By Engnr.Asad Iqbal Jamal Power Cube: S. No ALM Card ALM Name ALM Color Code ALM CODE 1 ALM1 UPEU EXT1 TO CPMU AC OFF ALM White Orang/Orange 65101 2 ALM2 DC LOW ALM White Green/Green 65108 3 ALM3 RECT FAULT AL White Blue/Blue 65125 4 ALM4 SMOKE ALM White Brown/Brown 65103 5 ALM5 UPEU EXT0 TO CPMU DOOR ALM White Orange/Orange 65104 6 ALM6 HIGH TEMP ALM White Green/Green 65105 7 DO_2 UPEU EXT0 TO HPMU DO2 GEN FAULT ALM White Blue/Blue 65109 8 DI_5 BATT ROOM TO HPMU DO5 BATT DOOR ALM White Orange/Orange 65104 9 EXT0(UE IU) UEIU EXT0 TO Civil ALM BOX(8,9) TOWER LIGHT ALM White Orange/Orange 65107 DO2: (White Blue/Blue) is From BBU (UPEU - EXT- ALM-0) to HPMU (D0-2) DO5: Battery Door Alarm (White Orange/White) is connected here. UEIU EXT1 White blue/Blue is connected in battery room for Battery AC. UEIU EXT0 White Orange/Orange is connected for Tower light By Asad Iqbal Jamal

Alm

Embed Size (px)

DESCRIPTION

alm

Citation preview

By Engnr.Asad Iqbal Jamal

Power Cube:S. NoALM CardALM NameALM Color CodeALM CODE

1ALM1UPEU EXT1TOCPMUAC OFF ALMWhite Orang/Orange65101

2ALM2DC LOW ALMWhite Green/Green65108

3ALM3RECT FAULT ALWhite Blue/Blue65125

4ALM4SMOKE ALMWhite Brown/Brown65103

5ALM5UPEU EXT0 TOCPMUDOOR ALMWhite Orange/Orange65104

6ALM6HIGH TEMP ALMWhite Green/Green65105

7DO_2UPEU EXT0 TOHPMU DO2GEN FAULT ALMWhite Blue/Blue65109

8DI_5BATT ROOMTOHPMU DO5BATT DOOR ALMWhite Orange/Orange65104

9EXT0(UEIU)UEIU EXT0TOCivil ALM BOX(8,9)TOWER LIGHT ALMWhite Orange/Orange65107

DO2: (White Blue/Blue) is From BBU (UPEU - EXT- ALM-0) to HPMU (D0-2)DO5: Battery Door Alarm (White Orange/White) is connected here.UEIU EXT1 White blue/Blue is connected in battery room for Battery AC.UEIU EXT0 White Orange/Orange is connected for Tower light

Mini Shelter:S. NoALM LocationCardALM NameALM Color CodeALM Code

1ALM1UPEUEXT1MAJ PWR FAILUREWhite Orang/Orange65110

2ALM2DC LOW ALMWhite Green/Green65108

3ALM3RECT FAULT ALMWhite Blue/Blue65125

4ALM4EMPTY CONNECTEDWhite Brown/Brown

5ALM5UPEU EXT0SMOKE ALMWhite Orang/Orange65103

6ALM6HIGH TEMP ALMWhite Green/Green65105

7ALM7DOOR ALMWhite Blue/Blue65104

8ALM8AC OFFWhite Brown/Brown65101

9EXT0(UEIU)UEIUTOWER LIGHTWhite Orang/Orange65107

Power Cube:Power Cube Alarm Configuration:There are two parts two alarm configuration (1) HPMU (2) CMPU.HPMU Port Configuration: Here we can configure only two alarms 1.Genset Fault, 2. Battery Door. Battery Door is already configured no need to configure while Genset Fault can be configured on HPMU DO2 as,Step 1 >Go to>SettingStep 2 >Go to>Put Password as (0)Step 3 >Go to>Alarm SettingStep 4 >Go to>Dry NodeStep 5 >Go to>Adio Backup DO2 (Make DO2 SDG Fail) So Now DO2 is configured for Genset Fault ALM.CPMU Port Configuration:AC OFF, DC LOW, HIGH TEMP, RECTIFIRE FAULT, SMOKE can be configured on CPMU as,Step 1 >Go to>SettingStep 2 >Go to>Alarm SettingStep 3 >Go to>Relay RelateStep 4 >Go to>Alarm (Configured each Alarm on desired port.

Power Cube Alarm Generation or Checking.1. AC OFF: Turn off the AC breaker AC Alarm will be appeared. If check the cable connection in the battery door upper most corner right side. For clearing this alarm turn on the AC braker.2. DC LOW: This is the most difficult alarm to generate. It can be generated in many ways but on simple way is given as,

Step 1 >Go to HPMU> SettingStep 2 >Go to>Put Password as (0)Step 3 >Go to>Critical PointStep 4 >Go to>Battery Under Volta:( Make it Maximum or 51.5V)Step 5 >Go to CPMU>SettingStep 6 >Go to>Battery SettingStep 7 >Go to>ChargeStep 8 >Go to>Boost (Make It maximum or 57.5)Step 9 >Go to>Click on Back Button and Press DC SettingStep 10 >Go to>Under Volt (Make it Maximum or 51.5)You will found DC low Alarm. It can remove by putting the original values back in the HPMU and CPMU.Reminder: This Alarm can be Generated Only and Only when voltage is greater than 53.3V and keep the Genset off for generation.3. RECTIFIRE FAULT: Take a cable tie and stop the fan in any rectifier module for 2minutes, a beef sound will produce and alarm will appear. For clearing remove the cable tie after a minute beef will stop and alarm will be clear.4. SMOKE ALARM: Produce the Smoke near to the smoke sensor. Smoke alarm will appear. For clearing this alarm remove the green connector back to smoke sensor and then insert back.5. DOOR ALARM: Open the Door alarm will appear and closed the door alarm will disappear.6. HIGH TEMP:Step 1>Go to> SettingStep 2>Go to>Ambient Temp Setting (Make it 25 or less alarm will appear. To clear it back make the value again the original.

7. Genset Fault: Stop the Generator and put the AC main braker turn off. It will appear and do its vice versa to clear this alarm.8. Genset Running: Make only this alarm polarity high in the power cube, then start the Genset alarm will appear and stop alarm will disappear.9. Tower Light Alarm: Turn off the tower light power alarm will appear, if not then climb up the tower and hide the light sensor from light, wait for few minutes while keeping the Tower Light power off. Alarm will appear and do vice versa to clear the alarm.

By Asad Iqbal Jamal