE PRIOR TO THE COMPLETION OF THAT PHASE OF THE
WORK.
5. INSPECTION OF FABRICATORS: WHERE FABRICATION OF STRUCTURAL
LOAD-BEARING MEMBERS AND ASSEMBLIES IS BEING PERFORMED ON THE
PREMISES OF A FABRICATOR'S SHOP, THE SPECIAL INSPECTOR SHALL VERIFY
THAT THE FABRICATOR MAINTAINS DETAILED FABRICATION AND QUALITY
CONTROL PROCEDURES THAT PROVIDE A BASIS FOR INSPECTION CONTROL OF
THE WORKMANSHIP AND THE FABRICATOR'S ABILITY TO CONFORM TO APPROVED
CONSTRUCTION DOCUMENTS AND REFERENCED STANDARDS, UNLESS THE WORK IS
DONE ON THE PREMISES OF A FABRICATOR REGISTERED AND APPROVED TO
PERFORM SUCH WORK WITHOUT SPECIAL INSPECTION.
6. STATEMENT OF SPECIAL INSPECTION: THIS SHEET SHALL BE CONSIDERED
THE STATEMENT OF SPECIAL INSPECTIONS.
7. CONTRACTOR RESPONSIBILITY: CORRECT DISCREPANCIES IDENTIFIED IN
THE SPECIAL INSPECTION WHERE WORK WAS NOT COMPLETED IN CONFORMANCE
WITH CONTRACT DOCUMENTS.
8. STRUCTURAL OBSERVATIONS: STRUCTURAL OBSERVATIONS SHALL BE
PROVIDED FOR SEISMIC RESISTANCE AND WIND REQUIREMENTS. MAINTAIN
ACCESS AND EXPOSURE TO WORK FOR STRUCTURAL OBSERVATIONS. STRUCTURAL
OBSERVATIONS SHALL BE PROVIDED AT THE FOLLOWING EXTENT: a. PRIOR TO
CLOSING WOOD SHEAR WALL WITH SHEATHING AT CAKE STORAGE
FACILITY.
9. STRUCTURAL STEEL: SPECIAL INSPECTION FOR STRUCTURAL STEEL SHALL
BE IN ACCORDANCE WITH THE REQUIREMENTS OF AISC 360, AISC 341, AND
THE BELOW TABLES.
10. STEEL CONSTRUCTION OTHER THAN STRUCTURAL STEEL: SPECIAL
INSPECTION FOR STEEL CONSTRUCTION OTHER THAN STRUCTURAL STEEL SHALL
BE IN ACCORDANCE WITH THE BELOW TABLE.
11. CONCRETE CONSTRUCTION: SPECIAL INSPECTIONS AND VERIFICATIONS
FOR CONCRETE CONSTRUCTION SHALL BE AS REQUIRED BY THE BELOW TABLE.
SPECIAL INSPECTION IS NOT REQUIRED FOR CONCRETE PATIOS, DRIVEWAYS
AND SIDEWALKS, ON GRADE.
12. MASONRY STRUCTURES: SPECIAL INSPECTION FOR MASONRY STRUCTURES
SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF TMS 402 AND TMS 602
AND THE BELOW TABLE. SUBMIT DOCUMENTATION THAT THE SPECIAL
INSPECTION TESTING AGENCY OR TESTING LABORATORY FOR MASONRY
STRUCTURES HAVE THE ABILITY TO COMPLY WITH THE REQUIREMENTS OF ASTM
C1093.
13. ARCHITECTURAL COMPONENTS SPECIAL INSPECTION FOR SEISMIC
RESISTANCE: PERIODIC SPECIAL INSPECTION IS REQUIRED DURING THE
ERECTION AND FASTENING OF EXTERIOR CLADDING, INTERIOR AND EXTERIOR
NONBEARING WALLS AND INTERIOR AND EXTERIOR VENEER.
14. MECHANICAL AND ELECTRICAL COMPONENTS INSPECTION FOR SEISMIC
RESISTANCE: PERIODIC SPECIAL INSPECTION IS REQUIRED DURING THE
INSTALLATION AND ANCHORAGE OF THE FOLLOWING SYSTEMS: a. DUCTWORK
AND PIPING SYSTEMS DESIGNED TO CARRY HAZARDOUS MATERIALS AND
THEIR
ASSOCIATED MECHANICAL UNITS.
15. SEISMIC CERTIFICATION OF NON-STRUCTURAL COMPONENTS: VERIFY THAT
THE LABEL, ANCHORAGE OR MOUNTING CONFORMS TO THE CERTIFICATE OF
COMPLIANCE.
16. DESIGNATED SEISMIC SYSTEM: WOOD SHEAR WALL AT CAKE STORAGE
FACILITY.
REQUIRED VERIFICATION AND INSPECTION OF WOOD CONSTRUCTION
SPECIAL
INSPECTION REQUIRED
VERIFICATION AND INSPECTION CONT PERIODIC REFERENCED STANDARD IBC
REF
YES 1. NAILING, BOLTING, ANCHORING AND OTHER FASTENING OF SHEAR
WALLS AND DIAPHRAGMS. -- X --
1705.12
YES 1. INSPECTION OF REINFORCING STEEL, INCLUDING PRE-STRESSING
TENDONS, AND VERIFY PLACEMENT
-- X ACI 318: CH. 20, 25.2, 25.3, 26.6.1-26.6.3
1908.4
a. VERIFY WELDABILITY OF REINFORCING BARS OTHER THAN ASTM
A706
-- -- AWD D1.4 ACI 318: 26.6.4
--b. INSPECT SINGLE-PASS FILLET WELDS, MAX 5/16"
c. INSPECT ALL OTHER WELDS
YES 3. INSPECT ANCHORS CAST IN CONCRETE -- X ACI 318:
17.8.2 --
YES
a. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED
ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS -- X ACI 318
17.8.2.4 -- b. MECHANICALLY ANCHORS AND ADHESIVE ANCHORS NOT
DEFINED IN 4.a
YES 5. VERIFYING USE OF REQUIRED DESIGN MIX -- X
ACI 318:Ch 19.26.4.3,
YES
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR STRENGTH
TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE
TEMPERATURE OF THE CONCRETE
X --
YES 7. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER
APPLICATION TECHNIQUES.
X -- ACI 318: 26.5 1908.6, 1908.7, 1908.8
YES 8. VERIFY MAINTENANCE OF SPECIAL CURING TEMPERATURE AND
TECHNIQUES.
-- X ACI 318: 26.5.3-26.5.5 1908.9
9. INSPECTION OF PRE-STRESSED CONCRETE FOR:
NO a. APPLICATION OF PRE-STRESSING FORCE. X --
ACI 318: 26.10
NO b. GROUTING OF BONDED PRE-STRESSING TENDONS X -- --
NO 10. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS -- X ACI
318:26.9 --
NO
11. VERIFICATION OF IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING
OF TENDONS IN POST-TENSIONED CONCRETE AND PRIOR TO REMOVAL OF
SHORES AND FORMS FROM BEAMS AND STRUCTURAL SLABS.
-- X ACI 318: 26.11.2 --
YES 12. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF THE
CONCRETE MEMBER BEING FORMED.
-- X ACI 318:
S-002
1976018.00-S-002.dwg
pw :\\
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
AM-WRF DEWATERING IMPROVEMENTS PROJECT
NOTES: 1. THE SPLICE LENGTH TABLE IS SPECIFIC TO TENSION
DEVELOPMENT AND
TENSION LAP SPLICE LENGTHS FOR WALLS, SLABS AND FOOTINGS DETERMINED
IN ACCORDANCE WITH ACI 318-14 CHAPTER 25, ACI 350-06 CHAPTER 12,
AND THE CRITERIA IN THIS DETAIL. CONTACT THE EOR FOR ANY
DISCREPANCIES TO THE CRITERIA IN THIS DETAIL.
2. LAP SPLICE LENGTHS ARE CLASS B LAPS, IN INCHES, FOR GRADE 60
REINF IN NORMAL-WEIGHT CONC WITH f'c ≥ 3,000 PSI.
3. OC SPACING OF REINF SHALL BE > TWICE THE CONC COVER PLUS ONE
BAR DIA. 4. TOP BARS ARE HORIZ BARS WITH > 12" OF CONC CAST
BELOW BARS. 5. FOR EPOXY-COATED REINF OR LIGHTWEIGHT CONC, CONTACT
THE EOR FOR
LAP SPLICE LENGTHS. 6. FOR BARS OF DIFFERENT SIZES, THE LAP SPLICE
LENGTHS OF THE SMALLER
BAR SHALL BE USED. 7. STAGGER LAPS A DISTANCE OF ONE-HALF THE
SPLICE LENGTH, UON.
LAP SPLICE LENGTH FOR REINFORCING BARS IN WALLS, SLABS & FTNGS
(INCHES)
IMPERIAL [SOFT METRIC] BAR SIZE COVER=1.00 IN. COVER=2.00
IN.COVER=1.50 IN.
TOP4 OTHER TOP 4 OTHER TOP 4 OTHER #3 [#10] 17 13 17 13 17 13 #4
[#13] 23 17 23 17 23 17
222822282633#5 [#16] #6 [#19] 46 35 34 26 34 26
384943555774#7 [#22] #8 [#25] 93 72 70 54 56 43
5369668687113#9 [#29] #10 [#32] 137 106 105 81 85 66 #11 [#36] 162
125 125 97 102 79
SCALE: NTS REV 00
S-3010CONCRETE REBAR LAP SPLICE
RECOMMENDED END HOOK DIMENSIONS
BAR SIZE D 180 ° HOOKS 90° HOOKS A or G J A or G
#3 0'-2 1/4" 0'-5" 0'-3" 0'-6" #4 0'-3" 0'-6" 0'-4" 0'-8" #5 0'-3
3/4" 0'-7" 0'-5" 0'-10" #6 0'-4 1/2" 0'-8" 0'-6" 1'-0" #7 0'-5 1/4"
0'-10" 0'-7" 1'-2" #8 0'-6" 0'-11" 0'-8" 1'-4" #9 0'-9 1/2" 1'-3"
0'-11 3/4" 1'-7" #10 0'-10 3/4" 1'-5" 1-'1 1/4" 1'-10" #11 1'-0"
1'-7" 1'-2 3/4" 2'-0"
SCALE: NTS S-3020REINFORCING HOOKS
REV 00
NOTES: 1. SEE SPECIFICATIONS FOR SEALANT, BACKER ROD, AND JOINT
FILLER
MATERIAL REQUIREMENTS.
JOINT SEALANT
BACKER ROD
ADJ WALL
NOTES: 1. SEE PLANS FOR CURB LOCATION AND DIMENSIONS.
ROUGH CJ
#3@12" UON
SCALE: 1-1/2" = 1'-0" S-3320CURB
REV 00
NOTES: 1. PLACE ALL EQUIPMENT ON CONCRETE PADS (UON). 2. SEPARATE
ALL STEEL SURFACES BEARING ON CONC BY MINIMUM 1/4" THICK
GROUT LAYER. 3. FOR INSTALLATION AT EXISTING SLABS, THE CONTRACTOR
SHALL LOCATE
AND AVOID DRILLING THRU EXISTING REINFORCING STEEL. 4. THE MAXIMUM
OF 8 TIMES THE BAR Ø OR 3" LESS THAN THE SLAB THICKNESS.
EPOXY ADHESIVE DOWEL ALL AROUND: #3@12" EW, H < 8" #4@12" EW, 8"
≤ H ≤ 12" #5@12" EW, H > 12"
#3@12" EW, H < 8" #4@12" EW, 8" ≤ H ≤ 12" #5@12" EW, H >
12"
ROUGHEN CJ
3/4" CHAMFER VERTICAL EDGES (TYP)
EQUIP BASEPLATE SEE NOTE 2
SCALE: NTS S-3832EQUIP PAD
CONC PAD, PIER OR WALL TO BE DEMOLISHED PER PLANS
(E) SLAB OR WALL TO REMAIN
1" MIN TYP
CHIP OUT CONC AND GRIND REINFORCING 1" FROM FACE
SAWCUT AROUND, DO NOT OVERSAW AT CORNERS
SCALE: 1-1/2" = 1'-0" S-3060CONCRETE REPAIR
REV 00 AT DEMOLITION
SUPPORT MATERIAL SCHEDULE
GRATING FRAME ANGLE ANCHOR STRAPS GALV STEEL GALV STEEL STEEL
STAINLESS STAINLESS STEEL ALUMINUM STAINLESS STEEL
FIBERGLASS STAINLESS STEEL
STRAP ANCHOR 1/4"x1-1/2" @ 18" CC AND 12" MAX FROM CORNER (MIN 2
PER MEMBER)
SIZE OR CUT VERT LEG FLUSH W/ T/ GRATE
1/4"
GRATING MATERIAL, THICKNESS, AND EXTENTS PER PLANS
2"
REV 00 EMBEDDED ANGLE
CONCRETE PAD SCHEDULE1
PAD WIDTH "W" LENGTH "L" THICK "T" "H" REINF ODOR CONTROL UNIT
14'-0" 19'-6" 16" 4" #6@10" T&B EA WAY SCREW PRESS ROOM
EXHAUST FAN 4'-8" 6'-0" 10" 3" #4@12" T&B EA WAY
MAKEUP AIR UNIT 11'-4" 9'-4" 12" 4" #5@10" T&B EA WAY
NOTES: 1. COORDINATE ALL DIMENSIONS WITH FAVORABLY REVIEWED
EQUIPMENT
ANCHORAGE AND INSTALLATION SHOP DRAWING. 2. EQUIPMENT BASEPLATE
SHALL BE UNDERLAIN BY A MINIMUM 1/4" NON-SHRINK
GROUT. 3. FOR EQUIPMENT PADS INSTALLED ON SLABS SEE S-3831 .
T
TYP REINF w/ STD HOOKS EA WAY
ADJACENT GRADE
SCALE: NTS REV 00
S-3342EQUIPMENT SLAB HEAVY EXTERIOR
NOTES: 1. PLACE ALL EQUIPMENT ON CONCRETE PADS (UON). 2. SEPARATE
ALL STEEL SURFACES BEARING ON CONC BY 1/4" (MIN) THICK
GROUT LAYER. 3. INSTALL THE MAX OF STANDARD HOOK DEVELOPMENT LENGTH
OR 3"
LESS THAN THE SLAB THICKNESS
#3@12" EW, H < 8" #4@12" EW, 8" ≤ H ≤ 12" #5@12" EW, H >
12"
ROUGHEN CJ
3/4" CHAMFER VERTICAL EDGES (TYP)
EQUIP BASEPLATE SEE NOTE 2
DOWEL ALL AROUND: #3@12" EW, H < 8" #4@12" EW, 8" ≤ H ≤ 12"
#5@12" EW, H > 12"
SCALE: NTS S-3831EQUIP PAD
REV 00 ON NEW CONC
NOTES: 1. JOINT FORMED WITH TOOL OR INSERT STRIP MAY BE SUBSTITUTED
FOR
SAWED TYPE WITH PRIOR ACCEPTANCE BY THE ENGINEER. 2. SAWED JOINT
MUST BE CONSTRUCTED WITHIN 12 HOURS OF CONCRETE
PLACEMENT. 3. THIS DETAIL DOES NOT APPLY TO SUSPENDED SLABS OR
LIQUID
CONTAINING BASINS UNLESS SPECIFICALLY NOTED.
SAWED JOINT (3/16"-3/8" WIDE) FILL W/ SEALANT WHERE NOTED ON PLANS
(TYP)
REINF NOTED TO BE DISCONTINUOUS PER PLANS
REINF NOTED TO BE CONTINUOUS OR PARTIALLY CONTINUOUS PER
PLANS
SCALE: 1-1/2" = 1'-0" S-3170CONTROL JOINT
REV 00
3' -9
1 /2
S-201
1976018.00-S-201.dwg
pw :\\
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
1/4"=1'-0"
30 6
1. SET CENTER SEGMENT OF TRENCH GRATING 1-1/2" BELOW FINISHED FLOOR
ELEVATION, SLOPE INFILL CONCRETE TO DRAIN. BOTTOM OF TRENCH TO BE
5" DEEP AT HIGH END, 8" DEEP AT FLOOR DRAIN. TRENCH GRATING TO BE
ALUMINUM WITH 3 4"x3
16" BEARING BARS AT 1-316" OC, CROSS BARS AT 4". ANGLE SUPPORTS TO
BE STAINLESS SEE S-3560 .
2. PLATFORM GRATING TO BE ALUMINUM WITH 1-3 4"x3 16"
BEARING BARS AT 1-316" OC, CROSS BARS AT 4" MAXIMUM. BARS TO HAVE
SERRATED, NON-SLIP TOP SURFACE. SEE STAIR DETAILS FOR GRATED TREAD
INFORMATION.
3. PROVIDE ISOLATION COATING BETWEEN ALUMINUM AND CEMENTITIOUS
MATERIALS. SEE SECTION 05500.
GENERAL NOTES:
SCREW PRESS ANCHOR PLATE BY MFR (TYP 12 EA PRESS)
BLOCKOUT AT ELECT PANEL SEE
CAST-IN-PLACE TRENCH DRAIN SEE NOTE 1
TRENCH DRAIN SEE NOTE 1
CONCRETE INFILL AT (E) TRENCH
CONCRETE INFILL AT (E) SUMP (TYP 2)
HVAC CONC EQUIP PAD SEE S-3831
ALUMINUM STAIRS
1 2" EXP JT SEE S-3161
SCREW PRESS (TYP 2)
PLATFORM COLUMN & BASEPLATE SEE
MFR (TYP 4 EA TANK)
SCREW PRESS CROSS BRACING BY MFR
FLOC TANK CROSS BRACING BY MFR
PLATFORM BRACING
PLATFORM BRACING
PLATFORM BRACING
PLATFORM BRACING
CONVEYOR CONCRETE APRON SLAB, TOP EL 203.00'+/-, FOR REINF SEE
SECTION E. PLACE CONTROL JOINTS AT 5' MAX SPACING. EXP JTS @ 20'
MAX SPACING.
PLATFORM BRACING
PLATFORM BRACING
PLATFORM BRACING
11 S-204
17 S-205
17 S-205
4 S-204
16 S-205
CL
CL
CL
CL
CL
CL
CL
CL
CL
CL
S-204
CHANNEL INSIDE CONNECTION SEE
(TYP 3 THIS LINE)
(E) SLAB
S-205
SCREW PRESS ROOM EXHAUST FAN EQUIPMENT SLAB (OFF PAGE) SEE
S-3342
D N
U P
2"
JDS
JDS
DEC
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
4 (TYP)
ALUMINUM GUARDRAIL
EL 209.00'
ALUMINUM GUARDRAIL SEE (TYP)
EL 216.60'
TYPE B CONC INFILL, REINF FACE W/ #5@12" EA WAY, EPOXY EMBED 4" AT
PERIMETER, SLOPE TOP SURFACE TO DRAIN (TYP)
TYPE B CONC INFILL, REINF FACE W/ #5@12" EA WAY, EPOXY EMBED REINF
4" AT PERIMETER
CAST-IN TRENCH DRAIN, T/ GRATE EL 202.88', FOR GRATE SUPPORT ANGLE
SEE S-3560
ALUMINUM SHIP'S LADDER
18 S-205
1. CONCRETE INFILL TOP SURFACE TO RECEIVE A TROWEL FINISH. SIDE
WALL OF TRENCH TO RECEIVE FILLED FINISH, TRENCH FLOOR TO RECEIVE
TROWEL FINISH.
2. PLATFORM GRATING TO ALUMINUM WITH 1-3 4"x3 16"
BEARING BARS AT 1-316" OC, CROSS BARS AT 4" MAXIMUM. BARS TO HAVE
SERRATED, NON-SLIP TOP SURFACE.
GENERAL NOTES:
#5@12" EA WAY
TYPE B CONC INFILL, REINF FACE W/ #5@12" EA WAY, EPOXY EMBED REINF
4" AT PERIMETER
TYPE B CONC INFILL, REINF FACE W/ #5@12" EA WAY, EPOXY EMBED REINF
4" AT PERIMETER
EXTERIOR PAVING SEE SECTION E
BLOCKOUT AT ELECT PANEL
*7'-01 2"
*4 '-8
1 4"
*1'-1"2'-33 4"2'-63
S-203
1976018.00-S-203.dwg
pw :\\
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
CS9x4.98 ALUM CHANNEL MITER AND FULL PEN WELD @ CORNERS
PLATFORM FRAMING AT EL 209.0' SHOWN FOR REFERENCE, GRATING NOT
SHOWN
COLUMN TO UPPER PLATFORM ELEVATION (TYP 5)
CS9x4.98 ALUM CHANNEL CROSS MEMBER (TYP 3)
FLOC TANKS NOT SHOWN FOR CLARITY
GRATING BELOW NOT SHOWN FOR CLARITY
BAND GRATING EDGE, 1" MIN SETBACK AT TANKS
SCALE: 12" = 1'-0"
EELEVATION SCALE: 12" = 1'-0"
EAST EDGE OF BLDG
PILASTER BEHIND (TYP 3)
(N) OPNG FOR CONVEYOR, CONFIRM OPNG DIMS W/ MFR PRIOR TO DEMO, FOR
FLASHING AROUND CONVEYOR SEE
(E) WINDOW OPNG, REMOVE WINDOW FRAME AND FILL WITH REINFORCED CMU
TO MATCH (E) AS SHOWN, FOR FLASHING AROUND CONVEYOR SEE
#5 REINF, W/ 6" EPOXY EMBED AT (E) CMU, LAP OPPOSING BARS 24"
MIN
(E) DOOR
C12x8.64 ALUM CHANNEL, MITER AT CORNER AND FULL PEN WELD
18 S-205
S-204
S-204
8 S-204
8 S-204
7 S-204
6 S-204
S-204
8 S-204
ALUM RT4x4x1/4
(TYP EA FACE)
PARTIAL PLAN AT EL 209.0' PARTIAL PLAN AT EL 216.60'
CL
CL
DN
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
7DETAIL SCALE: 3" = 1'-0"
10DETAIL SCALE: 3" = 1'-0"
14DETAIL SCALE: 3" = 1'-0"
ALUM L3x3x1 4 (TYP)
3/16 WELD 3 SIDES
3 8" ALUM PL
3 8"x8"x6" BENT
C12x8.64 ALUM CHANNEL BEYOND
3/16 WELD 3 SIDES
BRACES SET BACK-TO-BACK W/ 38" SPACER PLATE AND 3 8" SS MB
RT4x4x1 4" ALUM
INSIDE CHANNEL CONNETION
BACKSIDE CHANNEL CONNETION
12" GAP AT TOP OF WALKWAY GRATING
13 -
1/4
0.5"R
1/4
ALUMINUM STRINGER C12x8.64 UON
ALUM L3x3x1/4x0'-8" W/ (2)-5/8"Ø SS EXP ANCHORS, INSIDE FACE OF
STRINGER (TYP)
1"
4"
1/4 3 SIDES
NOTES: 1. HANDRAIL NOT SHOWN FOR CLARITY. 2. PROVIDE ISOLATION
COATING BETWEEN ALL ALUMINUM IN CONTACT
W/ CEMENTITIOUS MATERIALS.
CLOSURE PLATE
SEE PLAN
SE E
PL AN
1-3/4"x3/16" BB @ 15/16" CC SERRATED ALUM STAIR TREAD BOLTED TO
STRINGERS (TYP)
ALUMINUM STRINGER C12x8.64 UON
3' -6
GRATING SUPPORT AND STRINGER
19 -
1/2" Ø BOLT & NUT, TYP
SECTION X
X X
14 GA GALVANIZED STEEL CURB CAP PANEL WITH DRIP EDGE OVER 1/2" CDX
PLYWOOD. HEM EDGES AND SEAL JOINTS WEATHERTIGHT.
PRIOR TO SLIDING BOOT DOWN OVER PIPE, PLACE A CONTINUOUS BEAD OF
APPROVED SEALANT AROUND PIPE AT THE HEIGHT OF THE BOOT SO THAT WHEN
THE BOOT IS IN PLACE THE TOP OF THE BOOT ENGAGES THE SEALANT (SEE
NOTE 4 BELOW)
THRU VENT PIPE; SEE ALSO MECHANICAL
ROOF BOOT PIPE FLASHING CUT TO PIPE SIZE IN FIELD SO THAT FLASHING
FITS *SNUGLY AROUND PIPE; SET BASE IN CONTINUOUS BEAD OF APPROVED
SEALANT
#12 HEX HEAD LAP SCREW WITH NEOPRENE WASHER
*SNUGLY MEANS NO WATER CAN PENETRATE BETWEEN TOP OF BOOT &
PIPE
NOTES: 1. THE ROOF PIPE FLASHING MUST BE FASTENED TO THE PANEL ONLY
AND NOT INTO
THE ROOF SUBSTRATE TO ALLOW THE PANEL TO MOVE THERMALLY. 2.
ADEQUATE CLEARANCE MUST BE LEFT BETWEEN THE PIPE AND THE PANEL TO
ALLOW
FOR THERMAL MOVEMENT WITHOUT INTERFERENCE. 3. THIS DETAIL IS NOT
ALLOWED IN AREAS WITH SNOW AND ICE. 4. APPLY A SEALED, SMOOTH
COLLAR ON PIPE, IF NECESSARY, AT BOOT INTERFACE TO
ENSURE PROPER SEAL.
3" CANT STRIP
INSULATION SYSTEM
OR TO MATCH EQUIPMENT SUPPLIED
BACK DRAFT DAMPERS
NOTES: 1. TOP OF CURB SHALL BE LEVEL. TAPER WOOD CURB
BLOCKING
AS REQUIRED. 2. SIZE CURB FOR FAN AND ROOFING FELTS.
CARRY ROOFING FELT OVER CURB
2'-0" CLR OPENING
1" MIN TYP
2' -0
" C LR
O PE
N IN
MASONRY REGLET
SECTION Y
EXISTING MASONRY WALL
EXISTING MASONRY WALL
CONVEYOR
18 GAUGE SST DIVERTER MOUNT TO CONVEYOR COVER SECTION Z
18 GAUGE SST STEEL COVER
CLOSED CELL NEOPRENE EDGE TRIM
ADHESIVE EACH SIDE
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
ALUM RT 4x4x1 4,
3/4" ALUM PLATE
7 S-204
6 S-204
SECTION Y-Y
7 S-204
ELECT PANEL CS12x8.27 ALUM CHANNEL SET TOP FLANGE ABOVE WALKWAY FOR
MOUNTING ELECT PANEL
CS9x4.98 ALUM CHANNEL BYND
APPROX 16"x36" BLOCKOUT IN GRATING FOR CONDUIT ROUTING UNDER ELECT
PANEL, COORD W/ FAVORABLY REV'D MFR
(TYP 4)
ALUM GUARDRAIL
GALVANIZED STEEL CHECKERPLATE OVER TRENCH SEE SECTION A
(N) DOOR OPENING, ROUGH OPNG 3'-4"W x 7'-2"T. BURN BACK EXPOSED
BARS 1-INCH BELOW CONCRETE SURFACE. FILL WITH REPAIR MORTAR TO
MATCH FINISH AND ELEVATION OF EXISTING ADJACENT SURFACE. FOR DOOR
DETAILS SEE
2'-6"
*19'-0"
WEST BAY EAST BAY
8" CONVEYOR CONCRETE APRON SLAB, REINF W/ #5@12" EA WAY CTR SLAB,
SET T/ SLAB TO SLOPE W/ EXISTING FLOW LINES, FLUSH WITH AC PAVING
AT EDGES, SEE NOTE 2. PLACE CONVEYOR SUPPORTS ON 1" TO 2" TALL
GROUT PADS.
*14'-0"
9'-8" VIF
5' -8
ELECTR
CONCRETE SLAB FOR ODOR CONTROL UNIT, FOR REINF SEE S-3342
*2 4'
*7 '-6
CONCRETE SLAB FOR MAKEUP AIR UNIT, FOR REINF SEE S-3342
CTRL JT (TYP)
EXP JT (TYP)
S-210
1976018.00-S-210.dwg
pw :\\
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
FLOOR PLAN
1. CONCRETE SLAB TOP SURFACES TO RECEIVE FLOAT FINISH. SEE SECTION
03350.
2. CONCRETE CONVEYOR APRON SLAB TO BE INSTALLED WITH CONTROL JOINTS
SPACED AT MAXIMUM 5' ON CENTER IN EACH DIRECTION. SEE S-3170 .
PROVIDE CONTINUOUS REINFORCING THROUGH JOINTS. PLACE EXPANSION
JOINTS SPACED AT MAXIMUM 20' ON CENTER IN EAST/WEST DIRECTION. SEE
S-3161 .
GENERAL NOTES:
3/16"=1'-0"
EDGE OF ROOFLINE ABOVE
(E) COLUMN (TYP 31)
KALWALL CLOSURE PANELS AT (E) CLERESTORY (TYP 3 SIDES OF EAST BAY)
SEE SECTION D FOR TYP ATTACHMENT
OVERHEAD COILING DOOR
GALV HSS18x18x3 8
LINTEL BEAM AT T/ DOOR OPNG, SEE SECTION C FOR ANCHORAGE AND
KALWALL ATTACHMENT DETAILS
WOOD-FRAMED SHEAR WALL, PRESSURE-TREATED PLYWOOD SHEATHED WITH
GYPSUM EXTERIOR, EXTEND FROM TOP OF CONC WALL TO UNDERSIDE OF
GLULAM BEAM, ALONG CENTER WALL
(E) CONC WALL (CENTER WALL)
C S-212
C S-212
WALL CLOSURE SEE
(TYP 6)
OMIT STUDS AT COLUMNS, SPAN PLYWOOD FROM 6x6 TO 2x6 (OR 6x6) (TYP 3
LOCATIONS)
SPAN PLYWOOD FROM 6x6 TO 6x6, TYP EA SIDE (TYP 2 LOCATIONS)
12'-0" VIF IN TO IN
LOUVER OPNG PER MECHANICAL, DISCONTINUE KALWALL AND HSS ATTACHMENT
AT THESE LOCATIONS (TYP 8)
WEATHERTIGHT SST CLOSURE PANEL AT DUCT PENETRATION BY CONTRACTOR,
DISCONTINUE HSS AT THIS LOCATION
CONVEYOR CLOSURE PANEL SEE 1
S-213
S-211
1976018.00-S-211.dwg
pw :\\
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
TOP PLAN
1. STEEL PLATES AND SHAPES USED IN THE CAKE STORAGE BUILDING SHALL
BE HOT-DIP GALVANIZED IN ACCORDANCE WITH ASTM A123. STEEL BOLTS AND
ASSOCIATED HARDWARE SHALL BE 316 STAINLESS STEEL MEETING ASTM A193
(UON). ALL LUMBER AND PLYWOOD USED AT CENTER WALL SHALL BE PRESSURE
TREATED.
2. FRAMING SIZED FOR (1) NEW CONVEYOR AND SUPPORTS WEIGHING 180 PLF
AND (1) FUTURE CONVEYOR AND SUPPORTS WEIGHING 180 PLF.
GENERAL NOTES:
3/16"=1'-0"
17 '-7
3 S-213
4 S-213
S-213
CAKE STORAGE BUILDING SECTIONS
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
CHAMFER EA END
10d @ 6" NAILS, EA SIDE, PLYWOOD SHEATHING TO 2x6 HEADER
3 8"Øx6" LAG SCREW @
(E) CONCRETE CENTER WALL
EL 236.38' (PER RECORD DWGS, VIF)
EL 220.50' (PER RECORD DWGS, VIF)
DBL 2x6 PLATE W/ 5 8"Ø GALV RODS W/ 4" EPOXY EMBED @ 12" OC
10d @ 6" NAILS, EA SIDE, PLYWOOD SHEATHING TO 2x6 PLATE
MIN 12" PLYWOOD SHEATHING EA SIDE
2x6 STUDS @ MIN 2'-0" OC
S-211
CSECTION
GALV HSS18x18x3 8
3 4" PLATE
S-211
DSECTION
1 4"x10-1/2" GALV PLATE, CONTINUOUS
AROUND, FASTEN TO (E) GLULAM W/ 3
8Øx5" LAG SCREW @ 12" OC, PREDRILL 3
16"Ø HOLE TO PREVENT SPLITTING, NOTCH AT (E) TOP PLATES
CONTINUOUS CAP FLASHING, PRE-FINISHED
EMBED @ 24" OC, 2"Ø ACCESS HOLE IN TUBE STEEL TOP
SILL FLASHING, PRE-FINISHED
TRANSLUCENT PANEL BY KALWALL; OR EQUAL. FIELD VERIFY ROUGH OPNGS
PRIOR TO FABRICATION
SILICONE SEALANT EA SIDE
1 2" MOISTURE RESISTANT G.W.B. EA SIDE, PAINT FINISH PER
09900
3 4" SILICONE SEALANT FILLET EA SIDE
CONT PT 2x PLATE, FASTEN TO GLULAM W/ 3"X#10 SCREWS @ 6" OC, LAP
SCREWS 2"
HDG HSS4x4x 3 16
(E) 5-1/8x24 GLULAM BEAM
TRANSLUCENT PANEL BY KALWALL; OR EQUAL. FIELD VERIFY ROUGH OPNGS
PRIOR TO FABRICATION
SILL FLASHING, PRE-FINISHED, TURN UP AT STUBOUT WALL
1 4"x10-1/2" GALV PLATE, CONTINUOUS AROUND, FASTEN TO (E) GLULAM W/
3 8Øx5" LAG SCREW @ 12" OC, PREDRILL 3
16"Ø HOLE TO PREVENT SPLITTING, NOTCH AT (E) TOP PLATES
2-6
EL *220.50' (PER RECORD DWGS)
CONT PT 2x PLATE, FASTEN TO GLULAM W/ 3" SCREWS @ 6" OC, LAP SCREWS
2"
CAP FLASHING, PRE-FINISHED, SLOPE AWAY FROM BLDG
S-211
ESECTION
MITER AND PJP EMBED FRAMES AT CORNERS
1 2"x1
3/4"Ø HOLES @ 12" OC, EA SIDE OF PLATE
NOTE: FABRICATE COVER SEGMENTS IN MAX 2' WIDE SEGMENTS. HOT-DIP
GALVANIZE ASSEMBLY AFTER FABRICATION.
DEMO 4"x4" SECTION OF (E) CONC AROUND 3 SIDES OF TRENCH, SET FRAME
FLUSH W/ (E) SURFACE IN BED OF EPOXY NSG
3/16"=1'-0"
0 1
1"=1'-0"
0 1
1"=1'-0"
0 1
PT 2x6, FASTEN W/ (2) SIMPSON A35 EA SIDE, EA END. APPLY AT 10
LOCATIONS APPROXIMATELY EQUALLY SPACED
(2) PT 2x4, (1) EA SIDE OF 2x6, FASTEN TO SHEATHING W/ 2" LONG WOOD
SCREWS AT 3" OC
1 1/2"=1'-0"
1/4
1 2" GAP AS
1 2" PLATE
HOLD-DOWN AT WALL ENDS
PT 2x6, EA SIDE OF GLULAM, FASTEN W/ (2) SIMPSON A35 EA SIDE, EA
END. APPLY AT 29 LOCATIONS APPROXIMATELY EQUALLY SPACED.
(2) PT 2x4, (1) EA SIDE OF 2x6, FASTEN TO SHEATHING W/ 2" LONG WOOD
SCREWS AT 3" OC
SIMPSON A35, EA SIDE, EA END
1
1
1/4" STIFFENER PLATE OR 3/8" SHEAR PLATE, CLIP AT K-AREA
1 4"
1 14"3/8" THICK SHEAR PLATE W/ 2-7/8" Ø A325N BOLTS
STEEL BEAM PER FRAMING PLAN TOP FLANGE SLUSH
1 1/
2" M
IN 1
1/ 2"
M IN
3"
12"x18"x3/4" PLATE W/ (4) 3/4"Ø SS ROD, 8 INCH EPOXY
EMBEDMENT
1'-6"
1/4"
1/4"
1'-0"
4"
2x10 CEDAR TRIM, PAINT TO MATCH ADJACENT TRIM; FIELD VERIFY
KALWALL CLOSURE PANEL
2x6 CEDAR TRIM, PAINT TO MATCH ADJACENT TRIM; FIELD VERIFY
CONTINUOUS SEALANT
2 2
2 6
2 6
1/2" MOISTURE RESISTANT G.W.B.
2x8 CEDAR TRIM, PAINT TO MATCH ADJACENT TRIM; FIELD VERIFY
KALWALL CLOSURE PANEL
SEALANT TYPE A
1/ 4" 1"
1 3/4"
NO. 6 x 5/8" PAN-HEAD SHEET METAL SCREWS, PHILLIPS (FACTORY
PROVIDED) AT BOTTOM DOOR SHOE WITH RAIN SHIELD
1 5/
CONCRETE FLOOR SLAB
TYPICAL AT JAMBS: 10 GA COLD FORMED ANGLE 7" x 2", INSIDE RADIUS
MIN. 1/4", MAX. 3/8", MOUNT WITH POLYURETHANE CONSTRUCTION ADHESIVE
AND (3) 1/4"Ø x 3" EXPANSION ANCHORS (TOP, MIDDLE AND BOTTOM)
INSULATED ROLL-UP DOOR
CONC. PAD AT EXTERIOR DOORS
TYPICAL AT JAMBS: 10 GA COLD FORMED GALV ANGLE 7" x 2", INSIDE
RADIUS MIN. 1/4", MAX. 3/8", MOUNT TO MASONRY WITH POLYURETHANE
CONSTRUCTION ADHESIVE AND (3) 1/4"Ø x 3" EXPANSION ANCHORS (TOP,
MIDDLE AND BOTTOM)
INSULATED ROLL-UP DOOR
FASTENERS PER MANUFACTURER'S REQUIREMENTS
HOLLOW METAL FRAME
CLOSE ENDS OF RAIN HOOD
HOLLOW METAL DOOR
SS EXPANSION ANCHORS, MIN. 5" EMBED. INTO CONCRETE BEYOND. SEE
01190 FOR ANCHORAGE REQ'S.
BRACKET BOLTED TO GUIDE RAIL
CONCRETE WALL BEYOND
TYPICAL AT JAMBS: 10 GA COLD FORMED ANGLE 7" x 2", INSIDE RADIUS
MIN. 1/4", MAX. 3/8", MOUNT TO MASONRY WITH POLYURETHANE
CONSTRUCTION ADHESIVE AND (3) 1/4"Ø x 3" EXPANSION ANCHORS (TOP,
MIDDLE AND BOTTOM)
"Z-TYPE" LINTEL BRUSH SEAL, FASTEN PER MANUFACTURER
ROLL-UP DOOR HOOD
INSULATED ROLL-UP DOOR
18 GAUGE SST STEEL COVER
SLOTTED HOLE 2" LONG, TYP, W/ 14" SS BOLT THROUGH BACKING
FRAME
R O
U G
H O
PE N
IN G
D IM
EN SI
O N
JDS
JDS
DEC
S-213
1976018.00-S-213.dwg
pw :\\
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
S-210
SCALE: 1"=1'-0"
SCALE: 3"=1'-0"
PIPING DESIGNATION
NOMINAL PIPE DIAMETER
THERMAL METER T T
BUTTERFLY (FLANGED)
PINCH VALVE
NOTE: VALVE SYMBOLS SHOWN WITH SOLID FILL DENOTES VALVE IS NORMALLY
IN CLOSED POSITION.
ACTUATOR SYMBOL
PIPE SYMBOLS
PIPE SUPPORT DESIGNATION
TXXS PIPE SUPPORT DESIGNATION (TYPE XX SUPPORT) SEE PIPE SUPPORT
DETAILS FOR SPECIFIC REQUIREMENTS
1. INFORMATION PROVIDED ON THIS SHEET ARE MINIMUM REQUIREMENTS.
REFER TO THE SPECIFICATION SECTION 15050 FOR ADDITIONAL
REQUIREMENTS.
2. ALL PIPE JOINTS SHALL BE RESTRAINED UNLESS OTHERWISE
NOTED.
3. SIZE OF FITTINGS SHOWN ON DRAWINGS SHALL CORRESPOND TO ADJACENT
STRAIGHT RUN OF PIPE, UNLESS OTHERWISE INDICATED. TYPE OF JOINT AND
FITTING MATERIAL SHALL BE THE SAME AS SHOWN FOR ADJACENT STRAIGHT
RUN OF PIPE.
4. APPROPRIATE PIPE PENETRATION DETAILS SHALL BE USED.
5. ALL FLEXIBLE CONNECTORS OR FLANGED COUPLING ADAPTERS SHALL BE
PROVIDED WITH THRUST TIES, BLOCKS, OR ANCHORS, UNLESS OTHERWISE
NOTED. THRUST PROTECTION SHALL BE ADEQUATE FOR TEST PRESSURES
SPECIFIED.
6. NUMBER AND LOCATION OF UNIONS SHOWN ON DRAWINGS ARE ONLY
APPROXIMATE. PROVIDE ALL UNIONS NECESSARY TO FACILITATE CONVENIENT
REMOVAL OF VALVES AND MECHANICAL EQUIPMENT.
7. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING AND PERFORMING
THE CONNECTION OF THE PIPING AND ASSOCIATED APPURTENANCES INSTALLED
UNDER THIS CONTRACT TO THE EXISTING PIPING AND FACILITIES, AND TO
THE WORK OF OTHER CONTRACTORS.
8. PRIOR TO SUBMITTING PIPING DRAWINGS FOR ANY NEW PIPE THAT IS TO
CONNECT TO AN EXISTING PIPE OR STRUCTURE, THE CONTRACTOR SHALL
EXPOSE THE EXISTING PIPE OR STRUCTURE TO VERIFY ITS EXACT LOCATION,
SIZE, MATERIALS, AND INVERT ELEVATIONS.
9. ALL PIPING IS TO BE PAINTED AND LABELED UNLESS NOTED OTHERWISE.
LABELING SHALL INCLUDE FLOW DIRECTION ARROW AND PIPE USE.
10. ALL PIPING UNDER STRUCTURES TO BE CONCRETE ENCASED UNLESS NOTED
OTHERWISE.
GENERAL MECHANICAL PIPING NOTES
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
FASTEN SIGN TO HOSE RACK WITH RIVETS (TYP 4 PLACES)
DRILL FOR 3/8" DIA FASTENING (TYP 4 PLACES) NOTE 2
7"/10" RADIUS NOTE 5
M-002 6HOSE RACK DETAIL
1. ALL HOSE RACKS AND MOUNTINGS SHALL BE WELDED CONSTRUCTION.
MATERIAL SHALL BE 3/16" STEEL PL HOT DIP GALVANIZED AFTER FAB. ALL
BOLTS AND NUTS SHALL BE GALVANIZED.
2. CONTRACTOR SHALL COORDINATE BOLTS AND BOLT HOLE LOCATION WITH
HANDRAIL DIMENSIONS.
3. ROUND ALL CORNERS (3/4" R). 4. USE DIMENSIONS PRECEDING SLASH
WHERE LIQUID SERVICE TO THE UTILITY
STATION IS 1" DIA OR LESS, AND DIMENSIONS FOLLOWING SLASH FOR 1
1/2" DIA OR LARGER.
5. PROVIDE MESSAGE "50 LBS MAX" STAMPED ON FACE.
8 3/
ANCHOR ROD 3/8 X 9 X 9
BASE PLATE H (MAX.)
5/8" THROUGH BOLT WITH NUT & LOCK WASHER
2 1/2" STEEL PIPE. ATTACH DIRECTLY TO BASE PL WHEN HEIGHT LESS THAN
9" PLUS PIPE OD/2. MALLEABLE IRON REDUCER
3" STEEL PIPE
3/8" PL. 4" WIDE PIPE STRAP
3" STD. STL. PIPE, 3" LONG
PIPE STRAP 1/4" X 2"
GROUT OR DRYPACK 3/4" MIN., 2" MAX.
FLOOR, WALL OR CEILING
SST ANCHOR RODS WITH LOCK WASHERS, DOUBLE NUTTED AT SLAB. 6" EMBED
WITH HILTI HIT-HY200.
NOTES:
1 1/2" (TYP)
1. AS AN ALTERNATE, IF ADJUSTMENT IS NOT NECESSARY, DELETE PIPE AND
REDUCER AND WELD 3" STEEL PIPE DIRECTLY TO BOTTOM PIPE STRAP.
2. DO NOT CUT OR WELD AFTER GALVANIZING. 3. PIPE SUPPORT MAY BE
ORIENTATED IN ANY DIRECTION. 4. WHERE SLIDING SUPPORT REQUIRED,
OMIT GAP AND SIZE STRAP SO THAT IT FITS
LOOSE. 5. SEE SECTION 15060 FOR MATERIALS.
1/ 4"
M IN
PIPE ≤ 8" DIA
2" MIN, TYP CAST IRON FRAME AND COVER PLATE SIZE AS REQD
PRESSURE SIDE PIPE FLANGE DRILLED AND TAPPED FOR BOLTS
GRAVEL
NO SCALE
TYPE X1 PIPE PENETRATION
PROVIDE SEALANT AND BACKING ROD OR TAPE ON OUTSIDE WALLS.
1 1/2" MAX, 1/2" MIN
NOTES: LOCATE EXISTING REBAR PRIOR TO CUTTING EXISTING CONCRETE. DO
NOT CUT OR DAMAGE EXISTING REBAR.
SANITARY TEE
FINISHED FLOOR
CAST IRON BAR GRATE WITH LEGS
V
4"
NOTE:
HOSE RACK SEE DETAIL 6/M-002
PIPES, VALVES, AND END FITTINGS, SEE TYPE A UTILITY STATION THIS
DRAWING
WARNING SIGN, SEE UTILITY STATION NOTE 1
FOR PIPE/RAIL MOUNT SEE DETAIL 5/M-002
TOP RAIL
PROVIDE ISOLATION VALVE PER TYPE D UTILITY STATION FOR ALL OUTDOOR
UTILITY STATIONS.
TYPE B UTILITY STATION RAIL MOUNTED
DO NOT DRINK
1 1/2"
2 1/2"
WARNING SIGN SHALL HAVE WHITE LETTERING ON RED BACKGROUND.
MATERIALS IN ACCORDANCE WITH SPECIFICATION SECTION 10400.
3/4"
1"
1/8" STEEL PLATE
WATER PIPE NOTE: DIELECTRIC ISOLATION SHALL BE PROVIDED IF COPPER
PIPING IS USED. SEE UTILITY STATION NOTE 4.
U-BOLT TYPICAL
UTILITY STATION NOTES:
1. PROVIDE UTILITY STATIONS WITH WARNING SIGN THAT READS "NOTICE
NON-POTABLE WATER DO NOT DRINK" DISPLAYED IN A PROMINENT PLACE AT
THE UTILITY STATION. SEE DETAIL 4/M-002.
2. INSTALL ISOLATING VALVE WITH EXTENSION STEM AND VALVE BOX WITH
COVER MARKED "WATER."
3. TYPE B UTILITY STATION RAIL MOUNTED RACK IS SECURED TO HANDRAIL
AS SHOWN ON DETAIL 6/M-002.
4. PROVIDE DIELECTRIC ISOLATION BETWEEN PIPE AND HANDRAIL WHEN
PIPING IS COPPER. WRAP 1/16 THICK NEOPRENE A FULL 360° AROUND PIPE.
BOND TO PIPE WITH A COMPATIBLE WATERPROOF ADHESIVE. EXTEND NEOPRENE
1/2 INCH BEYOND STEEL CLAMP PLATE ON EACH SIDE.
RISER EXTENDED INTO FRAME AND COVER, SEE DETAIL 4/M-002
1/8 BEND
1/8 BEND
NO SCALE VAR 3CLEANOUT DETAIL (LINE END)
NO SCALE VAR 7EQUIPMENT DRAIN DETAIL
CLR 3"
EQUIPMENT PAD OR FINISHED FLOOR
DRAIN LINE
DRAIN LINE
LEAD SEAL PLUG CALKED FERRULE CLEANOUT
PACK ANNULAR SPACE WITH SEALANT
CLASS E CONCRETE
3" CLEAR
CW
GS
LW
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
SPM
SPM
SPM
M-005
1976018.00-M-005.dwg
pw :\\
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS ©. JANUARY 2021
1976018.00
FROM PLC/SCADA
9000 CFM
ODOR CONTROL
UNIT WW1-015ORT1211
1125 CFM OA 1125 CFM OA
POLYMER PUMP ROOM
1044 CFM
0.5 PSI 3/4" NG
TO SCREW PRESS ROOM
WW1-015HTR0003
WW1-015HTR0001
WW1-015HTR0002
WW1-015AHU0003A
M-006
1976018.00-M-006.dwg
pw :\\
ADJUST SCALES ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT
OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF